6
Philips Lighting TRIOS Luxsense LRL 1220/00 sensor, LRH 1221/00 TLD clip, LRH 1222/00 TL5 clip Product Details Luxsense is a light sensing device, meant to be integrated into the “down-lighting” luminaire, thus adding a regulating function in combination with a regulating ballast. Luxsense can be clicked on the lamp, using a special clip. It can also be clicked to the end lamella of the optic, using a special bracket, to be provided by the luminaire manufacturer. Luxsense can control up to 20 regulating electronic ballasts of the Philips HFR range. Luxsense can be manually adjusted by a rotating diafragm, in order to adjust the setpoint. The controller is connected to the 1-10 Vdc control input of the Philips HFR ballast Applications Luxsense is designed to save energy by compensating for excess lighting levels caused by overdesign of the lighting system (e.g. 600 lux installed, 500 lux required) and/or ingressing daylight. Energy saving is realized by reducing the output of the artificial light. The sensor is optimized for use in applications with 600 lux installed and 500 lux required with an assumed reflexion factor of the room of 30%. Actual circumstances may differ. To compensate for this, the sensitivity of the sensor can be adjusted manually over a range from 1/3 to 3. Therefore the minimum required reflection factor of the room must be 10% which is met by most practical conditions. Proper control operation is based on the condition that Luxsense controls at least 80% of the artificial light it ‘sees’. This can be critical in applications including a high amount of indirect light from other luminaires. ! Sensor TLD assembly TL5 assembly ! Application with sensor clicked on the lamp Application with sensor attached to end lamella

lrl1220d

  • Upload
    deshif

  • View
    37

  • Download
    1

Embed Size (px)

Citation preview

Page 1: lrl1220d

Philips Lighting

TRIOS LuxsenseLRL 1220/00 sensor, LRH 1221/00 TLD clip, LRH 1222/00 TL5 clip

Product Details• Luxsense is a light sensing

device, meant to be integratedinto the “down-lighting”luminaire, thus adding aregulating function incombination with a regulatingballast.

• Luxsense can be clicked on thelamp, using a special clip. It canalso be clicked to the endlamella of the optic, using aspecial bracket, to be providedby the luminaire manufacturer.

• Luxsense can control up to 20regulating electronic ballasts ofthe Philips HFR range.

• Luxsense can be manuallyadjusted by a rotating diafragm,in order to adjust the setpoint.

• The controller is connected tothe 1-10 Vdc control input ofthe Philips HFR ballast

Applications• Luxsense is designed to save

energy by compensating forexcess lighting levels caused by overdesign of the lightingsystem (e.g. 600 lux installed,500 lux required) and/oringressing daylight. Energysaving is realized by reducingthe output of the artificial light.

• The sensor is optimized for usein applications with 600 luxinstalled and 500 lux requiredwith an assumed reflexionfactor of the room of 30%.

• Actual circumstances may differ.To compensate for this, thesensitivity of the sensor can beadjusted manually over a rangefrom 1/3 to 3. Therefore theminimum required reflectionfactor of the room must be10% which is met by mostpractical conditions.

• Proper control operation isbased on the condition thatLuxsense controls at least 80%of the artificial light it ‘sees’. This can be critical inapplications including a highamount of indirect light fromother luminaires.

!

Sensor

TLD assembly TL5 assembly

!

Application with sensorclicked on the lamp

Application with sensorattached to end lamella

image photo
81221361.jpg
sec photo
81221362.jpg
image photo
81221381.jpg
sec photo
81221382.jpg
image photo
81221371.jpg
sec photo
81221372.jpg
figure
cemark.wmf
figure
TDT8004.wmf
figure
TDT8003.wmf
Page 2: lrl1220d

Environmental conditionsOperation conditions

Ambient temperature 5°C to 55°CRel. humidity 15% to 90%

no condensationMax. temperatureof clip to lampcontact surface 70°C

Storage conditionsAmbient temperature -25°C to 70°CRel. humidity 5% to 95% at 25°C

Safety When connected to the control input of a Philips HFR ballast, the sensor has double isolation to mains connected parts.

Connection 2x0,5mm2, flying leads, length 700mm.Colour coding: white/grey + ,white -.

When connected reversed to the ballast dim input, the ballast input is short circuited, resulting in minimum light output.

Housing material ASAcolour light grey (similar to RAL 7035)

Weight/dimensions Approx. 20 grams, 25x21x19mm.EMC According to IEC 1547/EN 50082-1Control signal input - operating voltage: +1,5 - +10Vdc

- operating current sink 100µA - 3mA (sufficient for 20 Philips HFR ballasts)

- control voltage variation: < 0,5V over current and temp.range

- default setting: 5Vdc at 37,5 lux/140µA- step response: within 2 sec. on 5V after power-up in case of insufficient ambient light

- max. input voltage (maximum rating): 15 Vdc

- max. current sink(maximum rating): 50 mA

Optical characteristics - It is assumed that the reflection in a room is such that a light level of 500 lux on a table (0,8 mtr in height) will result in 25 lux seen by the controller at ceiling height (2.5 mtr) under a viewing angle of 45°

- The opening angle can be adapted by the diafragm control, realizing an attenuation factor between 1/3 and 3.

TRIOS LuxsenseLRL 1220/00 sensor, LRH 1221/00 TLD clip, LRH 1222/00 TL5 clip

L

max. 20x Philips HFR

N

LN

White

White/grey

Ballast

Ballast

> 70 mm

Ballast

Ballast

-+

NL

Wiring diagram

Technical details

figure
TDT8016.wmf
Page 3: lrl1220d

TRIOS LuxsenseLRL 1220/00 sensor, LRH 1221/00 TLD clip, LRH 1222/00 TL5 clip

1919

1825

∅ 24.5

19

19

42

19

35

∅ 21

19

Dimensions

The sensor offers the following saving potential*

The average saving is 35% with ± 10%(window/corridor)± 5% (Summer/Winter)± 5% (South/North)

* Assumptions: 600 lux installed, 500 lux required,middle European office building, luminaire positionon 1m resp. 3,5m from the window, compared to anequivalent installation with electronic non-dim ballasts

summer

windowside

corridorside

windowside

corridorside

55%

35%

45%

25%

45%

south north

25%

35%

15%

winter

The setpoint of the sensor can be changed manually by using the rotary control ring on the front, which influences the diafragm. The housing is equipped with an indication of the default setting.

Note: this manual adjustment facility should preferably only be used in the commissioning phase, not by the users of the room.

more light on table

less light on table

+ -

LRL 1220 LRH 1221 LRH 1222

Saving Potential

Manual Adjustment

figure
TDT8007.wmf
figure
TDT8019.wmf
figure
TDT8002.wmf
figure
TDT8012.wmf
Page 4: lrl1220d

TRIOS LuxsenseLRL 1220/00 sensor, LRH 1221/00 TLD clip, LRH 1222/00 TL5 clip

A separate document is available that describes the commissioningprocess in detail. In short the steps are:• Find a room in the building that can be considered to be

representative for the whole building.• Install the luminaires with daylight control in this room and

convince yourself that the installed light level and the required light level are reasonably close to each other (within 30% range,

say 600 lux and 500 lux respectively). Light levels should be measured on the table, preferably without daylight contribution (e.g. at night).

• Manually adjust the rotary control such that the required light level is realized. Memorize the position of the control ring.

• Instruct installer to copy the position of the rotary control ring of every luminaire to be installed in comparible circumstances.

The lightsensor, LRL1220, represents a basic, straight forwardsolution to save energy. When applied with care as described inthis document, it will preform its function properly. This lightsensorshould however not be used in the following applications:• When light levels are required with a higher accuracy then

10% of the desired value. In that case, sensors and controllerswith a higher performance should be used.

• When the required light level is significantly lower than the installed level, e.g. more than 30% lower. In that case a dimming device should be installed instead.

• When the construction of the building is such that a largevariety of rooms exist, both in shape and decoration, leadingto individual fine tuning per room during commissioning. In that case, controls with optimized commissioning toolsshould be used.

The control characteristics are described in the graph. The lightsensor roughly compensates for 50% of the ingressing daylight by dimming the artificial light output, until the minimum output is reached (3% for Philips HFR)

Luxmeter 500 lux

+ -

0 200 400 600 800 1000Daylight (lux)

Installed

Required

Luminaire output

Total, without se

nsor

Total, with sensor

Daylight

Tabl

etop

ligh

tleve

l (lu

x)

1200 1400 1600 1800 20000

500

1000

1500

2000

2500

3000

Commissioning

Application Warnings

Control characteristics

Note: The factory setting is such that in normal office environments, no adjustment with the rotary control is required.

figure
TDT8015.wmf
figure
THB1045.wmf
figure
THB1047.wmf
figure
THB1048.wmf
figure
THB1089.wmf
Page 5: lrl1220d

TRIOS LuxsenseLRL 1220/00 sensor, LRH 1221/00 TLD clip, LRH 1222/00 TL5 clip

Ordering dataType Ordering EAN codes Packaging Packaging Weight

number quantity dimensionsTrios Luxsense pcs mm gLRL 1220/00 Sensor 9137 003 09103 8711 559 516912 100 460x220x110 ca. 2400

LRH 1221/00 Lamp Clip TL8 9137 003 09203 8711 559 516929 100 210x166x132 ca. 450

LRH 1222/00 Lamp Clip TL5 9137 003 09303 8711 559 516936 100 210x166x132 ca. 450

LRL 1220/05 Sensor with clip TL5 9137 003 09903 8711 559 516974 1 120x130x30 ca. 248711 559 516967 20 370x260x130 ca. 600

LRL 1220/08 Sensor with clip TL8 9137 003 09803 8711 559 516998 1 120x130x30 ca. 248711 559 516981 20 370x260x130 ca. 600

The lightsensor can be mounted in the luminaire either by clicking on the lamp, or by fixing it to the end lamella.

Mounting on the lampThis is an option for all luminaires with a direct line of sight between the lamp and the floor of the room.The lamp clip LRH 1221 should be used in case of TLD lamps, LRH 1222 in case of TL5. The sensor can easily be clicked into the lampclip.The unit must be located:• At the (eletrical) “cold” side of the lamp. This is the side of

the lamp that is connected to the terminals of the ballast that allow for the longest wiring to the lamp. A distinct “cold side”is usually clearly marked on ballasts using the “half-bridge” principle (e.g. all Philips HF ballasts).

• As close to the end cap of the lamp as possible, but at least 7 cm away from that end cap

Please note:• It is not allowed to use lamp clips with TL5 HO (high output)

lamps, due to their high lamp surface temperatures. • Metal mirror-optics shall be properly connected to “earth”

(TLD and TL5 applications).• Mounting on the lamp is an option only for luminaires that do

not obscure the sensitivity opening angle.

Mounting on the end lamellaAs an alternative, the receiver can be mounted on the end lamella. This requires a special mounted bracket, to be provided by the luminaire manufacturer. It must be strictly avoided that the sensitivityopening angle is obscured by the optics or construction parts of the luminaire. Mounting at the (electrical) “cold side” of the lampis recommended.

Basic dimensions of bracket

click

2

1

Made in E.U.

LRL 1220Made in E.U.

LRL 1220Made in E.U.

LRL 1220

> 7 cm

end lamellaspecial bracket

19

14.1

5.1

front view; dimensions have to be

exactly implemented

side view; design depending

on luminaire optic

16.9

Instructions for luminaire construction

figure
TDT8005.wmf
figure
TDT8013.wmf
figure
TDT8011.wmf
Page 6: lrl1220d

TRIOS LuxsenseLRL 1220/00 sensor, LRH 1221/00 TLD clip, LRH 1222/00 TL5 clip

3222 636 3501001/99Printed in the NetherlandsData subject to changehttp://www.lighting.philips.com