91
This document is the property of Carrier Corporation and is delivered on the express condition that it is not to be disclosed, reproduced in whole or in part, or used for manufacture by anyone other than Carrier Corporation without its written consent, and that no right is granted to disclose or so use any information contained in said document. Carrier reserves the right to change or modify the information or product described without prior notice and without incurring any liability. © 2005, Carrier Corporation 808-335 Rev. 08/05 LonWorks Carrier Translator Overview and Configuration Manual Introduction ................................................................. 1 About this Manual .................................................. 1 Operating Characteristics ........................................... 3 Templates ................................................................ 3 Default Address and Baud Rate .............................. 5 LonWorks Carrier Translator Configuration Tables ...................................................................... 6 Carrier Translator Configuration Table ........... 6 Chiller Mapping Tables .................................. 6 Generic Mapping Tables ................................ 6 Rooftop Mapping Tables .............................. 7 Carrier Translator Device Configuration Table ............................................................... 7 Carrier Translator Maintenance Tables ................... 7 Chiller, Rooftop, Generic Mapping Maintenance Tables ....................... 7 Communication Status Maintenance Table .... 7 Messages Maintenance Table ....................... 7 Configuration ............................................................... 9 Configuration Process ............................................. 9 Select the LonWorks Profile ........................... 9 Map CCN Points with LonWorks Variables .. 10 Check for Mapping Errors and Confirm Values in Maintenance Tables .................................. 11 Commissioning the Device on the LonWorks Network ......................................................... 12 Carrier Translator Configuration (CONFIG) Table .. 13 Chiller Mapping Configuration (CHLRMAP1) Table 1 .................................................................... 16 Chiller Mapping Configuration (CHLRMAP2) Table 2 .................................................................... 21 Rooftop Mapping Configuration (RTUMAP1) Table 1 .................................................................... 25 Rooftop Mapping Configuration (RTUMAP2) Table 2 .................................................................... 31 Generic Mapping Configuration (GNRCMAP1) Table 1 .................................................................... 36 Generic Mapping Configuration (GNRCMAP2) Table 2 .................................................................... 40 Maintenance ................................................................ 45 Chiller Maintenance (CHLRMNT1) Table 1 .................................... 45 Chiller Maintenance (CHLRMNT2) Table 2 .................................... 48 Rooftop Maintenance (RTUMNT1) Table 1 ...................................... 50 Rooftop Maintenance (RTUMNT2) Table 2 ...................................... 52 Generic Maintenance (GNRCMNT1) Table 1 ................................... 55 Generic Maintenance (GNRCMNT2) Table 2 ................................... 57 Communication Status (COMMSTAT) Maintenance Table ........................................ 59 Messages Maintenance (MESSAGES) Table .............................................................. 61 Appendix ...................................................................... 63 Index ............................................................................ 77

LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

  • Upload
    lenhi

  • View
    233

  • Download
    0

Embed Size (px)

Citation preview

Page 1: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

This document is the property of Carrier Corporation and is delivered on the express condition that it is not to be disclosed,reproduced in whole or in part, or used for manufacture by anyone other than Carrier Corporation without its written consent, andthat no right is granted to disclose or so use any information contained in said document.

Carrier reserves the right to change or modify the information or product described without prior notice and without incurring anyliability.

© 2005, Carrier Corporation 808-335 Rev. 08/05

LonWorksCarrier Translator

Overview and ConfigurationManual

Introduction ................................................................. 1About this Manual .................................................. 1

Operating Characteristics ........................................... 3Templates ................................................................ 3Default Address and Baud Rate .............................. 5LonWorks Carrier Translator ConfigurationTables ...................................................................... 6

Carrier Translator Configuration Table ........... 6Chiller Mapping Tables .................................. 6Generic Mapping Tables ................................ 6Rooftop Mapping Tables .............................. 7Carrier Translator Device ConfigurationTable ............................................................... 7

Carrier Translator Maintenance Tables ................... 7 Chiller, Rooftop, Generic

Mapping Maintenance Tables ....................... 7Communication Status Maintenance Table .... 7Messages Maintenance Table ....................... 7

Configuration ............................................................... 9Configuration Process ............................................. 9

Select the LonWorks Profile ........................... 9Map CCN Points with LonWorks Variables ..10Check for Mapping Errors and Confirm Valuesin Maintenance Tables ..................................11Commissioning the Device on the LonWorksNetwork .........................................................12

Carrier Translator Configuration (CONFIG) Table ..13Chiller Mapping Configuration (CHLRMAP1)Table 1 ....................................................................16Chiller Mapping Configuration (CHLRMAP2)Table 2 ....................................................................21Rooftop Mapping Configuration (RTUMAP1)Table 1 ....................................................................25Rooftop Mapping Configuration (RTUMAP2)Table 2 ....................................................................31

Generic Mapping Configuration (GNRCMAP1)Table 1 ....................................................................36Generic Mapping Configuration (GNRCMAP2)Table 2 ....................................................................40

Maintenance ................................................................45 Chiller Maintenance (CHLRMNT1) Table 1 ....................................45

Chiller Maintenance(CHLRMNT2) Table 2 ....................................48Rooftop Maintenance(RTUMNT1) Table 1 ......................................50Rooftop Maintenance(RTUMNT2) Table 2 ......................................52Generic Maintenance(GNRCMNT1) Table 1 ...................................55Generic Maintenance(GNRCMNT2) Table 2 ...................................57Communication Status (COMMSTAT)Maintenance Table ........................................59Messages Maintenance (MESSAGES)Table ..............................................................61

Appendix ......................................................................63

Index ............................................................................77

Page 2: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

ii

Page 3: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

iii

ManualRevisions

The LonWorks Carrier Translator Overview and ConfigurationManual is catalog number 808-335, Rev. 08/05. This manualreplaces the LonWorks Overview and Configuration Manual,catalog number 808-288, 12/03.

Section/Chapter Changes

1. Under Commissioning the Device on the LonWorks Network,on page 12, added new paragraphs 1 and 2.

2. Under Chiller Mapping Configuration (CHLRMAP1) Table 1on page 21, revised the description of nviOccSchedule.

3. Under Chiller Mapping Configuration (CHLRMAP2) Table 1on page 23, revised the LON Variable Type for nviPRESS1and nvoPRESS1 - 4.

4. Revised Figure 3-4, Rooftop Mapping 1 Configuration(RTUMAP1) Table to remove the Value fornvoUnitStatus.in_alarm.

5. Under Rooftop Mapping Configuration (RTUMAP1) Table 1on page 28, revised the description of nviOccSchedule.

6. Under Rooftop Mapping Configuration (RTUMAP1) Table 1on pages 30-31, revised the Example for nviPRESS1, andrevised the descrption and Example for nvoPRESS1 - 2.

7. Under Generic Mapping Configuration (GNRCMAP1) Table1 on pages 39-40, revised the description of nviOccSchedule,and the Lon Variable Type for nviPRESS1 - 2 andnvoPRESS1 - 6.

8. In Figure A-2 on page 65 and Figure A-4 on page 67, revisedthe SNVT Type for nviPRESS1, and nvoPRESS1 throughnvoPRESS4.

9. In Figure A-9 on page 72 and Figure A-11 on page 74, re-vised the SNVT Type for nviPRESS2, and nvoPRESS3through 6.

Configuration

Page 4: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

iv

Page 5: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

Introduction

Page 6: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

1

This manual contains information about the functions of the LonWorksCarrier Translator module with LON FT-10A (free topology) communi-cation and how the user configures the LonWorks Carrier Translator toperform those functions.

The manual is divided into the following sections:

• Introduction• Operating Characteristics• Configuration• Maintenance

The Introduction consists of this description of the manual.

The Operating Characteristics section contains a description of theCarrier Translator hardware and a summary description of its configura-tion and maintenance tables.

The Configuration section contains detailed lists of the decisions for eachCarrier Translator configuration table. Each list entry includes thedecision’s purpose, the range of values that may be used, and the defaultvalues that will appear in the decision if it is not configured by the user.The mapping tables include an explanation of each decision, along withthe LonWorks read/write access, LON Variable Type, and an exampleCCN point name.

The Maintenance section contains detailed lists of the decisions for eachCarrier Translator maintenance table. Each list entry includes thedecision’s purpose and the range of values that may be displayed.

The Appendix contains examples of actual configurations for a chiller,rooftop, and generic template, along with a list of LON SNVTs andcorresponding CCN point names and descriptions.

About thisManual

Introduction

Page 7: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

2

Page 8: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

OperatingCharacteristics

Page 9: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

3

The LonWorks Carrier Translator with LON FT-10A (free topology)communication is a micro controller-based module that provides theability to integrate Carrier CCN-based controllers into LonWorks-basednetworks.

The LonWorks Carrier Translator (33CNTRANLON) provides CCNto LON FT-10A ANSI/EIA-709.1 protocol conversion.

The Carrier Translator can be mounted in the controls section of anyCCN equipment and converts the CCN-based controller data toLonWorks. The Carrier Translator is outdoor duty rated and contains aCCN RS-485 connector and a LON FT-10A communications connec-tor.

The LonWorks Carrier Translator can convert Carrier equipment withCCN controls to LON and outputs the CCN data in standard LONRooftop or Chiller profiles. Carrier rooftop units can be converted to thestandard LonMark Rooftop Unit (RTU) Functional profile 8030 Version1.1. Carrier chillers can be converted to the standard LonMark ChillerFunctional profile 8040 Version 1.0. The chiller and rooftop profilesinclude additional LON SNVTs beyond those required by the LONstandard profiles. These additional SNVTs allow for enhanced LONcapability beyond the standard LON-defined profiles. In addition to therooftop and chiller profiles, a generic LON profile is also supplied. Thisprofile can be used to convert Carrier controllers that may not convertefficiently into the LonMark Rooftop or Chiller profiles.

When connected to a CCN controller, the LonWorks Carrier Translatorallows a third party LON device to read and write to the CCNcontroller’s mapped status display, time schedule, and setpoint scheduledata. Note that LON status display write access is subject to the CCNequipment controller’s defined read/write access for each status displayitem.

The LonWorks Carrier Translator contains chiller, rooftop, and genericLON templates that allow mapping of various CCN points to LONSNVTs. Tables 2-1 through 2-3 show the type and quantity of CCNpoints in each supplied template.

OperatingCharacteristics

Templates

Page 10: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

4

Reads Writes

Space Temperature Space TemperatureOutdoor Air Temperature Outdoor Air TemperatureOutdoor Air Humidity Outdoor Air HumidityCO2 (PPM) Space HumidityCooling Coil % CO2 (PPM)Heating Coil % Supply Air Setpoint (VAV)Economizer Position % Setpoint OffsetFan Speed % 6 Setpoints (degF)Normal/Alarm Discrete 1 Setpoint (PPM)Controlling Setpoint Occupancy Schedule (>64E)4 Generic Temperature 1 Generic Temperature8 Generic Discrete 3 Generic Discrete2 Generic Pressure ("H2O) 3 Generic Discrete3 Generic Percentage 1 Generic Pressure ("H2O)2 Generic Delta Temp 2 Generic Percentage2 Generic (0 to 65535) 1 Generic (0 to 65535)2 Generic (-32767 to 32767)

Reads Writes

Percent Capacity Chiller Start/StopActive Demand Limit Percent Active Demand Limit PercentChilled Water Control Temp Chilled Water Control TempEntering Chilled Water Temp Hot Water Control TempLeaving Chilled Water Temp Occupancy Schedule (>64E)Entering Cond Water Temp 1 Generic TemperatureLeaving Cond Water Temp 2 Generic DiscreteChilled Water Flow Discrete 1 Generic Pressure (PSI)Cond Walter Flow Discrete 1 Generic (0 to 65535)6 Generic Temperature6 Generic Discrete4 Generic Pressure (PSI)2 Generic Percentage2 Generic Delta Temp2 Generic (0 to 65535)2 Generic (-32767 to 32767)

Table 2-1Rootop Template

Table 2-2Chiller Template

Page 11: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

5

Reads Writes

Cooling Coil % 6 Setpoints (degF)Heating Coil % Occupancy Schedule (>64E)Second Heating Coil % 3 Generic TemperatureEconomizer Position % 3 Generic DiscreteFan Speed % 1 Generic Pressure ("H2O)Normal/Alarm Discrete 1 Generic Pressure (PSI)8 Generic Temperature 2 Generic Percentage8 Generic Discrete 1 Generic PPM2 Generic Pressure ("H2O) 1 Generic (0 to 65535)4 Generic Pressure (PSI)4 Generic Percentage2 Generic Delta Temp1 Generic PPM2 Generic (0 to 65535)2 Generic (-32767 to 32767)

The LonWorks Carrier Translator’s default CCN address is 0,200 (busnumber, system element number). The default CCN baud rate is 9600bps.

Each LonWorks Carrier Translator has a unique LON address. TheLON address can be sent to LON configuration tools when the LONservice pin is pressed.

The Carrier Translator has three LEDs that are used to indicate opera-tional status:

LED Color Indicates

Status Red Operating, initialization and configurationstatus. The LED blinks at a 2 Hz ratewhen initializing and at 1 Hz whenoperating correctly.

CCN Yellow The Carrier Translator is sending CCNcommunication messages to theconnected CCN controller. If theconnected CCN controller is responding,its CCN LED will blink when a messageis sent back to the Carrier Translator.

(continued)

Table 2-3Generic Template

Default Addressand Baud Rate

Table 2-4Carrier Translator LEDs

Page 12: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

6

LED Color Indicates

LON Green The Carrier Translator is sending LONcommunication messages to the thirdparty LonWorks network.

The Carrier Translator contains the configuration tables listed below. Fordescriptions of the decisions in each table, refer to the Configurationsection of this manual. The purpose of each table is summarized on thefollowing pages.

Carrier Translator Device Configuration Table (CtlrID)Chiller Mapping Table 1 (CHLRMAP1)Chiller Mapping Table 2 (CHLRMAP2)Carrier Translator Configuration Table (CONFIG)Generic Mapping Tab le 1 (GNRCMAP1)Generic Mapping Table 2 (GNRCMAP2)Rooftop Unit Mapping Table 1 (RTUMAP1)Rooftop Unit Mapping Table 2 (RTUMAP2)

The Carrier Translator Configuration Table (CONFIG) contains deci-sions used to specify the following:

• LonWorks Profile (Rooftop, Chiller, Generic)• CCN Address• Auto-mapping• Reset Points Profile

The Chiller Mapping Tables (CHLRMAP1 and CHLRMAP2) are usedto map or associate CCN points with the variables in the LonWorksChiller profile, which is based on LonMark Functional Profile Chiller8040 V 1.0. These tables are configured if the Carrier TranslatorCONFIG Table's Device Type decision is set to 2 (Chiller).

The Carrier Translator's Generic Mapping Tables (GNRCMAP1 andGNRCMAP2) are used to map or associate CCN points with thevariables in the LonWorks generic controller profile. These tables areconfigured if the Carrier Translator CONFIG Table's Device Typedecision is set to 3 (Generic). This table could be used, for example, toallow LON access to an air handler.

Table 2-4Carrier Translator LEDs(continued)

LonWorks CarrierTranslatorConfigurationTables

Carrier TranslatorConfiguration Table

Chiller Mapping Tables

Generic MappingTables

Page 13: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

7

Chiller, Rooftop,Generic MappingMaintenance Tables

The Carrier Translator's Rooftop Mapping Tables (RTUMAP1 andRTUMAP2) are used to map or associate CCN points with the variablesin the LonWorks rooftop profile, which is based on LonMark FunctionProfile Rooftop Unit 8030 Version 1.1. The table is configured if theCarrier Translator CONFIG Table's Device Type decision is set to 1(Rooftop).

The Carrier Translator contains a Device Configuration Table (CtlrID).By changing the information that appears in this table, you can change thename, description, and location that appears for the Carrier Translator inthe CCN front end's (example: ComfortWORKS/ComfortVIEW)Controller List.

The Carrier Translator contains the following maintenance tables:

Chiller Mapping Table 1 (CHLRMNT1)Chiller Mapping Table 2 (CHLRMNT2)Communication Status Table (COMSTAT)Generic Mapping Table 1 (GNRCMNT1)Generic Mapping Table 2 (GNRCMNT2)LonWorks Messages Table (MESSAGES)Rooftop Unit Mapping Table 1 (RTUMNT1)Rooftop Unit Mapping Table 2 (RTUMNT2)

The maintenance values displayed in these tables are read-only valuesthat show the current value of the CCN points that have been mapped tothe Lonworks variables as the points exist in the CCN system element.These values are updated every 30 seconds. Note that if a LonWorksread (nvo) and write (nvi) variable have been mapped to the same CCNpoint, they will display the same value in the maintenance table display.

The maintenance values displayed in this table are read-only values thatshow diagnostic data about LonWorks-to-CCN system element com-munication.

The maintenance values displayed in this table are read-only values thatshow diagnostic data about LonWorks-to-CCN system element com-munication messages.

Rooftop MappingTables

Carrier TranslatorDevice ConfigurationTable

Carrier TranslatorMaintenanceTables

Messages MaintenanceTable

Communication StatusMaintenance Table

Page 14: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

8

Page 15: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

Configuration

Page 16: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

9

The LonWorks Carrier Translator's operation is controlled by decisionsentered in a group of configuration tables. The Carrier Translator containsthe following configuration tables:

CTLR_ID Carrier Translator Controller IdentificationTable

CHLRMAP1 Chiller Mapping Configuration Table 1CHLRMAP2 Chiller Mapping Configuration Table 2CONFIG Carrier Translator Configuration TableGNRCMAP1 Generic Configuration Table 1GNRCMAP2 Generic Configuration Table 2RTUMAP1 Rooftop Unit Configuration Table 1RTUMAP2 Rooftop Unit Configuration Table 2

LonWorks Carrier Translator configuration and start-up consists of fourmain processes:

1. Physically connect the LonWorks Carrier Translator to the CCNsystem element.

2. Select the appropriate LonWorks profile. You do this in theCONFIG Table.

3. Map, or associate, CCN points with LonWorks points by config-uring the appropriate set of configuration tables (rooftop, chiller,or generic), depending on the device type that you selected in theCONFIG Table.

4. Commission the Carrier Translator on the LonWorks network.

Each of the above-listed processes is discussed below.

1. Connect the target CCN system element to the CarrierTranslator's CCN connector. Confirm that the element is poweredand communicating on the CCN Bus.

2. Using a CCN front end (such as a Network Service Tool,ComfortVIEW, or ComfortWORKS) access the CarrierTranslator’s CONFIG Table and select the appropriateLonWorks profile (Rooftop, Chiller, or Generic) by entering a 1,2, or a 3 into the CONFIG Table's Device Type decision.

Configuration

ConfigurationProcess

Select the LonWorksProfile

Page 17: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

10

3. Enter appropriate values into all CONFIG Table decisions anddownload the CONFIG Table into the Carrier Translator.

If the Carrier Translator is on a CCN bus with elements other thanthe single CCN device with which it is communicating, you must:

• Set Bus and Element #s• Set the Reset Points Profile decision to Yes• Download.

This chapter's Carrier Translator Configuration (CONFIG) Tablesection contains explanations of and allowable entries and defaultvalues for each CONFIG Table decision.

After approximately 5 seconds, the Carrier Translator shouldidentify the target CCN system element and begin to download itstables. This takes 10 to 40 seconds, depending on the number oftables in the target CCN system element. During this period, theYellow LED will flash to indicate CCN bus activity. When theflashing stops, the download is complete.

Note: Do not cycle Carrier Translator power within 30 secondsof downloading the CONFIG Table or any of the map-ping tables. Be sure that the Yellow CCN LED is NOTflashing.

1. Using a CCN front end, access the appropriate set of configurationtables, depending on the value you specified in the CONFIG Table'sDevice Type decision :

Rooftop (Device Type 1) - RTUMAP1 and RTUMAP2Chiller (Device Type 2) - CHLRMAP1 and CHLRMAP2Generic (Device Type 3) - GNRCMAP1 and GNRCMAP2

2. You will now "map" or associate CCN point names with eachLonWorks network variable name that is listed in the configurationtables. Note that those LonWorks network variables having readaccess begin with the characters nvo and LonWorks networkvariables with write access begin with the characters nvi.

Entries are case insensitive - upper or lower case characters may beused.

Map CCN Points withLonWorks Variables

Page 18: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

11

In the Lon structure, there are different types of points for readingand writing purposes. If a CCN point is to be both read andwritten to by the Lon system, it is recommended that you use twoLon points to accomplish this. The reason for using a separateLon point to read the CCN point is in case that CCN point isforced by a higher level function than the Carrier Translator itself,which uses Control forces.

Also in the Lon structure, there are dedicated types of points fordifferent types of generic values, such as Temperature, Tempera-ture Difference, Pressure, Percent, and Discrete. You mustassociate a particular CCN point with the matching Lon point typeor the Carrier Translator will not function properly.

In addition, for the Carrier Translator's chiller and rooftop map-ping tables, the identity of some Lon points have been pre-determined to conform to the LonMark functional profile for theparticular device type. Using these points, where possible, allowsthe generic point types that appear later in the mapping table to beused for other CCN points. Example: In the Chiller tables thereare dedicated Lon points for Entering and Leaving Chilled WaterTemperature, and in the Rooftop tables there are dedicated pointsfor Space and Outside Air Temperature.

Explanations of each table decision, along with example CCNpoint names, can be found later in this Configuration chapter.Examples of completed templates and lists of SNVTs and corre-sponding CCN points can be found in the Appendix.

1. Using a CCN front end, access the two configuration mappingtables (chiller, rooftop, or generic) that were used in Step 2 of theMap CCN Points with LonWorks Variables procedure, whichappears prior to this section of the Configuration chapter.

2. Download each table to the Carrier Translator and wait approxi-mately one minute.

During this time the Carrier Translator performs error checking toverify if you have entered any non-existent point names as well aschecks for correct point types (analog/discrete,etc.).

3. Upload the tables and check the displayed tables.

Look for any decisions that may have the message error**1 orerror**2 displayed in their Value column. These messagesindicate that the entry that was made for this decision is invalid:

Check for MappingErrors and ConfirmValues in MaintenanceTables

Page 19: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

12

error**1 Indicates that the point name was not found in thetarget CCN system element.

error**2 The point name was found on the target CCN devicebut the data type is not valid to this LonWorks net-work variable.

The errors should be corrected and the tables downloaded.

Example: If, in the CHILLERMAP1 Table, the nvoTEMP1decision has been configured with the point nameDP_A, which is a pressure, the message error**2 willbe displayed because this decision requires a tempera-ture point.

After verifying that there are no error messages in either Configurationmapping Table, cycle power to the Carrier Translator and observe theyellow LED. This is the CCN communication indicator.

Approximately one minute after the yellow LED stops blinking, check theappropriate Maintenance Tables to confirm that the correct data isdisplayed for each configured point.

Note: The Carrier Translator polls the CCN system element every30 seconds to both Read and Write CCN points.

The Carrier Translator is now fully commissioned on the Carrier/CCNside and is ready for the Lon systems integrator to commission the Lonside using a Lon software tool such as LonMaker.

A list of the actual CCN points configured in the appropriate MAP1 andMAP2 templates should be supplied to the systems integrator to assisthim/her with the commissioning process. A blank copy of these templatescan be found in the Appendix of this manual. Additionally, the NeuronIDof the Echelon Lon processor chip should also be supplied to the systemsintegrator. This is a 12 character alphanumeric code that can be found ona white label located along the upper edge of the control board, oppositethe Lon connector.

After the LonWorks Carrier Translator is added to the LonWorksnetwork, the LonWorks network variables that were mapped in thischapter's Map CCN Points with LonWorks Variables procedure can beused to read/write data points on the target CCN system element.

Commissioning theDevice on theLonWorks Network

Page 20: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

13

Carrier TranslatorConfiguration(CONFIG) Table

The Carrier Translator's CONFIG Table is shown below. An explanationof each decision, including allowable entries and default values follows.

Note: When starting up the Carrier Translator this is the first tableyou must configure.

Device Type1=Rftp, 2=Chillr,3=Gnrc

Use this decision to select the desired LonWorks Profile. After enteringthis value and downloading this table to the Carrier Translator, theappropriate LonWorks variable names will be loaded into the CarrierTranslator.

Allowable Entries 1 = Rooftop2 = Chiller3 = Generic

Default Value 0

Figure 3-1Carrier TranslatorConfiguration (CONFIG)Table

Page 21: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

14

Use this decision to specify the bus number of the CCN system elementto which the Carrier Translator is connected.

Note: If you do not enter a value for this decision or if the value isincorrect, the Carrier Translator will attempt to find the ele-ment address itself. You will then have to upload this table tocheck if the correct address has been found.

Allowable Entries 0-239

Default Value 0

Use this decision to specify the number of the CCN system element towhich the Carrier Translator is connected.

Note: If you do not enter a value for this decision or if the value isincorrect, the Carrier Translator will attempt to find the ele-ment address itself. You will then have to upload this table tocheck if the correct address has been found.

Allowable Entries 0-239

Default Value 0

Use this decision to disable or enable the Carrier Translator's automaticmapping feature. Setting this decision to No will cause the Carrier Trans-lator to upload mapping tables that may exist in the target CCN systemelement. Setting this decision to Yes will disable automatic mapping andwill cause the Carrier Translator to use the mapping tables from theCarrier Translator.

Note: No current CCN system element contains automatic mappingtables.

Allowable Entries 0 = No1 = Yes

Default Value 0

Target Bus No.

Target Address

Disable Auto-mapping

Page 22: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

15

Reset Points Profile Use this decision to clear the contents of all of the Carrier Translator'sCCN point to LonWorks variable mapping tables. This decision resets toNo on completion of the operation. The following tables will be cleared:

RTUMAP1 and RTUMAP2CHLRMAP1 and CHLRMAP2GNRCMAP1 and GNRCMAP2

Note: Do not save this decision set to Yes. Do not cycle CarrierTranslator power for at least 30 seconds after downloadingthis decision set to Yes. If you do cycle power within 30seconds of downloading this decision as Yes, the CarrierTranslator will return to its default address of 0,200 at a baudrate of 9600 baud.

Allowable Entries 0 = No1 = Yes

Default Value 0

Use this decision to clear the COMMSTAT Maintenance Table's NumSuccessful Messages and Num Failed Messages counters. This decisionresets to No on completion of the operation.

Note: Do not save this decision set to Yes.

Allowable Entries 0 = No1 = Yes

Default Value 0

Use this decision to specify whether the Carrier Translator should act asa CCN alarm acknowledger for all alarm messages received from theCCN Bus. There must be only one CCN alarm acknowledger per CCN.

Note that alarms from the Carrier Translator's target system element areplaced into the Carrier Translator's buffer.

Allowable Entries 0 = No1 = Yes

Default Value 1

Reset Comm. Counters

Alarm Acknowledger

Page 23: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

16

Chiller MappingConfiguration(CHLRMAP1)Table 1

The Carrier Translator's CHLRMAP1 Table is used to map or associateCCN points with the variables in the LonWorks chiller profile (which isbased on LonMark Functional Profile: Chiller 8040 V 1.0). This tableshould be configured if the Carrier Translator CONFIG Table's DeviceType decision was set to 2 (Chiller). A sample CHLRMAP1 Table isshown below. An explanation of each decision, including LonWorksread/write access, LON Variable Type, along with an example CCNpoint name follows.

CCN point names can consist of up to 8 characters. The default for eachdecision is blank.

Figure 3-2Chiller Mapping 1Configuration (CHLRMAP1)Table

Allowable Entries andDefault Value

Page 24: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

17

Use this decision to specify the name of the discrete CCN point that theLON system can write to in order to start or stop the chiller.

LON Variable Type SNVT_switch

Read/Write Access Write

Example CHIL_S_SChiller Start/Stop

Use this decision to specify the name of the analog CCN point that theLON system can write to in order to set the leaving chilled water tem-perature setpoint when the chiller is operating in cooling mode.

LON Variable Type SNVT_temp_p

Read/Write Access Write

Example CTRL_PNTControl Point

Use this decision to specify the name of the discrete CCN point that theLON system can read in order to indicate the chiller's current status (on/off ).

Note: Most CCN chillers do not contain this point.

LON Variable Type SNVT_switch

Read/Write Access Read

Use this decision to specify the name of the analog CCN point that theLON system can read in order to obtain the current value of the chiller'scooling or heating setpoint. The setpoint to be used (cooling or heating)depends on the chiller's current operating mode.

LON Variable Type SNVT_temp_p

Read/Write Access Read

Example CTRL_PNTControl Point

Use this decision to specify the name of the analog CCN point that theLON system can write to in order to set the capacity limit of the chiller.

LON Variable Type SNVT_lev_percent

Read/Write Access Write

Example DEM_LIMActive Demand Limit

nviCoolSetpt

nvoOnOff

nvoActiveSetpt

nviCapacityLim

nviChillerEnable

Page 25: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

18

Use this decision to specify the name of the analog CCN point that theLON system can write to in order to set the heating setpoint.

LON Variable Type SNVT_temp_p

Read/Write Access Write

Example CTRL_PNTControl Point

Use this decision to specify the name of the analog CCN point that theLON system can read in order to obtain the current running capacity ofthe chiller.

LON Variable Type SNVT_lev_percent

Read/Write Access Read

Example CAP_TPercent Total Capacity

Use this decision to specify the name of the analog CCN point that theLON system can read in order to obtain the chiller's current capacity limitsetpoint.

LON Variable Type SNVT_lev_percent

Read/Write Access Read

Example DEM_LIMActive Demand Limit

Use this decision to specify the name of the analog CCN point that theLON system can read in order to obtain the leaving chilled water tem-perature.

LON Variable Type SNVT_temp_p

Read/Write Access Read

Example LWTLeaving Fluid Temp

Use this decision to specify the name of the analog CCN point that theLON system can read in order to obtain the entering chilled watertemperature.

LON Variable Type SNVT_temp_p

Read/Write Access Read

Example EWTEntering Fluid Temp

nviHeatSetpt

nvoActualCapacity

nvoCapacityLim

nvoEntCHWTemp

nvoLvgCHWTemp

Page 26: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

19

nvoLvgCNDWTemp

Use this decision to specify the name of the analog CCN point that theLON system can read in order to obtain the entering condenser watertemperature.

LON Variable Type SNVT_temp_p

Read/Write Access Read

Example COND_EWTCondenser Entering Fluid

Use this decision to specify the name of the analog CCN point that theLON system can read in order to obtain the leaving condenser watertemperature.

LON Variable Type SNVT_temp_p

Read/Write Access Read

Example COND_LWTCondenser Leaving Fluid

Use this decision to provide the name of the discrete CCN point that theLON system can read in order to obtain the main running mode of thechiller.

Note: Most CCN chillers do not contain this point.

LON Variable Type SNVT_chlr_status

Read/Write Access Read

Use this decision to provide the name of the discrete CCN point that theLON system can read in order to obtain the main operating status of thechiller.

Note: Most CCN chillers do not contain this point.

LON Variable Type SNVT_chlr_status

Read/Write Access Read

Use this decision to provide the name of the discrete CCN point theLON system can read in order to obtain the alarm status of the chiller.

Note: Most CCN chillers do not contain this point.

LON Variable Type SNVT_chlr_status

Read/Write Access Read

nvoChillerStat.run_mode

nvoEntCNDWTemp

nvoChillerStat.in_alarm

nvoChillerStat.op_mode

Page 27: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

20

Use this decision to specify the name of the discrete CCN point that theLON system can read in order to obtain the status of the chiller (start/stop).

LON Variable Type SNVT_chlr_status

Read/Write Access Read

Example CHIL_S_SChiller Start/Stop

Use this decision to specify the name of the discrete CCN point that theLON system can read in order to obtain the chiller's local or networkcontrol status.

Note: Most CCN chillers do not contain this point.

LON Variable Type SNVT_chlr_status

Read/Write Access Read

Use this decision to specify the name of the discrete CCN point that theLON system can read in order to indicate that the chiller cannot reachsetpoint.

Note: Most CCN chillers do not contain this point.

LON Variable Type SNVT_chlr_status

Read/Write Access Read

Use this decision to specify the name of the discrete CCN point that theLON system can read in order to indicate if chilled water flow is present.

LON Variable Type SNVT_chlr_status

Read/Write Access Read

Example COOLFLOWCooler Flow Switch

Use this decision to specify the name of the discrete CCN point that theLON system can read in order to indicate if condenser water flow ispresent.

LON Variable Type SNVT_chlr_status

Read/Write Access Read

Example CONDFLOWCondenser Flow Switch

nvoChillerStat.run_enabl

nvoChillerStat.Local

nvoChillerStat.Limited

nvoChillerStat.cndw_flow

nvoChillerStat.chw_flow

Page 28: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

21

nviOccSchedule Use this decision to specify the name of the CCN occupancy schedulethat the LON system can write to in order to set occupancy times.

Note: The chiller unit must be configured to use a global occupancyschedule (Allowable entries: OCCPC65E to OCCPC99E).Refer to the chiller documentation for additional information onthe setup of the global occupancy schedule.

LON Variable Type SNVT_tod_event

Read/Write Access Write

Example OCCPC66EOccupancy Equipment

The Carrier Translator's CHLRMAP2 Table is used to map or associateCCN points with the variables in the LonWorks chiller profile. This table,in addition to the CHLRMAP1 Table, should be configured if the CarrierTranslator CONFIG Table's Device Type decision was set to 2 (Chiller).A sample CHLRMAP2 Table is shown below. An explanation of eachdecision, including LonWorks read/write access, LON Variable Type,along with an example CCN point name follows.

CCN point names can consist of up to 8 characters. The default for eachdecision is blank.

Use this decision to specify the name of the analog CCN point that theLON system can write to in order to set an additional chiller operatingtemperature.

LON Variable Type SNVT_temp_p

Read/Write Access Write

Example OATOutdoor Air Temperature

Use these 6 decisions to specify the names of the analog CCN pointsthat the LON system can read in order to obtain additional chiller operat-ing temperatures.

LON Variable Type SNVT_temp_p

Read/Write Access Read

Example TMP_SCTASaturated Condensing Temp

Chiller MappingConfiguration(CHLRMAP2)Table 2

Allowable Entries andDefault Value

nviTEMP1

nvoTEMP1 - 6

Page 29: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

22

Figure 3-3Chiller Mapping 2Configuration (CHLRMAP2)Table

Page 30: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

23

Use this decision to specify the name of the analog CCN point that theLON system can write to in order to set an additional chiller operatingpressure.

Note: 1. Most CCN chillers do not allow write access to this point.2. For use with points having units of psi (kPa).

LON Variable Type SNVT_press

Read/Write Access Write

Use these 4 decisions to specify the names of the analog CCN pointsthat the LON system can read in order to obtain additional chiller operat-ing pressures.

Note: 1. For use with points having units of psi (kPa).

LON Variable Type SNVT_press

Read/Write Access Read

Example SP_ASuction Pressure Circuit A

Use these 2 decisions to specify the names of the analog CCN pointsthe LON system can read in order to obtain additional chiller operatingparameters in percentage.

LON Variable Type SNVT_lev_percent

Read/Write Access Read

Example CAPA_APercentage Operating Capacity

Use these 2 decisions to specify the names of the analog CCN pointsthat the LON system can read in order to obtain additional chiller differ-ential temperatures.

LON Variable Type SNVT_temp_diff

Read/Write Access Read

Example SH_ASuction Superheat

Use these 2 decisions to specify the names of the discrete CCN pointsthat the LON system can write to in order to set additional discreteoperating parameters.

LON Variable Type SNVT_switch

Read/Write Access Write

Example EMSTOPEmergency Stop

nvoPRESS1 - 4

nviPRESS1

nvoPCT1 - 2

nvoTEMPDIFF1 - 2

nviDISCRETE1 - 2

Page 31: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

24

Use these 6 decisions to specify the names of the discrete CCN pointsthat the LON system can read in order to obtain additional discreteoperating parameters.

LON Variable Type SNVT_switch

Read/Write Access Read

Example FANS_1Fan 1 Relay

Use this decision to specify the name of the analog or multi-state CCNpoint that the LON system will write to in order to set additional analogor multi-state operating parameters.

LON Variable Type SNVT_count

Read/Write Access Write

Example S_HRSService Ontime Hours

Use these decisions to specify the names of the analog or multi-stateCCN points that the LON system will read in order to obtain additionalanalog or multi-state values.

LON Variable Type SNVT_count

Read/Write Access Read

Example STATRun Status

Use these decisions to specify the names of the analog or multi-stateCCN points that the LON system will read in order to obtain additionalanalog or multi-state values.

LON Variable Type SNVT_count_inc

Read/Write Access Read

Example STATRun Status

nvoDISCRETE1 - 6

nviCOUNT1

nvoCOUNT1 - 2

nvoCOUNTinc1 - 2

Page 32: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

25

The Carrier Translator's RTUMAP1 Table is used to map or associateCCN points with the variables in the LonWorks rooftop profile (which isbased on LonMark Functional Profile: Rooftop Unit (RTU) 8030Version 1.1). This table should be configured if the Carrier TranslatorCONFIG Table's Device Type decision was set to 1 (Rooftop). Asample RTUMAP1 Table is shown on the page which follows. Anexplanation of each decision, including LonWorks read/write access,LON Variable Type, along with an example CCN point name follows.

CCN point names can consist of up to 8 characters. The default for eachdecision is blank.

Use this decision to specify the name of the analog CCN point that theLON system can write to in order to set the space temperature.

LON Variable Type SNVT_temp_p

Read/Write Access Write

Example SPTSpace Temperature

Use this decision to specify the name of the analog CCN point that theLON system can write to in order to set the temperature setpoint.

LON Variable Type SNVT_temp_p

Read/Write Access Write

Example CTRL_PNTControl Point

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate the space temperature.

LON Variable Type SNVT_temp_p

Read/Write Access Read

Example SPTSpace Temperature

Use this decision to specify the name of the discrete CCN point that theLON system can read in order to indicate the rooftop's operating mode.

Note: CCN rooftops do not contain this point.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

nviSpaceTemp

nvoUnitStatus.mode

nvoSpaceTemp

nviSetPoint

Allowable Entries andDefault Value

Rooftop MappingConfiguration(RTUMAP1)Table 1

Page 33: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

26

Figure 3-4Rooftop Mapping 1Configuration (RTUMAP1)Table

Page 34: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

27

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate the current primary heatcapacity in percent full scale.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Example HCAPHeating % Total Capacity

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate the current secondary heatcapacity in percent full scale.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Example HCAPHeating % Total Capacity

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate will indicate the currentsecondary cooling capacity in percent full scale.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Example CCAPCooling % Total Capacity

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate will indicate the currenteconomizer position in percent full scale.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Example ECONOPOSEconomizer Position %

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate the current fan speed inpercent full scale.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Example VFDVariable Frequency Drive Speed %

nvoUnitStatus.heat_out_s

nvoUnitStatus.cool_out

nvoUnitStatus.econ_out

nvoUnitStatus.fan_out

nvoUnitStatus.heat_out_p

Page 35: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

28

nvoUnitStatus.in_alarm Use this decision to provide the name of the discrete CCN point that theLON system can read in order to indicate the alarm status of the rooftop.

Note: Most CCN rooftops do not contain this point.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Use this decision to specify the name of the CCN occupancy schedulethat the LON system can write to in order to set occupancy times.

Note: The rooftop unit must be configured to use a global occupancyschedule (Allowable entries: OCCPC65E to OCCPC99E).Refer to the rooftop documentation for additional informationon the setup of the global occupancy schedule.

LON Variable Type SNVT_tod_event

Read/Write Access Write

Example OCCPC66EOccupancy Equipment

Use this decision to specify the name of the analog CCN point that theLON system will write to in order to set the active temperature setpoint.

Note: Most CCN rooftops do not contain this point.

LON Variable Type SNVT_temp_p

Read/Write Access Write

Use this decision to specify the name of the analog CCN point that theLON system will write to in order to set the outside air temperature.

LON Variable Type SNVT_temp_p

Read/Write Access Write

Example OATOutside Air Temperature

Use this decision to specify the name of the analog CCN point that theLON system will write to in order to set the outside air relative humidity.

LON Variable Type SNVT_lev_percent

Read/Write Access Write

Example OARHOutside Air Relative Humidity

nviOccSchedule

nviSetptOffset

nviOutsideRH

nviOutsideTemp

Page 36: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

29

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate the temperature setpoint.

LON Variable Type SNVT_temp_p

Read/Write Access Read

Example CTRL_PNTControl Point

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate the outside air temperature.

LON Variable Type SNVT_temp_p

Read/Write Access Read

Example OATOutside Air Temperature

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate the outside air relative humid-ity.

LON Variable Type SNVT_lev_percent

Read/Write Access Read

Example OARHOutside Air Relative Humidity

Use this decision to specify the name of the analog CCN point that theLON system will write to in order to set the relative humidity.

LON Variable Type SNVT_lev_percent

Read/Write Access Write

Example RHRelative Humidity

Use this decision to specify the name of the analog CCN point that theLON system will write to in order to set the CO2 level in ppm.

LON Variable Type SNVT_ppm

Read/Write Access Write

Example IAQIndoor air quality

nvoEffectSetpt

nvoOutsideTemp

nvoOutsideRH

nviSpaceRH

nviCO2

Page 37: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

30

Use this decision to specify the name of the analog CCN point that theLON system will read to indicate the CO2 level in ppm.

LON Variable Type SNVT_ppm

Read/Write Access Read

Example IAQIndoor air quality

Use this decision to specify the name of the analog CCN point that theLON system will write to in order to set an additional rooftop operatingtemperature.

LON Variable Type SNVT_temp_p

Read/Write Access Write

Example OATOutdoor Air Temperature

Use these 4 decisions to specify the analog CCN point names that theLON system will read to indicate additional rooftop operating tempera-tures.

LON Variable Type SNVT_temp_p

Read/Write Access Read

Example TMP_SCTASaturated Condensing Temp

Use this decision to specify the name of the analog CCN point that theLON system will write to in order to set an additional rooftop operatingpressure.

Note: For use with points having units of "H2O (Pa).

LON Variable Type SNVT_press_p

Read/Write Access Write

Example SPStatic Pressure

nvoCO2

nviTEMP1

nvoTEMP1-4

nviPRESS1

Page 38: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

31

Use these 2 decisions to specify the names of the analog CCN point thatthe LON system will read to indicate additional rooftop operating pres-sures.

Note: For use with points having units of "H2O (Pa).

LON Variable Type SNVT_press_p

Read/Write Access Read

Example SPStatic Pressure

The Carrier Translator's RTUMAP2 Table is used to map or associateCCN points with the variables in the LonWorks rooftop profile. Thistable should be configured if the Carrier Translator CONFIG Table'sDevice Type decision was set to 1 (Rooftop). A sample RTUMAP2Table is shown on the page which follows. An explanation of eachdecision, including LonWorks read/write access, LON Variable Type,along with an example CCN point name follows.

CCN point names can consist of up to 8 characters. The default for eachdecision is blank.

Use these 2 decisions to specify the names of the analog CCN pointsthat the LON system will write to in order to set additional rooftopoperating parameters in percentage.

LON Variable Type SNVT_lev_percent

Read/Write Access Write

Example ECONPOSEconomizer Position

Use these 3 decisions to specify the names of the analog CCN point thatthe LON system will read to indicate additional rooftop operating param-eters in percentage.

LON Variable Type SNVT_lev_percent

Read/Write Access Read

Example CAPA_APercentage Operating Capacity

Allowable Entries andDefault Value

Rooftop MappingConfiguration(RTUMAP2)Table 2

nvoPRESS1 - 2

nvoPCT1-3

nviPCT1-2

Page 39: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

32

Figure 3-5Rooftop Mapping 2Configuration (RTUMAP2)Table

Page 40: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

33

Use these 2 decisions to specify the names of the analog CCN pointsthat the LON system will read to indicate additional rooftop differentialtemperatures.

LON Variable Type SNVT_temp_diff

Read/Write Access Read

Example SH_ASuction Superheat

Use these 3 decisions to specify the names of the discrete CCN pointsthat the LON system will write to in order to set additional discreteoperating parameters.

LON Variable Type SNVT_switch

Read/Write Access Write

Example EMSTOPEmergency Stop

Use these 8 decisions to specify the names of the discrete CCN pointsthat the LON system will read to indicate additional discrete operatingparameters.

LON Variable Type SNVT_switch

Read/Write Access Read

Example FANS_1Fan 1 Relay

Use this decision to provide the name of the analog CCN point thattheyLON system will write to in order to set the CO2 threshold value.

LON Variable Type SNVT_ppm

Read/Write Access Write

Example IAQSIndoor Air Quality Setpoint

Use this decision to provide the name of the analog CCN point that theLON system will write to in order to set the occupied cooling setpoint.

LON Variable Type SNVT_temp_setpt

Read/Write Access Write

Example OCSPOccupied Cool Setpoint

nviDISCRETE1 - 3

nvoDISCRETE1 - 8

nciCO2Limit

nciSetpnts.occupied_cool

nvoTEMPDIFF1 - 2

Page 41: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

34

nciSetpnts.occupied_heat

nciSetpnts.standby_heat

nciSetpnts.unocc_heat

nciSetpnts.unocc_cool

Use this decision to provide the name of the analog CCN point that theLON system will write to in order to set the cooling setpoint in standbymode.

Note: Most CCN rooftops do not use this mode.

LON Variable Type SNVT_temp_setpt

Read/Write Access Write

Use this decision to provide the name of the analog CCN point that theLON system will write to in order to set the unoccupied cooling setpoint.

LON Variable Type SNVT_temp_setpt

Read/Write Access Write

Example UCSPUnoccupied Cool Setpoint

Use this decision to provide the name of the analog CCN point that theLON system will write to in order to set the occupied heating setpoint.

LON Variable Type SNVT_temp_setpt

Read/Write Access Write

Example OHSPOccupied Heat Setpoint

Use this decision to provide the name of the analog CCN point that theLON system will write to in order to set the heating setpoint in standbymode.

Note: Most CCN rooftops do not use this mode.

LON Variable Type SNVT_temp_setpt

Read/Write Access Write

Use this decision to provide the name of the analog CCN point that theLON system will write to in order to set the unoccupied heating setpoint.

LON Variable Type SNVT_temp_setpt

Read/Write Access Write

Example UHSPUnoccupied Heat Setpoint

nciSetpnts.standby_cool

Page 42: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

35

Use this decision to specify the name of the analog or multi-state CCNpoint that the LON system will write to in order to set additional analogor multi-state operating parameters.

LON Variable Type SNVT_count

Read/Write Access Write

Example OASPOA cfm Setpoint

Use these 2 decisions to specify the names of the analog or multi-stateCCN points that the LON system will read in order to obtain additionalanalog or multi-state values.

LON Variable Type SNVT_count

Read/Write Access Read

Example OACFMOA Airflow

Use these 2 decisions to specify the names of the analog or multi-stateCCN points that the LON system will read in order to obtain additionalanalog or multi-state values.

LON Variable Type SNVT_count_inc

Read/Write Access Read

Example OACFMOA Airflow

nviCOUNT1

nvoCOUNT1 - 2

nvoCOUNTinc1 - 2

Page 43: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

36

The Carrier Translator's GNRCMAP1 Table is used to map or associateCCN points with the variables in the LonWorks generic controllerprofile. This table should be configured if the Carrier TranslatorCONFIG Table's Device Type decision was set to 3 (Generic). Thistable could be used, for example, to allow LON access to an air handler.A sample GNRCMAP1 Table is shown on the page which follows. Anexplanation of each decision, including LonWorks read/write access,LON Variable Type, along with an example CCN point name follows.The decision explanations and example point names below are takenfrom a CCN air handler. Keep in mind, however, that the generic con-troller profile can also be used with other types of CCN controllers.

CCN point names can consist of up to 8 characters. The default for eachdecision is blank.

Use this decision to specify the name of the discrete CCN point that theLON system can read in order to indicate the air handler's operatingmode.

Note: Most CCN air handlers do not contain this point.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate the current primary heatcapacity in percent full scale.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Example HCVHeating Coil Valve %

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate the current secondary heatcapacity in percent full scale.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Example HCVHeating Coil Valve %

Allowable Entries andDefault Value

Generic MappingConfiguration(GNRCMAP1)Table 1

nvoUnitStatus.mode

nvoUnitStatus.heat_out_p

nvoUnitStatus.heat_out_s

Page 44: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

37

Figure 3-6Generic Mapping 1Configuration (GNRCMAP1)Table

Page 45: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

38

Use this decision to specify the name of the analog CCN point that thatthe LON system can read in order to indicate the current cooling capac-ity in percent full scale.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Example CCVCooling Coil Valve

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate the current economizer posi-tion in percent full scale.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Use this decision to specify the name of the analog CCN point that theLON system can read in order to indicate the current fan speed inpercent full scale.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

Example VFDVariable Frequency Drive Speed %

Use this decision to provide the name of the discrete CCN point that theLON system can read in order to indicate the alarm status of the airhandler.

Note: Most CCN air handlers do not contain this point.

LON Variable Type SNVT_hvac_status

Read/Write Access Read

nvoUnitStatus.cool_out

nvoUnitStatus.econ_out

nvoUnitStatus.fan_out

nvoUnitStatus.in_alarm

Page 46: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

39

Use this decision to specify the name of the CCN occupancy schedulethat the LON system can write to in order to set occupancy times.

Note: The CCN unit must be configured to use a global occupancyschedule (Allowable entries: OCCPC65E to OCCPC99E).Refer to the CCN documentation for additional information onthe setup of the global occupancy schedule.

LON Variable Type SNVT_tod_event

Read/Write Access Write

Example OCCPC66EOccupancy Equipment

Use these 3 decisions to specify the name of the analog CCN point thatthe LON system can write to in order to set an additional air handleroperating temperature.

LON Variable Type SNVT_temp_p

Read/Write Access Write

Example OATOutdoor Air Temperature

Use these 8 decisions to specify the analog CCN point names that theLON system can read in order to indicate additional air handler operatingtemperatures.

LON Variable Type SNVT_temp_p

Read/Write Access Read

Example SATSupply Air Temperature

Use these 2 decisions to specify the name of the analog CCN point thatthe LON system can write to in order to set an additional air handleroperating pressure.

Note: 1. Most CCN air handlers do not allow write access to thispoint.

2. PRESS1 is for use with points having units of "H20 (Pa).3. PRESS2 is for use with points having uints of psi (kPa).

LON Variable Type PRESS1: SNVT_press_pPRESS2: SNVT_press

Read/Write Access Write

nviOccSchedule

nviTEMP1 - 3

nvoTEMP1 - 8

nviPRESS1 - 2

Page 47: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

40

Use these 6 decisions to specify the names of the analog CCN pointthat that the LON system can read in order to indicate additional airhandler operating pressures.

Note: 1. PRESS1-2 are for use with points having units of "H20 (Pa).2. PRESS3-6 are for use with points having units of psi (kPa).

LON Variable Type PRESS1-2: SNVT_press_pPRESS3-6: SNVT_press

Read/Write Access Read

Example SPStatic Pressure

Use these 2 decisions to specify the names of the analog CCN pointsthat the LON system can read in order to indicate additional air handlerdifferential temperatures.

Note: Most CCN air handlers do no contain these points.

LON Variable Type SNVT_temp_diff

Read/Write Access Read

The Carrier Translator's GNRCMAP2 Table is used to map or associateCCN points with the variables in the LonWorks generic profile. Thistable, in addition to the GNRCMAP1 Table, should be configured if theCarrier Translator CONFIG Table's Device Type decision was set to 3(Generic). A sample GNRCMAP2 Table is shown below. An explana-tion of each decision, including LonWorks read/write access, LONVariable Type, along with an example CCN point name follows. Thedecision explanations and example point names below are taken from aCCN air handler. Keep in mind, however, that the generic controllerprofile can also be used with other types of CCN controllers.

CCN point names can consist of up to 8 characters. The default for eachdecision is blank.

Use these 2 decisions to specify the names of the analog CCN pointsthat the LON system will write to in order to set additional operatingparameters in percentage.

LON Variable Type SNVT_lev_percent

Read/Write Access Write

Example MIXDMixed Air Damper

nvoTEMPDIFF1 - 2

Generic MappingConfiguration(GNRCMAP2)Table 2

nviPCT1 - 2

nvoPRESS1 - 6

Page 48: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

41

Figure 3-7Generic Mapping 2Configuration (GNRCMAP2)Table

Page 49: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

42

Use these 4 decisions to specify the names of the analog CCN pointsthat the LON system can read in order to indicate additional air handleroperating parameters in percentage.

LON Variable Type SNVT_lev_percent

Read/Write Access Read

Example RFVCReturn Fan Volume Control

Use these 3 decisions to specify the names of the discrete CCN pointsthat the LON system can write to in order to set additional discreteoperating parameters.

LON Variable Type SNVT_switch

Read/Write Access Write

Example FLTSFilter Status

Use these 8 decisions to specify the names of the discrete CCN pointsthat the LON system can read in order to indicate additional discreteoperating parameters.

LON Variable Type SNVT_switch

Read/Write Access Read

Example FANS_1Fan 1 Relay

Use this decision to provide the name of the analog CCN point that theLON system can write to in order to set the occupied cooling setpoint.

LON Variable Type SNVT_temp_setpt

Read/Write Access Write

Example OCSPOccupied Cool Setpoint

Use this decision to provide the name of the analog CCN point that theLON system can write to in order to set the cooling setpoint in standbymode.

Note: Most CCN air handlers do not use this mode.

LON Variable Type SNVT_temp_setpt

Read/Write Access Write

nvoDISCRETE1 - 8

nciSetpnts.occupied_cool

nciSetpnts.standby_cool

nviDISCRETE1 - 3

nvoPCT1 - 4

Page 50: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

43

Use this decision to provide the name of the analog CCN point that theLON system can write to in order to set the unoccupied cooling setpoint.

LON Variable Type SNVT_temp_setpt

Read/Write Access Write

Example UCSPUnoccupied Cool Setpoint

Use this decision to provide the name of the analog CCN point that theLON system can write to in order to set the occupied heating setpoint.

LON Variable Type SNVT_temp_setpt

Read/Write Access Write

Example OHSPOccupied Heat Setpoint

Use this decision to provide the name of the analog CCN point that theLON system can write to in order to set the heating setpoint in standbymode.

Most CCN air handlers do not contain this point.

LON Variable Type SNVT_temp_setpt

Read/Write Access Write

Use this decision to specify the name of the analog CCN point that theLON system will write to in order to set an additional operating param-eter in PPM.

LON Variable Type SNVT_ppm

Read/Write Access Write

Example AQ1Air Quality 1 (ppm)

Use this decision to specify the name of the analog CCN point that theLON system will read in order to obtain an additional analog values inPPM.

LON Variable Type SNVT_ppm

Read/Write Access Read

Example AQ1Air Quality 1 (ppm)

nciSetpnts.standby_heat

nciSetpnts.occupied_heat

nviPPM1

nvoPPM1

nciSetpnts.unocc_cool

Page 51: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

44

Use this decision to specify the name of the analog or multi-state CCNpoint that the LON system will write to in order to set additional analogor multi-state operating parameters.

LON Variable Type SNVT_count

Read/Write Access Write

Example OASPOA cfm Setpoint

Use these 2 decisions to specify the names of the analog or multi-stateCCN points that the LON system will read in order to obtain additionalanalog or multi-state values.

LON Variable Type SNVT_count

Read/Write Access Read

Example OACFMOA Airflow

Use these 2 decisions to specify the names of the analog or multi-stateCCN points that the LON system will read in order to obtain additionalanalog or multi-state values.

LON Variable Type SNVT_count_inc

Read/Write Access Read

Example OACFMOA Airflow

nvoCOUNT1 - 2

nvoCOUNTinc1 - 2

nviCOUNT1

Page 52: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

Maintenance

Page 53: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

45

The Carrier Translator contains the maintenance tables listed below.

CHLRMNT1 Chiller Maintenance Table 1CHLRMNT2 Chiller Maintenance Table 2COMMSTAT Communication Status Maintenance TableGNRCMNT1 Generic Maintenance Table 1GNRCMNT2 Generic Maintnenance Table 2MESSAGES Messages Maintenance TableRTUMNT1 Rooftop Maintenance Table 1RTUMNT2 Rooftop Mainten ance Table 2

The maintenance values displayed in these tables are read-only valuesthat show the current value of the CCN points that have been mapped tothe Lonworks variables as the points exist in the CCN system element.These values are updated every 30 seconds. Note that if a LonWorksread (nvo) and write (nvi) variable have been mapped to the same CCNpoint, they will display the same value in the maintenance table display.

Figure 4-1 on the page which follows illustrates the Chiller Maintenance(CHLRMNT1) Table. An explanation of each value in the table follows.Note that the valid display ranges are dependent on the point.

Indicates the commanded state of the chiller (on or off).

Indicates the commanded value for the leaving chilled water temperaturesetpoint when the chiller is operating in cooling mode.

Indicates the chiller's current status (on/off ).

Note: Most CCN chillers do not contain this point.

Indicates the current value of the chiller's cooling or heating setpoint. Thesetpoint to be displayed (cooling or heating) depends on the chiller'scurrent operating mode.

Indicates the commanded value for the capacity limit of the chiller.

nviChillerEnable

ChillerMaintenance(CHLRMNT1)Table 1

nviCoolSetpt

nvoOnOff

nvoActiveSetpt

Maintenance

nviCapacityLim

Page 54: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

46

Figure 4-1Chiller Maintenance(CHLRMNT1)Table 1

Page 55: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

47

Indicates the commanded heating setpoint.

Indicates the current running capacity of the chiller.

Indicates the chiller's current capacity limit setpoint.

Indicates the leaving chilled water temperature.

Indicates the entering chilled water temperature.

Indicates the entering condenser water temperature.

Indicates the leaving condenser water temperature.

Indicates the main running mode of the chiller.

Note: Most CCN chillers do not contain this point.

Indicates the main operating status of the chiller.

Note: Most CCN chillers do not contain this point.

Indicates the alarm status of the chiller.

Note: Most CCN chillers do not contain this point.

Indicates the start or stop status of the chiller.

Indicates the chiller's local or network control status.

Note: Most CCN chillers do not contain this point.

Indicates if the chiller cannot reach setpoint.

Note: Most CCN chillers do not contain this point.

Indicates the presence of chilled water flow.

Indicates the presence of condenser water flow.

Indicates the next commanded occupancy state, as determined by theCCN global occupancy equipment table.

nviHeatSetpt

nvoActualCapacity

nvoCapacityLim

nvoLvgCNDWTemp

nvoEntCNDWTemp

nvoEntCHWTemp

nvoLvgCHWTemp

nvoChillerStat.run_mode

nvoChillerStat.op_mode

nvoChillerStat.in_alarm

nvoChillerStat.run_enabl

nvoChillerStat.Local

nvoChillerStat.Limited

nvoChillerStat.cndw_flow

nvoChillerStat.chw_flow

nviOccSchedule

Page 56: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

48

Figure 4-2 shown below illustrates the Chiller Maintenance(CHLRMNT2) Table. An explanation of each value in the table follows.Note that the valid display ranges are dependent on the point.

ChillerMaintenance(CHLMNT2) Table2

Figure 4-2Chiller Maintenance(CHLRMNT2)Table 2

Page 57: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

49

nviTEMP1

nvoPRESS1 - 4

nvoTEMP1 - 6

nviPRESS1

Indicates an additional chiller commanded operating temperature.

Indicates additional chiller operating temperatures.

Indicates an additional chiller commanded operating pressure.

Indicates additional chiller operating pressures.

Indicates additional chiller operating parameters in percentage.

Indicates additional chiller differential temperatures.

Indicates additional commanded discrete operating parameters.

Indicates additional discrete operating parameters.

Indicates chiller commanded analog or multi-state parameter.

Note: This point will always display in customary US units.

Indicate chiller analog or multi-state values.

Note: These points will always display in customary US units.

Indicate chiller analog or multi-state values.

Note: These points will always display in customary US units.

nvoPCT1 - 2

nvoTEMPDIFF1 - 2

nviDISCRETE1 - 2

nvoDISCRETE1 - 6

nviCOUNT1

nvoCOUNT1 - 2

nvoCOUNTinc1 - 2

Page 58: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

50

Figure 4-3 on the page which follows illustrates the Rooftop Maintenance(RTUMNT1) Table. The maintenance values displayed in this table areread-only values that show the current value of the CCN points that havebeen mapped to the Lonworks variables as the points exist in the CCNsystem element. These values are updated every 30 seconds. An expla-nation of each value in the table follows. Note that the valid displayranges are dependent on the point.

Indicates the commanded space temperature.

Indicates the commanded temperature setpoint.

Indicates the space temperature.

Indicates the rooftop's operating mode.

Note: Most CCN rooftops do not contain this point.

Indicates the current primary heat capacity in percent full scale.

Indicates the current secondary heat capacity in percent full scale.

Indicates the current cooling capacity in percent full scale.

Indicates the current economizer position in percent full scale.

Indicates the current fan speed in percent full scale.

Note: Most CCN rooftops do not contain this point.

Indicates the alarm status of the chiller.

Notes: Most CCN rooftops do not contain this point.

Indicates the next commanded occupancy state, as determined by theCCN global occupancy equipment table.

Indicates the commanded temperature setpoint offset.

Notes: Most CCN rooftops do not contain this point.Metric points will always assume ^T, even if the point ismapped to a temperature.

RooftopMaintenance(RTUMNT1)Table 1

nviSpaceTemp

nvoUnitStatus.mode

nvoSpaceTemp

nviSetPoint

nvoUnitStatus.heat_out_s

nvoUnitStatus.cool_out

nvoUnitStatus.econ_out

nvoUnitStatus.heat_out_p

nvoUnitStatus.fan_out

nvoUnitStatus.in_alarm

nviOccSchedule

nviSetptOffset

Page 59: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

51

Figure 4-3Rooftop Maintenance(RTUMNT1)Table 1

Page 60: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

52

Indicates the commanded outside air temperature.

Indicates the commanded outside air relative humidity.

Indicates the setpoint temperature.

Indicates the outside air temperature.

Indicates the outside air relative humidity.

Indicates the commanded space relative humidity.

Indicates the commanded CO2 level in ppm.

Indicates the commanded CO2 level in ppm.

Indicates an additional rooftop commanded operating temperature.

Indicate additional rooftop operating temperatures.

Indicates an additional rooftop commanded operating pressure.

Indicate additional rooftop operating pressures.

Figure 4-4 illustrates the Rooftop Maintenance (RTUMNT2) Table. Themaintenance values displayed in this table are read-only values that showthe current value of the CCN points that have been mapped to theLonworks variables as the points exist in the CCN system element.These values are updated every 30 seconds. An explanation of eachvalue in the table follows. Note that the valid display ranges are depen-dent on the point.

Indicate rooftop commanded parameters in percentage.

Indicate additional rooftop operating parameters in percentage.

Indicate additional rooftop differential temperatures.

Indicate additional discrete commanded operating parameters.

nvoEffectSetpt

nvoOutsideTemp

nvoOutsideRH

nviSpaceRH

nviCO2

nvoCO2

nviTEMP1

nvoTEMP1-4

RooftopMaintenance(RTUMNT2)Table 2

nviPRESS1

nvoPRESS1 - 2

nvoPCT1-3

nvoTEMPDIFF1 - 2

nviDISCRETE1 - 3

nviPCT1-2

nviOutsideTemp

nviOutsideRH

Page 61: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

53

Indicate additional discrete commanded operating parameters.

Indicates the commanded CO2 threshold value.

Indicates the commanded occupied cooling setpoint.

Indicates the commanded cooling setpoint in standby mode.

Note: Most CCN rooftops do not use this mode.

Indicates the commanded unoccupied cooling setpoint.

Indicates the commanded occupied heating setpoint.

Indicates the commanded heating setpoint in standby mode.

Note: Most CCN rooftops do not use this mode.

Indicates the commanded unoccupied heating setpoint.

Indicates a rooftop commanded analog or multi-state parameter.

Note: This point will always display in customary US units.

Indicate rooftop analog or multi-state values.

Note: These points will always display in customary US units.

Indicates rooftop analog or multi-state values.

Note: These points will always display in customary US units.

nciSetpnts.occupied_cool

nciSetpnts.standby_cool

nciSetpnts.unocc_cool

nciSetpnts.occupied_heat

nciSetpnts.standby_heat

nciSetpnts.unocc_heat

nviCOUNT1

nvoCOUNT1 - 2

nvoCOUNTinc1 - 2

nvoDISCRETE1 - 8

nciCO2Limit

Page 62: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

54

Figure 4-4Rooftop Maintenance(RTUMNT 2)Table 2

Page 63: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

55

Figure 4-5 on the page which follows illustrates the Generic Maintenance(GNRCMNT1) Table. The maintenance values displayed in this table areread-only values that show the current value of the CCN points that havebeen mapped to the Lonworks variables as the points exist in the CCNsystem element. These values are updated every 30 seconds. An expla-nation of each value in the table follows. Note that the valid displayranges are dependent on the point.

Indicates the controller's operating mode.

Note: Most CCN controllers do not contain this point.

Indicates thecurrent primary heat capacity in percent full scale.

Indicates the current secondary heat capacity in percent full scale.

Indicates the current cooling capacity in percent full scale.

Indicates the current economizer position in percent full scale.

Indicates the current fan speed in percent full scale.

Indicates the alarm status of the controller.

Note: Most CCN air handlers do not contain this point.

Indicates the next commanded occupancy state, as determined by theCCN global occupancy equipment table.

Indicates an additional controller commanded operating temperature.

Indicate additional controller operating temperatures.

Indicate additional controller commanded operating pressures.

Note: Most CCN controllers do not allow write access to this point.

Use these 6 decisions to specify the names of the analog CCN point thatwill indicate additional controller operating pressures.

Indicate additional controller differential temperatures.

Note: Most CCN air handlers do not contain this point.

GenericMaintenance(GNRCMNT1)Table 1

nvoUnitStatus.mode

nvoUnitStatus.heat_out_p

nvoUnitStatus.heat_out_s

nvoUnitStatus.cool_out

nvoUnitStatus.econ_out

nvoUnitStatus.fan_out

nvoUnitStatus.in_alarm

nviOccSchedule

nviTEMP1 - 3

nvoTEMP1 - 8

nviPRESS1 - 2

nvoTEMPDIFF1 - 2

nvoPRESS1 - 6

Page 64: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

56

Figure 4-3Generic Maintenance(GNRCMNT1)Table 1

Page 65: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

57

Figure 4-6 on the page which follows illustrates the Generic Maintenance(GNRCMNT2) Table. The maintenance values displayed in this table areread-only values that show the current value of the CCN points that havebeen mapped to the Lonworks variables as the points exist in the CCNsystem element. These values are updated every 30 seconds. An expla-nation of each value in the table follows. Note that the valid displayranges are dependent on the point.

Indicate additional controller commanded parameters in percentage.

Indicate additional controller operating parameters in percentage.

Indicate additional commanded discrete operating parameters.

Indicate additional discrete operating parameters.

Indicates the commanded occupied cooling setpoint.

Indicates the commanded cooling setpoint in standby mode.

Note: Most CCN controllers do not use this mode.

Indicates the commanded unoccupied cooling setpoint.

Indicates the commanded occupied heating setpoint.

Indicates the commanded heating setpoint in standby mode.

Note: Most CCN controllers do not contain this point.

Indicates a commanded parameter in PPM.

Indicates an analog value in PPM.

Indicates a commanded analog or multi-state parameter.

Note: This point will always display in customary US units.

Indicate analog or multi-state values.

Note: These points will always display in customary US units.

Indicate analog or multi-state values.

Note: These points will always display in customary US units.

Generic MappingMaintenance(GNRCMNT2)Table 2

nvoPCT1 - 4

nviDISCRETE1 - 3

nvoDISCRETE1 - 8

nciSetpnts.occupied_cool

nciSetpnts.standby_cool

nciSetpnts.unocc_cool

nciSetpnts.occupied_heat

nciSetpnts.standby_heat

nviPCT1 - 2

nviPPM

nvoPPM

nviCOUNT1

nvoCOUNT1 - 2

nvoCOUNTinc1 - 2

Page 66: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

58

Figure 4-6Generic Mapping 2Maintenance (GNRCMNT2)Table

Page 67: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

59

Figure 4-7 below illustrates the Communication Status Maintenance(COMMSTAT) Table. The maintenance values displayed in this tableare read-only values that show diagnostic data about LonWorks-to-CCN system element communication. These values are updated every 30seconds. An explanation of each value in the table follows.

Note: This information is primarily intended to be used by the Lonsystems integrator for troubleshooting.

CommunicationStatusMaintenance(COMMSTAT)TableFigure 4-7Communications StatusMaintenance (COMMSTAT)Table

Page 68: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

60

Num SuccessfulMessages

Num Failed Messages

Communication History1 - 4

CommunicationType

Successful?

Indicates the number of successful read, write, and other communicationmessages sent from LonWorks to the CCN system element. This value isa running total of the number of successful messages detected since thelast communication reset. It is not reset on cycling CARRIER TRANS-LATOR power. It can be reset, however, using the CONFIG Table'sReset Comm. Counters decision.

Valid Display 0 - 65,000

Indicates the number of unsuccessful read, write, and other communica-tion messages sent from LonWorks to the CCN system element. Thisvalue is a running total of the number of unsuccessful messages detectedsince the last communication reset. It is not reset on cycling power to theCarrier Translator. It can be reset, however, using the CONFIG Table'sReset Comm. Counters decision.

Valid Display 0 - 65,000

These 4 decisions display the below-listed data about the four mostrecent LonWorks-to-CCN communication messages.

Indicates the type of communication message.

Valid Display 1 = Read Network Variable2 = Write Network Variable3 = Other

Indicates whether or not this communication was successful.

Valid Display Yes/No

Page 69: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

61

Figure 4-8 below illustrates the Messages Maintenance (MESSAGES)Table. The maintenance values displayed in this table are read-onlyvalues that show diagnostic data about LonWorks-to-CCN systemelement communication messages. These values are updated every 30seconds. An explanation of each value in the table follows.

Note: This information is primarily intended to be used by the Lonsystems integrator for troubleshooting.

MessagesMaintenance(MESSAGES)Table

Figure 4-8Messages Maintenance(MESSAGES)Table

Page 70: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

62

LON Message 1 - 10 These 10 decisions display diagnostic information about the 10 mostrecent LonWorks-to-CCN communication messages.

Valid Display Self configurationRead all NVsPropagate NV#Set NV#Read NV#

where: NV = Network Variable# = Number of the NetworkVariable

The Propagate and Set commands both refer to writes to CCN points.Propagate indicates that the value has not changed, but the CarrierTranslator's 30 second refresh has caused Lonworks to write to theCCN point again. Set indicates that Lonworks has written a new value tothe CCN point.

Page 71: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

Appendix

Page 72: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

63

This section contains examples of actual configurations for a chiller,rooftop, and generic template, along with a list of LON SNVTs andcorresponding CCN point names and descriptions.

Appendix

Page 73: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

64

Figure A-2Sample Configuration forCHLRMAP1 Table

Job

Site

:LE

I Add

ress

:0,

211

Atta

ched

Dev

ice:

19XR

IIIA

ttach

ed D

evic

e Add

ress

:0,

1LO

N P

rofil

e:C

hille

r Pro

file

CHLR

MAP

1SN

VT T

ype

R

ead

CC

N P

oint

C

CN

Poi

nt

or W

rite?

Des

crip

tion

Nam

env

iChi

llerE

nabl

e...

......

......

......

.SN

VT_s

witc

hPO

INT0

1....

..W

......

......

......

......

Chi

ller S

tart/

Stop

......

......

......

......

......

...C

HIL

_S_S

nviC

oolS

etpt

......

......

......

......

...SN

VT_t

emp_

pPO

INT0

2....

..W

......

......

......

......

Leav

ing

Chi

lled

Wat

er C

ontro

l Poi

nt...

..LC

W_S

TPT

nvoO

nOff

......

......

......

......

......

..SN

VT_s

witc

hPO

INT0

3....

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oAct

iveSe

tpt.

......

......

......

....S

NVT

_tem

p_p

POIN

T04.

.....

R...

......

......

......

....L

eavi

ng C

hille

d W

ater

Con

trol P

oint

.....

LCW

_STP

Tnv

iCap

acity

Lim

......

......

......

.....

SNVT

_lev

_per

cent

POIN

T05.

.....

W...

......

......

......

...Ac

tive

Dem

and

Lim

it...

......

......

......

......

DEM

_LIM

nviH

eatS

etpt

......

......

......

......

...SN

VT_t

emp_

pPO

INT0

6....

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

oAct

ualC

apac

ity...

......

......

..SN

VT_l

ev_p

erce

ntPO

INT0

7....

..R

......

......

......

......

.Mot

or P

erce

nt K

ilow

atts

......

......

......

....K

W_P

nvoC

apac

ityLi

m...

......

......

......

.SN

VT_l

ev_p

erce

ntPO

INT0

8....

..R

......

......

......

......

.Act

ive

Dem

and

Lim

it...

......

......

......

......

DEM

_LIM

nvoL

vgCH

WTe

mp

......

......

......

.SN

VT_t

emp_

pPO

INT0

9....

..R

......

......

......

......

.Lea

ving

Chi

lled W

ater

......

......

......

......

..LC

Wnv

oEnt

CH

WTe

mp

......

......

......

.SN

VT_t

emp_

pPO

INT1

0....

..R

......

......

......

......

.Ent

erin

g C

hille

d W

ater

......

......

......

......

.EC

Wnv

oEnt

CN

DW

Tem

p...

......

......

.SN

VT_t

emp_

pPO

INT1

1....

..R

......

......

......

......

.Ent

erin

g C

onde

nser

Wat

er...

......

......

...EC

DW

nvoL

vgCN

DWTe

mp

......

......

.....

SNVT

_tem

p_p

POIN

T12.

.....

R...

......

......

......

....L

eavi

ng C

onde

nser

Wat

er...

......

......

.....

LCD

Wnv

oChi

llerS

tat.r

un_m

ode

......

...SN

VT_c

hlr_

stat

usPO

INT1

3....

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oChi

llerS

tat.o

p_m

ode

......

....S

NVT

_chl

r_st

atus

POIN

T14.

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoC

hille

rSta

t.in_

alar

m...

......

..SN

VT_c

hlr_

stat

usPO

INT1

5....

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oChi

llerS

tat.r

un_e

nabl

......

...SN

VT_c

hlr_

stat

usPO

INT1

6....

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oChi

llerS

tat.L

ocal

......

......

....S

NVT

_chl

r_st

atus

POIN

T17.

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoC

hille

rSta

t.Lim

ited

......

......

.SN

VT_c

hlr_

stat

usPO

INT1

8....

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oChi

llerS

tat.c

hw_f

low

......

....S

NVT

_chl

r_st

atus

POIN

T19.

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoC

hille

rSta

t.cnd

w_f

low

......

..SN

VT_c

hlr_

stat

usPO

INT2

0....

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

iOcc

Sche

dule

......

......

......

...SN

VT_o

ccup

ancy

POIN

T21.

.....

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

Page 74: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

65

Figure A-2Sample Configuration forCHLRMAP2 Table

CHLR

MAP

2SN

VT T

ype

Rea

d or

Writ

e?C

CN

Poi

nt D

escr

iptio

nC

CN

Poi

nt N

ame

nviT

EMP1

......

......

......

......

......

.SN

VT_t

emp_

pPO

INT2

2...

...W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

oTEM

P1...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

3...

...R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oTEM

P2...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

4...

...R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oTEM

P3...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

5...

...R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oTEM

P4...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

6...

...R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oTEM

P5...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

7...

...R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oTEM

P6...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

8...

...R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

iPR

ESS1

......

......

......

......

....S

NVT

_pre

ssPO

INT2

9...

...W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

oPR

ESS1

......

......

......

......

...SN

VT_p

ress

POIN

T30

......

R...

......

......

......

....E

vapo

rato

r Ref

rig P

ress

ure

......

......

......

ERP

nvoP

RES

S2...

......

......

......

......

SNVT

_pre

ssPO

INT3

1...

...R

......

......

......

......

.Con

dens

er R

efrig

Pre

ssur

e...

......

......

...CR

Pnv

oPR

ESS3

......

......

......

......

...SN

VT_p

ress

POIN

T32

......

R...

......

......

......

....O

il Pu

mp

Del

ta P

......

......

......

......

......

..O

ILPD

nvoP

RES

S4...

......

......

......

......

SNVT

_pre

ssPO

INT3

3...

...R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oPCT

1...

......

......

......

......

.....S

NVT

_lev

_per

cent

POIN

T34

......

R...

......

......

......

....A

vera

ge Li

ne C

urre

nt...

......

......

......

......

AMPS

_%nv

oPCT

2...

......

......

......

......

.....S

NVT

_lev

_per

cent

POIN

T35

......

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoT

EMPD

IFF1

......

......

......

....S

NVT

_tem

p_di

ff_p

POIN

T36

......

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoT

EMPD

IFF2

......

......

......

....S

NVT

_tem

p_di

ff_p

POIN

T37

......

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nviD

ISC

RET

E1...

......

......

......

..SN

VT_s

witc

hPO

INT3

8...

...W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

iDIS

CR

ETE2

......

......

......

.....S

NVT

_sw

itch

POIN

T39

......

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nvoD

ISCR

ETE1

......

......

......

....S

NVT

_sw

itch

POIN

T40

......

R...

......

......

......

....C

hille

r Sta

rt/St

op...

......

......

......

......

......

CH

IL_S

_Snv

oDIS

CRET

E2...

......

......

......

.SN

VT_s

witc

hPO

INT4

1...

...R

......

......

......

......

.Chi

lled

Wat

er F

low

Sta

tus

......

......

......

.CH

W_F

LOW

nvoD

ISCR

ETE3

......

......

......

....S

NVT

_sw

itch

POIN

T42

......

R...

......

......

......

....C

onde

nser

Wat

er F

low

Sta

tus.

......

......

CD

W_F

LOW

nvoD

ISCR

ETE4

......

......

......

....S

NVT

_sw

itch

POIN

T43

......

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoD

ISCR

ETE5

......

......

......

....S

NVT

_sw

itch

POIN

T44

......

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoD

ISCR

ETE6

......

......

......

....S

NVT

_sw

itch

POIN

T45

......

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nviC

OUN

T1...

......

......

......

......

.SN

VT_c

ount

POIN

T46

......

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nvoC

OUN

T1...

......

......

......

......

SNVT

_cou

ntPO

INT4

7...

...R

......

......

......

......

.Con

trol M

ode

......

......

......

......

......

......

...M

OD

Env

oCO

UNT2

......

......

......

......

...SN

VT_c

ount

POIN

T48

......

R...

......

......

......

....R

un S

tatu

s...

......

......

......

......

......

......

...ST

ATU

Snv

oCO

UNTi

nc1

......

......

......

.....S

NVT

_cou

nt_i

ncPO

INT4

9...

...R

......

......

......

......

.Sys

tem

Ala

rm/A

lert

......

......

......

......

.....

SYS_

ALM

nvoC

OUN

Tinc

2...

......

......

......

..SN

VT_c

ount

_inc

POIN

T50

......

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

Page 75: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

66

Figure A-3CHLRMAP1 Table SNVTsand CCN Points

LEI A

ddre

ss:

Atta

ched

Dev

ice:

Atta

ched

Dev

ice A

ddre

ss:

LON

Pro

file:

(NA)

Mea

ns n

ot g

ener

ally

app

licab

le to

CC

N

CHLR

MAP

1...

......

......

......

......

SNVT

Typ

eR

ead

or W

rite?

..C

CN

Poi

nt D

escr

iptio

nnv

iChi

llerE

nabl

e...

......

......

......

.SN

VT_s

witc

hPO

INT0

1W

......

......

......

......

Chi

ller S

tart/

Stop

(1/0

)nv

iCoo

lSet

pt...

......

......

......

......

SNVT

_tem

p_p

POIN

T02

W...

......

......

......

...C

hille

d W

ater

Con

trol T

emp

(deg

F)nv

oOnO

ff...

......

......

......

......

.....

SNVT

_sw

itch

POIN

T03

R...

......

......

......

....C

hille

r On/

Off

(1/0

) (N

A)nv

oAct

iveSe

tpt.

......

......

......

....S

NVT

_tem

p_p

POIN

T04

R...

......

......

......

....C

hille

d W

ater

Con

trol T

emp

(deg

F)nv

iCap

acity

Lim

......

......

......

.....

SNVT

_lev

_per

cent

POIN

T05

W...

......

......

......

...Ac

tive

Dem

and

Lim

it (%

)nv

iHea

tSet

pt...

......

......

......

......

SNVT

_tem

p_p

POIN

T06

W...

......

......

......

...H

ot W

ater

Con

trol T

emp

(deg

F)nv

oAct

ualC

apac

ity...

......

......

..SN

VT_l

ev_p

erce

ntPO

INT0

7R

......

......

......

......

.Pec

ent C

apac

ity (%

)nv

oCap

acity

Lim

......

......

......

....S

NVT

_lev

_per

cent

POIN

T08

R...

......

......

......

....A

ctiv

e D

eman

d Li

mit

(%)

nvoL

vgCH

WTe

mp

......

......

......

.SN

VT_t

emp_

pPO

INT0

9R

......

......

......

......

.Lea

ving

Chi

lled

Wat

er T

emp

(deg

F)nv

oEnt

CH

WTe

mp

......

......

......

.SN

VT_t

emp_

pPO

INT1

0R

......

......

......

......

.Ent

erin

g C

hille

d W

ater

Tem

p (d

egF)

nvoE

ntC

ND

WTe

mp

......

......

....S

NVT

_tem

p_p

POIN

T11

R...

......

......

......

....L

eavi

ng C

ond

Wat

er T

emp

(deg

F)nv

oLvg

CNDW

Tem

p...

......

......

..SN

VT_t

emp_

pPO

INT1

2R

......

......

......

......

.Ent

erin

g C

ond

Wat

er T

emp

(deg

F)nv

oChi

llerS

tat.r

un_m

ode

......

...SN

VT_c

hlr_

stat

usPO

INT1

3R

......

......

......

......

.(N

A)nv

oChi

llerS

tat.o

p_m

ode

......

....S

NVT

_chl

r_st

atus

POIN

T14

R...

......

......

......

....(

NA)

nvoC

hille

rSta

t.in_

alar

m...

......

..SN

VT_c

hlr_

stat

usPO

INT1

5R

......

......

......

......

.Chi

ller I

n Al

arm

(1/0

) (N

A)nv

oChi

llerS

tat.r

un_e

nabl

......

...SN

VT_c

hlr_

stat

usPO

INT1

6R

......

......

......

......

.Chi

ller R

un E

nabl

ed (1

/0) (

NA)

nvoC

hille

rSta

t.Loc

al...

......

......

.SN

VT_c

hlr_

stat

usPO

INT1

7R

......

......

......

......

.Chi

ller L

ocal

Ena

bled

(1/0

) (N

A)nv

oChi

llerS

tat.L

imite

d...

......

....S

NVT

_chl

r_st

atus

POIN

T18

R...

......

......

......

....C

hille

r Dem

and

Lim

ited

(1/0

) (N

A)nv

oChi

llerS

tat.c

hw_f

low

......

....S

NVT

_chl

r_st

atus

POIN

T19

R...

......

......

......

....C

hille

d W

ater

Flo

w D

etec

ted

(1/0

)nv

oChi

llerS

tat.c

ndw

_flo

w...

.....

SNVT

_chl

r_st

atus

POIN

T20

R...

......

......

......

....C

ond

Wat

er F

low

Det

ecte

d (1

/0)

nviO

ccSc

hedu

le...

......

......

......

SNVT

_occ

upan

cyPO

INT2

1W

......

......

......

......

Glo

bal C

CN

Occ

upan

cy (>

64)

Page 76: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

67

Figure A-4CHLRMAP2Table SNVTsand CCN Points

CHLR

MAP

2SN

VT T

ype

Rea

d or

Writ

e?C

CN

Poi

nt D

escr

iptio

nnv

iTEM

P1...

......

......

......

......

....S

NVT

_tem

p_p

POIN

T22

......

W...

......

......

......

....T

empe

ratu

re (d

egF)

nvoT

EMP1

......

......

......

......

......

SNVT

_tem

p_p

POIN

T23

......

R...

......

......

......

.....

Tem

pera

ture

(deg

F)nv

oTEM

P2...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

4...

...R

......

......

......

......

..Te

mpe

ratu

re (d

egF)

nvoT

EMP3

......

......

......

......

......

SNVT

_tem

p_p

POIN

T25

......

R...

......

......

......

.....

Tem

pera

ture

(deg

F)nv

oTEM

P4...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

6...

...R

......

......

......

......

..Te

mpe

ratu

re (d

egF)

nvoT

EMP5

......

......

......

......

......

SNVT

_tem

p_p

POIN

T27

......

R...

......

......

......

.....

Tem

pera

ture

(deg

F)nv

oTEM

P6...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

8...

...R

......

......

......

......

..Te

mpe

ratu

re (d

egF)

nviP

RES

S1...

......

......

......

......

.SN

VT_p

ress

POIN

T29

......

W...

......

......

......

....P

ress

ure

(PSI

)nv

oPR

ESS1

......

......

......

......

...SN

VT_p

ress

POIN

T30

......

R...

......

......

......

.....

Pres

sure

(PSI

)nv

oPR

ESS2

......

......

......

......

...SN

VT_p

ress

POIN

T31

......

R...

......

......

......

.....

Pres

sure

(PSI

)nv

oPR

ESS3

......

......

......

......

...SN

VT_p

ress

POIN

T32

......

R...

......

......

......

.....

Pres

sure

(PSI

)nv

oPR

ESS4

......

......

......

......

...SN

VT_p

ress

POIN

T33

......

R...

......

......

......

.....

Pres

sure

(PSI

)nv

oPCT

1...

......

......

......

......

.....S

NVT

_lev

_per

cent

POIN

T34

......

R...

......

......

......

.....

Perc

ent (

%)

nvoP

CT2

......

......

......

......

......

..SN

VT_l

ev_p

erce

ntPO

INT3

5...

...R

......

......

......

......

..Pe

rcen

t (%

)nv

oTEM

PDIF

F1...

......

......

......

.SN

VT_t

emp_

diff_

pPO

INT3

6...

...R

......

......

......

......

..D

elta

Tem

pera

ture

(^F)

nvoT

EMPD

IFF2

......

......

......

....S

NVT

_tem

p_di

ff_p

POIN

T37

......

R...

......

......

......

.....

Del

ta T

empe

ratu

re (^

F)nv

iDIS

CR

ETE1

......

......

......

.....S

NVT

_sw

itch

POIN

T38

......

W...

......

......

......

....D

iscr

ete

(1/0

)nv

iDIS

CR

ETE2

......

......

......

.....S

NVT

_sw

itch

POIN

T39

......

W...

......

......

......

....D

iscr

ete

(1/0

)nv

oDIS

CRET

E1...

......

......

......

.SN

VT_s

witc

hPO

INT4

0...

...R

......

......

......

......

..D

iscr

ete

(1/0

)nv

oDIS

CRET

E2...

......

......

......

.SN

VT_s

witc

hPO

INT4

1...

...R

......

......

......

......

..D

iscr

ete

(1/0

)nv

oDIS

CRET

E3...

......

......

......

.SN

VT_s

witc

hPO

INT4

2...

...R

......

......

......

......

..D

iscr

ete

(1/0

)nv

oDIS

CRET

E4...

......

......

......

.SN

VT_s

witc

hPO

INT4

3...

...R

......

......

......

......

..D

iscr

ete

(1/0

)nv

oDIS

CRET

E5...

......

......

......

.SN

VT_s

witc

hPO

INT4

4...

...R

......

......

......

......

..D

iscr

ete

(1/0

)nv

oDIS

CRET

E6...

......

......

......

.SN

VT_s

witc

hPO

INT4

5...

...R

......

......

......

......

..D

iscr

ete

(1/0

)nv

iCO

UNT1

......

......

......

......

....S

NVT

_cou

ntPO

INT4

6...

...W

......

......

......

......

.Gen

eric

ana

log

or d

iscr

ete

(0-6

5535

)nv

oCO

UNT1

......

......

......

......

...SN

VT_c

ount

POIN

T47

......

R...

......

......

......

.....

Gen

eric

ana

log

or d

iscr

ete

(0-6

5535

)nv

oCO

UNT2

......

......

......

......

...SN

VT_c

ount

POIN

T48

......

R...

......

......

......

.....

Gen

eric

ana

log

or d

iscr

ete

(0-6

5535

)nv

oCO

UNTi

nc1

......

......

......

.....S

NVT

_cou

nt_i

ncPO

INT4

9...

...R

......

......

......

......

..G

ener

ic a

nalo

g or

dis

cret

e (-3

2767

- 327

67)

nvoC

OUN

Tinc

2...

......

......

......

..SN

VT_c

ount

_inc

POIN

T50

......

R...

......

......

......

.....

Gen

eric

ana

log

or d

iscr

ete

(-327

67 - 3

2767

)

Page 77: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

68

Figure A-5Sample Configuration forRTUMAP1 Table

Job

Site

:LE

I Add

ress

:0,

204

Atta

ched

Dev

ice:

48H

G C

entu

rian

Atta

ched

Dev

ice A

ddre

ss:

0, 1

LON

Pro

file:

Roo

ftop

RTUM

AP1

SNVT

Typ

eR

ead

or W

rite?

CC

N P

oint

Des

crip

tion

CC

N P

oint

Nam

env

iSpa

ceTe

mp

......

......

......

......

SNVT

_tem

p_p

POIN

T01

.....

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nviS

etPo

int.

......

......

......

......

....S

NVT

_tem

p_p

POIN

T02

.....

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nvoS

pace

Tem

p....

......

......

......

.SN

VT_t

emp_

pPO

INT0

3...

..R

......

......

......

......

.Spa

ce T

empe

ratu

re...

......

......

......

......

..SP

Tnv

oUni

tSta

tus.

mod

e...

......

......

SNVT

_hva

c_st

atus

POIN

T04

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoU

nitS

tatu

s.he

at_o

ut_p

......

SNVT

_hva

c_st

atus

POIN

T05

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoU

nitS

tatu

s.he

at_o

ut_s

......

SNVT

_hva

c_st

atus

POIN

T06

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoU

nitS

tatu

s.co

ol_o

ut...

......

..SN

VT_h

vac_

stat

usPO

INT0

7...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oUni

tSta

tus.

econ

_out

......

...SN

VT_h

vac_

stat

usPO

INT0

8...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oUni

tSta

tus.

fan_

out.

......

.....

SNVT

_hva

c_st

atus

POIN

T09

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoU

nitS

tatu

s.in

_ala

rm...

......

..SN

VT_h

vac_

stat

usPO

INT1

0...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

iOcc

Sche

dule

......

......

......

...SN

VT_o

ccup

ancy

POIN

T11

.....

W...

......

......

......

...O

ccup

ancy

Sch

edul

e...

......

......

......

.....

OC

CPC

65E

nviS

etPt

Offs

et...

......

......

......

...SN

VT_t

emp_

pPO

INT1

2...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

iOut

sideT

emp

......

......

......

...SN

VT_t

emp_

pPO

INT1

3...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

iOut

sideR

H...

......

......

......

....S

NVT

_lev

_per

cent

POIN

T14

.....

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nvoE

ffect

Setp

t....

......

......

......

..SN

VT_t

emp_

pPO

INT1

5...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oOut

sideT

emp

......

......

......

..SN

VT_t

emp_

pPO

INT1

6...

..R

......

......

......

......

.Out

door

Air T

empe

ratu

re...

......

......

......

OAT

nvoO

utsid

eRH

......

......

......

......

SNVT

_lev

_per

cent

POIN

T17

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nviS

pace

RH

......

......

......

......

...SN

VT_l

ev_p

erce

ntPO

INT1

8...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

iCO

2...

......

......

......

......

......

..SN

VT_p

pmPO

INT1

9...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

oCO

2...

......

......

......

......

......

.SN

VT_p

pmPO

INT2

0...

..R

......

......

......

......

.Ind

oor A

ir C

O2

Leve

l....

......

......

......

......

IAQ

nviT

EMP1

......

......

......

......

......

.SN

VT_t

emp_

pPO

INT2

1...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

oTEM

P1...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

2...

..R

......

......

......

......

.Sup

ply A

ir Te

mpe

ratu

re...

......

......

......

..SA

Tnv

oTEM

P2...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

3...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oTEM

P3...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

4...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oTEM

P4...

......

......

......

......

...SN

VT_t

emp_

pPO

INT2

5...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

iPR

ESS1

......

......

......

......

....S

NVT

_pre

ss_p

POIN

T26

.....

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nvoP

RES

S1...

......

......

......

......

SNVT

_pre

ss_p

POIN

T27

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoP

RES

S2...

......

......

......

......

SNVT

_pre

ss_p

POIN

T28

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

Page 78: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

69

Figure A-6Sample Configurationfor RTUMAP2 Table

RTUM

AP2

SNVT

Typ

eR

ead

or W

rite?

CC

N P

oint

Des

crip

tion

CC

N P

oint

Nam

env

iPCT

1SN

VT_l

ev_p

erce

ntPO

INT2

9W

nviP

CT2.

......

......

......

......

......

...SN

VT_l

ev_p

erce

ntPO

INT3

0...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

oPCT

1...

......

......

......

......

.....S

NVT

_lev

_per

cent

POIN

T31

.....

R...

......

......

......

....E

cono

miz

er P

ositi

on...

......

......

......

......

ECO

NO

POS

nvoP

CT2

......

......

......

......

......

..SN

VT_l

ev_p

erce

ntPO

INT3

2...

..R

......

......

......

......

.Eco

nom

izer

Min

. Pos

ition

in E

ffect

......

MIN

_PO

Snv

oPCT

3...

......

......

......

......

.....S

NVT

_lev

_per

cent

POIN

T33

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoT

EMPD

IFF1

......

......

......

....S

NVT

_tem

p_di

ff_p

POIN

T34

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoT

EMPD

IFF2

......

......

......

....S

NVT

_tem

p_di

ff_p

POIN

T35

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nviD

ISC

RET

E1...

......

......

......

..SN

VT_s

witc

hPO

INT3

6...

..W

......

......

......

......

Cur

rent

ly O

ccup

ied

......

......

......

......

......

OC

CU

PIED

nviD

ISC

RET

E2...

......

......

......

..SN

VT_s

witc

hPO

INT3

7...

..W

......

......

......

......

Uni

t Shu

tdow

n In

put.

......

......

......

......

FIRE

DOW

Nnv

iDIS

CR

ETE3

......

......

......

.....S

NVT

_sw

itch

POIN

T38

.....

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nvoD

ISCR

ETE1

......

......

......

....S

NVT

_sw

itch

POIN

T39

.....

R...

......

......

......

....C

urre

ntly

Occ

upie

d...

......

......

......

......

...O

CC

UPI

EDnv

oDIS

CRET

E2...

......

......

......

.SN

VT_s

witc

hPO

INT4

0...

..R

......

......

......

......

.Sup

ply

Fan

Stat

us...

......

......

......

......

...FA

N_S

TAT

nvoD

ISCR

ETE3

......

......

......

....S

NVT

_sw

itch

POIN

T41

.....

R...

......

......

......

....H

eatin

g St

age

1...

......

......

......

......

......

.HEA

T_1

nvoD

ISCR

ETE4

......

......

......

....S

NVT

_sw

itch

POIN

T42

.....

R...

......

......

......

....H

eatin

g St

age

2...

......

......

......

......

......

.HEA

T_2

nvoD

ISCR

ETE5

......

......

......

....S

NVT

_sw

itch

POIN

T43

.....

R...

......

......

......

....C

ompr

esso

r A1

......

......

......

......

......

.....

CO

MP_

A1nv

oDIS

CRET

E6...

......

......

......

.SN

VT_s

witc

hPO

INT4

4...

..R

......

......

......

......

.Com

pres

sor B

1...

......

......

......

......

......

..C

OM

P_B1

nvoD

ISCR

ETE7

......

......

......

....S

NVT

_sw

itch

POIN

T45

.....

R...

......

......

......

....C

ompr

esso

r C1

......

......

......

......

......

.....

CO

MP_

C1

nvoD

ISCR

ETE8

......

......

......

....S

NVT

_sw

itch

POIN

T46

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nciC

O2L

imit

......

......

......

......

...SN

VT_p

pmPO

INT4

7...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nc

iSet

Pnts

.occ

upie

d_co

ol...

...SN

VT_t

emp_

setp

tPO

INT4

8...

..W

......

......

......

......

Occ

upie

d C

oolin

g Se

tpoi

nt...

......

......

...O

CSP

nciS

etPn

ts.s

tand

by_c

ool.

......

SNVT

_tem

p_se

tpt

POIN

T49

.....

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nciS

etPn

ts.u

nocc

_coo

l....

......

SNVT

_tem

p_se

tpt

POIN

T50

.....

W...

......

......

......

...U

nocc

upie

d C

oolin

g Se

tpoi

nt...

......

......

UC

SPnc

iSet

Pnts

.occ

upie

d_he

at...

..SN

VT_t

emp_

setp

tPO

INT5

1...

..W

......

......

......

......

Occ

upie

d H

eatin

g Se

tpoi

nt...

......

......

...O

HSP

nciS

etPn

ts.s

tand

by_h

eat.

......

SNVT

_tem

p_se

tpt

POIN

T52

.....

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nciS

etPn

ts.u

nocc

_hea

t....

......

SNVT

_tem

p_se

tpt

POIN

T53

.....

W...

......

......

......

...U

nocc

upie

d H

eatin

g Se

tpoi

nt...

......

.....

UH

SPnv

iCO

UNT1

......

......

......

......

....S

NVT

_cou

ntPO

INT5

4...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

oCO

UNT1

......

......

......

......

...SN

VT_c

ount

POIN

T55

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoC

OUN

T2...

......

......

......

......

SNVT

_cou

ntPO

INT5

6...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oCO

UNTi

nc1

......

......

......

.....S

NVT

_cou

nt_i

ncPO

INT5

7...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oCO

UNTi

nc2

......

......

......

.....S

NVT

_cou

nt_i

ncPO

INT5

8...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..

Page 79: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

70

Figure A-7RTUMAP1 Table SNVTs andCCN Points

Job

Site

:LE

I Add

ress

:A

ttach

ed D

evic

e:A

ttach

ed D

evic

e Add

ress

:LO

N P

rofil

e:(N

A) M

eans

not

gen

eral

ly a

pplic

able

to C

CN

RTUM

AP1

SNVT

Typ

eR

ead

or W

rite?

CC

N P

oint

Des

crip

tion

nviS

pace

Tem

p...

......

......

......

..SN

VT_t

emp_

pPO

INT0

1...

....W

......

......

......

......

Spac

e Tem

pera

ture

(deg

F)nv

iSet

Poin

t....

......

......

......

......

SNVT

_tem

p_p

POIN

T02

......

.W...

......

......

......

...Su

pply

Air

Setp

oint

on

VAV

units

(deg

F)nv

oSpa

ceTe

mp.

......

......

......

...SN

VT_t

emp_

pPO

INT0

3...

....R

......

......

......

......

.Spa

ce T

empe

ratu

re (d

egF)

nvoU

nitS

tatu

s.m

ode

......

......

..SN

VT_h

vac_

stat

usPO

INT0

4...

....R

......

......

......

......

.(N

A)nv

oUni

tSta

tus.

heat

_out

_p...

..SN

VT_h

vac_

stat

usPO

INT0

5...

....R

......

......

......

......

.Hea

ting

Coi

l Val

ve (%

)nv

oUni

tSta

tus.

heat

_out

_s...

..SN

VT_h

vac_

stat

usPO

INT0

6...

....R

......

......

......

......

.Sec

onda

ry H

eatin

g C

oil V

alve

(%) (

NA)

nvoU

nitS

tatu

s.co

ol_o

ut...

......

.SN

VT_h

vac_

stat

usPO

INT0

7...

....R

......

......

......

......

.Coo

ling

Coi

l Val

ve (%

)nv

oUni

tSta

tus.

econ

_out

......

..SN

VT_h

vac_

stat

usPO

INT0

8...

....R

......

......

......

......

.Eco

nom

izer

(%)

nvoU

nitS

tatu

s.fa

n_ou

t....

......

.SN

VT_h

vac_

stat

usPO

INT0

9...

....R

......

......

......

......

.Fan

Spe

ed (%

)nv

oUni

tSta

tus.

in_a

larm

......

....S

NVT

_hva

c_st

atus

POIN

T10

......

.R...

......

......

......

....D

iscr

ete

Alar

m p

oint

(1/0

)nv

iOcc

Sche

dule

......

......

......

..SN

VT_o

ccup

ancy

POIN

T11

......

.W...

......

......

......

...G

loba

l CC

N O

ccup

ancy

(>64

)nv

iSet

PtO

ffset

......

......

......

.....

SNVT

_tem

p_p

POIN

T12

......

.W...

......

......

......

...Te

mpe

ratu

re (d

egF)

nviO

utsid

eTem

p...

......

......

.....

SNVT

_tem

p_p

POIN

T13

......

.W...

......

......

......

...O

utdo

or A

ir Tem

pera

ture

(deg

F)nv

iOut

sideR

H...

......

......

......

...SN

VT_l

ev_p

erce

ntPO

INT1

4...

....W

......

......

......

......

Out

door

Air

RH

(%)

nvoE

ffect

Setp

t....

......

......

......

.SN

VT_t

emp_

pPO

INT1

5...

....R

......

......

......

......

.Con

trollin

g Se

tpoi

nt (d

egF)

nvoO

utsid

eTem

p...

......

......

....S

NVT

_tem

p_p

POIN

T16

......

.R...

......

......

......

....O

utdo

or A

ir Tem

pera

ture

(deg

F)nv

oOut

sideR

H...

......

......

......

..SN

VT_l

ev_p

erce

ntPO

INT1

7...

....R

......

......

......

......

.Out

door

Air

RH

(%)

nviS

pace

RH

......

......

......

......

..SN

VT_l

ev_p

erce

ntPO

INT1

8...

....W

......

......

......

......

Spac

e R

H (%

)nv

iCO

2...

......

......

......

......

......

.SN

VT_p

pmPO

INT1

9...

....W

......

......

......

......

IAQ

(PPM

)nv

oCO

2...

......

......

......

......

......

SNVT

_ppm

POIN

T20

......

.R...

......

......

......

....I

AQ (P

PM)

nviT

EMP1

......

......

......

......

......

SNVT

_tem

p_p

POIN

T21

......

.W...

......

......

......

...Te

mpe

ratu

re (d

egF)

nvoT

EMP1

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T22

......

.R...

......

......

......

....T

empe

ratu

re (d

egF)

nvoT

EMP2

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T23

......

.R...

......

......

......

....T

empe

ratu

re (d

egF)

nvoT

EMP3

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T24

......

.R...

......

......

......

....T

empe

ratu

re (d

egF)

nvoT

EMP4

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T25

......

.R...

......

......

......

....T

empe

ratu

re (d

egF)

nviP

RES

S1...

......

......

......

......

SNVT

_pre

ss_p

POIN

T26

......

.W...

......

......

......

...Pr

essu

re (“

H2O

)nv

oPR

ESS1

......

......

......

......

..SN

VT_p

ress

_pPO

INT2

7...

....R

......

......

......

......

.Pre

ssur

e (“H

2O)

nvoP

RES

S2...

......

......

......

.....

SNVT

_pre

ss_p

POIN

T28

......

.R...

......

......

......

....P

ress

ure (

“H2O

)

Page 80: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

71

Figure A-8RTUMAP2 Table SNVTs andCCN Points

RTUM

AP2

SNVT

Typ

eR

ead

or W

rite?

CC

N P

oint

Des

crip

tion

nviP

CT1.

......

......

......

......

......

..SN

VT_l

ev_p

erce

ntPO

INT2

9...

....W

......

......

......

......

Perc

ent (

%)

nviP

CT2.

......

......

......

......

......

..SN

VT_l

ev_p

erce

ntPO

INT3

0...

....W

......

......

......

......

Perc

ent (

%)

nvoP

CT1

......

......

......

......

......

.SN

VT_l

ev_p

erce

ntPO

INT3

1...

....R

......

......

......

......

.Per

cent

(%)

nvoP

CT2

......

......

......

......

......

.SN

VT_l

ev_p

erce

ntPO

INT3

2...

....R

......

......

......

......

.Per

cent

(%)

nvoP

CT3

......

......

......

......

......

.SN

VT_l

ev_p

erce

ntPO

INT3

3...

....R

......

......

......

......

.Per

cent

(%)

nvoT

EMPD

IFF1

......

......

......

...SN

VT_t

emp_

diff_

pPO

INT3

4...

....R

......

......

......

......

.Del

ta T

empe

ratu

re (^

F)nv

oTEM

PDIF

F2...

......

......

......

SNVT

_tem

p_di

ff_p

POIN

T35

......

.R...

......

......

......

....D

elta

Tem

pera

ture

(^F)

nviD

ISC

RET

E1...

......

......

......

.SN

VT_s

witc

hPO

INT3

6...

....W

......

......

......

......

Dis

cret

e (1

/0)

nviD

ISC

RET

E2...

......

......

......

.SN

VT_s

witc

hPO

INT3

7...

....W

......

......

......

......

Dis

cret

e (1

/0)

nviD

ISC

RET

E3...

......

......

......

.SN

VT_s

witc

hPO

INT3

8...

....W

......

......

......

......

Dis

cret

e (1

/0)

nvoD

ISCR

ETE1

......

......

......

...SN

VT_s

witc

hPO

INT3

9...

....R

......

......

......

......

.Dis

cret

e (1

/0)

nvoD

ISCR

ETE2

......

......

......

...SN

VT_s

witc

hPO

INT4

0...

....R

......

......

......

......

.Dis

cret

e (1

/0)

nvoD

ISCR

ETE3

......

......

......

...SN

VT_s

witc

hPO

INT4

1...

....R

......

......

......

......

.Dis

cret

e (1

/0)

nvoD

ISCR

ETE4

......

......

......

...SN

VT_s

witc

hPO

INT4

2...

....R

......

......

......

......

.Dis

cret

e (1

/0)

nvoD

ISCR

ETE5

......

......

......

...SN

VT_s

witc

hPO

INT4

3...

....R

......

......

......

......

.Dis

cret

e (1

/0)

nvoD

ISCR

ETE6

......

......

......

...SN

VT_s

witc

hPO

INT4

4...

....R

......

......

......

......

.Dis

cret

e (1

/0)

nvoD

ISCR

ETE7

......

......

......

...SN

VT_s

witc

hPO

INT4

5...

....R

......

......

......

......

.Dis

cret

e (1

/0)

nvoD

ISCR

ETE8

......

......

......

...SN

VT_s

witc

hPO

INT4

6...

....R

......

......

......

......

.Dis

cret

e (1

/0)

nciC

O2L

imit

......

......

......

......

..SN

VT_p

pmPO

INT4

7...

....W

......

......

......

......

IAQ

Set

poin

t (PP

M)

nciS

etPn

ts.o

ccup

ied_

cool

.....

SNVT

_tem

p_se

tpt

POIN

T48

......

.W...

......

......

......

...Te

mpe

ratu

re S

etpo

int (

degF

)nc

iSet

Pnts

.sta

ndby

_coo

l....

..SN

VT_t

emp_

setp

tPO

INT4

9...

....W

......

......

......

......

(NA)

nciS

etPn

ts.u

nocc

_coo

l....

.....

SNVT

_tem

p_se

tpt

POIN

T50

......

.W...

......

......

......

...Te

mpe

ratu

re S

etpo

int (

degF

)nc

iSet

Pnts

.occ

upie

d_he

at...

.SN

VT_t

emp_

setp

tPO

INT5

1...

....W

......

......

......

......

Tem

pera

ture

Set

poin

t (de

gF)

nciS

etPn

ts.s

tand

by_h

eat.

.....

SNVT

_tem

p_se

tpt

POIN

T52

......

.W...

......

......

......

...(N

A)nc

iSet

Pnts

.uno

cc_h

eat.

......

..SN

VT_t

emp_

setp

tPO

INT5

3...

....W

......

......

......

......

Tem

pera

ture

Set

poin

t (de

gF)

nviC

OUN

T1...

......

......

......

......

SNVT

_cou

ntPO

INT5

4...

....W

......

......

......

......

Gen

eric

ana

log

or d

iscr

ete

(0-6

5535

)nv

oCO

UNT1

......

......

......

......

..SN

VT_c

ount

POIN

T55

......

.R...

......

......

......

....G

ener

ic a

nalo

g or

dis

cret

e (0

-655

35)

nvoC

OUN

T2...

......

......

......

.....

SNVT

_cou

ntPO

INT5

6...

....R

......

......

......

......

.Gen

eric

ana

log

or d

iscr

ete

(0-6

5535

)nv

oCO

UNTi

nc1

......

......

......

....S

NVT

_cou

nt_i

ncPO

INT5

7...

....R

......

......

......

......

.Gen

eric

ana

log

or d

iscr

ete

(-327

67 - 3

2767

)nv

oCO

UNTi

nc2

......

......

......

....S

NVT

_cou

nt_i

ncPO

INT5

8...

....R

......

......

......

......

.Gen

eric

ana

log

or d

iscr

ete

(-327

67 - 3

2767

)

Page 81: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

72

Figure A-9Sample Configuration forGNRCMAP1 Table

Job

Site

:LE

I Add

ress

:0,

182

Atta

ched

Dev

ice:

Prem

ierL

ink

Atta

ched

Dev

ice A

ddre

ss:

0, 3

1LO

N P

rofil

e:G

ener

ic

GNR

CMAP

1SN

VT T

ype

Rea

d or

Writ

e?C

CN

Poi

nt D

escr

iptio

nC

CN

Poi

nt N

ame

nvoU

nitS

tatu

s.m

ode

SNVT

_hva

c_st

atus

POIN

T01

Rnv

oUni

tSta

tus.

heat

_out

_p...

..SN

VT_h

vac_

stat

usPO

INT0

2...

....R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oUni

tSta

tus.

heat

_out

_s...

..SN

VT_h

vac_

stat

usPO

INT0

3...

....R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oUni

tSta

tus.

cool

_out

......

....S

NVT

_hva

c_st

atus

POIN

T04

......

.R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoU

nitS

tatu

s.ec

on_o

ut...

.....

SNVT

_hva

c_st

atus

POIN

T05

......

.R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoU

nitS

tatu

s.fa

n_ou

t....

......

.SN

VT_h

vac_

stat

usPO

INT0

6...

....R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oUni

tSta

tus.

in_a

larm

......

....S

NVT

_hva

c_st

atus

POIN

T07

......

.R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nviO

ccSc

hedu

le...

......

......

.....

SNVT

_occ

upan

cyPO

INT0

8...

....W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

iTEM

P1...

......

......

......

......

...SN

VT_t

emp_

pPO

INT0

9...

....W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

iTEM

P2...

......

......

......

......

...SN

VT_t

emp_

pPO

INT1

0...

....W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

iTEM

P3...

......

......

......

......

...SN

VT_t

emp_

pPO

INT1

1...

....W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

oTEM

P1...

......

......

......

......

..SN

VT_t

emp_

pPO

INT1

2...

....R

......

......

......

......

.Sup

ply A

ir Te

mpe

ratu

re...

......

......

......

..SA

Tnv

oTEM

P2...

......

......

......

......

..SN

VT_t

emp_

pPO

INT1

3...

....R

......

......

......

......

.Out

door

Air T

empe

ratu

re...

......

......

......

OAT

nvoT

EMP3

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T14

......

.R...

......

......

......

....S

pace

Tem

pera

ture

......

......

......

......

.....

SPT

nvoT

EMP4

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T15

......

.R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoT

EMP5

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T16

......

.R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoT

EMP6

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T17

......

.R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoT

EMP7

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T18

......

.R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoT

EMP8

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T19

......

.R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nviP

RES

S1...

......

......

......

......

SNVT

_pre

ss_p

POIN

T20

......

.W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nviP

RES

S2...

......

......

......

......

SNVT

_pre

ssPO

INT2

1...

....W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

oPR

ESS1

......

......

......

......

..SN

VT_p

ress

_pPO

INT2

2...

....R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oPR

ESS2

......

......

......

......

..SN

VT_p

ress

_pPO

INT2

3...

....R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oPR

ESS3

......

......

......

......

..SN

VT_p

ress

POIN

T24

......

.R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoP

RES

S4...

......

......

......

.....

SNVT

_pre

ssPO

INT2

5...

....R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oPR

ESS5

......

......

......

......

..SN

VT_p

ress

POIN

T26

......

.R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoP

RES

S6...

......

......

......

.....

SNVT

_pre

ssPO

INT2

7...

....R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oTEM

PDIF

F1...

......

......

......

SNVT

_tem

p_di

ff_p

POIN

T28

......

.R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoT

EMPD

IFF2

......

......

......

...SN

VT_t

emp_

diff_

pPO

INT2

9...

....R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..

Page 82: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

73

Figure A-10Sample Configurationfor GNRCMAP2 Table

GNR

CMAP

2SN

VT T

ype

Rea

d or

Writ

e?C

CN

Poi

nt D

escr

iptio

nC

CN

Poi

nt N

ame

nviP

CT1

SNVT

_lev

_per

cent

POIN

T30

Wnv

iPCT

2....

......

......

......

......

.....

SNVT

_lev

_per

cent

POIN

T31

.....

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nvoP

CT1

......

......

......

......

......

.SN

VT_l

ev_p

erce

ntPO

INT3

2...

..R

......

......

......

......

.Coo

ling

% T

otal

Cap

acity

......

......

......

..C

CAP

nvoP

CT2

......

......

......

......

......

.SN

VT_l

ev_p

erce

ntPO

INT3

3...

..R

......

......

......

......

.Hea

ting

% T

otal

Cap

acity

......

......

......

..H

CAP

nvoP

CT3

......

......

......

......

......

.SN

VT_l

ev_p

erce

ntPO

INT3

4...

..R

......

......

......

......

.Eco

nom

izer

Pos

ition

......

......

......

......

...EC

ON

POS

nvoP

CT4

......

......

......

......

......

.SN

VT_l

ev_p

erce

ntPO

INT3

5...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

iDIS

CR

ETE1

......

......

......

....S

NVT

_sw

itch

POIN

T36

.....

W...

......

......

......

...R

emot

e O

ccup

ied

Mod

e...

......

......

......

.RM

TOCC

nviD

ISC

RET

E2...

......

......

......

.SN

VT_s

witc

hPO

INT3

7...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

iDIS

CR

ETE3

......

......

......

....S

NVT

_sw

itch

POIN

T38

.....

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nvoD

ISCR

ETE1

......

......

......

...SN

VT_s

witc

hPO

INT3

9...

..R

......

......

......

......

.Sup

ply

Fan

Rel

ay...

......

......

......

......

.....

SFnv

oDIS

CRET

E2...

......

......

......

SNVT

_sw

itch

POIN

T40

.....

R...

......

......

......

....E

cono

miz

er A

ctiv

e...

......

......

......

......

...EC

OS

nvoD

ISCR

ETE3

......

......

......

...SN

VT_s

witc

hPO

INT4

1...

..R

......

......

......

......

.Rem

ote

Occ

upie

d M

ode

......

......

......

....R

MTO

CCnv

oDIS

CRET

E4...

......

......

......

SNVT

_sw

itch

POIN

T42

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoD

ISCR

ETE5

......

......

......

...SN

VT_s

witc

hPO

INT4

3...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oDIS

CRET

E6...

......

......

......

SNVT

_sw

itch

POIN

T44

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoD

ISCR

ETE7

......

......

......

...SN

VT_s

witc

hPO

INT4

5...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oDIS

CRET

E8...

......

......

......

SNVT

_sw

itch

POIN

T46

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nciS

etPn

ts.o

ccup

ied_

cool

.....

SNVT

_tem

p_se

tpt

POIN

T47

.....

W...

......

......

......

...O

ccup

ied

Coo

ling

Setp

oint

......

......

......

OC

SPnc

iSet

Pnts

.sta

ndby

_coo

l....

..SN

VT_t

emp_

setp

tPO

INT4

8...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nc

iSet

Pnts

.uno

cc_c

ool.

......

..SN

VT_t

emp_

setp

tPO

INT4

9...

..W

......

......

......

......

Uno

ccup

ied

Coo

ling

Setp

oint

......

......

...U

CSP

nciS

etPn

ts.o

ccup

ied_

heat

....S

NVT

_tem

p_se

tpt

POIN

T50

.....

W...

......

......

......

...O

ccup

ied

Hea

ting

Setp

oint

......

......

......

OH

SPnc

iSet

Pnts

.sta

ndby

_hea

t....

..SN

VT_t

emp_

setp

tPO

INT5

1...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nc

iSet

Pnts

.uno

cc_h

eat.

......

..SN

VT_t

emp_

setp

tPO

INT5

2...

..W

......

......

......

......

Uno

ccup

ied

Hea

ting

Setp

oint

......

......

..U

HSP

nviP

PM...

......

......

......

......

......

SNVT

_ppm

POIN

T53

.....

W...

......

......

......

......

......

......

......

......

......

......

......

......

......

....

nvoP

PM...

......

......

......

......

.....

SNVT

_ppm

POIN

T54

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nviC

OUN

T1...

......

......

......

......

SNVT

_cou

ntPO

INT5

5...

..W

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.nv

oCO

UNT1

......

......

......

......

..SN

VT_c

ount

POIN

T56

.....

R...

......

......

......

......

......

......

......

......

......

......

......

......

......

.....

nvoC

OUN

T2...

......

......

......

.....

SNVT

_cou

ntPO

INT5

7...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oCO

UNTi

nc1

......

......

......

....S

NVT

_cou

nt_i

ncPO

INT5

8...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..nv

oCO

UNTi

nc2

......

......

......

....S

NVT

_cou

nt_i

ncPO

INT5

9...

..R

......

......

......

......

......

......

......

......

......

......

......

......

......

......

..

Page 83: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

74

Figure A-11GNRCMAP1 Table SNVTsand CCN Points

Job

Site

:LE

I Add

ress

:A

ttach

ed D

evic

e:A

ttach

ed D

evic

e Add

ress

:LO

N P

rofil

e:(N

A) M

eans

not

gen

eral

ly a

pplic

able

to C

CN

GNR

CMAP

1SN

VT T

ype

Rea

d or

Writ

e?C

CN

Poi

nt D

escr

iptio

nnv

oUni

tSta

tus.

mod

eSN

VT_h

vac_

stat

usPO

INT0

1R

(NA)

nvoU

nitS

tatu

s.he

at_o

ut_p

.....

SNVT

_hva

c_st

atus

POIN

T02

......

R...

......

......

......

....H

eatin

g C

oil V

alve

(%)

nvoU

nitS

tatu

s.he

at_o

ut_s

.....

SNVT

_hva

c_st

atus

POIN

T03

......

R...

......

......

......

....S

econ

dary

Hea

ting

Coi

l Val

ve (%

)nv

oUni

tSta

tus.

cool

_out

......

....S

NVT

_hva

c_st

atus

POIN

T04

......

R...

......

......

......

....C

oolin

g C

oil V

alve

(%)

nvoU

nitS

tatu

s.ec

on_o

ut...

.....

SNVT

_hva

c_st

atus

POIN

T05

......

R...

......

......

......

....E

cono

miz

er (%

)nv

oUni

tSta

tus.

fan_

out.

......

....S

NVT

_hva

c_st

atus

POIN

T06

......

R...

......

......

......

....F

an S

peed

(%)

nvoU

nitS

tatu

s.in

_ala

rm...

......

.SN

VT_h

vac_

stat

usPO

INT0

7...

...R

......

......

......

......

.Dis

cret

e Al

arm

poi

nt (1

/0)

nviO

ccSc

hedu

le...

......

......

.....

SNVT

_occ

upan

cyPO

INT0

8...

...W

......

......

......

......

Glo

bal C

CN

Occ

upan

cy (>

64)

nviT

EMP1

......

......

......

......

......

SNVT

_tem

p_p

POIN

T09

......

W...

......

......

......

...Te

mpe

ratu

re (d

egF)

nviT

EMP2

......

......

......

......

......

SNVT

_tem

p_p

POIN

T10

......

W...

......

......

......

...Te

mpe

ratu

re (d

egF)

nviT

EMP3

......

......

......

......

......

SNVT

_tem

p_p

POIN

T11

......

W...

......

......

......

...Te

mpe

ratu

re (d

egF)

nvoT

EMP1

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T12

......

R...

......

......

......

....T

empe

ratu

re (d

egF)

nvoT

EMP2

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T13

......

R...

......

......

......

....T

empe

ratu

re (d

egF)

nvoT

EMP3

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T14

......

R...

......

......

......

....T

empe

ratu

re (d

egF)

nvoT

EMP4

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T15

......

R...

......

......

......

....T

empe

ratu

re (d

egF)

nvoT

EMP5

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T16

......

R...

......

......

......

....T

empe

ratu

re (d

egF)

nvoT

EMP6

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T17

......

R...

......

......

......

....T

empe

ratu

re (d

egF)

nvoT

EMP7

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T18

......

R...

......

......

......

....T

empe

ratu

re (d

egF)

nvoT

EMP8

......

......

......

......

.....

SNVT

_tem

p_p

POIN

T19

......

R...

......

......

......

....T

empe

ratu

re (d

egF)

nviP

RES

S1...

......

......

......

......

SNVT

_pre

ss_p

POIN

T20

......

W...

......

......

......

...Pr

essu

re (“

H2O

)nv

iPR

ESS2

......

......

......

......

...SN

VT_p

ress

POIN

T21

......

W...

......

......

......

...Pr

essu

re (P

SI)

nvoP

RES

S1...

......

......

......

.....

SNVT

_pre

ss_p

POIN

T22

......

R...

......

......

......

....P

ress

ure (

“H2O

)nv

oPR

ESS2

......

......

......

......

..SN

VT_p

ress

_pPO

INT2

3...

...R

......

......

......

......

.Pre

ssur

e (“H

2O)

nvoP

RES

S3...

......

......

......

.....

SNVT

_pre

ssPO

INT2

4...

...R

......

......

......

......

.Pre

ssur

e (P

SI)

nvoP

RES

S4...

......

......

......

.....

SNVT

_pre

ssPO

INT2

5...

...R

......

......

......

......

.Pre

ssur

e (P

SI)

nvoP

RES

S5...

......

......

......

.....

SNVT

_pre

ssPO

INT2

6...

...R

......

......

......

......

.Pre

ssur

e (P

SI)

nvoP

RES

S6...

......

......

......

.....

SNVT

_pre

ssPO

INT2

7...

...R

......

......

......

......

.Pre

ssur

e (P

SI)

nvoT

EMPD

IFF1

......

......

......

...SN

VT_t

emp_

diff_

pPO

INT2

8...

...R

......

......

......

......

.Del

ta T

empe

ratu

re (^

F)nv

oTEM

PDIF

F2...

......

......

......

SNVT

_tem

p_di

ff_p

POIN

T29

......

R...

......

......

......

....D

elta

Tem

pera

ture

(^F)

Page 84: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

75

Figure A-12GNRCMAP2 Table SNVTsand CCN Points

GNR

CMAP

2SN

VT T

ype

Rea

d or

Writ

e?C

CN

Poi

nt D

escr

iptio

nnv

iPCT

1....

......

......

......

......

......

SNVT

_lev

_per

cent

....P

OIN

T30

.....

W...

......

......

......

...Pe

rcen

t (%

)nv

iPCT

2....

......

......

......

......

......

SNVT

_lev

_per

cent

....P

OIN

T31

.....

W...

......

......

......

...Pe

rcen

t (%

)nv

oPCT

1...

......

......

......

......

.....

SNVT

_lev

_per

cent

....P

OIN

T32

.....

R...

......

......

......

....P

erce

nt (%

)nv

oPCT

2...

......

......

......

......

.....

SNVT

_lev

_per

cent

....P

OIN

T33

.....

R...

......

......

......

....P

erce

nt (%

)nv

oPCT

3...

......

......

......

......

.....

SNVT

_lev

_per

cent

....P

OIN

T34

.....

R...

......

......

......

....P

erce

nt (%

)nv

oPCT

4...

......

......

......

......

.....

SNVT

_lev

_per

cent

....P

OIN

T35

.....

R...

......

......

......

....P

erce

nt (%

)nv

iDIS

CR

ETE1

......

......

......

.....

SNVT

_sw

itch

......

.....

POIN

T36

.....

W...

......

......

......

...D

iscr

ete

(1/0

)nv

iDIS

CR

ETE2

......

......

......

.....

SNVT

_sw

itch

......

.....

POIN

T37

.....

W...

......

......

......

...D

iscr

ete

(1/0

)nv

iDIS

CR

ETE3

......

......

......

.....

SNVT

_sw

itch

......

.....

POIN

T38

.....

W...

......

......

......

...D

iscr

ete

(1/0

)nv

oDIS

CRET

E1...

......

......

......

.SN

VT_s

witc

h...

......

..PO

INT3

9...

..R

......

......

......

......

.Dis

cret

e (1

/0)

nvoD

ISCR

ETE2

......

......

......

....S

NVT

_sw

itch

......

.....

POIN

T40

.....

R...

......

......

......

....D

iscr

ete

(1/0

)nv

oDIS

CRET

E3...

......

......

......

.SN

VT_s

witc

h...

......

..PO

INT4

1...

..R

......

......

......

......

.Dis

cret

e (1

/0)

nvoD

ISCR

ETE4

......

......

......

....S

NVT

_sw

itch

......

.....

POIN

T42

.....

R...

......

......

......

....D

iscr

ete

(1/0

)nv

oDIS

CRET

E5...

......

......

......

.SN

VT_s

witc

h...

......

..PO

INT4

3...

..R

......

......

......

......

.Dis

cret

e (1

/0)

nvoD

ISCR

ETE6

......

......

......

....S

NVT

_sw

itch

......

.....

POIN

T44

.....

R...

......

......

......

....D

iscr

ete

(1/0

)nv

oDIS

CRET

E7...

......

......

......

.SN

VT_s

witc

h...

......

..PO

INT4

5...

..R

......

......

......

......

.Dis

cret

e (1

/0)

nvoD

ISCR

ETE8

......

......

......

....S

NVT

_sw

itch

......

.....

POIN

T46

.....

R...

......

......

......

....D

iscr

ete

(1/0

)nc

iSet

Pnts

.occ

upie

d_co

ol...

...SN

VT_t

emp_

setp

t....

POIN

T47

.....

W...

......

......

......

...Te

mpe

ratu

re S

etpo

int (

degF

)nc

iSet

Pnts

.sta

ndby

_coo

l....

...SN

VT_t

emp_

setp

t....

POIN

T48

.....

W...

......

......

......

...(N

A)nc

iSet

Pnts

.uno

cc_c

ool.

......

...SN

VT_t

emp_

setp

t....

POIN

T49

.....

W...

......

......

......

...Te

mpe

ratu

re S

etpo

int (

degF

)nc

iSet

Pnts

.occ

upie

d_he

at...

..SN

VT_t

emp_

setp

t....

POIN

T50

.....

W...

......

......

......

...Te

mpe

ratu

re S

etpo

int (

degF

)nc

iSet

Pnts

.sta

ndby

_hea

t....

...SN

VT_t

emp_

setp

t....

POIN

T51

.....

W...

......

......

......

...(N

A)nc

iSet

Pnts

.uno

cc_h

eat.

......

...SN

VT_t

emp_

setp

t....

POIN

T52

.....

W...

......

......

......

...Te

mpe

ratu

re S

etpo

int (

degF

)nv

iPPM

......

......

......

......

......

....S

NVT

_ppm

......

......

...PO

INT5

3...

..W

......

......

......

......

IAQ

(PPM

)nv

oPPM

......

......

......

......

......

...SN

VT_p

pm...

......

......

POIN

T54

.....

R...

......

......

......

....I

AQ (P

PM)

nviC

OUN

T1...

......

......

......

......

.SN

VT_c

ount

......

......

.PO

INT5

5...

..W

......

......

......

......

Gen

eric

ana

log

or d

iscr

ete

(0-6

5535

)nv

oCO

UNT1

......

......

......

......

...SN

VT_c

ount

......

......

.PO

INT5

6...

..R

......

......

......

......

.Gen

eric

ana

log

or d

iscr

ete

(0-6

5535

)nv

oCO

UNT2

......

......

......

......

...SN

VT_c

ount

......

......

.PO

INT5

7...

..R

......

......

......

......

.Gen

eric

ana

log

or d

iscr

ete

(0-6

5535

)nv

oCO

UNTi

nc1

......

......

......

.....

SNVT

_cou

nt_i

nc...

...PO

INT5

8...

..R

......

......

......

......

.Gen

eric

ana

log

or d

iscr

ete

(-327

67 - 3

2767

)nv

oCO

UNTi

nc2

......

......

......

.....

SNVT

_cou

nt_i

nc...

...PO

INT5

9...

..R

......

......

......

......

.Gen

eric

ana

log

or d

iscr

ete

(-327

67 - 3

2767

)

Page 85: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

76

Page 86: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

Index

Page 87: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

77

Index

AAddress and Baud Rate 5

BBaud Rate and Address 5

CChiller Maintenance Table 1 45Chiller Maintenance Table 2 48Chiller Mapping Table 1 16Chiller Mapping Table 2 21Chiller Template

points in 4CHLRMAP1 Table 16CHLRMAP2 Table 21CHLRMNT1 Table 45CHLRMNT2 Table 48Commissioning

on the LonWorks Network 12COMMSTAT Table 59Communication Status Maintenance

Table 59CONFIG Table 13Configuration

procedure for 9Configuration Table 13Configuration Tables 9

EErrors

mapping 11

GGeneric Maintenance Table 1 55Generic Maintenance Table 2 57Generic Mapping Table 1 36Generic Mapping Table 2 40Generic Template

points in 5GNRCMAP1 Table 36GNRCMAP2 Table 40GNRCMNT1 Table 55GNRCMNT2 Table 57

LLED Indicators 5

MMaintenance Tables 45Mapping Errors 11Messages Maintenance Table 61MESSAGES Table 61

RRooftop Maintenance Table 2 52Rooftop Template

points in 4RTUMNT1 Table 50RTUMNT2 Table 52

Page 88: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

78

Page 89: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

Reader'sComments

Fold so that the mailing address is visible, staple closed,and mail.

Your comments regarding this manual will help us improve futureeditions. Please comment on the usefulness and readability of thismanual, suggest additions and deletions, and list specific errors andomissions.

Document Name: Publication Date:

Usefulness and Readability:

Suggested Additions and Deletions:

Errors and Omissions (Please give page numbers):

Date:Name:Title or Position:Organization:Address:

Page 90: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

Carrier CorporationCarrier World Headquarters Building

One Carrier PlaceFarmington, CT 06034-4015

Attn: CCN Documentation

Page 91: LonWorks Carrier Translator The LonWorks Carrier Translator with LON FT-10A (free topology) communication is a micro controller-based module that provides the ability to integrate

808 - 335 Rev. 08/05