LONWORKS® DAMPER INTERFACE CATALOGUE RELEASE: 1.9 AUGUST 2017 Lonworks® Damper Interface Catalogue Two Position, Three Position & Hot Smoke Fire Damper Interface This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product will directly put at risk the lives of the occupants and the fabric of the building. ALWAYS READ THIS DOCUMENT BEFORE INSTALLATION. PLEASE RETAIN FOR FUTURE REFERENCE.

Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 1 -

Lonworks® Damper Interface cataloguetwo position, three position & Hot smoke fire Damper Interface

this product forms part of a life safety system. failure to correctly store, handle, install and maintain the product will directly put at risk the lives of the occupants and the fabric of the building.

aLways reaD tHIs Document Before InstaLLatIon. pLease retaIn for future reference.

Page 2: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 2 -

two position Damper Interfacethe Actionair Damper Interface provides a complete Lonworks® communication device to control dampers.

safegard developed the Lonmark® functional profile (11001) for smoke fire dampers and this has been adopted worldwide .

eLectrostatIc sensItIVe DeVIce

SFDI-FT / FDI-FT / SDI-FT230V / 120V / 24V

sfDI - ftthe Actionair Smoke Fire Damper Interface provides a complete Lonworks® communication device to control any failsafe spring-return smoke fire damper actuator that incorporates two auxiliary switches.

fDI - ftthe Actionair Fire Damper Interface provides a complete Lonworks® communication device to failsafe, via an electromagnet, any spring-return fire damper. monitoring of the open and/or closed position is optional.

sDI - ftthe Actionair Smoke Damper Interface provides a complete Lonworks® communication device to control any open/closed smoke damper actuator that incorporates two auxiliary switches.

t wo posItIon smoke fIre Damper Interface optIons:

Please note: Each interface is available in 24V, 120V, or 230V. Please specify a voltage at time of order.

Page 3: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 3 -

Dimensions and mountingthe compact and robust design of the interface enclosure allows the unit to be mounted to a duct, block wall or stud wall.

ensure the Interface is located close enough to the actuator/damper it is controlling/monitoring. normally, actuator/electromagnet leads are 1m in length. also, ensure the Interface is accessible for future maintenance purposes.

please note:

• 150mmclearancerequiredforlidremovalandat cable entry points.

• Unusedcableentriesshouldbesealedwithblind washers.

• DonotdrilltheenclosureasthiswillaffectitsIp rating.

mounting Diagram

four mounting holes Ø 6mm for mounting with suitable screws depending on whether mounting to a duct, block wall or stud wall.

Dimensions in mm.

160

200 75

aprox25

aprox25

60 15

120

220

10

preparation• Onlytrainedandqualifiedpersonnelshouldbeallowedto

install,replaceorservicethisequipment.Installationshouldbe in accordance with the relevant local safety standards.

• Theconnectorscanaccommodatecablediametersupto2.5mm2. It is recommended that all wires be crimped to easeinstallation and replacement of the product.

• ThemainswiringshouldcomplywithIEC60227orIEC60245.

• Aswitchorcircuitbreakershouldbeincludedaspartoftheinstallation.

• TheswitchorcircuitbreakershouldmeettherelevantrequirementsofIEC60947-1andIEC60947-3.

• Theswitchorcircuitbreakershouldbeincloseproximitytotheequipmentandbewithineasyreachoftheoperator.

• Theswitchorcircuitbreakershouldbemarkedasthedisconnectingdevicefortheequipmentandshoulddisconnect both poles of the supply

Installation1. Disconnect the local supply before commencing any work

2.

on the Interface.

wire the interface in accordance with the wiring diagrams shownfollowing.Iftheactuatoristobelocatedmorethan5mfrom the Interface then contact Actionair systems for technical assistance.

3. please be aware that the switch and auxiliary inputs arenot optically isolated. It is recommended that the optional detectors (smoke or heat) use failsafe open contacts to guarantee their detection in the event of a fault condition.

It is also recommended that the network cables are not run alongsideanyhighvoltageorhighfrequencysources.Also,network cables must not be mixed on an individual network astheyhaveverydifferentelectricalcharacteristicsandcouldrender the system unreliable.

4. If fDI-ft, the electromagnet failsafe realease is optional. Ifused, the electromagnet must be protected by a suitablesnubber device.

5. IfFDI-FT,themonitoringofthedamperpositionsisoptional.

6. once wiring is complete, apply power to the DI-ft. the greenpower LeD should illuminate to indicate the presence of power.

7. the Interface is now ready to be configured using a standardLonworks tool such as Lonmaker or the Actionair system.

Page 4: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 4 -

sfDI-ft wiring: 230V & 120V

NetworkNetwork

L N

1AT

F1

To SmokeDetector

SD

To Heat DetectorHD

OPTIONAL

Aux Inputs

L N

POWER IN NETWORK NETWORK

230VActuator Drive

SAFEGARDSGS230-T

Actuator Example

S6 S4

S2 S1

L N S6 S4 S2 S1 + - + -

AUX1ACTUATOR DRIVE SWITCH INPUTS AUX2

ThermalTrip

ActuatorPosition

Sense

2 1

Green LED

Red LED

Yellow LED

Blue LED

Power LED

Service LED

Service Pin

To SmokeDetector

SD

To Heat DetectorHD

OPTIONAL

Aux Inputs

NetworkNetwork

POWER IN

+ -

24V ACOR

+ -

24V DC

+ -

NETWORK NETWORK

+ -

ThermalTrip

24VActuator Drive

ActuatorPosition

Sense

Actuator Example

S6 S4

S2 S1

S6 S4 S2 S1 + - + -

AUX1ACTUATOR DRIVE SWITCH INPUTS AUX2

+ -

2 1

SAFEGARDSGS24-T

Green LED

Red LED

Yellow LED

Blue LED

Power LED

Service LED

Service Pin

sfDI-ft wiring: 24V

fDI-ft wiring: 230V & 120V

To SmokeDetector

SD

To Heat DetectorHD

OPTIONAL

Aux Inputs

DamperPosition

Sense

Electromagnetfailsafe release

FireDamper

OPENCLOSED

NetworkNetwork

L N

1AT

L N

L N

POWER IN

+ - + -

AUX1ACTUATOR DRIVE SWITCH INPUTS AUX2

NETWORK NETWORK

OPEN CLOSED

Green LED

Red LED

Yellow LED

Blue LED

Power LED

Service LED

Service Pin

F1

To SmokeDetector

SD

To Heat DetectorHD

OPTIONAL

Aux Inputs

DamperPosition

Sense

Electromagnetfailsafe release

FireDamper

OPENCLOSED

NetworkNetwork

POWER IN

+ -

24V ACOR

+ -

24V DC

+ -

OPEN CLOSED + - + -

NETWORK NETWORK

AUX1ACTUATOR DRIVE SWITCH INPUTS AUX2

+ -

+ -

Green LED

Red LED

Yellow LED

Blue LED

Power LED

Service LED

Service Pin

fDI-ft wiring: 24V

Page 5: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 5 -

LeD Behaviour

Winkfunction:ServiceLEDflashesfor5s

functIon green reD yeLLow BLue

Open On Off

Closed Off On

travelling flashing flashing

fault flashing

ping one-shot

offline on on on on

maintenance24V AC/DC version 5x20mm,Time-LagFuse,2Arated(seeF1onwiringdiagrams);forexampleLittlefuse215series

120/230VAC versions 5x20mm,Time-LagFuse,1Arated(seeF1onwiringdiagrams);forexampleLittlefuse215series

sDI-ft wiring: 230V & 120V

To SmokeDetector

SD

To Heat DetectorHD

OPTIONAL

Aux Inputs

NetworkNetwork

L N

1AT

L N

POWER IN NETWORK NETWORK

BELIMOBE230

Actuator Example

S6 S4

S2 S1

230VActuator Drive

L2N S6 S4 S2 S1 + - + -

AUX1ACTUATOR DRIVE SWITCH INPUTS AUX2

ActuatorPosition

Sense

32 1

L1

Green LED

Red LED

Yellow LED

Blue LED

Power LED

Service LED

Service Pin

F1

To SmokeDetector

SD

To Heat DetectorHD

OPTIONAL

Aux Inputs

NetworkNetwork

POWER IN

+ -

24V ACOR

+ -

24V DC

+ -

NETWORK NETWORK

+ -

ActuatorPosition

SenseS6 S4

S2 S1

+ - + -

AUX1 AUX2

32 1

BELIMOBE24

Actuator Example

24VActuator Drive

S6 S4 S2 S1

SWITCH INPUTS

+1 +2-

ACTUATOR DRIVE

Green LED

Red LED

Yellow LED

Blue LED

Power LED

Service LED

Service Pin

sDI-ft wiring: 24V

Page 6: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 6 -

Lonmark objects

nv1nviRequestSNVT_obj_request

Mandatory network variables

Optional network variables

nv2nvoStatusSNVT_obj_status

nv4nvoAlarmSNVT_alarm

Node object

FSDA object

Optional network variables

Configuration properties

nc141 Zone Number

nc45 Drive Time

nc48 Receive Heartbeat

nc148 Manufacture Date

nc147 Maintenance Date

nc146 Installation Date

nc61 OEM Label

nc41 Actuator Label

nc17 Location Label

Mandatory Optional

Mandatory network variables

nviActuDriveSNVT_hvac_emergnv1

nv3nvoActuDriveFbSNVT_hvac_emerg

nc49 Send Heartbeat

nc44 Safety Position

nc30 Turn Off Time

nv2nvoActuPosnSNVT_hvac_emerg

Page 7: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 7 -

Lonworks Neuronchip FT5000

transceiver type ft-X2

service functions service pin, service LeD and neuron ID self-adhesive tag

supply (please specify at time of order)

Inputvoltages (230±23)VAC,50Hz (120±12)VAC,60Hz (24±4.8)VAC,50Hz (24 ± 2.4) V Dc

Maximumpowerconsumption 2.5W

output contact type Dpco mechanical

relay contacts

Maximumswitchedload 25VA

Inputs contact type non-isolated dry contacts

sense current 10 ma

environmental Operatingtemperature -5°Cto70°C

Storagetemperature -20°Cto70°C

Humidity 25%RHto90%RHat70°C

maximum altitude 2000 m

conformance agency Listings ce

emc en60730-1:00+a1:04+a2:08 +a16:07 cIspr 22 /FCCpart15,cl.B

LVD EN60730-1:2005+…+A2:2008

Lonmark 11001

enclosure material aBs base with polycarbonate lid

IPrating IP54

flammability uL 94V-0

pollution category 2

Dimensions(exclglands) 200mmx120mmx75mm (L x w x D)

Dimensions(inclglands) 200mmx170mmx75mm (L x w x D)

two position smoke fire Damper Interface specifications

Note:

OptionalHDIEavailable:300°Cfor2houror600°Cfor½ hour applications. please refer to Hot enclosures catalogue or contact Actionair for details.

Page 8: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 8 -

three position Damper Interfacethe Actionair 3psfDI-ft provides a complete Lonworks® device to control a single modulating actuator that incorporates two auxiliary switches.

eLectrostatIc sensItIVe DeVIce

3PSFDI-FT 24V25VA

auto modeDamper can be set to a balance position or drive open/closed and failsafe via spring-return or drives to the failsafe position.

Local modeDamper can be modulated via a 2-10V signal from the Bms and only instructed to failsafe by the system in the event of a fire alarm/fireman’s override input.

tHree posItIon smoke fIre Damper Interface optIons:

~

Page 9: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 9 -

Dimensions and mountingthe compact and robust design of the interface enclosure allows the unit to be mounted to a duct, block wall, or stud wall.

ensure the interface is located close enough to the actuator it is controlling/monitoring. normally actuator leads are 1 m in length. ensure the interface is accessible for future maintenance purposes.

please note:

• 150mmclearancerequiredforlidremovalandat cable entry points.

• Unusedcableentriesshouldbesealedwith blind washers.

• Donotdrilltheenclosureasthiswillaffectits Ip rating.

mounting Diagram

160

200

four mounting holes Ø 6mm for mounting with suitable screws depending on whether mounting to a duct, block wall or stud wall.

Dimensions in mm.

120

220

10

75

aprox25

aprox25

60 15

Page 10: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 10 -

preparation• Onlytrainedandqualifiedpersonnelshould

be allowed to install, replace, or servicethisequipment.Installationshouldbeinaccordance with the relevant local safetystandards.

• Theconnectorscanaccommodatecablediametersupto2.5mm2. It is recommendedthat all wires are crimped to ease installationand replacement of the product.

Installation1. Disconnect the local supply before

2.

commencing any work on the interface.

wire the interface in accordance with the wiring diagram shown across. If the actuator islocatedmorethan5mfromtheinterface,then contact Actionair for technical assistance.

3. It is recommended that the network cablesare not run alongside any high voltage or highfrequencysources.Networkcablesshouldnotbe mixed on an individual network as theyhaveverydifferentelectricalcharacteristicsand could render the system unreliable.

4. once the wiring is complete, apply power tothe interface.

5. Theinterfaceisnowreadytobeconfiguredusing the safegard Builder installation tool.

replacement fuse2 a time-lag fuse (see f1 on wiring diagram).Suggestedreplacement:Littelfuse215series.

wiring Diagram 3psfDI-ft in enclosure without lid

LOCAL Mode

NetworkNetwork

+ -

24V AC

OR+ -

24V DC

C1 C1

+ -

Service LED

Power LED

Service Pin

Learn LED

Learn Switch

ThermalTripModulating

actuator

C2 C3 C4

S6 S4 S2 S1 U1 GND Y1 GND

LOCAL CONTROLACT AUX SWITCHES

Green

Red

Yellow

Blue

24V GND Y U

ACTUATOR DRIVE

Stat

us

LED

s

+ -

C1POWER IN

U1GND

Y1GND From BMS

To BMS

Setp

oin

tp

ote

nti

om

eter

C5C6NETWORK NETWORK

GNDGND

F1

ConneCTor DeSCrIPTIon

c1-1 24 V powerc1-2 gnDc2-4 actuator 24 Vc2-3 actuator gnDc2-2 actuator y signalc2-1 actuator u signalc3-4 s6c3-3 s4c3-2 s2c3-1 s1

ConneCTor DeSCrIPTIon

c4-4 u1 to Bmsc4-3 gnD to Bmsc4-2 y1 from Bmsc4-1 gnD from BmsC5-1 GND(donotconnect)C5-2 NetworkC5-3 Networkc6-1 gnD (do not connect)c6-2 networkc6-3 network

Page 11: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 11 -

NetworkNetworkSmoke control system

ThermalTripModulating

actuator

C2 C3 C4

S6 S4 S2 S1 U1 GND Y1 GND

ACT AUX SWITCHES

Green

Red

Yellow

Blue

24V GND Y U

ACTUATOR DRIVE

Stat

us

LED

s

+ -

C1POWER IN

Setp

oin

tp

ote

nti

om

eter

C5C6NETWORK NETWORK

GNDGND

F1

auto mode

Status LEDs

Winkfunction:ServiceLED(yellow)flashesfor5s

functIon green reD yeLLow BLue

Open On Off

Closed Off On

Balanced on on

travelling flashing flashing

fault flashing

ping one-shot

offline on on on on

Page 12: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 12 -

Learn mode

Status LEDsfunctIon green reD yeLLow

Learn On/Off On/Off

NetworkNetworkSmoke control system

Learn Switch on

ThermalTripModulating

actuator

C2 C3 C4

S6 S4 S2 S1 U1 GND Y1 GND

ACT AUX SWITCHES

Green

Red

Yellow

Blue

24V GND Y U

ACTUATOR DRIVE

Stat

us

LED

s

+ -

C1POWER IN

Setp

oin

tp

ote

nti

om

eter

1

3

4

Learn Switch off5C5C6NETWORK NETWORK

GNDGND

F1

Use the potentiometer to balance the damper in the required position- The Learn LED illuminates when the actuator is within 2º of the setpoint

2 Rotate the potentiometer to 0% to fully close the damper

Service Pin (hold for 1sec)

Page 13: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 13 -

Local mode

Status LEDsfunctIon green reD yeLLow

Local on

NetworkNetwork

ThermalTripModulating

actuator

C2 C3 C4

S6 S4 S2 S1 U1 GND Y1 GND

LOCAL CONTROLACT AUX SWITCHES

Green

Red

Yellow

Blue

24V GND Y U

ACTUATOR DRIVE

Stat

us

LED

s

+ -

C1POWER IN

Setp

oin

tp

ote

nti

om

eter

BUILDINGMANAGEMENT

SYSTEM

Smoke control system

C5C6NETWORK NETWORK

GNDGND

F1

Page 14: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Lonworks® Damper Interface cataLogue reLease: 1.9 august 2017

- PAGE 14 -

three position smoke fire Damper Interface specifications

Lonworks Neuronchip FT5000

transceiver type ft-X2

service functions service pin, service LeD, and neuron ID self-adhesive tag

supply Inputvoltage (24±4.8)VAC,50Hz

(24 ± 2.4) V Dc

max power consumption 1.3 w

output contact type spst mechanical

relay contact

Maxswitchedload 25VA

Inputs contact type non-isolated dry contacts

sense current 10 ma

environmental Operatingtemperature -5°Cto70°C

Storagetemperature -20°Cto70°C

Humidity 25%RHto90%RHat70°C

maximum altitude 2000 m

conformance emc en 60730-1:00+a1:04+a2:08+a16:07

agency listings ce

enclosure material aBs base with polycarbonate lid

IPrating IP54

flammability uL 94V-0

pollution category 2

Dimensions(exclglands) 200mmx120mmx75mm (L x w x D)

Dimensions(inclglands) 200mmx170mmx75mm (L x w x D)

Note:

OptionalHDIEavailable:300°Cfor2houror600°Cfor½ hour applications. please refer to Hot enclosures catalogue or contact Actionair for details.

Page 15: Lonworks® Damper Interface catalogue - Swegon...Lonworks® Damper Interface cataL ogue reLease: 1.9 august 2017 - PAGE 1 - Lonworks® Damper Interface catalogue two position, three

Dampers· smoke/fire dampers· fire dampers· VcD’s· Shut-offdampers· access doors· Industrial & heavy duty dampers (uL approved)

Damper controL proDuctsActionair have been the market leaders in this area of damper control & monitoringsystemsandofferacomprehensiverangeofcontrolpanelsolutionsforeveryprojectsizeandapplication.

from our top specification V3 addressable system to our new low cost smart system forupto36dampers,wehaveacontrolpanelsolutiontomeetallrequirements.Wealsoofferstandardelectro-mechanicalpanelswherelowdamperquantityandsimplecontrolisrequired.

A l s o AvA i l A b l E f r o m s A f E G A r d

unit 33, southern cross Business park, Bray, co. wicklow, a98 Ht99, IrelandT:+35312761600F:+35312761611E: [email protected] www.safegard.ie

complies with european standards

WARNING: The responsible body shall be made aware that, if the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

The information herein is subject to change without notice. We do not assume any liability arising out of the use of this product. Purchase of goods and services is subject to Actionair standard terms and conditions. Product warranty 12 months from date of delivery.

SwegonAirManagement,SouthStreet,Whitstable,Kent,CT53DU,UKT: 01227 276100 F: 01227 264262 E: [email protected] www.actionair.co.uk

actionair and safegard are brand names of swegon air management and safegard systems respectively and both companies are part of the swegon group.