Upload
laxmikant-sharma
View
71
Download
4
Embed Size (px)
Citation preview
ZXWM-32 (V1.10)
DWDM Optical Transmission System
Installation Manual
For Long Haul System
ZTE CORPORATION
11
© ZTE Corporation. 2001, Shenzhen, P. R. China
All rights reserved. No part of this publication may be excerpted, reproduced, translated, annotated or edited, in any form or by any means, without the prior written permission of the copyright owner.
ZXWM-32 (V1.10)
DWDM Optical Transmission System
Installation Manual for Long Haul System
* * * *
3/F., A Wing, ZTE Plaza, Hi-Tech Industrial Park, Shenzhen, P. R. China
Tel: (0086) 755–26770192
Fax: (0086) 755–26770160
Post-code: 518057
* * * *
December, 2001 First Edition, First Print
Preface
In recent years, with the rapid development of the global telecommunication market, especially the
emergence of new services, such as the Internet, high-quality videoconference system and multi-media etc,
there arises a burgeoning need of large-scale, high-performance network transmission. Because of its “one-
wavelength-in-one-fiber” mode, the traditional fiber transmission system SDH and PDH is so restricted by
the characteristics of its own equipment that neither its transmission capacity nor expansion mode can meet
the need, while leaving the massive bandwidth resources of fibers far from being fully exploited. Dense
Wavelength Division Multiplex (DWDM), a new transmission technology, has become the most effective
and practical means for the fiber expansion.
The ZXWM-32 DWDM optical transmission system is the DWDM product developed by ZTE
CORPORATION. This manual introduces the system structure of ZXWM-32 DWDM optical transmission
system, and describes the installation and testing, packaging, delivery and storage of this product, which
focuses on the hardware installation, NMS system installation and system testing and debugging.
This manual applies to ZXWM-32 (V1.10), which has the introductions of many new functions added on
the basis of Version 1.0, such as the descriptions of OADM equipment, those of the system optical
multiplexer section protection function, details of NMS functions and some updates, serving as a reference
for the engineering and O&M personnel.
This series of document contains 5 manuals. The other manuals are:
ZXWM-32 (V1.10) DWDM Optical Transmission System Technical Manual
ZXWM-32 (V1.10) DWDM Optical Transmission System installation manual for VLH system
ZXWM-32 (V1.10) DWDM Optical Transmission System installation manual for ZXONM E300
ZXWM-32 (V1.10) DWDM Optical Transmission System Operation and Maintenance Manual
for ZXONM E300
-3-
Statement: Since the products and technologies are being continuously updated and perfected by
ZTE CORPORATION, the contents in this manual may differ from the actual product. To get newly
updated information of the product, please contact our local service office.
Contents
1 SYSTEM STRUCTURE......................................................................................................................................3
1.1 SYSTEM MECHANICAL STRUCTURE.................................................................................................................3
1.2 SYSTEM COMPOSITION...................................................................................................................................10
1.2.1 Rack system configuration.....................................................................................................................10
1.2.2 OA sub-rack structure............................................................................................................................11
1.2.3 OTU sub-rack structure.........................................................................................................................14
1.2.4 Configurations of sub-rack board plugging area..................................................................................16
1.2.5 Diagram of connections of optical fibers between Optical Terminal Multiplexer Equipment Boards..22
1.2.6 Diagram of connections of optical fibers between Optical Line Amplifier equipment boards.............23
1.2.7 Diagram of connections of optical fibers between Optical Add-Drop Multiplexer equipment boards.23
1.3 INTERFACE DESCRIPTIONS.............................................................................................................................24
1.3.1 Descriptions to the interface of power supply alarm units inside rack.................................................24
1.3.2 Internal electric interfaces of rack........................................................................................................28
1.3.3 Optical interface....................................................................................................................................31
2 INSTALLATION PREPARATIONS AND INSTALLATION FLOW..........................................................44
2.1 EQUIPMENT ROOM ENVIRONMENT REQUIREMENTS.......................................................................................44
2.2 PREPARATION OF INSTALLATION TOOLS.........................................................................................................44
2.3 UNPACKING INSPECTIONS..............................................................................................................................45
2.4 INSTALLATION FLOW DIAGRAM.....................................................................................................................46
3 HARDWARE INSTALLATION.......................................................................................................................47
3.1 RACK INSTALLATION.....................................................................................................................................47
3.1.1 Installation on the equipment room floors.............................................................................................47
3.1.2 Rack top installation..............................................................................................................................49
3.2 POWER SUPPLY ALARM UNIT INSTALLATION.................................................................................................50
3.3 SUB-RACK INSTALLATION..............................................................................................................................51
3.3.1 Structural installation............................................................................................................................51
3.3.2 Electric connection................................................................................................................................51
3.4 FAN INSTALLATION........................................................................................................................................51
3.4.1 Structural installation............................................................................................................................51
3.5 EXTERNAL POWER SUPPLY INSTALLATION.....................................................................................................53
3.6 BOARD INSTALLATION...................................................................................................................................55
3.6.1 Board installation..................................................................................................................................55
3.7 CAMOUFLAGE BOARDS INSTALLATION..........................................................................................................56
3.8 OPTICAL CABLE CONNECTION.......................................................................................................................56
3.8.1 Terminal equipment optical line connections........................................................................................56
-1-
11
3.8.2 Line equipment optical line connections...............................................................................................60
3.8.3 OADM equipment optical line connections...........................................................................................61
4 SYSTEM TESTING AND DEBUGGING.......................................................................................................64
4.1 RACK POWER-ON TEST..................................................................................................................................64
4.2 BOARD POWER-ON TEST................................................................................................................................64
4.3 RACK ALARM LAMP TEST..............................................................................................................................65
4.4 HARDWARE TEST...........................................................................................................................................65
4.4.1 Terminal NE1 test..................................................................................................................................65
4.4.2 Line NE test............................................................................................................................................67
4.4.3 Combined adjusting of system...............................................................................................................67
4.5 SOFTWARE TEST.............................................................................................................................................68
4.6 SYSTEM SHUT-DOWN.....................................................................................................................................69
5 PACKAGING, DELIVERY AND STORAGE................................................................................................70
5.1 PACKAGING...................................................................................................................................................70
5.1.1 Packaging of PCBs................................................................................................................................70
5.1.2 Packaging of cables...............................................................................................................................70
5.1.3 Complete Product Packaging................................................................................................................71
5.1.4 Computer packaging..............................................................................................................................71
5.2 DELIVERY......................................................................................................................................................71
5.3 STORAGE.......................................................................................................................................................72
APPENDIX:...........................................................................................................................................................73
A. “OPTICAL TRANSMISSION EQUIPMENT INSTALLATION REQUIREMENTS”...........................73
1 INSTALLATION OF THE EQUIPMENT...................................................................................................................73
2 CABLE INSTALLATION.......................................................................................................................................74
3 EQUIPMENT APPEARANCE AND ON-SITE CLEANUP...........................................................................................76
B “Connectors and adapters introduce”.................................................................................................................76
-2-
22
1 System Structure
1.1 System mechanical structure
ZXWM-32 employs the standard 19-inch rack of single-cabinet configuration.
Three height options for the complete products are provided (2.0m, 2.2m and 2.6m). Figure 1-1 to 1-4 show
the appearance of the cabinet, which are installed by the same method.
The whole product line of ZXWM-32 system contains 8/16/32/40×2.5Gb/s optical terminal multiplexer
equipment(OTM), optical add-drop multiplexer equipment(OADM), and optical line amplifier
equipment(OLA). For the structure diagrams of OTM, OADM, and OLA equipment, please refer to figure
1-2, figure1-3, and figure 1-4 respectively.
The sizes and weights of the main components are listed in table 1-1.
Table 1-1 Sizes and weights of rack components
Name Size: H×W×D (mm) Unit Weight (kg)
Rack (2.0m/2.2m/2.6m) (2000, 2200 or 2600)×600×300 75, 80, 90
OTU rack 488.5×480.5×256 20
OA rack 622×480.5×256 20
Power supply plug-in box 177×482.6×85.5 10
Installation base (optional)H×560×280 (H is up to users’
decision) 15
-3-
33
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Figure 1-1-1 External size of a cabinet
-4-
Chapter 1 System Structure
Figure 1-1-2 External size of a cabinet
-5-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
-6-
Chapter 1 System Structure
Figure 1-1-3 External size of a cabinet
-7-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Figure 1-2 Optical terminal multiplexer equipment (OTM) structure diagram
-8-
Chapter 1 System Structure
Figure 1-3 Optical add-drop multiplexer equipment (OADM) structure diagram
-9-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Figure 1-4 Optical line amplifier equipment (OLA) structure diagram
-10-
Chapter 1 System Structure
1.2 System composition
1.2.1 Rack system configuration
Figure 1-5 is the schematic diagram of ZXWM-32 rack system.
Figure 1-5 Rack system schematic diagram
-11-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
A complete product consists of three OTU sub-racks and one OA sub-rack.
The 322.5G system optical terminal unit comprises three racks, each consists of OTU sub-rack 1, OTU
sub-rack 2 and OA sub-rack.
The optical line amplifier equipment comprises one rack, which consists of a single sub-rack, the OA sub-
rack. Each cabinet is equipped with a power supply alarm unit, providing power supply and audio/light
alarms for the system.
1.2.2 OA sub-rack structure
An OA sub-rack consists of a common interface area, board plugging area, optical fiber wiring area and fan
area. The OA sub-rack structure is shown as in figure 1-6.
Figure 1-6 OA sub-rack structure diagram
-12-
Chapter 1 System Structure
With simple mechanical structure, the rack is composed of the aluminum front/rear beam, left/right side
board and the guide rail bar.
The public interface area includes the electrical port and the signal connection port.
The board plugging area comprises 14 guide rail slots, with a spacing of 30mm between every two slots.
There is the fiber winding tray inside the wiring area, used for optical fiber winding and wiring.
The fan plug-in box contains the plug-in box mechanical parts, three fans, one power switch and one power
supply port.
The OA subrack interface area is shown in Fig. 1-7.
Fig. 1-7 The schematic diagram of the OA subrack interface area
-13-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Description of the subracks in the OA subrack interface area is given below:
STOP-RING: The control interface to stop the ring.
POWER: The –48V power supply interface.
2MHz: The 2MHz external synchronous clock interface.
2Mbps: The 2Mbps external synchronous clock interface.
PHONE1: The orderwire telephone interface.
PHONE2: The orderwire telephone interface.
WARN: The alarm output interface.
ALM-IN: The alarm input interface.
V.35: The V.35 interface. (Reserved)
RS232: The RS232 interface. (Reserved)
RS485: The RS485 interface. (Reserved)
USER RS232: The RS232 transparent user interface.
USER RS422: The RS422 transparent user interface.
RJ45: The RJ 45 NM interface.
AUI: The AUI interface (reserved).
DATA1: The 64-core bus data interface.
DATA2: The 64-core bus data interface.
-14-
Chapter 1 System Structure
1.2.3 OTU sub-rack structure
An OTU sub-rack consists of a common interface area, board plugging area, optical fiber wiring area and
fan area. The sub-rack structure is shown as in figure 1-8.
Figure 1-8 OTU sub-rack structure diagram
With simple mechanical structure, the rack is composed of the aluminum front/rear beam, left/right side
board and the guide rail bar.
The public interface area includes the electrical port and the signal connection port.
The board plugging area comprises 14 guide rail slots, with a spacing of 30mm between every two slots.
There is the fiber winding tray inside the wiring area, used for optical fiber winding and wiring.
The fan plug-in box contains the plug-in box mechanical parts, three fans, one power switch and one power
supply port.
The OTU subrack interface area is shown in Fig. 1-9.
-15-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Fig. 1-9 The schematic diagram of the OTU subrack interface area
The description of the OTU subrack interface area is given below:
POWER: The –48V power supply interface.
DATA: The 64-core bus data interface.
Note: The OTU subrack on the upper side of the rack is defined as the OTU1 subrack while the one on the
lower side is defined as the OTU2 subrack.
-16-
Chapter 1 System Structure
1.2.4 Configurations of sub-rack board plugging area
1.2.4.1 A typical configuration of the board plugging area of the sending terminal equipment
A typical configuration of the board plugging area of the sending terminal equipment OTU-1 sub-rack is
shown as in figure 1-10.
OTU sub-rack fan area
O
T
U
1
O
T
U
2
O
T
U
3
O
T
U
4
O
T
U
5
O
T
U
6
O
T
U
7
O
T
U
8
O
T
U
9
O
T
U
10
O
T
U
11
O
T
U
12
O
T
U
13
O
T
U
14OTU sub-rack common interface area
Optical fiber area
Figure 1-10 Sending terminal equipment OTU-1 sub-rack plugging area configuration diagram
A typical configuration of the board plugging area of the optical multiplexer terminal equipment OA sub-
rack is shown as in figure 1-11.
Figure 1-11 Sending
terminal equipment
OA sub-rack plugging area
configuration diagram
A typical configuration of the board plugging area of the sending terminal equipment OTU-2 sub-rack is
shown as in figure 1-12.
OTU sub-rack fan area
O
M
U
O
T
U
15
O
W
O
S
C
N
C
P
O
T
U
16
O
T
U
17
O
T
U
18
O
B
A
Fan
Optical fiber area
-17-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
O
T
U
19
O
T
U
20
O
T
U
21
O
T
U
22
O
T
U
23
O
T
U
24
O
T
U
25
O
T
U
26
O
T
U
27
O
T
U
28
O
T
U
29
O
T
U
30
O
T
U
31
O
T
U
32OTU sub-rack common interface area
Optical fiber area
Figure 1-12 Sending terminal equipment OTU-2 sub-rack plugging area configuration diagram
1.2.4.2 A typical configuration of the board plugging area of the receiving terminal equipment
A typical configuration of the board plugging area of the receiving terminal equipment OTU-1 sub-rack is
shown as in figure 1-13.
OTU sub-rack fan area
O
T
U
R
1
O
T
U
R
2
O
T
U
R
3
O
T
U
R
4
O
T
U
R
5
O
T
U
R
6
O
T
U
R
7
O
T
U
R
8
O
T
U
R
9
O
T
U
R
10
O
T
U
R
11
O
T
U
R
12
O
T
U
R
13
O
T
U
R
14OTU sub-rack common interface area
Optical fiber area
Figure 1-13 Receiving Terminal equipment OTU-1 sub-rack plugging area configuration diagram
A typical configuration of the board plugging area of the optical demultiplexer terminal equipment OA sub-
rack is shown as in figure 1-14.
-18-
Chapter 1 System Structure
Figure 1-14 Receiving
Terminal equipment OA
sub-rack plugging area
configuration diagram
A typical
configuration of the board plugging area of the receiving terminal equipment OTU-2 sub-rack is shown as
in figure 1-15.
OTU sub-rack fan area
O
T
U
R
19
O
T
U
R
20
O
T
U
R
21
O
T
U
R
22
O
T
U
R
23
O
T
U
R
24
O
T
U
R
25
O
T
U
R
26
O
T
U
R
27
O
T
U
R
28
O
T
U
R
29
O
T
U
R
30
O
T
U
R
31
O
T
U
R
32OTU sub-rack common interface area
Optical fiber area
Figure 1-15 Receiving terminal equipment OTU-2 sub-rack plugging area configuration diagram
1.2.4.3 A typical configuration of the board plugging area of the optical add-drop equipment
A typical configuration of the board plugging area of the optical add-drop equipment OTU-1 sub-rack is
shown as in figure 1-16.
OTU sub-rack fan area
O
T
U
1
O
T
U
2
O
T
U
3
O
T
U
4
O
P
A
O
A
D
O
T
U
R
O
T
U
R
O
T
U
R
O
T
U
R
O
P
A
O
T
U
R
16
O
T
U
R
17
O
T
U
R
18
N
C
P
O
T
U
R
15
O
D
U
Fan
Optical fiber area
-19-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
1 2 3 4OTU sub-rack common interface area
Optical fiber area
Figure 1-16 Optical add-drop multiplexer equipment OTU-1 sub-rack plugging area configuration diagram
A typical configuration of the board plugging area of the optical add-drop equipment OA sub-rack is shown
as in figure 1-17.
Figure 1-17
Optical add-drop multiplexer
equipment OA sub-rack
plugging area configuration
diagram
A typical configuration of the board plugging area of the optical add-drop equipment OTU-2 sub-rack is
shown as in figure 1-18.
OTU sub-rack fan area
O
T
U
R
1
O
T
U
R
2
O
T
U
R
3
O
T
U
R
4
O
A
D
O
P
A
O
T
U
1
O
T
U
2
O
T
U
3
O
T
U
4
OTU sub-rack common interface area
Optical fiber area
O
B
A
O
W
O
S
C
N
C
P
O
B
A
Fan
Optical fiber area
-20-
Chapter 1 System Structure
Figure 1-18 Optical add-drop multiplexer equipment OTU-2 sub-rack plugging area configuration diagram
1.2.4.4 A typical configuration of the board plugging area of the line amplifier equipment
A typical configuration of the board plugging area of the line amplifier OA sub-rack is shown as in figure
1-19.
O
L
A
O
W
O
S
C
N
C
P
O
L
A
Fan
Optical fiber area
Figure 1-19 Line equipment OA sub-rack plugging area configuration diagram
Features of the board structure:
1. The size of all sub-rack boards is 300 mm×210 mm
2. A single board consists of the front panel, board extractor, and the PCB. Plugs are provided on the PCB
to connect to the sockets on the back plate.
3. On the front panel you will see the board name corresponding to the board slot of the sub-rack.
The board types are listed in table 1-2.
Table 1-2 Board type list
No. Full Name
1 Optical Transponder Unit (OTU)
2 Optical Multiplex Unit (OMU)
3 Optical Demultiplex Unit (ODU)
4 Optical Amplifier Optical booster amplifier
-21-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
(OA)
(OBA)
Optical preamplifier (OPA)
Optical line amplifier (OLA)
5 Order Wire Board (OW)
6Optical Supervision
Channel Board(OSC)
Optical Supervision Channel
terminal (OSCT)
Optical supervision Channel
line (OSCL)
6 Net Control Processor (NCP) Board
7 Optical Add-Drop Board(OAD)
8 Optical Performance Monitor Board(OPM)
9 Optical Protection Board(OP)
Note: The OW board must be plug in the 6th slot, the osc board can be plug in the 7th or 9th slot , the NCP
board must be plug in the 8th solt , except that the OW, OSC and NCP board are fixed in the plugging area,
all boards of the main optical channel is allowed to be located freely as per requirements. Mixed plugging
is allowed in the plugging area. Figure 1-10 to Figure 1-19 are the diagrams of the recommended board
plugging. You may make flexible configurations as per requirements.
Each board slots on the back plate of a sub-rack consists of two sockets: a signal socket and a –48V power
supply socket. On all back plates, every power supply socket is the 12-pin socket. The signal definitions are
shown in figure 1-20, in which the upper two rows are for –48V grounding and the lower two rows are for
–48V power supply.
Figure 1-20 Back plate 12-pin power supply socket
-22-
Chapter 1 System Structure
1.2.5 Diagram of connections of optical fibers between Optical Terminal Multiplexer Equipment Boards
The connection of optical fibers between optical terminal multiplexer equipment boards (take the 32-
channel system as an example) is shown as in figure 1-21.
Figure 1-21 Optical fiber connection diagram of ZXWM-32 optical terminal multiplexer equipment
1.2.6 Diagram of connections of optical fibers between Optical Line Amplifier equipment boards
The connection of optical fibers between line amplifier equipment boards is shown in figure 1-22.
-23-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Figure 1-22 Optical fiber connection diagraph of ZXWM-32 optical line amplifier equipment
1.2.7 Diagram of connections of optical fibers between Optical Add-Drop Multiplexer equipment boards
The connection of optical fibers between optical add-drop multiplexer equipment boards is shown in figure
1-23.
Figure 1-23 Optical fiber connection diagraph of ZXWM-32 optical add-drop multiplexer equipment
1.3 Interface descriptions
1.3.1 Descriptions to the interface of power supply alarm units inside rack
The power supply alarm unit consists of the power supply alarm plug-in box and the alarm light boards.
-24-
Chapter 1 System Structure
The power supply alarm unit has the following functions and features:
1. It features the 10A overcurrent protector;
2. It provides power for up to three subracks, with identically defined interfaces.
3. It provides power for up to three sets of fan units, with identically defined interfaces.
4. It provides power supply inputs with 1+1 protection function.
5. It also provides the audible and visual alarm function.
The main specification of the power supply alarm unit are:
1. Output voltage ranges from –40V to –60V, with the rated voltage of –48V.
2. The maximal output current in the power supply output interface of each subrack is 10A.
3. The maximal output current of each fan interface is 3A.
The Fuse has the following features:
1. Size: Ф5mm×20mm package (glass)
2. Specification: 10A/250VAC; F10AL; FAST; low-breaking
Alarm lights boards are in the middle top of a rack. Green-lamp lighting solely means that the power supply
is normal and no alarms in the rack; both green-lamp and red-lamps lighting means that there are urgent
alarm(s) in the rack; both green-lamp and yellow-lamp lighting means that there are non-urgent alarm(s) in
the rack.
Some examples are as following:
“OTU input LOS alarm” is an urgent alarm, both red-lamp and green-lamp light.
“OTU low input power alarm” is a non-urgent alarm, both yellow-lamp and green-lamp light.
Fig. 1-24 shows the structure of the power supply alarm plug-in box.
The dimension of power supply alarm box is 177mm×482.6mm×85.5mm.
-25-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Fig. 1-24 The structure diagram of the power supply alarm plug-in box
The front view of the power supply alarm unit is shown in Fig. 1-25
Fig. 1-25 The front view of the power supply alarm plug-in box
The description of each interface in this front view is given below.
OUT1~OUT3: The –48V power supply overcurrent protectors of the three subracks, each of which should
be inserted by a 10A fuse.
LAMP: The alarm indicator interface, connected to the alarm indicator board (LED board).
-26-
Chapter 1 System Structure
-48V (I): The air switch 1.
GND (I): The connection terminal 1.
PGND: The grounding terminal.
GND (II): The connection terminal 2.
-48V (II): The air switch 2.
The back view of a power supply alarm unit is shown in Fig. 1-26
Fig. 1-26 The rear view of the power supply alarm plug-in box
The description of each interface in this rear view is given below.
OUT1~OUT3: -48V output to the subracks. The schematic diagram of the socket pins is shown in Fig. 1-
27. The signal definitions of the power supply output interfaces are listed in Table 1-3.
Fig. 1-27 The schematic diagram of the OUT1~OUT3 power suppluy socket on the backplane of the
power supply alarm plug-in box
-27-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Table 1-3 The description of the pin signals of the OUT1~OUT3 power supply socket on the
backplane of the power supply alarm plug-in box
Pin No. Signal description
1 -48V.
2 -48V.
3 -48V.
4 Protection ground
5 -48V ground
6 -48V ground
FAN: With -48V output, it provides power supply for three fan plug-in boxes. Fig. 1-28 shows the
schematic diagram of the fan socket pin while Table. 1-4 lists the power supply output interface signals of
the fan.
Fig. 1-28 FAN power supply socket on the back panel of the power supply alarm plug-in box
Table 1-4 The description of the pin signals of the FAN power supply socket on the back panel of the
power supply alarm plug-in box
Pin No. Signal description
1 -48V.
2 -48V.
3 -48V.
4 -48V ground
5 -48V ground
6 -48V ground
-28-
Chapter 1 System Structure
BUZZER: The buzzer interface
WARN: The alarm interface, from the OA subrack.
ALM_OUT: The external output alarm interface
This interface is used to be connected to the column head cabinet or to other supervision unit. And all
signals are isolated by the relay.
1.3.2 Internal electric interfaces of rack
The internal electric interfaces of a rack is shown as in figure 1-29 (A front view. The broken-lined ovals
indicate that the plugs are at the back).
-29-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Figure 1-29 Schematic diagram of the internal electric interfaces in a rack
-30-
Chapter 1 System Structure
Explanations to the codes in the diagram is shown in table 1-5.
Table 1-5 Electric interface descriptions table
Interface No. Interface name Interface No. Interface name
4 Alarm light signal input socket 20OA sub-rack-48 power supply
input
5 Buzzer signal output interface 212MHz external synchronization
input clock interface
6 alarm signal input interface 22
2Mbps external
synchronization input clock
interface
7 Alarm light signal output socket 23 OW interface 1
8 Alarm signal output interface 24 alarm signal output interface
9-48V power supply output
interface 125 OW interface 2
10-48V power supply output
interface 226
monitoring alarm input
interface
11-48V power supply output
interface 327 V.35 interface (reserved)
12Fan power supply output
interface28 RS232 interface (reserved)
13OTU sub-rack 2 –48V power
supply input29 RS485 interface (reserved)
14
OTU subrack 2 64-pin data
socket 30, 31user transparent channel
interface 1, 2
15 Fan power supply input socket 32 RJ45 interface
16OTU sub-rack 1 –48V power
supply input33 AUI interface (reserved)
17OTU subrack 1 64-pin data
socket34, 35 64-pin data interface
18 Fan power supply input socket 36Fan power supply input
interface
19 ring trip signal input socket 37 Fan power supply switch
38 Fan power supply switch 39 Fan power supply switch
OTU sub-rack common interface area includes the following interfaces:
A power supply interface PWR (13) or PWR (16)
-31-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
A bus data interface DATA (14) or DATA (17).
OA sub-rack common interface area includes the following interfaces:
Two OW phone connection interfaces PHONE1 (23) and PHONE2 (25).
Two transparent user interfaces USER232 (30) and USER422 (31)
NMIs, including a RJ45 (32) interface.
Two 64-pin bus data interfaces DATA1 (34) and DATA2 (35).
A –48V power supply interface PWR (20)
Two alarm interfaces, which are respectively the alarm output interface WARN (24), and the alarm
input interface ALM_IN (26).
Two 2M external synchronization clock interfaces 2MHz (21) and 2Mbps (22).
A ring trip control interface STOP_RING (19).
1.3.3 Optical interface
1.3.3.1 OTU
The interfaces on OTU are shown as in figure 1-30.
Figure 1-30 OTU front panel schematic diagram
-32-
Chapter 1 System Structure
The indicators of the OTU front panel are described as follows:
1. ALM (red): the alarm indicator.
2. NOM (green): the normal work indicator.
Dimensions of the OTU board are(300mm×210mm×30mm).
The interfaces of the OTU front panel are described as follows:
1. OUT: optical output interface (SC/PC connector);
2. IN: optical input interface (SC/PC connector);
OTU Interface Specifications
1. Interface specification of 2.5Gb/s OTU at thetransmit-side (OTUT)
Table 1-6 Transmit-side 2.5Gb/s OTU interface specifications of ZXWM-32(V1.10) DWDM system
Items Unit Parameters
The point parameter at the OTU output end
Spectral
characteristics
Maximum –20dB
spectral width nm ≤0.2
minimum side mode
suppression ratio dB >=35
Mean launched power dBm -3 ~ +1
Extinction ratio dB >=8.2
Eye pattern mask In compliance with G.957 requirements
Central frequency THz 192.1 ~ 195.2
Channel spacing GHz 100
Maximum central frequency deviation GHz +/-20
Output jitter UI
B1(5kHz~20MHz): <=0.5
B2(1MHz~20MHz): <=0.1
The point parameter at the OTU input end
Receiver sensitivity dBm <=-18/-28[Note]
Receiver Overload power dBm >=0/-9[Note]
Receiver reflectance dB <=-27
Note : in the table, for the PIN OTU board, the receiver sensitivity is <=-18dBm, overload power is >=0dBm; For the APD
OTU board, the receiving sensitivity is <=-28dBm, overload power is >=-9dBm.
-33-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
2. Interface specification of 2.5Gb/s OTU at the receiving end (OTUR)
Table 1-7 Receive-side 2.5Gb/s OTU interface specifications of ZXWM-32(V1.10) DWDM system
Items Unit Parameters
The point parameter at the OTU output end
Spectral
characteristics
Maximum –20dB
spectral width nm ≤1
minimum side mode
suppression ratio dB >=35
Mean launched power dBm -3 ~ +1
Extinction ratio dB >=8.2
Eye pattern mask In compliance with G.957 requirements
Output wavelengh nm 1280~1335/1500~1580[Note]
Output jitter UI
B1(5kHz~20MHz): <=0.5
B2(1MHz~20MHz): <=0.1
The point parameter at the OTU input end
Receiver sensitivity dBm <=-28
Receiver Overload power dBm >=-9
Receiver reflectance dB <=-27
Note : in the table, for the 1310nm OTUR board, the range of wavelengh is 1280~1335nm; For the 1550nm OTUR board,
the range of wavelengh is 1500~1580nm.
1.3.3.2 OMU
The OMU interface is shown as in figure 1-31.
-34-
Chapter 1 System Structure
Figure 1-31 OMU front panel schematic diagram
The indicators of the OMU front panel are described as follows:
1. ALM (red): the alarm indicator.
2. NOM (green): the normal work indicator.
Dimensions of the OMU board are(300mm×210mm×120mm).
The interfaces of the OMU front panel are described as follows:
1. CHn: 8/16/32/40 optical input interfaces (SC/PC connector);
2. OUT: optical output interface (SC/PC connector);
3. MON: local optical monitoring interface
Major performance parameters of OMU of ZXWM-32 (V1.10) optical transmission system are listed in
Table 1-8.
Table 1-8 Performance parameters of OMU of ZXWM-32 (V1.10) optical transmission system
Item Unit Parameters
Insertion loss dB <=17
The maximum insertion loss difference of various channels dB <=3
-35-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
1.3.3.3 ODU
The ODU interface is shown as in figure 1-32.
Figure 1-32 ODU front panel schematic diagram
The indicators of the ODU front panel are described as follows:
1. ALM (red): the alarm indicator.
2. NOM (green): the normal work indicator.
Dimensions of the ODU board are(300mm×210mm×120mm).
The interfaces of the ODU front panel are described as follows:
1.CHn: 8/16/32/40 optical output interfaces (SC/PC connector);
2. OUT: optical output interface (SC/PC connector);
3. UDG: upgrade interface (SC/PC connector).
Major performance parameters of ODU of ZXWM-32 (V1.10) optical transmission system are listed in
Table 1-9.
-36-
Chapter 1 System Structure
Table 1-9 Performance parameters of ODU of ZXWM-32 (V1.10) optical transmission system
Item Unit Parameters
Insertion loss dB <10
Separation of adjacent channels dB >=25
Separation of non-adjacent channels dB >=25
1.3.3.4 OBA
The interfaces on OBA is shown in Fig. 1-33.
Figure 1-33 OBA front panel schematic diagram
Dimensions of the OBA board are(300mm×210mm×60mm).
The optical interfaces of the OBA front panel are described as follows:
1. IN: 1550 input interface (SC/PC connector);
2. OUT: line output interface (SC/PC connector);
3. SIN: the 1510 input interface from the supervisory channel (SC/PC connector);
4. MON: local monitoring output interface (SC/PC connector).
Performance parameters of the optical booster amplifier of the ZXWM-32 (V1.10) WDM optical
transmission system are listed in Table 1-10.
-37-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Table 1-10 Performance parameters of ZXWM-32(V1.10)DWDM system optical booster amplifier
Items Unit Parameters
Total input power range dBm -8~-3
Maximum total output power dBm 20
Noise coefficient dB <=6
Input return loss dB >=27
Output return loss dB >=27
Gain flatness dB <=2
Gain tilt dB/dB <=1.6
Polarization related gain change dB <=2
1.3.3.5 OPA
The interfaces on OPA is shown in Fig. 1-34.
Figure 1-34 OPA front panel schematic diagram
Dimensions of the OPA board are(300mm×210mm×60mm).
The optical interfaces of the OPA front panel are described as follows:
1. IN: Line input interface (SC/PC connector);
-38-
Chapter 1 System Structure
2. OUT: 1550 output interface (SC/PC connector);
3. SOUT: the 1510 output interface to the supervisory channel (SC/PC connector);
4. MON: local monitoring output interface (SC/PC connector);
Performance parameters of the preamplifier of the ZXWM-32 (V1.10) WDM optical transmission system
are listed in Table 1-11.
Table 1-11 Performance parameters of ZXWM-32(V1.10)DWDM system preamplifier
Items Unit Parameters
Total input power range dBm -8~-3
Maximum total output power dBm 12
Noise coefficient dB <=6
Input return loss dB >=27
Output return loss dB >=27
Gain flatness dB <=2
Gain tilt dB/dB <=1.6
Polarization related gain change dB <=2
1.3.3.6 OLA
The interfaces on OLA is shown in Fig. 1-35.
-39-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Figure 1-35 OLA front panel schematic diagram
Dimensions of the OLA board are(300mm×210mm×60mm).
The optical interfaces of the OLA front panel are described as follows:
1. IN: line input interface (SC/PC connector);
2. OUT: line output interface (SC/PC connector);
3. SOUT: the 1510 output interface to the supervisory channel (SC/PC connector);
4. SIN: the 1510 input interface from the supervisory channel (SC/PC connector);
5. MON: local monitoring output interface (SC/PC connector).
Performance parameters of the optical line amplifier of the ZXWM-32 (V1.10) WDM optical transmission
system are listed in Table 1-12.
Table 1-12 Performance parameters of ZXWM-32(V1.10)DWDM system optical line amplifier
Items Unit Parameters
Total input power range dBm -8~-3
Maximum total output power dBm 20
Noise coefficient dB <=6
Input return loss dB >=27
Output return loss dB >=27
Gain flatness dB <=2
Gain tilt dB/dB <=1.6
Polarization related gain change dB <=2
1.3.3.7 OSCT
The interfaces on OSCT are shown as in figure 1-36.
The optical interfaces are as below:
OUT: the output optical interface to the supervision channel
IN: the input optical interface to the supervision channel
-40-
Chapter 1 System Structure
Figure 1-36 OSCT front panel schematic diagram
Dimensions of the OSCT board are(300mm×210mm×30mm).
The interfaces of the OSCT front panel are described as follows:
1. OUT: supervisory channel output interface (SC/PC connector);
2. IN: supervisory channel input interface (SC/PC connector).
1.3.3.8 OSCL
The interfaces on OSCL are shown as in figure 1-37.
-41-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Figure 1-37 OSCL front panel schematic diagram
Dimensions of the OSCL board are(300mm×210mm×30mm).
The interfaces of the OSCL front panel are described as follows:
1. OUT1: supervisory channel output optical interface 1;
2. IN1: supervisory channel input optical interface 1;
3. OUT2: supervisory channel output optical interface 2;
4. IN2: supervisory channel input optical interface 2
The interface parameters of OSC are listed in Table 1-13.
Table 1-13 Main performance specification of OSC in the ZXWM-32(V1.10) optical transmission system
Item Unit Parameters
Working wavelength nm 1510±10
Average signal transmission power dBm -7~0
-42-
Chapter 1 System Structure
1.3.3.9 OAD
The interfaces on OAD are shown as in figure 1-38.
Figure 1-38 OAD front panel schematic diagram
The indicators of the OAD front panel are described as follows:
1. ALM (red): the alarm indicator.
2. NOM (green): the normal work indicator.
Dimensions of the OAD boardare(300mm×210mm×60mm).
The interfaces of the OAD front panel are described as follows:
1. IN: combination signal input interface (SC/PC connector);
2 DROPn: four-channel/eigtht-channel signal output interface (SC/PC connector);
3. ADDn: four-channel/eigtht-channel signal input interface (SC/PC connector);
4. OUT: combination signal output interface (SC/PC connector)
The interface parameters of OAD of ZXWM-32(V1.10) DWDM optical transmission system
-43-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
are listed in Table 1-14.
Table 1-14 The interface parameters of OAD
Items Unit Parameters
Insertion loss of input-drop interface dB <=5
Insertion loss of add-output interface dB <=5
Insertion loss of input-output interface dB <=8
Separation of adjacent channels at drop interface dB >=35
Separation of non-adjacent channels at drop interface dB >=22
Separation of output interface to drop channel dB >=33
Optical return loss dB >=40
1.3.3.10 OPM
The interfaces on OPM are shown as in figure 1-39.
Figure 1-39 OPM front panel schematic diagram
The indicators of the OPM front panel are described as follows:
1. ALM (red): the alarm indicator.
2. NOM (green): the normal work indicator.
Dimensions of the OPM board are(300mm×210mm×60mm).
-44-
Chapter 1 System Structure
The interfaces of the OPM front panel are described as follows:
1. INn: two optical input interfaces (SC/PC connector), and n indicates 1~2.
-45-
2 Installation Preparations and
Installation Flow
The internal structure components of the equipment shall be well installed during the cabinet assembly, and
the boards inside the cabinet shall be packaged separately for delivery. No particular requirements during
the installation.
2.1 Equipment room environment requirements
Space requirements:
The room reserved for opening doors at either side shall not be less than 800mm.
Operation temperature:
To guarantee performance indexes:0℃~ +50℃
To guarantee working: -5℃ ~ +55℃
Relative humidity:
To guarantee performance indexes:10% ~ 95%(+35℃)
To guarantee working: 5% ~ 95%(+35℃)
Cleanness: The density of dust particles larger than 5μm in diameter shall be ≤ 3×104 particle/m3; non-
conductive, non-magneto-conductive and non-corrosive dust particles.
Required DC power supply range: -40V ~ -60V.
2.2 Preparation of installation tools
Prepare the following tools:
A percussive electric drill, Φ16 drilling bit, a hammer, a mandrill specially for installing bulge nuts, a cross
screwdriver, and a wrench.
The following documentation shall be prepared:
-46-
4646
Chapter 2 Installation Preparations and Installation Flow
ZXWM-32 DWDM Optical Transmission System Technical Manual 1
ZXWM-32 DWDM Optical Transmission System Operation and Maintenance Manual 1
ZXWM-32 DWDM Optical Transmission System Installation Manual 1
2.3 Unpacking inspections
Check the arrival of the total articles.
Check the conditions of the packaging boxes to see if there is any damage, and make records.
Unpack carefully, and check the inside pieces against the shipping bill and the packing list.
Check if there is any loosened part or visual damage on the rack. Check the completeness and
conditions of the connectors, cables, optical fibers and jumpers.
If there is any damage or loss, contact the local maintenance center of our company, so as to make
compensations as soon as possible.
-47-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
2.4 Installation flow diagram
The installation flow is shown as in figure 2-1.
Figure 2-1 ZXWM-32 DWDM optical transmission system installation and testing flow
-48-
3 Hardware Installation
3.1 Rack installation
3.1.1 Installation on the equipment room floors
The bottom of a rack is shown as in figure 3-1.
Figure 3-1 The dimensional drawing of drilling on a rack installation base (mm)
On the equipment room floor that is provided, mark the positions of the base lines of the rack and the
positions of the installation holes.
3.1.1.1 Direct installation on the concrete floor
Fittings for the installation are as below:
Bulge nuts (with taper pin) M12×50 4
hexagonal bolts M12×25(GB5783-86) 4
Spring washers 12 (GB93-87) 4
Flat washer12 (GB97.1-85) 4
-49-
4949
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Big flat washer12 (GB96-85) 4 (optional)
Install following the steps as below:
1. As per the dimensions shown in figure 3-1, drill four Φ16 round holes at the installation positions on the
concrete floor, and the holes are as deep as 50mm.
2. Clear the dust and earth off the floor, and put four M12×50 steel bulge nuts into the holes, and then put
the taper pins into the nuts. Hammer the taper pins with the hammer and the special-purposed mandrill, so
that the bottoms of the taper drills and the nut bottoms will be on the same level.
3. Move the rack to the working place, and adjust its bottom level.
4. Remove the adjusting bolts off the rack bottom, and point the installation holes on the rack bottom to the
nut holes, and then put on the flat washers and the spring washers in turn. Finally, screw down the M12×25
hexagonal bolts into the nuts.
3.1.1.2 Installation on the suspended floor
Fittings for the installation are as below:
Bulge nuts (with taper pin) M12×50 4
hexagonal bolts M12×25(GB5783-86) 8
Spring washers 12 (GB93-87) 8
Flat washer12 (GB97.1-85) 12
Big flat washer12 (GB96-85) 4 (optional)
Nut M12 (GB6170-86) 4
Install following the steps as below:
1. As per the dimensions shown in figure 3-1, drill four Φ16 round holes at the installation positions on the
concrete floor, and the holes are as deep as 50mm.
2. Clear the dust and earth off the floor, and put four M12×50 steel bulge nuts into the holes, and then put
the taper pins into the nuts. Hammer the taper pins with the hammer and the special-purposed mandrill, so
that the bottoms of the taper drills and the nut bottoms will be on the same level.
3. Move the installation base to the working place.
-50-
Chapter 4 NMS System Installation
4. Point the installation holes on the rack bottom to the nut holes, and then put on the flat washers and the
spring washers in turn. Finally, screw down the M12×25 hexagonal bolts into the nuts, so as to fix the
installation base onto the ground.
5. Remove the adjusting bolts off the rack bottom, and point the installation holes on the bottom to the
corresponding installation holes on the installation base.
6. Use the M12×25 hexagonal bolts, flat washers, spring washers and nuts to fix the rack with the
installation base.
3.1.2 Rack top installation
The installation dimension of the rack top is shown as in figure 3-2.
420
600
230
300
4-φ 16
Outline of the equipment
Figure 3-2 The dimensional drawing of rack top installation (mm)
In the upward outgoing line mode, use four angular section pieces (X, X1, Y and Y1, which are determined
by the wiring troughs of the office side and the relative installation position of the rack). Fix one side of a
angular section piece onto the top rims of the rack by using the M6 (or M8) bolts, nuts, and plat and spring
washers, and fix the other side of it onto the wiring trough of the office side. Refer to figure 3-3.
-51-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Figure 3-3 Angular section piece diagram
3.2 Power supply alarm unit installation
This part shall be installed before delivery. Please check the following parts:
1. Check if the M6 fixing bolts between the alarm box fixing board and the external-tooth washer of the
rack is loose. Fix it if it is loose.
2. Check the power supply alarm boards and the alarm light boards, leads, buzzer and other parts, which
shall be complete.
3. Check the appearance of the power supply alarm boards and the alarm light boards, leads, buzzer and
other parts, which shall be free of damage or stain.
4. Check it against figure 1-25. The LAMP (7) and the alarm lamp board interface 4 (the input socket of
alarm lamp signals) shall be connected through cables. The 9-pin socket shall be perfectly connected.
5. Check it against figure 1-25. The fuses in the fuse seat OUT1, OUT2 and OUT3 shall be well installed.
6. Check it against figure 1-26. The BUZZER interface shall be perfectly connected with the buzzer.
-52-
Chapter 4 NMS System Installation
3.3 Sub-rack installation
3.3.1 Structural installation
Set the OA or OTU sub-rack on the stainless tray of the rack according to configurations, and guide it into
the rack cautiously. Fix it to the external-tooth washer with the M6 bolts after it is in the right position.
3.3.2 Electric connection
Make the connections according to figure 1-18 and table 3-1 and 3-2.
Table 3-1 Internal connections of a rack
A-end Interface B-end interface Connection cable
PWR ( 20 ) OUT1 ( 9 ) 1.2m 054L33 power supply cable
WARN ( 24 ) WARN ( 6 ) 1.5m 054L38 alarm cable
STOP_RING ( 19 ) Ring trip switch 0.35m 054L39 ring trip cable
DATA1 ( 34 ) DATA ( 17 ) 0.32m 054L40 data cable
DATA2 ( 35 ) DATA ( 14 ) 1.4m 054L41 data cable
PHONE1 ( 23 ) Internal OW telephone Telephone self-provide line
Table 3-2 External connections of a rack
A-end Interface B-end interface Connection cable
RJ45 ( 32 ) NMS computer 054L13 network line (the actual length is
determined by actual configurations)
2MHz ( 21 ) Office side Coaxial cable (the actual length is determined by
actual configurations)
2Mbps ( 22 ) Office side Coaxial cable (the actual length is determined by
actual configurations)
USER1 ( 30 ) Computer 5m 054L20 transparent user channel line
USER2 ( 31 ) Computer 5m 054L21 transparent user channel line
PHONE2 ( 25 ) OW telephone 054L16 2-core network line (the actual length is
determined by actual configurations)
V.35 ( 27 ) Reserved
RS232 ( 28 ) Reserved
RS485 ( 29 ) Reserved
3.4 Fan installation
3.4.1 Structural installation
Procedures of sub-rack fan installation:
1. Unpack and take out the fan and check the appearance to see if there is any damage.
-53-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
2. Set the fan on the stainless tray of the rack, and guide it in carefully. Screw down the bolts after it is in
the right position.
Procedures of OA sub-rack fan installation:
1. Unpack and take out the fan and check the appearance to see if there is any damage.
2. After opening the backdoor of the rack, set the fan on the stainless tray of the rack, and guide it in
carefully. Screw down the bolts after it is in the right position.
Note: the power supply switch of the OA sub-rack fan shall be positioned facing the front opening of the
fan box. Install the OA sub-rack fan from the back of the sub-rack, and install the OTU sub-rack fan from
the front of the sub-rack.
Make the connections according to figure 1-18 and table 3-3, 3-4 and 3-5.
Table 3-3 Table of configuration and connections of the three sub-racks of the terminal equipment
A-end Interface B-end interface Connection cable
OTU1 sub-rack fan air socket
(18)FAN (12)
0.7/1.8/1.95 m 054L36 fan cable OA sub-rack fan air socket (36) FAN (12)
OTU2 sub-rack fan air socket
(15)FAN (12)
Table 3-4 Table of configuration and connections of the dual sub-racks of the terminal equipment
A-end Interface B-end interface Connection cable
OTU1 sub-rack fan air socket
(18)FAN(12)
0.7/1.8m 054L35 fan cable
OA sub-rack fan air socket (36) FAN(12)
Table 3-5 Table of configuration and connections of the single sub-rack of the line equipment
A-end Interface B-end interface Connection cable
OA sub-rack fan air socket (36) FAN(12) 1.8m 054L37 fan cable
-54-
Chapter 4 NMS System Installation
3.5 External power supply installation
The connection of power supply is shown as in figure 3-4.
Figure 3-4 External power supply accessing connection diagram
The ZXWM-32 signal rack equipment provides two groups of –48V power supply inputs (it is allowed to
select any one of them, and it is recommended to introduce both, so as to provide protection), including two
–48V terminals, one –48GND signal ground terminal, and one PGND protection ground terminal.
-55-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Connection methods for the first group of –48V input:
1. Peel the multi-strand black leads of over 4mm2 (10mm2 is recommended) in length, and plug it into the
GDN (I) connection terminal. Tighten it with a screwdriver. The other end of the copper wire is connected
the –48V ground provided in the equipment room.
2. Peel the multi-strand blue leads of over 4mm2 (10mm2 is recommended) in length, and plug it into the –
48V (I) air switch. Tighten it with a screwdriver. The other end of the copper wire is connected the –48V
ground provided in the equipment room.
Connection methods for the second group of –48V input:
1. Peel the multi-strand black leads of over 4mm2 (10mm2 is recommended) in length, and plug it into the
GDN (I) connection terminal. Tighten it with a screwdriver. The other end of the copper wire is connected
the –48V ground provided in the equipment room.
2. Peel the multi-strand blue leads of over 4mm2 (10mm2 is recommended) in length, and plug it into the –
48V (I) air switch. Tighten it with a screwdriver. The other end of the copper wire is connected the –48V
ground provided in the equipment room.
The connection method for the protection grounds(PGND):
1. Peel the multi-strand yellow leads of over 10mm2 in length, and weld it onto the 100A connection lug,
and install it to the protection ground end of the rack. The other end of the lead is connected to the
protection ground provided in the equipment room.
2. Peel the multi-strand yellow leads of over 10mm2 in length, and weld it onto the 100A connection lug,
and install it to the protection ground end of the rack. The other end of the copper wire is connected to one
end of the PGND of the grounding terminal. Please make sure to tighten the connections.
3. Fix the two lugs that are crimped to the protection ground terminal tightly using bolts.
Cautions:
1. All external power supplies of a rack must be led in through the lead grooves either on the top or at the
bottom of the rack. The upward wiring mode is preferential.
2. Before the connection, use a multimeter to test the voltage output of the equipment room. The rating is –
48V, and the allowed flowing range is –40V~-60V.
3. Connect the power supply at the ZXWM-32 rack side first. And after make sure that the equipment room
power supply output end is in the disconnected status, connect the power distribution terminals at the office
end according to the office application requirements.
-56-
Chapter 4 NMS System Installation
4. Before the connection, make sure the air switch is in off status. Switch to the “OFF” position to turn it
off, and “ON” to turn it on.
5. Connect the –48V ground and the protection ground (the protection ground is preferentially
recommended) before connecting the –48V power supply.
6. It is allowed to use thicker leads as the power wire and the grounding wire according to actual
conditions, however, their diameters shall not exceed the aperture of connection terminals.
3.6 Board installation
3.6.1 Board installation
Installation procedure
1. Take the board out of the anti-static bag, and check if there is any external mechanical damage. Be
cautious not to damage the optical fiber interface. After making certain that there is no abnormality, start
the installation.
2. Plug the board to the corresponding slot according to the board type marked on the front panel, and
according to the configuration table. Underprop the board with your balm to insert it into the slot. Close the
extractor with your thumb. Push the board into the right position along the guiding rail carefully.
3. Fix the board on the sub-rack using the board fixing bolt on the baffle.
Cautions:
1. Before installation, put on the anti-static wrist strap, so as to connect the human body to the protection
ground of the rack.
2. Pay attention to point the board to precisely to the corresponding socket on the back plate, and it shall be
plugged in the guiding rail vertically.
3. On-line swapping is supported. Nevertheless, it is recommended to plug the board after turning off the
power.
4. Pay attention not to damage the fiber tail when you plug the optical board.
5. The power supply alarm boards and the alarm lamp boards shall be well installed before delivery. Please
check if they are loose or missing.
3.7 Camouflage boards installation
Each sub-rack may have a certain number of blank slots due to different configurations. Each blank slot is
equipped with standard fascia panel. During the installation, move the baffles slightly leftwards or
-57-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
rightwards, to adjust the gaps between slots, and to even the gaps. And then, fix the board on the sub-rack
using the board-fixing bolt on the baffle.
3.8 Optical cable connection
The typical configurations of fiber tails: 10m in length; one end of the optical fiber jumper shall be SC/PC,
which is inside the rack, and the other end shall be FC/PC, which is outside of the rack. The optical fiber
inside the rack shall all be the 1.5m jumper with both ends being SC/PC.
3.8.1 Terminal equipment optical line connections
For the terminal optical line connection, refer to figure 3-5 and 3-6 (take the 32-channel system as an
example, and the actual front panel of a board as the standard).
-58-
Chapter 4 NMS System Installation
Figure 3-5 A-direction sending terminal equipment optical line connection diagram
-59-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Figure 3-6 A-direciton receiving terminal equipment optical line connection diagram
-60-
Chapter 4 NMS System Installation
The connection relationship of the optical line shown in figure 3-5 and 3-6 are listed in table 3-6 and 3-7.
Table 3-6 A-direction sending terminal equipment optical line connection relationships
End A End B Remarks
The A-direction STM signal input fiber
outside the rackEach OTU IN n
Optical fibers are connected
in one-to-one correspondence
OTU OUTn OMU IN nOptical fibers are connected
in one-to-one correspondence
OMU OUT OBA IN
OSCT OUT OBA SIN
OPA SOUT
(B-direction receive terminal
equipment)
OSCT IN
OBA OUTThe A-direction optical line output (to ODF)
outside the rack
Table 3-7 A-direction receiving terminal equipment optical line connection relationships
End A End B Remarks
The A-direction optical line input (to
ODF) outside the rackOPA IN
OPA OUT ODU IN
OPA SOUTOSCT IN
(B-direction sending terminal equipment);
ODU OUTn Each OTUR INOptical fibers are connected
in one-to-one correspondence
Each OTUR OUTnThe A-direction STM signal output fiber
outside the rack
Optical fibers are connected
in one-to-one correspondence
Note:
OMU MON is used for performing optical signal monitoring. ODU MON is used for performing optical signal monitoring. “N” indicates the number
of channels, which is generally 4/8/16/32.
Cautions:
-61-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
1. Figure 3-5 and 3-6 show the connection methods of optical fiber. During actual operations, set the optical
fiber jumper in the wiring area, and make sure that the diameter of the jumper curve shall be over 10cm.
2. Before connecting the jumper connectors, we have to make sure that the fiber tips of the connectors are
cleaned properly. Cleaning the fiber is very important and should be done perfectly. The cleaning should be
done with a clean and new lens tissue. During cleaning one should not touch the fiber tip with hands. The
perfect cleaning can be done using absolute alcohol.
3. During the extraction of optical fiber, nip the jumper head lightly and plug it into the socket gently. If
you hear a “click” sound, it indicates that the jumper is in right position. Make sure the connection in the
right position.
4. It is forbidden to pull or drag the soft line of the fiber.
5. The optical fiber between sub-racks is connected via the optical fiber wiring area and the diversion
trench on the side of the rack. The wire guide of the rack is used for the fiber coming in or going out of the
rack.
3.8.2 Line equipment optical line connections
The line equipment optical line connection is shown as in figure 3-7 (take the actual front panel of the
board as the standard).
Figure 3-7 Line equipment optical line connection diagram
-62-
Chapter 4 NMS System Installation
The connection relationship of the optical line shown in figure 3-7 is listed in table 3-8.
Table 3-8 Line equipment optical line connection relationship
End A End B
The A-direction optical line input (to ODF) outside the rack OLA1 IN
OLA1 SOUT OSCL IN1
OSCL OUT1 OLA1 SIN
OLA1 OUT The A-direction optical line output (to ODF) outside the rack
The B-direction optical line input (to ODF) outside the rack OLA2 IN
OLA2 SOUT OSCL IN2
OSCL OUT2 OLA2 SIN
OLA2 OUT The B-direction optical line output (to ODF) outside the rack
3.8.3 OADM equipment optical line connections
For the OADM equipment optical line connection, refer to figure 3-8 (take the 32-channel OADM system
as an example, and the actual front panel of a board as the standard).
-63-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Figure 3-8 OADM equipment optical line connection diagram
The connection relationship of the optical line of A-direction shown in figure 3-8 is listed in table 3-9.
-64-
Chapter 4 NMS System Installation
Table 3-9 The Oadm equipment A-direction optical line connection relationship
End A(1) End A(2) Remarks
The A-direction optical line input (to
ODF) outside the rack
OPA IN
OPA SOUT OSCL IN1
OPA OUT OAD IN
OAD Dn The A-direction STM signal input fiber
outside the rack (To SDH receiver).
Optical fibers are
connected in one-
to-one
correspondence
The A-direction STM signal input fiber
outside the rack (From SDH transmitter)
.
OTU INN Optical fibers are
connected in one-
to-one
correspondence
OTU OUTN OAD An Optical fibers are
connected in one-
to-one
correspondence
OAD OUT OBA IN
OBA OUT The B-direction optical line output (to
ODF) outside the rack
OSCL OUT1 OBA SIN
-65-
4 System Testing and Debugging
4.1 Rack power-on test
1. Before the power-on test, check the connections of each interface mentioned above.
2. Turn on the rack power supply switch. If the green lamp on the rack top flashes, it indicates that the rack
power supply works normally.
3. Switch on the fan, to see if it works properly.
4. Test the sub-rack voltage, and the rating shall be –48V.
Cautions:
1. Before power-on, make sure that the input voltage of the rack is normal, with the rating as –48V, and the
allowed floating range as –40V~–60V.
2. Turn on the rack power supply switch. If the green lamp on the rack top doesn’t flash, shut off the air
switch, and check the power supply access, and the connection of alarm lamp cable.
3. Make sure the protection ground and the –48V signal ground and other electric potential is 0V.
4. If the fan doesn’t move, please check the power access.
4.2 Board power-on test
1. Make sure that the boards are correctly installed.
2. Connect the air switch, to power on the sub-racks.
3. After the setting, only the green lights flash.
Cautions:
1. At the moment of board power-on, the red and green lamps flash alternatively, indicating that the boards
are normally powered on, and are ready for configurations.
2. After the configuration, if the green lamp flashes, and the green lamp is constantly on, it indicates that
the configuration is completed, but there is alarm, which might be caused by the lack of input optical
-66-
6666
Chapter 5 System Testing and Debugging
signals. Please recognize the alarms according to actual conditions.
3. Before the boards are delivered from the factory, the user programs on them shall be well installed. If the
both the red and the green lamp flash at the same time, it might be caused by the lack of user program on
the board, and it is needed to download the program on-line.
4.3 Rack alarm lamp test
The rack alarm lamp is in the middle of the rack top. If only the green lamp is on, it indicates that the rack
power-on is normal without alarms, and the equipment works normally. If both the green and the red lamps
are on, it indicates that the rack has urgent alarm. If both the green and the yellow lamps are on, it indicates
that the rack has non-urgent alarm.
If there are alarms, it is possible to check the alarm contents through the “fault” function of the SMCC
network management system.
4.4 Hardware test
The equipment test at the project stage is relatively simple that is limited by the conditions, which mainly
concerns the testing of system operations. The required testing instrument includes optical power meter,
multi-wavemeter SDH analyzer, etc.
At the phase of project testing, the hardware testing of ZXWM-32 mainly includes the testing and adjusting
of main optical channel performances, involving the testing of optical power, optical SNR, error code
performances, and jittering performance, and the selection of optical attenuator, in addition, the optical
monitoring channel performance test, the order wire performance test, etc.
The test can be conducted through the combined testing method, starting from the 1~N lines of NEs of
terminal NE1 to the terminal NE2.
4.4.1 Terminal NE1 test
The procedures are as follows:
1. Test the input and output optical power of OTU
The allowed input power range of the PIN type receiver module is 0~-18dBm, and that of the APD type
receiving module is -8~-25dBm. If the input optical power exceeds the above range, it is necessary to add
a proper attenuator to the input end.
The output power range of the optical transmitting module is 0~-10dBm, and the typical value is 0dBm.
-67-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
Note: If no modulating optical signal is added to OTU, the output optical power will be different in some
way.
2. Test OMU output optical power
If the optical power meter is used for the testing, OMU output optical power can be calculated in the
following way:
General output power of OMU=the average value of the input power of each channel+10*lgN-insertion
loss
Here, “N” is the number of optical channels.
If the multi-wavemeter is used for the testing, the insertion loss is the difference between the output optical
power of each OMU channel and each OTU output power.
The insertion loss of a 8-channel system shall be less than 10dB. The insertion loss of a 16-channel system
shall be less than 14dB,and the 32-channel system shall be less 10dB(for thin film or AWG-type) or
17dB(for couple-type).
3. Adjust OBA input optical power, and test the output optical power.
Caculate the gain of OBA, to see if it meets the requirements of the specifications. The typical gain value
is 25dB.
4. Test the input and output optical power of OPA
Add an attenuator to OBA output, which accesses the OPA input end, testing the optical power of each
optical interface. OPA output gain is 17, 22, or 27dB.
5. Test the output optical power of each channel of ODU
Generally speaking, the average output optical power of each ODU channel is 5dB less than the input value
of each channel.
6. Test the input and output optical power of OSC
OSC input optical power shall be higher than –48dBm, and the typical value of output optical power is
within 0~-7dBm.
7. At the end of optical interface performance testing, connect the optical fiber of OBA and OPA.
4.4.2 Line NE test
The procedures are as follows:
-68-
Chapter 5 System Testing and Debugging
1. Test the loss of line fiber
Purpose: The actual testing of line fiber loss can help to choose the volume of the optical attenuator, to
guarantee the input and output power of each optical devices to be within the working range.
Method: Measure the output optical power of the OA of the previous NE and the optical power of the line
to the current NE, and the difference between the two is the line power loss of this section, which includes
the optical fiber loss and the inserting loss.
2. Test the input and output optical power of OLA1
Test the output gain of OLA1 board, to see if it meets the specification requirements.
The typical gain of a 8×22dB system is 22dB. The typical gain of a 5×30dB system is 30dB. The typical
gain of a 3×33dB system is 33dB.
3. Test the input and output optical power of OLA2
Add an attenuator to OLA1 output, which accesses the OLA2 input end, testing the optical power of each
optical interface. The typical gain value of OLA2 is the same as that of OLA1.
4. Test the input and output optical power of OSC
OSC input optical power shall be higher than –48dBm, and the typical value of output optical power is
within 0~-7dBm.
5. At the end of optical interface performance testing, connect the optical fiber of OLA1 and OLA2.
4.4.3 Combined adjusting of system
The procedures are as follows:
1. Measure the signal frequency, optical power, and OSNR of each optical channel by using the multi-
wavemeter, to see if they meet the specification requirements.
It is required that the signal frequency difference be within 5GHz. The typical value of the Max. power of
each channel is 6dBm. The OSNR of MPI-R point is more than 22dB.
2. The error code of channel loopback test and the jittering performance
Perform loop testing on each channel, and use the SDH analyzer to test the error code performance and the
jittering performance.
According to the specifications, each channel shall be free of bit error in 24 hours, and the output jittering
value shall be less than 0.15UI (for the B2 filter). In addition, if conditions allow, it is also possible to test
-69-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
whether the input jittering allowance and the jittering transfer function meet the corresponding
requirements.
3. Test OW performance
Test the addressing call, group call and three-way call function of the OW telephone.
If one party calls another, he is only required to dial the OW number of the another party directly. Method
for group call: The caller dials 999, and then dials the password of the local telephone (the default password
is the local telephone number). Method for the 3-way call: the caller presses #, and then dials the number of
the second party. After hearing the answer of the second party, he then presses # again and dials the third
party number.
4.5 Software test
Log in the user and access software interface; log in the sub-network and access the sub-network
management window, to perform the following tests:
1. Set alarms and query the current and historical alarm status.
2. Set the performance and query the current and historical performance.
3. Set the security management.
4.6 System shut-down
Turn “off” the two air switches on the power supply alarm unit on the upper part of the rack, so that the
rack is in the status of power breakdown.
-70-
5 Packaging, Delivery and Storage
5.1 Packaging
The packaging of all parts of the ZXWM-32 equipment adopts the practical vibration absorption and other
protection measures to ensure the safety of equipment during transportation.
5.1.1 Packaging of PCBs
First of all, seal the bottom seams of the packing box and write down the box numbers. Then put foam
cards for equipment into the box. Operation workers should wear anti-static wrist straps and use the air
pressure gun to clear the dusts off the inside and outside of the rack. Then connect the grounds for the rack.
Pull out the PCBs from the rack and put each PCB into an anti-static plastic bag with its connector
downward, together with two bags of desiccants. Seal the bag with transparent tape and put the bag into the
PCB packing box. Two foam cards are placed on both inter sides of the box, and one foam card is placed
between every two PCBs. Finally, put a foam card on the top of the box, together with the packing list.
If a box is not fully packed, use the foam cards to fill it. Pay attention to the degree of tightness so that the
box is in proper tightness and the PCBs will not shake in the box. The PCB should not be pressed and
damaged.
5.1.2 Packaging of cables
First, put the camouflage boards at the bottom layer, which shall cross each other and are separated with
foamed boards.
Put another layer of foam on the camouflage boards, and then put in the cables, order-wire phones, and the
coaxial cable heads that are well sealed with plastic bags.
Put some foam on the top and put in the optical fiber, and then the packing list.
If the packing box is not full, use the foam cards to fill it. Pay attention to the degree of tightness so that the
box is in proper tightness and the PCBs will not shake in the box. The PCBs should not be pressed or
damaged.
5.1.3 Complete Product Packaging
Paste the labels for anti-static wrist strap sockets on both sides of the rack, where the anti-static wrist strap
-71-
7171
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
sockets are placed.
Place two foam cards respectively on the front and the back of the rack, as well as on the two sides. Bind
them with the sealing tapes. And then, use foam to wrap the rack wholly. Enlace the rack on its upper,
middle and bottom part with tapes, and cover it with plastic bag and then enlace the rack again in the same
way. Finally, suspend the rack and seal the plastic wrap with tapes tightly without any leak. Then suspend
the rack and place it steadily into the packing box. Fill the box with foams around the rack so that the rack
does not shake in the box. Put into the packing list.
5.1.4 Computer packaging
1. Packing monitors
Pack the monitor, and seat it steadily on the foam slots in the cartoon with bottom down. And then, cover it
with another foam with the smooth surface of the foam outward. Seal the seam with tapes.
2. Packing the CPU
Pack the CPU cabinet in a plastic bag and seat it onto the foam slot evenly with bottom downward. Then
place another piece of foam on the CPU cabinet. Note that the computer number should be consistent with
the box number.
3. Packing Keyboards
Stick the label of the product serial number to the keyboard, and then put the keyboard into the keyboard
box. Then place the keyboard box on the foam in the box neatly.
4. Packing accessories
Put power wires, network lines, user manuals and software accessories into the accessory box, and then the
accessory box into the cartoon. The accessory box and the keyboard box should be parallel. After
making sure of the completeness, seal the cartoon.
5.2 Delivery
1. During shipping, products shall be handled gently so that they are not damaged. No tossing or rough
handling is allowed.
2. The products shall be placed neat and tidy on transportation vehicles, compact, safe, and reliable, so as to
prevent damage to the products during transportation due to shaking. Note that computers and board
boxes should be placed on the tops of other heavy objects.
3. During long distance transportation, the products shall not be put in open ships or trucks, and during the
transit halfway, they shall not be put in outdoor warehouses. Avoid shipping them in the same vehicles
-72-
Chapter 6 Packaging, Delivery and Storage
together with easily combustible, explosive, and corrosive goods, and they shall not be exposed to rain,
snow, or other liquid.
5.3 Storage
1. During storage, products should be placed in the original packing. The original protective package
should be kept. Pay attention to keep the completeness of the parts and prevent losses.
2. The storehouse of the products should be kept in order and the storage amount shall be marked. The
storage environment should be kept clean and dry, with the temperature of 0℃~45 and relative℃
humidity of 5%~95%. Moisture-proof, dust-proof and anti-corrosion measures should be taken in the
storehouse.
3. Generally, the storage period should be less than half a year.
-73-
Appendix:
A. “Optical Transmission Equipment
Installation Requirements”
1 Installation of the equipment
1. General requirements
(1) Make sure that the optical communication equipment to be installed is consistent with the principle
diagram, the installation shop drawing and the technique documents. The modifications or substitutes of
all materials, components and techniques cannot be conducted without the approval of specified
programs.
(2) The layout and wiring of complete products shall be practical, easy for assembly, testing, adjusting and
maintenance.
(3) The installation methods shall be decided as per the requirements of the technical documents. No
damage to the installation components or the declining of performances is allowed during the
installation. If mechanical processing is necessary, be sure not to damage any assembled apparatus or
component.
(4) For the installation that require fixed structures, it is required to install them firmly. Avoid such
phenomena as inclining, rocking, shaking, rotating, or deflecting.
(5) All types of gaskets shall cling to the assembly parts, and no crimple or rupture is allowed.
(6) The components at the locked position shall be smooth at locking after installation and adjusting.
(7) At the end of the installation, there shall be no remaining of metal filings or other debris.
2. Installing iron frames and racks
(1) The installation position of all iron frames and racks shall meet the requirements of the plan of
-74-
7474
Appendix
equipment room design.
(2) The posts of iron frames shall be vertical, and the difference of both ends shall not exceed 1% of the
total length of the post.
(3) Racks shall be firmly fixed, and it shall not swag during the extracting of boards, optical fiber or cables.
(4) All fastening pieces must be tightened, and for screws of the same type, the part outside the screw cap
must be of the same length.
3. Installing boards
(1) It is required to wear the anti-static wrist strap during board extracting or plugging, and be sure that the
wrist strap is reliably connected with the screening ground of the rack.
(2) Take out the board out of the anti-static bag carefully, and check if there is any mechanical damage.
(3) Insert the board into the corresponding slot of the sub-rack following the requirements of the technical
specifications, and tighten the screws.
2 Cable installation
1. Installation cables
(1) The norm and pattern of cables shall meet the requirements of the design, and construct as per the shop
drawing.
(2) Reserve enough optical cable and optical soft lines as per the standards and designing requirements.
(3) The optical cable terminal connectors shall be installed at proper position. Keep away from any hot
source or other unsafe factors. _
(4) The optical fiber soft lines shall be laid separately, which shall be put inside the troughs or plastic
sleeves, to avoid being twisted. The curve radius shall meet the standard requirements. It is not allowed
to bind the optical fiber soft lines with other lines, in order to avoid the damage of soft lines.
2. Installing optical connectors
(1) The norms and types of all optical connectors shall meet the designing requirements, and meet the
requirements of connection loss, repeatability, and interchangeability. Make proper test on the
connection loss between installation.
(2) Keep the installed connectors clean. The connectors installed on the fiber tails that is led out of the
optical cable terminal connectors must be plugged into the optical distributors as per the construction
-75-
ZXWM-32 (V1.10) DWDM Optical Transmission System Installation Manual for Long Haul system
requirements. The optical connectors that are not inserted into the optical distributor temporarily shall
be well covered with plastic jacket. It is forbidden to stain the surface of the optical connector.
(3) The optical fiber connector on the optical distributor shall be firmly installed, meeting technical
requirements.
3. Laying cables
(1) The norms and types of cables shall meet requirements, and the DC electric features shall meet the
related standards.
(2) The cuts of cables shall be even, and the cores or the insulation parts shall not be damaged.
(3) The high-frequency cables shall be bound individually, which shall be kept straight without crossing,
and the degree of curves shall be in consistent with other cables.
(4) The walkway cables shall be bound firmly with proper tightness. No obvious twisted lines can be seen.
The cables shall not extend out of the troughs, and no dead corner at the turning. No tapping in the
middle of the cables.
(5) Use insulation protection for the screening lines or naked lines that are possible to be short circuited.
4. Welding cable cores
(1) The insulation layer of the part of a lead terminal head that needs welding shall be peeled off, before
screwing it tight and making the process of flow soldering.
(2) Try to success in welding the welded point at one time, avoiding repeated welding or overlong welding.
(3) The welded point shall appear smooth and firm. No remained welding flux on the surface after welding.
(4) No rosin joint, missed or wrong welding.
3 Equipment appearance and on-site cleanup
1. At the end of the installation, please clean the surface of the equipment. Crew tight the rack and boards,
and close the doors.
2. Adjust the directions of optical cable and the electric cables, making sure they look neat.
3. Clean up the equipment room. Put the empty packing boxes and bags in proper place. Specified
personnel shall be appointed to keep the related documentation and accessories.
-76-
Appendix
B “Connectors and adapters introduce”
Connectors:
1. FC/PC connector:
The FC/PC connector is a one-piece, easy assembly connector designed to be fully compliant to the NTT-FC
connector. Pre-dome zirconia ferrule and Telcordia compliant boot minimizes assembly time in the field and in
production environments.
Description:
The FC Connectors are fiber optic connectors designed to minimize assembly time in the field and in production
environments.
The connectors feature pre-assembled, one-piece construction and offer the user the added feature of a key-
adjustment mechanism.
The bodies are machined in nickel-brass and include a single mode grade, zirconia ceramic, pre-dome ferrule with
a concentricity of less than 1.0µm. The new series accommodates 3mm, 2mm, and 0.9mm fiber types.
Technical specification (Dimensions in mm):
-77-
2. SC/PC connector:
The SSC-PE Series is a one-piece, easy assembly connector designed to be fully compliant to the NTT-SC
connector. Pre-dome zirconia ferrule and Telcordia compliant boot minimizes assembly time in the field and in
production environments.
Product FC/PC Patch cord
Mode Single mode Multi mode
Insertion loss ≤0.3dB ≤0.3dB
Return loss ≥45dB --
Repeatability ΔIL≤0.1dB, ΔRL<5dB
Heat Cycle (-40℃~70℃) ΔIL≤0.2dB, ΔRL<5dB
Operating Temp -40℃~+75℃
Storage Temp -45℃~+85℃
Cable Length Option
-78-
Appendix
Description:
The SSC-PE Series SC/PC Connectors are fiber optic connectors designed to minimize assembly time in the field
and in production environments.
The connectors feature pre-assembled, one-piece construction with push-pull coupling and offer the user the
added feature of a key-adjustment mechanism.
The bodies consist of a lightweight, compact plastic housing and include a single mode grade, zirconia ceramic,
pre-dome ferrule with a concentricity of less than 1.0µm. The new series accommodates 3mm, 2mm, and 0.9mm
fiber types (Dimensions in mm).
Product SC/PC Patch cord
Mode Single mode Multi mode
Insertion loss ≤0.3dB ≤0.3dB
Return loss ≥45dB --
Repeatability ΔIL≤0.1dB, ΔRL<5dB
Heat Cycle (-40℃~70℃) ΔIL≤0.2dB, ΔRL<5dB
Operating Temp -40℃~+75℃
Storage Temp -45℃~+85℃
Cable Length Option
-79-
3. SC/PC-FC/PC (Dimensions in mm)
-80-
Appendix
Adapters:
1. FC/PC adapter:
The FC/PC adapter is a high quality; flange mount adapter designed for single mode NTT-FC connector
applications. The female-female threaded adapter is fully compliant with JIS-C-5970 and can be ordered with
either a single mode grade Phosphor Bronze or Zirconia Ceramic sleeve. Mounting is accomplished via two self-
tapping screws.
Metal body adapters are made from precision milled nickel/brass construction and incorporate ultra-pure
Phosphor Bronze or Zirconia Ceramic compliant split sleeves (Dimensions in mm).
2. SC/PC adapter:
-81-
The SSC-A1 Series is a tight tolerance; plastic bodied flange mount adapter designed for single mode NTT-SC
connector applications. The female-female push-pull adapter is fully compliant with JIS-C-5973 and can be
ordered with either a single mode grade Phosphor Bronze or Zirconia Ceramic sleeve. Mounting is via two metal
locking tabs attached to the body or use of two self-tapping screws.
Plastic body adapters are made from high-impact plastic injection molded to SII's exacting standards for finish and
fit. Available in standard SC to SC or hybrid SC to FC formats, the adapters are equipped with either Phosphor
Bronze or Zirconia Ceramic compliant split sleeves.
-82-