LEGACY REPORT
Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543Regional Office # 900 Montclair Road, Suite A, Birmingham, Alabama 35213 # (205) 599-9800Regional Office # 4051 West Flossmoor Road, Country Club Hills, Illinois 60478 # (708) 799-2305
ICC Evaluation Service, Inc.www.icc-es.org
Legacy report on the 1997 Uniform Building Code™
ER-5033Reissued July 1, 2007
Copyright © 2007Page 1 of 11
ICC-ES legacy reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as
an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, Inc., express or implied, as to
any finding or other matter in this report, or as to any product covered by the report.
DIVISION: 06—WOOD AND PLASTICSection: 06090—Wood and Plastic Fastenings
KC METAL ANCHOR DOWNS, ANCHOR BOLTS,ANCHORS, FOUNDATION ANGLES AND FOUNDATIONSTRAPS
KC METAL PRODUCTS, INC.1960 HARTOG DRIVESAN JOSE, CALIFORNIA 95131
1.0 SUBJECT
KC Metal Anchor Downs, Anchor Bolts, Anchors, FoundationAngles and Foundation Straps.
2.0 DESCRIPTION
2.1 AD, AD-A and AD-B Anchor Down Series:
The Anchor Down anchors connect vertical wood members toconcrete foundations having a minimum compressivestrength of 2,500 psi (17.2 MPa) at 28 days. The anchorconsists of a steel plate that is fabricated into a taperedchannel section, and a horizontal steel plate seat welded tothe channel web. The steel complies with ASTM A 570 Grade33 requirements. The channel web and plate seat haveprepunched bolt holes for bolt connections to the face of thestud or post and to the foundation.
The AD series Anchor Downs must be placed, from the topof the mudsill or plate to the first bolt closest to the plate seat,a minimum of 43/8 inches (111 mm) for AD2; 51/4 inches (133mm) for AD5 and AD6; 61/8 inches (156 mm) for AD7; and 7inches (178 mm) for AD9, AD12 and AD15.
The AD-A and AD-B series Anchor Downs are designed toprovide sufficient distance between prepunched bolt holes tomeet the required seven-bolt-diameter minimum end distancefor the first bolt closest to the plate seat. The die-formedanchor bent channel is welded to the web above the first bolthole. The AD-A series Anchor Downs have a 3/16-inch- (4.7mm) to 3/8-inch-thick (9.5 mm) ASTM A 36 steel load transferplate, tack-welded to the seat. See Figure 1 for descriptivedetails. Table 1 specifies fastener schedules, minimumembedment of anchor bolts and allowable loads.
2.2 KCAB Super Speed Anchor Bolt Series:
The anchor bolts resist uplift forces imposed on vertical woodmembers and foundation attached to any uplift-resistingconnector. The anchor bolts are manufactured from steelcomplying with ASTM A 307. The bolts have threads at oneend and a loop and reverse hook at the other end. The
minimum compressive strength of normal-weight concrete is2,500 psi (17.2 MPa) at 28 days. Dimensional characteristicsand allowable loads are set forth in Table 2. See Figure 2 fordescriptive and installation details.
2.3 SA, SAI, SAM, SAT, SAMT, HSA and HSAT StrapAnchor Series:
These strap anchors provide wind and seismic anchorage forconcrete walls anchored to wood floor or roof diaphragms.The strap anchors are made from No. 12 gage or No. 10 gageby 2-inch-wide (51 mm) galvanized steel. The embossed end,which has a right-angled bend and a 2-inch (51 mm)extension, is embedded 4 inches (102 mm) into minimum2,000 psi (1.4 MPa) concrete, with the strap anchor lying overthe top of the wall ledger or blocking.
The HSA series anchors are similar to SA anchors, andhave embedment depths of 6 inches (152 mm) for the HSA28and 81/4 inches (210 mm) for the HSA35. HSAT anchors areidentical to the HSA except for a 90-degree twist in the strapto facilitate attachment to the side of a purlin.
The SA51 and SA68 strap anchors are designed to provideuplift resistance to double 2x band joist and raised floorfoundation systems subjected to wind or earthquake loading.The strap anchors are fabricated from ASTM A 653 SS Grade37 steel. The SA2545, SA3522, HSA3522 and HSA3522-2Pare for installation in concrete footings where horizontal coldjoints exist between the slab and the footing or foundationwall. The anchor is installed with a minimum No. 4 reinforcingbar installed in and parallel to the concrete footing, in theshear cone, having a minimum length of 24 inches (610 mm),centered at the anchor. Minimum anchor embedment depthsinto concrete for the HSA3522, HSA3522-2P, SA2545 andSA3522 are 10 inches (254 mm), 14 inches (356 mm), 6inches (152 mm) and 8 inches (203 mm), respectively. SeeFigure 3 for descriptive details. Table 3 specifies strapdimensions, fastener schedules and allowable loads.
2.4 WA, WAL, WAM, WAH and WAI Wall Anchor Series:
These anchors are similar to HSA wall anchors except thatthe bent ends are not embedded in concrete. WA, WAL andWAI anchors have a bent 90-degree seat, and WAM andWAH anchors have a die-formed seat, attached to straps ofvarious lengths with prepunched nail and bolt holes. Theanchor bolt type and embedment in the concrete wall requireanalysis and design. Table 4 specifies anchor dimensions,fastener schedules and allowable loads. The No. 18 and No.16 gage steel used to fabricate the anchors conforms toASTM A 653 SS Grade 33 steel, and the No. 12 and No. 11gage steels conform to ASTM A 653 SS Grade 37 steel. SeeFigure 4 for descriptive details and typical installation.
Page 2 of 11 ER-5033
2.5 SSAD Super Speed Anchor Down Series:
SSAD strap anchors are die-formed from No. 12 gage by 3-inch-wide (76 mm) galvanized steel meeting the requirementsfor ASTM A 653 SS Grade 40 steel. These strap anchors aresimilar to HSA3522 strap anchors, and are for installation inconcrete footings or foundation walls. The anchor is hookedaround a minimum No. 4 by 24-inch-long (610 mm)reinforcing bar and provides uplift resistance to double 2-byor solid wood posts undergoing wind or seismic loading. Thestrap has embossed markings for nails installed with a nailgun. Table 5 specifies stem wall thickness, minimumembedment into concrete, fastener schedules and allowableloads. See Figure 5 for descriptive and installation details.
2.6 RFA Retrofit Foundation Angles Series:
These angles are die-formed from No. 12 gage galvanizedsteel meeting the requirements for ASTM A 653 SS Grade 37steel. The top horizontal legs of the angles have prepunchednail and bolt holes for attachment to the mudsill plate, andvertical legs of the angles have two bolt holes for attachmentto the concrete foundation. These angles are used forattaching existing sill plates to existing concrete stem walls.The angles have slots at the bend line which allow foradjustment of the angle for attachment to sloping stem walls.Table 6 specifies dimensions, fastener schedules andallowable loads. See Figure 6 for descriptive details andtypical installation.
2.7 RFS Retrofit Foundation Strap Series:
These straps are die-formed from No. 12 gage galvanizedsteel meeting the requirements for ASTM A 653 SS Grade 37steel. The straps are designed for the retrofitting of existingstructures. Straps attach existing stud or joist to foundationstem wall. Straps may be attached to stud or joist with nailsor bolts, and to the existing foundation stem wall with retrofitanchor bolts. Table 7 specifies strap dimensions, fastenerschedules and allowable loads. See Figure 7 for descriptiveand installation details.
2.8 Design:
Allowable loads for the connectors described in this report arefor connectors installed on wood members having a minimumspecific gravity of 0.50, seasoned to a moisture content of 19percent or less used under continuously dry conditions. Forconnections in wood that is unseasoned or partiallyseasoned, or when connections are exposed to wet-serviceconditions, or where the in-service temperature exceeds100°F (37.8°C), the allowable loads in this report must bemultiplied by the adjustment factors specified in the NDS,1991 revised edition, as referenced in Chapter 23, Division III,of the 1997 Uniform Building Code™ (UBC). The maximumadjusted load shall not exceed the maximum design loadshown in the tables.
In designing wood members connected to the AD, AD-Aand AD-B series anchor downs, the following must beconsidered for single-shear applications:
• The wood member must be checked for its design capacityat the critical net section, reducing the gross sectionproperties for holes or other removed wood, for combinedbending and axial tension, due to eccentricity, and fortensile stresses in accordance with Section 3.9 of theapplicable NDS.
• The wood members must be checked for its designcapacity for compression parallel and perpendicular tograin.
• Allowable stresses and other adjustment factors, asapplicable, from the NDS must be used for checking the
design capacity of the wood member. Design capacities ofthe wood member may also be adjusted by a load durationfactor (CD) as specified in the UBC.
2.9 Installation:
KCAB bolts are to be installed prior to the pouring ofconcrete. Bolts are placed 45 degrees diagonally from thefoundation stem wall, in the direction of an indicator stampedon the bolt head. Bolts are placed in concrete complying withChapter 19 of the UBC. The bolts must have a minimum 13/4-inch (44 mm) edge distance and a minimum 5-inch (127 mm)end distance. See Figure 3 for details.
Anchors and straps must be installed in accordance withthis report and the manufacturer’s instructions.
2.10 Material Specifications:
2.10.1 Steel: Base-metal design steel thicknesses for thegage numbers are 0.1196 inch (3 mm) for 11 gage, 0.1046inch (2.65 mm) for 12 gage, 0.0598 inch (1.5 mm) for 16gage, and 0.0478 inch (1.2 mm) for 18 gage. The uncoatedminimum steel thickness of the connectors in this report, asdelivered to the jobsite, shall not be less than 95 percent ofthese thicknesses at any location except at bends andcorners.
Galvanized steel connectors conforming to ASTM A 653 SSGrade 37 have a minimum yield strength of 37,000 psi (255MPa) and a minimum tensile strength of 52,000 psi (360MPa) with galvanized coating conforming to ASTM A 653G60. Galvanized steel connectors conforming to ASTM A 653SS Grade 40 special grade, have a minimum yield strength of42,000 psi (289 MPa) and a minimum tensile strength of56,000 psi (388 MPa) with galvanized coating conforming toASTM A 653 G60. Galvanized steel connectors conforming toASTM A 653 SS Grade 33 have a minimum yield strength of33,000 psi (230 MPa) and a minimum tensile strength of45,000 psi (310 MPa) with galvanized coating conforming toASTM A 653 G60. Galvanized steel connectors conformingto ASTM A 570 Grade 33 have a minimum yield strength of33,000 psi (230 MPa) and a minimum tensile strength of52,000 psi (360 MPa).
2.10.2 Wood: Lumber is nominal-dimension lumber unlessnoted otherwise, and has a minimum specific gravity of 0.50,such as that of Douglas fir–larch, and must have a moisturecontent not exceeding 19 percent unless the connection hasbeen designed with the appropriate wet-service factor, Cm,specified in the UBC. Glue-laminated timber must becomprised of Douglas fir or southern pine wood species. Useof connectors is limited to lumber that has not been treatedwith fire-retardant chemicals.
2.10.3 Fasteners: Common wire steel nails must conform tothe nominal sizes specified in ASTM F 1667 (FederalSpecification FF-N-105B), unless otherwise noted, and musthave minimum dimensions and bending yield strength asshown in the table below:
NAIL TYPE NAIL SHANKDIAMETER
(inch)
NAIL LENGTH
(inches)
BENDINGYIELD
STRENGTH,Fyb (psi)
10d × 11/2 0.148 11/2 90,000
16d common 0.162 31/2 90,000
16d sinkers 0.148 31/4 90,000
Fasteners for pressure-preservative-treated wood must beof hot-dipped, zinc-coated galvanized stainless steel, siliconbronze or copper. Fasteners required to be corrosion-resistant must be either zinc-coated fasteners or stainlesssteel fasteners.
Page 3 of 11 ER-5033
Bolts must conform with ASTM A 307, and shall have aminimum bending yield strength (Fyb) of 45,000 psi (310MPa).
2.10.4 Welds: AD, AD-A and AD-B Anchor Down Serieshave structural welding and are manufactured under anindependent quality control program with inspections byTesting Engineers, Inc. (AA-532).
2.11 Identification:
The anchor downs and straps are stamped with the name ofKC Metal Products, Inc., the evaluation report number (ER-5033) and the model designation. Bolts are identified by anarrow and the size designation stamped within a circle on topof the anchor head; along with the letters “KC” stamped onthe bolt as shown in Figure 2. Bolt packages bears the nameand address of KC Metal Products, Inc., and the evaluationreport number (ER-5033).
3.0 EVIDENCE SUBMITTED
Descriptive data, drawings, reports of structural load tests andcalculations, and a quality control manual.
4.0 FINDINGS
That the KC Metal Anchor Downs, Anchor Bolts, Anchors,Foundation Angles and Foundation Straps described inthis report comply with the 1997 Uniform Building Code™(UBC), subject to the following conditions:
4.1 The products are identified and installed inaccordance with this report and the manufacturer’sinstructions.
4.2 Allowable loads are as set forth in Tables 1 through7 and as described in Section 2.8 of this report.
4.3 Calculations showing compliance with this report,and design details, are furnished to the buildingofficial, verifying that the concrete foundation isadequate to resist the load applied from theconnectors or anchor bolts.
4.4 Anchor bolts are spaced a minimum of 24 inches(610 mm) on center unless design details arefurnished for closer spacing.
4.5 Lumber has a minimum specific gravity of 0.50 anda moisture content of 19 percent or less.Prefabricated wood products must have anequivalent specific gravity of 0.50.
4.6 Use of the connectors is limited to lumber that hasnot been treated with fire-retardant chemicals.
4.7 Where applicable, adjustment factors for wet-service conditions, elevated temperatures [greaterthan 100°F (37.8°C)] and pressure-treated woodmust be considered.
This report is subject to re-examination in two years.
Page 4 of 11 ER-5033
TABLE 1—AD1, AD-A AND AD-B ANCHOR DOWNS SERIES1
PARTNUMBER
STEELTHICK-NESS(inch)
WIDTH(inches)
HEIGHT(inches)
“e” 6
(inches)NUMBERAND SIZE
OFBOLTS
ONWOOD
CONCRETEANCHOR
BOLTDIAMETER2
(inches)
CONCRETEANCHOR
BOLTMINIMUMEMBED-
MENT2 FORfNc= 2,500 psi
(inches)
ALLOWABLE LOADS3, 4,SINGLE SHEAR (pounds)
Net Wood Thickness (inches)
11/2 21/2 3 31/2 41/2 51/2
AD2 3/16 21/2 6 13/8 2—5/85/8 9 1,630 2,625 2,855 2,855 2,850 2,845
AD5 3/16 21/2 61/4 21/8 2—3/43/4 11 1,940 3,140 3,745 4,080 4,070 4,060
AD6 1/4 21/2 121/2 17/8 3—3/4 1 12 2,850 4,685 5,685 6,235 6,165 6,135
AD75 1/4 3 113/4 21/8 3—7/8 11/8 18 3,325 5,400 6,485 7,595 8,255 8,200
AD9 1/4 31/2 161/2 21/8 3—1 11/8 25 — — — 8,560 10,760 10,665
AD12 1/4 31/2 201/2 21/8 4—1 11/8 36 — — — 10,975 13,950 13,755
AD15 1/4 31/2 241/2 21/8 5—1 11/8 43 — — — 13,020 16,765 16,395
AD2A 12 gage 21/2 8 11/2 2—5/85/8 13 1,570 2,575 2,790 2,790 2,790 2,790
AD5A 10 gage 31/4 91/4 21/16 2—3/43/4 15 1,895 3,120 3,720 4,045 4,035 4,025
AD6A 3/16 31/4 111/4 23/16 2—7/87/8 12 2,245 3,650 4,385 5,090 5,520 5,505
AD7A 1/4 31/2 143/4 25/16 3—7/8 11/8 19 3,310 5,370 6,445 7,545 8,320 8,265
AD8A 3/16 31/2 143/4 23/16 3—7/87/8 20 3,190 5,355 6,490 7,630 8,075 8,025
AD9A 1/4 41/4 171/2 23/8 3—1 11/8 30 3,675 5,990 7,215 8,485 10,885 10,790
AD10A 3/16 31/2 181/4 23/16 4—7/87/8 20 3,905 6,830 8,375 9,755 10,440 10,320
AD14A 1/4 31/2 203/4 23/16 4—1 1 24 — — — 10,975 13,950 13,755
AD20A 1/4 41/4 203/4 23/8 4—1 11/4 27 — — — 10,805 13,885 14,045
AD2B 3/16 21/2 8 11/2 2—5/85/8 9 1,630 2,625 2,855 2,855 2,850 2,845
AD5B 3/16 31/4 91/4 21/16 2—3/43/4 11 1,930 3,140 3,760 4,095 4,085 4,075
For SI: 1 pound = 4.45 N, 1 inch = 25.4 mm.
1The anchor down shall be located on the wood member so that an end distance equal to seven times the bolt diameter is provided.2The anchor bolt between the concrete and the anchor down shall have sufficient embedment to resist allowable loads. Anchor bolts shall have ahook with a minimum return of seven times the diameter. When threaded rod or all-thread is used at the base as the anchor bolt, it shall havesufficient tensile capacity to resist allowable loads. Bolts shall meet specifications of ASTM A 307.3The allowable loads are based on lumber with a minimum specific gravity of 0.50, a moisture content of 19 percent or less, and an in-servicetemperature of 100°F (37.8°C) or less, or as described in Section 2.8 of this report.4Allowable loads have been increased by 331/3% for wind or earthquake in accordance with the UBC.5When AD7 product is installed using 1-inch-diameter anchor bolt, a standard cut washer must be used. Allowable loads are the same as those shownin the table.6“e” = Eccentricity measured from the face of the wood member to the center of the hole for anchor rod [inch(mm)]. In designing wood members,see requirements as described in Section 2.8 of this report.
Page 5 of 11 ER-5033
For SI: 1 inch = 25.4 mm.
FIGURE 1—AD, AD-A AND AD-B SERIES ANCHOR DOWNS
ANCHOR DOWNS—TYPICAL INSTALLATION
Page 6 of 11 ER-5033
For SI: 1 inch = 25.4 mm.
TABLE 2—KCAB SUPER SPEED ANCHOR BOLTS SERIES
STOCK NO. DIAMETER(inch)
LENGTH, L(inches)
MINIMUMEMBEDMENT,
LE(inches)
LENGTH OFTHREADEDPORTION(inches)
ALLOWABLE UPLIFT LOADS (pounds)
6-inch Concrete Stem Wall 8-inch Concrete Stem Wall
EndCondition1
CenterCondition2
EndCondition1
CenterCondition2
KCAB16 5/8 17 12 5 4,265 4,600 4,765 4,765
KCAB20 5/8 21 16 5 5,200 5,200 5,200 5,200
KCAB24 5/8 25 20 5 5,200 5,200 5,200 5,200
KCAB28 7/8 29 24 5 — — 9,335 10,165
KCAB34 7/8 34 26 8 — — 9,335 10,165
KCAB36 7/8 36 28 8 — — 9,335 10,165For SI: 1 pound = 4.48 N, 1 inch = 25.4 mm.
1End condition details are noted in Figure 3.2Center condition requires a minimum of 12 inches between the anchor bolt and the end of the concrete foundation.
KCAB ANCHOR BOLT INSTALLATION DETAILS
FIGURE 2—KCAB AND SUPER SPEED ANCHOR BOLTS SERIES
Page 7 of 11 ER-5033
TABLE 3—SA, SAI, SAT, SAMT, HSA AND HSAT STRAP ANCHORS SERIES1
STOCKNUMBER
STRAP DIMENSIONS TOTAL NUMBER ANDTYPE OF FASTENERS
ALLOWABLE TENSION LOADS2,4,5,6
(pounds)
Thickness(gage)
Width(inches)
Length(inches)
Nails3 Bolts(Alternate)
Nails Bolts
Normal Maximum7 Normal Maximum7
SA18 12 2 181/2 12—16d 2—1/2 1,730 2,305 1,360 1,815
SA23 12 2 233/4 18—16d 3—1/2 2,590 3,455 2,040 2,720
SA28 12 2 29 24—16d 4—1/2 3,455 4,610 2,720 3,625
SA35 12 2 35 24—16d 4—1/2 3,455 4,610 2,720 3,625
SA118 12 2 18 14—10d ×11/2
— 1,455 1,940 — —
SA123 12 2 23 19—10d ×11/2
— 1,975 2,635 — —
SA128 12 2 28 23—10d ×11/2
— 2,600 3,465 — —
SA135 12 2 35 23—10d ×11/2
— 3,015 4,020 — —
SAT18 12 2 181/2 8—16d 2—1/2 1,150 1,535 1,360 1,815
SAT23 12 2 233/4 14—16d 3—1/2 2,015 2,690 2,040 2,720
SAT28 12 2 29 20—16d 4—1/2 3,455 4,610 2,720 3,625
SAT35 12 2 35 20—16d 4—1/2 3,455 4,610 2,720 3,625
SA2545 12 2 253/8 18—16d 3—1/2 2,590 3,455 2,040 2,720
SA3522 12 2 35 20—16d 3—1/2 2,880 3,840 2,040 2,720
SA51 12 2 51 9—16d — 1,270 1,690 — —
SA68 12 2 68 9—16d — 1,270 1,690 — —
HSA28 10 2 29 24—16d 4—1/2 3,650 4,865 2,740 3,655
HSA3522 10 2 35 24—16d 4—1/2 3,650 4,865 2,740 3,655
HSA3522-2P
10 2 39 24—16d 4—1/2 3,650 4,865 2,740 3,655
HSA35 10 2 35 29—16d 4—1/2 4,410 5,875 2,740 3,655
HSAT28 10 2 29 18—16d 3—1/2 2,735 3,650 2.055 2,740
HSAT35 10 2 35 22—16d 3—1/2 3,345 4,460 2,055 2,740
SA2545 12 2 253/8 18—16d 3—1/2 2,590 3,456 2,040 2,720
SA3522 12 2 35 20—16d 3—1/2 2,880 3,840 2,040 2,720
SAM258 12 2 253/8 18—16d 3—1/2 2,590 3,455 2,040 2,720
SAMT258 12 2 253/8 & 283/4 14—16d 3—1/2 2,015 2,690 2,040 2,720For SI: 1 pound = 4.48 N, 1 psi = 6.89 kPa, 1 inch = 25.4 mm.
1Lumber used with HSA and HSAT must be minimum nominal 4 × (31/2 net) thickness.2The strap anchors are designed for use with minimum nail embedment in wood per the UBC.3The nails are 16d common, or equivalent.4The normal loads may be increased for duration of load in accordance with UBC Chapter 23, up to the maximum load tabulated.5Allowable loads are for embedment of bent end of strap at least 4 inches into concrete having minimum compressive strength at 28 days of2,000 psi.6The allowable loads are based on lumber with a minimum specific gravity of 0.50, a moisture content of 19 percent or less, and an in-servicetemperature of 100°F (37.8°C) or less, or as described in Section 2.8 of this report.7The maximum allowable load values include a 331/3% increase for wind or seismic loading.8The “M” designation provides for a minimum 4 inches of strap embedment in a masonry concrete block wall with minimum 2000 psi concretegrout in cells.
Page 8 of 11 ER-5033
For SI: 1 inch = 25.4 mm.
FIGURE 3—SA, SAI, SAT, SAMT, HSA AND HSAT SERIES STRAP ANCHORS
Page 9 of 11 ER-5033
TABLE 4—WA, WAL, WAM, WAI ANCHORS SERIES1, 2, 3, 4
PARTNUMBER
MATERIAL NUMBER AND SIZE OF FASTENERS ALLOWABLE LOADS (pounds)
Strap Section Base Plate(inch)
Nails Bolts(number—diameter)
Anchor Bolt(inch)
Nails Bolts
100% 133% 5 100% 133% 5
WA 13/4 × 191/8 × 16 gage 1/4 8—16d — 3/4 1,080 1,440 — —
WAL50 2 × 20 × 12 gage 1/4 10—16d — 1/2 1,440 1,920 — —
WAL34 2 × 20 × 12 gage 1/4 10—16d 2—1/2"Ø MB 3/4 1,440 1,920 940 1,250
WAM 2 × 27-11/16 × 12 gage 7 gage 24—16d 4—1/2"Ø MB 3/4 3,455 4,605 1,880 2,505
WAM22 21/2 × 219/16 × 12 gage — 30—16d sinkers — 5/8 3,600 4,800 — —
WAH 21/2 × 219/16 × 11 gage — 32—16d sinkers — 5/8 4,095 5,460 — —
WAH16 21/2 × 157/8 × 11 gage — 18—16d — 5/8 2,695 3,580 — —
WAI131 33/4 × 31 × 18 gage 1/4 16—10d × 11/2 inches — 5/8 1,505 1,880 — —For SI: 1 pound = 4.48 N, 1 inch = 25.4 mm.
1Bolt values are based on minimum 11/2-inch net lumber thickness. Nail values are based on minimum 2-inch net lumber thickness.2Bolts shall meet or exceed specifications of ASTM A 307.3Concrete anchors must be structurally checked to adequately resist the allowable loads shown.4The allowable loads are based on lumber with a minimum specific gravity of 0.50, a moisture content of 19 percent or less, and an in-servicetemperature of 100°F (37.8°C) or less, or as described in Section 2.8 of this report.5Allowable loads have been increased by 331/3% for wind or earthquake in accordance with the UBC.
TYPICAL WAM INSTALLATION (others are similar)
FIGURE 4—WA, WAL, WAM, WAI ANCHORS SERIES
Page 10 of 11 ER-5033
TABLE 5—SSAD SUPER SPEED ANCHOR DOWN SERIES
PART NO. STEM WALL THICKNESS EMBEDMENT (le)(inches)
NAIL SCHEDULE(number—size)
ALLOWABLE LOAD1,2,3,4
SSAD8
6 inches
8 24—16d sinker 2,780
SSAD8RJ 8 24—16d sinker 2,780
SSAD10 10 28—16d sinker 3,285
SSAD10RJ 10 28—16d sinker 3,285
SSAD14 14 38—16d sinker 5,820
SSAD14RJ 14 30—16d sinker 5,010
SSAD8
8 inches
8 24—16d sinker 4,005
SSAD8RJ 8 24—16d sinker 4,005
SSAD10 10 28—16d sinker 4,675
SSAD10RJ 10 28—16d sinker 4,675
SSAD14 14 38—16d sinker 5,820
SSAD14RJ 14 30—16d sinker 5,010For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N.
1Allowable loads have been increased by 331/3% for wind or earthquake in accordance with the UBC.2Allowable loads are for concrete with a minimum compressive strength of 2000 psi at 28 days.3Allowable loads are for use with 16d sinkers, 10d commons, or equivalent gun nails 0.148 inch in diameter by 3 inches long.4Allowable loads are for strap end distance equal to embedment; reduce for corner installation.
For SI: 1 inch = 25.4 mm.
FIGURE 5—SSAD-SUPER SPEED ANCHOR DOWNS SERIES
Page 11 of 11 ER-5033
TABLE 6—RFA-RETROFIT FOUNDATION ANGLES SERIES
STOCKNUMBER
ANGLE DIMENSIONS TOTAL FASTENERS ALLOWABLE LOADS2 (pounds)
Thickness(gage)
L(Inches)
B(inches)
Nails to Plate Anchor Bolts1 Parallel toPlate
Perpendicular to Plate
TowardsPlate
Away fromPlate
RFA86 12 8 5 7—10d × 11/2 2—1/2 N 725 725 725
RFA88 12 8 7 7—10d × 11/2 2—1/2 N 725 725 725
RFA136 12 13 5 11—10d × 11/2 3—1/2 N 1,145 1,145 1,145
RFA138 12 13 7 11—10d × 11/2 3—1/2 N 1,145 1,145 1,145For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N.
1Anchor bolt and embedment must be designed to resist allowable loads shown.2Allowable loads shown includes additional loads due to eccentricity.
For SI: 1 inch = 25.4 mm.
FIGURE 6—TYPICAL RFA-RETROFIT FOUNDATION ANGLES SERIES
TABLE 7—RFS-RETROFIT FOUNDATION STRAPS SERIES
STOCK LUMBER STRAP DIMENSIONS (inches) FASTENER SCHEDULE ALLOWABLE UPLIFT LOADS1,2,3 (133%)
(pounds)
L W Joist/Stud Anchor Bolt4 Joist Stud
RFS19 191/2 21/2
8—10d × 11/2
2—1/2
1,110 1,110
2—1/2 M.B. 760 1,280
RFS25 251/2 21/2 8—10d × 11/2 2—1/2 1,110 1,110For SI: 1 pound = 4.45 N, 1 inch = 25.4 mm.
1Bolt values are based on minimum 11/2-inch net lumber thickness.2The allowable loads are based on lumber with a minimum specific gravity of 0.50, a moisture content of 19 percent or less, and an in-servicetemperature of 100°F (37.8°C) or less, or as described in Section 2.8 of this report.3Allowable loads are increased for duration of load; no further increase is allowed.4Concrete bolt type and embedment must be designed to resist the allowable loads shown.
FIGURE 7—RFS-RETROFIT FOUNDATION STRAPS SERIES