Page 1: Launching & Sustaining an Energy Savings Initiative

1

Launching & Sustaining

an Energy Savings Initiative

Better Buildings By Design 2013

Page 2: Launching & Sustaining an Energy Savings Initiative

2

Cast of Characters

• Richard Morley – VP Support Services – CVMC

• Gregory R. Liebert – Liebert Engineering, Inc.

• Randy Mead – Control Technologies

• Tim Perrin – Efficiency Vermont

• CVMC Board of Directors, and CEO

• Many, many others from across each organization

Page 3: Launching & Sustaining an Energy Savings Initiative

3

Sustainability

Leader

Energy Star

(25% reduction)

Energy Master Plan

ESI Meetings

Update Energy Star

Here Today

Page 4: Launching & Sustaining an Energy Savings Initiative

4

Background

• 334K sq-ft hospital in Berlin @ 122 beds

• $2.0–$2.5M annual energy costs (electric & oil)

Page 5: Launching & Sustaining an Energy Savings Initiative

5

Call to Action

“Mr. Morley, what is CVMC doing related to sustainability?”

Page 6: Launching & Sustaining an Energy Savings Initiative

6

What Should We Do?

Page 7: Launching & Sustaining an Energy Savings Initiative

7

Page 8: Launching & Sustaining an Energy Savings Initiative

8

Why an Energy Master Plan?

• Become the inin Central Vermont, and beyond.

• A credible Green Strategy / Story had to be built upon a foundation of

• Commitment to developing a comprehensive Energy Master Plan to , to uncover conservation and efficiency opportunities in order to improve their carbon footprint and green profile, and give them substantial message to share with staff, patients, and community.

• The Energy Master Plan would guide (ERM) analysis and

implementation if feasible.

Page 9: Launching & Sustaining an Energy Savings Initiative

9

Why an Energy Master Plan?

• Implementation of the plan shall reduce annual energy costs, while

, and avoid creating a “sick building” in the name of energy savings.

• All energy conservation and efficiency improvements shall be , specifically net present value analysis that weigh initial capital cost, future operating, and maintenance costs.

• Achievement of for Healthcare certification (first in Vermont).

Page 10: Launching & Sustaining an Energy Savings Initiative

10

Energy Use Analysis

including original construction drawings, as-built documents (as available) and control system documentation were collected, reviewed and summarized.

to understand system configurations, and observe actual operating conditions.

(BAS) accessed remotely to extract current and historical for all major HVAC systems.

• Several years was collected, and analyzed for daily, weekly, monthly, seasonal, and yearly trends.

• Daily were analyzed to determine use patterns.

Page 11: Launching & Sustaining an Energy Savings Initiative

11

Energy Use Analysis

Page 12: Launching & Sustaining an Energy Savings Initiative

12

Energy Use Analysis

Page 13: Launching & Sustaining an Energy Savings Initiative

13

Energy Use Analysis

Page 14: Launching & Sustaining an Energy Savings Initiative

14

Survey & Findings

Page 15: Launching & Sustaining an Energy Savings Initiative

15

Survey & Findings

Heating System:

• Two Fuel Fired Steam Boilers

• Capacity 12,075 lbs/hr each

• 86% Efficiency (non-condensing)

• Heat Recovery Strategies:

Flue Gas: none

Water Side: none

• Steam-to-Hot Water Heat Exchangers for:

Perimeter Zone Heat (convectors/baseboard)

Air System Reheat

Domestic Hot Water Generation

Page 16: Launching & Sustaining an Energy Savings Initiative

16

Survey & Findings

Page 17: Launching & Sustaining an Energy Savings Initiative

17

Survey & Findings

Page 18: Launching & Sustaining an Energy Savings Initiative

18

Survey & Findings Office and Administration Areas

Private and open offices, and general administration areas are dense with

computers, printers, fax machines, copy machines, water coolers, coffee

makers, speciality machines, task lighting, and personal devices and

appliances, where the majorty of them, if not all, consume electricity whether

in operation or not. Of course they consume more when on, but the stand-

by power or “phantom” loads are significant, and with a staff or over 300,

total an amount worthy of reduction considerations.

Almost all of the standby power is converted into heat. During warm periods,

additional energy is consumed to remove the extra heat from standby power

devices through ventilation and air-conditioning. So, there is a cost for

generating the waste heat, and a cost to remove it from the space.

Standby = Phantom electrical load

This is plug load, some

time active, and

sometime phantom

Standby power load – laser printer

Page 19: Launching & Sustaining an Energy Savings Initiative

19

Change Recommendations

Air Handling Systems:

1. Retro-commissioning, calibration, and verification

2. Sequence of Operation evaluation, documentation and

modification for:

• Supply air temperature reset

• Economizer operation

• Static pressure reset

• Space temperature control

3. Redistribution of loads for improved performance

4. ASHRAE-170 for minimum requirements

Page 20: Launching & Sustaining an Energy Savings Initiative

20

Change Recommendations

Chiller Water and Boilers:

1. Retro-commissioning, calibration, and verification

2. Sequence of Operation evaluation, documentation and

modification for:

• Air side ecominizing

• Chiller sequencing

• Chiller & tower optimization

• Seasonal start-up & shutdown3

3. Cooling tower and chiller cross-connect

Page 21: Launching & Sustaining an Energy Savings Initiative

21

Change Recommendations

Chilled Water and Boilers:

CVMC Cooling Load vs. Reheat Load - 2009

-

200,000

400,000

600,000

800,000

1,000,000

1,200,000

1,400,000

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

kWh

Reheat kWh

Cooling kWh

Page 22: Launching & Sustaining an Energy Savings Initiative

22

Change Recommendations

People:

. Regardless of title, position, schedule, or responsibilities, everyone either change the facility’s profile, or maintain the status quo

. Everyone should be on the lookout for power consuming devices that are operating or in a standby mode, and switch them off if not needed.

. Doors, windows, and other openings to the outside during all seasons must be closed to stop an exchange of heat and air.

. Leave setting on HVAC, mechanical, electrical, lighting systems, and equipment alone

to for an energy committee and devote time to make a green difference.

if you you’ve found or suspect something is consuming too much energy or wasting energy.

Page 23: Launching & Sustaining an Energy Savings Initiative

23

Energy Savings Analysis

Page 24: Launching & Sustaining an Energy Savings Initiative

24

Page 25: Launching & Sustaining an Energy Savings Initiative

25

Develop the Game Plan

Page 26: Launching & Sustaining an Energy Savings Initiative

26

Develop the Game Plan

Page 27: Launching & Sustaining an Energy Savings Initiative

27

Progress Towards Goal

Page 28: Launching & Sustaining an Energy Savings Initiative

28

Early Successes

Page 29: Launching & Sustaining an Energy Savings Initiative

29

Chiller Cross-connect

Page 30: Launching & Sustaining an Energy Savings Initiative

30

Templifier

Page 31: Launching & Sustaining an Energy Savings Initiative

31

Re-tuning Control Sequences of Operation

Page 32: Launching & Sustaining an Energy Savings Initiative

32

Collect and Review Documentation

Page 33: Launching & Sustaining an Energy Savings Initiative

33

Floor Plans

Page 34: Launching & Sustaining an Energy Savings Initiative

34

Control Drawings

Page 35: Launching & Sustaining an Energy Savings Initiative

35

BAS Screen Shots

Page 36: Launching & Sustaining an Energy Savings Initiative

36

AO04

DO01

DO02

AO01

AO02

Low Limit Desc AHU1 Fan CmdAction 0-Direct

Input Addr

Output

Binary Output

Desc Commissioning

Input[1]

Input[2]

Output

Priority Input (2)

[NA]

SF Cmd

Desc Heating ValveLOutput 4LScale 100

HOutput 20HScale 0

Input Addr

Output

Analog Output

AHU Heating Valve

Input[1]

Input[2]

Output

AND / AND

Low Limit

AHUS20 Enable

Desc Commissioning

Input[1]

Input[2]

Output

Priority Input (2)

[NA]

Desc OADamperCmdAction 0-Direct

Input Addr

Output

Binary Output

Desc Commissioning

Input[1]

Input[2]

Output

Priority Input (2)

[NA]

OADamperCmd

LOutput 0LScale 0

HOutput 20HScale 100

Supply Fan VFD

Input Addr

Output

Analog Output

LpEnb

Input

Setpt

TR

Igain

Derv

OutRef

Action

RmpTm

Output

Loop Single

[50]

[100] Reverse

Space Diff Pressure

SF Cmd

Space DP Sp

Desc Commissioning

Input[1]

Input[2]

Output

Priority Input (2)

[NA]

SF Speed

Index 35nciRampTime

nci_count_inc_f [2]

Index 34nciIgain

nci_count_inc_f [0.1]Index 33

nciTR3

nci_count_inc_f [10]

Input[1]

Input[2]

Output

High Select

Input[1]

Input[2]

InSel

Output

Select

SF Cmd

[0] [100]

Input[1]

Input[2]

InSel

Output

Select

Low Limit

[0]

SFSpdOvrdValue [30]

MinSFSpd

MinSFSpd

Desc Commissioning

Input[1]

Input[2]

Output

Priority Input (2)

[NA]

Input[1]

Input[2]

InSel

Output

Select

Low Limit

[100]

SFSpeedCmd

HtgVlvOvrd

Input[1]

Input[2]

Output

AND / AND

SF Status

Desc Commissioning

Input[1]

Input[2]

Output

Priority Input (2)

[NA]

Input

Setpt

InDiff

Direct

Reverse

Thermostat

[2] Condensate Low Limit Alarm

Latch

Reset

Data

Output

Latch

Reset

Reset

Input[1]

Input[2]

Input[3]

Output

OR / OR

Low Limit Sensor

Supply Fan

Outside Air Damper

Supply Fan Speed

Heating Valve

LpEnb

Input

Setpt

TR

Igain

Derv

OutRef

Action

RmpTm

Output

Loop Single

[50]

Condensate Temp

Condensate LL Sp

Input[1]

Input[2]

Output

Add / Add

[0]

OAT <42F

[40]

[0.1]

OAT

Input

Setpt

InDiff

Direct

Reverse

Thermostat

[42]

[2]

[100] Reverse

Condensate LL Signal

[2]

Input[1]

Input[2]

Input[3]

Output

High Select

Condensate LL Signal

StmVlvSignal

StmVlvCmd

Dehumid Enable

Input

TripOn

TripOff

Output

Limit Thermostat

Desc Commissioning

Input[1]

Input[2]

Output

Priority Input (2)

LpEnb

Input

Setpt

TR

Igain

Derv

OutRef

Action

RmpTm

Output

Loop Single

[40]

[0.1]

[50]

[100] Reverse

[30]

Humidifier Enable

LpEnb

Input

Setpt

TR

Igain

Derv

OutRef

Action

RmpTm

Output

Loop Single

[30]

[0.1]

[10]

[100] Reverse

[30]

Humidifier Enable

Input[1]

Input[2]

Output

Low Select

HiSaRHSp

Input[1]

Input[2]

InSel

Output

Select

[0]

[NA]

LOutput 4LScale 0

HOutput 10HScale 100

Humidifier Valve

Input Addr

Output

Analog Output

Supply Air Humidity

Humidifier Enable

Desc Commissioning

Input[1]

Input[2]

Output

Priority Input (2)

Input[1]

Input[2]

Output

AND / AND

TmEnb

Input

OffDly

Output

TmRem

Off Delay

[60]

Input[1]

Input[2]

InSel

Output

Select

[0]

HumidLockout

[NA]

Input[1]

Input[2]

Output

Priority Input (2)

HumidLockout [NA]

Space Humidity Sp

Space Humidity Sp

Supply Air Humidity

[85]

[75]

Input

TripOn

TripOff

Output

Limit Thermostat

TmEnb

Input

MinOff

Output

TmRem

Minimum Off

[30]

[100]

[50]

[40]

Input

TripOn

TripOff

Output

Limit Thermostat

Input[1]

Input[2]

Output

OR / OR

Input

TripOn

TripOff

Output

Limit Thermostat

Input[1]

Input[2]

Output

Add / Add

Space Humidity Sp

[10]

Humidifier Valve

LpEnb

Input

Setpt

TR

Igain

Derv

OutRef

Action

RmpTm

Output

Loop Single

[50]

[50]

[0.1]

[100] Reverse

[2]

SALL Signal

SAT

System Cooling Enabled

Input[1]

Input[2]

Input[3]

Output

AND / AND

Dehumid Call

SALL Signal

Dehumidification

AHU Humidifier Valve

Dehumid Call

Dehumid Sp

Dehumid Sp

Input[1]

Input[2]

Output

Sub / Sub

[5]

Dehumid Off Sp

Dehumid Off Sp

SF Status

SF Status

Input

Filter

Output

Filter

[0.01]

Input

Filter

Output

Filter

[0.01]

OAT <42F SALL Enab

SALL Enab

Input[1]

Input[2]

Input[3]

Output

Mul / Add

[0]

Input[1]

Input[2]

Output

OR / OR

SF Status

SF Cmd

Input[1]

Input[2]

Output

OR / OR

SF Status

[100]

Dehumid Enable

SASP Minimum

Wrap Rm %RH

Wrap Rm %RH

Wrap Rm %RH

Wrap Rm %RH

SA Low Limit Alarm

[100]

Input[1]

Input[2]

Input[3]

Output

OR / OR

SA Low Temp Alarm

Input[1]

Input[2]

InSel

Output

Select

SFSpeedCmd

SFSpdOvrdEnab

Input[1]

Input[2]

InSel

Output

Select

OADOvrdEnab

OADOvrdEnabValve

SFOvrdEnab

SFOvrdEnabValve

StmVlvOvrdEnab

Input[1]

Input[2]

InSel

Output

Select

Input[1]

Input[2]

InSel

Output

Select

StmVlvCmd

Input

Filter

Output

Filter

[1]

Input[1]

Input[2]

Output

AND / AND

Humidifier Enable

Input

OutMin

OutMax

Output

Limit

[0]

[50]

TmEnb

Input

OnDly

Output

TmRem

On Delay

[15]

[30]

Input[1]

Input[2]

InSel

Output

Select

Controller Software

Page 37: Launching & Sustaining an Energy Savings Initiative

37

Sequence of Operations CVMC Hot Water Upgrade Project:

Barre, Vermont CTI Job # V04355 Hot Water Circulating Pump Start Up

1. The hot water heating circulator pump shall run continuously. The hot water heating circulating pumps will cycle every 200

hours. On a call for start-up the hot water heating circulating pump will ramp up to the preset frequency. If the lead pump

fails to start than the lag pump will enable and an alarm will be initiated. The lead pump is selectable from the graphical user

interface (GUI)

Hot Water Heating System Operation

1. The hot water circulating pump VFD’s will modulate to maintain system differential pressure. Provide a user programmable

set point on the “front-end” for the hot water heating system differential pressure. The hot water circulating pump VFD’s

will not be modulated below the minimum flow set point for the pumps (33%, adjustable from GUI). Provided a user

programmable set point for the hot

water circulator pump VFD minimum flow. When the hot water pump VFD is at the minimum flow set point, the

differential bypass valve will modulate to maintain system differential pressure.(16 psi, adjustable from GUI)

Hot Water Heating System Temperature Control

1. The hot water steam converters will cycle every 200 hours. On a call for switch over, the lag hot water steam converter

motorized butterfly valve shall be opened. When the lag hot water steam converter motorized butterfly valve is opened, the

lead hot water steam converter motorized butterfly valve shall be closed. If the lag hot water steam converter motorized

butterfly valve fails to open an alarm shall be initiated and the lead steam converter motorized butterfly valve shall remain

open. If the lead hot water steam converter motorized butterfly valve fails to close and alarm shall be initiated. The hot

water steam converter steam control valves will modulate in sequence to maintain a hot water supply temperature according

to the following reset schedule:

OA Temp: -30ºF to 50ºF

HWS Temp: 180ºF to 160ºF

OA Temp: 50ºF to 95ºF

HWS Temp: 160ºF to 140ºF

Provide user programmable set points for both reset schedule outdoor air temperature ranges. Provide a user programmable

set point for both hot water heating temperature ranges. Provide a user programmable hot water heating system reset

schedule override.

Perimeter Hot Water Heating System Operation And Control

1. The perimeter hot water circulating pumps shall be enabled when the outdoor air temperature is below set point.(40F,

adjustable from GUI) Provide a

user programmable set point for perimeter hot water circulating pump enable temperature. The perimeter hot water

circulating pumps will cycle every 200 hours. On a call for start-up the hot water heating circulating pump VFD will ramp

up to the preset frequency. If the lead pump fails to start than the lag pump will enable and an alarm will be initiated. The

perimeter circulating pump VFD’s will modulate to maintain system differential pressure. Provide a user programmable set

point on the “front-end for the perimeter heating system differential pressure. (8 psi, adjustable from GUI) The perimeter

circulating pump VFD’s will

not be modulated below the minimum flow set point for the pumps. Provide a user programmable set point for the perimeter

circulator pump VFD minimum flow. When the perimeter pump VFD is at the minimum flow set point, the differential

bypass valve will modulate to maintain system differential pressure. The mixing valve shall modulate to maintain a

perimeter hot water supply temperature according to the following reset schedule.

OA Temp: -30ºF to 50ºF

HWS Temp: 160ºF to 130ºF

Provide user programmable set points for both reset schedule outdoor air temperature ranges. Provide a user programmable

set point for both hot water heating temperature ranges. Provide a user programmable hot water heating system reset

schedule override.

1980 Heating System Operation And Control

Reheat pumps:

The lead reheat hot water circulating pump shall be enabled at all times. If the lead pump fails to start then the lag pump will

enable and an alarm will be initiated. When the outside air temperature falls below the user adjustable setpoint(currently 15F), both reheat pumps will operate at the

same time.

Perimeter pumps:

The lead reheat hot water circulating pump shall be enabled when the outside air temperature falls below the user adjustable

setpoint(currently 45F). If the lead pump fails to start then the lag pump will enable and an alarm will be initiated.

Heat Echangers:

The heat exchanger control valves are currently controlled via a pneumatic control system.

Revise Sequences to Actual Conditions

Page 38: Launching & Sustaining an Energy Savings Initiative

38

Evaluate

Page 39: Launching & Sustaining an Energy Savings Initiative

39

Propose

Page 40: Launching & Sustaining an Energy Savings Initiative

40

Propose

Page 41: Launching & Sustaining an Energy Savings Initiative

41

Create/Validate New Sequences

Page 42: Launching & Sustaining an Energy Savings Initiative

42

Analyze Current Conditions

Page 43: Launching & Sustaining an Energy Savings Initiative

43

Calibrate

Page 44: Launching & Sustaining an Energy Savings Initiative

44

Calibrate

Page 45: Launching & Sustaining an Energy Savings Initiative

45

Calibrate

Page 46: Launching & Sustaining an Energy Savings Initiative

46

Implement New Sequences

Page 47: Launching & Sustaining an Energy Savings Initiative

47

Fine Tuning

Page 48: Launching & Sustaining an Energy Savings Initiative

48

Monitoring Based Commissioning

Page 49: Launching & Sustaining an Energy Savings Initiative

49

Monitoring Based Commissioning

Page 50: Launching & Sustaining an Energy Savings Initiative

50

Monitoring Based Commissioning

Page 51: Launching & Sustaining an Energy Savings Initiative

51

Energy Metrics

Page 52: Launching & Sustaining an Energy Savings Initiative

52

Update Documentation

Page 53: Launching & Sustaining an Energy Savings Initiative

53

Page 54: Launching & Sustaining an Energy Savings Initiative

54

Energy Star Score

34 54

13%

reduction

Page 55: Launching & Sustaining an Energy Savings Initiative

55

Page 56: Launching & Sustaining an Energy Savings Initiative

56

Ongoing Efforts

• Finish AHU SOO upload, debug, and verification

• Chilled Water SOO / Chiller optimization

• New loads for the Templifier

• Building heating hot water SOO

• HVAC operation versus requirements of ASHRAE-170

• AHU-1 off load and optimization

• Pneumatic to digital upgrades

• Shifting AHU loads

• Summer boiler

Page 57: Launching & Sustaining an Energy Savings Initiative

57

Lessons Learned

• Make the commitment

• Engage leadership

• Identify an Energy Champion

• Team-based approach to leverage skills

• Perseverance

• “It really does work”

• Have fun!

Page 58: Launching & Sustaining an Energy Savings Initiative

58

Questions?