Laboratory for Fire Safety Classification of fire resistance in accordance with EN 13501-2:2016 of a timber floor construction made of Staircraft TFSi I-joists, chipboard flooring and gypsum plasterboard ceiling incorporating four DETA and four JCC downlights Classification report Report number YA 2183-1E-RA-001 dated February 10, 2020

Laboratory for Fire Safety€¦ · EN 1363-1:2012 3.2 Test results The construction has been tested using the standard heating curve as defined in EN 1363-1:2012 with heating from

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

  • Laboratory for Fire Safety

    Classification of fire resistance in accordance with EN 13501-2:2016 of a timber floor construction made of Staircraft TFSi I-joists, chipboard flooring and gypsum plasterboard ceiling incorporating four DETA and four JCC downlights

    Classification report

    Report number YA 2183-1E-RA-001 dated February 10, 2020

  • S p o n s o r St a i r c r af t G rou p

    C ol l i e ry Lan e N ort h

    B ayt on Road I nd u s t r i a l E s t at e

    C ov e n t ry , C V 7 9 NW

    U n i t e d K i n g d om

    P r e p a r e d b y P e u tz b v

    Li n d e n l a an 41 , N L- 65 84 A C Mol e n h o e k

    P os t b u s 66 , NL- 65 85 ZH Mook

    T h e N e t h e r l an d s

    N o t i fi e d b o d y N B 22 64

    P r o d u c t n a m e T i m b e r fl oor c on s t ru c t i on

    R e p o r t n u m b e r Y A 2 18 3- 1 E - RA - 00 1D a t e o f i s s u e February 10, 2020R e f e r e n c e J Z / TB r / / Y A 21 83 - 1 E- RA - 0 01R e p r e s e n t a t i v e J . Z w a r t , M S c .A u t h o r T . B r z o s k o w s k i , M S c .

    + 3 1 8 5 8 2 2 8 6 2 1

    t . b r z o s k o w s k i @ p e u t z . n l

    T h i s c l a s s i fi c a t i o n r e p o r t , c o n t a i n i n g 8 p a g e s a n d a n A p p e n d i x c o n t a i n i n g 1 2 p a g e s , c a no n l y b e u s e d a n d r e p r o d u c e d a s a n e n t i t y .

    Laboratory for Fire Safety

    Classification of fire resistance in accordance with EN 13501-2:2016 of a timber floor construction made of Staircraft TFSi I-joists, chipboard flooring and gypsum plasterboard ceiling incorporating four DETA and four JCC downlights

    peutz bv, postbus 66, 6585 zh mook, +31 85 822 86 00, [email protected], www.peutz.nl

    All orders are accepted and executed according to 'De Nieuwe Regeling 2011' (The New Rules)

    BTW NL004933837B01 KvK: 12028033

    mook – zoetermeer – groningen – düsseldorf – dortmund – berlijn – leuven – parijs – lyon – sevilla YA 2183-1E-RA-001 2

  • 1 I n t r o d u c t i o n

    This classification report defines the fire resistance classification assigned to a timber floorconstruction made of Staircraft TFSi I-joists, chipboard flooring and gypsum plasterboardceiling incorporating four DETA and four JCC downlights. The system was tested in the PeutzLaboratory for Fire Safety in Mook using the standard heating curve and in accordance withthe procedures given in EN 13501-2:2016.

    For performing the testing and classification, the Laboratory for Fire Safety is recognized by the ''Stichting Raad voor Accreditatie'' (RvA).

    The RvA is member of the EA MLA (EA MLA: European Accreditation Organisation MultiLateral Agreement: http://www.european-accreditation.org).

    EA: “Certificates and reports issued by bodies accredited by MLA and MRA members are considered to have the same degree of credibility, and are accepted in MLA and MRA countries.”

    YA 2183-1E-RA-001 3

  • 2 D e t a i l s o f t h e c l a s s i fi e d s y s t e m

    2.1 G e n e r a l

    The element, is defined as a loadbearing floor with fire separating function according toEN 13501-2:2016, paragraph 7.3.3. The floor has been classified for the fire applied frombelow only.

    2.2 P r o d u c t d e s c r i p t i o n

    The element, a timber floor construction made of Staircraft TFSi I-joists, chipboard flooringand gypsum plasterboard ceiling incorporating four DETA and four JCC downlights is fullydescribed in the test report listed in table 3.1.

    The Staircraft TFSi I-joists are 220 mm high, made of two rectangular timber flanges of47 mm x 47 mm connected to each other with 11 mm thick OSB4 board. The Staircraft TFSiI-joists were positioned at 600 mm centres. The web at the end of the Staircraft TFSi I-joistswas filled from both sides with MDF 'end blocks' (48 mm x 123 mm x 18 mm).On the top of the Staircraft TFSi I-joists a flooring of chipboard 22 mm thick (full board1800 mm x 600 mm) has been applied. Under the Staircraft TFSi I-joists a ceiling of gypsum plasterboard (12.5 mm, British Gypsum,GYPROC Wallboard, type A) has been mounted (full board 2400 mm x 1200 mm). The jointsbetween the boards were filled with joint filler which was also used to cover the heads of thescrews. The perimeter joints (bearing sides) between the floor construction and thesupporting construction were filled with intumescent sealant. Four DETA (2 x L1701WH4, 1x L1680, 1 x L1682) and four JCC (2 x JC94113WH,2 x JC1001/WH) downlights were incorporated in the gypsum plasterboards fitted through70 mm diameter apertures drilled in the ceiling.At the request of the sponsor an extra load of 106 kg/m2 has been applied during the test.For the purpose of the supporting construction a frame work made of aerated concrete(class G4/600), respectively 200 mm thick in the vertical direction (bearing sides) and150 mm thick in the longitudinal direction (free edges), has been used.

    For more details of the layout of the construction please refer to the drawing in Appendix 1.

    YA 2183-1E-RA-001 4

  • 3 R e p o r t a n d t e s t r e s u l t s i n s u p p o r t o f t h e c l a s s i fi c a t i o n

    3.1 U s e d r e p o r t

    An overview of the report used is given in Table 3.1. The client has stated that the reportprovided may be used for this classification report.

    t3.1 Used report

    Name of laboratory Name of sponsor Reports reference number and date Used methods

    Peutz bv Staircraft Group Ltd Test report Y 2183-3E-RA-001 dated February 4, 2020EN 1365-2:2014

    EN 1363-1:2012

    3.2 T e s t r e s u l t s

    The construction has been tested using the standard heating curve as defined inEN 1363-1:2012 with heating from below.

    The summary of the test results achieved is shown in Table 3.2. The test was finished after45 minutes, all criteria has been attained.

    t3.2 Test results

    Test standard Parameter Result

    EN 1363-1:2012 Loadbearing capacity (R) 45 min

    EN 1365-2:2014 Integrity (E) 45 min (due to reaching R)

    Thermal insulation (I) 45 min

    YA 2183-1E-RA-001 5

  • 4 C l a s s i fi c a t i o n a n d fi e l d o f a p p l i c a t i o n

    4.1 R e f e r e n c e o f c l a s s i fi c a t i o n

    This classification has been carried out in accordance with Clause 7.3.3 of EN 13501-2:2016.

    4.2 C l a s s i fi c a t i o n

    The element, a timber floor construction, is classified according to the followingcombinations of performance parameters and classes as appropriate.

    Fire resistance classification

    REI 45 RE 30*

    *A classification RE 45 is not possible according to EN 13501-2:2016

    4.3 F i e l d o f a p p l i c a t i o n

    This classification is valid for the construction given on the drawings in Appendix 1 and thedescription given in Chapter 2.2. The field of application is based on the direct field ofapplication in accordance with the test standard EN 1365-2:2014. The test results are directlyapplicable to a similar untested floor or roof construction with the following end useapplications.

    4.3.1 C o n s t r u c t i o n e l e m e n t

    The span of the construction may be increased or decreased, the spacing of the StaircraftTFSi I-joists may be decreased, or the depth and flange size of the Staircraft TFSi I-joistsincreased, provided that the maximum moments and shear forces on the Staircraft TFSiI-joists, considering the load applied in practise, are not greater than those tested(106 kg/m2), when calculated on the same basis in the fire condition.

    4.3.2 T h e d i m e n s i o n c r o s s w i s e t o t h e s p a n d i r e c t i o n

    The dimension perpendicular to the span direction may be increased or decreased providedthat the spacing of the Staircraft TFSi I-joists is not greater than 600 mm.

    YA 2183-1E-RA-001 6

  • 4.3.3 B o a r d s o f t h e c e i l i n g

    The maximum size of boards of the ceiling is 2450 mm x 1250 mm, provided that the numberof fixings per square meter remains at least the same as tested. The boards shall be of thetype British Gypsum, Gyproc Wallboard, Type A, 12.5 mm.

    4.3.4 C a v i t y

    The height of the cavity between the ceiling and the flooring may be increased but witha minimum Staircraft TFSi I-joists height of 220 mm. No extra material may be added to thatcavity.

    4.3.5 F i t t i n g s

    D E T A d o w n l i g h t s a n d J C C d o w n l i g h t s

    The centre-to-centre distance between 2 random fittings shall be no less than 600 mm in thedirection parallel to the joists and no less than than 600 mm in the direction perpendicularto the joists. Alternatively the downlights may be spaced closer than 600 mm perpendicularto the joists provided that the spacing is adjusted accordingly in the parallel direction suchthan the density of downlights per m2 is no greater than one downlight per ca. 1.5 m2 for theentire ceiling area. The distance between a downlight and a joint of the gypsum board shallbe at least 200 mm measured from the centre of the downlight. The diameter of the holes inthe gypsum boards for the installation of the downlights shall not exceed 70 mm.

    YA 2183-1E-RA-001 7

  • 5 L i m i t a t i o n s

    This classification document does not represent type approval of certification of this product.

    Mook,

    J. Zwart, MSc.

    Deputy Head of Laboratory for Fire Safety

    D.J. den Boer, BSc.

    Management

    This report contains 8 pages and 1 appendix:Appendix 1 Drawings of the classified system.

    YA 2183-1E-RA-001 8

  • Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.1

  • Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.2

  • Interior Lighting

    Deta Electrical Company Ltd. Luton Bedfordshire UK

    Tel. +44 1582 544 548 [email protected] DS0174 – NPD 0523 V1.1 01/2020

    LED Fire Rated Downlights Non Dimmable

    Description A range of non dimmable low energy LED fire rated downlights in two versions, fixed and bathroom, and three finishes of white, chrome and satin chrome.

    Standards EN 60598 Safety

    BS 476-21 Fire rating

    BS EN 140-3 Acoustic - airborne

    BS EN 140-6 Acoustic - impact

    BS 5250 Control of Condensation

    Features ● Quarter turn screw fix bezel ● Fixing spring suitable for single or double

    thickness plasterboard ● Large terminal block for looping T&E cable ● Supplied with non dimmable, branded LED

    lamp ● Two lamp colour temperatures available,

    4000K and 2800K ● Insulation separator allows insulation material

    to be laid over the top ● Intumescent disk provides fire rating

    mechanism ● Gasket prevents air movement through fitting

    (BS 5230 Control if Condensation) and reduces passage of sound (Part E of Building Regs.)

    ● 2-year guarantee

    Technical Specification Voltage rating 240Vac Lamp Fixed & Tilt – 50W (max.)

    IP65 – 35W (max.) IP rating Fixed IP20 Bathroom IP65 Fire rating 30, 60 and 90 mins. Class II double insulated Dimmable No Precautions Do not pack insulation

    material around fitting No user serviceable parts

    Dimensions Fixed IP65

    Cut out Ø 70-75 70-75

    Min. Void depth

    140 140

    Bezel Ø 86.5 86.5 All dimensions in mm

    Range 4000K lamp colour temperature

    LED Low Energy Fixed White L1680WH4

    LED Low Energy Fixed Chrome L1680CH4

    LED Low Energy Fixed Satin Chrome L1680SC4

    LED Low Energy IP65 White L1682WH4

    LED Low Energy IP65 Chrome L1682CH4

    LED Low Energy IP65 Satin Chrome L1682SC4

    2800K lamp colour temperature

    LED Low Energy Fixed White L1680WH3

    LED Low Energy Fixed Chrome L1680CH3

    LED Low Energy Fixed Satin Chrome L1680SC3

    LED Low Energy IP65 White L1682WH3

    LED Low Energy IP65 Chrome L1682CH3

    LED Low Energy IP65 Satin Chrome L1682SC3

    Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.3

  • Fire Rated Downlights IP65 Dimmable

    A range of low energy LED GU10 fire rated downlights, dimmable and IP65 as standard, suitable for all indoor applications. This ergonomic design incorporates innovative features offering a blend of aesthetics and enhanced performance.

    Features ● Dimmable and IP65 as standard, suitable

    for all indoor applications ● Spring loaded GU10 lamp holder allows

    for easy lamp replacement and accommodates LED lamps of varying heights (PATENT FILED)

    ● Bespoke terminal housing allows insulation to be laid directly over the top of the fitting

    ● Large terminal housing provides additional wiring space and houses screwless terminal block for looping twin and earth cable

    ● Top and side vents maximize heat dissipation to ensure longevity of the lamps

    ● Two lamp options - 4000K and 2800K, optimized for use with DETA Dimmers

    ● Twist and lock bezel in Matte White, Chrome and Satin Chrome finishes

    ● Fixing spring suitable for single or double thickness plasterboard

    ● Fire rating compliance for 30,60 (Part B of Building Regs.)

    ● Gasket prevents air movement through fitting (BS 5250 Control of Condensation) and reduces passage of sound (Part E of Building Regs.)

    Range

    L1701WH3 LED FR Fixed IP65 Dimmable 2800K White L1701CH3 LED FR Fixed IP65 Dimmable 2800K Chrome L1701SC3 LED FR Fixed IP65 Dimmable 2800K Satin Chrome

    L1701WH4 LED FR Fixed IP65 Dimmable 4000K White

    L1701CH4 LED FR Fixed IP65 Dimmable 4000K Chrome

    L1701SC4 LED FR Fixed IP65 Dimmable 4000K Satin Chrome

    Technical Specification

    Voltage rating 240V AC 50 Hz

    Lamp GU10 LED IP rating IP65

    Fire rating 30, 60 aminutes Electrical lass 1 Dimmable Dimmable lamp supplied Cut out Ø 70-75mm

    Standards

    BS EN 60598-1 Safety

    BS EN 60598-2-2 Recessed Luminaires – Particular Requirements

    BS EN 1365-2 Fire Resistance BS 5250 Control of Condensation

    DS0234 – NPD 0569 V1 07/19

    Deta Electrical Company Ltd. Kingsway House Laporte Way

    Luton Bedfordshire LU4 8RJ UK Tel. +44 1582 544 548 [email protected]

    Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.4

  • Fireguard Mains IP20 Recessed Twist & Lock Downlight 50WUnlamped White

    JC94113WH

    Features & Benefits• Twist & Lock lamp retainer for easy lamp removal• Fire-rated 240V 50W MAX downlights, maintaining the fire-rating of ceilings• Press-fit terminal, loop-in/loop-out• Lamp not supplied

    General InformationProduct Group Fire-rated downlights

    Product Range Fireguard

    Trade Name Fireguard

    Lighting Product Type Fired Rated Downlights

    Product Shape Round

    Mounting Recessed

    Product Weight 0.254kg

    Color Finish White

    Overall Dimensions 103.5 x 85 mm

    Recommended Product Location indoor use only

    Minimum Void Requirement 150mm

    Method Of Fix Spring clips

    Product Aperture Size 74mm

    JCC Lighting

    Innovation Centre, Beeding Close, Southern Cross

    Trading Estate, Bognor Regis, West Sussex, PO22 9TS

    Company Registration Number: 03044848 | VAT Number: 918544112

    T: 01243 838999 | F: 01243 838998 | [email protected] | www.jcc.co.uk

    Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.5

  • IP Rating IP20

    Environment Indoor

    Suitable For Zones Outside Zone 2

    Lamp Supplied No

    Distance From Lighted Object 0.5m

    Origin Of Manufacture PRC

    Warranty 2 year standard warranty (See Website for terms and conditions)

    ElectricalVoltage Rating 220-240

    Operating Frequency (Hz) 50/60Hz

    Luminaire Circuit Wattage 50W max

    Class Class II, double insulated with earth provision

    Input Electrical Connections Live(Brown)Neutral(blue) with earth provision - Loop in/Loop out press fit terminal

    Dimmable Check with lamp manufacturer

    Lampholder GU10 cap

    ThermalsRoom Ambient Temperature Not ToExceed

    26°C

    Room Ambient Temperature 25°C

    Insulation Coverage see instruction sheet

    Minimum Free Air Space At least 75mm around fitting

    Performance DataEnergy Rating This luminaire is compatible with bulbs of the energy class A+ to E

    ConstructionPrimary Material Steel

    Rim Or Attachment Die-cast aluminium

    PackagingLuminaire Carton Dimensions 125 x 125 x 90 mm

    Quantity Per Outer Carton 40

    Bar Code EAN Number 5052544047411

    Packaged Weight 0.299kg

    Standards & ApprovalsListings CE

    Listings Fire Rating

    Manufactured In Accordance To BS EN 60598-2-1, 2-2

    CE Marked Yes

    JCC Lighting

    Innovation Centre, Beeding Close, Southern Cross

    Trading Estate, Bognor Regis, West Sussex, PO22 9TS

    Company Registration Number: 03044848 | VAT Number: 918544112

    T: 01243 838999 | F: 01243 838998 | [email protected] | www.jcc.co.uk

    Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.6

  • Batch Coded yes

    WEEE Symbol yes

    Certificate Of Conformity Available on request

    Accredited Members LIA, ISO9001:2015, ISO14001:2015

    JCC Lighting

    Innovation Centre, Beeding Close, Southern Cross

    Trading Estate, Bognor Regis, West Sussex, PO22 9TS

    Company Registration Number: 03044848 | VAT Number: 918544112

    T: 01243 838999 | F: 01243 838998 | [email protected] | www.jcc.co.uk

    Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.7

  • JCC Lighting

    Innovation Centre, Beeding Close, Southern Cross

    Trading Estate, Bognor Regis, West Sussex, PO22 9TS

    Company Registration Number: 03044848 | VAT Number: 918544112

    T: 01243 838999 | F: 01243 838998 | [email protected] | www.jcc.co.uk

    Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.8

  • V50 Fire-rated LED downlight 7W 650lm IP65 WHJC1001/WH

    Features & Benefits• Two colour selectable from below the ceiling, 3000K & 4000K• Ultra-low profile suitable for shallow 50mm ceiling voids• Fully fire-rated for 30, 60 and 90 minute ceilings• IP65, suitable for bathrooms (internal use only)• Strong protected spring clips• Fast, push-fit termination with remote driver• Triac dimmable as standard (recommended dimmer list on JCC website)• Twist & lock bezel design• Available as complete fixture (JC1001) or without bezel (JC1001/NB)• JC1001/NB requires separate bezel (JC1006)

    General InformationProduct Group Fire-rated Downlights

    Product Range V50

    Trade Name V50

    Light Source LED

    Light Source Features Colour Selectable

    Lighting Product Type Fired Rated Downlights

    Product Shape Round

    Mounting Recessed

    Product Weight 0.29kg

    JCC Lighting

    Innovation Centre, Beeding Close, Southern Cross

    Trading Estate, Bognor Regis, West Sussex, PO22 9TS

    Company Registration Number: 03044848 | VAT Number: 918544112

    T: 01243 838999 | F: 01243 838998 | [email protected] | www.jcc.co.uk

    Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.9

  • Color Finish White

    Overall Dimensions Ø84 x 67.7

    Overall Dimensions (mm) Rim Ø84

    Recommended Product Location Indoor use only

    Minimum Void Requirement 50mm

    Method Of Fix Recessed with Spring Clips

    Product Aperture Size 70mm

    IP Rating IP65

    Environment Indoor

    Luminaire Accessories Black, Brushed Brass, Brushed Nickel or Chrome Replacement Bezel; Concealer Ring;Converter Plate

    Duration Of Fire Protection (mins) 30/60/90

    Origin Of Manufacture Made In China

    Warranty 2 years standard warranty extends to a 3 year commercial warranty or 5 year domesticwarranty when registered within the first year of purchase (See Website for terms andconditions)

    Dimming Protocol Compatibility Triac

    Driver Manufacturer JCC

    LED Manufacturer/Type Hongli

    ElectricalVoltage Rating 230-240

    Secondary Running Current 175mA

    Operating Frequency (Hz) 50/60Hz

    CC or CV CC

    Luminaire Circuit Wattage 7.5

    Sec - Voltage (V) 36VDC

    Class II

    Input Electrical Connections Push Fit Terminals LEN Loop In/Loop Out

    Dimmable Yes

    Max No. In Run 20

    ThermalsRoom Ambient Temperature Not ToExceed

    30°C

    Insulation Coverage Loosely Cover with Mineral Wool Insulation

    Performance DataEnergy Rating A+

    Actual Lumen Output 600/650

    Lumens Per Circuit Watt 80/87

    LED Life (Hours) (L70) 51000

    JCC Lighting

    Innovation Centre, Beeding Close, Southern Cross

    Trading Estate, Bognor Regis, West Sussex, PO22 9TS

    Company Registration Number: 03044848 | VAT Number: 918544112

    T: 01243 838999 | F: 01243 838998 | [email protected] | www.jcc.co.uk

    Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.10

  • Hours life stated is an indication of expected L70 chip and light output calculations whenoperating in optimum conditions. Product warranty period supports the full productduring the term given. The L70 hours expectancy is not correlated with the full productwarranty term, nor is it a representation of lumen depreciation during the warrantyperiod.

    Color Rendering Index 80-89

    CRI: Ra 80

    Correlated Color Temperature 3000K/4000K

    Light Distribution Detail 60-degree

    LOR (Light Output Ratio) % 100%

    Photometry Available Yes: available on request.

    ConstructionPrimary Material Steel

    Lens PC

    Heat Sink Extruded Aluminium

    Driver Housing Polycarbonate

    Rim Or Attachment Die-cast Aluminium

    PackagingLuminaire Carton Dimensions 12 x 10 x 8.2cm

    Quantity Per Outer Carton 20

    Bar Code EAN Number 5052544081231

    Packaged Weight 0.4kg

    Standards & ApprovalsListings CE

    Listings Fire Rating

    Manufactured In Accordance To BS EN 60598:2015, 2-1, 2-2

    CE Marked Yes

    Batch Coded Yes

    Certificate Of Conformity Yes: available on request.

    Accredited Members LIA, ISO9001:2015, ISO14001:2015

    JCC Lighting

    Innovation Centre, Beeding Close, Southern Cross

    Trading Estate, Bognor Regis, West Sussex, PO22 9TS

    Company Registration Number: 03044848 | VAT Number: 918544112

    T: 01243 838999 | F: 01243 838998 | [email protected] | www.jcc.co.uk

    Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.11

  • JCC Lighting

    Innovation Centre, Beeding Close, Southern Cross

    Trading Estate, Bognor Regis, West Sussex, PO22 9TS

    Company Registration Number: 03044848 | VAT Number: 918544112

    T: 01243 838999 | F: 01243 838998 | [email protected] | www.jcc.co.uk

    Appendix 1 Drawings of the classified system

    YA 2183-1E-RA-001 1.12

    1 Introduction2 Details of the classified system2.1 General2.2 Product description

    3 Report and test results in support of the classification3.1 Used report3.2 Test results

    4 Classification and field of application4.1 Reference of classification4.2 Classification4.3 Field of application4.3.1 Construction element4.3.2 The dimension crosswise to the span direction4.3.3 Boards of the ceiling4.3.4 Cavity4.3.5 FittingsDETA downlights and JCC downlights

    5 Limitations