Knight School
Silent Knight Software SuiteIntelliknight™ Training
Module 2
Knight SchoolKnight School
SystemSystem
Summary of all the SBUS Modules and addressable
points in your program
Knight SchoolKnight School
Left click, right click on Module�Select Add
Add SBUS ModuleAdd SBUS Module
2
Knight SchoolKnight School
Add SBUS ModuleAdd SBUS Module
Select the type of SBUS Module to add from the list provided
Knight SchoolKnight School
SBUS Module IDSBUS Module ID
Left click, right click to change address of the SBUS Module�Select from 1 to 31
Knight SchoolKnight School
Can see the SBUS Module you added
Can Edit SBUS
Module�Such as the name
SBUS Module AddedSBUS Module Added
3
Knight SchoolKnight School
SystemSystem
Identify what you want to look at�Check options
Can be sorted
Knight SchoolKnight School
Input ZonesInput Zones
Screen for adding �Zones
�Programming zone
�Zone characteristics
Programming � Input points
�Detectors
�Pull Stations
�Monitor, Minimon
Knight SchoolKnight School
Left click, right click to add more zones�Enter starting
number
� Indicate number of
zones
�Can have up to 125
zones
Adding a ZoneAdding a Zone
4
Knight SchoolKnight School
Left click, right click to change the name of a zone� Example = First Floor
� Name will show when you have an alarm
Naming a ZoneNaming a Zone
Knight SchoolKnight School
2 Count � 2 detectors to activate an alarm
� Waterflow and Pull Station are still instant
Alarm Verification� One detector has to go into alarm
twice
� First time FACP resets
Positive Alarm Sequence � 15 second delay on alarm
� Giving someone with authority, time to active a PAS input for additional
180 seconds
�NFPA 72 6.8.1.3.1.2
� Otherwise goes into alarm
Detector CharacteristicsDetector Characteristics
Knight SchoolKnight School
Single Interlock�Two addressable detectors
�Or manual release switch
Double Interlock� Interlock switch
�Combination of two
�Addressable detectors
�Manual release switches
Detector CharacteristicsDetector Characteristics
5
Knight SchoolKnight School
Heat Sensor� left click, right click to
select
�Can adjust heat sensor
threshold
�135F – 150F Hochiki
�135F – 190F SK-Heat-HT
Zone CharacteristicsZone Characteristics
Knight SchoolKnight School
Cadence�Left click, right click to
select drop down
�Left click select Cadence
�Constant
� March Code
�ANSI Temporal 3
�ANSI Temporal 4
�SD500-6SB – Hochiki
�SK Intelligent Sounder Base
Zone CharacteristicsZone Characteristics
Knight SchoolKnight School
Zone CharacteristicsZone Characteristics
Cadence�Left click, right click
to select drop down
�Left click select
Cadence�Constant
� March Code
�ANSI Temporal 3
�ANSI Temporal 4
�SK Intelligent Sounder Base
6
Knight SchoolKnight School
Local zone�Left click, right click to select
�Select “Yes” will not report to Central Station
�Example = dorm rooms, hotel rooms, apartments
�Meant for Sounder Base
Zone CharacteristicsZone Characteristics
Knight SchoolKnight School
Input ZonesInput Zones
Select what points you want to view
Can sort by
different fields
Knight SchoolKnight School
There are two categories�Modules
�Sensors
Editing SLC PointsEditing SLC Points
7
Knight SchoolKnight School
Left click, right click on Name �Up to 20 characters
Editing Input Point NamesEditing Input Point Names
Knight SchoolKnight School
Left click, right click, on the point type�Select its attributes
Editing Point TypesEditing Point Types
Knight SchoolKnight School
Only SLC Module types will be available�Contact Input
�Relay
�NAC
�2-wire Detector module
Editing SLC ModulesEditing SLC Modules
8
Knight SchoolKnight School
Only sensor types will be available�Detector
�Supervisory Detector
�CO/Fire Detector
�Accessory Base
Editing SensorsEditing Sensors
Knight SchoolKnight School
Detector Alarm event
DetectorDetector
Knight SchoolKnight School
Supervisory event�Avoids potential false
alarms
Used in�Assisted Living
�Dorms
�Hotel Rooms
Supervisory DetectorSupervisory Detector
9
Knight SchoolKnight School
COCO\\Fire DetectorsFire Detectors
Both Alarm�CO
�Fire Alarm
Supervisory CO�Fire Alarm
Alarm CO�Supervisory Fire
Both Supervisory�CO and Fire
Knight SchoolKnight School
Add under Sensors�Select base type
Adding Accessory BaseAdding Accessory Base
Knight SchoolKnight School
Sensors are assigned to a zone
Accessory Bases are assigned to a group
SK-DUCT detectors cannot use Single/Multi-
Station and MUST be mapped to a Group�Relay is an independent address
Accessory BasesAccessory Bases
10
Knight SchoolKnight School
Left click, right click under “Accessory Options”Select �Multistation (MST)
�Single (SST)
�System Mappable (SYS MAP)
Accessory OptionsAccessory Options
Knight SchoolKnight School
Apartment, dorm, assisted living…�Detector with sounder base in each room
Hallway
Single StationSingle Station
Knight SchoolKnight School
Hallway
Single StationSingle Station
The hallway detectors are in a zone�Same SLC, separate zone from the room detectors
�All of the hallway detectors can be in the same zone
11
Knight SchoolKnight School
Hallway
Single Station ProgramSingle Station Program
When a detector activates in one room�Only its sounder activates
�Room detectors can all be in the same zone
�Single Station 1 base sounds
Knight SchoolKnight School
When one of the hallway smokes activates� It will activate all mapped outputs
�Per mapping
�Floor above / floor below
�Or the whole facility
Hallway
Single StationSingle Station
Knight SchoolKnight School
When one smoke detector with sounder base activates�All sounder bases in that
zone will activate
Assisted Living Example
Multi Station ProgramMulti Station Program
12
Knight SchoolKnight School
Zone 1 is defaultLeft click, right click Zone and modify what zone you want it to be in
Must add Zone before you can assign it
Assigning Input Points to a ZoneAssigning Input Points to a Zone
Knight SchoolKnight School
What's wrong with picture?
You need another zone to change the
zone number
Assigning Input Points to a ZoneAssigning Input Points to a Zone