56
P321.de System Data Sheet Plaster and Façade Systems Knauf WARM WALL Basis in Solid Construction ETICS with Insulation Materials made of EPS P321a.de With mineral-based render system P321b.de With mineral-based / organic-based render system P321c.de With mineral-based scratch render system P321d.de With organic render system P321e.de With Sandstein-Design wall panels 2018-07 Note on English translation / Hinweise zur englischen Fassung This is a translation of the System Data Sheet valid in Germany. All stated details and properties are in compliance with the regulations of the German standards and building regulations. They are only applicable for the specified products, system components, application rules, and construction details in connection with the specifications of the respective certificates and approvals. Knauf Gips KG denies any liability for applications outside of Germany as this requires changes acc. to the respective national standards and building regulations. Dies ist eine Übersetzung des in Deutschland gültigen Detailblattes. Alle angegebenen Werte und Eigenschaften entsprechen den in Deutschland gültigen Normen und bauaufsichtlichen Regelungen. Sie gelten nur bei Verwendung der angegebenen Produkte, Systemkomponenten, Anwendungsregeln und Konstruktionsdetails in Verbindung mit den Vorgaben der bauaufsichtlichen Nachweise. Die Knauf Gips KG lehnt jegliche Haftung für Einsatz und Anwendung außerhalb Deutschlands ab, da in diesem Fall eine Anpassung an nationale Normen und bauaufsichtliche Regelungen notwendig ist.

Knauf WARM WALL Basis in Solid Construction ETICS with

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Knauf WARM WALL Basis in Solid Construction ETICS with

P321.deSystem Data Sheet

Plaster and Façade Systems

NEW ■Thick layer systems: Basecoat: SM700 Pro up to 10 mm, Lustro up to 15 mm ■Final coat: SM700 Pro up to 10 mm as well as with trowel finish ■Sandstein-Design ■Structural fire protection measures against exposure to fire from the exterior

Knauf WARM WALL Basis in Solid ConstructionETICS with Insulation Materials made of EPSP321a.de With mineral-based render systemP321b.de With mineral-based / organic-based render systemP321c.de With mineral-based scratch render systemP321d.de With organic render systemP321e.de With Sandstein-Design wall panels

2018-07

Note on English translation / Hinweise zur englischen FassungThis is a translation of the System Data Sheet valid in Germany. All stated details and properties are in compliance with the regulations of the German standards and building regulations. They are only applicable for the specified products, system components, application rules, and construction details in connection with the specifications of the respective certificates and approvals.Knauf Gips KG denies any liability for applications outside of Germany as this requires changes acc. to the respective national standards and building regulations.

Dies ist eine Übersetzung des in Deutschland gültigen Detailblattes. Alle angegebenen Werte und Eigenschaften entsprechen den in Deutschland gültigen Normen und bauaufsichtlichen Regelungen. Sie gelten nur bei Verwendung der angegebenen Produkte, Systemkomponenten, Anwendungsregeln und Konstruktionsdetails in Verbindung mit den Vorgaben der bauaufsichtlichen Nachweise.Die Knauf Gips KG lehnt jegliche Haftung für Einsatz und Anwendung außerhalb Deutschlands ab, da in diesem Fall eine Anpassung an nationale Normen und bauaufsichtliche Regelungen notwendig ist.

Page 2: Knauf WARM WALL Basis in Solid Construction ETICS with

2 P321.de Knauf WARM WALL Basis

ContentsUsage instructions

Notes I Certificates of usability .....................................................................................................................................................3

IntroductionSystem overview .............................................................................................................................................................................4

Data for planningSystem components .......................................................................................................................................................................7Thermal insulation ........................................................................................................................................................................12Fire protection ...............................................................................................................................................................................13Dowelling .......................................................................................................................................................................................25

Construction detailsPlinth application ..........................................................................................................................................................................30Window connection ......................................................................................................................................................................32Window connection I Special details ..........................................................................................................................................33Expansion and connection joints I Balcony and terrace connection ......................................................................................34Connection to roof ........................................................................................................................................................................35

Special versionsCornice profile, ashlar profile ......................................................................................................................................................37

Installation and applicationPreconditions I Machine technology ..........................................................................................................................................38Substrate inspection and preparation ........................................................................................................................................39Insulation panels ..........................................................................................................................................................................40Driving-rain proof window connection profiles .........................................................................................................................43Driving-rain proof window connection profiles I Plaster system .............................................................................................44

UsageMaintenance ..................................................................................................................................................................................51

Material requirementKnauf WARM WALL Basis ...........................................................................................................................................................52

Information on sustainabilityKnauf WARM WALL Basis ...........................................................................................................................................................56

Page 3: Knauf WARM WALL Basis in Solid Construction ETICS with

3P321.de Knauf WARM WALL Basis

Usage instructionsNotes I Certificates of usability

Notes on the documentKnauf System Data Sheets are the planning and application basis for the planners and professional installers with the application of Knauf systems. The contained information and specifications, constructions, details and stated products are based, unless otherwise stated, on the certificates of usability (e.g. National Technical Test Certificate (abP) and / or German National Technical Approvals (abZ)) valid at the date they are published as well as on the applicable standards. In addition, design and structural requirements and those regarding building physics (fire protection and sound insulation) are considered. The details shown are solution suggestions intended for general orientation in the subject matter and must be adapted accordingly to suit the constructional features on site. Ancillary trades are only represented schematically.

References to other documentsSystem data sheets

■ WARM WALL Keramik in solid construction with mineral wool and EPS insulation materials as well as ceramic linings, see system data sheet P329.de.

■ WARM WALL Plus in solid construction with mineral wool insulation materials, see system data sheet P323.de.

Product data sheets ■ Observe the product data sheets of the Knauf system components

Intended use of Knauf systemsPlease observe the following:

Caution

Knauf systems may only be used for the application cases as stated in the Knauf documentation. In case third-party products or components are used, they must be recommended or approved by Knauf. Flawless application of products / systems assumes proper transport, storage, assembly, installation and maintenance.

General instructionsBuilding physics requirements must be examined and tested in detail.Thermal bridges must be avoided, see DIN 4108 amendment 2.The assessment of the thermal insulation shall be performed in accordance with DIN 4108-2 and EnEV (German energy saving ordinance).The structural stability of the existing wall must be assured before installation of ETICS. The proof must include all load-bearing and associated elements.Special care must be taken, particularly with the application of the connections.

TermsSplash water zoneThe splash water zone starts with the edge of the ground line or top edge of the covering and has a height of at least 300 mm and generally up to 600 mm. Water from precipitation must be diverted away by constructional measures (gravel bed or layer that interrupts capillary action). Paving stone or paving must be installed with the corresponding slope away from the building and be constructionally separated from the building. Observe the DIN 18533.Explanation of termsIn this system data sheet, the following terms that diverge from the system approvals are used:

■ Finish coat with paint coat / Sandstein-Design instead of a final coatingSound insulationThe weighted sound reduction index Rw,ETICS of the uninterrupted solid wall (without window / door openings) with WARM WALL Basis acc. to abZ Z-33.41-81 or Z-33.43-82 can be determined with the aid of the Knauf Schallschutzprognose-Tools sound insulation forecasting tool (German only):www.knauf.de/schallschutzprognose

Certificate of usabilityKnauf System German National Technical

Approvals

WARM WALL Basis in solid construction with adhesively bonded EPS insulation materials

Z-33.41-81

WARM WALL Basis in solid construction with adhesively bonded and dowel fixed EPS insulation materials

Z-33.43-82

Page 4: Knauf WARM WALL Basis in Solid Construction ETICS with

4 P321.de Knauf WARM WALL Basis

IntroductionSystem overview

Knauf WARM WALL Basis in timber construction with insulation materials made of EPSKnauf WARM WALL Basis is a building authority approved external thermal insulation composite system (ETICS) with insulation materials made of expanded polystyrene (EPS) for new and old buildings. The façade insulation panels are either adhesively bonded to the substrate or additional dowels are applied in addition to adhesive. The panels have end to end joints or a tongue and groove on the long edge. The latter guarantee a safe and fast insulation panel bond with a flat surface. The mortar pocket on the rear avoids thermal bridges as the adhesive does not get into the insulation panel joints. The WARM WALL Basis system can be employed as a not easily flammable system up to the high-rise building limit (determination of the building height is dependent on the respective applicable state building code).Properties

■ Reaction to fire of ETICS depending on the version is not easily flammable (building material class B1) or flammable (building material class B2), refer to table page 14

■ Insulation material thickness: permissible up to maximum 400 mm ■ Sound insulation: With enhanced requirements, the use of elastified insulation materials (EPSe) in conjunction with thick layer plaster systems is recommended

Masonry / concrete with or without plaster

Adhesive

EPS insulation material(with system dowels if necessary)

Basecoat, mat reinforcementPrimers

Finish coat, paint / impregnation is necessary

Plinth connection, e.g. Thermal bridge free with Peri plinth end profile

Plinth insulation panel

Page 5: Knauf WARM WALL Basis in Solid Construction ETICS with

5P321.de Knauf WARM WALL Basis

IntroductionSystem overview

System overviewKnauf System P321a.de

WARM WALL Basis mineral-based

P321b.de WARM WALL Basis mineral-based / organic

P321c.de WARM WALL Basis scratch render

P321d.de WARM WALL Basis organic

P321e.de WARM WALL Basis Sandstein-Design

Description Natural rendering mor-tar made of high-quality mineral-based raw ma-terials and optionally available with marble grains. Robust, durable, open to diffusion with variable render surface. Combined with a miner-al reinforcement layer.

Organically bonded finishing plaster for a more intensive range of colour shades. Combined with a mineral reinforcement layer.

Classic, thick layer mineral-based scratch render system with an open surface structure. Natural self-cleaning effect, very robust sys-tem and highest level of sound insulation.

Synthetic resin bonded, diffusion capable plaster system with low absorption of water. Optional use of silicon resin render, synthetic resin render or silicate render for a larger range of available colour hues.

Wall lining systems with a substrate made of naturally occurring sedimentary structures on a fleece made of natural fibres. Combined with a mineral reinforcement layer.

Reaction to fire/Building material class ETICS Flammable B2, not easily flammable B1 (see from page 13)

Maximum total insulat-ing material thickness t 400 mm

Plaster system layer thickness (reinforce-ment layer and final coat/lining)

4.5 – 20 mm 4.5 – 18 mm Approx. 17 mm 4 – 5 mm 10 – 15 mm

Façade

Adhesive SM700 Pro, SM700, SM300, Pastol, Lustro, Duo-Kleber, Sockel-SM, Speedero KlebeschaumInsulation materials EPS Nut&Feder, Standard, SunJa (grey board with white EPS upper layer)

System dowels (if reqd.) Schlagdübel CNplus 8 insulation anchor nails, Schraubdübel STR U 2G dowelsBasecoat SM700 Pro, SM700, SM300, Sockel-SM, Lustro SM300 Pastol SM700 Pro, SM700,

SM300, Sockel-SMReinforcing mesh 4x4 mm, 5x5 mm Reinforcing mesh Pastol 4x4 mm, 5x5 mmPrimers Isogrund (recommended) Quarzgrund pro – Quarzgrund pro IsogrundFinal coat / lining SM700 Pro SP 260, RP

240 Noblo, Noblo Filz Carrara, MineralAktiv Scheibenputz floated render, MineralAktiv Scheibenputz Dry scratch render

Conni S Addi S Kati S

Mak3 Conni S Addi S Kati S

Sandstein-Design Kleber adhesive and Sanstein-Design Wand-platte wall panels

Coat / sealing Siliconharz-EG-Farbe paint, Autol, Fassadol, Fassadol TSR, Minerol, MineralAktiv Fassaden-farbe paint

Autol, Fassadol Fassadol TSR, Minerol (on Kati S only) MineralAktiv Fassadenfarbe paint

Impregnation (if necessary)

Autol, Fassadol Fassadol TSR, Minerol (on Kati S only) MineralAktiv Fassadenfarbe paint

1x Sandstein-Design Grund primer wand at least 2x Sandstein-Design Versiegelung sealing

Plinth / splash water area

Adhesive Sockel-SM, Sockel-SM Pro, SM700 Pro, SM700, SM700, Duo-KleberInsulation material Sockeldämmplatte 032, Sockeldämmplatte 035Plinth connection (with recessed plinth)

Sockel-Abschlussprofil Peri plinth profile (free of thermal bridges), plinth profile and push on plinth profile

Basecoat Sockel-SM, Sockel-SM Pro, SM700 Pro, SM700, SM700Mesh reinforcement, primer, finish coat / lining and paint

Such as façade (without Mak3), Butz, Sockel-SM Pro, Sockel-SM, Sandstein-Design

Moisture protection Sockel-Dicht (with Sockel-SM Pro as a basecoat and Sockel-SM Pro as a finish coat with a total thickness ≥ 7 mm not required)

Page 6: Knauf WARM WALL Basis in Solid Construction ETICS with

6 P321.de Knauf WARM WALL Basis

IntroductionSystem overview

System variantsEPS insulation materials

Scheme drawing Insulation material Bonding Dowel type

Adhesively bonded acc. to abZ Z-33.41-81 (substrate bond strength ≥ 0.08 N/mm²)

EPS Standard EPS SunJa EPS Nut&Feder

Partial or full surface adhesive application to panel or substrate –

Adhesively bonded and surface flush dowelled under the mesh acc. to abZ Z-33.43-82

EPS Standard EPS SunJa EPS Nut&Feder

Partial or full surface adhesive application to panel or substrate Screw-in dowel or anchor nail

Adhesively bonded and recessed dowelled under the mesh acc. to abZ Z-33.43-82

EPS Standard EPS SunJa EPS Nut&Feder

Partial or full surface adhesive application to panel or substrate

Schraubdübel STR U 2G dowel or Schlagdübel CNplus 8 anchor nail with dowel plate

Adhesively bonded and dowelled through the mesh acc. to abZ Z-33.43-82

EPS Standard EPS SunJa EPS Nut&Feder

Partial or full surface adhesive application to panel or substrate Screw-in dowel or anchor nail

Page 7: Knauf WARM WALL Basis in Solid Construction ETICS with

7P321.de Knauf WARM WALL Basis

Data for planningSystem components

Insulation materialInsulation material Description Rated value of

thermal conductivity λW/(m∙K)

Dimensionsw x l

mm

Application typeAcc. to DIN 4108-10

Insulation material thicknessmm

Façade

EPS Standard 035 white 0.035

500 x 1000 WAP 40 – 400EPS Standard 0341)

Grey 0.034

EPS Standard 0321)

Grey 0.032

EPS SunJa 032 Grey façade insulation panel with white EPS upper layer

0.032 500 x 1000 WAP 80 – 200

EPS Nut&Feder 035 white 0.035

500 x 10002) WAP 60 – 400EPS Nut&Feder 0341)

Grey 0.034

EPS Nut&Feder 0321)

Grey 0.032

Reveal

PF Slimtherm 022High-performance façade insulation panel

0.022

400 x 1200 WAP

20 – 40

0.021 50

PU Slimtherm 024High-performance façade insulation panel

0.026 500 x 1000 WAP 20 – 50

EPS Standard 035 white 0.035 500 x 1000 WAP 20 – 50

EPS Standard 032Grey 0.032 500 x 1000 WAP 20 – 50

Plinth

Sockeldämmplatte 035 plinth insulation panelEPS, white

0.035 500 x 1000 PW 30 – 400

Sockeldämmplatte 032 plinth insulation panelEPS, grey

0.032 500 x 1000 PW 40 – 200

1) Elastification as EPSe on request, maximum thickness 200 mm2) Cover dimension: 485 x 1000 mm

Page 8: Knauf WARM WALL Basis in Solid Construction ETICS with

8 P321.de Knauf WARM WALL Basis

Data for planningSystem components

Insulation material (continued)Insulation material Description Rated value of

thermal conductivity λW/(m∙K)

Dimensionsw x l

mm

Application typeAcc. to DIN 4108-10

Insulation material thickness

mm

Transoms / fire breaks

MW Volamit 040Mineral wool lamella 0.041 200 x 1200 WAP-zh

60 – 300Coated on both sides

MW Brandriegel 035 plus fire breakMineral wool fire break

0.035 200 x 1200 WAP-zg100 – 3001)

Coated on both sides

1) With insulation material thickness > 300 mm MW Brandriegel 035 plus fire break is adhesively full surface bonded in two layers with mineral adhesive.AccessoriesFaçade and ashlar profiles see page 37Thermal resistance Examples

Insulation material Thermal resistance R in (m²∙K)/WInsulation thickness t in mm60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400

EPS Standard / Nut&Feder 035 white 1.71 2.29 2.86 3.43 4.00 4.57 5.14 5.71 6.29 6.86 7.43 8.00 8.57 9.14 9.71 10.29 10.86 11.43EPS Standard / Nut&Feder 034 1.76 2.35 2.94 3.53 4.12 4.71 5.29 5.88 6.47 7.06 7.65 8.24 8.82 9.41 10.00 10.59 11.18 11.76EPS Standard / Nut&Feder 032 1.88 2.50 3.13 3.75 4.38 5.00 5.63 6.25 6.88 7.50 8.13 8.75 9.38 10.00 10.63 11.25 11.88 12.50

From the table, you can read off the thermal conductivity as well as the total thickness of the insulation material of the thermal resistance R using the rated value. The sum of all thermal resistances (plaster, masonry, insulation materials, etc.) is added to the sum of the 0.17 (m²∙K)/W of both thermal transfer resistances for interior and exterior and delivers the thermal transmission resistance. The inverse value of the thermal transmission resistance is the U value.

Page 9: Knauf WARM WALL Basis in Solid Construction ETICS with

9P321.de Knauf WARM WALL Basis

Data for planningSystem components

Final coat / liningCarraraMineral finishing plaster as a modelling plaster. For the creation of diverse textured or brushed final coat textures.Noblo FilzMineral-based, fine grain finishing plaster with 1.0 or 1.5 mm marble grains for fine sponged surface finishes.Noblo, SP 260, RP 240Mineral finishing renders as a floated render texture (Noblo and SP 260) and / or groove render texture (RP 240).SM700 ProThe mineral-based, universal all-rounder for façades and plinths can be sponge finished or freely-textured as a natural white or coloured top coat. A broom finish or trowel finish application of SM700 Pro caters for special highlights on the façade.MineralAktiv Scheibenputz and MineralAktiv Scheibenputz Dry floated rendersIn a system with MineralAktiv Fassadenfarbe paint the mineral floated render offers the highest level of protection against growth of algae and fungi and contributes to the permanent retention of impeccable façades. MineralAktiv Scheibenputz floated render also impresses with its elegant texture.Conni SReady-to-use, paste-like, soiling-resistant silicone resin floated render, highly water-repellent and highly water permeable.

Addi SReady-to-use, paste-like, organically bonded and silicone resin reinforced floated render for intensive colour shades. Very extra-hard wearing, water-repellent and water-vapour-permeable. Kati SReady-to-use, mineral silicate floated render with maximum 5 % organic share, highly water-repellent and highly water permeable.Mak3Classic mineral-based traditional scratch render with a mica additive provides excellent weather protection and a self-cleaning effect thanks to its surface.Sockel-SM Pro, Sockel-SMSystem approved and mineral-based universal all rounder on a cementitious basis for the plinth area. Use as an adhesive and reinforcing mortar as well as a sponged final coat. When using Sockel-SM Pro as a basecoat and render finish with a total render thickness ≥ 7 mm, no additional protection for the render against ground moisture (moisture protection) is necessary.ButzCan only be used in the plinth zone. Coloured stone render with washed plaster effect for surface design in areas subject to wear and tear, e.g. plinth surfaces in the splash water zone.Sandstein-DesignWall lining systems with a substrate made of naturally occurring sedimentary structures on a fleece made of natural fibres.

Characteristics of finish coats / wall linings for plinth and façadeProperties Mineral-based finishing plasters Organic finishing plasters Wall

LiningSilicate render

Silicon resin renders

Resin plasters

Sand-stein- Design

Noblo Filz, Noblo, SP 260, RP 240

SM700 Pro

Mak3 Carrara MineralAktiv Scheibenputz and MineralAktiv Scheibenputz Dry floated renders

Sockel-SM Pro

Sockel-SM

Kati S Conni S Butz Addi S

Binder Lime cement Hybrid binder Cement Potas-sium silicate, disper-sion

Silicone resin emulsion, disper-sion

Polymer disper-sion, silicone resin

Acrylate synthet-ic resin emul-sion

Hydrophobic (water-repellent) ●● ●● ●●●● ●●● ●● ●●●● ●●● ●●●●

Diffusion properties ●●●● ●●●● ●● ●● ●●● ●●● ●● ● ●●Colour shade range ●● ●● ● ● ●● ●●● ●● ●●●● ●●

Resistance to soiling ●●●● ●●●● ●●●● ●●●● ●●● ●●●● ●●● ●●●●

Plinth application ●● ●●●● ● ●● ●●●● ●●●● ● ●●● ●●●● ●● ●●●●

●●●● Ideal●●● Ideal to very well suited●● Very suitable● Suitable

Knauf Farbcenter (colour center)The Knauf Farbcenter provides information on the feasibility and luminosity of colour shades for Knauf paints and paste-like plasters / renders.www.knauf.de/farbservice

Page 10: Knauf WARM WALL Basis in Solid Construction ETICS with

10 P321.de Knauf WARM WALL Basis

Data for planningSystem components

Final coat / lining (continued)Use of finish coats for plinth and façade

Criteria Mineral-based finishing plasters Organic finishing plastersSilicate render

Silicon resin renders

Resin plas-ters

Noblo Filz

Noblo, SP 260

RP 240 SM700 Pro

Mak3 Carrara MineralAktiv Scheiben-putz floated render

MineralAktiv Scheiben-putz Dry floated render

Sockel-SM Pro, Sockel-SM

Kati S Conni S Butz Addi S

SurfacesSponged texture ● ● ●Scratched texture ●Freely styled texture ● ● ● ●Textured floated render ● ● ● ● ● ●

Textured groove render ●

ApplicationBy machine ● ● ● ● ● ● ● ● ● ● ● ●By hand ● ● ● ● ● ● ● ● ● ● ● ●Order informationBucket (paste-like) ● ● ● ● ●Bagged material ● ● ● ● ● ● ● ●

Knauf Farbcenter (colour center)The Knauf Farbcenter provides information on the feasibility and luminosity of colour shades for Knauf paints and paste-like plasters / renders.www.knauf.de/farbservice

Page 11: Knauf WARM WALL Basis in Solid Construction ETICS with

11P321.de Knauf WARM WALL Basis

Data for planningSystem components

Comparison of Knauf façade paintsCriteria Mineral based Organic

Silicate based dispersion Hybrid façade paint Silicone resin paints Silicone-reinforced pure acrylic paint

Minerol MineralAktiv Fassaden-farbe paint

Autol Siliconharz-EG-Farbe paint

Fassadol, Fassadol TSR

Binder Potassium silicate, dispersion Hybrid binder Silicone resin emulsion, dispersion Pure acrylicHydrophobic (water-repellent ) ●●● ●●● ●●●● ●●●● ●●●●

Diffusion properties ●●●● ●●●● ●●●● ●●● ●●Colour shade range ●● ●● ●●● ●● ●●●●Resistance to ageing ●●●● ●●●● ●●●● ●●●● ●●●●Hiding power ●●● ●●●● ●●●● ●●● ●●●●

●●●● Ideal●●● Ideal to very well suited●● Very suitable

Knauf Farbcenter (colour center)The Knauf Farbcenter provides information on the feasibility and luminosity of colour shades for Knauf paints and paste-like plasters / renders.www.knauf.de/farbservice

CoatsSiliconharz-EG-Farbe paintSiliconharz-EG-Farbe paint is especially suitable for equalisation (single coat) of mineral finishing coats with the same colour shade as the render and the paint. Suitable for equalisation of drying-related, weather-related or application-related differences in the colour shade on the finishing coat.AutolAutol is a highly permeable, matt, premium silicon resin self-cleaning effect façade paint. It is ideally suited as two paint coats on mineral and organically bound renders, as well as a top coat in case of different shades of finishing coat and paint. A significant reduction in the adhesion of dirt particles facilitates wash-off of dirt and soiling by the action of precipitation.FassadolFassadol is a highly permeable, matt and highly colour shade fast silicone-reinforced façade paint. It is ideally suited as two paint coats for intensive colour shades on mineral and organically bound renders, as well as a top coat in case of different shades of finishing coat and paint.Fassadol TSRFassadol TSR is a reflection-optimised, diffusion permeable, highly colour shade fast and high coverage silicone reinforced façade paint with a

satin-matt appearance. It is is suitable for applying two coats on white, mineral and organic bonded plaster systems on which a coating with a luminosity < 20 is to be applied.MinerolMinerol is a highly permeable, matt, premium silicate façade paint with organic stabilisers. It is ideally suited as a structure-retaining two coats paint on mineral renders. Minerol bonds by silification with the substrate and is an ideal coating on mineral renders, and on Kati S silicate floated render in case of different shades of finishing coat and paint.MineralAktiv Fassadenfarbe paintMineralAktiv Fassadenfarbe paint is a structure preserving, mineral façade paint on a hybrid binder basis without addition of softeners, solvents and preservatives. The optimised moisture management ensures that MineralAktiv Fassadenfarbe façade paint in a system with MineralAktiv finish coats is ideal in preventing growth of algae and mould. It has a high yield and an elegant mineral appearance.

Explanation of colour codeB P 2 5 7

Luminosity range (here: 70 to 79)BrighteningGreyingColour shade with English designation abbreviations (In this case: Blue Purplish)

Page 12: Knauf WARM WALL Basis in Solid Construction ETICS with

12 P321.de Knauf WARM WALL Basis

Data for planningThermal insulation

Thermal upgrade of common exiting wallsOverview of common existing walls and the required insulation material thicknesses

Existing walls With WARM WALL BasisExterior walls Density Thickness Rated value

of thermal conductivityλ

U value without ETICS system1)

Minimum insulation material thickness t in mmat U value2) ≤ 0.24 W/(m²∙K) acc. to EnEV 2014

Design thermal conductivity λ in W/(m∙K)

Building type kg/m³ mm W/(m∙K) W/(m²∙K) 0.035 0.034 0.032

Concrete 2400200

2.103.40 140 140 140

250 3.15 140 140 140

Solid brick1800 240

0.812.02 140 140 120

1800 300 1.76 140 140 1201800 365 1.54 140 120 120

Vertical coring bricks1200

2400.58

1.63 140 140 120300 1.40 140 120 120

1000240

0.451.37 140 120 120

300 1.16 120 120 120Light vertical coring brick 800 240 0.33 1.08 120 120 120

Lime sandstone KSV 1800240

0.992.27 140 140 120

300 1.99 140 140 120

Lime sandstone KSL 1400240

0.701.85 140 140 120

300 1.59 140 140 120

Light concrete cavity block 1200240

0.601.67 140 140 120

300 1.43 140 120 120

Light concrete solid brick 1000240

0.461.39 140 120 120

300 1.18 120 120 120

Normal-weight concrete cavity block 1800

2400.92

2.18 140 140 120300 1.91 140 140 120

Aerated concrete precision block

800240

0.270.92 120 120 100

300 0.76 120 100 100

500240

0.170.62 100 100 100

300 0.51 80 80 80

1)  Calculated with all wall constructions including 10 mm plaster (gypsum), λ = 0.39 W/(m∙K).2) Reduction using dowels not considered.

Calculation of the required insulation material thicknessAccording to EnEV the required U value for the exterior wall with ETICS system of 0.24 W/(m²∙K) may not be exceeded.The required insulation material thickness can be calculated as follows:

Legend

λInsulation material Design thermal conductivity of the insulating material in W/(m∙K)Urequired U value for exterior walls ≤ 0.24 W/(m²∙K) acc. to EnEV 2014tExisting wall Thickness of the existing wall without ETICS and without plaster in mλExisting wall Design thermal conductivity of the existing wall without ETICS and without plaster in W/(m∙ K)tPlaster Thickness of the plaster in mλPlaster Design thermal conductivity of the plaster in W/(m∙K)

Minimum insulation thickness = 1000 · λ Insulation · [ – – – 0.17 (m²·K)/W ]1

Urequired

t Existing wall

λ Existing wall

t Plaster

λ Plaster

Page 13: Knauf WARM WALL Basis in Solid Construction ETICS with

13P321.de Knauf WARM WALL Basis

Data for planningFire protection

Reaction to fireThe demands on the reaction to fire of the façade lining are defined in the state building codes (LBO) and the corresponding fire prevention regulations of the German states. They are graduated in dependence on the building height and / or building classes.Additional special guidelines or regulations must be observed for special constructions and buildings such as garages, hospitals, meeting halls, residential care homes, schools, shopping centres, etc. Special installation scenarios such as fire walls, building party walls, access galleries, escape routes, fire service passage routes, etc. must be designed as non-combustible according to the state building codes (building material class A according to DIN 4102-1).Building regulation minimum requirements

Height range1) Required fire behaviour of ETICS

Building material class of ETICSacc. to DIN 4102-1

h

Approx. 1 - 3(Low height buildings) h = 0 – 7 m Flammable B2

h

Building class 4 - 5(Medium height buildings) h > 7 – 22 m Not easily flammable B1

h High-rise buildings h > 22 m Non-combustible A2)

1) The specified heights are defined differently in the individual German states. They can be found in the respective state building codes. The height specifications refer to the dimension of the upper edge of the highest floor on which common rooms can be built, measured from the average terrain height (clause 2, paragraph 3 of the Musterbauordnung [German model building code]).

2)  Not possible with WARM WALL Basis; see system data sheet P323.de Knauf WARM WALL PlusBuilding regulation minimum requirements with other building types: see “Technische Systeminformation – WDVS und Brandschutz - Technical system information - ETICS and fire resistance” of the Fachverband Wärmedämm-Verbundsysteme e. V. (German only)

Page 14: Knauf WARM WALL Basis in Solid Construction ETICS with

14 P321.de Knauf WARM WALL Basis

Data for planningFire protection

Reaction to fire (continued)When using Knauf WARM WALL Systems with EPS insulation panels, additional fire protection measures are necessary should the external thermal insulation composite system be configured as a not easily flammable system (B1) according to the building regulation bye-laws. The fire protection measures protect the façade against fires from the exterior (plinth fires) and fires from the interior (room fires).Fire protection measures for WARM WALL Basis as a B1 system

Option RequirementsAdhesive Basecoat Final coat /

liningInsulation material thickness

Reinforcing mesh

Thickness basecoat / finish coat or total plaster thickness

Fire protection measuresPlinth fire

Room fireFire brakes: Lintel

Fire brakes: Lintel + reveal

Fire break: circumfer-ential

Mesh loop

Speedero (adhesive foam)

Mineral-based

Mineral-based

40 – 100 4x4 mm / 5x5 mm ≥ 4 mm ●> 100 – 2001) 5x5 mm ≥ 9 mm ● ●> 100 – 300 5x5 mm ≥ 4 mm / ≥ 2 mm ● ● ● ●> 300 – 400 5x5 mm ≥ 7 mm ● ● ● ●

Organic 40 – 100 4x4 mm / 5x5 mm ≥ 4 mm ●> 100 – 300 5x5 mm ≥ 4 mm / ≤ 2 mm ● ● ● ●> 300 – 400 5x5 mm ≥ 5 mm / ≤ 2 mm ● ● ● ●

Organic Organic 40 – 300 Pastol ≥ 4 mm ● ● ●Pastol (organic)

Mineral based

Mineral based

40 – 100 4x4 mm / 5x5 mm ≥ 4 mm ●> 100 – 2001) 4x4 mm / 5x5 mm ≥ 9 mm ● ●> 100 – 300 4x4 mm / 5x5 mm ≥ 4 mm ● ● ● ●

Organic 40 – 100 4x4 mm / 5x5 mm ≥ 4 mm ●> 100 – 300 4x4 mm / 5x5 mm ≥ 4 mm ● ● ● ●

Organic Organic 40 – 100 Pastol ≥ 4 mm ●> 100 – 300 Pastol ≥ 4 mm ● ● ● ●

Adhesive (mineral-based)

Mineral-based

Mineral-based

40 – 100 4x4 mm / 5x5 mm ≥ 4 mm ●> 100 – 2001) 4x4 mm / 5x5 mm ≥ 9 mm ● ●> 100 – 300 4x4 mm / 5x5 mm ≥ 4 mm ● ● ● ●> 300 – 400 4x4 mm / 5x5 mm ≥ 7 mm ● ●

Organic 40 – 100 4x4 mm / 5x5 mm ≥ 4 mm ●> 100 – 300 4x4 mm / 5x5 mm ≥ 4 mm ● ● ● ●> 300 – 400 4x4 mm / 5x5 mm ≥ 5 mm / ≤ 2 mm ● ●

Sandstein- Design

40 – 100 4x4 mm / 5x5 mm ≥ 4 mm ●> 100 – 300 5x5 mm ≥ 4 mm ● ● ● ●

Organic Organic 40 – 100 Pastol ≥ 4 mm ●> 100 – 300 Pastol ≥ 4 mm ● ● ● ●

1)  Without MineralAktiv Scheibenputz floated render

Note If necessary, an additional fire break is required, see design on page 15.

Additional mechanical fixing of fire breaksSystem variant

Approval Plinth fire

Additional fire break

Room fire

Fire wall

Adhesively bonded Z-33.41-81 ● ○ ○

Adhesively bonded and dowelled

Z-33.43-82 ● ● ● ●

●  Dowelling always necessary○  Dowelling only necessary with MW Brandriegel 035 plus fire brake or mineral wool insulation panels used as fire breaks

Page 15: Knauf WARM WALL Basis in Solid Construction ETICS with

15P321.de Knauf WARM WALL Basis

Data for planningFire protection

Fire resistance against fire from the exterior (plinth fire)Fire break, material and anchoring

■ Fire break made of MW Volamit 040 (mineral wool lamellae) or MW fire break 035 plus (mineral wool panels), installed horizontally around the building, fire break height ≥ 200 mm

■ Full surface adhesion only permissible for the system approved, mineral-based adhesive, e.g. SM300, SM700 Pro, SM700, Sockel-SM or Lustro

■ Dowelling: per element with at least 3x STR U 2G dowels or CNplus 8 insulation anchor nails under the mesh; number of dowels is dependent on the wind load(s)

■ With insulation material thicknesses > 300 mm fire breaks made of MW Brandriegel 035 plus fire break can be applied in two layers (adhesively bonded on full surface with mineral mortar and dowelled in the substrate)

Dimensions in mmFire break made of MW Volamit 040

MW Brandriegel 035 plus

≤ 400 ≤ 400 ≤ 200

1200

100

200

Construction examples and possible divergences are described in detail in the “Technical system information – ETICS and fire resistance“ of the Fachverband Wärmedämm-Verbundsysteme e. V. (German only)

Fire break at height of intermediate ceiling – applicationNon-combustible floor edge deckThe fire break must not be applied directly to the ceiling head (floor edge deck). It is sufficient to apply it in the ceiling area on a solid substrate.

Scale 1:10 I Dimensions in mm

Fire b

reak

heigh

t≥

200

Floor edge deck(non-combustible)

Fire break

Combustible floor edge deckIf a floor edge deck made of combustible insulation materials is located in the vicinity of a fire break, it must exceed the height of the floor deck above and below it by at least 50 mm. If this measure is not possible for technical reasons, the floor edge deck must be removed. Edge decks that have a plaster covering of non-combustible, reinforced plaster systems in a thickness of at least 4 mm are treated in the same way as non-combustible floor edge decks.

Scale 1:10 I Dimensions in mm

Ceilin

g heig

ht≥

50≥

50

Fire b

reak

heigh

t≥

200

Floor edge deck(combustible)

Mineral woolinsulation material

Inside cornersFrom ground level or the foot of other adjacent horizontal building elements up to the upper edge of the fire break at the height of the ceiling of the 3rd storey, Panzereckwinkel reinforced corner angles 70/90 are to be used with building inside corners. The thickness of the reinforcement layer should be referenced in the approvals. If a plinth is offset to the rear when compared to the ETICS to which it is connected above it, you can omit the reinforcing corner angle in the plinth area.

Dimensions in mm

≥ 300

A step or offset of the exterior wall of less than 0.3 m does not need to be considered as an inside corner.

Additional fire breakAn additional fire break is required as the uppermost connection of the ETICS at the transition to the combustible construction products (e.g. roof) at a maximum of 1 m underneath the adjacent combustible construction product. The material corresponds with that of the plinth fire break. The fire break is adhesively bonded along the entire surface with a mineral-based adhesive. Additional dowelling under the mesh is not required with an adhesively bonded system. Dowelling is always required with an adhesively bonded and dowelled system.

■ Mineral wool lamella: Schraubdübel STR U 2G screw-in dowel with Dübelteller SBL 140 plus dowel plate or Schlagdübel CNplus 8 anchor nail with Dübelteller DT 140 dowel plate

■ Mineral wool panels: Schraubdübel STR U 2G screw-in dowel with or without Dübelteller VT 2G dowel plate or Schlagdübel CNplus 8 anchor nail with or without Dübelteller DT 90 dowel plate

Fire resistance against fire from the interior (room fire)Design of the fire break against room fire see page 18.With an adhesively bonded system, mineral wool lamella are only adhesively bonded, however, mineral wool panels are adhesively bonded and dowelled. With an adhesively bonded system and dowelled system, both mineral wool lamella as well as mineral wool panels are adhesively bonded and dowelled.

Page 16: Knauf WARM WALL Basis in Solid Construction ETICS with

16 P321.de Knauf WARM WALL Basis

Data for planningFire protection

EPS insulation panels up to 300 mmFire protection measures against plinth fire

■ Apply a fire break with full surface adhesive and dowelling on the lower edge of the ETICS and / or maximum of 90 cm above the ground level or adjacent, horizontal building elements (e.g. roof parking, etc.)

■ Apply a fire break with full surface adhesive and dowelling at the height of the ceiling of the 1st storey above ground level or adjacent, horizontal building elements, axial spacing ≤ 3 m to the fire break arranged below it; if the spacing is greater, additional fire breaks must be installed

■ Apply a fire break with full surface adhesive and dowelling at the height of the ceiling of the 3rd storey above ground level or adjacent, horizontal building elements, axial spacing ≤ 8 m to the fire break arranged below it; if the spacing is greater, additional fire breaks must be installed

■ Apply full surface adhesive and dowelling for further fire breaks to transitions from the exterior wall to horizontal protruding surfaces (e.g. of openings, passages, arcades), as well as areas exposed to fire from the exterior located on the 1st to 3rd storey.

■ From ground level or the foot of other adjacent horizontal building elements up to the upper edge of the fire break at the height of the ceiling

of the 3rd storey, Panzereckwinkel reinforced corner angles 70/90 are to be used (see page 15); the minimum thickness of the plaster system (reinforcement layer and final coating) can be taken from the table on page 14

Fire protection measures against room fireApply a fire break with full surface adhesive and dowelling above the fire break at the height of 3rd storey and if necessary fire protection measures against room fire (see approvals, section Lintels and reveals or page 18). As the resulting fire resistance measures necessary against a plinth fire extend from the plinth to above the 3rd storey, they include a room fire.Additional fire breakApply an additional fire break with full surface adhesive a maximum of 1 m below the adjacent combustible building products (e.g. on the upper termination of the ETICS underneath the roof) and apply dowels if necessary (see page 15).

Note

In the fire protection zone plinth fire and room fire, a re-spective spacing between the lower edge of the lintels and the lower edge of the fire break of at least 0.5 m must be observed.

Fire break

Additional fire break with axial spacing > 8 m

Fire break

Additional fire break with axial spacing > 3 m

Fire breakSplash water / plinth area

Additional fire break(on transition to combustible

construction products)

Fire break acc. to approval,section Lintels and reveals,

see also pages 18 to 19

1st storey

2nd storey

3rd storey

4rd storey

≤ 1 m

≤ 3 m

≤ 8 m

≤ 0.9

m

Flammable roof

Plint

h fire

prote

ction

zone

Room

fire p

rotec

tion z

one

Ground level or adjacent, used horizontalbuilding elements

Page 17: Knauf WARM WALL Basis in Solid Construction ETICS with

17P321.de Knauf WARM WALL Basis

Data for planningFire protection

EPS insulation panels > 300 mm to 400 mmFire protection measures against plinth fire

■ Apply ETICS with mineral wool insulating material acc. to Z-33.43-82 or Z-33.44-83 in non-combustible design (A2 acc. to DIN 4102-1 or A2-s1, d0 acc. to EN 13501-1) or a non-combustible other exterior wall cladding above a maximum 90 cm high splash water area above ground level or adjacent, horizontal building elements (e.g. roof parking, etc.) used up to the height of the ceiling above the 2nd storey, however, the height must be at least 6 m

■ Apply a fire break with full surface adhesive and dowelling on the lower edge of the WARM WALL Basis (with EPS insulation panels)

■ Apply a fire break with full surface adhesive and dowelling at the height of the ceiling of the 3rd storey above ground level or adjacent, horizontal building elements, axial spacing ≤ 3 m to the fire break arranged below it; if the spacing is greater, additional fire breaks must be installed

■ Apply full surface adhesive and dowelling for further fire breaks to transitions from the exterior wall to horizontal protruding surfaces (e.g. of openings, passages, arcades), as well as areas exposed to fire from the exterior located on the 1st to 3rd storey.

■ From ground level or the foot of other adjacent horizontal building

elements up to the upper edge of the fire break at the height of the ceiling of the 3rd storey, Panzereckwinkel reinforced corner angles 70/90 are to be used (see page 15); the minimum thickness of the plaster system (reinforcement layer and final coating) can be taken from the table on page 14

Fire protection measures against room fireApply a fire break with full surface adhesive and dowelling above the fire break at the height of the 3rd storey and if necessary fire protection measures against room fire (see approvals, section Lintels and reveals or page 18). As the resulting fire resistance measures necessary against a plinth fire extend from the plinth to above the 3rd storey, they include a room fire. Additional fire breakApply an additional fire break with full surface adhesive a maximum of 1 m below the adjacent combustible building products (e.g. on the upper termination of the ETICS underneath the roof) and apply dowels if necessary (see page 15).

NoteIn the fire protection zone plinth fire and room fire, a respective spacing between the lower edge of the lintels and the lower edge of the fire break of at least 0.5 m must be observed.

Non-combustible ETICS with mineral wool insulation material oralt. other non-combustible exterior

wall cladding

Fire break

Additional fire break(on transition to combustible

construction products)

Fire break acc. to approval,section Lintels and reveals,

see also pages 18 to 19

Fire break

Additional fire breakwith axial spacing > 3 m

Splash water / plinth area

1st storey

2nd storey

3rd storey

4rd storey

≤ 1 m

≥ 6 m

≤ 3 m

≤ 0.9

m

Plint

h fire

prote

ction

zone

Room

fire p

rotec

tion z

one

Ground level or adjacent, used horizontalbuilding elements

Flammable roof

Page 18: Knauf WARM WALL Basis in Solid Construction ETICS with

18 P321.de Knauf WARM WALL Basis

Data for planningFire protection

Design of the fire break against room fire ■ Consider fire protection measures against a room fire above the fire break at the height of the ceiling of the 3rd storey (see scheme drawings on page 16 to 17); as the resulting fire resistance measures necessary against a plinth fire extend from the plinth to above the 3rd storey, and they include a room fire

■ Horizontally arranged fire breaks made of MW Volamit 040 (mineral wool lamella) or MW Brandriegel 035 plus fire break must be circumferentially installed around the building as a full surface adhesively bonded configuration on at least every second storey.

■ If dowelling is required for the system (see page 26), the circumferential and full surface adhesively bonded fire breaks are dowelled in each element with 2 dowels fitted in the centre at a spacing of 60 cm under the mesh ▪ MW Volamit 040: Dowel with additional Dübeltellern DT 140 dowel

plates or SBL 140 plus ▪ MW Brandriegel 035 plus fire break: Schraubdübel STR U 2G screw-in

dowel with or without Dübelteller VT 2G dowel plate or Schlagdübel CNplus 8 anchor nail with or without Dübelteller DT 90 dowel plate

■ If the system is only adhesively bonded, fire breaks made of MW Volamit 040 are only adhesively bonded on the full surface and fire breaks made of MW Brandriegel 035 plus fire break require additional dowelling.

■ Edge areas located directly at openings require an additional reinforcement with Gewebeeckwinkel (mesh corner angles)

■ Alternatively, the use of a fire break in the lintel area or a three-sided encapsulation of wall openings is possible with fire breaks in acc. to abZ Z-33.41-81 and Z-33.43-82 (for more detail see “Technische Systeminformation – WDVS und Brandschutz - Technical system information - ETICS and fire resistance” of the Fachverband Wärmedämm-Verbundsysteme e. V. (German only)

Window frame flush with the masonry Window frame in the middle of the masonry

Window frame projected or partly in the insulation level

≥ 30

1)

≥ 20

0

1) See DIN 4108 Amendment 2

> 100

≤ 50

0

Gewebe-eckwinkel meshcorner angle

Fire break

> 100 > 100

Details Scale 1:10 I Dimensions in mm

5th storey

6th storey

7th storey

G P321 d B d i l

View Dimensions in mm

≤ 50

0≥

200Fire break

Page 19: Knauf WARM WALL Basis in Solid Construction ETICS with

19P321.de Knauf WARM WALL Basis

Data for planningFire protection

Design of the fire break against plinth and room fireCircumferential fire break

Remark Scheme drawings

Definition of stories

Stories above ground acc. to clause 2 (6) of the German Model Building Code (MBO).Cellar levels, where the mean cellar ceiling does not extend more than 1.40 metres above ground level, shall not be considered as a floor level (storey), as well as hollow areas (jamb walls) between the top floor and the roofing that cannot be used as common rooms.The height specifications can diverge from one another in the different state building codes.

Two-storey building

On low height buildings (0 – 7 m, see also page 13), possibly excluding special constructions, no additional fire protection measures are required from the point of view of the building codes. In case the ETICS are still to be not easily flammable in design, additional fire protection measures against plinth fire as well as an additional fire break on the connection to the combustible construction products (e.g. roof) are required. Fire protection measures against room fire are already incorporated due to the building height.

With gabled roof (generally flammable)

Plint

h fire

prote

ction

zone

With flat roof (Example: non-combustible)

Plint

h fire

prote

ction

zone

G P321 d BR i h i Fl

≤ 1.40 m

Stor

ies ab

ove g

roun

d

≤ 1.40 m

SF = storey floor Ground level

SF

SF

SF

SF

SF Attic

4th storey

3rd storey

2nd storey

1st storey

Cellar level

Design of the fire break against room fire (continued)Use of Speedero adhesive foam

Remark Scheme drawing

Fire protection measures against a room fire when Speedero adhesive foam is used in conjunction with Pastol basecoat up to an insulation material thickness of 300 mm as a lintel fire break or a lintel and reveal fire break. If the system is applied with Speedero adhesive foam and mineral-based basecoat, from insulation material thickesses of 100 mm, a lintel fire break and a lintel and reveal fire break or circumferential fire break can be used.

Insulation material thickness t ≥ 40 mm, Example: non-combustible roof

Plint

h fire

prote

ction

zone

Room

fire

prote

ction

zone

Page 20: Knauf WARM WALL Basis in Solid Construction ETICS with

20 P321.de Knauf WARM WALL Basis

Data for planningFire protection

Design of the fire break against plinth and room fire (continued)Circumferential fire break (continued)

Remark Scheme drawings

Three-storey building

It is recommended that ETICS on buildings of classes 1 to 3 that are a maximum of three stories should be not easily flammable in their design. This necessitates the application of fire protection measures against a plinth fire as well as an additional fire break at the connection to combustible construction products (e.g. roof). These already cover fire protection measures against room fire due to the building height.

With gabled roof (generally flammable)

Plint

h fire

prote

ction

zone

With flat roof (Example: non-combustible)

Plint

h fire

prote

ction

zone

Four and five storey buildings

On higher buildings above the three-storey plinth fire protection zone, fire protection measures against a room fire are to be considered. An upper additional fire break is only required at the transition to combustible roof constructions.

Example: combustible roof

Plint

h fire

prote

ction

zone

Room

fire

prote

ction

zone

G P321 d BR i h i

Example: non-combustible roof

Plint

h fire

prote

ction

zone

Room

fire

prote

ction

zone

Six-storey building

The fire protection measures against a room fire must be considered if applicable. An upper additional fire break is only required at the transition to combustible roof constructions.

Insulation material thickness t ≤ 100 mm, Example: combustible roof

Plint

h fire

prote

ction

zone

Room

fire

prote

ction

zone

Insulation material thickness t > 100 mm, Example: combustible roof

Plint

h fire

prote

ction

zone

Room

fire

prote

ction

zone

Page 21: Knauf WARM WALL Basis in Solid Construction ETICS with

21P321.de Knauf WARM WALL Basis

Data for planningFire protection

Design of the fire break against plinth and room fire (continued)Circumferential fire break (continued)

Remark Scheme drawings

Different building section heights

On building sections of different heights, the position of the fire break must be planned so that the fire break is at the same height in all parts of the building. Offsets up to a height of 1 m can be negotiated with an "upward" or "downward" offset. Alternatively possible is a complete fire protection related separation of the ETICS in the joint area of both buildings by a vertical and continuous fire break.

With downward offset, Example: combustible roof

Plint

h fire

prote

ction

zone

Room

fire

prote

ction

zone

Offsets with vertical fire break, Example: non-combustible roof

Plint

h fire

prote

ction

zone

Room

fire

prote

ction

zone

Offset exterior wall openings

Exterior wall openings on façades are not always located at the same height and do not always have the same size. Downward offsetRetention of the maximum clearance of 0.5 m above the lintel with windows installed below it can be ensured by a local "downward offset" of the fire break.Upward offsetIn cases where the openings are directly in the horizontal path of the fire break, the fire break must be offset upwards around the opening. The height of the offset must be limited to 1 m.

With downward offset, Example: combustible roof

≤ 0.5

m

With upward offset, Example: non-combustible roof

≤ 1 m

≤ 0.5

m

Continuous strip windows, individual openings

Continuous strip windows on a building that horizontally interrupt the applied ETICS can assume the function of a fire break in the room fire protection zone (insulation material thickness t > 100 mm). Additional inclusion of fire breaks above the continuous strip windows can be therefore omitted. The vertical reveal to which the fire break is joined in the lintel area must be insulated along the entire height with mineral wool. The opening in the structural element for the strip window must have a minimum height of 1 m.Individual openings on each floor, e.g. doors, circumferential fire break, do not require a circumferential fire break. Rather, the fire break must first be continued into the reveal and then continued at the same height.An upper additional fire break is only required at the transition to combustible roof constructions.

Insulation material thickness t > 100 mm, example: combustible roof

Room

fire

prote

ction

zone

Plint

h fire

prote

ction

zone

Reveal insulation:mineral wool

Page 22: Knauf WARM WALL Basis in Solid Construction ETICS with

22 P321.de Knauf WARM WALL Basis

Data for planningFire protection

Design of the fire break against plinth and room fire (continued)Circumferential fire break (continued)

Remark Scheme drawings

Multi-storey, glazed stairwells

If a building features a fire protection staircase acc. to clause 35 of the German Model Building Code (MBO) with cross-floor, multi-storey glazing, the cross-floor "exterior wall" openings must be fully surrounded along the perimeter with mineral wool strips at a minimum width of 200 mm in the same way as the fire break.

Example: combustible roof

Balconies, loggias and access galleries

Exterior areas that project out from the façade, such as slabs from balconies and access galleries and that interrupt the fully horizontal ETICS, assume the function of a fire stop, so that the additional inclusion of fire breaks in this area is unnecessary. The fire break must connect to the side at the level of the cantilever slab. The cantilever slabs must be solid and mineral-based and at least fire resistant (F30 acc. to DIN 4102-2 or alt. REI 30 acc. to EN 13501-2). The cantilever slabs must connect completely to the exterior wall without a gap or with load bearing thermal insulation elements (e.g. ISO-Korbs), that are fire resistance rated (min. F30 acc. to DIN 4102-2 or alt. REI 30 acc. to EN 13501-2, connected with the exterior wall. Otherwise the fire break should be continued preferably under the cantilever slab.

Example: combustible roof

Offsets in the vicinity of the cantilever slabs

With offset ≤ 1 mIf a direct horizontal path for the fire break and cantilever slab is not possible, connection to the side is possible by an upward and downward offset.With offset > 1 mIf the fire break cannot be directly connected to the side of the cantilever slab, or if the cantilever slab as a fire break cannot be used due to the lack of a fire resistance class, the fire break should be continued preferably under the cantilever slab.If continuation of the fire break under the cantilever slab is not possible, e.g. due to an existing roller blind cassette, a non-combustible fire protection board that is at least 10 mm thick can be adhesively bonded and dowelled to the lower side of the cantilever slab in order to achieve the protective objective.

With offset ≤ 1 m

≤ 1 m

With offset > 1 m

> 1 m

Page 23: Knauf WARM WALL Basis in Solid Construction ETICS with

23P321.de Knauf WARM WALL Basis

Data for planningFire protection

Design of the fire break against plinth and room fire (continued)Circumferential fire break (continued)

Remark Scheme drawings

Sloping site

If the façade surfaces are at differing heights, e.g. on slopes, it may be useful to consider the sides of the building separately for fire protection purposes. This can be archived by a fire break that is implemented vertically along the entire height of the building at a spacing of maximum 1 m from the outer corner of the building. On the surfaces separated from one another the respective fire protection measures against a plinth fire, and if necessary, against a room fire must be implemented. On the building sides located in sloped sites, it is necessary to evaluate whether there are areas with an increased fire load. The fire protection measures must be planned accordingly.

Example: combustible roof

Vertical fire break forseparation of the rear

of the building fromother surfaces

Plint

h fire

prote

ction

zone

Plint

h fire

prote

ction

zone

Room

fire

prote

ction

zone

Staggered stories

Fire protection measures against a plinth fire must be implemented with staggered stories if on an adjacent area comparable fire loads such as on a building plinth can occur, e.g. on parking levels. For balconies, loggias or roof terraces used for residential purposes before staggered stories, fire protection measures must not be considered. The corresponding additional fire break is only required at the transition to combustible roofs.

Example: combustible roof

Plint

h fire

prote

ction

zone

Plint

h fire

prote

ction

zone

Room

fire

prote

ction

zone

Parking level

Mixed façades

On mixed façades where different façade systems are applied (ETICS, back-ventilated curtain walls, facing masonry, etc.) adjacent to one another, it is possible that the fire can spread to the ETICS from the adjacent façade system. To prevent the spread of fire to the ETICS, areas of the ETICS must be protected continuously by horizontal fire breaks or vertical fire breaks and be separated from other façade systems.

Example: combustible roof

ETICS

ETICSETICS

Page 24: Knauf WARM WALL Basis in Solid Construction ETICS with

24 P321.de Knauf WARM WALL Basis

Data for planningFire protection

Design of the fire break against plinth and room fire (continued)Circumferential fire break (continued)

Remark Scheme drawings

Dormer features

If dormer windows are part of the roof, i.e. recessed by at least 0.5 m perpendicularly to the façade below them, the application of the upper additional fire break in the dormer area is unnecessary.

< 0.5 m recessed offset, Example: combustible roof

≥ 0.5 m recessed offset, Example: combustible roof

≥ 0.5 m

Three-sided building recesses

ETICS in three-sided building recesses, which are deeper than 1 m and do not exceed 4 m in width, should have non-combustible insulation material applied to the full surface (in accordance with clause 3 in conjunction with clause 14 of the German Model Building Code), and shall apply in particular for window openings of stairwells located in these walls.

Example: combustible roof

Plint

h fire

prote

ction

zone

Room

fire

prote

ction

zone

> 1 m

≤ 4 m

Non-combustibleinsulation material

Expansion joint without embedding firewall

If an expansion joint interrupts a fire break without integrated fire wall, it should be filled completely with mineral wool at a height of at least 1 m above and below the fire break. Additionally on both sides of the expansion joint above and below the fire break, a mineral wool strip with a total width of at least 200 mm must substitute the polystyrene rigid foam.For external sealing of expansion joints against driving rain, materials can be used that are classified as (DIN EN ISO 13943) flammable.

Example: combustible roof

≥ 1 m

≥ 1 m

Room

fire

prote

ction

zone

Plint

h fire

prote

ction

zone

Source: “Technische Systeminformation – WDVS und Brandschutz - Technical system information - ETICS and fire resistance” of the Fachverband Wärmedämm-Verbundsysteme e. V. (German only)

Page 25: Knauf WARM WALL Basis in Solid Construction ETICS with

25P321.de Knauf WARM WALL Basis

Data for planningDowelling

Fire protection, transition of integrated fire wallsFire walls must prevent the spread of fire to other buildings or building sections and must always be considered in the ETICS. They can be interior fire walls for partitioning rooms or for subdividing longer buildings (maximum spacing of 40 m acc. to clause 30 of the German Model Building Code) as well as building party walls acc. to clause 30 of the German Model Building Code. The state building codes must be observed and in individual cases the work must be coordinated with the respective building supervisory authorities.Details Without expansion joint

■ MW Brandriegel 035 plus fire break or MW Volamit 040 should be adhesively bonded on the full surface at the height of the fire wall in a width of at least 20 cm and, if dowelling for the system is required, apply 2 dowels for each element fitted in the centre at a spacing of 60 cm

■ MW Brandriegel 035 plus fire break: Mechanical fastening using Schraubdübel STR U 2G screw-in dowels or Schlagdübel CNplus 8 anchor nails; MW Volamit 040: For dowelling additional Dübelteller DT 140 dowel plates or SBL 140 plus are to be used.

Fire wall

≥ 2001)

MW Volamit 040 orMW Brandriegel 035 plus

With expansion joint ■ On both sides of the fire break MW Brandriegel 035 plus fire break or MW Volamit 040 should be adhesively bonded on the full surface at the height of the fire wall and, if dowelling for the system is required, apply 2 dowels for each element fitted in the centre at a spacing of 60 cm

■ MW Brandriegel 035 plus fire break: Mechanical fastening using Schraubdübel STR U 2G screw-in dowels or Schlagdübel CNplus 8 anchor nails; MW Volamit 040: For dowelling additional Dübelteller DT 140 dowel plates or SBL 140 plus are to be used

■ Fill cavity expansion joints fully with mineral woolFire wall 1 Fire wall 2

MW Volamit 040 orMW Brandriegel 035 plus

Mineral wool backfillFor expansion joint design see

page 34≥ 2001)

Scale 1:10 I Dimensions in mm

1)  Observe regional building authority requirements: Thickness of the vertical fire break ≥ thickness of the entire fire wallSource: “Technische Systeminformation – WDVS und Brandschutz - Technical system information - ETICS and fire resistance” of the Fachverband Wärmedämm-Verbundsysteme e. V. (German only)Fire break design

Remark Scheme drawing

If an expansion joint is located in the middle of a fire wall (usually the case), it must be completely filled with mineral wool. Furthermore, on both sides for the expansion joint vertical mineral wool strips must be applied exceeding the fire wall thickness. The total width is at least 200 mm in this case. If the ETICS are applied using dowels, the mineral wool must also be adhesively bonded and dowelled to the full surface. For integrated fire walls in the splash water area, the vertical fire breaks can be applied up to 300 mm over the adjacent horizontal surfaces or ground level. For external sealing of expansion joints against driving rain, materials can be used that are classified as flammable (EN ISO 13943) at the least.

Example: combustible roof, adhesively bonded and dowelled system

≥ 30

0 mm

Room

fire

prote

ction

zone

Plint

h fire

prote

ction

zone

Source: “Technische Systeminformation – WDVS und Brandschutz - Technical system information - ETICS and fire resistance” of the Fachverband Wärmedämm-Verbundsysteme e. V. (German only)

Page 26: Knauf WARM WALL Basis in Solid Construction ETICS with

26 P321.de Knauf WARM WALL Basis

Data for planningDowelling

Calculation of the number of dowels: refer also towww.knauf.de/duebelrechner

Dowel ratingMethod for determination of wind loadsPractice-based methodSuitable for all building types up to a maximum height of 25 m in wind zones 1 to 3 (Recommended by the German association Fachverband Wärmedämm-Verbundsysteme e. V. in conjunction with the DIBt).Simplified methodIn accordance with EN 1991-1-4 and EN 1991-1-4/NA, the simplified method can be used for a building up to a height of 25 m provided that it is situated on flat terrain up to a height of 800 m above sea level. The height / width ratio must be ≤ 2. The dowel rating acc. to the simplified method is shown on pages 26 to 29. Standard methodIn case of buildings in wind zone 4 and / or buildings exceeding 25 m in height, for disjointed floor layouts or a ratio of height / width > 2, the standard method in acc. to EN 1991-1-4 and EN 1991-1-4/NA must be used.

Overview, dowelling for substrate

Building materials

Building bricksSolid bricks / high-precision clay blocksVertical coring bricksHorizontally perforated bricks

Lime sandstones Solid bricks / perforated bricksSlag bricks Solid bricks / perforated bricksLight concrete Solid bricks / solid blocksMasonry Normal concreteConcrete Normal concrete

EPS

Substrate bond strength < 0.08 N/mm² or not certified

Substrate bond strength ≥ 0.08 N/mm²

No dowelling (Wind suction we ≤ 2.2 kN/m²)

Dowelling under to through the mesh Number of dowels acc. to dowel rating (wind suction we ≤ 2.2 kN/m²)

Standardized substrate without plaster in acc. to the table Non standardized substrate or substrate with plaster

NoteDowel extraction tests will be necessary for dowelling on non-standardized substrates. The basis for the listed rating tables in accordance with the simplified method is the corresponding specified characteristic dowel load bearing capacity (dowel load capacity) NRk. Should the load bearing capacity be lower, an individual rating of the basis of the EN 1991-1-4 and EN 1991-1-4/NA will be required.

Dowel rating, simplified methodSimplified method procedure

Determination of the width of fringe A

see page 27

Reading of the number of dowels from the

table

see page 28

Selection of the dowel length in dependence

on the insulating material thickness

see page 29

Selection of the dowel in dependence on the substrate and type of

installation see page 29

Selection of the wind zone

see page 27

Page 27: Knauf WARM WALL Basis in Solid Construction ETICS with

27P321.de Knauf WARM WALL Basis

Data for planningDowelling

Width

Heigh

t

Length

Width of fringe A:1/5 e or 1/5 f

e = 2 x height or e = lengthf = 2 x height or f = widthThe smallest corresponding value is decisive.

A B A AB

A

1/5 e1/5 f

Determination of the width of fringe A

Dowel rating, simplified method (continued)Wind zones in Germany acc. to EN 1991-1-4/NA

4

Wind zoneInland

Wind zone

1

2Inland, coast and Baltic Sea islands

Wind zone 3Inland, coast and Baltic Sea islands

Wind zone 4Inland, coast and islands of the NorthSea and Baltic Sea

Schleswig-

34

Hamburg3

4

Mecklenburg-Vorpommern

Bremen

Niedersachsen 2Brandenburg

BerlinSachsen-Anhalt

SachsenThüringen

Hessen

Nordrhein-Westfalen

Rheinland-Pfalz 1

BayernSaarland Baden-

Württemberg

2

Holstein

Wind suction forces we in kN/m² acc. to EN 1991-1-4 and EN 1991-1-4/NA acc. to the simplified methodWind zone Region Wind suction forces we in kN/m²

Building height0 to 10 m 0 to 18 m 0 to 25 mFringe A Zone B Fringe A Zone B Fringe A Zone B

1 Inland 0.738 0.550 0.959 0.715 1.106 0.825

2Inland 0.959 0.715 1.180 0.880 1.328 0.990Coast and Baltic Sea islands 1.245 0.935 1.475 1.100 1.623 1.210

3Inland 1.180 0.880 1.401 1.045 1.623 1.210Coast and Baltic Sea islands 1.549 1.155 1.770 1.320 1.918 1.430

4Inland 1.401 1.045 1.696 1.265 1.918 1.430North and Baltic Sea coasts and Baltic Sea islands 1.844 1.375 2.065 1.540 2.286 1.705North Sea islands 2.065 1.540 – – – –

Page 28: Knauf WARM WALL Basis in Solid Construction ETICS with

28 P321.de Knauf WARM WALL Basis

Data for planningDowelling

Dowel rating, simplified method (continued)Dowelling under the meshTable 1: EPS, insulation material thickness t ≥ 40 mm

Wind zone Region Minimum number of dowels per m² acc. to system approval Z-33.43-82Load capacity dowel NRk ≥ 0.45 kN / dowelMaximum ETICS wind load: 2.20 kN/m²Wind loads acc. to EN 1991-1-4 and EN 1991-1-4/NA, simplified methodBuilding height0 to 10 m 0 to 18 m 0 to 25 mFringe A Zone B Fringe A Zone B Fringe A Zone B

1 Inland 6 41) 8 6 10 8

2Inland 8 6 10 8 10 8Coast and Baltic Sea islands 10 8 10 10 14 10

3Inland 10 8 10 10 14 10Coast and Baltic Sea islands 10 10 14 10 14 10

4Inland 10 10 14 10 14 10North and Baltic Sea coasts and Baltic Sea islands 14 10 14 10 – –North Sea islands 14 10 – – – –

1)  Use at least 5 dowels / m² for insulation thickness < 60 mmTable 2: EPS, insulation material thickness t ≥ 120 mm

Wind zone Region Minimum number of dowels per m² acc. to system approval Z-33.43-82Load capacity dowel NRk ≥ 0.50 kN / dowelMaximum ETICS wind load: 2.20 kN/m²Wind loads acc. to EN 1991-1-4 and EN 1991-1-4/NA, simplified methodBuilding height0 to 10 m 0 to 18 m 0 to 25 mFringe A Zone B Fringe A Zone B Fringe A Zone B

1 Inland 6 4 6 6 8 6

2Inland 6 6 8 6 8 6Coast and Baltic Sea islands 8 6 10 8 10 8

3Inland 8 6 10 8 10 8Coast and Baltic Sea islands 10 8 12 8 12 10

4Inland 10 8 12 8 12 10North and Baltic Sea coasts and Baltic Sea islands 12 10 14 10 – –North Sea islands 14 10 – – – –

Table 3: EPSe, insulation material thickness t ≥ 80 mm

Wind zone Region Minimum number of dowels per m² acc. to system approval Z-33.43-82Load capacity dowel NRk ≥ 0.45 kN / dowelMaximum ETICS wind load: 2.20 kN/m²Wind loads acc. to EN 1991-1-4 and EN 1991-1-4/NA, simplified methodBuilding height0 to 10 m 0 to 18 m 0 to 25 mFringe A Zone B Fringe A Zone B Fringe A Zone B

1 Inland 6 4 8 6 8 8

2Inland 8 6 8 8 8 8Coast and Baltic Sea islands 8 8 10 8 10 8

3Inland 8 8 10 8 10 8Coast and Baltic Sea islands 10 8 10 8 10 10

4Inland 10 8 10 8 10 10North and Baltic Sea coasts and Baltic Sea islands 10 10 14 10 – –North Sea islands 14 10 – – – –

Page 29: Knauf WARM WALL Basis in Solid Construction ETICS with

29P321.de Knauf WARM WALL Basis

Data for planningDowelling

Dowel selectionSelection of a suitable dowel

Usage categoriesAcc. to ETAG 014 or EAD 330196-00-0604

Wall material Schlagdübel CNplus 8 insulation anchor nail Schraubdübel STR U 2G dowelSurface flush:Recessed1):

Chi = 0.002 W/KChi = 0.001 W/K

Surface flush:Recessed1):

Chi = 0.002 W/KChi = 0.001 W/K

Load capacity dowel NRk in kN / dowel Load capacity dowel NRk in kN / dowelA Concrete 0.90 1.50

B Solid bricks, limestone blocks, solid brick / blocks made of light concrete 0.75 – 0.90 0.60 – 1.50

C Sand-lime perforated bricks, vertical coring bricks, light concrete hollow blocks 0.50 – 0.75 0.60 – 1.50

D Lightweight aggregate concrete 0.40 0.90E Aerated concrete (P2 – P7) 0.30 0.75

1)  From 80 mm insulation material thickness

Dowel lengths in dependence on the insulation material thickness (Tolerance compensation max. 5 mm)Insulation material thickness

Dowel length

Dowel positionSurface flush / recessed Surface flush / recessedSchlagdübel CNplus 8 insulation anchor nail Schraubdübel STR U 2G dowel

st

New building A, B, C

Old building2) A, B, C

New building D, E

Old building2) D, E

New building A, B, C, D

Old building2) A, B, C, D

New building E

Old building2) E

t s ≥ 35 mm s ≥ 35 mm s ≥ 55 mm s ≥ 55 mm s ≥ 25 mm s ≥ 25 mm s ≥ 65 mm s ≥ 65 mmmm mm mm mm mm mm mm mm mm60 1103) 1303) 1303) 1503) 1153) 1153) 1353) 1553)

80 130 150 150 170 115 135 155 175100 150 170 170 190 135 155 175 195120 170 190 190 210 155 175 195 215140 190 210 210 230 175 195 215 235160 210 230 230 250 195 215 235 255180 230 250 250 270 215 235 255 275200 250 270 270 290 235 255 275 295220 270 290 290 310 255 275 295 315240 290 310 310 330 275 295 315 335260 310 330 330 350 295 315 335 355280 330 350 350 370 315 335 355 375300 350 370 370 390 335 355 375 395320 370 390 390 – 355 375 395 415340 390 – – – 375 395 415 435360 – – – – 395 415 435 455380 – – – – 415 435 455 –400 – – – – 435 455 – –

2)  Including 20 mm old plaster3) Recessed installation not possible, dowels can only be placed surface flushs = anchoring depthCalculation of the dowel length: Anchoring depth s + (possibly 20 mm old plaster thickness + tolerance compensation) + 5 mm adhesive thickness + insulation material thickness t

Page 30: Knauf WARM WALL Basis in Solid Construction ETICS with

30 P321.de Knauf WARM WALL Basis

Construction detailsPlinth application

Minimal integration depth in the soilP321.de-SO-V17 Recessed plinth applicationApplication with Sockel-SM Pro

P321.de-SO-V18 Flush plinth application

Insulation material

If necessary, apply dowel (anchoring in stable substrate)Render system Sockel-SM Pro, t ≥ 7 mm

≤ 40 (see DIN 4108 Amendment 2)

Plinth insulation boardFleece laminated dimpled sheet

Sealing acc. to DIN 18533

Continuous adhesive bead≥ 50 mm with Sockel-SM Pro

Plinth connection profile, e.g. Perie.g. separating tape or separating strip

Fugendichtband FD joint sealing tape recommended withsubsequent installation of plinth insulation boards

Insulation material

Dowel (anchoring in stable substrate)Render system

Fleece laminated dimpled sheet

Sealing acc. to DIN 18533e.g. SM700 Pro

Plinth insulation board

Sockel-DichtSockel-Dicht (on bituminous

sealants)

Scale 1:10 I Dimensions in mm

Page 31: Knauf WARM WALL Basis in Solid Construction ETICS with

31P321.de Knauf WARM WALL Basis

Construction detailsPlinth application

Implemented with perimeter insulationP321.de-SO-V19 Recessed plinth applicationApplication with Sockel-SM Pro

P321.de-SO-V20 Flush plinth applicationApplication with slab and Sockel-SM Pro

Insulation material

Plinth connection profile, e.g. Peri

Dowel (anchoring in stablesubstrate)

Render system Sockel-SM Pro, t ≥ 7 mm≤ 40 (see DIN 4108 Amendment 2)

Fleece laminated dimpled sheetContinuous adhesive bead

≥ 50 mm with Sockel-SM ProSealing acc. to DIN 18533

Plinth insulation board

e.g. separating tape or separating strip

Fugendichtband FD joint sealing tape recommendedwith subsequent installation of plinth insulation boards

Dowel (anchoring in stablesubstrate)

Insulation material

Fleece laminated dimpled sheetPlinth insulation board

Sealing acc. to DIN 18533

Continuous adhesive bead≥ 50 mm with Sockel-SM Pro

Render system Sockel-SM Pro, t ≥ 7 mm

Scale 1:10 I Dimensions in mm

Page 32: Knauf WARM WALL Basis in Solid Construction ETICS with

32 P321.de Knauf WARM WALL Basis

Construction detailsWindow connection

Window in the middle of the masonryP321.de-FE-H1 Horizontal section P321.de-FE-V1 Vertical section

Window exterior flush with masonryP321.de-FE-H2 Horizontal section P321.de-FE-V2 Vertical section

1)  In case driving-rain proofing has not been certified, an additional Fugendichtband FD joint sealing tape must be installed (see detail at P321.de-FE-H2 as well as page 43).

≥ 30(see DIN 4108 Amendment 2)

Gewebeeckwinkel meshcorner angle

Driving-rain proofwindow connection profilee.g. EPS Standard 032(dowel is required)

e.g. EPS Standard 032

AdhesiveInsulation materialRender system

≥ 40

e.g. separating tapeor separating strip

SR tape and FugendichtbandFD joint sealing tape

≥ 30(see DIN 4108 Amendment 2)

Gewebeeckwinkelmesh corner angle

Window connection profile andFugendichtband FD joint sealing tape Adhesive

Insulation materialRender system

≥ 40

e.g. PerfexKeilplatte wedgeSpeederoadhesive foam

e.g. Knaufinstallation adhesive

Scale 1:10 I Dimensions in mm

Notes

Ensure that all openings (interface gaps) are sealed.The window installation and seals are represented schematically – refer to “Guideline on the installation of windows and doors” from the RAL-Gütegemeinschaft Fenster und Haustüren e.V. (German Quality Assurance Association Windows and Doors) or the guideline “Connection of windows and roller blinds with plaster, drywall and external thermal insulation composite systems” (German only) from the Fachverband der Stuckateure für Ausbau und Fassade Baden Württemberg, Germany.

Page 33: Knauf WARM WALL Basis in Solid Construction ETICS with

33P321.de Knauf WARM WALL Basis

Construction detailsWindow connection I Special details

Window before the masonryP321.de-FE-H3 Horizontal section P321.de-FE-V3 Vertical section

1)  In case driving-rain proofing has not been certified, an additional Fugendichtband joint sealing tape must be installed (see detail at P321.de-FE-H2 on page 32 as well as page 43).

≥ 30

Gewebeeckwinkelmesh corner angle

Driving-rain proofwindow connection profile 1)

(see DIN 4108 Amendment 2)

AdhesiveInsulation materialRender system

≥ 40

SR tape and Fugen-dichtband FD joint tape

e.g. separating tapeor separating strip

Scale 1:10 I Dimensions in mm

Scale 1:10 I Dimensions in mmLintel design for sun screening with fire break P321.de-FE-V7 Roller blind P321.de-FE-V8 Roller blindWithout insulation covering Insulation covering > 40 mm

2) See DIN 4108 amendment 2

Additional meshstrips ≥ 400 mm

Plinth protection boardVandalit, fastening withinstallation adhesive

e.g. PU Slimtherm

Plug on profile forplaster base boards

System dowelFull surface adhesive

Fire break

Fire break

Constructionaldowel recommended

> 40

Additional meshstrips ≥ 400 mm

System dowele.g. PU Slimtherm(dowel if necessary), recommended thickness: 60 mm(min. 30 mm)Plinth shielding board Vandalit (fix with installation adhesive to the roller blind cowl)

Mesh cornerangle drip edgeMesh profilerender connection

Notes

Rear-side coating of the plinth protection panel Vandalit as moisture protection is recommended.Ensure that all openings (interface gaps) are sealed.The window installation and seals are represented schematically – refer to “Guideline on the installation of windows and doors” from the RAL-Gütegemeinschaft Fenster und Haustüren e.V. (German Quality Assurance Association Windows and Doors) or the guideline “Connection of windows and roller blinds with plaster, drywall and external thermal insulation composite systems” (German only) from the Fachverband der Stuckateure für Ausbau und Fassade Baden Württemberg, Germany.

Page 34: Knauf WARM WALL Basis in Solid Construction ETICS with

34 P321.de Knauf WARM WALL Basis

Construction detailsExpansion and connection joints I Balcony and terrace connection

Note Observe the “Façade plinth render/External components” (German only), issued by Fachverband der Stuckateure für Ausbau und Fassade Baden-Württemberg, as well as the DIN 18533.

Balcony and terrace connection

Expansion and connection joints

P321.de-BA-V3 Projecting balcony slab P321.de-BA-V4 Projecting balcony slabRecessed plinth application Flush plinth application

Insulation material

Plinth connection profile, e.g. Peri

Plinth insulation board

Adhesive, e.g. Sockel-SM Pro

e.g. separating tape or separating stripPlinth insulation boardInsulation material

Adhesive, e.g. Sockel-SM Pro

Scale 1:10 I Dimensions in mm

Scale 1:5

P321.de-FU-H1 Building expansion joint P321.de-FU-H2 Connection to existing constructional componentNot in the fire wall area

Mineral wool backfillMesh profile expansion joint

Bridging of fire walls with an expansion joint: see details page 25

Joint sealing tape FDMesh profile render connection

Page 35: Knauf WARM WALL Basis in Solid Construction ETICS with

35P321.de Knauf WARM WALL Basis

Construction detailsConnection to roof

Connection to roofP321.de-DA-V1 Eaves connection to roof weatherboarding

P321.de-DA-V10 Steep roof connection to rising wall P321.de-DA-V3 Steep roof connection to rising wallWith flashing With metal connection mesh profile

1)  Refer to “Ausführung luftdichter Konstruktionen und Anschlüsse - Implementing airtight constructions and connections (German only)” issued by the Fachverband der Stuckateure für Ausbau und Fassade Baden-Württemberg, Germany

Boards intended to receive gypsum plasterApplication of full surface adhesive to the top mostinsulation board or in the edge area as a continuous strip> 100 mm1)

Joint sealing tape FD (surrounding the rafters)e.g. separating tape or separating strip

Insulation materialPlinth connectionprofile, e.g. Peri

≥ 20Plinth insulation boardAdhesive

Insulation material

Plinth connection profile, e.g. Peri

Plinth insulation board

Adhesive, e.g. Sockel-SM Pro

e.g. separating tape or separating strip

Scale 1:10 I Dimensions in mm

NoteObserve guideline “Metallanschlüsse an Putz und Wärmedämm-Verbundsysteme - Metal connections to render and external thermal insulation composite systems”, (German only) from the Fachverband der Stuckateure für Ausbau und Fassade Baden Württemberg, Germany as well as the DIN 18533.

Page 36: Knauf WARM WALL Basis in Solid Construction ETICS with

36 P321.de Knauf WARM WALL Basis

Construction detailsConnection to roof

Connection to roof (continued)P321.de-DA-V11 Pitched roof connection to rising wall

P321.de-DA-V5 Verge connection P321.de-DA-V12 Flat roof connection, attic coveringsWhen configured as a not easily flammable ETICS system B1

1)  Refer to “Ausführung luftdichter Konstruktionen und Anschlüsse - Implementing airtight constructions and connections (German only)” issued by the Fachverband der Stuckateure für Ausbau und Fassade Baden-Württemberg, Germany

Plinth connection profile, e.g. PeriInsulation material

≥ 20 mm

Plinth insulation board

Application of full surface adhesive to thetop most insulation board or in the edgearea as a continuous strip > 100 mm 1)

≥ 60(see DIN 4108Amendment 2)

Joint sealing tape FDe.g. separating tapeor separating strip

Insulationmaterial

Scale 1:10 I Dimensions in mm

NoteObserve guideline “Metallanschlüsse an Putz und Wärmedämm-Verbundsysteme - Metal connections to render and external thermal insulation composite systems”, (German only) from the Fachverband der Stuckateure für Ausbau und Fassade Baden Württemberg, Germany as well as the DIN 18533.

Page 37: Knauf WARM WALL Basis in Solid Construction ETICS with

37P321.de Knauf WARM WALL Basis

Special versionsCornice profile, ashlar profile

Cornice profile, ashlar profileApplication instructionsEPS profiles with paintable surface coatings must be adhesively bonded with Flex tile adhesive or Duo-Kleber adhesive in an edge ribbon and dab bonding method (adhesive surface share ≥ 60 %) on a sufficiently set, dry and even reinforcement layer. Seal the transitions.Adhesively bond profile joints with self-adhesive mesh strips (in scope of delivery) and fill the joints with a paste-like joint filler (in scope of delivery).With a projection > 50 mm, a sheet metal cover should be adhesively bonded onto coated profile surface using a special installation and assembly adhesive.Adhesive bonding and fixing of the profiles only on wall surfaces, no connection, e.g. with roof connection.Paint profiles with at least two coats of Autol.Do not use materials that contain solvents.

Details Scale 1:5 I Dimensions in mm

P321.de-EX-V1 Cornice profile, façade area P321.de-EX-V2 Cornice profile, window sill

P321.de-EX-H1 Cornice profile, window opening

Overhang

Façade profileFlex-Fliesenkleber tile adhesiveor Duo-Kleber adhesive(adhesive surface ≥ 60 %)Reinforcement layer withreinforcing meshFinishing plaster

WIndow sill support recommended

Slope ≥ 4 %

Façade profileFlex-Fliesenklebertile adhesive orDuo-Kleber(adhesive surface≥ 60 %)≥ 40

Façade profile

Flex-Fliesenkleber tile adhesiveor Duo-Kleber adhesive (adhesivesurface ≥ 60 %)

When a driving-rain proof window connection profile is installed an additional jointsealing tape is not required.

Example of a stylish façade design

Page 38: Knauf WARM WALL Basis in Solid Construction ETICS with

38 P321.de Knauf WARM WALL Basis

Installation and applicationPreconditions I Machine technology

PreconditionsAll connections and detail features must be clarified before application.The necessary substrate preparation must be undertaken on a case-by-case basis and must be described in full detail in the tender specifications. Substrate tests and possible measures are listed in this System Data Sheet on page 39.The surface of the substrate must be dry, even and free of grease and dust as well as free of any residual substances that may reduce the adhesion. Check the stability of existing coatings (paint coatings and old plasters) and compatibility with adhesive, and remove unstable coatings completely if necessary.Rising damp may not be present. All applied connections must be driving-rain proof. Ensure that all openings (interface gaps) are sealed.The internal plastering and screed works should be completed and the components should be dry enough so that an excessive accumulation of moisture is avoided.

The contractor is solely responsible for inspecting the condition of the substrate and the on-site conditions.The ambient temperature, substrate and material temperature must be at least +5 °C and may not exceed +30 °C during the entire application, drying and setting phase (if Kati is used as a finishing coat, at least +8 °C).Unfavourable weather influences such as high temperatures, wind or direct sunlight can change the application conditions. In case grey insulation panels are used it is necessary to provide sufficient shading, e.g. by provision of nets on the scaffolding until the basecoat is applied.Only cold, clean water (drinking water quality) may be used as mixing water.Water up to a temperature of +30 °C may be used on building sites in spring and autumn.Cover or apply a watertight covering to easily-soiled building components (e.g. window sills) prior to application. Protect surfaces from precipitation and direct sunlight.

Machine technology from Knauf PFT for the application of ETICSProduct Mixing pump /

feed pumpStator / rotor

Mortar hoses Wet mortar pumping distance

Bonding and reinforcement mortar

SM700 Pro, SM700G 4 D4-3 with Rotoquirl Ø 25 mm Up to 40 mRITMO L B4-2L with Rotomix Ø 25 mm Up to 10 m

SM300G 4 D4-3 Ø 25 mm Up to 30 m

RITMO L B4-2L Ø 25 mm Up to 10 mPuMax ex-works Ø 35 + 25 mm Up to 65 m

Sockel-SM Pro, Sockel-SMG 4 D4-3 with Rotoquirl Ø 25 mm Up to 30 mRITMO L B4-2L with Rotomix Ø 25 mm Up to 15 m

Duo-Kleber adhesiveG 4 D4-3 Ø 25 mm Up to 30 mRITMO L B4-2L Ø 25 mm Up to 20 m

LustroG 4 D4-3 Ø 25 mm Up to 40 mRITMO L B4-2L Ø 25 mm Up to 20 m

PastolSWING L / RITMO XL D6-3 Twister Ø 25 mm Up to 30 mSWING M B4-2 Ø 25 mm Up to 10 m

Finishing plasters

Mineral, thin-layer finishing coats (e.g. SP 260, RP 240, MineralAktiv Dry etc.)

G 4 D4-3 Ø 25 mm Up to 30 mRITMO L B4-2L Ø 25 mm Up to 20 m

Scratch render (Mak3)MA-MA ex-works Ø 50 + 35 + 35 + 25 mm Up to 50 mG 4 D6-3 Ø 35 + 35 + 25 mm Up to 36 mPuMax ex-works Ø 50 + 50 + 35 + 35 + 25 mm Up to 65 m

Paste-like finishing coats (e.g. Addi, Kati, Conni, MineralAktiv Scheibenputz floated render)

SWING L / SWING M B4-2L Ø 25 mm Up to 20 m

For further information on machine engineering see: www.pft.de

Page 39: Knauf WARM WALL Basis in Solid Construction ETICS with

39P321.de Knauf WARM WALL Basis

Installation and applicationSubstrate inspection and preparation

Substrate inspection and preparationThe surface of the wall must be flat, dry and free of grease and dust. In case coatings (e.g. Paint coats) are applied to the substrate, it is necessary to professionally assess their compatibility with the adhesive.Unevenness in the substrate up to a maximum of 20 mm can be covered with the adhesive if dowelling is used in addition to adhesive bonding, and with exclusive adhesively bonded systems this value is a maximum of 10 mm. Major unevenness should be equalized using a suitable plaster layer or by staggering the insulation panel thickness. The bond strength of the plaster should be tested after it has set.Substrate inspection and preparation for adhesive application of ETICS

Inspect for Test method Indication Technical instructions and measures

Surface strength

Scratch test with a solid, angular object

Surface is damaged with moderate pressure

Remove loose, crumbling or brittle parts manually or with a machine; soft layers are not a stable substrate for ETICS

Rubbing off by hand Low abrasion Treat the constructional component surface with a plaster reinforc-ing priming layer (Grundol - Siloxane reinforced deep primer E.L.F.)

With strong abrasion, extensive abrasion

Select additional dowelling for the insulation panels; remove the non-stable plaster / coating

Wet until saturation with water and apply scratch test

The surface softens with a wetting capacity spot test

Remove the non-stable plaster / coating

Stability of existing older layers

Cross-cut test Coating components splinter with moderate pressure; scratch impression is jagged or bulged

Remove the old coating / plaster, if necessary use additional mechanical fixing

Compatibility with existing old coating

Tear-off test Detachment1) Remove the old coating / plaster, if necessary use additional mechanical fixing

Moisture1) Visual inspection and scratch test if required

Damp areas, stains, discolouration's are evident

Technical / physical building causes should be remedied on the construction; allow to dry

Blooming (efflorescence)

Visual inspection Usually white salts or leaching of lime deposits

Technical / physical building causes should be remedied on the construction; then allow to dry off and remove dry salt deposits

Moss, algae, mould1)

Visual inspection Green or dark fouling Remove mechanically or by using a high pressure hot water cleaning jet, disinfect the affected area if necessary

Other soiling Visual inspection, haptic test (touch test)

Colour, smearing, tackiness Remove soiling

Absorbency Wetting capacity spot test with water

With high absorbency, quick absorption of water and quick darkening of the surfaces

Highly absorbent substrates or substrates with varying levels of absorbency should be treated with a primer to balance the rates of absorption

1)  Observe further details in acc. with Code of Practice No. 21 “Technische Richtlinien für die Planung und Verarbeitung von Wärmedämm-Verbundsystemen - Technical guidelines for planning and application of external thermal insulation composite systems” issued by the Bundesausschuss Farbe und Sachwertschutz (German only).

For painted façades we always recommend use of constructional dowelling.Bridging expansion joints in the exterior wall surfaces(e.g. the joints in the exterior wall surfaces of large panel construction using three-layer panels, see e.g. abZ Z-33.41-81 and Z-33.43-82)

■ Joint spacings up to 6.20 m ■ Insulation material thickness at least 60 mm ■ Basecoat Lustro or SM700 with reinforcement mesh 4x4 mm and thin-layer finishing coats or basecoat SM700 (t = approx. 7 mm) with reinforcement mesh 5x5 mm and thin-layer finishing coats or basecoat Pastol with reinforcement mesh Pastol and thin-layer finishing coats

■ The density of the EPS panels must be ≤ 20 kg/m³

Page 40: Knauf WARM WALL Basis in Solid Construction ETICS with

40 P321.de Knauf WARM WALL Basis

Installation and applicationInsulation panels

Insulation panels – adhesive bonding

Application method Adhesive share Application on

Manual adhesive bonding

Partial surface adhesive bonding ≥ 40 % Insulation

panelFull-surface bonding

Machine applied adhesive bonding

Partial surface adhesive bonding ≥ 60 % SubstrateFull-surface bonding

Manual foam adhesive bonding

Partial surface adhesive bonding ≥ 40 %

Insulation panel

Adhesive side of the insulation panels ■ EPS Standard: Side can be freely selected ■ EPS Nut&Feder: Side with tapered edges (dabs of mortar) ■ EPS SunJa 032: Grey side

Manual adhesive on insulation panelPartial surface adhesive bonding (adhesive area ratio of ≥ 40 %)Edge ribbon and dab bonding is performed by hand. The adhesive bonding surface with the substrate is ≥ 40 % after pressing in the insulation panels.

Apply an approx. 50 mm wide ribbon of mortar around the perimeter and 3 palm-sized adhesive dabs or strips on the insulation panel.Full-surface bonding

On even substrates, it is possible to apply the adhesive on the entire surface of the insulation panel with a notched trowel.

Machine applied adhesive on substratePartial surface adhesive (adhesive area ratio of ≥ 60 %)Apply machine applied adhesive in the form of mortar dabs directly on the substrate at spaces of maximum 100 mm using the meandering method and

apply the insulation panels immediately by pushing, floating and pressing. The required adhesive bonding surface is ≥ 60 % after pressing in the insulation panels. Apply a continuous strip of adhesive in the edge areas. Only apply a maximum of 3 m of adhesive in advance to the surface being worked.

Full-surface bondingAlternatively, the adhesive can be applied to the full surface directly on even substrates. Run a notched trowel through the adhesive directly before applying the insulation panels.

≤ 3 m

Manual foam adhesive bondingPartial surface adhesive bonding (adhesive area ratio of ≥ 40 %)With the use of Speedero adhesive foam, the insulation panels are to have an application at the entire perimeter of a string of adhesive in the vicinity of the panel edge and enclose an M or W shaped adhesive application so that adhesive is applied to at least of 40 % of the surface.

Plinth and splash water zoneInspect / supplement the building waterproof sealing before insulation work. The splash water zone must be applied up to a height of at least 300 mm above ground level with plinth insulation panels. When configured as a not easily flammable ETICS and the associated observance of the plinth fire protection zone, the plinth insulation panels can be applied up to a height of 0.9 m above the edge of the ground line. Adhesively bond plinth insulation panels with adhesive on mineral or bituminous waterproofing of buildings. The adhesive application is across the entire surface or using an edge ribbon and dab bonding method with an adhesive surface of at least 40 %. The lower edge of the plinth insulation panel must have a continuous strip applied at least 50 mm wide. The lower edge of the plinth insulation panel can be cut off with a minimal integration depth in the soil, in case of insulation material thicknesses exceeding 140 mm it can be slanted. Allow a setting time of at least 48 hours before continuing work.Adhesive bonding on bituminous substratesIn case of mineral adhesives (not necessary with Sockel-SM Pro), apply Sockel-Dicht on two component, bituminous substrates as a bonding layer and roughen the surface with a broom. Allow to dry and set fully before continuing.Insulation material from 150 mm above the edge of the ground line requires additional dowels (with the exception of full surface bonding with Sockel-SM Pro).

Notes

For further information on the installation and application of insulation panels and plaster system in the plinth area see pages 41 to 50.Observe the “Façade plinth render/External components” (German only), issued by Fachverband der Stuckateure für Ausbau und Fassade Baden-Württemberg, as well as the DIN 18533.

Insulation panels applicationInstall the plinth connection end profile horizontally and fix using anchor nails at spacings of approx. 300 mm. Compensate for substrate tolerances with washers. Connect the joints and the plinth connection end profiles with H connectors. Provide the outside corners with the appropriate mitring. Push on plinth profile made of plastic with drip edge and integrated reinforcement mesh strips on the plinth connection end profile ensuring joint offsetting to the insulation panel and plinth connection end profile.When connecting perimeter/plinth insulation to existing ETICS or when using a plinth connection end profile, a joint sealing tape FD is inserted between the perimeter/plinth insulation panel and plinth connection end profile. This is unnecessary of the ETICS are applied in conjunction with a Sockel-Abschlussprofil Peri plinth profile on an existing perimeter/plinth insulation. Peri is inserted between the perimeter insulation and the adhesively bonded insulation panel (see page 46).Apply insulation panels immediately to the fresh adhesive by pushing, floating and pressing.

Page 41: Knauf WARM WALL Basis in Solid Construction ETICS with

41P321.de Knauf WARM WALL Basis

Installation and applicationInsulation panels

Apply the insulation panels precisely and continuously starting from the bottom with the joints staggered at ≥ 100 mm (half panel length recommended for joint staggering). Cross joints, e.g. on opening corners should be avoided.Bonding of the insulation panels up to a thickness of 200 mm is possible without corner grooving, however, with more than 220 mm adhesive bonding with corner grooving is required.Adhesive may not be applied to the insulation panel joints. Open panel joints up to 5 mm in width can be filled with B1 foam, panel joints > 5 mm or skips can be cleanly sealed using equivalent insulation panel strips.It is recommended that the upper and lower edges of the insulation surface have a continuous strip of adhesive applied to ensure that back ventilation is excluded.Allow a setting time of at least 48 hours before continuing work.Corner configurationUp to 200 mm without corner grooving

≥ 100 mm joint offset

(half board length

recommended)

More than 200 mm with corner grooving

≥ 100 mm joint offset

(half board length

recommended)

Window and door openings

Avoid cross joints

Insulation panel dowellingThe wall must be sufficiently stable to allow the use of dowels.If insulation panels are to be fastened to ensure structural compliance, the certified dowels must be used (see page 26 to 29).Dowel extraction tests are necessary for substrates not stipulated in the respective dowel certifications, or should the characteristics of the substrate be unknown.The number of dowels can be taken from the tables on page 28 or the approval Z-33.43-82. The wind load can be determined with the simplified method (page 26 to 27) or acc. to EN 1991-1-4 and EN 1991-1-4/NA.Application of the dowels can commence after the adhesive has hardened sufficiently. The diameter of the drill must be ≥ 8 mm.Do not use impact or hammer drills on hollow or perforated bricks or masonry. Arrange the drill holes so that the concrete reinforcement is not damaged. Drill hole depth = dowel length + 10 mm (or +25 mm with recessed dowel installation). Clean the drill holes before the dowels are applied.Do not use worn drill bits. Resharpening of the drill bit is not permissible.Under the mesh the installation can be flush to the surface or recessed in the surface. When applying dowels through the reinforcement mesh the dowels can only be placed surface flush. The dowel must be set in the fresh basecoat layer after the application of the basecoat and the embedding of the reinforcing mesh. Then immediately (wet plaster on wet plaster) apply a second layer of basecoat.The substrate temperature must be ≥ 0 °C when placing a dowel. The exposure to UV light with direct exposure to sunlight for the dowel and insulation panel may not exceed 6 weeks.

Note For dowel rating and selection see page 26 to 29

Plinth and splash water zoneApply additional constructional, mechanical fixing of the plinth insulation panels from a height of 150 mm measured above the edge of the ground line, e.g. for bituminous or painted substrates with general building authority approved dowels with a dowel plate diameter 60 mm (2 dowels per panel).

Insulation panels – application (continued)

Page 42: Knauf WARM WALL Basis in Solid Construction ETICS with

42 P321.de Knauf WARM WALL Basis

Installation and applicationInsulation panels

Dowelling under the reinforcement mesh Scheme drawings I Dimensions in mm

Number of dowels Dowel arrangement

4 dowels/m² approx. 0.5 m²

≥ 100 mm to edge of building

5 dowels/m²

6 dowels/m²

8 dowels/m²

10 dowels/m²

12 dowels/m²

14 dowels/m²

Dowel ratings online see:www.knauf.de/duebelrechner

Note See DIN 55699 for dowel schemes for dowelling through the mesh.

Page 43: Knauf WARM WALL Basis in Solid Construction ETICS with

43P321.de Knauf WARM WALL Basis

Installation and applicationDriving-rain proof window connection profiles

Connection to window sill side section

Driving-rain proof window connection profilesSelection criteria

Window connection profiles Features Total plaster thickness

Flexible With shadow gap, single-part profile 6 – 12 mmDuo G6 With shadow gap, two-part profile 6 – 12 mmMilano With protective lip, two-part profile 6 – 10 mmUniversal Pro With shadow gap and integrated PUR sealing tape 6 – 12 mmUniversal-K Pro With shadow gap and integrated PUR sealing tape for scratch render 15 – 18 mmRoma With shadow gap, two-part profile for roller blind guide rails 6 – 10 mm

ApplicationWindow connection profiles

Window position in masonryCentred Flush Projected (plasterable reveal necessary)

Maximum insulation material thickness in mm with window size≤ 6 m² ≤ 10 m² ≤ 15 m² ≤ 6 m² ≤ 10 m² ≤ 15 m² ≤ 2 m² ≤ 6 m² ≤ 10 m² ≤ 15 m²

Flexible 200 200 – 200 200 – 100 – – –Duo G6 300 300 – 240 – – 240 240 – –Milano 160 160 – 160 160 – 100 – – –Universal Pro 400 400 400 400 400 400 400 400 400 400Universal-K Pro 200 200 200 200 200 200 200 200 200 200Roma 200 160 – 200 160 – 200 200 160 –

Notes

Window connection profiles are certified up to the stated insulation material thicknesses without additional joint sealing tape, for larger insulation material thickness an additional Fugendichtband FD joint sealing tape is required.Back profile joints with Fugendichtband FD joint sealing tape. Backing for Universal Pro and Universal-K Pro is not necessary (observe the product data sheet).

Window sill anddriving-rain proof sidesection with expansioncompensation

Glued onSR taperecommended

Fugendicht-band FD jointsealing tape.

Slope ≥ 8%

Insulation material(render systemnot shown)

SR taperecommended underrender system

Use of adhesively bonded window connection profilesAn adhesive bonding test must be performed before the use of adhesively bonded window connection profiles. For this purpose, clean a concealed location with a clean and dry cloth (without cleaning agent). The substrate should be level, dry and dust-free. Residues that can affect bonding must be removed. The temperature must be between +5 °C and +40 °C. Cut off a short section of the profile (approx. 10 cm), peel off the protective paper of the Sk-PE-Dichtband sealing tape and push the profile section firmly on. Wait 10 minutes and then tear the profile with force away from the substrate. The Sk-PE-Dichtband sealing tape must on the one hand remain completely attached to the profile and on the other hand completely to the substrate (continuous foam rupture). Thus the substrate is suitable for adhesive bonding.Should this not be the case, the window connection profile Universal Pro or Universal-K Pro with PUR sealing tape must be used.

Page 44: Knauf WARM WALL Basis in Solid Construction ETICS with

44 P321.de Knauf WARM WALL Basis

Installation and applicationDriving-rain proof window connection profiles I Plaster system

Applied render system Dimensions in mmMineral based Mineral / organic Scratch render

51) –

151.5

– 10SM700 Pro, SM700,

SM300, Sockel-SM,Lustro with reinforcing mesh

Finishing render (mineral)Paint if necessary

51) –

151.5

– 3

Finishing render (organic)Paint if necessary

SM700 Pro, SM700,SM300, Sockel-SM,Lustro with reinforcing mesh

710

SM300 withreinforcing mesh

Mak3Impregnation if required

Organic Sandstein-Design

22 –

3

Pastol with reinforcing mesh PastolFinishing render (organic)

Paint if necessary

ca. 5

5 – 10

Sandstein-Design wall panels or rollsSandstein-Design primer and sealing

SM700 Pro, SM700, SM300, Sockel-SMwith reinforcing mesh

Sandstein-Design adhesive

1) Thin-layer is also possible from 4.5 mm: Adhesive SM300 or Speedero adhesive foam, basecoat SM300 from 3.0 mm, reinforcement mesh 4x4 mm, final coats: Noblo, RP 240, SP 260, Noblo Filz, Conni S, Addi S, MineralAktiv Scheibenputz floated render or MineralAktiv Scheibenputz Dry floated render

Window connection profileflexible with reinforcing mesh

Roller shutter guide rails

Insulation material(render system notshown)

≥ 18 mm22 mm recommended

≤ 8 mm

Roller shutter guide rails

Window frame

Window connection profileflexible with reinforcing mesh

Render system

Driving-rain proof window connection profiles (continued)Window connection with roller blind guide rails

Scheme drawings

Page 45: Knauf WARM WALL Basis in Solid Construction ETICS with

45P321.de Knauf WARM WALL Basis

Installation and applicationPlaster system

Reinforcement (basecoat) layerFaçade reinforcement

System Basecoat Layer thickness Reinforcing mesh Mesh arrangement in the reinforcement layer

Mesh reinforcement joint overlap

Scratch render SM300 7 mm

Reinforcing mesh 4x4 mm or 5x5 mm

Upper half

≥ 100 mm

Mineral basedMineral / organic

SM700 Pro 5 – 10 mm

■ Up to 4 mm: centred ■ > 4 to 7 mm: upper half ■ > 7 mm: outer third

SM700, SM300, Sockel-SM 5 – 7 mm

Lustro 5 – 15 mm (> 10 mm double-layer)

SM300 3 – 5 mm Reinforcing mesh 4x4 mm

Organic Pastol 2 – 3 mm Reinforcing mesh Pastol Centred

Sandstein-DesignSM700 Pro 5 – 10 mm

Reinforcing mesh 4x4 mm or 5x5 mm

■ > 4 to 7 mm: upper half ■ > 7 mm: outer third

SM700, SM300, Sockel-SM 5 – 7 mm Upper half

With Noblo 1.5 mm and Carrara 1.0 mm an additional mesh layer is recommended.

Reinforcement in dependence on the finishing plaster and luminosity of the final coatingFinishing plasters Graining Luminosity of the final coating

Siliconharz-EG-Farbe paint, Autol, Fassadol, Minerol, MineralAktiv Fassadenfarbe paint Fassadol TSR1)

mm 100 to 30 29 to 25 24 to 20 19 to 15 14 to 10 < 20Noblo Filz, SM700 Pro 1.0 ● ● ●● ●●● ●●● ●●Noblo Filz 1.5 ● ● ●● ●●● ●●● ●●Noblo 1.5 ●● ●● ●● ●●● On request ●●Noblo, RP 240 2.0 – 3.0 ● ● ● ●●● On request ●SP 260 2.0 – 5.0 ● ● ● ●●● On request ●Mak3 2.0 – 3.0 ● On request On request On request On request –Carrara 1.0 ●● ●●● On request On request On request On requestMineralAktiv Scheibenputz floated render 1.5 – 3.0 ● ● ● ●●● On request ●

MineralAktiv Scheibenputz Dry floated render 2.0 – 3.0 ● ● ● ●●● On request ●

Conni S, Addi S, Kati S1.5 – 2.0 ● ● ● ●●● ●●● ●3.0 ● ● ● ●● ●●● ●

1)  White finishing plasters must be used when applying Fassadol TSR.●  Single layer mesh reinforcement●●  Double layer mesh reinforcement●●● Double layer only on small surfaces, larger surfaces on request

Page 46: Knauf WARM WALL Basis in Solid Construction ETICS with

46 P321.de Knauf WARM WALL Basis

Installation and applicationPlaster system

Reinforcement layer (continued)Fully embed strips of reinforcement mesh or Gewebeeckwinkel Sturzecke mesh corner angle for lintel corner at the inner corners between the window reveal and window lintel in the basecoat. Subsequently apply Gewebeeckwinkel mesh corner angles perpendicular and flush. Apply the reinforcement layer and level it.Except when using Gewebeeckwinkel Sturzecke mesh corner angle for lintel corner, extending diagonally from all opening corners embed Gewebeeckpfeile mesh corner arrows or approx. 300 x 500 mm strips of reinforcement mesh in the wet mortar.Subsequently embed Armiergewebe reinforcement mesh on the entire surface with at least a joint overlap of 100 mm fresh-in-fresh in the basecoat layer. Apply a full covering of basecoat to the mesh. The mesh is arranged in the centre when the basecoat thickness is up to 4 mm, for > 4 to 7 mm layer thickness it is in the upper half of the basecoat layer and for > 7 mm in the exterior third.For scratch render the layer thickness of SM300 must be 7 mm. On the reinforcing mesh, apply minimum 2 to 3 mm of SM300 and after initial setting roughen the surface horizontally with a brush.If a double reinforcement is necessary (see table on page 45), the lower reinforcing mesh is applied with a respective overlap of approx 100 mm in the first basecoat layer of 2 to 3 mm without creases. After the basecoat layer has hardened, the second basecoat mesh is embedded with a joint overlap of ≥ 100 mm and a joint overlap of the second mesh to one another of ≥ 100 mm in the second layer of the basecoat. The position of the second mesh corresponds to the position of a simple reinforcement with a mesh. Alternatively, the second reinforcement layer can also be applied onto the fresh first reinforcement layer. For this purpose, apply basecoat as wet plaster on wet plaster onto the first basecoat layer and apply reinforcement mesh with staggered joints. The diagonal reinforcements are embedded before the second mesh layer.Avoid excessive smoothing of the reinforcement layer to prevent a concentration of fine particles or formation of a sinter layer on the surface.Rub off any burrs that have formed when drying.Plaster connections should be separated with a separating tape, separation strip, profiles or similar from the constructional components.Reinforcement of window lintel / revealImage 1 Dimensions in mm

Over

lap≥

100

Gewebeeckwinkelmesh corner angle

lintel corner

Gewebeeckwinkelmesh cornerangle

The lintel / reveal corner areas require additional Gewebeeckwinkel Sturzecke mesh corner angle reinforcement.

Image 2 Dimensions in mm

Over

lap≥

100

Gewebeeckpfeil meshcorner angleMesh strips

Gewebeeckwinkelmesh cornerangle

Alternatively, the lintel / reveal corner areas can be reinforced with Gewebeeckpfeile mesh corner arrow or reinforcement mesh strips.

Basecoat drying timeBefore application of a further coating (primer / basecoat) it is important to ensure that the basecoat is fully dry. The minimum drying time is generally approx. 1 day/mm layer thickness. With Pastol the weather dependent drying time is at least 3 days. With unfavourable weather conditions (e.g. high levels of air humidity or low temperatures) the drying time is extended, e.g. the drying time at +5 °C is around double so long. For further information please refer to the product data sheets of the subsequent coatings.Plinth and splash water zoneApply at least 5 mm basecoat covering the full surface embed reinforcement mesh 4x4 mm or 5x5 mm to the entire surface in the upper third of the basecoat. Stagger the joints by at least 100 mm. When insulation is applied in areas contacting the soil, the reinforcement layer ends about 200 to 300 mm underneath the edge of the ground line.

Page 47: Knauf WARM WALL Basis in Solid Construction ETICS with

47P321.de Knauf WARM WALL Basis

Installation and applicationPlaster system

EPS

Peri

EPS insulation material

Plaster system and dowelling not shown

Plinth connection profilePeri (with reinforcing mesh)

Adhesive

Plinth insulation board(with subsequent installation of theplinth insulation board jointsealing tape FD recommended)

Reinforcement layer (continued)Thermal bridge free Peri plinth profile

Apply the basecoat on the façade insulation panel, push in the Peri plinth connection profile between the perimeter / plinth insulation and the façade insulation, align flush and embed the reinforcement mesh.Connect the profiles with the supplied connectors. Provide the outside corners with the appropriate mitring. Constructional separation of the plinth plaster, e.g. by using a separating strip, profile or similar. When implementing the transition between the façade insulation and the plinth insulation, driving-rain proofing must be observed. If necessary apply a Fugendichtband FD joint sealing tape.

Impact resistance and resistance to hailImpact resistance tested following the ETAG 004 Scheme drawings

Organic system variants, partial design in areas subject to impacts

Up to 20 Joules

EPS 032

2 – 3 mm Pastol with1x reinforcing mesh Pastol

Quarzgrund Pro

Addi S

Up to 40 Joules

Quarzgrund Pro

EPS 032

3 mm Pastol with2x reinforcing mesh Pastol

Addi S

Up to 80 Joules

3 mm Pastol with1x reinforcing mesh Pastol and1x reinforcing mesh 5x5 mm

Quarzgrund Pro

EPS 032

Addi S

Page 48: Knauf WARM WALL Basis in Solid Construction ETICS with

48 P321.de Knauf WARM WALL Basis

Installation and applicationPlaster system

Impact resistance and resistance to hail (continued)Resistance to hail acc. to the Swiss hail protection register Scheme drawings I Dimensions in mm

Hail protection categories of different design variantsHail resistance functionality: HW 4*Hail resistance appearance: HW 4*

EPS 032, t = 140 mm

System Sandstein-Design

SM700 Pro with reinforcingmesh 5x5 mm

System dowel with dowel plate

7 – 8

Hail resistance functionality: HW 4*Hail resistance appearance: HW 4*

EPS 032, t = 140 mm

Addi S 2.0 mm

Pastol with reinforcingmesh Pastol

System dowel with dowel plate

≥ 5 – 6

Hail resistance functionality: HW 3* Hail resistance appearance: HW 3*

EPS 032, t = 140 mm

Addi S 2.0 mm

SM700 Pro with reinforcingmesh 5x5 mm

System dowel with dowel plate

≥ 7

Hail resistance functionality: HW 2*Hail resistance appearance: HW 3*

EPS 032, t = 140 mm

Addi S 2.0 mm

SM300 Pro with reinforcingmesh 5x5 mm

System dowel with dowel plate

6 – 7

Testing of the impact resistances of ETICS surfaces following the ETAG 004 ■ A steel ball (1 kg mass) dropping from 1.02 m corresponds to a kinetic energy of 10 joules (ETAG 004) ■ The highest category (I) acc. to ETAG demands an impact resistance of 10 joules for areas subjected to damage caused by vandalism

20 40 80

Drop heightapprox

8.0 m

approx4.0 m

approx2.0 m

1 kg steel ball

10 30 50 60 70 JoulesETICS surface impact resistance

Comparison example: A hailstone of 5 cm diameter achieves an impact energy of approx 28 joules (Source: Hagel Informationszentrum, Switzerland).

Page 49: Knauf WARM WALL Basis in Solid Construction ETICS with

49P321.de Knauf WARM WALL Basis

Installation and applicationPlaster system

Finish coatPrimerStir the contents of the container thoroughly and repeat occasionally.With thin-layer mineral-based finishing coats, dilute Isogrund 1:1 with clean water and apply uniformly with a roller to the entire surface or apply using a suitable spray device. With Pastol or Conni, Kati and Addi on SM700, SM700 PRO, SM300 and Lustro, apply undiluted Quarzgrund Pro uniformly using a roller or brush and spread crosswise. Avoid streaking. When applying pigmented Conni, Kati and Addi, Quarzgrund Pro pigmented in the same or similar colour shade is recommended.Allow a drying time of at least 2 hours before applying the finishing coat with Quarzgrund Pro and at least 12 hours for Isogrund.Plaster application

Finishing plasters Minimum layer thickness in mm

Façade

Carrara, Noblo Filz (freely styled texture)

3 – 5

Noblo Filz (sponged) 2 – 3Noblo, SP 260, RP 240 Grain sizeSM700 Pro (sponged) 3SM700 Pro (trowel finish) 10 (average layer thickness)SM700 Pro (freely styled texture) 3 – 10Conni S, Addi S, Kati S Grain sizeMineralAktiv Scheibenputz and MineralAktiv Scheibenputz Dry floated renders

Grain size

Mak3 10 (scratched finish)

Plinth area

Sockel-SM Pro (sponged)1) Sockel-SM (sponged)2) 2

Butz 2

1) Only in conjunction with Sockel-SM Pro as a basecoat. Sockel-Dicht is unnecessary in case Sockel-SM Pro is used as a render system (basecoat and fínish coat) in a total thickness ≥ 7 mm.

2)  Only in conjunction with Sockel-SM as a basecoat.Water quantity and mixing in acc. with the current product data sheet.Check the containers before use to ensure that the colour shades are correct. When applying a shaded finish coat, ensure that the batch numbers are the same or only mix sufficient render required to finish a full rendered surface.Slight differences in colour hues can occur due to the use of natural aggregates. When reordering, always state the consignment number of the previous delivery.Ensure uniform grain distribution.The type of tool used influences the surface roughness and it is therefore essential to use the same tool for a consistent finish.Ensure that there are sufficient workers available on every scaffolding level to avoid bothersome structural effects. Work quickly fresh in fresh and do not rework hardened surfaces. Avoid work stoppages on continuous surfaces and always complete self-contained areas.Observe Code of Practice no. 26 “Farbveränderungen von Beschichtungen im Außenbereich - Colour changes in exterior coatings” of the Bundesausschuss Farbe und Sachwertschutz (Federal Paint and Property Protection Committee).

Plaster connections should separated from the constructional components with a separating tape, separation strip, profiles or similar.CarraraApply / spray an approx. 5 mm (at least 3 mm on recesses) layer of Carrara onto a continuous surface and spread flush with a straightedge or finish trowel and texture it immediately using the required tool (sponge, trowel, brush, roller, etc.)Noblo FilzApply a fully covering coat of Noblo Filz in grain thickness, allow to dry and then apply a second coat in grain thickness, and immediately sponge / felt, without using water. Apply approx. 3 to 5 mm for free textures, spread flush and texture immediately with the required tool.Noblo, SP 260, RP 240Apply the render with a stainless steel finishing trowel or trowel, spread flush in grain size and texture immediately as required using a suitable tool.SM700 ProFor sponged surfaces SM700 Pro is applied in a layer thickness of approx. 3 mm on the basecoat. The drying time of the basecoat can be reduced to 1 day if the basecoat layer is applied with SM700 Pro. Start sponging or free texturing with initial setting of the SM700 Pro.For surfaces with a trowel finish, apply SM700 Pro in an average layer thickness of 10 mm and create the surface.For surfaces with a broom finish, apply approx. 3 mm SM700 Pro, level and use a coarse broom (with strong coarse bristles) and pull a single stroke through the wet / damp surface.MineralAktiv Scheibenputz and MineralAktiv Scheibenputz Dry floated rendersKnauf MineralAktiv Scheibenputz floated render is applied over the entire surface in grain thickness with a stainless steel trowel, and directly after application it is worked uniformly and without interruption to the desired texture using a hard plastic trowel. Sponge rubber floating produces a coarser more rustic texture finish.Conni S, Addi S, Kati SReady-to-use, paste-like final coat must be mixed thoroughly. When necessary, a small quantity of water may be added to set the application consistence. Apply Conni S, Addi S or Kati S (floated render texture) with a stainless steel trowel in grain size to the entire surface and trowel smooth with circular movements without interruption using a hard plastic trowel.Mak3Apply the scratch render layer of approx. 13 or 14 mm by machine (application by hand only on small surfaces), level with the notched scraper and smoothen with the wide spatula and consolidate (danger of trapped air bubbles). When initial setting commences, possible on the same day but usually on the following day, scratch in circular motions and remove small unevenness's with the scraper. The optimum scratch time is when the grain cracks when scratched. Premature scratching results in a darker colour and unclear structure.Plinth and splash water zoneApply a primer to suit the selected top coat, observe the required drying times. Apply plinth renders, e.g. Sockel-SM Pro or Sockel-SM on the following day on the system-compatible reinforcement layer and sponge.Sockel-SMAfter the top coat in the area contacting the soil has dried, apply moisture protection for the plastered surface with Sockel-Dicht (apply at least 50 mm above the edge of the ground line), which must connect to the building sealing (overlap of approx. 50 to 100 mm) or must be pulled 50 to 100 mm onto the uncoated perimeter insulation panels. Apply in two steps. Minimum layer thickness 2.5 mm.

Page 50: Knauf WARM WALL Basis in Solid Construction ETICS with

50 P321.de Knauf WARM WALL Basis

Installation and applicationPlaster system

Sockel-SM ProWhen applying the Sockel-SM Pro render system with a total layer thickness (basecoat and finish coat) of at least 7 mm, additional moisture protection with Sockel-Dicht is unnecessary.ButzAllow a drying time of at least 2 hours before applying Butz on Quarzgrund Pro.Mix the contents of the container well, apply using a stainless steel trowel slightly thicker than the grain size and level in one direction.

Sandstein-DesignSandstein-Design Wandplatte wall panels are applied with Sandstein-Design Kleber adhesive using a notched trowel (6 mm) onto the dry basecoat pretreated with Isogrund, and pressed on uniformly using a Sandstein-Design Werkzeug tool. Directly after application of the Sandstein-Design wall panels, smoothen the existing Sandstein-Design Kleber adhesive in the joints, e.g. using a damp paint brush. Ensure a uniform joint width of recommended 6 to 8 mm. When the Sandstein-Design adhesive is sufficiently dry, apply a generous coating of Sandstein-Design Grund primer to the entire surface. After waiting for at least one further day, apply 2 generous coatings of Sandstein-Design Versiegelung sealing to the entire surface. Protect applied Sandstein-Design wall panels against precipitation until the sealed surface is fully dry.Another coating of sealing can be applied on the following day as protection against graffiti. Depending on the geographic location and climatic conditions, chalking may occur after some time. Regular maintenance is recommended, and if required the façade should be cleaned and primed and then sealed.

Mechanical protection in the plinth areaAs protection for the plinth in the area contacting the soil against mechanical influences of the soil or gravel bed, use of a fleece laminated dimpled sheet up to the edge of the ground line is recommended.

CoatsPrimerAs a primer, e.g. a coat of Grundol is recommended. Façade paintUse a trial coat to ensure the colour shade is correct. Never apply the content from different buckets together on a common wall. Mix the contents together in a clean bucket beforehand. Stir the contents of the bucket thoroughly.The application consistency can be modified in acc. with the Product Data Sheet.Apply a thin and even paint coat crosswise without joints on the fully hardened (generally after 7 days drying time) and dried final coat.Always complete surfaces that can be viewed together on the same day.

Notes

All the products listed here are formulated, so that a preventative and retarding action against soiling is in effect. Permanent protection against soiling caused by microorganisms such as algae and fungus cannot be guaranteed. The susceptibility depends on the local and environmental conditions. Loss of the technical function of the render or coating due to microbial fouling with algae and fungus on the surface is practically non-existent.Observe the Code of Practice "Egalisationsanstriche auf Edelputzen – Farbtonegalisierende Beschichtung - Equalization coats on finishing plasters”, issued by the Industrieverband WerkMörtel e. V.

ImpregnationSuitable impregnation is recommended when using Mak3 in exposed locations and in the vicinity of waterbodies.

Final coat (continued)

Page 51: Knauf WARM WALL Basis in Solid Construction ETICS with

51P321.de Knauf WARM WALL Basis

UsageMaintenance

Inspect for Technical instructions and measures

Soiling Clean the finish coat or the Sandstein-Design surface using a high-pressure water jet (water temperature below +60 °C, observe the regional wastewater discharge regulations) adapted to the substrate, and if required, apply a new coat of paint to the façade finish coat with a system-conform paint, or apply new primer and sealing to the Sandstein-Design once sufficiently dry.

Microbiological growth (e.g. algae, mould) Clean using a high-pressure water jet (water temperature below +60 °C, observe the regional wastewater discharge regulations) adapted to the substrate, apply Algizid (ready-to-use solution) and clean the finish coat or the Sandstein-Design surface, and if required, apply a new coat of paint to the façade finish coat with a system-conform paint, or apply new primer and sealing to the Sandstein-Design once sufficiently dry.

Sealing of elastic connections (windows, doors, expansion joints, façade penetrations)

Joints applied with permanently-elastic materials are maintenance joints and should be inspected and replaced at regular intervals, if required, or sealed to repel moisture.

Mechanical damage Fill with equivalent insulation materials, reapply the render including the reinforcement mesh, new Sandstein-Design surface with primer and sealing or final coat and if necessary, apply a new coat of paint with a system-conform paint. Repairs to small areas and spots may stand out visually from the rest of the surface. Differences in texture and colour of the finishing coat may be visible.

The recommendations of the ETAG 004 (Guideline for European technical approval of ETICS with rendering) detailing the use, maintenance and repair of ETICS must be considered.

MaintenanceMaintenance of the façade surface should be performed at regular intervals taking the size, architecture and location into consideration. Maintenance is understood to mean cleaning, painting or, if required, renewing of connections on the intact External Thermal Insulation Composite Systems (ETICS). It is necessary to undertake corrective measures as quickly as possible if a maintenance issue is identified in order to assure the ETICS service life and protect the visual appearance. We generally recommend consulting experienced and qualified specialist companies if a maintenance issue is identified.CracksLimited cracking shall not be classified as a fault, if it does not impair the technical and optical characteristic value of the render (compare to DIN 18550-1). In recesses in the render structure, individual fine shrinkage cracks and pores that have occurred in the render and in the coating / paint coats are permissible. A technical defect has occurred if the driving

rain-proofing of the masonry and / or the weathering resistance of the render and coating is no longer assured. A general maximum crack width value cannot be specified, as this is dependent on the render used, the render system and the render substrate in each individual case. A visual defect is present, if the cracks are considered to be bothersome under normal viewing conditions (e.g. perspective, distance), and the rendered surface has a special design or representative significance. Also refer to the WTA Code of Practice "Assessment and Repair of Cracked Rendering on Façades”.Graffiti protection with Sandstein-DesignThe prerequisite for the successful removal of Graffiti is a triple coat of Sandstein-Design sealing. Contamination from graffiti can only be removed using a special cleaning agent. Removal of defilement caused by graffiti can be undertaken by a certified specialist company. After removal, new weather-proof sealing must be applied with Sandstein-Design Versiegelung sealing.

Page 52: Knauf WARM WALL Basis in Solid Construction ETICS with

52 P321.de Knauf WARM WALL Basis

Material requirementKnauf WARM WALL Basis

Material requirement

Plin

th

Faça

de

System components Remark Unit Quantity as average valueP321a.deMineral based

P321b.deMineral / organic

P321c.deScratch render

P321d.deOrganic

P321e.deSandstein- Design

Bonding layer per m² plinth without addition for waste

●1) Sockel-Dicht Full surface application kg 3.8Adhesive per m² plinth / façade without addition for waste (40 % – 100 % adhesive area ratio)

●2) ● SM300

Max. layer thickness 5 mm

kg 3.1 – 7.7●2) ● SM700 Pro kg 2.9 – 7.1●2) ● SM700 kg 2.8 – 6.9●2) ● Sockel-SM kg 4.0 – 8.0●3) Sockel-SM Pro kg 4.0 – 8.0●2) ● Duo-Kleber adhesive kg 2.7 – 6.8

● Lustro kg 1.8 – 4.4● Pastol4) Layer thickness 2 – 3 mm kg 2.8 – 4.2● Speedero adhesive foam 30 mm wide string of adhesive ml/m² 66 – 200

Insulation material per m² of plinth / façade without allowance for loss and waste

● Plinth insulation panel

Insulation material thickness:

Integration into the soil: m² 1Up to 200 mm

> 200 mm→→

Up to 3 mUp to 0.5 m

● EPS Standard 035 white Thickness 40 – 400 mm m² 1● EPS Standard 034 Thickness 40 – 400 mm m² 1● EPS Standard 032 Thickness 40 – 400 mm m² 1● EPS SunJa 032 Thickness 80 – 200 mm m² 1● EPS Nut&Feder 035 white Thickness 60 – 400 mm m² 1● EPS Nut&Feder 034 Thickness 60 – 400 mm m² 1● EPS Nut&Feder 032 Thickness 60 – 400 mm m² 1

Plinth connection per m of façade without allowance for loss and waste Only with recessed plinth

● Plinth connection profile Projection of 30 to 300 mm m/m 1

● Plinth profilePlinth profile with drip edge and reinforcement mesh for plaster thicknesses 6 mm, 10 mm or 14 mm

m/m 1

● Assembly kit plinth end profiles Fasteners set/m 0.04

● Peri plinth end profile For plaster thicknesses 3 mm, 7 mm or 17 mm m/m 1

1) Not required when using Sockel-SM Pro as an adhesive on bituminous sealants.2) When bonding on bituminous waterproofing apply Sockel-Dicht as a bonding layer and additionally apply dowels to insulation material from 150 mm above

the edge of the ground line.3) With full surface bonding on bituminous waterproofing additional dowelling of the insulation material from 150 mm above the edge of the ground line is

unnecessary.4)  Can be used up to 400 mm insulation material thickness only with flammable ETICS systems B2. 

Page 53: Knauf WARM WALL Basis in Solid Construction ETICS with

53P321.de Knauf WARM WALL Basis

Material requirementKnauf WARM WALL Basis

Material requirement (continued)

Plin

th

Faça

de

System components Remark Unit Quantity as average valueP321a.deMineral based

P321b.deMineral / organic

P321c.deScratch render

P321d.deOrganic

P321e.deSandstein- Design

Dowel per m² plinth / façade / if necessary fire break without addition for waste

● ●Schlagdübel CNplus 8 insulation anchor nail

Anchoring depth s ≥ 35 mm, ≥ 55 mm for categories D and E

≥ 4 pcsNumber of dowels dependent on wind load, see table on page 28; 2 dowels per plinth insulation panel from a height of 150 mm above the edge of the ground line

● ●Schraubdübel STR U 2G dowel

Anchoring depth s ≥ 25 mm, ≥ 65 mm for category E

●Dübelteller SBL 140 plus dowel plate

For surface flush dowelling of additional fire breaks with MW Volamit 040

●CNplus-Rondelle EPS dowel plate

Grey or white dowel plate made of EPS for recessed dowel fitting when Schlagdübel CNplus 8 insulation anchor nails are used

●STR Rondelle EPS dowel plate

Grey or white dowel plate made of EPS for recessed dowel fitting when Schraubdübel STR U 2G dowels are used

Basecoat per m² plinth / façade without addition for waste

● ● SM300 Layer thickness 3 – 5 mm1), 5 – 7 mm, 7 mm with scratch render kg 4.5 – 10.5 4.5 – 10.5 10.5 – 7.6 – 10.5

● ● SM700 Pro Layer thickness 5 – 10 mm kg 7.0 – 13.0 7.0 – 13.0 – – 7.0 – 13.0● ● SM700 Layer thickness 5 – 7 mm kg 7.0 – 10.0 7.0 – 10.0 – – 7.0 – 10.0● ● Sockel-SM Layer thickness 5 – 7 mm kg 7.0 – 10.0 7.0 – 10.0 – – 7.0 – 10.0●2) Sockel-SM Pro Layer thickness 5 mm kg 8.0 8.0 – – –

● Lustro Layer thickness 5 – 15 mm (> 10 mm double-layer) kg 4.3 – 13.0 4.3 – 13.0 – – –

● ● Pastol Layer thickness 2 – 3 mm kg – – – 2.8 – 4.2 –

Reinforcement mesh per m² of plinth / façade without allowance for loss and waste

● ● Reinforcing mesh 4x4 mm100 mm joint overlap

m2 1.1 1.1 1.1 – 1.1● ● Reinforcing mesh 5x5 mm m2 1.1 1.1 1.1 – 1.1● ● Reinforcing mesh Pastol m2 – – – 1.1 –Moisture protection per m² plinth without addition for waste●3) Sockel-Dicht Layer thickness min. 2.5 mm (two coats) kg 3.8 3.8 3.8 3.8 3.8

Priming per m² plinth / façade without addition for waste

● ● Isogrund (recommended) Diluted: 1:1 with water kg (0.1) – – – 0.1● ● Quarzgrund pro Undiluted kg – 0.174) – 0.174) –

1) Thin-layer is also possible from 4.5 mm: Adhesive SM300 or Speedero adhesive foam, basecoat SM300 from 3.0 mm, reinforcement mesh 4x4 mm, final coats: Noblo, RP 240, SP 260, Noblo Filz, Conni S, Addi S, MineralAktiv Scheibenputz floated render or MineralAktiv Scheibenputz Dry floated render

2)  Only in conjunction with Sockel-SM Pro as a top coat in layer thickness 2 mm.3)  With Sockel-SM Pro as a basecoat and Sockel-SM Pro as a finish coat with a total thickness ≥ 7 mm not required.4)  With a coloured finishing top coat Quarzgrund Pro in the same colour shade is recommended.

Page 54: Knauf WARM WALL Basis in Solid Construction ETICS with

54 P321.de Knauf WARM WALL Basis

Material requirementKnauf WARM WALL Basis

Material requirement (continued)

Plin

th

Faça

de

System components Remark Unit Quantity as average valueP321a.deMineral based

P321b.deMineral / organic

P321c.deScratch render

P321d.deOrganic

P321e.deSandstein Design

Finishing coat per m² plinth / façade without addition for waste

● ●

SM700 Pro Sponged Trowel finish Freely styled texture

Grain size1.0 mm 1.0 mm 1.0 mm

Layer thickness 3 mm Average layer thickness 10 mm Layer thickness 3 – 10 mm

kg kg kg

4.2 14.0 4.2 – 14.0

– – –

– – –

– – –

– – –

● ● SP 2602.0 mm1) 3.0 mm1) 5.0 mm1)

Layer thickness 2 mm Layer thickness 3 mm Layer thickness 5 mm

kg kg kg

3.2 3.8 5.0

– – –

– – –

– – –

– – –

● ● RP 240 2.0 mm1) 3.0 mm1)

Layer thickness 2 mm Layer thickness 3 mm

kg kg

3.1 3.8

– –

– –

– –

– –

● ● Noblo1.5 mm1) 3) 2.0 mm1) 3.0 mm1)

Layer thickness 1.5 mm Layer thickness 2 mm Layer thickness 3 mm

kg kg kg

2.3 3.0 3.7

– – –

– – –

– – –

– – –

● ● Noblo Filz 1.0 mm1) 1.5 mm1)

Layer thickness 2 mm Layer thickness 3 mm

kg kg

3.2 4.6

– –

– –

– –

– –

● ● Carrara 1.0 mm3) Layer thickness 3 – 5 mm kg 3.8 – 6.5 – – – –

● ● MineralAktiv Scheibenputz floated render

1.5 mm1) 2.0 mm1) 3.0 mm1)

Layer thickness 1.5 mm Layer thickness 2 mm Layer thickness 3 mm

kg kg kg

2.4 3.2 4.2

– – –

– – –

– – –

– – –

● ● MineralAktiv Scheibenputz Dry floated render

2.0 mm1) 3.0 mm1)

Layer thickness 2 mm Layer thickness 3 mm

kg kg

2.4 3.4

– –

– –

– –

– –

● ● Conni S1.5 mm1)

2.0 mm1)

3.0 mm1)

Layer thickness 1.5 mm Layer thickness 2 mm Layer thickness 3 mm

kg kg kg

– – –

2.2 2.8 3.7

– – –

– 2.8 –

– – –

● ● Addi S1.5 mm1) 2.0 mm1) 3.0 mm1)

Layer thickness 1.5 mm Layer thickness 2 mm Layer thickness 3 mm

kg kg kg

– – –

2.2 2.8 3.7

– – –

– 2.8 –

– – –

● ● Kati S1.5 mm 2.0 mm 3.0 mm

Layer thickness 1.5 mm Layer thickness 2 mm Layer thickness 3 mm

kg kg kg

– – –

2.4 3.0 3.8

– – –

– 3.0 –

– – –

● Mak3

2.0 mm 3.0 mm

Layer thickness unscratched: 12 mm Layer thickness unscratched: 13 mm

kg kg

– –

– –

22.02) 23.02)

– –

– –

●4) Sockel SM Pro (sponged) 1.0 mm Layer thickness 2 mm kg 3.0 – – – 3.0●5) Sockel SM (sponged) 1.0 mm Layer thickness 2 mm kg 3.0 – – – 3.0● Butz 2.0 mm Layer thickness 2 mm kg – 4.5 – 4.5 –

1) Thin-layer is also possible from 4.5 mm: Adhesive SM300 or Speedero adhesive foam, basecoat SM300 from 3.0 mm, reinforcement mesh 4x4 mm, final coats: Noblo, RP 240, SP 260, Noblo Filz, Conni S, Addi S, MineralAktiv Scheibenputz floated render or MineralAktiv Scheibenputz Dry floated render

2) Suitable impregnation is recommended in exposed locations and in the vicinity of waterbodies.3) Additional mesh layer in basecoat is recommended.4)  Only in conjunction with Sockel-SM Pro as a basecoat, with a total layer thickness  ≥ 7 mm Sockel-Dicht is not required.5)  Only in conjunction with Sockel-SM as a basecoat.

Page 55: Knauf WARM WALL Basis in Solid Construction ETICS with

55P321.de Knauf WARM WALL Basis

Material requirementKnauf WARM WALL Basis

Material requirement (continued)

Plin

th

Faça

de

System components Remark Unit Quantity as average valueP321a.deMineral based

P321b.deMineral / organic

P321c.deScratch render

P321d.deOrganic

P321e.deSandstein-Design

Wall liningper m² plinth / façade without addition for waste

● ● Sandstein-Design wall panels Layer thickness 2 – 3 mm m2 – – – – 1● ● Sandstein-Design roll Layer thickness 2 – 3 mm m2 – – – – 1● ● Sandstein Design adhesive Layer thickness approx. 2 mm kg/m² – – – – 1.5 – 2.0

Coat/sealing per m² plinth / façade without addition for waste

● ● Siliconharz-EG-Farbe paint Single coat1) l 0.17 – 0.22 – – – –● ● Autol paint Double coat l 0.25 – 0.40 0.25 – 0.40 – 0.25 – 0.40 –● ● Fassadol Double coat l 0.30 – 0.45 0.30 – 0.45 – 0.30 – 0.45 –● ● Fassadol TSR2) Double coat l 0.35 – 0.45 0.35 – 0.45 – 0.35 – 0.45 –● ● Minerol Double coat l 0.25 – 0.40 0.25 – 0.403) – 0.25 – 0.403) –● ● MineralAktiv Fassadenfarbe paint Double coat l 0.28 – 0.40 0.28 – 0.40 – 0.28 – 0.40 –● ● Sandstein-Design Grund Diluted: 1:2 with water l/m2 – – – – 0.30

● ● Sandstein-Design Versiegelung sealing

Double coat Triple coat (plinth area, graffiti protection)

l/m2 l/m2

– –

– –

– –

– –

0.30 0.45

1)  Recommendation: Double coat for enhanced weather-proofing (see “Code of Practice No. 9 - Coatings on mineral renders” from the Bundesausschuss Farbe und Sachwertschutz).

2) Only on white, newly created finish coats in combination at least 5 mm thick, mineral reinforcement layer.3)  Can only be used on Kati S.

Page 56: Knauf WARM WALL Basis in Solid Construction ETICS with

The iPad App Knauf Infothek now provides all the current information and documents from Knauf Gips KG at any time and in every location in a clear and comfortable way.Knauf Infothek

All technical changes reserved. Only the current printed instructions are valid. The stated information represents current state-of-the-art Knauf technology. The entire state of approved engineering rules, appropriate standards, guidelines, and rules of crafts-manship are not included herewith. These and all application instructions have to be adhered to separately by the installer. Our warranty is expressly limited to our products in flawless condition. All application quantities and delivery amounts are based on empirical data that are not easily transferable to other deviating areas.All rights reserved. All amendments, reprints and photocopies, including those of excerpts, require our expressed permission.

The stated constructional and structural design specifications and characteristics of building physics of Knauf systems can only be ensured with the exclusive use of Knauf system components, or other products expressly recommended by Knauf.

Knauf Gips KG Am Bahnhof 7, 97346 Iphofen, GermanyKnauf DirectTechnical Advisory Service:

[email protected]

www.knauf.de

P321.de/eng/07.18/0/Dbl

Information on sustainabilityKnauf WARM WALL Basis

Information on the sustainability of Knauf WARM WALL BasisBuilding assessment systems ensure the sustainable quality of buildings and constructional structures by a detailed assessment of ecological, economic, social, functional and technical aspects.In Germany the following certification systems are of particular relevance:

■ DGNB system Deutsches Gütesiegel Nachhaltiges Bauen der DGNB (German association for environmentally sustainable building)

■ BNB (Quality rating system for environmentally sustainable building)

■ LEED (Leadership in Energy and Environmental Design).

Knauf WARM WALL systems can positively influence many of these criteria.DGNB/BNBEcological quality

■ Criterion: Total primary energy requirement Reduction of the building energy requirement over the entire lifecycle due to efficient WARM WALL systems

Economic quality ■ Criterion: Building related life-cycle costs Reduction of the operating costs due to cost-effective WARM WALL systems

Sociocultural and functional quality ■ Criterion: Thermal comfort in summer or winter Cozy room climate with WARM WALL systems

Technical quality ■ Criterion: Premium quality thermal and moisture protection for the building shell With WARM WALL systems significantly exceeding the EnEV requirements

LEEDMaterials and resources

■ Credit: Regional materials Availability depending on location of building. Information on request.