Drywall and Floor Systems D131 Knauf Free-spanning Ceilings D131 – Knauf Free-spanning Ceilings with metal substructure CW/UW 2007-04 New Free-spanning Ceiling with T connection and L connection D131

Knauf D131 System

Embed Size (px)

DESCRIPTION

D21

Citation preview

Page 1: Knauf D131 System

Drywall and Floor Systems

D131 Knauf Free-spanning Ceilings

D131 – Knauf Free-spanning Ceilings with metal substructure CW/UW

2007-04

New■ Free-spanning Ceiling with T connection and L connection

D131

Page 2: Knauf D131 System

Copyright by Knauf Gips KG D131-S02 Stand 04.072

Comparison of Knauf BoardsBoard type General

FewEasycontrol jointsinstallation

Building physics

Stability /SoundFirestrength

SophisticatedapplicationpropertiesSurfacequality

Knauf Wallboard

Knauf Fire-resistant Board

GKB / GKBI

GKF / GKFI

Diamant GKFI

Solid Board GKF / GKFI*)

*)

*)

*)(Hard gypsum board)

suitable more suitable most suitable

12.5

18 to 25

2x 12.5

TN 3.5 x 25 mm

TN 3.5 x 35 mm

TN 3.5 x 25 mm

Drywall Screws

Metal substructure

Fastening of cladding / covering strips on substructure with Knauf Screws

Thickness in mm

Knauf Boards

Covering strip

25 TN 3.5 x 35 mm

w 120 mm

(Penetration 10 mm; metal thickness s 0.7 mm)

Multi-layer cladding

In case of multi layer cladding, apply layerswith staggered joints according to applicationscheme.Press boards of each layer firmly on to thesubstructure and screw attach each layer separately. For fastening of first layer, spacing of screws can be increased up to max. 500 mmif second layer is applied immediately afterwards(within one working day).In case of multi-layer cladding, a filling of jointsof first layer without further finishing is sufficient.

1st board layer

Boar

d widt

h1250

2nd board layer

1250

Boar

d widt

h 1250

1250

500

250

170

170

340

Alternating fastening

Cut edge joint

Knauf CW double profile

Knauf Drywall ScrewTN 3.5x35

*) Impregnated boards GKBI and GKFI are suitable for humid rooms

Thickness in mm

Alternating fastening Centers of fasteners max. 170 mm

Centers of fasteners max. 250 mm

Drywall Screws

Metal substructure

Diamant Screws

HGP 3.9 x 23 mm

-

HGP 3.9 x 23 mm

TN 3.5 x 35 mm HGP 3.9 x 35 mm

Optimum sound protection

All dimensions in mm

All dimensions in mm

Knauf Premium Drywalling

through total decouplingInstallation cavityFree available installation cavity

from basic ceiling or existing ceilingwithout interfering suspenders

(Penetration 10 mm; metal thickness s 0.7 mm)

+ +

protection insulation

D131 Knauf Free-spanning CeilingsKnauf Boards / Fastening of Cladding / Multi-layer Cladding

2

Page 3: Knauf D131 System

Subceilings that are fire protection rated independently

ABP P-3964/2172

ProofMineral wool insulation layer acc. to DIN EN 13162, section 3.1.1Building material class AMelting point 1000 °Cacc. to DIN 4102-17

SBuilding material class AGe.g. Knauf Insulation

Note:Free-spanning Fireboard CeilingsF90 Independently from belowF90 Independently from below and from above

Knauf Technical Data Sheet K219

F30

18 625

D131 Knauf Free-spanning Ceiling

40 -Mineral wool G

insulationorwithout

min. B2

2x 12.5 500

25 625

F30 F30

Type A

Covering strip: GKF 25 mm

Type B

F30 F30

Flanking components should have a fire resistance class of F30.

18 625 40 40Mineral wool S

60 30oder

insulationorwithout

min. B2

18 625

Fire resistanceclass for fireexposure

from fromNo fire protection requirementsto basic ceiling / roof construction

From below

From above

Requirement to the basic

The basic ceiling should havethe same fire protection rate

ceiling for fire protection:

(plenum)

required for

thickness

mm

Knauf Boards

Max.

kg/m³

density

mm mm

thickness

Insulation layerCeiling

fire protection

Min. Min.Min.axial

b

Soild

Boa

rdKn

auf G

KF

Diam

ant

below above

profile

spacing

KnaufPremiumDrywalling

Covering strip: GKF 25 mm

with upper board layer

with insulation layer

2x 12.5 500

Independently from below

The handy dimensions of the Solid Board makes transport and installation easy.Easy handling

Particularly good sound insulation with Diamant Boards.Sound insulation:

D131 Knauf Free-spanning Ceiling Independently from below and from above

System "Multi-level Ceiling" is possible (see page 16)

System "Multi-level Ceiling" is possible (see page 16)

as the subceiling

GKF 12.5 mm

D131 Knauf Free-spanning CeilingsFire Protection from Below / from Below and from Above

3

Page 4: Knauf D131 System

30 mm

single or double profiles (per flange)

Connections to partitions

625 m

m

30 mm

Covering strip GKF 25 mm120 mm wide

with UW runner by riveting,

with Metal Screw LB 3.5x9.5 mmScrew Knauf CW profiles at web

Screw connection of Knauf CW double profiles

750 mm

Knauf UW runner

Knauf CW double profile

Knauf single or double CW profiles

Connect Knauf CW profiles as

crimping or screwing with KnaufMetal Screws LB 3.5x9.5 mm.

Anchoring of the supporting UW perimeter runners

Metal stud partitions

Reinforced concrete walls

without cavities or

Anchoring on Maximum spacing of

Substantial masonry

625 mm

light concrete (density 1000 kg/m³)

Other materials

2x Knauf All Purpose Screw FN 4.3x35

Knauf Ceiling Steel Dowel

Knauf Nailable Plug L 8/80

Knauf Nailable Plug L 8/80

Suitable anchors

Anchoranchors

2x Knauf All Purpose Screw FN 4.3x65(Anchoring in metal studs)

For room widths 2.25 m the number of anchors can be reduced by 50 %, i.e. the spacing of the anchors can be doubled.

300 mm

minumum shear load capacity 0.35 kN per anchor

for cladding thickness up to 20 mm

Knauf CW double profiles with covering strip

625 m

m

Knauf UW runner

acc. to permission ETA - 07/0049

at a spacing of 750 mm

D131 Knauf Free-spanning CeilingsAnchoring

4

Page 5: Knauf D131 System

bb

Details, scale 1:5

500

62,5

75

UW runner

Knauf CWKnauf CW profile

Knauf CW double profile,

68

Fastening

Knauf CW double profile,

e. g. with Metal Screws

Free-spanning

by riveting, crimping or

LB 3.5x9.5

as ceiling profileMetal Screw

Knauf GKB 2x 12.5 mm Knauf GKB 12.5 mm Knauf GKB 18 mm

b

UW runneras ceiling profile with UW runner

b

Cladding Knauf GKB12.5 mm

2x 12.5 mmor

18 mm

Max. room width 5.5 m

A

A

C

C

CW 50CW 75CW 100CW 125

0.6 mmMetal thickness

2.53.253.754.25

Knaufas ceiling profile

Max. room width (m)

UW 50UW 75UW 100UW 125

0.6 mmMetal thickness

UW perimeter runneras wall connection

CW 150 4.75 UW 150

500 mm 500 mm 625 mm

Knauf CW double profile

Cladding thickness in mm

2.252.753.253.754.25

12.5 2x 12.5 12.5

33.754.2555.5

2.53.253.754.254.75

2x 12.5

2.753.2544.55

18

with max. axial spacing of ceiling profileswith max. axial spacing of ceiling profilesMaximum room width

Cladding thickness in mm

Knauf CW single profileas ceiling profile

Construct. connection to partitionD131-A1 Cut edge joint single profileD131-C1 Cut edge joint double profileD131-C2All dimensions in mm

load

CW Profile

extra1) load

extraloadextra

loadextra

loadextra

1) 1) 1) 1)

2.533.544.5

22.533.54

2.753.544.55

2.2533.544.5

2.2533.544.5

1) Including extra loads ( 0.05 kN/m² = 5 kg/m² ) for insulation layers required for sound protection

Maximum room width

single profile

centers 750 mm

No jointing is allowed for free-spanning ceilingprofilesHigher room widths with mid-span support areavailable on request

Knauf CW single profile,

e. g. with Metal Screws

Free-spanning

by riveting, crimping or

LB 3.5x9.5

connect with UW runner

500b 500b

+++++

or

625b 625b

acc. to page 4

connect each flangeLB 3.5x9.5

D131 Knauf Free-spanning CeilingsWithout Fire Protection

5

Page 6: Knauf D131 System

Cladding Knauf GKF18 mm

class A

Mineral woolinsulation layer

Thickness 40 mm

25 / 2x 12.5 mmNo insulation layer required.

DIN EN 13162,

b

Max. room width 4.5 m

D D

A

AC

C

BB

section 3.1.1

625 mm2.753.25

4

18 / 25 mm33.5

4.53.54

500 mm 2x 12.5 mm

2x CW 502x CW 752x CW 1002x CW 125

Metal thickness 0.6 mm

Knauf CW double profile Max. axial spacing

bas ceiling profile ceiling profile

Cladding Max. room width

(max. 0.15 kN/m²)Min. thickness

2x CW 150

2.25 2UW 75UW 100

UW 150UW 125

UW perimeter runneras wall connection

Metal thickness 0.6 mm

UW 50

with additional ceilinglevel acc. to page 16

Details, scale 1:5

Max. room width

68 75

75

Solid Board 25 mm

UW perimeter runner,Free-spanning Knauf CW single profile,

connect with UW runner by riveting, crimping ore. g. with Metals Screws LB 3.5x9.5

Knauf GKF 2x 12.5 mm

Solid Board 25 mm

UW perimeter runner

Mineral wool,building material class A,

min. thickness 40 mm,(required for fire

protection) Knauf GKF 18 mm

Fix UW perimeter runner to metal studs of partition with 2 Knauf All Purpose Screws

Knauf CW Profile

Knauf CW double profileas ceiling profile

Knauf CW double profile

Knauf CW double profile

as ceiling profile

Supporting connection to partitionD131vu-D1 Longitudinal edge jointD131vu-B1

Constructional connection to partitionD131vu-A1 Cut edge jointD131vu-C1

All dimensions in mm

Including extra loads ( 0.05 kN/m² = 5 kg/m² ) for insulation layers required for fire protection and/or sound insulation.

anchoring acc. to page 4

No jointing is allowed for free-spanning ceilingprofilesHigher room widths with mid-span support areavailable on request

Max. room width (m)

building material class B2 is allowed.

625b 625b 500b

FN 4.3x35, acc. to page 4 as ceiling profile

Metal Screw LB 3.5x9,5

acc. to

Building material

Insulation of minimum

D131 Knauf Free-spanning CeilingsFire Resistance F30 ● Independently from Below

6

Page 7: Knauf D131 System

Thickness: 40 mm; density: 40 kg/m³

Thickness: 60 mm; density: 30 kg/m³

Details, scale 1:5

Covering strip GKF 25 mm UW perimeter runner

Mineral wool, S

100120

1010

93

Knauf GKF 18 mm

120 mm wide

or60 mm; 30 kg/m³

40 mm; 40 kg/m³

Constructional connection to partitionD131vuvo-A1

Longitudinal edge jointD131vuvo-B1Supporting connection to partitionD131vuvo-D1

Cut edge jointD131vuvo-C1

All dimensions in mm

Cladding Knauf GKF18 mm

Mineral wool insulation layeracc. to DIN EN 13162, section 3.1.1

No jointing is allowed for free-spanning ceilingprofiles

or

S Building material class A,melting point 1000 °C,acc. to DIN 4102-17

25 mm (covering strip 120 mm wide)

Type A

Max. room width 4 m

b

2x CW 502x CW 752x CW 1002x CW 125

Metal thickness 0.6 mm

625 mm

Knauf CW double profile

UW 75UW 100UW 125UW 150

UW perimeter runneras wall connection

18 mm

2.2533.54

as ceiling profileCladding Max. room width

Metal thickness 0.6 mmMin. thickness

22.753.253.5

Including extra loads ( 0.05 kN/m² = 5 kg/m² ) for insulation layers required for fire protection and/or sound insulation.

(max. 0.15 kN/m²)

with additional ceilinglevel acc. to page 16

Max. axial spacing

bceiling profile

Max. room width (m)

93Covering strip GKF 25 mm

120 mm wide

Knauf GKF 18 mm

Knauf CW double profileas ceiling profile

Knauf CW Profile

Fix UW perimeter runner to metal studs of partition with 2 Knauf All Purpose Screws FN 4.3x35, acc. to page 4

Knauf CW double profileas ceiling profile

Covering strip GKF 25 mm60 mm wide

Max. room width

625b 625b 625b

A

AC

C

BBD D

Higher room widths with mid-span support areavailable on request

D131 Knauf Free-spanning CeilingsFire Resistance F30 ● Independently from Below and from Above - Type A

7

Page 8: Knauf D131 System

Details, scale 1:5

Constructional connection to partitionD131vuvo-A2

Longitudinal edge jointD131vuvo-B2Supporting connection to partitionD131vuvo-D2

Cut edge jointD131vuvo-C2

All dimensions in mm

Cladding Knauf GKF18 mm

No jointing is allowed for free-spanning ceilingprofiles

25 mm (covering strip 120 mm wide)

Type B

Max. room width (m)

Covering upper board layer with 10

5,5

Knauf CW double profile

100120

1010

105.5

Knauf GKF 12.5 mm, applied loose Covering upper board layer with

with tight joints, on entire area

Covering upper board layer

b

D D

A

AC

C

Knauf GKF 12.5 mm

2x CW 502x CW 752x CW 1002x CW 125

Metal thickness 0.6 mm

625 mm

Knauf CW double profile

UW 75UW 100UW 125UW 150

UW perimeter runneras wall connection

18 mm

2.2533.54

as ceiling profileCladding Max. room width

Metal thickness 0.6 mmMin. thickness

22.753.253.5

1) Including extra loads ( 0.05 kN/m² = 5 kg/m² ) for insulation layers required for fire protection and/or sound insulation.

(max. 0.15 kN/m²)

with additional ceilinglevel acc. to page 16

Max. axial spacing

bceiling profile

2.252.753.253.75

1)

22.533.25

Covering of Knauf CW double profiles incl.applied loose with tight joints

covering strips on the entire ceiling area

Knauf CW double profileas ceiling profile

Fix UW perimeter runner to metal studs of partition with 2 Knauf All Purpose Screws FN 4.3x35, acc. to page 4

as ceiling profileKnauf GKF 18 mm

Covering strip GKF 25 mm120 mm wide

Knauf GKF 12.5 mm, applied loose

Knauf CW Profile

Covering strip GKF 25 mm60 mm wide

Knauf CW double profileas ceiling profile

Max. room width

625b 625b 625b

+ extra load1)+ extra load

Max. room width 4 m

BB

Knauf GKF 18 mm

Covering strip

120 mm wideGKF 25 mm

UW perimeter runner

with tight joints, on entire area

Higher room widths with mid-span support areavailable on request

D131 Knauf Free-spanning CeilingsFire Resistance F30 ● Independently from Below and from Above - Type A

8

Page 9: Knauf D131 System

With weight determination - Required profile dimensions of supporting Knauf UA Profiles

Knauf CW CW

CW 50500 mm 500 mm

+

625 mm

CW 75

CW 100

CW 125

CW 150

1.5 3 2.4

1.75 3.5 2.8

2 4 3.2

2.25 4.5 3.6

2.5 5 4

axial spacing axial spacing

e.g. insulation ....Profile

Weight of substructure (kg/m²) Possible extra load (kg/m²)

Dead weight of ceilingWeight of Knauf Boards (kg/m²)Type Weight

mm

12.5

25 / 2x 12.525

18acc. to

11.3

22.54.5

16.2

Diamant1040 kg/m³ *)

12.52x 12.5

Knauf GKB / GKF

Covering strip

1326

DIN 1055-1:2002-06

*) Load assumption for dimensioning

900 kg/m³ *)

Thicknesssingle profile

+

Multi-level ceiling is not considered

2

2.5

2x UA 75

2x UA 100

Profile dimensions

Without weight determination - Required profile dimensions of supporting Knauf UA Profiles for room widths up to 3.5 m

The determination of the dead weight is the basis for the determination of the profile dimension of the supporting UA Profile

Copyright by Knauf Gips KG D131-S09 Stand 04.07

Ceiling of continuous room Adjacent roomLoad class Max. room

2

0.15

2.52.5 3 3.5 4 4.5 5 5.5

3.54.55.5

2x UA 50

2x UA 752x UA 75

0.30

2.53.54.55.5

2x UA 75

0.502.53.54.5

0.65 2.53.5

2x UA 100 2x UA 125 2x UA 125 2x UA 150Multi-level ceiling

Max. Room width (m)

2

2.5

Calculation example:

CW double profile 125Axial spacing 625 mm 3.6 kg/m²

Knauf GKF 18 mm 16.2 kg/m²

26.1 kg/m²Dead weight 0.261 kN/m²Load class 0.30 kN/m²

3 3

3.5 3.5

2x UA 125

2x UA 150

Ceiling of continuous room Adjacent roomMax. Room width (m)

2x UA 75

2x UA 100

2x UA 75

2x UA 100

2x UA 100

2x UA 125

2x UA 75

2x UA 100

2x UA 100

2x UA 125

2x UA 125

2x UA 100

2x UA 125

2x UA 150

2x UA 150

2x UA 100

2x UA 125

2x UA 125

2x UA 150

2x UA 150

2x UA 100

2x UA 125

2x UA 150

2x UA 125

2x UA 150

2x UA 150

2x UA 125

2x UA 150

-

-

-

-

-

-

-

-

-

-

-

-

double profile

2x UA 150

9

kN/m² width (m)Max. room width (m)

The continouos room is decisive for weight determination

Indep. from below and from above (Type A)

Covering strip 4.5 kg/m²Insulation layer

1.8 kg/m²60 mm, 30 kg/m³

21 +

21 +

Adjacent roomRoom width

Room

widt

hCo

ntin

uous

room

*

12

Use the respective table of the construction to determine the maximum permissible room widthSee pages 5 to 8

**

**

D131 Knauf Free-spanning CeilingsProfile Dimensions - Supporting Profiles for T and L Connections

9

Page 10: Knauf D131 System

Metal stud partition

Reinforced concrete wall

4x Knauf All Purpose Screw

3x Knauf Ceiling Steel Dowel

Anchoring substrateKnauf UA Profiles 50 Knauf UA Profiles 75-150

Spacing of Distance to room periphery

Other substrate Suitable anchor, min. load capacity:

8x Knauf All Purpose Screwapprox. 70 mm 50 mm + with Metal Traverse

6x Knauf Ceiling Steel Dowel 50 to 80 mm

alternating in slot rowsanchors

1 kN 2 kN Refer to instructions of anchor manufacturer

Anchor

T connection L connection Top view - scheme drawings

Adjacent roomRoom width

Room

widt

hCo

ntin

uous

room

Thickness ofcladding of partitionof the adjacent room

Extension length of Knauf UA profile ca. 650 mm *)

Top view

1

Room periphery

Example: Metal stud partition

Cont

inuo

us ro

om

Adjacent room

*) Extension length in case of reinforced concrete wall: UA 50: 200 mm, UA 75-150: 400 mm (with Knauf Ceiling Steel Dowel acc. to approval ETA - 07/0049)

View

fastened on metal stud of partitionas installation aid, to be used for UA 100 and bigger,

Knauf UA Profile 2Knauf UA Profile 1

Supporting profiles:

connected with attachment screws M8

(UA 50: 2x M8, UA 75 to 150: 4x M8)

"Detail A"

Adjacent roomRoom width

Room

widt

hCo

ntin

uous

room

Metal TraverseMetal stud partition

UW perimeter profile

Knauf All Purpose Screw FN

Knauf All Purpose Screws FN

1

1

Direct anchoring of supporting Knauf UA Profile

"Detail A" - direct anchoring of supporting Knauf UA Profiles on wall

750 mm

Note

FN 4.3 x 35 (cladding thickness 20 mm) / FN 4.3 x 65with suitable washer, t = 2 mm, Ø 30 mm

with suitable washer, t = 2 mm, Ø 30 mm

with washer

UW-Randprofil

Supporting Knauf UA Profiles , 21

at perimeter connection

in slot rows with attachment screws M8

Room

perip

hery

Supporting Knauf UA Profile ,1

Supporting Knauf UA Profiles , connected alternating 21

Metal Traverseanchored on Metal Traverse with

(see also table below)

E

E

E

"Detail A"E

+

+

For configuration / anchoring of UW Profiles and CW Profiles (ceiling profiles) see pages 12 and 13

ca. 70

Connection Angle

50 to 80 mm

First anchor

Room periphery

D131 Knauf Free-spanning CeilingsSupporting Profiles for T Connection and L Connection

10

Page 11: Knauf D131 System

L Connection Top view - scheme drawings

Example: Metal stud partition

Adjacent roomRoom width

Room

widt

hCo

ntin

uous

room

"Detail B" - Anchoring of supporting Knauf UA Profiles with 2x Connection Angles on wall21 +

Room periphery

UW perimeter profile

2x Connection Angle,anchored on Metal Traverse with Knauf All Purpose Screws FN (see also table below)

Metal Traverse

Metal stud partition

Anchoring of supporting Knauf UA Profiles with 2x Connection Angles on wall21 + All dimensions in mm

Top view

and Connection Angle,

(UA 50: 2x M8, UA 75 to 150: 4x M8)

For configuration / anchoring of UW Profiles and CW Profiles (ceiling profiles) see pages 12 and 13Note

Substrate / anchors / spacings

Other substrate

Total min. load capacity 1 kN

Metal stud partition with Metal Traverse4x Knauf All Purpose ScrewUA 50:

UA 75 to 150: 8x Knauf All Purpose ScrewFN 4.3 x 35 (cladding thickness 20 mm) / FN 4.3 x 65

with suitable washer, t = 2 mm, Ø 30 mm

Reinforced concrete wall4x Knauf Ceiling Steel DowelUA 50:

UA 75 to 150:

with suitable washer, t = 2 mm, Ø 30 mm

6x Knauf Ceiling Steel Dowel

50 50 50

50 50

70 70

Suitable anchor (Refer to instructions of manufacturer for spacings of anchors)

Total min. load capacity 2 kNUA 75 to 150:UA 50:

2x Connection Angle, bended

2x Connection Angle, bended

933429

.529

.5

200100100

82.5

Connection Angle

connected with attachment screws M8

Connection angle,before bending

All dimensions in mm

(acc. to approval ETA - 07/0049)

E

E

"Detail B"

Knauf UA Profile 2Knauf UA Profile 1

Supporting profiles:

Room

perip

hery

Supporting Knauf UA Profiles , 21 +

D131 Knauf Free-spanning CeilingsSupporting profile for L Connection

11

Page 12: Knauf D131 System

Installation of Metal Traverse*) inmetal stud partition for anchoring ofsupporting Knauf UA Profile

Connect supporting Knauf UA Profiles

alternating in slot rows at aspacing 750 mm

Connect UW perimeter runner with

Screws FN 4.3x35 mm at web, at a

Interleave UW-Profil with supporting Knauf UA Profile , and connect them

Anchoring supporting Knauf UA Profileon Metal Traverse with Knauf All Purpose

with Metal Screws LB 3.5x9.5 mm on the

2

1

4

1

3

43

"Detail B" - construction

Anchor both bended ConnectionAngles on Metal Traverse with

Metal Traverse

Knauf CW Profiles

UW Profiles

Supporting profiles

Room periphery

Connection Angle

Supporting profiles

For installation and anchoring of

profiles of the continuous room

Place angle in UW perimeter

see "Detail A"

Metal Traverse

Example: Metal stud partition - scheme drawings"Detail A" - construction

*) For installation of Metal Traverse see

spacing of 500 mm

Knauf All Purpose Screws FN

1

21

1

upper flange at a spacing of 250 mm

3

For installation of the ceiling

UW Profiles 43 +

Screws FN (see page 10)

Additionally connect supporting profiles

(UA 50: 2x M8, UA 75 to 150: 4x M8)

with attachment screws M8

at perimeter connection with M8 screws

UW Profile with 2x Knauf All Purpose

rooms into the UW perimeter runner

(see page 11)

runner of the adjacent room

Profiles and Connection

(UA 50: 2x M8, UA 75-150: 4x M8)

Connect supporting Knauf UA21

Washers:Apply attachment screws M8 that are included in the Connection Angle kit with one washer on the side of the nut.

UW Profiles

Knauf CW Profiles

Angles with attachment screws M8

1

2

Apply customary attachments screws M8 (strength class 8.8) with two washers (one on each side).

(see page 4)

(t = 2 mm, Ø 30 mm)

see "Detail A"

Insert ceiling profiles of the continuous

Installation of Metal Traverse*) inmetal stud partition for anchoringof Connection Angle

Example: Metal stud partition - scheme drawings

Technical Data Sheet W21 Knauf Sanitary Built-Ins

+

+

(Cut out upper flange in the areawhere the angle will be placed,

Fire protection:For configuration with fire protection see details on page 13.

Notes

Room periphery

Room periphery

Room periphery

if necessary)

D131 Knauf Free-spanning CeilingsSupporting Profiles for T Connection and L Connection

12

Page 13: Knauf D131 System

Details, scale 1:5D131-E1 Supporting profile for T connection and L connection D131vu-E1 Supporting profile for T and L connection

D131vuvo-E1 D131vuvo-E2

Without fire protection F30 Independently from below 250 mm 250 mm

25 mm

25 mm

10 mm

250 mm 250 mm

25 mm 25 mm

20 mm

25 mm

20 mm

25 mm

20 mm

acc. to DIN EN 13162, section 3.1.1S Building material class A,

melting point 1000 °C,

acc. to DIN 4102-17

Mineral wool insulation layer Note:

12

Supporting profile for T connection and L connection Supporting profile for T and L connection

UW Profile 3Metal Screw

runner 4

2x FN 4.3x35, Knauf UA ProfileKnauf UA Profile

Attachment screw M8,

Connection Angle,

Knauf CW double

LB 3.5x9.5,

UA 100 and bigger

Continuous room Adjacent room

Supporting profiles

Continuous room Adjacent room

3

SMineral wool

SMineral wool

as installation aid, for

Knauf CW doubleprofile as ceiling profile as ceiling profile

F30 Independently from below and from above - Type 2

in supporting profilesSMineral woolin supporting profiles

up toCW double profiles

Knauf CW doubleprofile as ceiling Knauf CW double

profile as ceiling

Knauf CW double

profiles

Knauf CW doubleprofiles as ceiling

Refer to respective configuration of the Free-spanning Ceiling:(see pages 5 to 8)

density 30 kg/m³

spacing 250 mm

spacing 500 mm

UW Profile 3Metal Screw

2x FN 4.3x35,

LB 3.5x9.5,spacing 250 mm

spacing 500 mm

spacing 500 mm

Cut out upper flangeif necessary

UW perimeterrunner 4

UW perimeter

12

Knauf UA ProfileKnauf UA Profile

Supporting profiles

profile

Room periphery

profileprofile

12

Knauf UA ProfileKnauf UA Profile

Supporting profiles

12

Knauf UA ProfileKnauf UA Profile

Supporting profiles

profiles

Room peripheryRoom periphery

runner 4

profiles as ceiling

D131 Knauf Free-spanning CeilingsSupporting Profiles for T Connection and L Connection

13

Page 14: Knauf D131 System

Details, scale 1:5

Drywall Screw TN 3.5x35

Knauf CW Profile UW perimeter profile

5 20

Board strip GKF 25 mm

e. g. Knauf Fugenfüller Leicht

20 5

Knauf Nailable Plug L8/80Board strip GKF 25 mm

Connection to wall with shadow gapD131-SO-A1 Connection to wall with shadow gapD131-SO-D1Examples: Fire resistance F30 Independently from below and from above Type A

Movement jointD131-SO-C3 Ceiling bulkheadD131-SO-A2

a 20 mm

Covering strip GKF 25 mm

fastened to metal stud of ceiling bulkheadKnauf All Purpose Screw FN 4.3x35,

Fire resistance F30Application acc. to Technical Data Sheet

Ceiling bulkhead

D16 Knauf Ceiling Built-Ins

Board strip GKF 18 mmGlued with Knauf FugenfüllerLeicht on one side

All dimensions in mm

100 100

25 a a 25

Ceiling plan

A1A1

For details of lighting and access panel see page 15

D1

D1

A2A2C3C3

Lighti

ng

Acce

ss pa

nel

C1C1

B1

B1

C2 / C4C2 / C4

B2 / B4

B2 / B4

Knau

f CW

doub

le pr

ofile

Edge Trim, if necessary

Edge Trim, if necessary

Ceiling bulkhead

Knauf CW Profile

Knauf GKF 18 mm

D131 Knauf Free-spanning CeilingsCeiling Plan - Shadow Gap, Movement Joint, Ceiling Bulkhead

14

Page 15: Knauf D131 System

Fire protection encasement for built-in lighting Details, sclae 1:5

25 400 mm

providers spec.

Höh

e25Steel staples

acc. to DIN 18182

Encasement 400 x 1000 mmmade of Knauf GKF 25 mm

Lighti

ng bo

x

Built-in lighting,fastening acc. to

Axial spacing of ceiling profiles

Built-in lighting,

providers spec.fastening acc. to

Encasement 400 x 1000 mm

Steel staplesacc. to DIN 18182

made of Knauf GKF 25 mm

Additional profile (for openingsup to 200 x 200 mm not required)

Lateral section of built-in lightingD131-SO-C1 Longitudinal section of built-in lightingD131-SO-B1

Access panelLateral section of access panelD131-SO-C4

Axial spacing of ceiling profiles

Clearance

Clearance

Knauf Alutop Access Panel

UW Profile

6 6450 mm

1500 mm

Drywall Screw TB 3.5x35,spacing 170 mm

Longitudinal section of access panelD131-SO-B4

Example: Fire resistance F30 Independently from below

Example: Fire resistance F30 Independently from below and from above

66

625 mm

625 mm

Knauf Alutop Access Panel

Lateral section of access panelD131-SO-C2

Longitudinal section of access panelD131-SO-B2

25 1000 mm

5

5

Board srips GKF, fastened onUW Profile with Drywall Screws TN

Type A Type B

Type A Type B

Board strip GKF fastened onCW Profile with Drywall Screws TN

CW Profile

Drywall Screw TB 3.5x35,spacing 170 mm

Knauf Alutop Access Panel(clearance)

450 mm x 450 mm450 mm x 1500 mm

The Knauf Alutop Access Panel can beIntermediate sizes on requestStandard sizes:fully dismounted

D131 Knauf Free-spanning CeilingsLighting, Access Panel

15

Page 16: Knauf D131 System

Exposed ceiling below free-spanning ceiling

bAxial spacing of furring channel

b

c

Axial sp

acing of ca

rrying ch

annel

a

Spacing of suspenders

Example: Fire resistance F30 Independently from below and from above

1

2

Proof: ABP P-3964/2172

F30Knauf Free-spanning Ceiling D131

E. g. Cleaneo Acoustic Design Ceiling

Apply suspended channels of exposed ceilingalways lateral to ceiling profiles of fire

(Application acc. to Technical Data Sheet D12)

Independently from below and Independently from below

For exposed ceilings made of metal:Min. suspension height 150 mm

Anchoring of suspenders in ceiling channelsof the fire protection level withKnauf All Purpose Screws FN 4.3x35 /FN 4.3x65 (acc. to ABP P-VHT-1802/05-FN)Max. load of exposed ceiling:100 N per suspender

Free-spanning ceiling as fire protection levelThe additional dead load of the exposed ceiling ( 0.15 kN/m²) has to be

Ceiling.Maximum room widths can be taken from the tables on pages 6 to 8.

considered for the maximum ceiling span (room width) of the Free-Spanning

1000

1200

Max. spacings of exposed ceiling

carrying channels

Max. Max. spacing of Max.

500

furring channelsup to 0.15

load class kN/m²

625

a b

All dimensions in mm

500

*) Suspension must be fastened to ceiling profiles of the fire protection level

(for Cleaneo AcousticCeilings see D12)

caxial spacing axial spacingsuspenders *),

21

Knauf All Purpose Screw FN

Detail, scale 1:5

Knauf Board

Alternative suspension:Direct Bracket

UW perimeter profile,

Example: Fire resistance F30 Independently from below

Knauf CW double profile

Universal Bracket for CD 60x27(apply alternating)

Knauf Exposed Ceiling below Free-spanning CeilingD131-D112

see Technical Data Sheet D12

(bend side tabs)

21

Type A

Technical Data Sheet D11 Knauf Board Ceilings Technical Data Sheet D12 Knauf Cleaneo Acoustic Ceilings

anchoring on wall acc. to page 4

+Knauf All Purpose ScrewFN 4.3x35 / FN 4.3x65

exposed ceiling

expose

d ceili

ng

exposed ceiling

Exposed ceiling 0.15 kN/m²2

Fire protection level1

from above

protection level

D131 Knauf Free-spanning CeilingsMulti-level Ceiling

16

Page 17: Knauf D131 System

Description Unit Amount as average value

resistanceItalic= not provided by Knauf

Consumption per m² ceiling without allowance for loss and cut-off. Amounts refer to a ceiling area of: 2.5 m x 10 m = 25 m²

Without firefrom below

Fire resistance: Independently Fire resistance: Independently

12,5 mm

Connection to wallUW perimeter profile

Knauf Boards

Fastening of covering strips - Knauf Drywall Screws

Fastening of Knauf Boards - Knauf Fasteners, see page 2

Filling

Uniflott / Uniflott imgregnated; for hand filling

TN 3.5 x 35 mm

1st layer2nd layer

Knauf Wallboard GKB / GKBI; 12.5 mmKnauf Fire-resistant Board GKF / GKFI or Diamant GKFI; 12.5 mm

(regard fire protection specifications, see page 3)

alt.

Jointfiller Super; for machine fillingFugenfüller Leicht; for hand fillingJoint Tape Kurt (for cut edge and longitudinal edge joints)

Trenn-Fix 65

Edge Trim 23/13; 2.75 m long

m

m

pcs

pcs

pcs

pcs

kg

m

m

m

Covering strip 120 mm wide:

Connection of CW Profile with UW perimeter runner:

Solid Board GKF / GKFI; 25 mmCovering upper board layer:Knauf Fire-resistant Board GKF / GKFI; 12.5 mm

SubstructureSingle profile as ceiling profile - length acc. to span width (room width)

m

pcs

kg

kg

0.8 0.8

1.7 - - -1.9 - - -

12 - --- - -

- - - 0.2

- - - -

- - - 8

19 14- -1922 17

-

0.3 0.5 0.5 0.4

0.4 0.6 - -0.3 0.5 0.5 0.40.75 0.75 1.55 0.75

1 1 1 1

as required

Knauf All Purpose Screws 2x FN 4.3x35 for metal stud partitionsfastener approved for substrate, e. g.

Knauf Ceiling Steel Dowels for reinforced concrete wallsor

Knauf All Purpose Screws FN 4.3x35 for metal stud partitionsfastener approved for substrate, e. g.

Knauf Ceiling Steel Dowels for reinforced concrete wallsbzw. pcs

pcspcs

e. g. metal rivet

pcsMetal Screw LB 3.5 x 9.5 mm (connection of CW Profiles at web)Knauf CW 50 / 75 / 100 / 125 / 150 x 50 x 0.6 m

- 3- 3.8 3 3 **)

Connection of CW Profile with UW perimeter runner: e. g. 2x metal rivets - 3.2 -

2.8 2.8 2.8 2.82.7 2.7 2.7 2.7

2.4 2.4

from below and from above

*) Not possible with UW 50 / **) not possible with CW 150

18 mm2x 12,5 mm 25 mm

2.6

Solid Board GKF / GKFI; 25 mm alt.

Knauf Fire-resistant Board GKF / GKFI; 18 mmalt. 11-

---

--

Fastening of cladding

500 mm 625 mm500 mm 625 mm

Type A

0.8

Profile spacingProfile spacing Profile spacing Profile spacing18 mm

625 mmProfile spacing

Type B

2.82.7

T connection / L connectionKnauf UA Profiles / UW ProfilesMetal traverse / Connection Angle

(see pages 9 to 13)

Suitable anchor

mStSt

as required as required as required

as required as required as required 1

as required as required as required as required

as required as required as required as required

--

3 **)

-2.4

as required

as required

--

0.2

1

1-

8

-17

0.4

-0.40.75

1

as required

as required

Insulation layer

0.8 *) 0.8 *)UW 50 / 75 / 100 / 125 / 150 x 40 x 0.6

Knauf CW 50 / 75 / 100 / 125 / 150 x 50 x 0.6 0.2 0.20.2 0.2 **) 0.2 **)

Knauf CW 50 / 75 / 100 / 125 / 150 x 50 x 0.6

CW Profile - length acc. to span width (room width)

Double profile as ceiling profile - length acc. to span width (room width)

Joint Tape Kurt (for cut edge joints) 0.35 0.35 0.35 0.35 0.35m

bzw.or

TRIAS; for hand fillingalt. 0.3 0.5 0.5 0.4 0.4

D131 Knauf Free-spanning CeilingsConsumption of Material of selected examples

17

Page 18: Knauf D131 System

Item Description No. of units Unit price Total price

...... Subceiling DIN 18168-1, installation height in m ...................., as free-spanning ceiling,ceiling span in m ............................. .Fire resistance class according to DIN 4102-2 F 30,*for the ceiling independently resistant to fi re from below to protect the basic ceiling and the plenum, */for the ceiling independently resistant to fi re from the plenum and from below to protect the room below the ceiling, the basic ceiling and the plenum *.Anchored on reinforced concrete/ masonry/ metal stud partition/ wood frame partition/ ........................... *.Substructure made of galvanized metal channels acc. to DIN 18182-1,ceiling channels as single/ double * CW profi les CW 50/ 75/ 100/ 125/ 150 *.Insulation layer made of mineral wool acc. to DIN EN 13162 thickness in mm ..............., min. density in kg/ m³ ..................., * building material class A, melting point ≥ 1000 °C (1832 °F). */additional board layer on ceiling channels made of Knauf Boards GKF, thickness 12.5 mm *.Cladding made of gypsum boards acc. to DIN 18180:Knauf Diamant/ Knauf Solid Boards GKF/ GKFI */ Knauf Boards GKF/ GKFI/ GKB/ GKBI *, application acc. to DIN 18181, single/ double * layer, thickness 12.5/ 18/ 25/ 2x12.5 * mm.Joint fi lling in accordance with Code of Practice no. 2 (IGG, April 2003)quality standard Q1 basic fi lling to be coated with plaster/ ........... */ quality standard Q2 standard jointing *.Product/ System: Knauf Free-spanning Ceiling D131 ......... m² .......... € .......... €

...... Subceiling DIN 18168-1 as described above, with additional exposed ceiling.Sound absorption coeffi cient according to DIN EN ISO 11654 αW = .............*.Confi guration of acoustical ceiling level with furring channels and carrying channels,suspend with Universal Bracket to ceiling profi les of Free-spanning Ceiling D131,plenum damping with mineral wool, thickness min. 20 mm *.Cladding made of perforated/ slotted * gypsum boards DIN 18180,Knauf Cleaneo Acoustic with air-cleaning effect, board thickness 12.5 mm, application acc. to DIN 18181, single layer,perforation Standard Circular R: 6/18 R/ 8/18 R/ 10/23 R/ 12/25 R/ 15/30 R */perforation Alternating Circular R: 8/12/50/ 12/20/66 * R/perforation Random Plus R: 8/15/20 R/ 12/20/35 R */ perforation Standard Square Q: 8/18 Q, 12/25 Q *,lamination on rear side with sound absorbent Knauf Standard Fleece, color: white/ black/ ............ *.Joint treatment: fi lling/ with Knauf Joint Cover Profi le, color ........../ .......... *.Product/ System: Knauf Cleaneo Acoustic Ceiling D127 below Free-Spanning Ceiling D131 ......... m² .......... € .......... €

...... Connection of free-spanning ceiling to free-spanning ceiling as T connection/ L connection *,Span width of continuous ceiling in m ........., Span width of adjacent ceiling in m ..........,Anchored on: wall made of reinforced concrete/ masonry/ metal stud partition ........................... *.Confi guration with supporting profi les as double profi les Knauf UA 50/ 75/ 100/ 125/ 150 *acc. to Knauf Technical Data Sheet D131, current edition. .......... m² .......... € .......... €

* Cancel not applicable items Sub-total ............... €

D131 Knauf Free-spanning CeilingsSpecifications / Substructure

ConstructionKnauf Free-Spanning Ceilings are solely anchored on the walls at perimeter. Knauf Boards are fas-tened to a metal substructure made of Knauf CW profi les as single or double profi les.The application of additional loads like lighting fi x-tures with max. 100 N (10 kg) per double profi le and exposed ceilings such as D127 Knauf Acous-tic Ceilings with load per unit area of 15 kg/m² or max. single load of 100 N with suitable anchors di-rectly to the metal substructure is permissible. Re-

gard extra loads for dimensioning of T or L con-nections.Joints of free-spanning channels are not allowed. Movement joints have to be transferred into the construction of the free-spanning ceilings. Use control joints in the case of ceiling areas over ap-prox. 15 m length, or for narrow ceiling spaces caused by a break of a wall. Separate connec-tions of boards to components made of a dif-ferent building material, especially columns, or

thermally highly stressed built-ins like lighting fi x-tures, for instance with shadow gaps.Knauf profi les are delivered galvanized. The cor-rosion protective coating is suffi cient for indoor application, including bathrooms and kitchens in private housing. For other areas, e.g. under infl u-ence of outdoor air, additional corrosion protec-tion is necessary (see DIN 18168-1 table 2).

18

Page 19: Knauf D131 System

D131 Knauf Free-spanning CeilingsApplication / Filling / Coat and Linings

ApplicationSubstructure■ Supporting perimeter connection made of UW

Profi les. Anchoring acc. to table on page 4. ■ In case of sound protection requirements, seal

up carefully with Acoustical Sealant according to DIN 4109, supplement 1, chapter 5.2; porous sealant strips like Sealing Tape are usually not suitable in this case.

■ Ceiling profi les made of Knauf CW Profi les as single or double profi les. In case of fi re protec-tion requirements, apply only double profi les.

■ Connect CW Profi les as double profi les at web with metal screws acc. to page 4.

■ Support length of CW Profi les in UW perimeter runners has to be at least 30 mm. Connect upper fl anges of UW/CW Profi les by riveting, screwing or crimping, if no covering strip is required.

Cladding■ In case of fi re protection requirements, attach

Knauf Board Strips GKF, 25 mm thick, 120 mm wide, as covering strips on upper fl anges of CW double profi les alternating with Drywall Screws TN 3.5 x 35 mm at max. 250 mm centers.

■ Apply Knauf Boards lateral to ceiling profi les.■ Stagger cut edge joints by at least 400 mm while

placing them on profi les. If using 4AK Boards (4-

side tapered edges) cross joints are allowed in connection with fi lling with joint tape, preferably Knauf Joint Tape Kurt.

■ Start fastening of Knauf boards either in the mid-dle or at a corner in order to prevent upsetting deformation. Press boards fi rmly on to the grid and fasten with Drywall Screws acc. to page 2.

■ Use separation strip Trenn-Fix and fi ller or acry-late for connections to other components.

Multi-level CeilingApplication according to instructions on page 16.

FillingSurface quality■ Filling of gypsum boards acc. to the required

quality standard Q1 ro Q4 acc. to Code of Prac-tice No. 2 “Verspachtelung von Gipsplatten, Oberfl ächengüten“ o the IGG.

Filling compoundsSelect suitable fi lling compound considering qual-ity requiremens and board type: ■ Uniflott: Hand filling without joint tape: HRAK, HRK / with joint tape: AK■ Uniflott impregnated: Hand filling of impregnated boards without joint tape: HRAK, HRK hydrophobic, green■ TRIAS: Hand filling without joint tape: HRAK, HRK / with joint tape: AK color adapted to paper color of gypsum boards, reduced absorption for surfaces with uniform ap-

pearance

■ Fugenfüller Leicht: Hand filling with joint tape: HRAK, AK■ Jointfiller Super: Machine filling with joint tape: HRAK, AK■ Readygips: Hand or machine filling with joint tape: AK

Application■ For multi layer cladding, fi ll in joints of fi rst layers,

smooth joints of top layer.■ Fill all visible screw heads as well.■ Recommendation: Fill cut edge joints of visible

layers using Knauf Joint Tape Kurt, no matter which fi lling material is used.

■ Slightly sand visible surface after drying of fi lling compound, if necessary.

General note: Filling of all concealed board lay-ers in case of multi-layer cladding is necessary to preserve the required properties for fi re protection, sound insulation and stability.

Application temperature/ climate■ Filling of joints should only take place after the

boards have been allowed to rest in the given humidity and temperature zones, and no more longitudinal changes can be expected, i.e. ex-pansion or contraction.

■ Joints should be filled at a minimum room and surface temperature of +10 °C (50 °F).

■ In case of mastic asphalt screed, fill joints after screed has been applied.

■ Refer to Code of Practice No. 1 “Baustellen-bedingungen“ of the IGG.

Coats an liningsPre-treatmentBefore applying paints or coats the fi lled surface should be dust-free. Pre-treat and prime gypsum board surfaces before the application of coats and linings (wallpaper) ac-cording to Code of Practice No. 6 of the IGG “Vor-behandlung von Trockenbaufl ächen aus Gipsplat-ten zur weitergehenden Oberfl ächenbeschichtung bzw. –bekleidung“. Ensure that the primer and the coat, paint or lining are compatible.To settle the different suction properties of the fi lled areas and the paper surface, primers such as Knauf Tiefengrund/ Spezialgrund/ Putzgrund are suitable.In case of wallpaper lining a primer that allows an easier removal of wallpaper for redecoration is rec-ommended.

Suitable coats and linings The following coats and linings can be used on Knauf Boards:■ Wallpapers: Paper, textile, and synthetic wallpa-

pers. Use only adhesives made of cellulose ac-cording to Code of Practice no. 16 “Technische Richtlinien für Tapezier- und Klebearbeiten“, re-leased by Bundesausschuss Farbe und Sach-wertschutz.

■ Plasters: Knauf Structured Plasters, Knauf Skim Plasters, entire surface smoothing such as Knauf Readygips or Knauf Multi-Finish, up to 2 mm thickness.

Regard extra load of plaster for the evaluation of permissible room width and when dimensioning L or T connections.

Plaster coating only in connection with filling with joint tape.

■ Coats: Resin dispersion paints, multicolored (rainbow) emulsion, oil paint, matte-fi nish lac-quer, alkyd resin paint, polymer resin paint, PUR lacquer, or epoxy-based lacquer.

■ Silicate-based emulsion paints may be used af-ter application of a primer that is suitable for the respective surface acc. to the instructions of the provider.

Unsuitable are:■ Alkaline coats such as lime, water glass paints

and silicate-based paintsAfter wallpapering or plastering ensure adequate ventilation for fast drying.

Note:Gypsum plasterboard surfaces that have con-stantly been exposed to light without any protec-tion can cause yellowing after coating. Therefore a trial coat is recommended that will extend across several boards including all joints. Yellowing can, however, be successfully avoided only by using a special primer.

19

Page 20: Knauf D131 System

D131 Knauf Free-spanning CeilingsDeclaration of Compliance

Declaration of compliance by the system manufacturer

Knauf Gips KGAm Bahnhof 797346 Iphofen, Germany

It is certified herewith that the construction variants, application details and specified products included in Knauf Technical Data Sheet D131 Knauf Free-spanning Ceilings, edition 2007-04 are fully in accordance with the specified valid building supervisory proofs respectively.

As far as specified for the respective system / detail, this applies particularly to ■ the structural calculation acc. to DIN 18168 and/or DIN EN 13964■ fire protection acc. to ABP P-3964/2172

In order to fulfill the building supervisory requirements specified above in the installation of Knauf ceiling systems, building and application have to be done according to the valid edition of Knauf Technical Data Sheet D131 with system components specified there. This has to be certified by the installer of the component with the declaration of compliance (see above) towards the contractor.

Iphofen, April 2007

Prof. Dr. Hummel Dr. Ruf

Declaration of compliance by the installer of the building component

Installer: .................................................................................................................................................................................................(name, address) .................................................................................................................................................................................................

Site / building: .................................................................................................................................................................................................

Date of installation: .................................................................................................................................................................................................

Building Component / .................................................................................................................................................................................................requirements: .................................................................................................................................................................................................

It is certified herewith that the Knauf Free-spanning Ceiling system as stated above has been built and installed in accordance with

Knauf Technical Data Sheet D131 Knauf Free-spanning Ceilings, edition 2007-04

with the system components specified there, and has therefore been built regarding the declaration of compliance by the system manufacturer below in accordance with the valid building supervisory proofs concerning statics, sound insulation and fire protection.

.............................................................................................................. ..........................................................................................................Place, date Stamp and signature

A declaration of compliance specifi ed for your project is available from Knauf Direkt Technical Advisory Service.

D131/engl./D/04.07/FB/D

All technical changes reserved. Only the current printed instructions are valid. Our warranty is expressly limited to our products in flawless condition. All application quantities and delivery amounts are based on empirical data that are not easily transferable to other deviating areas. The stated information represents current state-of-the-art Knauf technology. The entire state of approved engineering rules, appropriate standards, guidelines, and rules of craftsmanship are not included herewith. These and all application instructions have to be adhered to separately by the in-staller. All rights reserved. All amendments, reprints and photocopies, including those of excerpts, require the express permission of Knauf Gips KG, Am Bahnhof 7, 97346 Iphofen, Germany. Delivery via professional building material distributors only, in accordance with our current business, delivery and payment terms.

The constructional and structural properties, and characteristic building physics of Knauf systems can solely be ensured with the exclusive use of Knauf system components, or other products expressly recommended by Knauf.

Knauf Drywall and Floor Systems Am Bahnhof 7, 97346 Iphofen, Germany

Phone.: +49 9001 31-1000 *

Knauf DirectTechnical Advisory Service:

Fax: +49 1805 31-4000 **

* A rate of 0.39 € per minute will be charged for calls from within the German landline network. Callers whose phone numbers are not registered in the address database of Knauf Gips KG, i.e. private builders or non-patrons, will be charged a rate of 1.69 € per minute. Calls from mobile phones will be charged 1.48 € per minute.

** 0,14 €/Min.

www.knauf.de

s amp l e

smem manufacturer

s ame construction variants, application details anon 2007-04 are fully in accordance with the s

he respective system / detailtion acc. to DIN 18168 and/or DINABP P-3964/2172

rvisory requirements spnauf Technical Data

nent with the declaration of compliance (see

phofen, April 2

Dr. Hummel s amme

mp l e.................................................

.........................................................................................

......................................................................................

...................

...................

............

as been built and installed

07-04

n and fire protection.

......... ...... Sta Stmp l e

sss