H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 1
KKT Water Chiller forMAGNETOM AVANTOMAGNETOM ESPREEMAGNETOM Trio, A Tim System
R 134a
KCC 215-L-U/S (US market)
KCC 215-L-S (r.o.w. market)
Siemens Medical Solutions AG
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 2 © KKT-KRAUS Refrigeration & Air Conditioning
The illustrations of products of the Siemens company
are shown with friendly permission by Siemens Medical Solutions.
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 3
list of contents
page 5 description KKT waterchiller
page 6 nameplate KCC 215-L-U/S
page 7 technical data KCC 215-L-U/S
page 8 nameplate KCC 215-L-S
page 9 technical data KCC 215-L-U/S
page 10 dimensions KCC 215 (inch)
page 11 dimensions KCC 215 (mm)
page 12 key: cold water / glycol diagram
page 13 cold water / glycol diagram
page 14 key: refrigerant diagram / compact design
page 15 refrigerant diagram / compact design
page 16 waterchiller installation / I
page 17 waterchiller installation / II
page 18 IFP (manufacturer = Kutting)
page 19 IFP (manufacturer = Kutting)
page 20 overvolting protection
page 21 overview of waterchillertransfer station / remote control panel
page 22 transport
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 4 © KKT-KRAUS Refrigeration & Air Conditioning
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 5
2 separate cooling circuits 50/50 %
partial / emergency cooling possiblewith one compressor
high quality safety and controlinstruments
R 134a „Ozon Safe refrigerant“
The KKT Waterchillers are conceived, developed and produced as a compact systemfor the MAGNETOM AVANTO / ESPREE / TRIO. They are suitable for outdoor installati-ons. Power supplies of 380V - 480V/50-60Hz. UL approved version is 480V/60Hz. Am-bient temperatures up to 118.4° F [48°] C. Installation up to 6,562 feet [2,000 m] abovesea level possible.Produced and testet in accordance with Siemens Medical Engineering specifications.
frontal operation
mainly Siemens products in the switch box
totally integrated automation with display(Siemens S7)
operator panel
separate fault alarm
switch box heater / fans
UPS operation - optional extra available throughour customer service (low starting current)
no fuses (only automatic fuses / circuit breakers)
wired on clamps
cooling circuit including pump, regulation valve, filter strainer,shut-off fittings, automatic air vent, fill- and outlet valves,thermometers, pressure gauges
expansion receiver, safety valve, pressure gauge
flow control
overheating protection
glycol filled
description KKT Waterchiller - Outdoor Version
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 6 © KKT-KRAUS Refrigeration & Air Conditioning
nameplate KCC 215-L-U/S
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 7
technical data
Waterchiller Typ KCC 215-L-U/S outdoor use
designed for MAGNETOM AVANTO / ESPREE / Trio, A Tim System
standard device standard noteconstruction
nominal cooling capacity (Btu/hr [kW]) 205,000 [60.0]refrigeration medium R 134aquantity of compressors 2compressor capacity (HP [kW]) 18.2 [13.4] Fabr.: DWM Type: ZR 16
volume of condenser airflow (m³/s [m³/h]) 10.0 [36,000]number of axial fans (piece) 4condenser fan motor (HP [kW]) 1.54 [1.15]max. ambient air temperature (°F [°C]) +118 +48min. ambient air temperature (°F [°C]) -4.0 [-20]
cooling medium PCW/AFN PKW/AFN AFN = 38% ethylene glycol ratemin. cooling medium out (°F [°C]) +66.2 [+19.0]max. cooling medium out (°F [°C]) +71.6 [+22.0]temperature stabilty (K) ±0.8min. volume of cooling medium (gpm [l/min]) 34.34 [130.0]ext. pump pressure (psig [bar]) 58.0 [4.0] Fabr.: Speck Type: IN-V10-50pump power (HP [kW]) 4.0 [3.0]
noise level (dB[A]) 61 abt. 32.8 ft [10m] distance/ 118°F [48°C]55 abt. 32.8 ft [10m] distance/ 90°F [32°C]50 abt. 32.8 ft [10m] distance/ 70°F [21°C]
power supply (V/Ph/Hz) 480/3/60 tolerance -14/+10%V/±1 Hzcontrol voltage (VDc) 24full load amps (A) 58.5form of protection IP 54internal piping volume (gals. [l]) 4.49 [17.0]plumbing 2”
shipping weight (lbs [kg]) 3,527 [1,600]operation weight (lbs [kg]) 2,425 [1,100]
[....] = alternate units
WWWWWarning:arning:arning:arning:arning:The 38% glycol rate dependsThe 38% glycol rate dependsThe 38% glycol rate dependsThe 38% glycol rate dependsThe 38% glycol rate dependsnot on the local ambientnot on the local ambientnot on the local ambientnot on the local ambientnot on the local ambienttemperature !!!temperature !!!temperature !!!temperature !!!temperature !!!
Do not use propylene glycol orDo not use propylene glycol orDo not use propylene glycol orDo not use propylene glycol orDo not use propylene glycol orautomotive antifreeze.automotive antifreeze.automotive antifreeze.automotive antifreeze.automotive antifreeze.
R 134a
120.47 inch
3,060 mm
37.80 inch960 mm
72.0
5 in
ch1,
830
mm
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 8 © KKT-KRAUS Refrigeration & Air Conditioning
nameplate KCC 215-L-S
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 9
technical data
Waterchiller Typ KCC 215-L-S outdoor use
designed for MAGNETOM AVANTO / ESPREE / Trio, A Tim System
standard device standard noteconstruction
nominal cooling capacity (Btu/hr [kW]) 205,000 [60.0]refrigeration medium R 134aquantity of compressors 2compressor capacity (HP [kW]) 21.7 [16.0] Fabr.: DWM Type: ZR 19
volume of condenser airflow (m³/s [m³/h]) 10.0 [36,000]number of axial fans (piece) 4condenser fan motor (HP [kW]) 1.54 [1.15]max. ambient air temperature (°F [°C]) +118 +48min. ambient air temperature (°F [°C]) -4.0 [-20]
cooling medium PCW/AFN PKW/AFN AFN = 38% ethylene glycol ratemin. cooling medium out (°F [°C]) +66.2 [+19.0]max. cooling medium out (°F [°C]) +71.6 [+22.0]temperature stabilty (K) ±0.8min. volume of cooling medium (gpm [l/min]) 34.34 [130.0]ext. pump pressure (psig [bar]) 58.0 [4.0] Fabr.: Speck Type: IN-V10-70pump power (HP [kW]) 4.0 [3.0]
noise level (dB[A]) 61 abt. 32.8 ft [10m] distance/ 118°F [48°C]55 abt. 32.8 ft [10m] distance/ 90°F [32°C]50 abt. 32.8 ft [10m] distance/ 70°F [21°C]
power supply (V/Ph/Hz) 380-480/3/50 tolerance -14/+10%V/±1 Hzcontrol voltage (VDc) 24full load amps (A) 55.0form of protection IP 54internal piping volume (gals. [l]) 4.49 [17.0]plumbing 2”
shipping weight (lbs [kg]) 3,638 [1,650]operation weight (lbs [kg]) 2,535 [1,150]
[....] = alternate units
WWWWWarning:arning:arning:arning:arning:The 38% glycol rate dependsThe 38% glycol rate dependsThe 38% glycol rate dependsThe 38% glycol rate dependsThe 38% glycol rate dependsnot on the local ambientnot on the local ambientnot on the local ambientnot on the local ambientnot on the local ambienttemperature !!!temperature !!!temperature !!!temperature !!!temperature !!!
Do not use propylene glycol orDo not use propylene glycol orDo not use propylene glycol orDo not use propylene glycol orDo not use propylene glycol orautomotive antifreeze.automotive antifreeze.automotive antifreeze.automotive antifreeze.automotive antifreeze.
R 134a
120.47 inch
3,060 mm
37.80 inch960 mm
72.0
5 in
ch1,
830
mm
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 10 © KKT-KRAUS Refrigeration & Air Conditioning
dimensions KCC 215 (inch)
waterchiller
rain protecting plate
switchboard
1.06
0.79
0.59
1.10
0.59
1.38
0.67
1.57
118.11
119.68
11.81
11.22
35.04
6.10 59.05 59.05
0.79
air in air in
8
air inair in
6
6 = switchboard ventilation
7 = cable passage "main power"
2 = water supply to IFP (2") fermale
4 = main switch
3 = DDC-display
1 = water return from IFP (2") fermale
detail x
service side
dimensions in inch.
KCC 215-L...
rain protecting plate
carriage hole
detail x
5 = controll lamps
air inair in
air in
air in
8 = cable passage "data transfer cable"
37.00
35.43
1.57
37.80
8.0715.9420.28
24.02
4.53
1 72
4.53
~3.15
3
6
65
4
37.80
120.47
air in
air out
air out air out
72.05
120.47
118.111.57
air out
air in
20.87
air out
5.90
2.00
3.54
41.14
64.17
72.0
5
119.69
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 11
dimensions KCC 215 (mm)
rain protecting plate
switchboard
27
20
air in air in
8
air inair in
15
28
1535
17
air inair in
air in
air in
8 = cable passage "data transfer cable"
KCC 215-L...
air out
air in
530
air out
150
5090
1045
1630
1830
3040
3060
300040
940
900
40
960
205405515
610
115
1 72
115
ca.803
6
65
4
960
3060
air in
air out
air out air out
1830
40
3000
3040
300
285
890
155 1500 1500
20
6
6 = switchboard ventilation
7 = cable passage "main power"
2 = water supply to IFP (2") fermale
4 = main switch
3 = DDC-display
1 = water return from IFP (2") fermale
waterchiller
detail x
service side
dimensions in mm.
rain protecting plate
carriage hole
detail x
5 = controll lamps
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 12 © KKT-KRAUS Refrigeration & Air Conditioning
key: cold water- / glycol diagram
safety relief valve (water)
automatic air vent
non-return valve
manual air vent
filling and draining cock
shut-off valve
TA regulating valve
filter strainer
cooler (Siemens)
evaporator
air receiver with automaticair vent
TT
PI
temperature sensor
pressure gauge
expansion receiver
flow meter
high pressure pump
FS
H
H
transfer station
overflow valve
ACS
IFP
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 13
cold water- / glycol diagram
2"
2" H
1/2"
H
TA
PI
TT
PI
TT FS
IFP ACS Siemens
1 1/2"
XGE 42-LR 1 1/2"
1 1/2"
with insulationCu-pipe
KKTwaterchiller
evaporator1
2evaporator
hose
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 14 © KKT-KRAUS Refrigeration & Air Conditioning
key: refrigerant diagram
Schrader valve
moisture indicator
inspection gauge with
refrigerant dehydrator
refrigerant non-return valve
vibration absorber
refrigerant shut-off valve
evaporator
receiver
with cap
PZAHH
suction gas line
liquid line
hot gas line
pipe mixing section
high pressure switch
low-/high pressure receiver
expansion valve
thermostatic
compressor with
condenser with fan
Rotalock valve
solenoid valve
PTHPTL
TC
R134a
el.
crank-tub-heater
M
speed controller
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 15
refrigerant diagram
TCTC
PTH
PTH
PTL
PTH
PTL
M M
el.
condensor 1 condensor 2
1evaporator
2evaporator
system 1
system 2PZAHH
el.
MM
TC
TC
PTH
PZAHH
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 16 © KKT-KRAUS Refrigeration & Air Conditioning
waterchiller installation / I
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 17
waterchiller installation / II
installation example C
installation example B
installation example A
free access for servicing
free access for servicing
Air outlet keep free!
min.
40inch
min.1000mm
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 18 © KKT-KRAUS Refrigeration & Air Conditioning
IFP - manufacturer
for further information contact Siemens Customer Support
connector fittingslocated inside KKT-Chiller
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 19
IFP - manufacturer
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 20 © KKT-KRAUS Refrigeration & Air Conditioning
overvoltage protection
X8 Chiller cabinet
X81 ACC roof
overvoltage protector
grounding wire
data transfer cable(164 ft / 50m)
Filter out
Filter in
connectiongrounding wire
mains boxgrounding bus
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 21
overview of waterchillertransfer station / remote control panel
= deliveret with chiller
= not scope of delivery KKT
2
data transfer cable
recommended
interface station
2
for water pipes
< 45m/148ft
> 45m/148ft consult KKT
pipe dimensions
technic room
one way distance
indoor
outdoor
2 1/2"/65mm
ASC SiemensXGE 42-LR 1 1/2"
2"
2"
KCC 215-L...
IFP
1
= scope of delivery KKT1
3
4
= deliveret with chiller
15 x AWG 26,
4
3
2"/50mm< 25m/82ft
4
164ft50m
protectorovervoltagedata transfer cable
datatransfercable
mains box
ACC
X81 X80
datatransfer
cable
X810IFP
ground
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 22 © KKT-KRAUS Refrigeration & Air Conditioning
transport
min.158inch
min.4,000mm
min.
158inch
min.
4,000mm
110.2
4inch
2,800mm
STRAP OR ROPE*
LOCKING PIN
SPILT PINS
LIFTINGTUBE
*Attention: don't use metal rope !!
lifting tubediameter max: 1.23inch/33mm
diameter min: 1.18inch/30mm
material thrickness: min. 0.12inch/3mm
length: 47.24inch/1,200mm
* = shipping weight
spacers
~ 3,63
8 lbs*
~ 1,65
0 kg
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
© KKT-KRAUS Refrigeration & Air Conditioning page 23
H:\PM\Geraete\Avanto\Prospekt\Avanto0107.pmd
page 24 © KKT-KRAUS Refrigeration & Air Conditioning
Technical developmentmay cause changes of configuration
KKT-KRAUSRefrigeration & Air ConditioningIndustriestraße 23aD 91207 Lauf a. d. Pegnitz
Mail [email protected]