KEO Design Report

Embed Size (px)

Citation preview

  • 8/20/2019 KEO Design Report

    1/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0201-MC-KEO-RP-00209 Page i

    Rev. D02

    Control Sheet

    IA/12-13/D/003/ST

    Pre Contract Professional Consultancy Design Services

    for AI Rayyan Road & AI Bustan Street South (P007)

    AL RAYYAN ROAD 

    Al Rayyan Road

    Junctions R6 Road Tunnel

    Tunnel SCADA PMCS Control Concept

    Prepared by: 

    Doc. No.: EXW-P007-0201-MC-KEO-RP-00209

    Rev. D02 

  • 8/20/2019 KEO Design Report

    2/40

  • 8/20/2019 KEO Design Report

    3/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0201-MC-KEO-RP-00209 Page iii

    Rev. D02

    TABLE OF CONTENTS

    1.0 INTRODUCTION ...................................................................................................................................... 1 

    1.1 Document Purpose and Scope ........................................................... ....................................................... 1 

    1.2 Related Documents .................................................................................................................................. 1 

    1.3 Related Drawings ..................................................................................................................................... 1 

    1.4 Codes and standards applicable .............................................................................................................. 4 

    1.5 List of Abbreviations ............................................................... ................................................................. . 5 

    2.0 ASHGHAL’S RELEVANT OBJEVTIVES ............................................................................................................ 9 

    3.0 ELECTROMAGNETIC COMPATIBILITY (EMC) ...................................................................................... 9 

    3.1 Normative references .......................................................................................................................... 9 

    4.0 PMCS OVERVIEW .................................................................................................................................. 10 

    4.1 Introduction............................................................................................................................................ 10 

    4.2 System Architecture ............................................................................................................................... 11 

    4.3 SCADA Servers ........................................................................................................................................ 11 

    4.4 Supervisory Control PLC’s ................................................................. ...................................................... 12 

    4.5 Outstation PLC’s .......................................................... ................................................................. .......... 12 

    4.6 Dual configuration ................................................................................................................................. 12 

    4.7 SCADA Graphical User Interface (Operator Interface) ...................... ..................................................... 13 

    4.8 TMC/TSS ........................................................... ................................................................. ..................... 14 

    4.9 Engineering Terminal ............................................................................................................................. 14 

    4.10 Control & Monitoring Software............................................................................................................ 15 

    4.11 Control Network ................................................................................................... ................................ 15 

    4.12 Instrumentation Interface .................................................................................................................... 15 

    4.13 Cable Types .......................................................................................................................................... 16 

    4.14 Equipment Accommodation ............................................................ ..................................................... 16 

    4.15 Power Supply Redundancy ................................................................................................................... 16 

    4.16 Capacity Sizing ..................................................................................................................................... 16 

    5.0 GENERAL MONITORING AND CONTROL SCHEME ..................................................................................... 16 

    5.1 Data Acquisition ..................................................................................................................................... 16 

    5.2 Alarm Monitoring ........................................................ ................................................................. .......... 17  

    5.3 Control and Data Flows .......................................................... ................................................................ 18 

    5.4 Control Modes ............................................................. ................................................................. .......... 18 

    5.5 Running Hours and Plant Metrics .......................................................................................................... 19 

    5.6 Signal Conditioning ................................................................................................................................ 19 

    6.0 TUNNEL LIGHTING SYSTEM CONTROL SCHEME ........................................................................................ 20 

    6.1 Control Scheme Overview ...................................................................................................................... 20 

    6.2 General Lighting Control Scheme ................................................................ ........................................... 20 6.3 Automatic Control Mode ........................................................ ................................................................ 21 

  • 8/20/2019 KEO Design Report

    4/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0201-MC-KEO-RP-00209 Page iv

    Rev. D02

    6.4 Manual Operator Override from TMC Control Mode ........................................................ ..................... 21 6.5 Manual Operator Override from SCADA GUI Control Mode ................................................................ .. 22 

    6.6 Manual Operator Override from SCP Control Mode .............................................................................. 22 

    6.7 Manual Operator Override from LCP Control Mode .............................................................................. 23  

    6.8 Lamp Status Monitoring ........................................................................................................................ 23 

    6.9 Emergency Standby Generator Load Shedding ...................................................................................... 23 

    7.0 FIRE SAFETY SYSTEMS CONTROL SCHEME ................................................................................................ 23 

    7.1 Emergency/Electrical Distribution Panels Control Scheme .................................................................... 23 

    7.2 Smoke Detection System ........................................................ ................................................................ 24 

    7.3 Smoke Control Panels ............................................................. ................................................................ 24 

    8.0 COMMUNICATIONS SYSTEMS CONTROL SCHEME .................................................................................... 25 

    8.1 Control Scheme Overview ...................................................................................................................... 25 

    8.2 Emergency Roadside Telephones Control Scheme ................................................................................. 25 

    8.3 Public Automatic Branch Exchange Control Scheme ......................................................... ..................... 25 

    8.4 Airwave and Emergency Services Radio Repeater Control Scheme ....................................................... 25  

    8.5 Public Address Control Scheme ............................................................................................................ .. 25 

    9.0 ELECTRICAL SUPPLY SYSTEMS CONTROL SCHEME .................................................................................... 26 

    9.1 Control Scheme Overview ...................................................................................................................... 26 

    9.2 MV System Control Scheme ................................................................................................................... 26 

    9.3 Transformer Control Scheme ................................................................................................................. 26 9.4 LV System Control Scheme ................................................................ ..................................................... 28 

    9.5 Emergency Standby Generator Control Scheme .................................................................................... 31 

    9.6 UPS Systems Control Scheme ................................................................................................................. 32 

    10.0 MISCELLANEOUS SYSTEMS CONTROL SCHEME ....................................................................................... 34 

    10.1 Control Scheme Overview .................................................................................................................... 34 

    11.0 INTERFACES ............................................................................................................................................ 34 

    11.1 TMC Interface ............................................................ ................................................................. .......... 34 

    11.2 Physical Locations of PMCS Plant Interfaces ........................................................................................ 34 

    11.3 Plant Interfaces .................................................................................................................................... 34 11.4 Ethernet TCP/IP Infrastructure ........................................................ ..................................................... 35 

  • 8/20/2019 KEO Design Report

    5/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 1 of 36

    Rev. D02

    1.0 INTRODUCTION

    1.1 Document Purpose and Scope

    This document describes the outline design for the Tunnel Plant Monitoring and Control System

    (PMCS) that forms part of the Tunnel construction works.

    This document provides the following information:

      Overview of the PMCS

      PMCS system architecture and topology

      Description of plant interfaces

      Description of external interfaces

      Details of schemes for plant monitoring and control

    1.2 Related Documents

    Document Number Title

    EXW-P007-0201-MC-KEO-RP-00209 Tunnel SCADA PMCS Control Concept (This Document)

    EXW-P007-0201-MC-KEO-RP-00210 Tunnel TMC/TSS – SCADA/PMCS Control Interface

    EXW-P007-0201-MC-KEO-RP-00211 Tunnel PMCS Smoke Control Panel Control Interface

    EXW-P007-0201-MC-KEO-RP-00212 Tunnel PMCS Plant I/O Control Interface List

    EXW-P007-0201-MC-KEO-RP-00213 Tunnel CCTV Camera Specification

    EXW-P007-0201-MC-KEO-RP-00214 Mechanical, Electrical and Systems – General Specifications

    EXW-P007-0201-MC-KEO-RP-00215 Tunnel Pumped Drainage Installations

    EXW-P007-0201-MC-KEO-RP-00216 Tunnel Fire Safety Systems Specification

    EXW-P007-0201-MC-KEO-RP-00217 Tunnel Panels

    EXW-P007-0201-MC-KEO-RP-00218 Tunnel Cross Passage Doors

    EXW-P007-0201-MC-KEO-RP-00219 Tunnel Way Finding Signs

    EXW-P007-0201-MC-KEO-RP-00220 Tunnel Operational Control Concept

    EXW-P007-0201-MC-KEO-RP-00221 Tunnel Ventilation Control Concept

    EXW-P007-0201-MC-KEO-RP-00222 Junction R6 Road Tunnel – Detailed Design M&E Systems

    EXW-P007-0201-MC-KEO-RP-00223 Contract 2 Underpasses – Detailed Design M&E Systems

    EXW-P007-0201-MC-KEO-RP-00224 Not used

    EXW-P007-0201-MC-KEO-RP-00225 Underpass Pumped Drainage installations

    1.3 Related Drawings

    Drawing No. Title

    EXW-P007-0201-JF-KEO-DG-

    00100-001

    RAYYAN ROAD KEY PLAN M&E LAYOUT (SHEET 1 OF 1)

    EXW-P007-0201-MC-KEO-

    DG-00106-001

    RAYYAN ROAD FIRE SAFETY TYPICAL PLAN & SECTIONS (SHEET 1 OF 2)

    EXW-P007-0201-MC-KEO-

    DG-00106-002

    RAYYAN ROAD FIRE SAFETY TYPICAL PLAN & SECTIONS (SHEET 2 OF 2)

    EXW-P007-0201-MC-KEO-

    DG-00107-001

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES

    LOCATION (SHEET 1 OF 8)

  • 8/20/2019 KEO Design Report

    6/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 2 of 36

    Rev. D02

    Drawing No. Title

    EXW-P007-0201-MC-KEO-

    DG-00107-002

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES

    LOCATION (SHEET 2 OF 8)

    EXW-P007-0201-MC-KEO-

    DG-00107-003

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES

    LOCATION (SHEET 3 OF 8)

    EXW-P007-0201-MC-KEO-

    DG-00107-004

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES

    LOCATION (SHEET 4 OF 8)

    EXW-P007-0201-MC-KEO-

    DG-00107-005

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES

    LOCATION (SHEET 5 OF 8)

    EXW-P007-0201-MC-KEO-

    DG-00107-006

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES

    LOCATION (SHEET 6 OF 8)

    EXW-P007-0201-MC-KEO-

    DG-00107-007

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES

    SECTION (SHEET 7 OF 8)

    EXW-P007-0201-MC-KEO-

    DG-00107-008

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES

    SECTION (SHEET 8 OF 8)EXW-P007-0201-MC-KEO-

    DG-00201-001

    RAYYAN ROAD JUNCTION 6 TUNNEL TU1 ILLUMINATED EMERGENCY WAY

    FINDING SIGN LOCATIONS (SHEET 1 OF 4)

    EXW-P007-0201-MC-KEO-

    DG-00201-002

    RAYYAN ROAD JUNCTION 6 TUNNEL TU1 ILLUMINATED EMERGENCY WAY

    FINDING SIGN LOCATIONS (SHEET 2 OF 4)

    EXW-P007-0201-MC-KEO-

    DG-00201-003

    RAYYAN ROAD JUNCTION 6 TUNNEL TU1 ILLUMINATED EMERGENCY WAY

    FINDING SIGN LOCATIONS (SHEET 3 OF 4)

    EXW-P007-0201-MC-KEO-

    DG-00201-004

    RAYYAN ROAD JUNCTION 6 TUNNEL TU1 ILLUMINATED EMERGENCY WAY

    FINDING SIGN LOCATIONS (SHEET 4 OF 4)

    EXW-P007-0201-MC-KEO-

    DG-00301-001

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP, CCP & TULDB LOCATIONS

    (SHEET 1 OF 7)

    EXW-P007-0201-MC-KEO-

    DG-00301-002

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP, CCP & TULDB LOCATIONS

    (SHEET 2 OF 7)EXW-P007-0201-MC-KEO-

    DG-00301-003

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP, CCP & TULDB LOCATIONS

    (SHEET 3 OF 7)

    EXW-P007-0201-MC-KEO-

    DG-00301-004

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP, CCP & TULDB LOCATIONS

    (SHEET 4 OF 7)

    EXW-P007-0201-MC-KEO-

    DG-00301-005

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP, CCP & TULDB LOCATIONS

    (SHEET 5 OF 7)

    EXW-P007-0201-MC-KEO-

    DG-00301-006

    RAYYAN ROAD JUNCTION R6 TUNNEL- TYPICAL SINGLE EMERGENCY PANEL

    ARRANGEMENT (WITHOUT HYDRANT) (SHEET 6 OF 7)

    EXW-P007-0201-MC-KEO-

    DG-00301-007

    RAYYAN ROAD JUNCTION R6 TUNNEL- TYPICAL INDIVIDUAL LIGHTING

    DISTRIBUTION PANEL (SHEET 7 OF 7)

    EXW-P007-0201-MC-KEO-

    DG-00302-001

    RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP &CCP GROUP

    ARRANGEMENT (SHEET 1 OF 1)

    EXW-P007-0201-MC-KEO-

    DG-00401-001

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 PA/VA SYSTEM LOCATIONS (SHEET 1

    OF 6)

    EXW-P007-0201-MC-KEO-

    DG-00401-002

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 PA/VA SYSTEM LOCATIONS (SHEET 2

    OF 6)

    EXW-P007-0201-MC-KEO-

    DG-00401-003

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 PA/VA SYSTEM LOCATIONS (SHEET 3

    OF 6)

    EXW-P007-0201-MC-KEO-

    DG-00401-004

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL PA/VA SYSTEM LOCATIONS (SHEET

    4 OF 6)

    EXW-P007-0201-MC-KEO-

    DG-00401-005

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL PA/VA SYSTEM LOCATIONS (SHEET

    5 OF 6)

    EXW-P007-0201-MC-KEO-DG-00401-006 AL RAYYAN ROAD JUNCTION R6 ROAD TUNNEL PA/VA CONFIGURATION(SHEET 6 OF 6)

  • 8/20/2019 KEO Design Report

    7/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 3 of 36

    Rev. D02

    Drawing No. Title

    EXW-P007-0201-MC-KEO-

    DG-00402-001

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 PA/VA SCHEMATIC SHEET (SHEET 1

    OF 1)

    EXW-P007-0201-MC-KEO-

    DG-00501-001

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 GENERAL FIRE DETECTION &

    WARNING (SHEET 1 OF 4)`

    EXW-P007-0201-MC-KEO-

    DG-00501-002

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 GENERAL FIRE DETECTION &

    WARNING (SHEET 2 OF 4)`

    EXW-P007-0201-MC-KEO-

    DG-00501-003

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 GENERAL FIRE DETECTION &

    WARNING (SHEET 3 OF 4)`

    EXW-P007-0201-MC-KEO-

    DG-00501-004

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 GENERAL FIRE DETECTION &

    WARNING (SHEET 4 OF 4)`

    EXW-P007-0201-MC-KEO-

    DG-00601-001

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VENTILATION LAYOUT (SHEET 1 OF

    4)

    EXW-P007-0201-MC-KEO-

    DG-00601-002

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VENTILATION LAYOUT (SHEET 2 OF

    4)

    EXW-P007-0201-MC-KEO-

    DG-00601-003

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VENTILATION LAYOUT (SHEET 3 OF

    4)

    EXW-P007-0201-MC-KEO-

    DG-00601-004

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VENTILATION LAYOUT (SHEET 4 OF

    4)

    EXW-P007-0201-MC-KEO-

    DG-00701-001

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 LANE CONTROL SIGNS LOCATION

    LAYOUT (SHEET 1 OF 4)

    EXW-P007-0201-MC-KEO-

    DG-00701-002

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 LANE CONTROL SIGNS LOCATION

    LAYOUT (SHEET 2 OF 4)

    EXW-P007-0201-MC-KEO-

    DG-00701-003

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 LANE CONTROL SIGNS LOCATION

    LAYOUT (SHEET 3 OF 4)

    EXW-P007-0201-MC-KEO-

    DG-00701-004

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 LANE CONTROL SIGNS LOCATION

    LAYOUT (SHEET 4 OF 4)EXW-P007-0201-MC-KEO-

    DG-00702-001

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL PMCS/SCADA COMMUNICATION

    NETWORK SHEET 1 OF 1

    EXW-P007-0201-MC-KEO-

    DG-00800-001

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 CCTV CAMERA SCHEMATIC (SHEET 1

    OF 1)

    EXW-P007-0201-MC-KEO-

    DG-00801-001

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 CCTV CAMERA LAYOUT (SHEET 1 OF

    5)

    EXW-P007-0201-MC-KEO-

    DG-00801-002

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL CCTV CAMERA SCHEMATIC (SHEET

    2 OF 5)

    EXW-P007-0201-MC-KEO-

    DG-00801-003

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL CCTV CAMERA SCHEMATIC (SHEET

    3 OF 5)

    EXW-P007-0201-MC-KEO-

    DG-00801-004

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL CCTV CAMERA SCHEMATIC (SHEET

    4 OF 5)

    EXW-P007-0201-MC-KEO-

    DG-00801-005

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL CCTV CAMERA SCHEMATIC (SHEET

    5 OF 5)

    EXW-P007-0201-MC-KEO-

    DG-00802-001

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VAID CAMERA LAYOUT (SHEET 1 OF

    5)

    EXW-P007-0201-MC-KEO-

    DG-00802-002

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL VAID SYSTEM SCHEMATIC (SHEET

    2 OF 5)

    EXW-P007-0201-MC-KEO-

    DG-00802-003

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL VAID CAMERA CONFIGURATION

    (SHEET 3 OF 5)

    EXW-P007-0201-MC-KEO-

    DG-00802-004

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VAID CAMERA LAYOUT (SHEET 4 OF

    5)

    EXW-P007-0201-MC-KEO-

    DG-00802-005

    RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VAID CAMERA CONFIGURATION

    (SHEET 5 OF 5)

    EXW-P007-0201-MC-KEO- RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VAID CAMERA SYSTEM SCHEMATIC

  • 8/20/2019 KEO Design Report

    8/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 4 of 36

    Rev. D02

    Drawing No. Title

    DG-00803-001 (SHEET 1 OF 1)

    EXW-P007-0201-MC-KEO-

    DG-00901-001

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL ERT NETWORK (SHEET 1 OF 1)

    EXW-P007-0201-MC-KEO-

    DG-00902-001

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL LHD DTS SCHEMATIC (SHEET 1 OF

    2)

    EXW-P007-0201-MC-KEO-

    DG-00902-002

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL LEAKY FEEDER (SHEET 2 OF 2)

    EXW-P007-0201-MC-KEO-

    DG-00903-001

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL FIRE SAFETY SYSTEMS (SHEET 1 OF

    1)

    EXW-P007-0201-MC-KEO-

    DG-00904-001

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL LANE CONTROL SIGN SYSTEM

    SCHEMATIC (SHEET 1 OF 2)

    EXW-P007-0201-MC-KEO-

    DG-00904-002

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL DMS/LCS CONFIGURATION (SHEET

    2 OF 2)

    EXW-P007-0201-MC-KEO-DG-00905-001

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL IMPOUNDING SUMP VENTILATIONSCHEMATIC (SHEET 1 OF 1)

    EXW-P007-0201-MC-KEO-

    DG-00906-001

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL SCP GA PANEL LAYOUT (SHEET 1

    OF 3)

    EXW-P007-0201-MC-KEO-

    DG-00906-002

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL SCP GA PANEL LAYOUT (SHEET 2

    OF 3)

    EXW-P007-0201-MC-KEO-

    DG-00906-003

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL SCP GA PANEL LAYOUT (SHEET 3

    OF 3)

    EXW-P007-0201-MC-KEO-

    DG-00907-001

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL – TYPICAL SMOKE CONTROL

    PANEL LAYOUT (SHEET 1 OF 1)

    EXW-P007-0201-MC-KEO-

    DG-00908-001

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL - CROSS PASSAGE DOORS (SHEET 1

    OF 3)

    EXW-P007-0201-MC-KEO-DG-00908-002

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL - TYPICAL CROSS CONNECTIONDOORS (SHEET 2 OF 3)

    EXW-P007-0201-MC-KEO-

    DG-00908-003

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL - DETAIL OF FIRE BRIGADE

    CONNECTORS (SHEET 3 OF 3)

    EXW-P007-0201-MC-KEO-

    DG-00909-001

    RAYYAN ROAD JUNCTION R6 ROAD TUNNEL - DETAIL OF FIRE BRIGADE

    CONNECTORS (SHEET 3 OF 3)

    EXW-P007-0201-CD-KEO-

    DG-00212-005

    Al RAYYAN ROAD JUNCTION R6 ROAD TUNNEL ATTENUATION TANK

    SECTIONAL DETAIL (SHEET 5 OF 6)

    EXW-P007-0201-CD-KEO-

    DG-00212-006

    Al RAYYAN ROAD JUNCTION R6 ROAD TUNNEL ATTENUATION TANK/PLANT

    ROOM INSTALLATION SCHEMATIC (SHEET 6 OF 6)

    EXW-P007-0201-CD-KEO-

    DG-00208-001

    Al RAYYAN ROAD UNDERPASS DRAINAGE CHANNEL DETAILS

    1.4 Codes and standards applicable

    Hierarchy of codes, standards and specifications

    1.  National legislation, codes and statutes

    2.  Regional legislation, codes and statutes

    3.  This document

    4.  UK Highways Agency BD78/99 and NFPA 502

    5.  UK Highways Agency Series 7000 specifications

    6.  PIARC Road Tunnel Manual

  • 8/20/2019 KEO Design Report

    9/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 5 of 36

    Rev. D02

    7.  Ashghal ITS Specifications

    8.  Federal Highway Administration (System Engineering Handbook for ITS Systems)

    9.  QCS Specifications 201010. WIS Standards

    1.5 List of Abbreviations

    The abbreviations used in this Specification and the associated Plant Specifications have the

    following meanings:

    Abbreviation Meaning

    ac Alternating Current

    AC Air Changes

    AFBMA Anti-Friction Bearing Manufacturer’s Association 

    AI Analogue InputAIP Approval in Principle

    AISI American Iron and Steel Institute

    AO Analogue Output

    ASTM American Society for Testing and Materials

    ATEX ATmosphères EXplosives or Explosive Atmospheres

    BS British Standard

    BG Break Glass

    CCD Charged Coupled Device

    CCTV Closed Circuit Television

    CD-R Compact Disc Recordable

    CD Compact Disc

    CDM Construction Design and Management (Regulations)

    CDROM Compact Disc Read Only Memory

    CER Communications Equipment Room

    CM Configuration Management

    C of C Certificate of Conformity

    CO Carbon Monoxide

    COSHH Control of Substances Hazardous to Health

    CPD Cross Passage Door

    DB Distribution Board

    DC Direct Current

    DI Digital Input

    DMRB Design Manual for Roads and Bridges

    DP Distribution Panel

    DO Digital Output

    DOL Direct-on-line

    DSEAR Dangerous Substances and Explosive Atmospheres Regulations UK (ATEX 137

    implementation)

    DTS Distributed Temperature sensing

    DW Duct Work (Specification)

    EC European Commission

    EDP Emergency Distribution Point

    ELV Extra Low Voltage

    EMC Electromagnetic CompatibilityEMF Electromagnetic Fields

  • 8/20/2019 KEO Design Report

    10/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 6 of 36

    Rev. D02

    Abbreviation Meaning

    EMI Electromagnetic Interference

    EN European Standard

    EP Emergency Point

    EPDM Ethylene Propylene Diene Monomer

    EPROM Erasable Programmable Read Only Memory

    E2PROM Electrically Erasable Programmable Read Only Memory

    EEPROM Electrically Erasable Programmable Read Only Memory

    ERT Emergency Roadside Telephone

    EX Explosion Proof rated

    FAP Fire Alarm Panel

    FAT Factory Acceptance Tests

    FDS Functional Design Specification

    FL Factory Link

    FO Fibre Optic

    FP Fire Protection

    FRLS Fire Retardant Low Smoke

    FS Fire Survivable

    FSK Frequency Shift Key

    FSC Forest Stewardship Council

    GSM Global System for Mobiles

    GUI Graphical User Interface

    HA Highways Agency UK

    HDLC High level Data Link Control

    HEMP High Energy Magnetic Impulse

    HH High-HighHMI Human Machine Interface

    HVAC Heating/Ventilation/Air-Conditioning

    HVCA Heating and Ventilating Contractor’s Association UK

    HV High Voltage

    Hz Hertz

    IEC International Electrotechnical Commission

    I/O Input/Output

    IP Ingress Protection

    IP Internet Protocol

    IRT Incident Response Team i.e. Emergency Services

    ISO International Standards OrganisationITS Intelligent Transportation Systems

    LCP Local Control Panel

    LCS Lane Control Signs

    LCS Lighting Control System

    LEL Lower Explosive Level

    LFS Low Fume and Smoke

    LHD Linear Heat Detection

    LL Low-Low

    LPCB Loss Prevention Certification Board

    LSOH Low Smoke Zero Halogen

    LV Low Voltage, Voltage below 1000 Vac and above 50 Vac.

    M&E Mechanical and Electrical

    MCB Miniature Circuit Breaker

  • 8/20/2019 KEO Design Report

    11/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 7 of 36

    Rev. D02

    Abbreviation Meaning

    MCC Motor Control Centre

    MCCB Moulded Case Circuit Breaker

    MCHW Manual of Contract Documents for Highway Work in the UK

    MES Mechanical - Electrical - Systems

    MET Metrological/Environmental/Traffic

    MMFO Multi-Mode Fibre Optic

    MTBF Mean Time Between Failure

    MTTR Mean Time to Repair

    MUX Multiplexer

    MV Medium Voltage, voltage above 1000 Vac but below HV

    NAMAS National Measurement Accreditation Services

    N/B Northbound

    NEMA National Electrical Manufacturer’s Association 

    NER Neutral Earthing ResistorNFPA National Fire Protection Association

    NO Niitrogen Oxide

    NPSH Net Positive Suction Head

    NR Noise Reduction

    NRV Non-Return Valve

    NTCIP National Transportation Communications for ITS Protocol

    ODVA Open DeviceNet Vendors Association

    O&M Operations and Maintenance

    OPC Open Process Control

    PA Public Address

    PABX Private Automatic Branch ExchangePAVA Public Address Voice Alarm

    PC Personal Computer

    PEFC Programme for the Endorsement of Forest Certification

    PIARC The World Road Association

    PLC Programmable Logic Controller

    PMCS Plant Monitoring and Control System

    PN Pressure Normal

    PQP Project Quality Plan

    PROM Programmable Read Only Memory

    PSU Power Supply Unit

    PTZ Pan, Tilt and ZoomPVC Polyvinyl Chloride

    QA Quality Assurance

    QC Quality Control

    QCS Qatar Construction Standards

    RAM Random Access Memory

    RH Relative Humidity (as %)

    RIO Remote Input / Output

    RS232 Recognised Standard 232

    RS422 Recognised Standard 422

    RS485 Recognised Standard 485

    RTD Resistance Temperature Detector

    RTU Remote Terminal Unit

    SAT Site Acceptance Tests

  • 8/20/2019 KEO Design Report

    12/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 8 of 36

    Rev. D02

    Abbreviation Meaning

    S/B Southbound

    SCADA Supervisory Control and Data Acquisition

    SCP Smoke Control Panel

    SDS Software Design Specifications

    SFA Service Factor Amperes

    SLV Safety Low Voltage

    SMFO Single Mode Fibre Optic

    STP Sheilded Twisted Pair

    TCP/IP Transmission Control Protocol/Internet Protocol

    TDSCG Tunnel Design and Safety Consultation Group

    TERP Tunnel Emergency Response Plan

    TFT Thin Film Transistor (Display Technology)

    TM Tunnel Maintainer

    TMC Traffic Management Centre/Tunnel Management Centre

    TOA Tunnel Operating Authority

    TR Technical Requirement

    TSB Tunnel Service Building

    TSS Tunnel Sub-System

    UL Underwriters Laboratories

    UPS Uninterruptible Power supply

    USB Universal Serial Bus

    USSG United States Standard Gage

    UK United Kingdom

    UKAS United Kingdom Accreditation Service

    UTP Unsheilded Twisted PairV Volt(age)

    Vac Volts ac

    VAID Video Automatic Incident Detection

    VCR Video Cassette Recorder

    Vdc Volts dc

    VDU Visual Display Unit

    VESDA Very Early Smoke Detection Aspirator

    VID Video Incident Detection

    VIS Visibility

    VMS Variable Message Sign

    VSD Video Smoke DetectionVSD Variable Speed Detection

    WIS Water Industry Specifications UK

    XPLE Cross-linked Polyethylene

  • 8/20/2019 KEO Design Report

    13/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 9 of 36

    Rev. D02

    2.0 ASHGHAL’s RELEVANT OBJEVTIVES 

      To meet the requirements of the UK HA DMRB BD78/99, the UK HA MCHW 5.7.2 and

    Federal NFPA502 (IAN 020 Rev. A1) in respect to classification of tunnels and life safetyprovisions.

      Achieves environmental sustainability and whole life costs within the scheme budget

      To provide a safe tunnel environment for road users, operators, maintenance staff, police

    and the emergency services both during construction and in permanent conditions.

      Reduces operational and maintenance risks

      Meet The Road Tunnel Safety Regulations 2007 UK.

      Safety of the work force and the road users

      Deliver scheme as soon as possible

    3.0 Electromagnetic compatibility (EMC)

    3.1 Normative references

    The following referenced documents are indispensable for the application of this document.

    For dated references, only the edition cited applies. For undated references, the latest edition of the

    referenced document (including any amendments) applies.

    The applicable environment here is industrial.

    Reference, Technical Committee, Title SubjectNormative references

    IEC 60050-161, International Electrotechnical Vocabulary (IEV) – Chapter 161: Electromagnetic

    compatibility

    IEC 61000-4-2, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement

    techniques – Section 2: Electrostatic discharge immunity test

    IEC 61000-4-3, Electromagnetic compatibility (EMC) – Part 4-3: Testing and measurement

    techniques – Radiated, radio-frequency, electromagnetic field immunity test

    IEC 61000-4-4, Electromagnetic compatibility (EMC) – Part 4-4: Testing and measurement

    techniques – Electrical fast transient/burst immunity test

    IEC 61000-4-5, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement

    techniques – Section 5: Surge immunity test

    IEC 61000-4-6, Electromagnetic compatibility (EMC) – Part 4-6: Testing and measurementtechniques – Section 6: Immunity to conducted disturbances, induced by radio-frequency fields

    IEC 61000-4-8, Electromagnetic compatibility (EMC) – Part 4: Testing and measurement

    techniques – Section 8: Power frequency magnetic field immunity test

    IEC 61000-4-11, Electromagnetic compatibility (EMC) – Part 4-11: Testing and measurement

    techniques – Voltage dips, short interruptions and voltage variations immunity tests

    CISPR 22, Information technology equipment – Radio disturbance characteristics – Limits and

    methods of measurement

    Residential, commercial, light industrial environment

    IEC 61000-6-3: Electromagnetic compatibility (EMC) - Part 6-3: Generic standards - Emission

    standard for residential, commercial and light-industrial environments

    Emission

    IEC 61000-6-1: Electromagnetic compatibility (EMC) - Part 6-1: Generic standards - Immunity

    for residential, commercial and light-industrial environments

    Immunity

    Industrial environment

  • 8/20/2019 KEO Design Report

    14/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 10 of 36

    Rev. D02

    IEC 61000-6-4: Electromagnetic compatibility (EMC) - Part 6-4: Generic standards - Emission

    standard for industrial environments

    Emission

    IEC 61000-6-2: Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity

    for industrial environments

    Immunity

    Power station and substation environment

    IEC 61000-6-5: Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity

    for power station and substation environments

    Immunity

    Indoor equipment

    IEC 61000-6-6: Electromagnetic compatibility (EMC) - Part 6-6: Generic standards - HEMP

    immunity for indoor equipment

    HEMP

    immunity

    4.0 PMCS Overview

    4.1 IntroductionThe PMCS will be formed as an autonomous monitoring and control system allowing all monitoring

    and control operations to be performed locally to the tunnel.

    The PMCS will be configured as a hierarchical distributed system, consisting of the following

    monitoring and control layers:

      Supervisory Control and Data Acquisition (SCADA) servers, incorporating the Graphical User

    Interface (GUI)

      Central supervisory control Programmable Logic Controllers (PLC’s) 

      Distributed outstation PLC’s associated with plant requiring local control functions, such asthose at local control panels

    The provision of layered hierarchical monitoring and control will provide the following benefits:

      Partitioning of monitoring and control capability to appropriate operating personnel

    throughout the infrastructure

      Reversionary monitoring and control capability in the event of incident

      Ability to commission and maintain assets independently of the complete infrastructure

    The SCADA Servers will be configured as a dual hot-standby pair.

    The supervisory control PLC’s will be configured as a dual hot-standby pair.

    Other PLC units will be configured in a dual hot-standby pair, where required, in order to provide a

    highly reliable and available system, otherwise a singular unit will be employed connected to either

    the A or B ring network.

    SCADA Server, supervisory control PLC, PLC, and RIO units will be interconnected by a dual

    redundant control network, in an A and B configuration.

    The SCADA/PMCS will contain a separate logic programming emulating an interface window , named

    the Tunnel Subsystem, which will interface with the TMC tunnel operator desk, for the remote

    interface and control in respect to the traffic control aspect of the tunnel operation.

  • 8/20/2019 KEO Design Report

    15/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 11 of 36

    Rev. D02

    4.2 System Architecture

    The overall PMCS system architecture will be as shown in Figure 1.

    Figure 1: PMCS Overall System Architecture

    4.3 SCADA Servers

    The SCADA Servers will perform overall management of the PMCS, including the following functions:

      Provision and management of the Operator GUI

      Datapoint storage and retrieval

    The SCADA Servers will be configured as dual industrial-grade PCs operating in hot-standby mode.

    NB Fan Starters,

    Pollution Sensors

    and VAID

    TMC Authorized UserTOA Authorized user

    Manual Overrides and

    Status Monitoring

    Tunnel Subsystem

    (TSS)

    Dual PLC

    Processors

    Control

    and Status

    Dual

    Redundant

    Dual PLC

    Processors

    Dual

    Redundant

    NB Smoke

    Control Panels

    Dual

    Redundant

    Dual

    Redundant

    SB Smoke

    Control Panels

    Control and

    Status

    Smoke Panel

    Control Requests

    and Plant Status

    SB Fan Starters,

    Pollution Sensors

    and VAID

    PMCS

    Dual Redundant

    SCADA Servers

  • 8/20/2019 KEO Design Report

    16/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 12 of 36

    Rev. D02

    4.4 Supervisory Control PLC’s 

    The supervisory control PLC’s performing overall management of the outstation PLC’s and RIO  units

    of the PMCS, including functions such as the following:

      Overall system control

      System moding

      Interfacing with the GUI

      Outstation PLC and RIO unit monitoring and control

      Data acquisition management

      System health monitoring

      System alarm monitoring

      Communications with Traffic Management Centre (TMC

    The supervisory control PLC’s will be configured as dual industrial-grade PLC’s operating in hot-

    standby mode.

    4.5 Outstation PLC’s 

    Outstation PLC’s will be used where control functionality is required to be distributed within the

    tunnel such as, for example, for the management of Smoke Control Panels (SCP’s). 

    Outstation PLC’s will be configured as dual industrial-grade PLC’s operating in hot-standby mode.

    4.6 Dual configuration

    Master-standby arbitration and selection of the supervisory control PLC’s will be achieved through

    the use of external *with respect to the PLC’s+ hardware watchdog timing circuitry. Such a hardware-based approach will provide much greater determinism of mutual exclusion of mastery.

    Upon system start-up one of the supervisory control PLC pair, arbitrarily selected, shall automatically

    be configured as the master, assuming control of the PMCS.

    The master-standby state of the supervisory control PLC’s will be used to derive and determine the

    master-standby configuration of other dual configuration units throughout the PMCS, thus removing

    the need for additional master-standby arbitration hardware in each instance of dual configurations

    throughout the system.

    External hardware-based watchdogging will be used to monitor the supervisory control PLC’s for

    failure, in which case mastery will be allocated the standby unit.

    Software-based heartbeat watchdogging will be employed by the supervisory control PLC’s to

    monitor the health of other dual configuration units throughout the PMCS, and allocation of mastery

    performed accordingly.

    The dual configuration scheme will transparently implement the following dual configuration

    functions:

      Replication of the processing context to the standby, including programs and data

      Detection of faults and switchover

  • 8/20/2019 KEO Design Report

    17/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 13 of 36

    Rev. D02

      Disqualification of failed units

      Re-qualification (i.e. re-synchronisation) of formerly failed units

      Manual de-selection of the master  Heartbeat monitoring

    4.7 SCADA Graphical User Interface (Operator Interface)

    A SCADA operator interface (GUI) will be provided for use by Operators within each of the following

    locations:

      the Tunnel Services Building, (Master)

      TOA Operator Interface at the TMC

      Traffic Control Interface at the TMC

    The Master SCADA GUI will be delivered by dual redundant servers and all SCADA GUI’s will provide

    the following features and functions:

      Operator access via password-protected login

      System mimic display, including the following:

    o  Display of tunnel systems status in graphical format annotated with key system

    parameter values

    o  Display of alarm conditions

    o  Display of tunnel system operational moding

      Alarm management, including the following:

    o  Display of alarm conditions

    o  Alarm acknowledgements

    o  Alarm log viewing

      Operator control actions, including the following:

    o  Setting of operational parameters for applicable tunnel systems

    o  Mode control of applicable tunnel systems

    o  Disqualification of sensors from participation in control mode demand calculation

    algorithms

      Data review and trending

      PMCS system management, including the following:o  Logging of significant TPCMS events such as the following:

      Operator login/logout

      Significant Operator control actions

    o  Manual selection of dual configuration control processor changeover

    o  System start-up and shutdown [interlocked]

    o  Access to server operating system environment

    The SCADA GUI will be presented on an Operator terminal featuring TFT-LCD monitor, keyboard, and

    mouse/pointing device.

  • 8/20/2019 KEO Design Report

    18/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 14 of 36

    Rev. D02

    4.8 TMC/TSS

    The Tunnel Subsystem (TSS) is an segregation of a partition of the control and monitoring logical

    software system deployed within the SCADA/PMCS application servers/PLCs at the TSB thatfacilitates the control and monitoring of carriageway and tunnel infrastructure through the TMC

    Traffic system, providing functions such as the following:

      The setting of signs

      Control of tunnel lighting

      Control of tunnel ventilation (0%- 50% and 100%, however we expect that only 50 and 100%

    will be implemented)

      PA message control, manual and automatic)

    The TMC Traffic system acts as an integrated incident management tool that reacts to all relevant

    situations by selecting the appropriate Tunnel Emergency Response Plan (TERP) from its database

    and will display this to the Traffic Control Operator dealing with the tunnel incident for acceptance

    and execution.

    The TMC Tunnel System allows Traffic Control Operators to execute pre-defined response plans, as

    well as allowing Operators to effect ad-hoc control actions in response to particular tunnel incidents

    and situations.

    4.9 Engineering Terminal

    The PMCS will provide connectivity for an mobile engineering terminal for use by maintenance

    personnel. The mobile engineering terminal may be connected to any suitable port on the PMCS

    control network.

    The engineering terminal will provide features and functions related to the commissioning and

    maintenance of the system, including the following:

      Monitoring and control of plant

      Modification of the system control programs

      Modification of system configuration parameters

      Manual selection of dual configuration control processor changeover

      Manual disqualification and re-qualification of dual configuration control processors  Fault diagnostic facilities

      Logging and trending facilities

    The engineering terminal will not normally be connected to the system, but will be capable of being

    removed / inserted into the operational system.

    The engineering terminal will consist of an industrial rough service Ultrabook with network interface

    card hosting the engineering terminal software application.

  • 8/20/2019 KEO Design Report

    19/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 15 of 36

    Rev. D02

    4.10 Control & Monitoring Software

    All PMCS control software will be developed using industry-standard software development

    processes and methodologies.

    PLC Control software will be developed in accordance with IEC 61131-3, Programmable controllers -

    Part 3: Programming languages, 2003, in one of the following forms:

      Ladder logic

      Function block

      Structured text

      Instruction list

    All Control and monitoring software will be developed in accordance with BS EN 61508 Safety

    Integrity Level (SIL) 2 and a validation process shall be carried out confirming the criteria reached,

    i.e. SIL2.

    4.11 Control Network

    The PMCS processing and I/O units will intercommunicate control and data via a dedicated dual

    redundant Ethernet-based control network.

    The PMCS control network will be formed of multi-mode fibre optic and copper segments, as

    required.

    The backbone of the PMCS control network linking central control units to outstation units will be

    two fibre optic circuits, each arranged in a ring topology to form two independent ‘A’ and ‘B’ closed-

    loop self-healing networks capable of continued operation in the event of a fibre-optic cable

    disconnection or network switch failure.

    The dual supervisory control PLC’s will each be provided with dual connections to both the ‘A’ and

    ‘B’ control networks, thereby providing resilience in the event of failure of one of the supervisory

    control PLC’s. 

    Each PMCS outstation processing and I/O unit will be provided with a single connection to one of the

    ‘A’ or ‘B’ networks. At outstation locations where dual redundant processing and I/O units are

    deployed, then each of these will be provide with a single connection to the ‘A’ and ‘B’ control

    networks; one unit to the ‘A’ control network and one unit to the ‘B’ control network.

    The dual SCADA Servers will each be provided with a single connection to the ‘A’ or ‘B’ control

    networks; one to the ‘A’ control network and one to the ‘B’ control network. 

    The PMCS will use Ethernet-based Open Process Control (OPC) protocols for internal and external

    communications.

    4.12 Instrumentation Interface

    The PMCS will provide connectivity to a range of instrumentation industry standards including the

    following:

  • 8/20/2019 KEO Design Report

    20/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 16 of 36

    Rev. D02

      4-20mA current loop

      Volt-free contacts

      Serial protocols to include EIA-RS232, EIA-RS485 and USB connections  Generic Fieldbus and open/proprietary implementations thereof

      Industrial Ethernet OVDA compliant implementation

    4.13 Cable Types

    Connections to plant will be implemented using the following cable types, as appropriate, and

    dependent upon the specific requirements of the plant selected during detailed design stages:

      Cat5e unshielded twisted pair (UTP) in accordance with TIA/EIA-568-B

      Cat5e shielded twisted pair (STP) in accordance with TIA/EIA-568-B

      Single-mode fibre-optic cable to (See ITS Specifications)  BS5308 Instrumentation Cable Part 1 Type 1

    4.14 Equipment Accommodation

    Remote Network switches and PLCs will be installed at the following locations:

      Within the TSB within dedicated racks and remote positions (several locations)

      Within 4 No. SCP’s outside each portal (Dual configuration) 

      Within 8 No. EDP’s within each bore (16 In total, single configuration interleaved)

      In the midpoint sump plant room, (Dual Configuration)

    4.15 Power Supply Redundancy

    Dual configuration PMCS Server and PLC processing units will be fed through the UPS system and

    parallel power supplies to ensure that failure of a single supply does not induce a common-mode

    failure to redundant equipment.

    4.16 Capacity Sizing

    The PMCS will be capacity sized to accommodate the requirements of the outline design detailed

    herein. Furthermore, allowances will be made for additional capacity, as follows:

      I/O intrinsic average spare capacity: 10%

      I/O spare capacity by addition of modules: 25%  I/O spare capacity by addition of subsystems: 50%

      PLC Processor capacity by addition of spare capacity: 100%

      SCADA Server disk/processing spare capacity: 200%

    5.0 General Monitoring and Control Scheme

    5.1 Data Acquisition

    The PMCS performs logging of all data point values acquired or derived into a historical database.

    Log entries will provide the following information:

  • 8/20/2019 KEO Design Report

    21/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 17 of 36

    Rev. D02

      Time stamp of entry

      Date stamp of entry

      Identity of the data point  Data point value with scaling

    Data point transmission through the PMCS will be optimised with respect to update rates and data

    push/pull configuration in order that:

      Valid and current data is always available throughout the system

      Data currency is always deterministic

      Throughput on the transmission infrastructure is optimal

      The transmission infrastructure can accommodate worst case data-burst situations,

    particularly in non-normal scenarios.

    The dual supervisory control PLC’s will independently gather all data from local sources regardless of

    master-standby status. This approach will provide validation that each main supervisory control PLC

    has an active communication link with the outstation devices, and will maintain data currency

    allowing hot-swap to the standby in the event of failure of the master unit.

    5.2 Alarm Monitoring

    The PMCS will monitor all controlled plant for alarm conditions, including PMCS-internal fault

    conditions.

    The following alarm conditions will be monitored, as follows:

      Alarm indications generated as a result of detection of conditions external to the PMCS. The

    nature and extent of such alarms will be determined during subsequent design stages, but

    are likely to include sensing of out-of-band parameters, i.e. physical measurements outside

    their expected range.

      Alarm indications generated as a result of detection of conditions internal to the PMCS. The

    nature and extent of such alarms will be determined at subsequent design stages, but are

    likely to include sensing of failure of control system processors, and the like.

    Alarm indications will be filtered and stored by the PMCS.

    Filtered alarm indications will be transmitted to the TAO/TMC for remote condition monitoring.

    Two forms of alarm and fault monitoring mechanisms will be provided, as follows:

      Active reporting by exception, whereby the plant and PMCS elements will signal alarm and

    fault conditions detected

      Polled monitoring by PMCS, whereby the active control elements of the control system will

    intercommunicate periodically in order to determine the ‘health’, i.e. the correct operati on,

    of the control system itself.

  • 8/20/2019 KEO Design Report

    22/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 18 of 36

    Rev. D02

    Alarm indications will be ranked by importance/severity and displayed via the SCADA Tunnel

    Operator Terminal (GUI) such that conditions are displayed in different modes according to the

    condition severity and the operating privileges of any user logged on to the system.

    Alarm indications will be recorded in a historical database for subsequent analysis. Log entries will

    provide the following information:

      Time stamp of entry

      Date stamp of entry

      Description of the alarm condition

    5.3 Control and Data Flows

    The dual supervisory control PLC's will receive control commands from the SCADA Servers and will

    derive their own responses to these commands. The supervisory control PLC designated as master

    will be configured to issue demand outputs to the tunnel plant. The standby supervisory control PLC

    will be inhibited from issuing demand outputs.

    The master and standby supervisory control PLC’s will replicate commands and data between them

    in order that the processing context of both units remains synchronized, allowing hot-swap to the

    standby in the event of failure of the master unit.

    The SCADA Servers and TSS application will request data only from the supervisory control PLC that

    is designated as master.

    Dual configuration outstation PLC's will both transmit data to both supervisory control PLC’s. 

    Inputs from plant to dual PLC units will be read from PLC units and will be combined into a common

    data set. In the case of data mismatch the worst-case plant condition will be reported.

    Outputs to plant from dual RIO units will be configured so that either PLC device can operate the

    plant by paralleling of outputs, thereby ensuring continued / fail-safe plant operation in the event of

    failure of a single PLC unit.

    5.4 Control Modes

    The PMCS will provide a range of control modes to suit the operational requirements of the tunnelenvironment.

    The supervisory control PLC’s will accept requests for selection of control mode and will arbitrate

    these requests in order to activate the highest priority control mode.

    The following general control modes/sources will be provided ranked in increasing priority order:

      Automatic

    Automatic control mode is the default control mode and is always active, although possibly over-

    ridden by a higher priority control mode. Automatic control mode demand is derived from plantsensor levels and states, set-points, and control parameters. Automatic control mode demand will

  • 8/20/2019 KEO Design Report

    23/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 19 of 36

    Rev. D02

    always be derived and presented to Operators, regardless of the actual control mode active, thereby

    providing the operator with visibility of the automatically calculated demand.

      TMC Traffic Control operation through the TSS application

      TOA Tunnel Operation control relates to operator control and demand selections from the

    TMC Tunnel Operator interfaced via the TMC control stations and Network.

      Engineering Terminal

      Engineering Terminal control relates to operator control and demand selections from

    engineering/maintenance terminals connected at any location on the PMCS network

    infrastructure, and normally present at the TMC

      SCADA GUI application

      The SCADA GUI application is the primary source of system control moding', and is located

    within the Tunnel Services Building (TSB).

      Smoke Control Panels

      These control mode selections will be requested from the SCP’s. Arbitration of control

    requests will be performed in the event that both SCP's are accessed at the same time such

    that only one Smoke Control Panel can issue commands at a time.

      Local Plant Control

    Local plant control will be affected by direct operation of individual items of plant and/or their

    associated autonomous control systems via plant-local control panels. The PMCS will continue to

    monitor locally controlled plant and generate control demands wile local plant control is active; in

    order that seamless transition of control may be achieved once local plant control is relinquished.

    Additional control modes specific to particular tunnel systems will be provides, as required, and

    these are described herein within the sections detailing the control schemes for specific tunnel

    systems.

    5.5 Running Hours and Plant Metrics

    The PMCS will acquire/derive and store data relating to the running time of plant, as well as other

    metrics required to assist the effective and efficient plant maintenance. Data to be a

    acquired/derived and stored includes the following:

      Plant running time in hours

      Plant duty cycle

      Plant failure instances

      Plant failure instance periods

    The PMCS will provide the ability to reset metrics for individual items of plant.

    5.6 Signal Conditioning

    The PMCS will implement a scheme of signal conditioning and scaling that ensures that data is

    transmitted, stored, and manipulated in a uniform and consistent manner.

  • 8/20/2019 KEO Design Report

    24/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 20 of 36

    Rev. D02

    Where required, digital inputs will be conditioned by pulse stretching in order that fast switching

    signals are detected correctly

    Where required, digital inputs will be conditioned by de-bouncing in order that switch selections and

    the like are read correctly.

    6.0 Tunnel Lighting System Control Scheme

    6.1 Control Scheme Overview

    The PMCS will provide a range of control modes to provide efficient and effective control of the

    lighting system.

    The PMCS will accept requests for selection of control mode and will arbitrate these requests inorder to activate the highest priority control mode.

    Control modes that will be provided, ranked in increasing order of priority, are as follows:

      Automatic

      Manual Operator Override from TMC/TSS

      Manual Operator Override from TOA/SCADA GUI

      Manual Operator Override from SCP

      Manual Operator Override from Lighting Control Panel (LCP)

    Automatic control mode is the default control mode, and is always active, although possibly over-

    ridden by a higher priority control mode

    The manual operator override control modes provide an Incident Control sub-mode that allows

    lighting level change demands to be actioned with reduced rate-of-change constraints, thus allowing

    more rapid changes in lighting levels to be achieved.

    Lighting control will be achieved via an autonomous Lighting Control System (LCS). A LCS will be

    provided for each tunnel bore. Each LCS will be provided with a local LCP. The PMCS will interface

    with the LCS, generating demands for lighting levels and monitoring LCS and lighting system status.

    The Manual Operator Override from LCP, also known as Ancillary Local Manual Control, control

    mode will be provided by the LCS

    6.2 General Lighting Control Scheme

    The LCS will control the tunnel lighting automatically based upon photometer sensor readings.

    Two external photometers will be provided at the stopping distance from each tunnel bore entrance

    portal, and the average reading of these will be used by the LCS to calculate a lighting level demand

    for each tunnel bore.

    The LCS will support seven stages of lighting, with stage 1 providing the lowest level of illuminationand stage 7 providing the highest level of illumination, this representing 100% of total possible

  • 8/20/2019 KEO Design Report

    25/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 21 of 36

    Rev. D02

    lighting system output. The LCS will convert photometer sensor readings into a demand for lighting

    for stages 1 through to 7.

    The LCS will integrate photometer sensor readings in order to filter fast rate of change

    environmental effects upon the sensors, thus avoiding rapid and spurious lighting level changes.

    The LCS will sequence through lighting stages with a set-point limit period between stage transitions

    in order that gradual changes in lighting levels are achieved, with an associated reduction in peak

    inrush currents. An Incident Control Mode will be provided by the LCS in which the limit period

    between stage transitions is reduced so that more rapid changes in lighting level may be made.

    The LCS will detect lamp failures and switch in additional units to compensate and maintain lighting

    levels.

    Threshold zone luminance will track the L20 luminance measured by the external photometers. The

    threshold zone luminance will maintain 7% of the L20 value.

    Transition zone luminance will track the threshold zone luminance and will vary along the length of

    the zone following the reduction curve defined in BS5489-2.

    Exit zone luminance will be as defined in BS5489-2.

    Emergency lighting levels will be in accordance with BS5489-2 and BS EN 1838:1999, taken to be the

    greater of the required level for stage 2 lighting or 15lux.

    Lighting stages 1 through to 4 will be backed up by Emergency Standby Generator, with UPS support

    for stage 1 and 2 lighting to cover the period of generator start-up. Failure of the Emergency Standby

    Generator to provide a supply within 5 minutes of a demand will result in reversion to emergency

    lighting levels, which will be maintained for at least 2 hours via the UPS.

    6.3 Automatic Control Mode

    In Automatic control mode the LCS will autonomously control the lighting levels within each tunnel

    bore based upon external photometer sensor readings.

    The automatically calculated lighting stage demand, and the currently active lighting stage for each

    tunnel bore will be monitored by the PMCS, and this will be displayed on the SCADA GUI and

    recorded by the SCADA Servers. This will give the Operator visibility of how the lighting control will

    change when higher priority control modes are de-activated and lower priority control modes

    become active.

    6.4 Manual Operator Override from TMC Control Mode

    The PMCS will accept Manual Operator Override from TMC control mode demands for each tunnel

    bore. These demands will be for lighting stage 7 only.

    The Manual Operator Override from TMC control mode will remain active until the PMCS receives a

    control mode reset command from the TMC.

  • 8/20/2019 KEO Design Report

    26/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 22 of 36

    Rev. D02

    The SCADA GUI will provide a password-protected manual operator override control mode reset

    function in case it is not possible for the TMC operator to issue a reset command due to TMC

    communications link failures, and the like. The use of this function will be recorded by the SCADAServers for auditing purposes.

    6.5 Manual Operator Override from SCADA GUI Control Mode

    The PMCS will accept Manual Operator Override from SCADA GUI control mode demands for each

    tunnel bore. These demands will be for lighting stages 1 through 7.

    The PMCS will request the LCS to activate the lighting stage demanded by the operator. The LCS will

    arbitrate the PMCS lighting stage demand, only selecting for activation demanded lighting stages

    greater than the lighting stage demand calculated automatically by the LCS. Lighting stage demands

    rejected by the LCS will be displayed by the SCADA GUI and recorded by the SCADA Servers.

    The PMCS will provide an Incident Control Mode that will allow the PMCS to request the LCS to

    activate the demanded lighting stage with reduced transition times between lighting stages in order

    to allow more rapid variations in lighting levels to be achieved.

    The Manual Operator Override from SCADA GUI control mode will remain active until the PMCS

    receives a control mode reset command from the SCADA GUI.

    6.6 Manual Operator Override from SCP Control Mode

    The PMCS will accept Manual Operator Override from SCP control mode demands from for each

    tunnel bore. These demands will be for lighting stages 1 through 7.

    Four smoke control panels will be provided, situated at the portals, one per entrance and exit to

    each tunnel bore.

    Lighting control via the SCP’s will be arbitrated on a ‘first -come, first-served’ basis such that once an

    SCP has been granted control for a tunnel bore the other SCP’s will be locked out from control of

    that tunnel bore for the duration of the control selection being active.

    SCP’s will provide the following lighting-related controls and indicators for each tunnel bore:

      Request/relinquish local manual control selection control : 1 input latching toggle  Local manual control active indicator

      Currently selected lighting stage indicator: 7 stage indication from stage 1 to stage 7

      Requested lighting stage increment/decrement demand control: 2 input control with senses

    of ‘increment’ and ‘decrement’ 

      Incident control demand control: 2 input control with senses of ‘on’ and ‘off’ 

    The PMCS will request the LCS to activate the lighting stage demanded by the Operator at the SCP.

    The LCS will arbitrate the PMCS lighting stage demand, only selecting for activation demanded

    lighting stages greater than the lighting stage demand calculated automatically by the LCS. Lighting

    stage demands rejected by the LCS will be displayed by the SCADA GUI and recorded by the SCADAServers.

  • 8/20/2019 KEO Design Report

    27/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 23 of 36

    Rev. D02

    The PMCS will provide an Incident Control Mode that will allow the PMCS to request the LCS to

    activate the demanded lighting stage with reduced transition times between lighting stages in order

    to allow more rapid variations in lighting levels to be achieved.

    The Manual Operator Override from SCP control mode will remain active until the PMCS receives a

    relinquish control command from the SCP.

    6.7 Manual Operator Override from LCP Control Mode

    The Manual Operator Override from LCP control mode will be provided by the LCS.

    A local control panel will be provided, adjacent to the LCS at the TSB.

    The Manual Operator Override from LCP control mode will remain active until relinquished at the

    LCP.

    6.8 Lamp Status Monitoring

    The TPM&CS will continuously monitor the LCS for the status of the tunnel lamps, segmented into

    tunnel zones. The following information will be displayed on the SCADA GUI and recorded by the

    SCADA Servers for each tunnel zone:

      One or more lamp/ballast failures present

      One or more lamps in maintenance override

    6.9 Emergency Standby Generator Load Shedding

    The PMCS will inform the LCS that lighting stages in excess of stage 4 lighting cannot be exceededselected when the Emergency Standby Generator is active in the event of supply failure.

    The PMCS will inform the LCS that lighting stages in excess of stage 2 lighting cannot be selected

    when the Emergency Standby Generator has failed to become active on demand in the event of

    supply failure, and lighting is therefore supported by UPS only.

    7.0 Fire Safety Systems Control Scheme

    7.1 Emergency/Electrical Distribution Panels Control Scheme

    Emergency Panels (EP's) and Emergency Distribution Panels (EDP's) will be provided with limit

    switches to allow the detection of the following conditions:

      Fire extinguisher compartment door open/closed status

      Fire extinguisher present/removed status

      Emergency SOS telephone compartment door open/closed status

      Fire hydrant compartment door open/closed status.

    The PMCS will continuously monitor EP and EDP limit switch status this information will be displayed

    on the SCADA GUI and recorded by the SCADA Servers.

  • 8/20/2019 KEO Design Report

    28/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 24 of 36

    Rev. D02

    7.2 Smoke Detection System

    The Video Automatic Iincident Detection system for each tunnel bore will provide an array of

    discrete signals to signal each of the detection events for each VAID zone. The following detectionevents will be provided:

      Slow vehicle

      Stopped vehicle

      Vehicle in wrong direction

      Smoke detected

      Object in carriageway (size to be determined)

      Pedestrian/animal in carriageway

    VAID detection events will be displayed on the SCADA GUI and recorded by the SCADA Servers.

    The VAID systems for each tunnel bore will autonomously monitor and detect camera faults and will

    signal these to the PMCS. VAID system camera faults will be displayed on the SCADA GUI and

    recorded by the SCADA Servers.

    The VAID smoke detection events for both tunnel bores will be displayed at each SCP.

    The PMCS will allow the Operator to configure the VAID system for contra-flow working via the

    SCADA GUI. The use of this function will be recorded by the SCADA Servers.

    7.3 Smoke Control PanelsFour smoke control panels will be provided, situated at the portals, one per entrance and exit to

    each tunnel bore.

    SCP’s will provide the following control-related controls and indicators for each tunnel bore:

      Ventilation fan status indication

      Ventilation fan manual override control

      Lighting system status indication

      Lighting system manual override control

      Firealarm status

      SCP panel status

      Manual broadcast of PA messages

    SCP’s will provide a limit switch to sense the panel door open/close position. The PMCS will

    continuously monitor the limit switches for status and this information will be displayed on the

    SCADA GUI and recorded by the SCADA Servers.

  • 8/20/2019 KEO Design Report

    29/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 25 of 36

    Rev. D02

    8.0 Communications Systems Control Scheme

    8.1 Control Scheme OverviewThe PMCS will perform continuous monitoring of tunnel communications systems status and this

    information will be displayed on the SCADA GUI and recorded by the SCADA Servers.

    The status of the following communications systems will be monitored:

      Emergency Roadside Telephones

      Public Automatic Branch Exchange

      Airwave and Emergency Services radio repeater system

      Public Address system

    The PMCS will provide supervisory control of the following systems:

      Public Address system

    8.2 Emergency Roadside Telephones Control Scheme

    The open/closed status of each Emergency SOS telephone compartment door will be monitored.

    8.3 Public Automatic Branch Exchange Control Scheme

    The fault output of the PABX will be monitored for a failure status.

    8.4 Airwave and Emergency Services Radio Repeater Control Scheme

    The fault output of each component of the Radio Rebroadcast equipment will be monitored for afailure status.

    8.5 Public Address Control Scheme

    The PMCS will allow the Operator to select from eight pre-defined announcements for broadcast

    within each tunnel bore from either the SCADA GUI or the TMC.

    The PMCS will demand the broadcast of the last pre-defined announcement selected from either the

    SCADA GUI or the TMC, i.e. the SCADA GUI and the TMC will have equal priority in selecting pre-

    defined announcements for broadcast.

    The selected pre-defined announcement will continue to be broadcast until selected to stop at

    either the SCADA GUI or the TMC, or until superseded by another pre-defined announcement.

    The PMCS will monitor the Public Address system for confirmation that the commanded pre-defined

    announcement is selected for broadcast by the Public Address system, and this information will be

    displayed on the SCADA GUI and recorded by the SCADA Servers.

    The PMCS will monitor the Public Address system form amplifier line load discrepancy status

    information and this will be displayed on the SCADA GUI and recorded by the SCADA Servers.

  • 8/20/2019 KEO Design Report

    30/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 26 of 36

    Rev. D02

    9.0 Electrical Supply Systems Control Scheme

    9.1 Control Scheme OverviewThe PMCS will perform continuous monitoring of Electrical Supply systems status and this

    information will be displayed on the SCADA GUI and recorded by the SCADA Servers.

    The status of the following Electrical Supply systems will be monitored:

      High Voltage (HV) system

      Transformers

      Low Voltage (LV) system

      Emergency Standby Generators

      UPS systems

      Dual redundant power supplies (Equipment based)

    9.2 MV System Control Scheme

    Two HV supplies with appropriate redundancy will be supplied to meet the needs of the tunnel.

    The PMCS will perform continuous monitoring of HV system status and this information will be

    displayed on the SCADA GUI and recorded by the SCADA Servers. The following status information

    will be monitored:

      Bus status

      ACB status

    Description Type Direction Sense/Units Format

    TSB VCB 'A' Incomer Status DIG I Failed/Normal +24vdc

    TSB VCB 'B' Incomer Status DIG I Failed/Normal +24vdc

    TSB VCB 'A' Bus Status DIG I Failed/Normal +24vdc

    TSB VCB 'A' Bus Status DIG I Failed/Normal +24vdc

    TSB VCB Bus Coupler Status DIG I Failed/Normal +24vdc

    TSB VCB 'B' Bus Status DIG I Failed/Normal +24vdc

    TSB VCB 'B' Bus Status DIG I Failed/Normal +24vdc

    9.3 Transformer Control Scheme

    Four transformers will be installed onthis project as follows:

    The load capacity of new transformers for the tunnel and underpass will be determined based upon

    the detailed design of lighting, ventilation, drainage, communications and tunnel control systems.

    Transformers will be provided in a duty/duty/duty/stand-by arrangement with each duty

    transformer capable of supplying 1/3 of the total tunnel load. In the event of a single transformerfailure the stand-by transformer will operate to ensure that the electrical power supply to the tunnel

  • 8/20/2019 KEO Design Report

    31/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 27 of 36

    Rev. D02

    continues with full functionality. The transformers will be located within separate enclosures at the

    TSB. Low maintenance transformers will be utilised.

    Each transformer will be fitted with at least two temperature-sensing devices fitted within pockets in

    each phase winding to provide Over Temperature protection. The transformers will have Restricted

    Earth Fault protection, as well as conventional Overcurrent, and Earth fault protection.

    An estimate of the required loads based on the equipment being provided at part of the tunnel and

    underpass design (excluding ITS loads) indicates the following capacities for the new equipment:

      Transformer A - 1600 kVA (Duty)

      Transformer B - 1600 kVA (Duty)

      Transformer C - 1600 kVA (Duty)

      Transformer D - 1600 kVA (Standby)

    Description Type Direction Sense/Units Format

    Tx1 'A' Operating Temp DIG I Normal/High +24vdc

    Tx1 'A' Operating Temperature DIG I Normal/High +24vdc

    Tx1 'A' Primary Feeder Brkr Control DIG I Normal/LocalO/R +24vdc

    Tx1 'A' Primary feeder Brkr Control DIG I Normal/LocalO/R +24vdc

    Tx1 'A' Primary Feeder Brkr Posn DIG I /Open +24vdc

    Tx1 'A' Primary Feeder Brkr Posn DIG I /Closed +24vdc

    Tx1 'A' Primary feeder Brkr Posn DIG I -/Open +24vdc

    Tx1 'A' Primary feeder Brkr Posn DIG I -/Closed +24vdc

    Tx1 'A' Primary Feeder Brkr Service DIG I Avail/OutServ +24vdc

    Tx1 'A' Primary feeder Brkr Service DIG I Avail/OutServ +24vdc

    Tx1 'A' Primary Feeder Brkr Status DIG I Normal/Tripped +24vdc

    Tx 1'A' Primary feeder Brkr Status DIG I Normal/Tripped +24vdc

    Tx1 'A' Secondary Power Status DIG I Failed/Normal +24vdc

    Tx1 'A' Secondary Power Status DIG I Failed/Normal +24vdc

    Tx2 'A' Operating Temp DIG I Normal/High +24vdc

    Tx2 'A' Operating Temperature DIG I Normal/High +24vdc

    Tx2 'A' Primary Feeder Brkr Control DIG I Normal/LocalO/R +24vdc

    Tx2 'A' Primary feeder Brkr Control DIG I Normal/LocalO/R +24vdc

    Tx2 'A' Primary Feeder Brkr Posn DIG I /Open +24vdc

    Tx2 'A' Primary Feeder Brkr Posn DIG I /Closed +24vdc

    Tx2 'A' Primary feeder Brkr Posn DIG I -/Open +24vdc

    Tx2 'A' Primary feeder Brkr Posn DIG I -/Closed +24vdc

    Tx2 'A' Primary Feeder Brkr Service DIG I Avail/OutServ +24vdcTx2 'A' Primary feeder Brkr Service DIG I Avail/OutServ +24vdc

  • 8/20/2019 KEO Design Report

    32/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 28 of 36

    Rev. D02

    Tx2 'A' Primary Feeder Brkr Status DIG I Normal/Tripped +24vdc

    Tx2 'A' Primary feeder Brkr Status DIG I Normal/Tripped +24vdc

    Tx2 'A' Secondary Power Status DIG I Failed/Normal +24vdcTx2 'A' Secondary Power Status DIG I Failed/Normal +24vdc

    Tx3 'B' Operating Temp DIG I Normal/High +24vdc

    Tx3 'B' Operating Temperature DIG I Normal/High +24vdc

    Tx3 'B' Primary Feeder Brkr Control DIG I Normal/LocalO/R +24vdc

    Tx3 'B' Primary feeder Brkr Control DIG I Normal/LocalO/R +24vdc

    Tx3 'B' Primary Feeder Brkr Posn DIG I /Open +24vdc

    Tx3 'B' Primary Feeder Brkr Posn DIG I /Closed +24vdc

    Tx3 'B' Primary feeder Brkr Posn DIG I -/Open +24vdc

    Tx3 'B' Primary feeder Brkr Posn DIG I -/Closed +24vdc

    Tx3 'B' Primary Feeder Brkr Service DIG I Avail/OutServ +24vdc

    Tx3 'B' Primary feeder Brkr Service DIG I Avail/OutServ +24vdc

    Tx3 'B' Primary Feeder Brkr Status DIG I Normal/Tripped +24vdc

    Tx3 'B' Primary feeder Brkr Status DIG I Normal/Tripped +24vdc

    Tx3 'B' Secondary Power Status DIG I Failed/Normal +24vdc

    Tx3 'B' Secondary Power Status DIG I Failed/Normal +24vdc

    Tx4 'B' Operating Temp DIG I Normal/High +24vdc

    Tx4 'B' Operating Temperature DIG I Normal/High +24vdc

    Tx4 'B' Primary Feeder Brkr Control DIG I Normal/Local

    O/R

    +24vdc

    Tx4 'B' Primary feeder Brkr Control DIG I Normal/Local

    O/R

    +24vdc

    Tx4 'B' Primary Feeder Brkr Posn DIG I /Open +24vdc

    Tx4 'B' Primary Feeder Brkr Posn DIG I /Closed +24vdc

    Tx4 'B' Primary feeder Brkr Posn DIG I -/Open +24vdc

    Tx4 'B' Primary feeder Brkr Posn DIG I -/Closed +24vdc

    Tx4 'B' Primary Feeder Brkr Service DIG I Avail/OutServ +24vdc

    Tx4 'B' Primary feeder Brkr Service DIG I Avail/OutServ +24vdc

    Tx4 'B' Primary Feeder Brkr Status DIG I Normal/Tripped +24vdc

    Tx4 'B' Primary feeder Brkr Status DIG I Normal/Tripped +24vdc

    Tx4 'B' Secondary Power Status DIG I Failed/Normal +24vdc

    Tx4 'B' Secondary Power Status DIG I Failed/Normal +24vdc

    9.4 LV System Control Scheme

    Description Type Direction Sense/Units Format

    LV Bus Energised/De-energised DIG I De-

    Engsd/Engisdd

    +24vdc

    LV Closing Supply Battery Condtn DIG I Normal/Low +24vdc

  • 8/20/2019 KEO Design Report

    33/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 29 of 36

    Rev. D02

    LV Closing supply Battery Condtn DIG I Normal/Low +24vdc

    LV Bus Energised/De-energised DIG I De-

    Engsd/Engisdd

    +24vdc

    LV Closing Supply Battery Condtn DIG I Normal/Low +24vdc

    LV Closing supply Battery Condtn DIG I Normal/Low +24vdc

    LV Closing Supply Charger Status DIG I Normal/Fault +24vdc

    LV Closing supply charger Status DIG I Normal/Fault +24vdc

    LV Switchroom Air Extract Status DIG I Normal/Failed +24vdc

    LV Switchroom Air Supply Status DIG I Normal/Failed +24vdc

    LV Tripping Supply Battery Condtn DIG I Normal/Low +24vdc

    LV Tripping supply Battery Condtn DIG I Normal/Low +24vdc

    LV Tripping Supply Charger Status DIG I Normal/Fault +24vdc

    LV Tripping supply charger Status DIG I Normal/Fault +24vdc

    Bus Section ACB Local Override DIG I Normal/LocalO/R +24vdc

    Bus Section ACB Position DIG I -/Open +24vdc

    Bus Section ACB Position DIG I -/Closed +24vdc

    Bus Section ACB Service DIG I Avail/OutServ +24vdc

    ACB 'A' Incomer 1 Control DIG I Normal/LocalO/R +24vdc

    ACB 'A' Incomer 2 Control DIG I Normal/LocalO/R +24vdc

    ACB 'A' Incomer 1 Energy Reading ANA I kWh 4-20mA

    ACB 'A' Incomer 2 Energy Reading ANA I kWh 4-20mA

    ACB 'A' Incomer 1 Position DIG I -/Open +24vdc

    ACB 'A' Incomer 1 Position DIG I -/Closed +24vdc

    ACB 'A' Incomer 2 Position DIG I -/Open +24vdc

    ACB 'A' Incomer 2 Position DIG I -/Closed +24vdc

    ACB 'A' Incomer 1 Service DIG I Avail/OutServ +24vdc

    ACB 'A' Incomer 2 Service DIG I Avail/OutServ +24vdc

    ACB 'A' Incomer 1 Trip Status DIG I Normal/Tripped +24vdc

    ACB 'A' Incomer 2 Trip Status DIG I Normal/Tripped +24vdc

    ACB 'B' Incomer 1 Control DIG I Normal/LocalO/R +24vdc

    ACB 'B' Incomer 2 Control DIG I Normal/LocalO/R +24vdc

    ACB 'B' Incomer 1 Energy Reading ANA I kWh 4-20mA

    ACB 'B' Incomer 2 Energy Reading ANA I kWh 4-20mA

    ACB 'B' Incomer 1 Position DIG I -/Open +24vdc

    ACB 'B' Incomer 1 Position DIG I -/Closed +24vdc

    ACB 'B' Incomer 2 Position DIG I -/Open +24vdc

    ACB 'B' Incomer 2 Position DIG I -/Closed +24vdc

    ACB 'B' Incomer 1 Service DIG I Avail/OutServ +24vdc

  • 8/20/2019 KEO Design Report

    34/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 30 of 36

    Rev. D02

    ACB 'B' Incomer 2 Service DIG I Avail/OutServ +24vdc

    ACB 'B' Incomer 1 Trip Status DIG I Normal/Tripped +24vdc

    ACB 'B' Incomer 2 Trip Status DIG I Normal/Tripped +24vdc

    Bus 'A' Power Status DIG I Failed/Normal +24vdc

    Bus 'B' Power Status DIG I Failed/Normal +24vdc

    Bore A Restricted Earth Status DIG I - +24vdc

    Bore A Supply Power Reading ANA I kWh 4-20mA

    Bore A TxA 1 Power Monitoring ANA I kWh 4-20mA

    Bore A TxA 2 Power Monitoring ANA I kWh 4-20mA

    Bore A TxB 3 Power Monitoring ANA I kWh 4-20mA

    Bore A TxB 4 Power Monitoring ANA I kWh 4-20mA

    Bore A UPS A Power Monitoring ANA I kWh 4-20mA

    Bore A UPS B Power Monitoring ANA I kWh 4-20mA

    Bore B Restricted Earth Status DIG I - +24vdc

    Bore B Supply Power Reading ANA I kWh 4-20mA

    Bore B TxA 1 Power Monitoring ANA I kWh 4-20mA

    Bore B TxA 2 Power Monitoring ANA I kWh 4-20mA

    Bore B TxB 3 Power Monitoring ANA I kWh 4-20mA

    Bore B TxB 4 Power Monitoring ANA I kWh 4-20mA

    Bore B UPS A Power Monitoring ANA I kWh 4-20mA

    Bore B UPS B Power Monitoring ANA I kWh 4-20mA

    Bus 'A' Power Factor Corrector Stage 1 DIG I Off/On +24vdc

    Bus 'A' Power Factor Corrector Stage 1 DIG I On/Off +24vdc

    Bus 'A' Power Factor Corrector Stage 2 DIG I Off/On +24vdc

    Bus 'A' Power Factor Corrector Stage 2 DIG I On/Off +24vdc

    Bus 'A' Power Factor Corrector Stage 3 DIG I Off/On +24vdc

    Bus 'A' Power Factor Corrector Stage 3 DIG I On/Off +24vdc

    Bus 'A' Power Factor Corrector Stage 4 DIG I Off/On +24vdc

    Bus 'A' Power Factor Corrector Stage 4 DIG I On/Off +24vdc

    Bus 'A' Power Factor Corrector Stage 5 DIG I Off/On +24vdc

    Bus 'A' Power Factor Corrector Stage 5 DIG I On/Off +24vdc

    Bus 'A' Power Factor Corrector Stage 6 DIG I Off/On +24vdc

    Bus 'A' Power Factor Corrector Stage 6 DIG I On/Off +24vdc

    Bus 'A' Power Factor Corrector Status DIG I Normal/Fault +24vdc

    Bus 'B' Power Factor Corrector Stage 1 DIG I Off/On +24vdcBus 'B' Power Factor Corrector Stage 1 DIG I On/Off +24vdc

  • 8/20/2019 KEO Design Report

    35/40

     

    Tunnel SCADA PMCS Control Concept

    Specification 

    Doc. No. EXW-P007-0000-MC-KEO-RP-00209 Page 31 of 36

    Rev. D02

    Bus 'B' Power Factor Corrector Stage 2 DIG I Off/On +24vdc

    Bus 'B' Power Factor Corrector Stage 2 DIG I On/Off +24vdc

    Bus 'B' Power Factor Corrector Stage 3 DIG I Off/On +24vdcBus 'B' Power Factor Corrector Stage 3 DIG I On/Off +24vdc

    Bus 'B' Power Factor Corrector Stage 4 DIG I Off/On +24vdc

    Bus 'B' Power Factor Corrector Stage 4 DIG I On/Off +24vdc

    Bus 'B' Power Factor Corrector Stage 5 DIG I Off/On +24vdc

    Bus 'B' Power Factor Corrector Stage 5 DIG I On/Off +24vdc

    Bus 'B' Power Factor Corrector Stage 6 DIG I Off/On +24vdc

    Bus 'B' Power Factor Corrector Stage 6 DIG I On/Off +24vdc

    Bus 'B' Power Factor Corrector Status DIG I Normal/Fault +24vdc

    9.5 Emergency Standby Generator Control Scheme

    Description Type Direction Sense/Units Format

    Diesel A Alternator ACB Posn DIG I Open/Closed +24vdc

    Diesel A Alternator Output Status DIG I Normal/Failed +24vdc

    Diesel A Engine Fuel Tank Level