June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Guidelines and conventions for ALICE PVSSII control software
•Graphical User Interface•Naming and Numbering conventions•Project organization
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Selected tools and standards- news (1)
• Control applications run on Windows XP Operating System
• Linux Operating System approval from the ACC team is mandatory.
• PVSS II shall be use as the SCADA system• Framework tools shall be used for any development
of control applications • Finite State Machine shall be used for the full control
hierarchy in Alice• Sub-detector operation (states, actions, transitions..)
performed via the FSM mechanism• Except TPC and HMPID no reaction from detector side
so good agreements with these rules
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Who is doing what? - updates
• ACC team will ensure the support for all future tools developments (Fw, PVSS.. ) ([email protected])
• Every sub-detector shall nominate a person responsible or the control software (development and maintenance) and communicate this to the ACC team – no answer
• Sub-detector responsible must ensure that the control software follow the guidelines, its integration and functionality - no answer
• Any control software prior to the final installation shall be validated in the DCS lab with a reference system, therefore a time schedule is need it from the sub-detector responsible - no answer
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
General naming rules
• Two standards are valid:– interCapNotation – name splitting using underscore.
• Abbreviations are considered as single words.• Sub-detector identification mandatory the
standard three-letter sub-detector code shall be used (as defined in Appendix C of the document).
• Numbering starts at 0.
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Sub-detector codes:
CodeSub-detector
spd ITS pixel detector
sdd ITS drift detector
ssd ITS strip detector
tpc TPC
trd TRD
tof TOF
phs PHOS
cpv CPV
hmp HMPID
fmd FMD
pmd PMD
v00 V0
t00 T0
mch Muon tracker
mtr Muonb trigger
zdc ZDC
emc EMCal
Acorde
Codes for other systems or objects:
CodeSystem or object
tri Trigger
hlt High Level Trigger
daq Central DAQ
dcs Detector Control System
Experiment Control System
Cooling
Gas
Electricity
fra Front absorber
saa Small angle absorber
sfr Space frame
l3m L3 magnet
dim Dipole magnet
bmp Beam pipe
exh Experimental hall
int Integration
otr Other (not classified)
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Guidelines and conventions – 1 • PVSS project name
– project in US English language(PVSSen_US.iso88591)– every project shall be created as distributed system– naming convention for the detector top level*<dc_dcs> Ex: tpc_dcs, phs_dcs, sdd_dcs
dc Detector Code dcs abbreviation Detector Control System
*It is recommended to have one PVSSII project per detector i.e. with small number of channels (hv, lv, cooling, fero)
• PVSS System name and number– Names shall be in lowercase, underscore “_” shall be used to
separate words.– Naming convention is <dc_..> ex: tpc_dcs, phs_dcs– should intuitively describe its function and be documented by
sub-detector responsible – PVSSII system number per sub-detector is assigned by ACC
team following a written request. – electronic form available on the Alice DCS web page
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Guidelines and conventions – 2
• OPC and DIM servers – The same naming formula
• <dc_opcsn> where opcsn = opc server name,• <dc_dimsn> where dimsn = dim server name, Ex:
tpc_opcwiener tpc_dimfero
• OPC driver numbers• Framework PVSS OPC + Simulator driver numbers are
reserved– CAEN 6, Wiener 11, Iseg 8and 9, ELMB 7,
• For any new hardware integrated in the ALICE DCS control , the OPC and Dim driver numbers will be assigned by the ACC team, following a written request.
• DIM driver numbers– will follow the same policy as OPC
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Guidelines and Conventions - 3• Panels
– Look and feel• Will be displayed on screens with at least resolution of 1024 x 768
pixels.• Font to be used is: “Arial regular 10”; the background colour to be
used is: “_3DFace” (more conventions in the FW guidelines)• Naming of sub-systems and parameters shall be as the ones listed
(see Appendix A of the document).• Child panels shall be cascaded and have a close button at the
bottom right corner.• ALICE logo shall appear at the top left corner.• help button located at the top right corner, and give access to the
online help. • online help shall be provided in the standard format
– Naming convention• Same as the general convention , <dc_..> followed by a meaningful
abbreviation: ex: tpc_TrendingSectorA.pnl
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Guidelines and Conventions – 4• Panels
– Path and subfolders• For new hardware integration the folder structure shall be ..newHardwareName/config – contains the config file ..newHardwareName/dplist -- contains dpfileDataPoint /
DataPointTypes ex: newHardwareDP.dpl, newHardwareNameDPT.dpl
..newHardwareName/panels – contains the corresponding panels ..newHardwareName/scripts
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Guidelines and Conventions – 5• Development
– DataPointsTypes and DataPoints Naming scheme• PVSS II and Framework DP and DPT shall not be changed• For new hardware added the DP should be exactly the OPC
or DIM items names from the Space Name Server• The prefix (detector code) is mandatory . For DPT first letter
must be upper case for DP should be smaller case• The general naming scheme could be
<dc_ss...>, where ss is the Sub-System name Example: Tpc_hv_anode for DPT, tpc_hvAnodeSect1 for DP
• If detector need to split the name “underscore” as separation shall be used . Ex: tpc_hv_anode
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Guidelines and Conventions – 6
• Development– Libraries and control scripts
• Wherever applicable is recommended to use the Framework ones
• Must have meaningful name• interCapNotation use is strongly recommended• Must be documented in the header file or as a
separate text file in English.• Any upgrades or bug fixes made must contain the
developer name, date and a short description of the change(s).
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Guidelines and Conventions – 7
• Development – FSM objects
• States, actions, alarms shall follow the rules defined by PVSS, Framework and Giacinto’s presentation.
• Naming convention for: states and actions is uppercase • words can be separated by and underscore “_” (e.g.
GO_PHYSICS).• All sub-detectors must provide written documentation on
state diagram of their sub-detector, operation, action, alarms….
• Partitioning will be performed using the FSM tools in conjunction with the ECS partitioning tools
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Guidelines and Conventions – 7
• FSM operational panels – FSM toolkit shall be used a default layout is
provided fwUi.pnl– Two zone –control zone and monitoring zone– Control zone must contain all the CU need it for
operation– Monitoring zone can be used as the detector wants– It is recommended to fill this zone with
complementary information for the operator ex: state diagram of the CU, some crucial parameters
– ACC will soon provide some standard widgets
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Still under development!! Disregard the inconsistencies, it is shown as a working principle!!
June 14, 2005 Alice DCS workshop, UtrechtS.Popescu
Conclusions
• The document can be found http://alicedcs.web.cern.ch/AliceDCS/Documents/ “Guidelines and conventions for ALICE PVSSII control software “
• Still to come…– ACC will come soon with a proposed architecture for the FSM
hierarchy (tests are undergoing SP and AA)– Alarms messages and alarm handling is still to be defined, – A first proposal exist from IT-CO– Alice DCS widgets are still under discussion by the ACC team
• Strongly recommended to contact us if you are having doubts or missing information