242 249 250 235 236 234 243 244 245 232 241 230 240 246 247 248 229 228 227PC 227RR 226RR 225 204 239 238 237 221 220 222 219 223 217 207 209 210 203 212 215 200 215A 251 215 299EV1 OPEN TO BELOW OPEN TO BELOW 206 OPEN TO BELOW CHEEVER 214 PROJECT LOCATION 720 S. Tracy Ave., Bozeman, MT dRA-Architect.com dRA dennis Raffensperger Architect REV. DESCRIPTION DATE REVIEWED BY: DRAWN BY: SHEET DATE SHEET TITLE MONTANA STATE UNIVERSITY MSU-CPDC MONTANA STATE UNIVERSITY BOZEMAN, MONTANA PHONE: 406.994.5413 FAX: 406.994.5665 Consultant #: 1710 CLASSROOM RENOVATIONS 2018 CHEEVER HALL 214 100% CONSTRUCTION DRAWINGS Mosaic DRA COVER A000 03/19/2018 PROJECT #4 PPA#18-2015 CLASSROOM RENOVATIONS 2018 ADDRESS: MONTANA STATE UNIVERSITY BOZEMAN, MT 59717 PROJECT #4 CLASSROOM: CHEEVER HALL 214 SHEETS A000 COVER A001 GENERAL & CODE INFORMATION A100 DEMO PLANS A101 FLOOR PLAN, REFLECTED CEILING PLAN & DETAILS A200 ELEVATIONS A500 TYPICAL DETAILS 1" = 20'-0" CHEEVER SECOND FLOOR VACINITY MAP 1 PROJECT DIRECTORY MECHANICAL/ELECTRICAL/ PLUMBING ENGINEERING: 2880 TECHNOLOGY BLVD. WEST P.O. BOX 1113 BOZEMAN, MT 59771 - 1113 (406) 587 - 0721 CONTACT: Erik Renna, P.E. erenna@m - m.net ARCHITECT: MOSAIC ARCHITECTURE, P.C. 428 North Last Chance Gulch Helena, MT 59601 Ph. 406 - 449 - 2013, CONTACT(S) : Matt Aune, [email protected] 720 S. TRACEY AVE BOZEMAN, MT (406) 581 - 8759 CONTACT: DENNIS RAFFENSPERGER AIA dennis@dra - architect.com dRA d ennis R affensperger A rchitect CONSULTING ARCHITECT: MEP SHEETS E100 ELECTRICAL LIGHTING PLAN E200 ELECTRICAL POWER & SIGNAL PLAN M001 LEGEND, SCHEDULES & DETAILS M100 MECHANICAL PLAN

J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

Embed Size (px)

Citation preview

Page 1: J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

DN

DN

DN

DN

DN

UP

242

249250

235236

234

243244245

232

241230

240

246247248229228

227PC227RR226RR225

204

239

238

237

221220

222219

223

217

207

209

210

203

212

215

200

214

215A

251

215

299EV1

OPEN TOBELOW

OPEN TOBELOW

206

OPEN TOBELOW

CHEEVER 214

PROJECT LOCATION

72

0 S

. Tr

acy

Ave

., B

ozem

an, M

T

dRA-

Arc

hite

ct.c

om

dRA

den

nis

Raf

fens

perg

erArc

hite

ct

REV. DESCRIPTION DATE

REVIEWED BY:DRAWN BY:

SHEET

DATE

SHEET TITLE

MO

NT

AN

AST

AT

E U

NIV

ER

SIT

Y

MSU-CPDCMONTANA STATE UNIVERSITY

BOZEMAN, MONTANAPHONE: 406.994.5413

FAX: 406.994.5665

Consultant #:1710

CL

ASS

RO

OM

RE

NO

VA

TIO

NS

2018

CH

EEVE

R H

ALL

21

4 1

00

% C

ON

STR

UC

TIO

N D

RA

WIN

GS

MosaicDRA

COVER

A00003/19/2018

PR

OJE

CT

#4

PPA#18-2015

CLASSROOM RENOVATIONS 2018

ADDRESS:MONTANA STATE UNIVERSITY

BOZEMAN, MT 59717

PROJECT #4CLASSROOM: CHEEVER HALL 214

SHEETS

A000 COVERA001 GENERAL & CODE INFORMATIONA100 DEMO PLANSA101 FLOOR PLAN, REFLECTED CEILING PLAN & DETAILSA200 ELEVATIONSA500 TYPICAL DETAILS

1" = 20'-0"CHEEVER SECOND FLOOR VACINITY MAP1

PROJECT DIRECTORY

MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:

2880 TECHNOLOGY BLVD. WESTP.O. BOX 1113BOZEMAN, MT 59771-1113(406) 587-0721

CONTACT: Erik Renna, [email protected]

ARCHITECT:

MOSAIC ARCHITECTURE, P.C.428 North Last Chance GulchHelena, MT 59601Ph. 406-449-2013,

CONTACT(S) : Matt Aune, [email protected]

720 S. TRACEY AVEBOZEMAN, MT (406) 581-8759

CONTACT: DENNIS RAFFENSPERGER [email protected]

dRAdennis Raffensperger Architect

CONSULTING ARCHITECT:

MEP SHEETSE100 ELECTRICAL LIGHTING PLANE200 ELECTRICAL POWER & SIGNAL PLANM001 LEGEND, SCHEDULES & DETAILSM100 MECHANICAL PLAN

Page 2: J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

1. GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND ALL CONDITIONS OF THE EXISTING SITE.

2. RESPONSIBILITY FOR ON-SITE COORDINATION OF CONSTRUCTION ACTIVITIES IS WITH THE GENERAL CONTRACTOR.

3. ALL SHOP DRAWING DIMENSIONS TO BE CHECKED AND VERIFIED IN THE FIELD BY THE CONTRACTOR WHO WILL BE RESPONSIBLE FOR SAME.

4. GENERAL CONTRACTOR IS RESPONSIBLE FOR PATCHING OF ANY SURFACES DAMAGED DURING THE CONSTRUCTION PROCESSES. SURFACES ARE TO BE PATCHED FLUSH WITH EXISTING. MATCH EXISTING ADJACENT FINISH OR APPLY NEW FINISH AS SCHEDULED.

5. GENERAL CONTRACTOR TO COORDINATE ALL CUTTING AND PATCHING REQUIRED BY WORK OF ALL TRADES AND AS APPROVED BY ARCHITECT/ ENGINEER.

6. GENERAL CONTRACTOR TO PROVIDE ALL REQUIRED BLOCKING, ANCHORAGES FOR ACCESSORIES, MILLWORK, TRIM, GRAB BARS, CABINETS, SHELVING, TOILET ACCESSORIES, HANDRAILS, OTHER FLUSH OR SEMI-RECESSED EQUIPMENT, MECHANICAL AND ELECTRICAL ITEMS, OR AS SPECIFIED.

7. IN GENERAL, REPETITIVE DETAILS DRAWN ARE SHOWN IN FULL ONLY ONCE. REPETITIONS MAY NOT BE COMPLETE IN EVERY DETAIL AS SHOWN IN THE ORIGINAL DETAIL.

8. PARTITIONS ARE LOCATED BY ONE OF THE FOLLOWING METHODS:9. a) WHERE POSSIBLE, BY RELATIONSHIP TO ADJACENT STRUCTURE.10. b) TYPICAL RELATIONSHIP TO LARGE SCALE DETAILS.11. c) BY DIMENSION FROM STRUCTURE OR PARTITION ALREADY LOCATED.12. d) BY DIMENSION FROM GRID LINES.13. e) DIMENSIONS ARE TO FACE OF STUD.14. DIMENSIONS ARE SHOWN ON THE DRAWINGS. DO NOT SCALE THE DRAWINGS.15. ALL HEIGHTS ARE DIMENSIONED FROM THE TOP OF SUBFLOOR UNLESS NOTED OTHERWISE.16. EDGE TRIM AROUND ALL EDGES OF GYPSUM BOARD WALLS ABUTTING OTHER MATERIALS. LEAVE

1/4" GAP FROM WALL FOR SEALANT.17. WHERE COLUMNS AND STUD WALLS ALIGN, GYPSUM BOARD TO BE CONTINUOUS OVER COLUMNS

OR BOXED AROUND COLUMN IF COLUMN PROJECTS BEYOND WALL.18. GYPSUM BOARD IN TOILET AREAS AND OTHER AREAS INDICATED AS "WET AREAS" TO BE WATER

RESISTANT GYPSUM BOARD.19. BRING TO THE ATTENTION OF THE ARCHITECT ANY CONDITION OR AREA OF FINISH THAT IS IN

QUESTION OR NOT NOTED.20. SEAL OPENINGS IN FLOOR AROUND DUCTS, PIPES, VENTS, SOILPIPES, TRAPS, CONDUIT, ETC.

ACCORDING TO DETAILS & SPECIFICATIONS.21. ALL PENETRATIONS THROUGH WALLS ABOVE CEILING AND BELOW STRUCTURE ARE TO BE CLOSED

TIGHT AROUND PENETRATION. USE FIRESAFING WHERE FIRE-RATED WALLS AND FLOOR/CEILINGS ARE PENETRATED. SEE DETAILS AND SPECIFICATIONS.

22. DUST BARRIERS MUST BE INSTALLED WHEREVER NEW WORK IS ADJACENT TO OCCUPIED AREAS. BARRIERS MUST BE SEALED TO INSURE NO DUST TRANSMISSION TO OCCUPIED SPACES.

23. CONTRACTOR TO VERIFY ALL EQUIPMENT SIZES AND ROUGH-IN NEEDS AND ADJUST TO EXISTING CONDITIONS PRIOR TO BEGINNING WORK.

24. SEE MECHANICAL & ELECTRICAL FOR ADDITIONAL PLACEMENT OF SLEEVES & HANGERS REQUIRED BY WORK.

25. ALL MECHANICAL AND ELECTRICAL LINES TO BE INSTALLED TIGHT TO STRUCTURE WHERE POSSIBLE.

26. HEATING, PLUMBING AND ELECTRICAL PLANS WHERE SHOWN DIAGRAMMATICALLY ARE INTENDED TO INDICATE CAPACITY, SIZE AND LOCATION AND GENERAL ARRANGEMENTS. ALL NECESSARY FEATURES OF RELATED CONSTRUCTION WILL BE REQUIRED AS IF SHOWN IN DETAIL.

27. WHERE MECHANICAL AND ELECTRICAL EQUIPMENT LOCATIONS CONFLICT ELECTRICAL, LIGHT FIXTURE LOCATIONS SHALL TAKE PRECEDENCE.

28. WHERE PLUMBING OCCURS IN STUD WALL WITH HORIZONTAL OR VERTICAL PIPING, STUDS SHALL BE CONSTRUCTED DEEP ENOUGH TO ACCOMMODATE PIPING. SAME FOR ALL ELECTRICAL PANELS.

29. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL NEW MATERIALS (U.N.O.) AND QUALIFIED CRAFT PERSONS TO COMPLETE THE WORK.

30. CONSTRUCTION DOCUMENTS SHOW THE DESIGN INTENT OF THE PROJECT AND MAY NOT SHOW MINOR DETAILS OF PROPOSED INSTALLATIONS. THE INCLUSION OF THESE MINOR DETAILS IS IMPLIED TO PROVIDE A COMPLETE PROJECT AND ARE TO BE INCLUDED AS A PART OF A BID.

31. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT EXISTING CONDITIONS PRIOR TO PROCEEDING WITH EACH INSTALLATION OR PART OF THE WORK. DISCREPANCIES MUST BE REPORTED TO THE ARCHITECT PRIOR TO PROCEEDING.

32. THE GENERAL CONTRACTOR IS TO COORDINATE THE INSTALLATION OF MATERIALS AND WORK OF OTHERS WHO ARE NOT SUB-CONTRACTORS TO THE G.C., YET ARE REQUIRED TO PROVIDE A COMPLETED PROJECT. AREAS OF WORK REQUIRING COORDINATION INCLUDE BUT ARE NOT LIMITED TO THOSE INDICATED AS N.I.C. ON THE CONSTRUCTION DOCUMENTS.

33. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR COORDINATION OF WORK.34. IN THE CASE OF CONTRADICTIONS BETWEEN DRAWINGS OR BETWEEN DRAWINGS AND

SPECIFICATIONS, ASSUME THE MORE COSTLY APPROACH FOR BIDDING PURPOSES. BRING ALL CONTRADICTIONS TO THE ATTENTION OF THE ARCHITECT.

35. THE CONSTRUCTION DOCUMENTS CONSIST OF THE CONSTRUCTION DRAWINGS AND SPECIFICATIONS INCLUSIVELY. SOME ITEMS MAY BE SHOWN ONLY ON THE DRAWINGS, OR INDICATED ONLY IN THE SPECIFICATIONS. FOR EXAMPLE, THE SPECIFICATIONS MAY SAY TO PAINT ALL EXPOSED STRUCTURAL STEEL, BUT THIS MAY NOT BE CALLED OUT ON ALL OF THE DRAWINGS.

36. ALL WORK SHALL COMPLY WITH STATE AND LOCAL CODES. CONTRACTOR SHALL INSURE FULL COMPLIANCE WITH FLAME SPREAD REQUIREMENTS.

37. CONTRACTOR SHALL PROMPTLY REMOVE ALL WASTE MATERIALS AND LEAVE PREMISES AND SITE CLEAN.

38. THE CONTRACTOR SHALL PROVIDE ALL CEILING AND/OR WALL ACCESS PANELS/DOORS AS REQUIRED BY THE AIR CONDITIONING, PLUMBING & ELECTRICAL SYSTEMS, PROVIDE APPROVED ASSEMBLIES W/ SELF-CLOSING DEVICES IN RATED CONSTRUCTION. (PAINT TO MATCH ADJACENT WALL COLOR)

39. ALL PENETRATIONS OF FIRE RESISTIVE CONSTRUCTION SHALL BE PROTECTED WITH APPROVED FIRE ASSEMBLIES.

40. ELECTRICAL OUTLETS AND LIGHTING ARE ONLY SHOWN SPORATICALLY ON ARCHITECTURAL "A" SHEETS WHERE PLACEMENT OF SUCH IS CRITICAL TO PARTICULAR AESTHSTICS. ELECTRICAL INDICATIONS ON "A" SHEETS ARE NOT MEANT TO BE COMPLETE OR EXAUSTIVE. SEE ELECTRICAL DRAWINGS FOR ALL ELECTRICAL AND DATA FEATURES.

DRAWING SET NOTE: THESE DRAWINGS ARE TO BE UTILIZED AS A COMPLETE SET FOR BIDDING AND CONSTRUCTION. INDIVIDUAL SECTIONS OF DRAWINGS SHOULD NOT BE SEPARATED FROM THE ENTIRE SET. IMPORTANT NOTES FOR ONE AREA OF WORK MAY BE INCLUDED IN OTHER AREAS IN THE DRAWINGS. ALL CONTRACTORS AND SUPPLIERS MUST REVIEW ENTIRE DRAWING SET AND SPECIFICATIONS.

GENERAL NOTES:

1. THE GENERAL CONDITIONS TO THE CONTRACT FOR THE CONSTRUCTION OF BUILDINGS: THE MONTANA STATE UNIVERSITY GENERAL CONDITIONS TO THE CONTRACT FOR CONSTRUCTION, HEREINAFTER REFERRED TO AS THE GENERAL CONDITIONS, IS HEREBY MADE A PART OF THE ARCHITECTURAL SPECIFICATIONS.

2. CONTRACT DOCUMENTS INCLUDE THE ARCHITECT'S DRAWINGS, SPECIFICATIONS, GENERAL CONDITIONS, AGREEMENT (BUILDING CONTRACT) AND ALL ADDENDA. THEY ARE TO INCLUDE ALL LABOR, EQUIPMENT, AND MATERIALS NECESSARY FOR THE PROPER EXECUTION OF THE WORK EXCEPT AS MAY BE SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS OR FOR WHICH SEPARATE PRICES MAY BE ASKED IN THE BID PROPOSAL.

3. REGULATIONS, TAXES AND PERMITS: THE WHOLE OF THE WORK IS TO BE EXECUTED IN STRICT ACCORDANCE WITH THE REGULATIONS AND CODES OF THE GOVERNMENTAL AGENCIES WHOSE JURISDICTION IS APPLICABLE.

GENERAL CONDITIONS:

@ atA.B. anchor boltAC asphaltic concreteA/C air conditioningACC PNL access panelACOUST acousticalACT acoustical ceiling tileAD area drainADJ adjacentA.F.F. above finished floorA.I.B. air infiltration barrierALT alternateALUM aluminumANOD anodizedAPPROX approximateAPPRD approvedARCH architectAUTO automaticBBD bulletin boardBD boardBITUM bituminuousBL building lineBLDG buildingBLK blockBLKG blockingBLDG buildingBLKG blockingBM beam/bench markBO by ownerB.O. bottom ofBOT bottomBRK brickBRG bearingB/S building standardBSBD baseboardBTW betweenBTM/BOTT bottomBTWN betweenB.O.W. bottom of wallBU built upCAB cabinetCAP capacityCB catch basinCBD chalk boardCB-ICF cement based insulated concrete formCD ceiling diffuserC.F. cement fiber (siding and trim)/cubic feetCL centerlineC.B. catch basinC.C. center to centerCDX exterior grade plywoodC.T. ceramic tileCG ceiling grill/corner guardCH channelCI cast iron/cubic incheseCJ control jointCLG ceilingC.L.L. contract limit lineCL center lineCLO closetCLR clearCMU concrete masonry unitCMNT cementCMT ceramic mosaic tileCO clean outCOL/COLS column/columnsCONC concreteCOND conditionCONF conferenceCONN connectionCONST constructionCTRD centeredCONT continuousCONTR contractorCORR corridorCPT carpetCR ceiling registerCT ceramic tileCTR counterCUH cabinet unit heaterCW cold waterCY cubic yardDBL doubleDEPT departmentDF drinking fountainDIA diameterDIAG diagonalDIM dimensionDISP dispenserDL dead loadDN downDP demountable partitionDR doorDWR drawerDS downspoutDTL/DET detailDWG drawingE eastEA eachEIFS exterior insulation finish systemE.J. expansion jointEL/ELEV elevation - height/elevatorELEC electricalENCL enclosureEO electrical outletEP electrical panelEQ equalEQUIP equipmentEWC electrical water coolerEWH electrical water heater(E)/EXIST existingEWC electrical water coolerEWH electrical water heaterEXH exhaustEXP expansionEXT exteriorEWA/EW exterior wall assemblyFA fire alarm/floor-ceiling assemblyFABR fabricateFAH fire alarm hornFAS fire alarm stationFBR face brickFD floor drainFDN/FDTN foundationFFHB frost free hose bibFG finish gradeFH fire hydrantFIN. FLOOR top of floor sheathingFIN finishFIO furnished and installed by ownerFIX/FXTR fixtureF.O. face ofFDN foundationFEC fire extinguisher cabinetFF finished floorFLR/FL floorFLUOR fluorescentFND feminine napkin dispenser/disposalFOC face of concreteFOIC furnished by owner and installed byFOS face of studFOW face of wallFT foot or feetFTG footingFTIC furnished by tenant & installed by

contractorFE fire extinguisherGA gaugeGB grab barGAF brand name roofing productGALV galvanized G.C. general contractorGEN generalGI galvanized ironGL glassGLU LAM or G.L.B. glue laminated beamGRD grade/gridGS galvanized steelGWB gypsum wall boardGYP gypsumHB hose bibHC hollow core/handicappedHD BD Hard boardHDR headerHOR horizontalHP high pointHR hourHT heightHTG heatingHVAC heating, ventilation, air conditioningHW hot water

IN inchINCL includedINFO informationINSUL insulationINT interiorIWA/IW interior wall assemblyJAN janitorJST joistJT jointLAV lavatoryLF lineal footLTG lightingLVR louverM men'sMNFR/MANUF. manufacturerMAT materialMAX maximumMECH mechanicalMC medicine closetMDF medium density fiber boardMEMB membraneMEZZ mezzanineMH man holeMIN minimumMIRR mirrorMISC miscellaneousMO masonry openingMTL metalMULL mullionN northNA not applicableNAT naturalNIC not in contractNO numberNTS not to scaleOA over allO.C. on centerOD outside diameterOH overhead/opposite handOPNG openingOPP oppositePART.BD. particle boardPART’N/PART partitionPC precast concretePL platePLAM plastic laminatePLAST plasticPLWD plywoodPND paper napkin dispenserPNL panelPR pairPSL parallel strand lumberPT pointPTD paper towel dispenserPTD/R paper towel dispenser/receptaclePVMT pavementP.V.C. polyvinylchlorideQTY quantityR/RAD radiusR riserRA roof/ceiling assemblyRB rubber baseRD roof drainRDWD redwoodRE regardingREC recessedREF referenceREFR refrigeratorREINF reinforcingREQD/REQ requiredRES resilientRM roomRO rough openingRV roof ventR&S rod and shelfS southSACT suspended acoustical ceiling tileSAT suspended acoustical tile ceilingSC solid coreSCD seat cover dispenserSCHED scheduleSD soap dispenserSECT sectionSF square feetS.G. supply grillSGL safety glassSHLVS shelvesSHLVNG shelvingSHT sheetSHTG sheathingSHWR showerSIM similarSIM. similarS.I.P. structural insulated panelSLNT sealantSM surface mountedSOG slab on gradeS.STL./SS stainless steelS&P shelf and poleSPEC specificationsSS service sinkSTD standardSTL steelSTOR storageSTRUCT/STRUC structuralSUBFLR subfloorSUSP suspendedS&V stain and varnishSV sheet vinylSY square yardT tread/thermostatTB towel barTEL telephoneTEMP temperatureT&G tongue and grooveT.ALUM. tubular aluminumT.B. test boreTHK thickTHRU throughT.J.I./TJI Truss Joist IncorporatedT.O. top ofT.O.B. top of beamTOC top of concreteT.O.P. top of plateT.O. FTG top of footingT.O.S. top of steelT.O. SL. top of slabT.O.W. top of wallTP toilet paper holderTPD toilet paper dispenserTPG toppingTR/TRD treadT.S. tubular steelTV televisionTYP typicalUBC uniform building codeUG undergroundUH unit heaterUNO unless noted otherwiseUR urinalUV unit ventilatorVAC vacuum outletVAR variesVB vapor barrierVCT vinyl composition tileVEN veneerVERT verticalVEST vestibuleVG vertical grainVIN vinylVP veneer plasticVT vinyl tileVWC vinyl wall coveringW west/women/widthW/ withW/O with outWB wood baseWC water closetWD woodW/D washer/dryerWGW windowWGL wire glassWH water heaterWM wire meshWNDW/WDW windowWP waterproofWR water resistantWS weatherstripWSCT wainscotWT weightWWF welded wire fabricWWM welded wire meshX byYH yard hydrantYD yard

ABBREVIATIONS: REFERENCE SYMBOLS:

SCALE

SECTIONS / WALL SECTIONS

INTERIOR ELEVATIONS

DETAIL CALLOUT

ROOM NAME, NUMBER, AND AREA

GRID LINES:NUMBERS LEFT TO RIGHTLETTERS TOP TO BOTTOM

ELEVATION TAG,TYP. MAIN FLOOR = 100' - 0"

DRAWING TITLE

FIRE EXTINGUISHER, SEE CODE PLANS

SHEET NUMBER

DRAWING NUMBER

SHEET NUMBER

SHEET NUMBER

DRAWING NUMBER FE

FE

WITH CABINET

WALL-HUNG, NO CABINET

A1-0113

View Name1/8" = 1'-0"23

1

A101 SIM

A101

1

SIM

Room name

150 SF101

##

##

NameElevation1

A101 SIM

Room name

101150 SF

SUMMARY CODE REVIEW SEE CODE PLAN, THIS SHEET

OCCUPANCY CLASSIFICATION: BUSINESS GROUP BEDUCATIONAL OCCUPANCIES FOR STUDENTS ABOVE 12TH GRADE

TYPE OF CONSTRUCTION: 3B

SPRINKLER SYSTEM: NONE EXISTING NONE PROPOSED

PROPOSED SIZE:MAINTAINS EXISTING SIZE 1058 SQ FT

OCCUPANT LOADS:BUILDING SPACES:THIS PROJECT IS NOT CHANGING BUILDING AREA OR OCCUPANCY TYPE. THEREFORE IS NOT INCREASING OCCUPANT LOAD

BUILDING SUMMARY

THIS PROJECT SHALL COMPLY WITH THE LATEST EDITION OF CODES ADOPTED BY THE STATE OF MONTANA AND THE CITY OF BOZEMAN:

2012 International Building Code (IBC)2012 International Mechanical Code (IMC)2012 International Fuel Gas Code (IFGC)2012 Uniform Plumbing Code (IAMPO)2014 National Electrical Code (NEC)2012 International Fire Code (IFC)2012 International Energy Conservation Code (IECC)

APPLICABLE BUILDING CODES

Project Description:CLASSROOM REMODEL AT THE MONTANA STATE UNIVERISTY

EXITING, Main Floor:THIS IS AN INTERIOR REMODELING PROJECT WITH NO CHANGE ON EXISTING EXITING.

A B C

2

1

1057 SF

CHEEVER

214

72

0 S

. Tr

acy

Ave

., B

ozem

an, M

T

dRA-

Arc

hite

ct.c

om

dRA

den

nis

Raf

fens

perg

erArc

hite

ct

REV. DESCRIPTION DATE

REVIEWED BY:DRAWN BY:

SHEET

DATE

SHEET TITLE

MO

NT

AN

AST

AT

E U

NIV

ER

SIT

Y

MSU-CPDCMONTANA STATE UNIVERSITY

BOZEMAN, MONTANAPHONE: 406.994.5413

FAX: 406.994.5665

Consultant #:1710

CL

ASS

RO

OM

RE

NO

VA

TIO

NS

2018

CH

EEVE

R H

ALL

21

4 1

00

% C

ON

STR

UC

TIO

N D

RA

WIN

GS

AuthorChecker

GENERAL & CODEINFORMATION

A00103/19/2018

PR

OJE

CT

#4

PPA#18-2015

1 1/2" = 1'-0"SUMMARY CODE REVIEW21/4" = 1'-0"

CHEEVER CODE PLAN3

0' 2' 4' 8' 16'

Page 3: J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

J

SS

SS

S

WAP

S

A B C

2

1

DEMOLISHED

EXISTING WALL TO REMAIN

DEMO LEGEND

1.

2.

3.

4.

5.

6.

2.

6.

7.

7.

8.

8.

8.

9.

ACT-18'-11"

A. PATCH AND PREP ALL WALLS FOR PAINT UNLESS OTHERWISE INDICATED.B. VERIFY ALL CONDITIONS AND COORDINATE WITH ALL DISCIPLINES OF CONTRACT.

UNDOCUMENTED FIELD CHANGES MAY HAVE OCCURRED AND ARE TO BE BROUGHT TO THE ATTENTION OF THE ARCHITECT WHEN DISCOVERED.

C. WHERE DEMOLITION IS INDICATED, WALLS SHALL BE REMOVED AND CEILING SHALL BE PATCHED, REPAIRED AND PAINTED TO MATCH EXISTING.

D. UNLESS DEMOLITION IS INDICATED, PATCH AND PROTECT EXISTING CEILING.E. COORDINATE ALL MECHANICAL, ELECTRICAL, FIRE SYSTEMS, COMMUNICATIONS AND UTILITY

SHUT-DOWNS WITH OWNER PRIOR TO REMOVING AND OR RELOCATING, PER MSU REQUIREMENTS.

F. ALL DEMOLITION DRAWINGS ARE INTENDED TO SHOW GENERAL SCOPE OF WORK WITHIN THE INTENT OF THE PROJECT AND ARE NOT INTENDED TO EXCLUDE ANY DEMOLITION WORK NECESSARY FOR PRIOR COMPLETION OF THE WORK OUTLINED IN THE PROJECT DOCUMENTS. CONTRACTOR SHOULD ASSUME ADDITIONAL MINOR DEMOLITION ITEMS NOT SHOWN ON PLANS, NO ADDITIONAL PAYMENT WILL BE MADE FOR SUCH MINOR ELEMENTS.

G. THESE DRAWINGS INDICATE STRUCTURAL AND NON-STRUCTURAL DEMOLITION THAT IS TO OCCUR TO MAKE WAY FOR NEW CONSTRUCTION. ADDITIONAL STRUCTURAL DEMOLITION WORK, CONSTRUCTION OR SHORING REQUIRING COORDINATION WITH NEW STRUCTURAL INS INDICATED ON THE STRUCTURAL DRAWINGS.

H. SEE MECH. AND ELEC. DEMOLITION PLANS FOR SPECIFIC DEMO OF MECHANICAL AND ELECTRICAL SYSTEMS.

I. SEE HAZARDOUS MATERIALS ABATEMENT REPORT FOR ADDITIONAL INFORMATION AND COORDINATION.

GENERAL DEMOLITION NOTES:

72

0 S

. Tr

acy

Ave

., B

ozem

an, M

T

dRA-

Arc

hite

ct.c

om

dRA

den

nis

Raf

fens

perg

erArc

hite

ct

REV. DESCRIPTION DATE

REVIEWED BY:DRAWN BY:

SHEET

DATE

SHEET TITLE

MO

NT

AN

AST

AT

E U

NIV

ER

SIT

Y

MSU-CPDCMONTANA STATE UNIVERSITY

BOZEMAN, MONTANAPHONE: 406.994.5413

FAX: 406.994.5665

Consultant #:1710

CL

ASS

RO

OM

RE

NO

VA

TIO

NS

2018

CH

EEVE

R H

ALL

21

4 1

00

% C

ON

STR

UC

TIO

N D

RA

WIN

GS

MOSAICDRA

DEMO PLANS

A10003/19/2018

PR

OJE

CT

#4

PPA#18-2015

1/4" = 1'-0"CHEEVER DEMO PLAN1 1/4" = 1'-0"

CHEEVER DEMO RCP2

DEMOLITION NOTES1. REMOVE WHITEBOARDS. SALVAGE ANY WHITEBOARDS IN GOOD CONDITION AFTER REMOVAL; SEE HAZARDOUS

MATERIALS REPORT

2. PROTECT BRICK WALLS

3. KEEP AND PROTECT PIN-UP BOARDS

4. REMOVE CARPET AND BASE

5. KEEP AND PROTECT WINDOW SHADE

6. KEEP AND PROTECT ALL FLOOR VENTS

7. REMOVE DOOR HARDWARE. PREP FOR NEW ADA DOOR HARDWARE

8. PATCH AND PREP WALL FOR PAINT; PATCH AND PREP WALL ABOVE EXST CEILING FOR PAINT - SEE RCP

9. REMOVE ACOUSTIC CEILING TILES AND GRID. PATCH WALLS AFFECTED BY CEILING REMOVAL.

Page 4: J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

A B C

2

1

A200 1

A2003

A2002

A2004

4'-3 1/4"

P5

IN-CARPET TRACK FOR UMBILICAL. LOCATION TO BE FIELD VERIFIED

8"

A101

3

PODIUM NIC. FOR REFERENCE ONLY

REMOVE AND KEEP PINUP BOARDS TO PAINT BEHIND. INSTALL AFTER PAINTING IN ORGINAL LOCATION

21'-7

"

ALIGN EDGE OF 3 5/8" MTL STUD WALL WITH EDGE OF COLUMN

5

A101Sim

A200

8

Sim

5

A200Sim A B C

2

1

21'-7

"ACT-110'-0"

16'-9 3/4"PROJECTOR INSTALL:PROJECTOR NIC. GC TO RELOCATE EXST PROJECTOR POLE & MOUNT. GC TO INSTALL APPROPRIATE BACKING/SUPPORT. FINAL LOCATION TO BE FIELD VERIFIED.

PROJECTION SCREEN INSTALL:GC TO PURCHASE AND INSTALL SCREEN AND APPROPRIATE MOUNTING HARDWARE. GC TO INSTALL APPROPRIATE BACKING/SUPPORT. FINAL LOCATION TO BE FIELD VERIFIED.

GYP11'-2"

GYP11'-2"

7

A500Sim

EDGE OF SOFFIT ALIGN WITH FACE OF BRICK WALL

3'-3 1/2"

EDGE OF SOFFIT ALIGN WITH FACE OF BRICK WALL

NEW CEILING HEIGHT

7

A500Sim

ROOM FINISH LEGENDFLOOR FINISHES:

BASE FINISHES:

PAINTED GWB: PAINT COLOR OVER GYPSUM BOARD - TYP. U.N.O. COLOR AS INDICATED.

PAINT COLOR SELECTIONS:P1- OFF WHITE. SHERWIN WILLIAMS "CREAMY" SW-7012. LRV 83P5- ACCENT COLOR: DARK BLUE. "LOYAL BLUE" SW-6510. LRV 5

WALL FINISHES:

CARPET-CP1

FLOOR FINISH NOTES:1. IF FINISHES ARE NOT CLEARLY INDICATED FOR AN AREA, CLARIFY INTENT WITH

ARCHITECT.2. PROVIDE APPROPRIATE TRANSITION TRIM AT ALL MATERIAL CHANGES.3. TEST ALL SUBSTRATES TO VERIFY COMPLIANCE WITH FINISH MANUFACTURE'S

SPECIFICATIONS PRIOR TO FLOORING INSTALLATION.4. PATCH, REPAIR, AND/OR GRIND ALL SUBSTRATES TO ACCEPTABLE LEVEL OF

SMOOTHNESS/LEVELNESS PRIOR TO FLOORING INSTALLATION.5. FLOORING CHANGES FROM ROOM TO ROOM TO OCCUR DIRECTLY UNDER THE DOOR

LOCATION.6. SAMPLES FOR ALL FINISHES MUST BE SUBMITTED TO AND APPROVED BY ARCHITECT

PRIOR TO ORDERING.

SEE ROOM FINISH SCHEDULE FOR LISTING OF MATERIALS .

WALL FINISH NOTES:1. SEE INTERIOR ELEVATIONS FOR INTERIOR WINDOWS, SPECIAL WALL FINISHES, TRIM, ETC.2. IF FINISHES ARE NOT CLEARLY INDICATED FOR AN AREA, CLARIFY INTENT WITH ARCHITECT.3. PROVIDE APPROPRIATE TRANSITION TRIM AT ALL MATERIAL CHANGES.4. PROVIDE CLEAN, CONSISTENT CAULK JOINTS AT ABUTMENTS OF DISSIMILAR MATERIALS.5. PROVIDE METAL EDGING AT ALL GYPSUM BOARD EDGES THAT ABUT DISSIMILAR

MATERIALS.

CEILING FINISHES:

CEILING LAYOUT NOTES: LAY-IN CEILINGS ARE SHOWN CONCEPTUALLY. IT IS THE INTENT THE CEILINGS AREA CENTERED WITHIN THE ROOM. IN ODD SHAPED ROOMS, PRIMARY VISUAL AREA TO BE CENTERED. CEILNG INSTALLER SHOULD CONSULT WITH THE ARCHITECT IN THE FIELD FOR ANY AREAS IN WHICH THEY WOULD LIKE TO MODIFY THE LAYOUT FROM THAT SHOWN ON THE PLAN. MODIFICATIONS MAY BE ALLOWED, AT THE DISCRETION OF THE ARCHITECT, TO EASE INSTALLATION, SAVE CUTTING, OR INCREASE VISUAL APPEAL.

ACT-1 ACOUSTICAL TILE: ACT CEILING. BOTTOM OF NEW ACT CEILING TO BE LOCATED @ TOP OF WINDOW SILL (FIELD VERIFY FINAL ACT-1 HEIGHT).

CEILING TILE FINISH: 24"X48" ACOUSTIC TILES WITH FINE FISSURE FINISH IN WHITE COLOR, SEE SPEC

GYP GYP CEILING: PREP FOR PAINT: PAINT COLOR - P1

CHAIR RAIL: CORIAN SOLID SURFACE - TYP. U.N.O. COLOR AS INDICATED.

CORIAN COLOR SELECTIONS:CR4 - COBALT

CHAIR RAIL NOTES:1. FIELD LAYOUT ALL CHAIR RAIL LENGTHS2. CHAIR RAIL TO WRAP COLUMNS AS SHOWN IN INTERIOR ELEVATIONS.

CARPET TILE- CP1: 25CM X 1 M CARPET TILE. INSTALLATION METHOD: ASHLAR; VARY LOCATION OF ACCENT COLOR TO GET RANDOM PATTERN EFFECT

CARPET COLOR: BROWN MARBLE WITH BLUE & YELLOW LINEAR ACCENT COLORS

RUBBER BASE: BLACK BROWN COLOR, 3.2 MM THICK, 4" HIGH

TRANSITION STRIP: SOLID VINYL REDUCER STRIP; GRAPHITE GRAY COLOR.

EXISTING CONCRETE COLUMN

5/8" TYPE X GWB

3 5/8" MTL STUD FRAMING

3 5/8" MTL STUD FRAMING

ATTACH GWB TO COLUMN

DRYWALL J MOLDING

5/8" TYPE X GWB PAINTED

ATTACH TO EXST WALL W/ 3 5/8" MTL STUD FRAMING

3 5/8" MTL STUD FRAMING

6"

EXST WALL

ACOUSTIC CEILING

DRYWALL J MOLDING

5/8" TYPE X GWB PAINTED

4" RUBBER BASE

CARPET

EXST FLOOR

3 5/8" MTL STUD FRAMING

ATTACH FRAMING TO EXST FLOOR

ADHESIVE

72

0 S

. Tr

acy

Ave

., B

ozem

an, M

T

dRA-

Arc

hite

ct.c

om

dRA

den

nis

Raf

fens

perg

erArc

hite

ct

REV. DESCRIPTION DATE

REVIEWED BY:DRAWN BY:

SHEET

DATE

SHEET TITLE

MO

NT

AN

AST

AT

E U

NIV

ER

SIT

Y

MSU-CPDCMONTANA STATE UNIVERSITY

BOZEMAN, MONTANAPHONE: 406.994.5413

FAX: 406.994.5665

Consultant #:1710

CL

ASS

RO

OM

RE

NO

VA

TIO

NS

2018

CH

EEVE

R H

ALL

21

4 1

00

% C

ON

STR

UC

TIO

N D

RA

WIN

GS

AuthorChecker

FLOOR PLAN,REFLECTED CEILING

PLAN & DETAILS

A10103/19/2018

PR

OJE

CT

#4

PPA#18-2015

1/4" = 1'-0"CHEEVER PLAN1 1/4" = 1'-0"

CHEEVER RCP2

1 1/2" = 1'-0" REF: 1/ A101

PLAN DETAIL @ NEW WALL3

1 1/2" = 1'-0" REF: 1/ A101

WALL SECTION DETAIL5

Page 5: J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

P1

EXST. BRICK

P1

EXST. BRICK

P1

WB5

3'-0

"

1'-1"

RUBBER BASE

PROJECTION SCREEN INSTALL:FINAL LOCATION TO BE FIELD VERIFIED.VERIFY WALL TYPE AND PROVIDE APPROPRIATE ANCHOR FOR MOUNTING.

12'-3"

NEW ADA DOOR HARDWARE @ EACH DOOR. SEE SPEC

RAISED CEILING BEYOND

VERTICAL WIREMOLD

P1

P1

4" 4"

P1

CR43'

-0"

WB2

10"

8'-6"

RUBBER BASE

CR4

PROTECT EXST SHADE

P5P1P1 EXST. PIN-UP BOARD

P1

3'-0

"

RUBBER BASE RUBBER BASEP1

10"

CR4

(KEEP AND PROTECT PIN-UP BOARDS)

P1

3'-0

"

WB4

P1

10"

4'-10"

CR4

RUBBER BASE

3'-9"

10"

3/4" SOLID SURFACE MATERIAL W/ 45 DEGREE MITER JOINT @ TOP CORNER

3/4" PLYWD. CLEAT, GLUED TO SOLID SURF. MTL

SET CLEAT IN CONST. ADHESIVE

EXST WALL

CONTIN. SEALANT JT., COLOR MATCH TO SOLID SURF. MTL.

3/4" PLYWD. CLEAT SCREWED TO WALL

LEGRAND STEEL WIREMOLD V700 SERIES, OR EQ.

HUBBELL HBL5715BR TEE FITTING BEND RADIUS, OR EQ.

HUBBELL HBL5748 STANDARD I-GANG BOX, OR EQ., W/DUAL OUTLET1" TACK STRIP

8'-0"

4'-0

"

WB1

MARKER TRAY

1" TACK STRIP

10'-0"

4'-0

"

WB2

MARKER TRAY

1" TACK STRIP

12'-0"

4'-0

"

WB3

MARKER TRAY

1" TACK STRIP

16'-0"

4'-0

"

WB4

MARKER TRAY

1" TACK STRIP

20'-0"

4'-0

"

WB5

MARKER TRAY

NOTE: MOUNTING HEIGHT - BOTTOM OF WHITEBOARD IS TO BE 3' AFFWHITE BOARD TYPESSEE PLAN AND ELEVATIONS FOR LOCATIONS

10"

3/4" SOLID SURFACE MATERIAL W/ 45 DEGREE MITER JOINT @ TOP CORNER

SET CLEAT IN CONST. ADHESIVE

EXST WALL

CONTIN. SEALANT JT., COLOR MATCH TO SOLID SURF. MTL.

3/4" PLYWD. CLEAT SCREWED TO WALL

LEGRAND STEEL WIREMOLD 3000 SERIES, OR EQ., CONTIN.

3/4" PLYWD. CLEAT, GLUED TO SOLID SURF. MTL

SOLID SURFACE MTL

MITER CORNER, CONT SOLID SURFACE TO WALL FACE. TYP. @ ALL ENDS OF CHAIR RAIL

CHAIR RAIL DISTANCE TO VERTICAL WIREMOLD, SEE ELEVATION DWG

72

0 S

. Tr

acy

Ave

., B

ozem

an, M

T

dRA-

Arc

hite

ct.c

om

dRA

den

nis

Raf

fens

perg

erArc

hite

ct

REV. DESCRIPTION DATE

REVIEWED BY:DRAWN BY:

SHEET

DATE

SHEET TITLE

MO

NT

AN

AST

AT

E U

NIV

ER

SIT

Y

MSU-CPDCMONTANA STATE UNIVERSITY

BOZEMAN, MONTANAPHONE: 406.994.5413

FAX: 406.994.5665

Consultant #:1710

CL

ASS

RO

OM

RE

NO

VA

TIO

NS

2018

CH

EEVE

R H

ALL

21

4 1

00

% C

ON

STR

UC

TIO

N D

RA

WIN

GS

AuthorChecker

ELEVATIONS

A20003/19/2018

PR

OJE

CT

#4

PPA#18-2015

3/8" = 1'-0" REF: 1/ A101

Elevation CHEEVER EAST1

3/8" = 1'-0" REF: 1/ A101

Elevation CHEEVER NORTH3

3/8" = 1'-0" REF: 1/ A101

Elevation CHEEVER WEST ELEVATION2

3/8" = 1'-0" REF: 1/ A101

Elevation CHEEVER SOUTH4

1" = 1'-0" REF: 1/ A101

CHAIR RAIL DETAIL5 1" = 1'-0"RACEWAY ALTERNATE CHAIR RAIL DETAIL7

1" = 1'-0" REF: 1/ A101

PLAN DETAIL @ CHAIR RAIL END8

Page 6: J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

8" MAX OR NOTE (1)

1/2"

8" MAX OR NOTE (1)

NOTE (2)

MAIN RUNNER OR CROSS "T"

MIN. 3 TIGHTTURNS IN 1 1/2"

WALL ANGLE- ATTACH AT EACH STUD W/ 1-1/4" LONG S-12 PANCAKE HEAD SCREW, PROVIDE BLKG WHERE CLG. DOESN'T TERMINATE ON A STUD

FREE ENDFIXED END

NOTE:1. 1/4 OF THE LENGTH OF THE END RUNNER, WHICHEVER IS LEAST

2. PROVIDE SPACER @ FREE END WHERE THE FIRST RUNNER IS 12" OR MORE FROM WALL.

ACOUSTICAL PANEL1/8" POP RIVETAT EACH MEMBER

MIN (3) TIGHT TURNS IN 1-1/2" (TYP)

MAIN RUNNER OR CROSS "T"

HANGER WIRE

ACOUSTICAL PANEL

TO FIRSTBRACING

8" M

AX

4'-0

" MAX

TO

FIRS

T BR

ACIN

G

8" MAX

2'-0

"2'

-0"

2'-0

"2'

-0"

2'-0

"2'

-0"

4'-0"4'-0"6'-0"MAX. 4'-0" 4'-0"

FIRST BRACING POINT FROM WALL

4 WAY-45° DIAGONAL W/ VERTICAL STRUT 12 GAWIRE BRACING @ 8'-0"x12'-0" (10 GA. IF CLG. ISSUPPORTING PARTITIONS)

CROSS T BAR

MAIN T BAR

WALL LINE

WALL LINE

12 GA. VERTICAL HANGERWIRES @ 4'-0" O.C. EACH WAY

1

A500

2

A500

A500

8

10'-0" MAX.

1-1/2" 16 GA U-CHANNEL BRIDGING @ MIDSPAN

5/8" GYPSUM BOARD SCREWED TO JOIST BOTTOM FLANGE 1/4" MIN. PENETRATION

3-5/8" 20 GA JOISTS @ 24" MAX OC

12'-0" O.C.

4'-0"

45° MAX.

6'-0"MAX

2"MAX

2"2"4'-0"

PROVIDE (2) SLACK WIRES TO EA. FIXTURE. PROVIDE POSITIVE CLIP FROM FIXTURE TO MAIN RUNNERS. FIXTURE WEIGHT NOT TO EXCEED 56 LBS.

LATERAL BRACING SYSTEM @ 12'-0" O.C. EA WAY. BEGIN BRACING WITHIN 6'-0" OF PERIMETER & 2" FROM CROSS MEMBER. BRACING SYSTEM INCLUDES COMPRESSION STRUT W/ (1) HANGER WIRE THRU CTR & (4) HANGER WIRES SPLAYED IN (4) DIRECTIONS @ 45° MAX. CROSS RUNNERS FIT BETWEEN MAIN

RUNNERS

MAIN RUNNERS W/ #12WIRES TO STRUCT @ 4'-0" O.C.

MAIN RUNNERS W/ #12WIRES TO STRUCT @ 4'-0" O.C.

3/4" SEISMIC JOINT @ PERIMETER WALLS

ADDITIONAL HANGERS ALL MEMBERS W/ IN 8" OF PERIMETER

COUNTERSLOPE HANGERS IF MORE THAN 1:6 OUT OF PLUMB

TRAPEZE HANGER WIRES @ DUCTWORK & OTHER LG. OBSTRUCTIONS

BLDG STRUCT

PERIMETER CLOSURE ANGLE 2" MIN WIDTH

6" M

IN.

CEILING TILE AND TRACK OR OTHER CEILING TYPE, HT. PER RCP

GYP. BD CONTINUOUS AT B.O. STRUCTURE WHERE APPLICABLE.

GYP. BD CONTINUOUS TO STUCTURE ABOVE WHERE INDICATED IN ACOUSTIC LAYOUT PLAN

PER RCP

PER RCP

ALIGN W/FACE OF WALL BEYOND WHERE OCCURS

CORNER BEAD

5/8" GYP BD ON 3 5/8" STL STUD FRAMING

ACOUSTIC PANEL PER RCP

GYP. BD CONTINUOUS AT B.O. STRUCTURE WHERE APPLICABLE.

GYP. BD CONTINUOUS TO STUCTURE ABOVE WHERE INDICATED IN ACOUSTIC LAYOUT PLAN

PER RCP

PER RCP

CORNER BEAD

5/8" TYPE X GYP BD ON 3 5/8" STL STUD FRAMING

2"MAX

ROOF FRAMING ORBLOCKING AS REQUIRED

VERTICAL COMPRESSION STRUT DESIGNED FOR 200 LBS. COMPRESSION FORCE. ATTACH TOP & BOT. W/ ONE 1/4" Ø BOLT

CROSS TEES (FOR ACOUST TILES) OR 7/8"-26 GA FURRING HAT CHANNELS @ 2'-0" O.C. (FOR GYP. BRD.)

EYEBOLT SCREWED TO ROOF FRAMING OR BLOCKING ABOVE, TYP.

MAIN RUNNER TEES (FOR ACOUSTICAL TILES) OR 1-1/2" HOT ROLLED MAIN RUNNER CHANNELS @ 3'-0" O.C. (FOR GYP. BRD.)

#12 GA. VERTICAL HANGING WIRE 4'-0" O.C.

45° MIN.TYP. FOR 4

NOTE:

1. FOR LOCATION OF BRACING AND ADDITIONAL REQUIREMENTS, SEE DIAGRAM ACOUSTICAL CEILING DETAIL

SPLAY BRACING WIRE, SEE FOUR WAY BRACING TEE

72

0 S

. Tr

acy

Ave

., B

ozem

an, M

T

dRA-

Arc

hite

ct.c

om

dRA

den

nis

Raf

fens

perg

erArc

hite

ct

REV. DESCRIPTION DATE

REVIEWED BY:DRAWN BY:

SHEET

DATE

SHEET TITLE

MO

NT

AN

AST

AT

E U

NIV

ER

SIT

Y

MSU-CPDCMONTANA STATE UNIVERSITY

BOZEMAN, MONTANAPHONE: 406.994.5413

FAX: 406.994.5665

Consultant #:1710

CL

ASS

RO

OM

RE

NO

VA

TIO

NS

2018

CH

EEVE

R H

ALL

21

4 1

00

% C

ON

STR

UC

TIO

N D

RA

WIN

GS

AuthorChecker

TYPICAL DETAILS

A50003/19/2018

PR

OJE

CT

#4

PPA#18-2015

3" = 1'-0" REF: 3/ A500

ACOUSTICAL CEILING DETAIL #11

3" = 1'-0" REF: 3/ A500

ACOUSTICAL CEILING DETAIL #22

3" = 1'-0"DIAGRAM ACOUSTICAL CEILING DETAIL3

3" = 1'-0"FRAMED CEILING SYSTEM4

1 1/2" = 1'-0"SEISMIC CEILING ASSEMBLY5

1 1/2" = 1'-0"SOFFIT DETAIL - MTL STUD6 1 1/2" = 1'-0" REF: 2/ A101

CEILING TRANSITION DETAIL7

3" = 1'-0" REF: 3/ A500

SUSPENDED CEILING BRACING8

Page 7: J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

SUPPORT ROD TOSTRUCTURE (TYP)

UNI-STRUTTRAPEZE

INSTALL SEISMIC

RESTRAINTSPER CODE

COOPER B-LINE "SNAP 'N SHEILD"PIPE SUPPORT (OR APPROVED EQUAL)

3/4" CLOSED CELLELASTOMERICPIPE INSULATION

ELECTRICAL COORDINATIONCOORDINATE WITH OTHER TRADES TO ENSURE THAT ALL:

· ELECTRICAL DISCONNECTS· MOTOR STARTERS· VARIABLE FREQUENCY DRIVES· CONTROLS · ELECTRICAL ACCESSORIES

ARE FURNISHED BY THE APPROPRIATE TRADE AND THAT INSTALLATION HAS BEEN COORDINATED.

10"

COOPER "DURA-BLOK" OR EQUAL WITH TREADED

ROD AND UNISTRUT

COVER OPENING WITH BIRD SCREEN

"HYDRA-ZORB" OR EQUAL PIPE CLAMP

20 GAGE GALVANIZED SHEET METAL HOOD

WITH DRIP PAN EDGEREFRIGERANT PIPING & CONTROL WIRING

FILL OPENINGS WITH FOAM INSULATION AIR TIGHT AFTER LINES ARE INSTALLED

PRE-FABRICATED CURB

TOP OF ROOF DECK

UNISTRUT ANCHORED TO CURB. CLAMP REFRIGERATION LINES WITH "HYDRA-ZORB" CLAMP OR EQUAL

NOTE: CONTRACTOR SHALL PATCH AND REPAIR ROOFING MATERIAL AT THE NEW ROOF CURB PENETRATION WITH METHODS AND MATERIALS CONSISTENT WITH THE EXISTING ROOFING MATERIAL. CONTRACTOR SHALL BE CERTIFIED BY THE EXISTING ROOF NFGR IN ORDER TO MAINTAIN THE EXISTING ROOF WARRANTY.

RXTQ60TAVJU (77.13 kBtu/h)ADDITIONAL REFRIGERANT: 1.4 LBS

3/8" x 3/4" 1/4" x 1/2"

CU-1

FXQ15TAVJUFC-1

1/4" x 1/2"FXQ15TAVJUFC-1

1/4" x 1/2"FXQ15TAVJUFC-1

1/4" x 1/2"FXQ15TAVJUFC-1

KHRP26A22T9

KHRP26A22T9

KHRP26A22T9

3/8" x 5/8"

3/8" x 5/8"

DOUBLE 2x12 CURB MIN. -VFY. LOAD & ACCOMMODATE

CANT AS PER MANUF.

TREATED WD. BLOCKING SECURED TO ROOF DECK

POLYISO. INSUL.

SINGLE PLY MEM. MECH FASTENED

FLASHING & COUNTERFLASHING

HOT AIR WELD

SEAM CAULK

VIB. ISO. FURNISHED w/ CU.

MECH. UNIT FASTENED TO TREATED WD. BLOCKING

MATTHEW W.

CARR

No. 20181 PE

MONTA NA

L IC E NS ED

PR

OF

ESS IONA L ENGIN

EE

R

REV. DESCRIPTION DATE

REVIEWED BY:

DRAWN BY:

SHEET

DATE

SHEET TITLE

MO

NT

AN

AS

TA

TE

UN

IV

ER

SIT

Y

MSU-CPDCMONTANA STATE UNIVERSITY

BOZEMAN, MONTANA

PHONE: 406.994.5413

FAX: 406.994.5665

6159.001

CL

AS

SR

OO

MR

EN

OV

AT

ION

S 2

018

CH

EE

VE

R H

AL

L 2

14

10

0%

CO

NS

TR

UC

TIO

N D

RA

WIN

GS

MWCECR

LEGEND, SCHEDULES,

& DETAILS

M001

03/19/2018

PR

OJE

CT

#4

PPA#18-2015

NOTES: COOLING CAPACITIES ARE BASED ON 75F BD / 55F WB ENTERING CONDITIONS. HEATING CAPACITIES ARE BASED ON 70F BD ENTERING CONDITION. EACH FANCOIL SHALL BE CONTROLLED BY A SIMPLE WIRED ROOMCONTROLLER.

FC-1 DAIKIN FXZQ15TAVJU 2'x2' 4-WAY CASSETTE 405 - - 14,331 10,274 230 1 0.4 SEE NOTES

CFM ESP (in W.C.) TOTAL (KBTU/HR) SENSIBLE VOLTAGE PHASE MCA

MARK MFGRMODEL

NUMBERUNIT TYPE

SUPPLY FAN COOLING CAPACITY ELECTRICAL DATA

REMARKS

MULTI-SPLIT FAN COIL SCHEDULE (R-410a) - BID ALT

NOTES: COOLING CAPACITY IS BASED ON 80F BD / 67F WB INDOOR AND 95F DB / 75F WB OUTDOOR. HEATING CAPACITY IS BASED ON 70F BD / 60F WB AND 47F DB / 43F WB.

CU-1 DAIKIN RXTQ60TAVJU COOLING ONLY HEAT PUMP R-410A 53,875 18 - - - - 230 1 23.9 224.9 SEE NOTES

TOTALCAPACITY(BHU/HR)

IEERTOTAL

CAPACITY(BTU/HR)

C.O.P. VOLTAGE PHASE MCA

MARK MFGR MODEL NUMBER TYPE REFRIGERANT

COOLING DATA HEATING DATA ELECTRICAL

WEIGHT(LBS)

REMARKS

MULTI-SPLIT HEAT PUMP SCHEDULE (R-410a) - BID ALT

2REFRIGERANT PIPE SUPPORT

1REFRIGERANT PIPING ROOF PENETRATION HOOD

NOTES: PROVIDE MANUAL BALANCING DAMPER AT LOCATIONS WHERE A SPECIFIED AIR VOLUME IS REQUIRED I.E. FOR SUPPLY AND EXHAUST ONLY. COORDINATE FRAME AND MOUNTING TYPE WITH CEILING TYPES. SEE ARCHITECTURAL PLANS FOR CEILING TYPES. THE CONTRACTOR SHALL BERESPONSIBLE TO PROVIDE ALL FITTINGS AND ACCESSORIES REQUIRED FOR A COMPLETE INSTALLATION. SCHEDULES N.C. VALUES ARE VALID FOR SCHEDULE AIR FLOW ONLY AND REPRESENT A MAXIMUM ACCEPTABLE N.C. VALUE. SUBSTITUTED EQUIPTMENT SHALL HAVE N.C. VALUE EQUAL TO OR BELOWTHE SCHEDULES N.C. AT THE AIR FLOW LISTED ON THE PLANS.

R-1 KRUEGER S80 FIXED BLADE 30º SURFACE MOUNT RETURN GRILLE RETURN 1,200 0.016 - - 0.016 36"x18" N/A STEEL BY ARCH SEE NOTES

MARK MFGR MODEL DESCRIPTION FUNCTION MAX CFMNC AT MAX

CFMTHROW AT MAX

CFM (FT)PRESSURE DROP AT MAX CFM

(in. W.C.)NECK SIZE

(W"xH")DAMPER TYPE MATERIAL FINISH REMARKS

GRILLE, REGISTER AND DIFFUSER SCHEDULE

3VRF REFRIGERANT PIPING NETWORKBID ALTERNATE

BID ALTERNATE

BID ALTERNATE

BID ALTERNATE

4ROOF CURB DETAIL

Page 8: J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

T

T

A B C

1

2

FC-1FC-1

FC-1 FC-1FC-1 FC-1

1

(TYP)

2

3

CU-1

R-2

R-21200

4

4

3/4"ø CND3/4"ø CND

3/4"ø CND3/4"ø CND

3/4"ø CND3/4"ø CND

3/4"ø CND

5

(E)S

(TYP)

(E)S

6

RL/RS RL/RS

RL/RSRL/RS

RL/RS RL/RS

7

A.) IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO FIELD COORDINATE THE LOCATION OF EQUIPMENT ROUTING OF ALL DUCTWORK AND PIPING WITH ALL OTHER TRADES.

B.) IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO REVIEW THE DRAWINGS FOR ALL DICIPLINES AND PROVIDE ALL LABOR AND MATERIALS REQUIRED FOR A COMPLETE INSTALLATION.

C.) COORDAINTE THE INSTALLATION OF GRILLES, REGISTERS AND DIFFUSERS WITH THE ARCHITECTURAL REFLECTED CEILING PLANS AND THE ELECTRICAL LIGHTING PLANS.

D.) VERIFY THE LOCATION OF THERMOSTATS AND SENSORS WITH THE ARCHITECT AND ENGINEER PRIOR TO INSTALLATION. INSTALL THERMOSTATS 48" ABOVE FINISHED FLOOR PER ADA REQUIREMENTS.

E.) PROVIDE AND INSTALL SEISMIC BRACING FOR ALL EQUIPMENT, DUCTWORK AND PIPING PER THE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE.

F.) FLEXIBLE DUCTWORK BETWEEN BRANCH DUCTS AND GRILLES, REGISTERS OR DIFFUSERS SHALL BE LIMITED TO 5FT.

G.) PROVIDE AND INSTALL FIRE, SMOKE AND/OR COMBINATION SMOKE/FIRE DAMPERS WHERE DUCTWORK PASSES THROUGH FIRE RATED ASSEMBLIES. ASSOCAITED DUCTDETECTORS SHALL BE ADRESSABLE. SMOKE DAMPERS AND COMBINATION SMOKE/FIRE DAMPERS SHALL INCLUDE A KEYED REMOTE TEST SWITCH LOCATED IN AN ACCESSIBLE LOCATION. FIELD COORDINATE THE LOCATION OF TEST SWITCHES WITH THE ARCHITECT AND ENGINEER PRIOR INSTALLATION.

H.) SEAL ALL DUCT AND PIPE PENETRATIONS THROUGH FIRE RATED ASSEMBLIES WITH A UL-APPROVED FIRE STOP SYSTEM.

I.) PROVIDE ACCESS DOORS TO ALLOW SERVICE AND INSPECTION OF EQUIPMENT, VALVES, DAMPERS AND DEVICES INSTALLED ABOVE NON-REMOVABLE CEILINGS.

J.) PROVIDE REMOTE CONTROLLED DAMPER ACTUATORS FOR BALANCING DAMPERS INSTALLED IN INACCESIBLE LOCATION. PROVIDE RUSKIN ZPD25 OR APPROVED EQUAL.

GENERAL MECHANICAL NOTES

KEY NOTES:#

MATTHEW W.

CARR

No. 20181 PE

MONTA NA

L IC E NS ED

PR

OF

ESS IONA L ENGIN

EE

R

REV. DESCRIPTION DATE

REVIEWED BY:

DRAWN BY:

SHEET

DATE

SHEET TITLE

MO

NT

AN

AS

TA

TE

UN

IV

ER

SIT

Y

MSU-CPDCMONTANA STATE UNIVERSITY

BOZEMAN, MONTANA

PHONE: 406.994.5413

FAX: 406.994.5665

6159.001

CL

AS

SR

OO

MR

EN

OV

AT

ION

S 2

018

CH

EE

VE

R H

AL

L 2

14

10

0%

CO

NS

TR

UC

TIO

N D

RA

WIN

GS

MWCECR

MECHANICAL PLAN

M100

03/19/2018

PR

OJE

CT

#4

PPA#18-2015

3/8" = 1'-0"1MECHANICAL RENOVATION PLAN

1. ROUTE REFRIGERANT PIPING FROM EACH FAN COIL UNIT TO THE CONDENSING UNIT ON THE ROOF PER MANUFACTURER'S PIPING DIAGRAM.

2. NEW FAN COIL UNIT CONTROLLER. CONTROLLER SHALL BE INTERLOCKED WITH THE HEATING SYSTEM SO THAT COOLING IS DISABLED WHILE THE HEATING SYSTEM IS RUNNING. CONTRACTOR SHALL INSTALL A PNEUMATIC/ELECTRIC TRANSDUCER ON THE PNEUMATIC CONTROLS SYSTEM AT THE EXISTING THERMOSTAT TO SENSE WHEN HEATING IS ENABLED. THE VRF SYSTEM SHALL BE DISABLED WHEN THE HEATING IS OPERATIONAL.

3. INSTALL CONDENSING UNIT ON ROOF. SEE DETAIL 4/M001 FOR CURB INSTALLATION DETAIL. TWO CURBS SHALL BE INSTALLED WITH THE UNIT SECURED STRUCTURAL CHANNEL BETWEEN THE TWO CURBS.

4. REPLACE EXISTING RETURN GRILLE. VERIFY ACTUAL NECK SIZE PRIOR TO ORDERING RETURN GRILLE.

5. ROUTE 3/4" CONDENSATE LINE TO NEAREST DRAIN LINE LOCATED DOWN IN THE CORRIDOR OF THE SOUTHWEST CORNER OF THE ADJACENT CLASSROOM. FIELD VERIFY DRAIN LOCATION BEFORE CONNECTION.

6. REFRIGERANT LIQUID AND SUCTION LINES UP TO CU-1. SEE DETAIL 1/M001 FOR PENETRATION HOOD DETAIL. SEE DETAIL 3/M001 FOR PIPE LINE SIZING.

7. A PLASTIC ENGRAVED SIGN SHALL BE FASTENED TO THE WALL NEXT TO THE TWO THERMOSTATS. THE SIGN SHALL HAVE THE FOLLOWING VERBIAGE ENGRAVED, "THE THERMOSTAT LABELED 'JOHNSON CONTROLS' CONTROLS THE ROOM HEATING SETPOINT, THE ROOM TEMPERATURE SHALL BE SET TO 68ºF DURING HEATING MODE. THE THERMOSTAT LABELED 'DAIKIN' CONTROLS THE ROOM COOLING SET POINT. THE COOLING THERMOSTAT TEMPERATURE SHALL BE SET TO NO LESS THAN 75ºF." CONTRACTOR SHALL VERIFY THE ABOVE VERBIAGE WITH THE ARCHITECT AND OWNER PRIOR TO FABRICATION.

Page 9: J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

X

D-1

X X

X X

J

TV

X

X

X

OS

P

R1

R2

R3

R4

LV

F F

F

S S

S S

BRANCH CIRCUIT PANELBOARD

PANEL AND CIRCUIT DESIGNATION ARE SHOWN NEXT TOEACH DEVICE (PANEL NAME - CIRCUIT NUMBER). BRANCHCIRCUIT WIRE SIZE IS #12 UNLESS NOTED OTHERWISE. ASINGLE INSULATED GREEN GROUND CONDUCTOR SHALL BEPROVIDED WITH EACH HOME RUN. PROVIDE A SEPARATENEUTRAL FOR EACH CIRCUIT. HOME RUNS SHALL HAVE NOMORE THAN THREE CIRCUITS. LINE VOLTAGE AND LOWVOLTAGE WIRING IS NOT SHOWN ON PLANS. FOR EQUIPMENTCIRCUITING, SEE MEP COORDINATION SCHEDULE.

DUPLEX, 4PLEX RECEPTACLE. (MOUNT AT +18" AFF. UNO.)X-GFI-GFCI RECEPTACLEWP-WEATHER PROOF WITH WHILE IN USE COVER

DUPLEX, 4PLEX ABOVE COUNTER RECEPTACLE MOUNTED 4"ABOVE BACKSPLASH

FLOOR OUTLET - HUBBELL MODEL #HBLCFB401CB, COVERMODEL #HBLTCGNTBKSW, OR EQUAL.

FLOOR BOX WITH COMBINATION 4PLEX RECEPTACLE & 2TELEPHONE/DATA OUTLETS- HUBBELL MODEL#HBLCFB401CB, COVER MODEL #HBLTCGNTBKSW, OR EQUAL.

JUNCTION BOX

COMBO POWER/DATA DIVIDED TV BOX; 2-GANG, LEGRAND2444D-2NFW, OR EQUAL. DUPLEX RECEPTACLE & SINGLEGANG DATA PORT W/ FACEPLATES. SEE ARCHITECTURALFOR MOUNTING HEIGHT.

SPECIAL PURPOSE OUTLET, MOUNT AT +18" AFF. UNO.LETTER INDICATES TYPE:TYPE A: NEMA 5-20R, TYPE B: NEMA 5-30R,TYPE C: NEMA 5-50R, TYPE D: NEMA 6-20R,TYPE E: NEMA 6-30R, TYPE F: NEMA 6-50RTYPE G: NEMA 14-20R, TYPE H: NEMA 14-30RTYPE I: NEMA 14-50R

PUSHBUTTON (MOUNT AT +54" AFF, UNO.). "X" DENOTES TYPE:"EPO" = EMERGENCY POWER OFF"ADA" = HANDICAP ACCESSIBLE DOOR (DEVICE BY OTHERS)"ODO" = OVERHEAD DOOR OPERATOR (DEVICE BY OTHERS)

SURFACE MOUNTED RACEWAY: SEE PLANS & SPECS.

RACEWAY STUB-OUT OR STUB-UP WITH CAPPED END

RACEWAY STUB-OUT OR STUB-UP WITH BUSHED END

ELECTRICAL POWER LEGEND

STANDARD LIGHTING CONTROLS:SWITCHES AND LINE VOLTAGE DIMMERS

TOGGLE SWITCH (MOUNT AT 46" AFF. UNO.)

SUBSCRIPTS:

NO SUBSCRIPT INDICATES SINGLE POLE

"3" INDICATES THREE-WAY

"4" INDICATES FOUR-WAY

"D" INDICATES DIMMER SWITCH - PHILIPS SUNRISE - ON/OFF

"K" INDICATES KEYED SWITCH

"T" INDICATES TIMER

"P" INDICATES PILOT LIGHT

"OS" INDICATES WALL SWITCH OCC SENSOR-

- WATTSTOPPER DW100 (SINGLE OR DUAL DW-200 SWITCH).

"OSD" INDICATES WALL SWITCH OCC SENSOR w/ 0-10V DIMMING

- WATTSTOPPER W-311

"a" INDICATES SINGLE POLE LIGHTING SWITCH FOR ZONE a

"b" INDICATES SINGLE POLE LIGHTING SWITCH FOR ZONE b

"ab" INDICATES LIGHTING SWITCHES w/ MULTIPLE ZONES

DIGITAL LIGHTING CONTROLS:ROOM CONTROLLERS AND LOW VOLTAGE DEVICES

DIGITAL OCCUPANCY SENSOR - CEILING MOUNT.WATTSTOPPER LMDC-100 OR EQUAL

DIGITAL PHOTOCELL - CEILING MOUNT. WATTSTOPPERLMLS-400 OR EQUAL

ROOM CONTROLLER - WATTSTOPPER DLM LMRC-101 OR EQUAL.

ROOM CONTROLLER - WATTSTOPPER DLM LMRC-102 OR EQUAL.

ROOM CONTROLLER - WATTSTOPPER DLM LMRC-212 OR EQUAL.

ROOM CONTROLLER - WATTSTOPPER DLM LMRC-213 OR EQUAL.

LOW VOLTAGE SWITCH - WATTSTOPPER LMSW-10X, "X"DENOTES NUMBER OF BUTTONS. SEE LIGHTING CONTROLDIAGRAM ON THIS SHEET.

ELECTRICAL LIGHTING CONTROL LEGEND

RECESSED FLUORESCENT FIXTURE- "a" & "b" DESIGNATESSWITCH

RECESSED EMERGENCY FLUORESCENT FIXTURE- "a"& "b"DESIGNATES SWITCH

SURFACE OR PENDANT FLUORESCENT FIXTURE- "x"DESIGNATES SWITCH LEG

SURFACE OR PENDANT EMERGENCY FLUORESCENT FIXTURE-"x" DESIGNATES SWITCH LEG

1X4 SURFACE WALL MOUNT FLUORESCENT

FLUORESCENT STRIP OR INDUSTRIAL, SURFACE OR CHAINHUNG

POLE MOUNTED FIXTURE

LIGHTED BOLLARD

PENDANT FIXTURE; HIGH BAY, LOW BAY, DECORATIVE

EXIT SIGN - WALL MOUNT, CEILING MOUNT. ARROWINDICATES DIRECTION OF TRAVEL, SHADING INDICATESLIGHTED FACE.

EMERGENCY EGRESS BATTERY PACK, WALL MOUNT ORCEILING MOUNT

WALL MOUNTED SCONCE OR WALLPACK FIXTURE

SURFACE MOUNTED DOWNLIGHT

RECESSED CAN DOWNLIGHT

RECESSED CAN WALLWASHER

TRACK LIGHTING. SEE FIXTURE SCHEDULE AND LIGHTINGPLANS.

ELECTRICAL LIGHTING FIXTURE LEGENDTELEPHONE OUTLET

VOICE-DATA OUTLET. PROVIDE PATHWAY TO ACCESSIBLE CEILING

SPACE AS SHOWN ON PLANS. CABLING BY MSU IT.

DATA OUTLET

WIRELESS ACCESS POINT, COORDINATE WITH MSU IT.

STROBE WALL MOUNT (MOUNT AT +82" AFF, UNO.) AND CEILINGMOUNT

FIRE ALARM MANUAL STATION (MOUNT AT +46" AFF, UNO.)

HORN/STROBE WALL MOUNT (MOUNT AT +82" AFF, UNO.) ANDCEILING MOUNT

SPEAKER STROBE WALL MOUNT (MOUNT AT +82" AFF, UNO.) ANDCEILING MOUNT

SPEAKER, COORDINATE WITH MSU IT.

ELECTRICAL SYSTEM LEGEND

WAP

ELECTRICAL PROJECT NOTESA. PRIOR TO BID CONTRACTOR SHALL VISIT THE SITE. NOT ALL WORK

REQUIRED TO COMPLETE THE PROJECT IS SHOWN ON THE DRAWINGS. THECONTRACTOR SHALL BECOME THOROUGHLY FAMILIAR WITH ALL THE WORKREQUIRED TO COMPLETE THE PROJECT IN ADDITION TO THE LOCALCONDITIONS AND INCLUDE SAID WORK IN THE BID.

B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OFALL ELECTRICAL SERVICE WORK WITH UTILITY. OWNER PAYS ALL FEES,CONTRACTOR DOES ALL SCHEDULING AND COORDINATION OF WORK. IT ISTHE SOLE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE ALLSCHEDULES ARE MET.

C. GENERAL WORK PRACTICES FOR ELECTRICAL CONSTRUCTION SHALL BEIN ACCORDANCE WITH NECA 1, "STANDARD PRACTICES FOR GOODWORKMANSHIP IN ELECTRICAL CONTRACTING." THIS PUBLICATION ISAVAILABLE FROM NECA BY TELEPHONE AT 301-657-3110 OR ON-LINE ATWWW.NECANET.ORG.

D. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE WITHMECHANICAL FOR PLENUM SPACES AND PROVIDE PLENUM RATED CABLESWHERE REQUIRED FOR LIGHTING CONTROL, DATA, FIRE ALARM AND ALLOTHER L.V. SYSTEMS NOT INSTALLED IN CONDUIT. VERIFY CONDUITREQUIREMENTS ON DRAWINGS AND SPECIFICATIONS.

E. FIRE-RESISTANCE: PROVIDE A MINIMUM HORIZONTAL DISTANCE OF 24"BETWEEN OUTLET BOXES LOCATED ON OPPOSITE SIDES OFFIRE-RESISTANCE RATED WALLS. WHERE THIS IS NOT POSSIBLE INSTALL ULLISTED PUTTY PADS ON ALL OUTLET BOXES NOT MEETING THE 24"SEPARATION. PROVIDE A UL LISTED THROUGH -PENETRATION FIRESTOPFOR PENETRATIONS OF FIRE-RESISTANCE RATED ASSEMBLIES.

F. CONDUCTORS ARE SIZED PER THE 75 DEGREE C RATING COLUMN OF NECTABLE 310.16. IF THE TERMINAL USED FOR A TERMINATION OF A PARTICULARCONDUCTOR IS NOT MARKED, OR THE TERMINAL IS MARKED FOR 60 DEGREEC CONDUCTORS, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TOEITHER ADJUST THE AMPACITY OF THE CONDUCTOR TO MATCH THE 60DEGREE COLUMN OF TABLE 310.16, OR REPLACE THE TERMINAL WITH ONERATED FOR AT LEAST 75 DEGREES C

G. FOR 20A BRANCH CIRCUIT RUNS EXTENDING BEYOND 300 LINEAR FEET.CONDUCTOR SIZE SHALL BE A MINIMUM OF #10 CU.

H. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH 120V BRANCHCIRCUIT.

I. DURING DEMOLITION, THE CONTRACTOR SHALL NOTE ALL EXISTINGRACEWAY (BOTH SURFACE AND CONCEALED) TO THE EXTENT POSSIBLE.THESE RACEWAYS SHALL BE REUSED TO THE GREATEST EXTENT POSSIBLETO INSURE A CLEAN FINISHED PRODUCT. WHERE PRACTICAL, AND ALLOWEDPER CODE, FISHING THROUGH WALLS WITH MC CABLE IS PREFERRED TOSURFACE-MOUNTED CONDUIT.

J. CONTRACTOR SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OFLAMPS AND BALLASTS OFF-SITE. IT IS ASSUMED THE THE BALLASTS DO NOTCONTAIN PCBs. THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELYIF IT IS SUSPECTED THAT BALLASTS CONTAIN PCBs.

K. ALL POWER INTERRUPTIONS SHALL BE COORDINATED WITH OWNER. ANYDISRUPTION OF WORKERS IN THE SPACE SHALL BE KEPT TO A MINIMUM ANDBE COORDINATED WITH THE OWNER PRIOR TO WORK COMMENCING IN THATSPACE.

L. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANYEXISTING CIRCUITS THAT ARE INTENDED TO REMAIN THAT ARE SAW CUT ORINTERRUPTED AS PART OF THE DEMOLITION PROCESS. PROVISION FOR THISWORK SHALL BE INCLUDED IN THE BID. SUCH CIRCUITS INCLUDE BUT ARENOT LIMITED TO: INTERIOR RECEPTACLE CIRCUITS, INTERIOR LIGHTINGCIRCUITS, EXTERIOR BUILDING LIGHTING, SITE LIGHTING, ETC.

M. ELECTRICAL DRAWINGS SHOWING EXISTING BUILDING CONDITIONS,SUCH AS DEMOLITION DRAWINGS, EXISTING PANEL SCHEDULES, ETC AREBASED ON RECORD DRAWINGS AND SITE VISITS. IF ACTUAL EXISTINGCONDITIONS DIFFER FROM THOSE SHOWN ON DRAWINGS, PLEASE NOTIFYENGINEER.

A, AMP AMPERES

AC ALTERNATING CURRENT

A/C AIR CONDITIONING

AF AMP FUSE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AL ALUMINUM

AS AMP SWITCH

ATS AUTOMATIC TRANSFER SWITCH

BAS BUILDING AUTOMATION SYSTEM

BKR BREAKER

C RACEWAY/CONDUIT

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

C.O. RACEWAY/CONDUIT ONLY, WITH PULL STRING

CNTRL CONTROL

CU COPPER

DISC DISCONNECT

DIST DISTRIBUTION

DPDT DOUBLE POLE DOUBLE THROW

DWG DRAWING

EA EACH

EF EXHAUST FAN

ELEC ELECTRIC

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT

EX, EXIST EXISTING

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FATC FIRE ALARM TERMINAL CABINET

FD FUSED DISCONNECT

FIDS FLIGHT INFORMATION DISPLAY SYSTEM

FLR FLOOR

FO FIBER OPTIC

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

GEC GROUNDED ELECTRODE CONDUCTOR

GFI GROUND FAULT INTERRUPTER

GND GROUND

GRC GALVANIZED RIGID CONDUIT

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HTR HEATER

HVAC HEATING, VENTILATING & AIR CONDITIONING

HZ HERTZ

J-BOX JUNCTION BOX

KVA KILOVOLT AMPERES

KW KILOWATTS

LTG LIGHTING

LPW LUMENS PER WATT

MAG MAGNETIC STARTER

MAN MANUAL

MAX MAXIMUM

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MH METAL HALIDE

MIN MINIMUM

MSS MOTOR STARTER SWITCH

N NEUTRAL

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NFD NON-FUSED DISCONNECT

NIC NOT IN CONTRACT

NO NORMALLY OPEN

# NUMBER

OAE OR APPROVED EQUAL

OC ON CENTER

OCPD OVERCURRENT PROTECTION DEVICE

OH OVERHEAD

P POLE

PB PUSHBUTTON

PNL PANEL

PS POWER SUPPLY

PVC POLYVINYL CHLORIDE CONDUIT

PWR POWER

RECEPT RECEPTACLE

RCPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RM ROOM

RVNR REDUCED VOLTAGE NON-REVERSING

RVR REDUCED VOLTAGE REVERSING

SP SINGLE POLE TOGGLE SWITCH

SPEC SPECIFICATION

SPST SINGLE POLE SINGLE THROW

SSPB START-STOP PUSHBUTTON

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TB TELEPHONE BOARD

TC TIME CLOCK

TD TIME DELAY

TEL TELEPHONE

TSP TWISTED SHIELDED PAIR

TTB TELEPHONE TERMINAL BOARD

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

UON UNLESS OTHERWISE NOTED

V VOLT

VA VOLT AMPERES

VFD VARIABLE FREQUENCY DRIVE

W WATTS

WP WEATHERPROOF

W/O WITHOUT

XFMR TRANSFORMER

Y WYE CONNECTED

DELTA CONNECTED

PHASE

NOTE: THESE ABBREVIATIONS COMPRISE A STANDARD LIST; NOT ALL ABBREVIATIONS APPEAR ON THIS PROJECT.

ELECTRICAL ABBREVIATIONS LEGEND

LUMINAIRE SCHEDULETYPE LAMPS DESCRIPTION MFR CATALOG NO. OR SERIES MOUNTING/ VOLTAGE LLF (ASSUMED) NOTES

A1 LED 2'x4' RECESSED EDGE-LIT FLAT PANELPHILIPS

DAY-BRITE2FXP38L835-4-DS-UNV-DIM RECESSED/ 120-277 0.85 1

NOTES:

1. SUBMITTED LUMINAIRE REQUIRES PRIOR APPROVAL.

GENERAL NOTE:

THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL CEILING TYPES AND PROVIDE ALL REQUIRED MOUNTING ACCESSORIES.

ROOM CONTROLLERLMRC-102

NEUTRAL WHT

HOT BLK120/277

LIGHTING LOAD (a)

LIGHTING LOAD (b)

LMDC-100OCCUPANCY

SENSOR

DLM WALLSWITCH

LMSW-102

RJ45(TYP)

LMRJ SERIESPRE-TERMINATED

CABLES.

NOTES:

-DEVICES ARE PRESET FOR PLUG n' GO™ OPERATION.

-ALL ROOMS ARE STAND ALONE.

-NUMBER OF ZONES ("a" "b" ETC) INDICATED NUMBER OF RELAYS REQUIRED IN A ROOM.

-THE ROOM CONTROLLER DEFAULTS TO MULTI-LEVEL AUTOMATIC-ON/AUTOMATIC OFF.

DLM WALLSWITCH

LMSW-102

DLM WALLSWITCH

LMSW-101

a

b

aa

b

-REUSE EXISTING LIGHTING CIRCUIT IN ROOM. RE-ROUTE LINE VOLTAGE TO ROOM CONTROLLER AS REQUIRED.

IN EXPOSED FINISHED SPACES, PROVIDE CABLE IN RACEWAY.

PROVIDE LEGRAND STEEL WIREMOLD V700 SERIES OR EQUAL. RACEWAY

COLOR SHALL MATCH RACEWAY USED FOR RECEPTACLES & DATA.

ISS

EF

OR

P

LANO EN

G

INEER

ONT

MA

NA

LICENSED

GARTH L.

STEVENS

No. 11492 PE

REV. DESCRIPTION DATE

REVIEWED BY:

DRAWN BY:

SHEET

DATE

SHEET TITLE

MO

NT

AN

AS

TA

TE

UN

IV

ER

SIT

Y

MSU-CPDCMONTANA STATE UNIVERSITY

BOZEMAN, MONTANA

PHONE: 406.994.5413

FAX: 406.994.5665

6159.001

CL

AS

SR

OO

MR

EN

OV

AT

ION

S 2

018

CH

EE

VE

R H

AL

L 2

14

10

0%

CO

NS

TR

UC

TIO

N D

RA

WIN

GS

RMGS

ELECTRICAL

ABBREVIATIONS &

SYMBOLS

E001

03/19/2018

PR

OJE

CT

#4

PPA#18-2015

N.T.S.1CHEEVER 214 LIGHTING CONTROL DIAGRAM

Page 10: J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

LV

LV

OS

OS

R2

LV

33

33

GENERAL ELECTRICAL NOTES

A. ELECTRICAL DEVICES AND LIGHTS SHOWN IN GREY ARE EXISTING TO REMAIN. ELECTRICAL DEVICES AND LIGHTS SHOWN IN DASHED BLACK & SPECIFICALLY NOTED AS 'DEMO' ARE TO BE DEMOLISHED, UNO.

B. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE NO CONFLICTS IN LOCATION OF DUCTS, CONDUITS, DIFFUSERS, BOXES, AND OTHER ITEMS THROUGHOUT THIS PROJECT BEFORE FINAL PLACEMENT OF MATERIALS.

C. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS, WALLS, CEILINGS, AND ROOFS TO PERFORM THE REQUIRED WORK DEPICTED IN THESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR ALL PATCHING OF HOLES TO THE SATISFACTION OF THE ARCHITECT/ENGINEER.

KEY NOTES:#

A B C

1

2

a

bbb

b b

bb

b b

b

b

b

b

b

b

b

b

a

a

ab

ab

1 TYP.

A1 A1 A1

A1 A1

A1 A1 A1

A1 A1

A1A1A1

A1 A1

A1A1A1

A1 A1 a

A B C

1

2

DEMO (TYP. 4)

DEMO (TYP. 15)

DEMO DEMO

DEMO

ISS

EF

OR

P

LANO EN

G

INEER

ONT

MA

NA

LICENSED

GARTH L.

STEVENS

No. 11492 PE

REV. DESCRIPTION DATE

REVIEWED BY:

DRAWN BY:

SHEET

DATE

SHEET TITLE

MO

NT

AN

AS

TA

TE

UN

IV

ER

SIT

Y

MSU-CPDCMONTANA STATE UNIVERSITY

BOZEMAN, MONTANA

PHONE: 406.994.5413

FAX: 406.994.5665

6159.001

CL

AS

SR

OO

MR

EN

OV

AT

ION

S 2

018

CH

EE

VE

R H

AL

L 2

14

10

0%

CO

NS

TR

UC

TIO

N D

RA

WIN

GS

RMGS

ELECTRICAL

LIGHTING PLAN

E100

03/19/2018

PR

OJE

CT

#4

PPA#18-2015

1/4" = 1'-0"2CHEEVER 214 LIGHTING RENOVATION PLAN

1/4" = 1'-0"1CHEEVER 214 LIGHTING DEMOLITION PLAN

1 ALL NEW LIGHTING SHALL BE CIRCUITED VIA EXISTING BRANCH CIRCUIT PREVIOUSLY USED FOR LIGHTING WITHIN THE SPACE, WITH NEW CONTROLS. SEE SHEET E001 FOR LUMINAIRE SCHEDULE AND LIGHTING CONTROL DIAGRAM.

Page 11: J:MSU CLASSROOM REMODEL0.2 Revit … · all penetrations of fire resistive construction shall be protected with approved fire assemblies. 40. electrical outlets ... see electrical

WAP

J

J

SS

SS

S S

J J

JJ

M

J

SS

SS

S

WAP

S

DN

DN

DN

DN

DN

UP

242

249250

235236

234

243244245

232

241

230

240

246247248229228

227PC

227RR226RR

225

204

239

238

237

221

220

222219

223

217

207

209

210

203

212

215

200

214

215A

251

215

299EV1

OPEN TOBELOW

OPEN TOBELOW

206

OPEN TOBELOW

GENERAL ELECTRICAL NOTES

A. ELECTRICAL DEVICES AND LIGHTS SHOWN IN GREY ARE EXISTING TO REMAIN. ELECTRICAL DEVICES AND LIGHTS SHOWN IN DASHED BLACK & SPECIFICALLY NOTED AS 'DEMO' ARE TO BE DEMOLISHED, UNO.

B. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE NO CONFLICTS IN LOCATION OF DUCTS, CONDUITS, DIFFUSERS, BOXES, AND OTHER ITEMS THROUGHOUT THIS PROJECT BEFORE FINAL PLACEMENT OF MATERIALS.

C. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS, WALLS, CEILINGS, AND ROOFS TO PERFORM THE REQUIRED WORK DEPICTED IN THESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR ALL PATCHING OF HOLES TO THE SATISFACTION OF THE ARCHITECT/ENGINEER.

A B C

1

2

PROJECTOR

NEW WIREMOLD SYSTEM

1

10

ROOF CONDENSING UNIT (BID ALT)

3

4

NEW WIREMOLD SYSTEM 3

5

5

9 TYP.

11

FC-1 (BID ALT)

11

FC-1 (BID ALT)

11

FC-1 (BID ALT)

11

FC-1 (BID ALT)

12 TYP.

13

13

A B C

1

2

PROJECTOR(RELOCATE)

DEMO

DEMO

REMOVE EXISTING CEILING SPEAKERS AND ASSOCIATED WIRING (TYP. 6). SALVAGE FOR OWNER; COORDINATE WITH MSU IT.

DEMO

EXISTING WIRELESS ACCESS POINT SHALL BE SALVAGED FOR MSU IT TO REINSTALL IN NEW CEILING. LABEL & PROTECT ASSOCIATED CABLING FOR REUSE.

DEMO

DEMO

7

8

7 7

7

CHEEVER 214

PROJECT LOCATION

LOCATION OF EXISTING ELECTRICAL PANEL '22P1'

6

2

NEW LOAD CENTER (BID ALT)

NOTES:1. FIELD VERIFY FINAL LOCATION. COORDINATE WITH PODIUM AND MSU IT.2. PAINT VERTICAL WALL CHANNEL TO MATCH WALL COLOR.3. INCLUDE ALL REQUIRED COMPONENTS AND MANUFATURER ACCESSORIES FOR A COMPLETE SYSTEM.

END COMPONENT AS REQUIRED: CONNECTRAC IN-EC, OR EQUAL.

AV/DUPLEX RECEPTACLE COMBO BOX: CONNECTRAC

PS-A-288, OR EQUAL.IN-CARPET WIREWAY:

CONNECTRAC IN-048-GR, OR EQUAL

VERTICAL WALL CHANNEL TO CEILING: CONNECTRAC

AC-WC-144-AL, OR EQUAL

FLOOR

WALL

KEY NOTES:#

ISS

EF

OR

P

LANO EN

G

INEER

ONT

MA

NA

LICENSED

GARTH L.

STEVENS

No. 11492 PE

REV. DESCRIPTION DATE

REVIEWED BY:

DRAWN BY:

SHEET

DATE

SHEET TITLE

MO

NT

AN

AS

TA

TE

UN

IV

ER

SIT

Y

MSU-CPDCMONTANA STATE UNIVERSITY

BOZEMAN, MONTANA

PHONE: 406.994.5413

FAX: 406.994.5665

6159.001

CL

AS

SR

OO

MR

EN

OV

AT

ION

S 2

018

CH

EE

VE

R H

AL

L 2

14

10

0%

CO

NS

TR

UC

TIO

N D

RA

WIN

GS

RMGS

ELECTRICAL POWER

& SIGNAL PLAN

E200

03/19/2018

PR

OJE

CT

#4

PPA#18-2015

1/4" = 1'-0"4CHEEVER 214 ELECTRICAL RENOVATION PLAN

1/4" = 1'-0"3CHEEVER 214 ELECTRICAL DEMOLITION PLAN

1

2

RE-ROUTE 120V FEEDER AS REQUIRED FROM EXISTING PROJECTOR LOCATION TO NEW PROJECTOR. RE-USE EXISTING CIRCUIT.

PRICE THE FOLLOWING WORK UNDER MECHANICAL COOLING BID ALTERNATE: PROVIDE A NEW 120/208V 1-PH, 3W, 60A MLO, 4 SPACE LOAD CENTER. PROVIDE A NEW 50A/2P CIRCUIT BREAKER IN EXISTING WESTINGHOUSE PANEL '22P1' TO FEED NEW LOAD CENTER. RE-ARRANGE EXISTING BREAKERS IN PANEL '22P1' AS REQUIRED TO PROVIDE (2) ADJACENT SPACES FOR NEW BREAKER. PROVIDE (2) #8, #10 GND IN 3/4" EMT CONDUIT AND COORDINATE EXACT FEEDER ROUTING & NEW LOAD CENTER LOCATION IN FIELD.

PROVIDE SURFACE-MOUNT RACEWAY FOR ALL NEW RECEPTACLES SHOWN ON THIS WALL. SEE ARCHITECTURAL PLANS FOR MOUNTING HEIGHT OF RACEWAY & RECEPTACLES. BASE BID: PROVIDE LEGRAND STEEL WIREMOLD V700 SERIES. ALTERNATE BID: PROVIDE LEGRAND STEEL WIREMOLD 3000 SERIES.

PROVIDE IN-CARPET & VERTICAL WIREWAY SYSTEM PER DETAIL 2 ON THIS SHEET.

PROVIDE VERTICAL WIREMOLD FROM CEILING AT THIS CORNER TO FEED HORIZONTAL RUN OF WIREMOLD.

RE-USE EXISTING RECEPTACLE FEEDER(S) FROM PANEL '22P1' INTO ROOM 214.

REMOVE EXISTING DEVICE, WIREMOLD, AND IT'S CIRCUIT, BACK TO NEAREST UPSTREAM DEVICE TO MAINTAIN ORIGINAL CIRCUIT CONTINUITY.

REMOVE EXISTING RECEPTACLE AND IT'S CIRCUIT, BACK TO NEAREST UPSTREAM DEVICE TO MAINTAIN ORIGINAL CIRCUIT CONTINUITY.

CIRCUIT ALL NEW RECEPTACLES VIA EXISTING RECEPTACLE CIRCUITS IN ROOM, MARKED '22P1-14, 16, & 18' ON AS-BUILT PANEL DIRECTORY. FIELD VERIFY EXACT AS-BUILT CIRCUITING.

PRICE THE FOLLOWING WORK UNDER MECHANICAL COOLING BID ALTERNATE: PROVIDE A 35A/2P CIRCUIT BREAKER IN NEW LOAD CENTER TO FEED NEW CONDENSING UNIT ON ROOF. PROVIDE (2) #8, #10 GND IN 3/4" CONDUIT FOR FEEDER AND COORDINATE EXACT FEEDER ROUTING IN FIELD. PROVIDE 60A WP DISCONNECT SWITCH ON ROOF FOR LOCAL DISCONNECTING MEANS. PROVIDE 20A WP GFCI DUPLEX RECEPTACLE ON ROOF ADJACENT TO NEW CONDENSING UNIT. CIRCUIT VIA NEAREST 120V RECEPTACLE CIRCUIT. SEAL ALL PENETRATIONS THRU ROOF.

PRICE THE FOLLOWING WORK UNDER MECHANICAL COOLING BID ALTERNATE: PROVIDE A 15A/2P CIRCUIT BREAKER IN NEW LOAD CENTER TO FEED NEW FAN COIL(S) IN CLASSROOM CEILING. PROVIDE (2) #12, #12 GND IN 3/4" CONDUIT FOR FEEDER AND COORDINATE EXACT FEEDER ROUTING IN FIELD.

NEW CEILING SPEAKERS PROVIDED & INSTALLED BY MSU.

REPLACE EXISTING DEVICE & COVERPLATE WITH NEW WHITE DEVICE & COVERPLATE.

3

4

5

1" = 30'-0"1LEVEL 2 OVERALL PLAN

6

7

8

9

N.T.S.2ELECTRICAL IN-CARPET & VERTICAL WIREWAY DETAIL

10

11

12

13