Guide to Specifying Fire Penetrations

Page 2: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Introduction to Fire Rated Penetrations

This document aims to assist Architects, Engineers, Certifiers, Contractors and Builders in correctly specifying and installing fire rated penetration seals. All of the systems in this document are tested or assessed against AS 1530 Part 4 and AS 4072 Part 1.

This document is produced as a guide only and for specific FRL’s and test reports please contact Promat WA directly. Testing of a broad range of penetration seals is an ongoing process. If a specific service is not listed within this document, please contact Promat WA as there may be new test evidence available after the time of printing this document.

1. Identify if your penetration is passing through a floor or a wall, and establish the required FRL.

2. Use the table at the top of each page that matches your criteria to establish maximum opening size in the floor or wall to be penetrated.

3. Look up the specific service to identify the protection product required that meets your required criteria.

4. Make the appropriate selection and follow the installation instructions that are available in Promat WA’s Fire Stopping Application Guide.

5. Specification statements for Promat’s range of fire stopping products are listed on pages 13-15 of this document.

** Please Note: If your service or FRL required is not listed, please contact Promat WA and we will provide technical assistance.**

promatwa.com.au 08 9445 8300

How to use this document

2

Page 3: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Penetrations through Fire Rated Plasterboard & Concrete Walls with PROMASEAL® Bulkhead Batt

Aperture sizes for PROMASEAL® Bulkhead Batt System in Walls

Barrier Size Thickness FRL

PRO

MA

SEA

L®B

ulkh

ead

Bat

tsFi

tted

to A

pert

ure

600mm wide x 1500mm long

Maximum 1000mm high and anywidth to a maximum area of 1.0m2

500mm wide × infinite

2 x 50mm thick

-/120/120

-/120/120

-/120/120

600mm wide × 1200mm long -/180/180

Service Penetrations through PROMASEAL® Bulkhead Batt System in Walls

Barrier Service Protection Max FRL

PRO

MA

SEA

L® B

ulkh

ead

Bat

tsFi

tted

to A

pert

ure

2 x

50

mm

Brass Pipes Ø32mm to Ø100mm Single Pipe protectedwith 25mmPROMASEAL® Wrap 800mm each side of the wall

-/120/120

-/120/120

-/120/120with only FlexiWrap

FRL is -/180/90)**

uPVC pipe Ø40mm to Ø100mm

Copper, Steel & Iron Ø32mm to Ø150mm

Copper Pipe Ø19mm wrapped Armaflex & 6mm PROMASEAL® FlexiWrap fitted within steel sleeve

Trefoil Copper Pipe Ø19mm wrapped Armaflex & 6mm PROMASEAL® FlexiWrap fitted within steel sleeve

Bundle protectedwith 25mm PROMASEAL® Wrap

-/120/120

HDPE pipe Ø40mm to Ø100mm

PROMASEAL® FCW -/120/120

-/180/180

uPVC pipe Ø40mm PROMASEAL® FC 40 -/120/120

uPVC pipe Ø100mm PROMASEAL® FC 100 -/120/120

PEX pipe Ø20mm PROMASEAL® CFC -/120/120

AS1530.4: 2005 Appendix D, D1 and D2 cables

Cable tray and cables

Cables protected with 25mm PROMASEAL® Wrap 800mm each side of the wall

-/120/120

-/120/120

Cable bundle Ø60mm

Cable bundle Ø30mm PROMASEAL® AN Acrylic Sealant

-/120/120

Cable tray and cables 150mm wall 300mm PROMASEAL® SupaWrap

-/120/120

Fibre Optic cable bundle Ø60mm

-/120/120

-/180/180

PROMASEAL® FC

3

Page 4: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Penetrations through Floors with PROMASEAL® Bulkhead Batt

Aperture sizes for PROMASEAL® Bulkhead Batt System in Floors

Service Penetrations through PROMASEAL® Bulkhead Batt System in Floors

Service Penetrations through Bulkhead Batt System in Walls and Floors

PRO

MA

SEA

L®B

ulkh

ead

Bat

tsFi

tted

to A

pert

ure

600mm wide x 1500mm long

600mm wide × infinite long (supported at 600mm centres)

300mm wide × infinite long

2 x 50mm thick

-/120/120

-/120/120

-/120/120

Barrier Size Thickness FRL

PRO

MA

SEA

L® B

ulkh

ead

Bat

tsFi

tted

to A

pert

ure

2 x

50

mm

Brass Pipes Ø32mm to Ø100mm Single Pipe protectedwith 25mmPROMASEAL® Wrap 800mm each side of the floor

-/120/120

-/120/120Copper, Steel & Iron Ø32mm to Ø150mm

Copper Pipe Ø19mm wrapped Armaflex & 6mm PROMASEAL® FlexiWrap fitted within steel sleeve

AS1530.4: 2005 Appendix D, D1 and D2 cables

Cable trunking and cables

Cables protected with 25mm PROMASEAL® Wrap 800mm each side of the floor

-/120/120

-/120/120

Cable bundle Ø60mm

Cable bundle Ø30mm

PROMASEAL® AN Acrylic Sealant

-/120/120

-/120/120

-/120/120

Barrier Service Protection Max FRL

4

Page 5: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Penetrations through Walls with PROMASEAL® Mortar

Aperture sizes for PROMASEAL® Mortar System in Walls

Service Penetrations for PROMASEAL® Mortar System in Walls

PRO

MA

SEA

L®M

orta

rFi

tted

to A

pert

ure 600mm x 600mm

800mm x 800mm

800mm x 800mm

-/240/120

-/180/120

-/180/120

400 x 600mm -/240/240

90mm

90mm

105mm

105mm

Barrier Size Thickness FRL

PRO

MA

SEA

L® M

orta

r Fitt

ed to

Ape

rtur

e

Brass Pipes Ø32mm to Ø100mm Single Pipe protectedwith 25mmPROMASEAL® Wrap 800mm each side of the wall

-/120/120

-/120/120

-/120/120

uPVC pipe Ø16mm to Ø300mm

Copper, Steel & Iron Ø32mm to Ø150mm

Copper Pipe Ø19mm wrapped Armaflex & 6mm PROMASEAL® FlexiWrap fitted within steel sleeve

Trefoil Copper Pipe Ø19mm wrapped Armaflex & 6mm PROMASEAL® FlexiWrap fitted within steel sleeve

Bundle protectedwith 25mm PROMASEAL® Wrap

-/120/120

HDPE pipe Ø40mm to Ø200mm

PROMASEAL® FC + UniCollars

Consult Promat WA

Other Plastic Pipes PROMAT Collars

AS1530.4: 2005 Appendix D, D1 and D2 cables

Cable tray and cables

Cables protected with 25mm PROMASEAL® Wrap 800mm each side of the wall

-/120/120

PROMASEAL® AN Acrylic Sealant

Consult Promat WA

Consult Promat WA

-/120/120

Cables and Cable Bunches Consult Promat WA

Barrier Service Protection Max FRL

5

Page 6: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Penetrations through Floors with PROMASEAL® Mortar

Aperture sizes for PROMASEAL® Mortar System in Floors

Barrier Size Thickness FRL

PRO

MA

SEA

L®M

orta

rFi

tted

to A

pert

ure

800mm x 800mm

-/240/120

-/180/120

-/180/120400 x 600mm

-/240/240

90mm

90mm

105mm

800mm x 800mm

Support

Z Clips

Z Clips

Z Clips

Mechanical interlock

Service Penetrations through PROMASEAL® Mortar System in Floors

Service Penetrations through PROMASEAL® Mortar System in Walls and Floors

Brass Pipes Ø32mm to Ø100mm PROMASEAL® Wrap 800mm

-/120/120

-/120/120Copper, Steel & Iron Ø32mm to Ø150mm

Copper Pipe wrapped with Armaflex

AS1530.4: 2005 Appendix D, D1 and D2 cables

Cable trunking and cables

Cables protected with 25mm PROMASEAL® Wrap 800mm each side of the floor

-/120/120

-/120/120

Cables and cable bunchesPROMASEAL® AN Acrylic Sealant

-/240/120

PRO

MA

SEA

L® M

orta

r Fi

tted

to A

pert

ure

PROMASEAL® FlexiWrap

Barrier Service Protection Max FRL

6

-/120/120

Page 7: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Penetrations through Walls with PROMASEAL® Pillows

Aperture sizes for PROMASEAL® Pillow System in Walls

Service Penetrations through PROMASEAL® Pillow System in Walls

-/120/90

Brass Pipes Ø32mm to Ø100mm PROMASEAL® Wrap 800mm

-/120/120

-/120/120Copper, Steel & Iron Ø32mm to Ø150mm

AS1530.4: 2005 Appendix D, D1 and D2 cables

Cable trunking and cables

Cables protected with 25mm PROMASEAL® Wrap 800mm each side of the wall

-/120/120

-/120/120

Cables and cable bunches PROMASEAL® AN Acrylic Sealant

PRO

MA

SEA

L® P

illow

s Fi

tted

to A

pert

ure

AS1530.4: 2005 Appendix D, D1 and D2 cables

Cables protected with 600mmPROMASEAL®Pillows protruding200mm on both sides of walls

-/120/120

Barrier Service Protection Max FRL

PRO

MA

SEA

L®Pi

llow

s Fi

tted

to A

pert

ure 550mm x 550mm

550mm x 550mm

-/120/120

-/180/180

100mm

140mm

Barrier Size Thickness FRL

7

Page 8: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Penetrations through Floors with PROMASEAL® Pillows

Aperture sizes for PROMASEAL® Pillow System in Floors

Service Penetrations through PROMASEAL® Pillow System in Floors

-/120/90

Barrier Service Protection Max FRL

Brass Pipes Ø32mm to Ø100mm PROMASEAL® Wrap 800mm

-/120/120

-/120/120Copper, Steel & Iron Ø32mm to Ø150mm

AS1530.4: 2005 Appendix D, D1 and D2 cables

Cable trunking and cables

Cables protected with 25mm PROMASEAL® Wrap 800mm each side of the floor

-/120/120

-/120/120

Cables and cable bunches PROMASEAL® AN Acrylic Sealant

PRO

MA

SEA

L® P

illow

s Fi

tted

to A

pert

ure

AS1530.4: 2005 Appendix D, D1 and D2 cables

Cables protected with 600mmPROMASEAL®Pillows protruding200mm on top side of the floor

-/120/120

PRO

MA

SEA

L®Pi

llow

s Fi

tted

to A

pert

ure 550mm x 550mm

550mm x 550mm

-/120/120

-/180/180

125mm

150mm

Barrier Size Thickness FRL

Service Penetrations through PROMASEAL® Pillow System in Walls and Floors

8

Page 9: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Penetrations through Fire Rated Plasterboard, Masonry, AAC and Concrete Walls

Service Penetrations through Walls

Service Penetrations with PROMASEAL® FlexiWrap and SupaWrap in Walls

Barrier Service Protection Max FRL

PRO

MA

SEA

L® A

N A

cryl

ic S

eala

nt

Brass Pipes Ø32mm to Ø100mm PROMASEAL® Wrap 800mm each side of the wall

-/120/120

-/120/120

-/240/120

Copper, Steel & Iron Ø32mm to Ø150mm

Copper Pipe wrapped with Armaflex

AS1530.4: 2005 Appendix D, D1 and D2 cables

Cable tray and cables

Cables protected with 25mm PROMASEAL® Wrap 800mm each side of the wall

-/120/120

-/120/120

Cable bundle Ø60mm

Cable bundle Ø30mm

PROMASEAL® AN Acrylic Sealant

-/120/90

Cable tray and cables 150mm wall 300mm PROMASEAL® SupaWrap -/120/120

-/120/120

PROMASEAL® FlexiWrap

Other Plastic Pipes PROMAT Collars Consult Promat WA

uPVC pipe Ø16mm to Ø300mm

HDPE pipe Ø40mm to Ø200mm

PROMASEAL® FC + UniCollars

Consult Promat WA

Consult Promat WA

9

Page 10: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Penetrations through Floors with PROMASEAL® AN Acrylic Sealant

Service Penetrations through Floors

Service Penetrations with PROMASEAL® Collars and Wraps in Floors

Barrier Service Protection Max FRL

PRO

MA

SEA

L® A

N A

cryl

ic

Seal

ant o

r Con

cret

e Sl

ab

Brass Pipes Ø32mm to Ø100mm PROMASEAL® Wrap 800mm each side of the floor

-/120/120

-/120/120

-/240/120

Copper, Steel & Iron Ø32mm to Ø150mm

Copper Pipe wrapped with Armaflex

AS1530.4: 2005 Appendix D, D1 and D2 cables

Cable tray and cables

Cables protected with 25mm PROMASEAL® Wrap 800mm each side of the floor

-/120/120

-/120/120

Cable bundle Ø60mm

Cable bundle Ø30mm

PROMASEAL® AN Acrylic Sealant

PROMASEAL® FlexiWrap

Other Plastic Pipes PROMAT Collars Consult Promat WA

uPVC pipe Ø16mm to Ø300mm

HDPE pipe Ø40mm to Ø200mm

PROMASEAL® FC + UniCollars

Consult Promat WA

Consult Promat WA

-/120/120

Consult Promat WA

Plastic pipe Floor Waste Retrofit PROMASEAL® FWR Consult Promat WA

Plastic pipe Floor Waste Cast In PROMASNAP® Consult Promat WA

12

Page 11: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Specification Statements

PROMASEAL® Bulkhead Batt

Where appropriate, with or without service penetrations, the floor/wall openings should be properly fire stopped using PROMASEAL® Bulkhead Sealer in accordance with the required FRL (…/…/…) when tested and assessed in accordance with AS 1530.4. Installation of any fire stopping product should be carried out according to the manufacturer’s recommendations. Please consult Promat WA for more details. All work to be certified by an experienced installer in an approved manner.

PROMASEAL® Mortar

Openings in fire rated floors and walls are to be sealed using PROMASEAL® Mortar, formed and placed to the required depth in accordance with the required FRL (…/…/…) of the element. Where services penetrate the openings, PROMASEAL® AN Acrylic Sealant and PROMASEAL® fire stopping products may be required depending on the type of service and the manufacturer’s instructions, all in accordance with AS 1530.4 Please consult Promat WA for more details. All work to be certified by an experienced installer in an approved manner.

PROMASEAL® Pillows

Openings in fire rated floors and walls are to be sealed using PROMASEAL® Pillows, tightly packed in accordance with the manufacturers printed instructions. Where services penetrate the openings, the gaps between the services and the surrounding PROMASEAL® Pillows are to be sealed with PROMASEAL® AN Acrylic Sealant, all to achieve a FRL of (…/…/…) when tested to AS 1530.4. Please consult Promat WA for more details. All work to be certified by an experienced installer in an approved manner.

PROMASEAL® AN Acrylic Sealant

All perimeter gaps and penetration seals in fire rated plasterboard walls and ceilings are to be sealed with PROMASEAL® AN Acrylic Sealant to the required depth as tested and approved to AS 1530.4 and to the FRL (…/…/…) performance of the element. All details to be in accordance with the manufacturers printed instructions. Please consult Promat WA for more details. All work to be certified by an experienced installer in an approved manner.

13

Page 12: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Specification Statements

PROMASEAL® FLEXIWRAP

Where appropriate, the specified insulated penetrations through floor/wall should be properly fire stopped using PROMASEAL® FlexiWrap as tested and approved to AS 1530.4 and to the FRL (…/…/…) performance of the element. Please consult Promat WA for more details. All work to be certified by an experienced installer in an approved manner.

PROMASEAL® WRAP

Where appropriate, metal pipe and cable tray penetrations through floor/wall should be properly fire stopped using PROMASEAL® Wrap as tested and approved to AS 1530.4 and to the FRL (…/…/…) performance of the element. Please consult Promat WA for more details. All work to be certified by an experienced installer in an approved manner.

PROMASEAL® SupaWrap

Where appropriate, metal pipe and cable tray penetrations through walls should be properly fire stopped using PROMASEAL® SupaWrap as tested and approved to AS 1530.4 and to the FRL (…/…/…) performance of the element. Please consult Promat WA for more details. All work to be certified by an experienced installer in an approved manner.

PROMASEAL® Retrofit Fire Collars

Where plastic pipes penetrate through floor or wall openings, use PROMASEAL® Retrofit Collars as tested to AS 1530: Part 4: 2005 and AS 4072: Part 1: 2005 to maintain the FRL of the element. All work to be certified by an experienced installer in an approved manner.

PROMASTOP® UniCollar

Where plastic pipes penetrate through floor or wall openings, use PROMASEAL® UniCollar as tested to AS 1530: Part 4: 2005 and AS 4072: Part 1: 2005 to maintain the FRL of the element. All work to be certified by an experienced installer in an approved manner.

14

Page 13: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

Fire Rated Penetrations

Specification Statements

PROMASEAL® FCW Wall Collar

Where plastic pipe penetrations through wall openings, use PROMASEAL® FCW Wall Collars as tested to AS 1530: Part 4: 2005 and AS 4072: Part 1: 2005 to maintain the FRL of the element. All work to be certified by an experienced installer in an approved manner.

PROMASEAL® Conduit Collar

Where plastic pipes up to 32mm penetrate through wall openings, use PROMASEAL® Conduit Collar as tested to AS 1530: Part 4: 2005 and AS 4072: Part 1: 2005 to maintain the FRL of the element. All work to be certified by an experienced installer in an approved manner.

PROMASEAL® FWR Retrofit Fire Collars (FLOOR WASTE)

Where plastic pipes used for floor waste, use PROMASEAL® Retrofit Floor Waste Collars as tested to AS 1530: Part 4: 2005 and AS 4072: Part 1: 2005 to maintain the FRL of the element. All work to be certified by an experienced installer in an approved manner.

PROMASNAP® CAST IN Collar (FLOOR WASTE)

Where plastic pipes used for floor waste, use PromaSnap® Floor Waste Collars as tested to AS1530: Part 4 and AS4072: Part 1 to maintain the FRL of the element. All work to be certified by an experienced installer in an approved manner.

NOTES

_____________________________________________________________________________

_____________________________________________________________________________

_____________________________________________________________________________

_____________________________________________________________________________

_____________________________________________________________________________

_____________________________________________________________________________

_____________________________________________________________________________

_____________________________________________________________________________

15

Page 14: Guide to Specifying Fire Penetrations · Fire Rated Penetrations Introduction to Fire Rated Penetrations This document aims to assist Architects, Engineers, Certifiers, Contractors

promatwa.com.au 08 9445 8300