2 6 9 10 11 8 Control Dampers and Fire Dampers Insulated Control Dampers Non-Insulated Control Dampers Framing Jack Shaft Accessories Steel Control Dampers Fire Dampers Volume 1 - March 2010

Jack Shaft Control Dampers - Ventex Incventexinc.com/adm/files/downloads2/alumavent 12 page brochure march16 2010.pdfdamper and features the lowest air leakage rating available.The

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

2

6

9

10

11

8

Control Dampers

and Fire Dampers

Insulated Control Dampers

Non-Insulated Control Dampers

Framing

Jack Shaft

Accessories

Steel Control Dampers

Fire Dampers

Volume 1 - March 2010

Job Photo:University ofSherbrooke

Hospital CenterEmergency Standby

GeneratorSherbrooke, Quebec.

Alumavent’s 3900 Seriesis a premium low leakage insulated control

damper and features the lowest air leakage

rating available.The damper’s thermally

broken blade was developed to reduce the

thermal transfer of heat from one side of

the damper to the other. It minimizes con-

densation on the cold side of the damper

and helps prevent damper from freezing

closed. The thermally broken blade and

extremely low leakage performance of the

3900 greatly reduces the amount of thermal

transfer, significantly increases system effi-

ciencies, and offers increased energy savings.

All of these factors are important to con-

sider with today’s Green building practices.

3900 Insulated Control Dampers

2 Tel.: (905) 857-4700 • Fax: (905) 857-4730 • Toll Free: 1-800-668-7214 • www.ventexinc.com

SuperiorAir Leakage

Performance

SuperiorAir Leakage

Performance

SuperiorAir Leakage

Performance

SuperiorAir Leakage

Performance

SuperiorAir Leakage

Performance

AMCA Certified RatingsAlumavent Inc. certifies that the 3900 SeriesInsulated Parallel Blade Control Dampersshown here are licensed to bear the AMCASeal. The ratings shown are based on testsand procedures performed in accordancewith AMCA Publication 511 and complywith the requirements of the AMCACertified Ratings Program. The AMCACertified Ratings Seal applies to air per-formance ratings and air leakage ratings.

LEAKAGELeakage test was conducted in accordance with AMCA Standard 500-D-98. Holding torque applied was 6 in.-lbs./sq.fton parallel blade dampers. AMCA Standard 500-D-98 states that air leakage is based on operation between 50°F(10°C) and 104°F (40°C).

3960 Standard Installation Duct Frame

Dampers

3

Ratings Based on: AMCA Standard 500-D Intake Ducted Test Figure 5.3 Setup

Tel.: (905) 857-4700 • Fax: (905) 857-4730 • Toll Free: 1-800-668-7214 • www.ventexinc.com

Parallel blade dampers are usedwhen the damper is either open orclosed.

Opposed blade dampers areused to accurately

control the volume of airgoing through

the damper. Tobe used with

modulating actuators.

3961Quick Install Frame –The extruded aluminum hat shapeframe simplifies theinstallation of singlesection and multiplesection dampers significantly reducinglabour costs.

3965BFThermally Broken Frame –Allows the damper to actas a complete thermal barrier stopping thetransfer of heat or

cold along the ductwork.

3967BFSingle Sided flange– The 1” flangearound the perimeter of thisdamper allows for easierinstallation on a wall or on air handling units.

3900 Insulated Control Dampers

4

LinkageSlip proof linkage systemrequires no maintenance for the lifetime of the damper. Castnickel crank arms and 5/16” (8mm) nickel plated steel connec-tion rods that offer superior strength and ensures the actuatortorque is spread evenly across the damper.

Tel.: (905) 857-4700 • Fax: (905) 857-4730 • Toll Free: 1-800-668-7214 • www.ventexinc.com

Dampers

5

3900 Series * STANDARD CONSTRUCTION

Tel.: (905) 857-4700 • Fax: (905) 857-4730 • Toll Free: 1-800-668-7214 • www.ventexinc.com

Depth:4" (101 mm) –3960/39655.25” (133 mm) –3961

Depth with BladesOpen:6.125” (156 mm)

Minimum Height:6” (150 mm) - Single Blade15" (381 mm) -Multiple Blade

Maximum PanelWidth:48" (1219 mm)

Maximum PanelHeight:60" (1524 mm)

Maxximum PanelSize: 20 Sq.Ft.

Maximum SystemPressure:4" w.g. (1 kPa)

OperatingTemperatureRange: -40° to +180° F

Frame: 0.081” (2mm) ExtrudedAluminum

Blade: 0.063” (1.6mm) ExtrudedAluminum filled with2 part polyurethanefoam.

Beariings: 2 pieceacetal bearing. Hexagonouter shell and round

inner sleeve do notallow any metal tometal contact.

Blade Seals: Dualdurometer customdesign bulb seal

Jamb Seals:Extruded Santoprene

Standard MotorInstallation: FieldAdjustable Side ShaftDirect Drive

Linkage:Concealed in Frame(3960/3961)Outside of Frame(3965)

* See Page 9for Available Accessories

The Alumavent3900 Seriesdamper is the smart

choice when selecting

a control damper. You

can rely on its certified

performance, rugged

aluminum construction,

no maintenance linkage

system, and unique frame

designs to save money

from the time it is

installed.

The Standard Nylon BladeEnd Cap maximizes the contactarea of the blade and jamb seals,creating a better seal than the bladeand jamb seal alone. The smoothnylon surface of the end cap alsoensures smooth operation of thedamper and prevents the jamb sealfrom being damaged by the blade.

3165Flanged to Duct Frame – The frame is fasteneddirectly to the flange on the duct. The open area isequal to the duct size. Thismaximizes the free area and is recommended fordampers less than 30”(762 mm) high.

3161Quick Install Frame – The extruded aluminumhat shape frame simplifies the installation of singlesection and multiplesection dampers significantly reducinglabour costs.

3167Single Sided flange– The 1” flangearound theperimeter of thisdamper allows foreasier installationon a wallor on air handling units.

6

3100 Series Air Foil Control Dampers

Tel.: (905) 857-4700 • Fax: (905) 857-4730 • Toll Free: 1-800-668-7214 • www.ventexinc.com

Opposed bladedampers are used to

accurately control the volume of air going

through the damper.To be used with

modulating actuators.

Parallel blade dampers areused when the damper is eitheropen or closed.

3100 SeriesThe Alumavent 3100 is a premium, low leakage, extruded aluminum, airfoil damper. The thin airfoil profile minimizes the pressure drop andnoise through the damper. This makes the 3100 series an excellent

choice for air handlers. The hollow extruded aluminum bladeoffers superior rigidity and minimizes deflection at higher velocities.

3160StandardInstallation Duct Frame

7

s

Tel.: (905) 857-4700 • Fax: (905) 857-4730 • Toll Free: 1-800-668-7214 • www.ventexinc.com

3100 Series * STANDARD CONSTRUCTION

Depth:4" (101 mm) – 3160/31655.25” (133 mm) – 3161

Depth withBlades Open:6.125” (156mm)

MinimumHeight:8” (203 mm) -Single Blade15" (381 mm) -Multiple Blade

MaximumPanel Width:48" (1219 mm)

MaximumPanelHeight:60" (1524 mm)

MaxximumPanel Size: 20Sq.Ft.

MaximumSystemPressure:4" w.g. (1 kPa)

OperatingTemperatureRange: -40° to+180° F

StandardFinish: Mill

StandaardMotorInstallation:6” Side ShaftDirect Drive

Linkage:Concealed inFrame(3160/3161)Outside ofFrame (3165)

Blade EndCap:Nylon

* See Page 9 for Available Accessories

Silicone Blade and Jamb SealsFor extremely cold environments siliconeseals stay flexible to atemperature of -40F (-40C).

Broken FrameA thermally broken framereduces the amount ofthermal transfer from oneside of the damper to theother. The temperaturecan vary as much as 176F (80C) from oneside to the other.

Salt Water ConstructionTo be used in corrosive environments.

The steel components of the linkage are replaced withstainless steel hardware. The blades and frames are

anodized. (Note BF frame construction is not available withSW construction. Parallel blade operation only available).

0 Duct Mount

1 Quick’N’Stall Duct Mount

5 Flanged to Duct Mount

7 Front Flange Mount

8

Naming Convention

Mounting /Naming Convention

Tel.: (905) 857-4700 • Fax: (905) 857-4730 • Toll Free: 1-800-668-7214 • www.ventexinc.com

Flange Frames available for 4000 SeriesSingle Rear Flange:Flange on actuator side of damperSingle Front Flange:Flange on opposite side of actuatorDouble Flange:Flange on both sides of the damper.

Horizontal Jackshafts

9

vention Jack Shaft and Accessories

Tel.: (905) 857-4700 • Fax: (905) 857-4730 • Toll Free: 1-800-668-7214 • www.ventexinc.com

Electric:• Actuators:

Honeywell and Belimoelectric actuators

• 24Vdc, 24Vac, 120Vand 240V all available

with auxiliary switches• Internal and external

mounting.• 2 position (on / off) or

modulating controlwith feedback signal

Manual:• Manual Hand

Quadrants• Chain Operator

Operators

Type STS “Sure Turn System” Is made forindustrial applications where maintenance ondampers is not possible.

The STS features 1” stainless steel precisionshafting. The crank arms are fabricated from2” x 1/4” steel bar, welded to a 2” collar, andfastened to the shaft using a spring pin. Thepush rods are 1/2” diameter, stainless steel,threaded rod, capped with spherical rod endsto drive the damper. The metalized carbonbearings inhibit dirt or debris from gettinginside therefore, no maintenance is required.

Type STS“Sure Turn System”

Type A

Jumpers Field installed jumpers are available to drive a 2 panel damper. Lasercut from 10 Ga galvanized steel it is available to use on dampers under 18 sq.ft.

Vertical Jackshaft Connects two sections of dampers together using 1/2”stainless steel threaded rod and spherical ends.

The 4000 Seriesis Alumavent’s most economical control

damper can be used as a manualdamper as well as standard con-

trol damper in most low tomedium velocity and pressure

HVAC systems.The standardHD frame is roll formedfrom a single piece of16ga. gal. steel to increasethe structural integrityand reduce racking.Thecorners are fastenedtogether using togglelocks that won’tshake loose.

The 16 ga. steelblade features 3 Vgrooves that run thelength of thedamper to increasethe strength of theblade.They are theninstalled in thedamper using custom designed“W” bolts and nylonlock washers thatcan’t come loose.

The 4100is ideal for low leakage

applications due to its dualdurometer blade seals

which do not requireadhesives ormechanical fasten-ers. The com-pressible concavestainless steel jamb

seals ensure a tightseal along the jambs.

The concealed linkagein the frame removes the

linkage from the air stream, andreduces pressure drop.

4000

4100

10

Parallel bladedampers are usedwhen the damper iseither open orclosed.

Tel.: (905) 857-4700 • Fax: (905) 857-4730 • Toll Free: 1-800-668-7214 • www.ventexinc.com

4000 Steel Control Dampers

Standard adjustable drive shaft. The integraldrive shaft can be extended up to 12”it cannot come loose or be lost.

Opposed blade dampersare used to accurately con-trol the volume of air goingthrough the damper. To beused with modulating actuators.

51A Standard

51B B Channel

51C Square Transtion

51CRRound Transition

51COOval Transition

Vertical

Horizontal

11Tel.: (905) 857-4700 • Fax: (905) 857-4730 • Toll Free: 1-800-668-7214 • www.ventexinc.com

pers 5100 Series Fire Dampers

1. Blade: Roll formed 22GA.Galvanized Steel - Interlocking curtain type blade

2. Fusible Link:165°F (73.9°C) Standard212°F (100°C) Optional

3. Link Strap4. Frame: Roll formed 20 GA.

Galvanized Steel with hemmed edge

5. Constant Force Spring6. Lock Ramp

* 4000 Series STANDARD CONSTRUCTION

Depth:5" (127 mm)

Depth with Blades Open:6.375” (162 mm)

Minimum Height:8” (203 mm) - Single Blade14" (356 mm) - Multiple Blade

Maximum Panel Width:48" (1219 mm)

Maximum Panel Height:72" (1829 mm)

Maximmum System Pressure:4" w.g. (1 kPa)

Standard Finish:Mill Galvanized

Standard Motor Installation:Side Shaft Direct Drive - extendableup to 12”

Linkage:Concealed in Frame

* See Page 9 for AvailableAccessories

Fire DampersAlumavent is pleased to introduce

its 1.5 hour UL RatedStandard Curtain Type

Fire Damper.

Fire DamperModel 51A

C US

Distributed by:

Tel.: (905) 857-4700 • Fax: (905) 857-4730Toll Free: 1-800-668-7214

w w w . v e n t e x i n c . c o m

LOUVERS & BACK DRAFT DAMPERS

195 Healey Rd., Bolton, ON L7E 5B2Tel.: (905) 857-4700 Fax: (905) 857-4730

Toll Free: 1-800-668-7214 w w w. ve n t e x i n c . c o m

LOUVERS & BACK DRAFT DAMPERS

Archives of Ontario Building, York University, Toronto, Ontario

See Ventex Cataloguefor more Louvers and Back Draft Dampers

University of Sherbrooke Hospital CenterEmergency Standby GeneratorSherbrooke, Quebec.

Laval Subway Extension,Laval, Quebec