INTRODUCTION TO BUILDING SIMULATIONShreshth Nagpal

Page 2: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions
Page 3: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions
Page 4: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions
Page 5: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions

0

20

40

60

80

100

120

BUILDINGLOADS

PASSIVESTRATEGIES

ACTIVESYSTEMS

RENEWABLEENERGY

UPD

ATED

PRO

GRAM

INTERN

AL

LOAD

S

CO

NSTRU

CTIO

NSPE

CIF

ICATIO

NS

SO

LAR

SH

AD

ING

DAYLI

GH

TH

ARVESTIN

G

NATU

RAL

VEN

TIL

ATIO

N

DESIG

NED

LIG

HTIN

G

AIR

-SID

EH

VAC

SYTEM

WATER-S

IDE

HVAC

SYSTEM

SO

LAR

PH

OTO

VO

LTAIC

S

SM

ALL

-SCALE

WIN

D T

URBIN

ES

GO

AL

FOR 2

010

TARG

ET F

OR 2

030

CARBO

N

NEU

TRALI

TY

EXIS

ITN

GPE

RFO

RM

AN

CE

KBTU

/SF/

YR

OTH

ER P

OTEN

TIA

LTECH

NO

LOG

IES

Page 6: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions
Page 7: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions
Page 8: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions
Page 9: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions

INCIDENT SOLAR RADIATION Average Daily NEW DELHI, IND

rINCIDENT SOLAR RADIATION Average Daily NEW DELHI, IND

INCIDENT SOLAR RADIATION Average Daily NEW DELHI, IND

g y ,

SITE CLIMATE DATA

• LONGITUDE ‐76.47 E

• LATITUDE – 30.44 N

• ALTITUDE ‐ 304‐365 METERS ABOVE MSL

• MONSOON ‐ JULY TO SEPTEMBER

• TEMPERATURE –WINTER ‐ MIN. 1* C ‐ 16* C ( NOV. – JAN.)SUMMER – MIN. 27* C – 44* C ( APRIL – JULY)

• WIND DIRECTION ‐ FROM NORTH WEST TO SOUTH EAST IN WINTER & REVERSE IN SUMMER

monsoon season

Incident Solar

Cloud Cover

month of year

time of day

AVERAGE DAILY INCIDENT SOLAR RADIATION BY ORIENTATION (WH/SQM)

1. HORIZONTAL ROOF2. SOUTH‐WEST FAÇADE3. SOUTH‐EAST FAÇADE4. NORTH‐EAST FACADE

1 3

42

view from south

view from north

Page 10: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions

OUTDOOR COURTYARD

human sensitivity rendering

OUTDOOR COURTYARD

falsecolor

rendering

INDOORSPACE

human sensitivity rendering

INDOORSPACEfalsecolor

rendering

BUILDING PERFORMANCE ANALYSIS 

1.  The  solar  radiation  analysis  on  the  previous page  clearly  shows  that  roof  surfaces  receive  the 

maximum average daily radiation through the year  

followed by the south‐west facades.

2.  The  energy  use  characterization  of  a  baseline design  building  defined  by  performance 

parameters mandated  by  ASHRAE  standard  90.1‐

2004 illustrates that envelope loads result in almost 

half of the total cooling energy requirements of the 

building.

3.  Daylight  level  analysis  for  both  outdoor  and 

indoor  spaces  illustrates  that  there  may  be 

potential  discomfort  conditions  caused  due  to 

excessive radiation  and high contrast situations.

To optimize  the performance of  the building,  the 

design  intent  should  be  directed  towards  the 

following aspects:

•Reduction  in  direct  solar  radiation  incident  on building surfaces – especially during summers.

•Glare  control  and  maximum  visual  comfort  in 

both  indoor  and  outdoor  spaces  throughout  the 

year.

•Optimum  daylight  availability  in  regularly 

occupied spaces for maximum part of the year.

ENVE

LPE LO

ADS –56%

The chart on the right presents the annual 

energy use breakdown by end use and illustrates that half of the building energy is consumed by 

HVAC end uses comprising of Cooling, Heat Rejection, Pumping and Ventilation 

Fans.

Further Cooling load breakdown, as shown 

below, also suggests that 56% of the cooling load in 

the project is directly affected by the design of 

the building envelope. The rest is caused by heat gain from internal loads such as 

lighting and equipment.

ENERGY USE CHARACTERIZATION FOR ASHRAE CASE AND COMPARISON WITH DESIGNED ENVELOPE

Page 11: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions

OPTION I

OPTION III

OPTION II

BIPV OPPORTUNITY

+40%Frit @ 40%coverage

U: 0.25 (0.16cg)SHGC/SC: 0.31/0.36Tvis: 0.48

U: 0,41 (0.32cg)SHGC/SC: 0.27/0.31Tvis: 0.63

U: 0.32 (0.23cg)SHGC/SC: 0.09/0.10Tvis: 0.10

U: 0.41(0.32cg)SHGC/SC: 0.32/0.37Tvis: 0.70(0.58effective)Low E, Low Iron,

Color Neutral IGU

Low E, High VisibilityColor Neutral IGU

Heat Mirror InsulatedAqua+Clear, Low E

R-10 MASS WALLSR-18 ROOF

R-13 SPANDREL

R-18 ROOFR-10 WALLS

R-18 ROOFR-10 WALLS

R-13 SPANDREL

PV OPPORTUNITY

GY, kBTU/sqft/year

EXTERIOR40%

C

0

50

100

150

200

EXISTING BUILDING

PROPOSED DESIGN

HIGH-PER ENVELOPE

AGGRESSIVE LIGHTING

DAYLIGHT HARVESTING

NORMALIZED SITE ENERGY, kBTU/sqft/year

49%

kBTU

/sqf

t/ye

ar

PERFORMANCETARGET

EXTERIOR

STEAM DHW

FANS

PUMPS

HEAT REJECT

STEAM COOL

ELEC COOL

STEAM HEAT

ELEC HEAT

EQUIPMENT

LIGHTING

47%46%

60%

40%

Page 12: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions

open working areaopen working area

conferenceconference

cabincabincabincabin

cabincabin

cabincabin

cabincabin

lobbylobby

cabincabin

mdmd cabincabin

storestore

cabincabin‐‐55

cabincabin‐‐44

cabincabin‐‐11cabincabin‐‐22cabincabin‐‐33lobbylobby

open working areaopen working area

EXISTING LOWER FLOOR PLAN RECOMMENDED LOWER FLOOR  PLAN OPTION

EXISTING UPPER FLOOR PLAN RECOMMENDED UPPER FLOOR PLAN OPTION

DAYLIGHT AUTONOMY STUDY WITH RECOMMENDED  SOUTH AND WEST WALL DESIGN

REDUCED WEST RECEIVED RADIATION

INCR

EASED SOUTH

 REC

EIVE

DAYLIGHT

DAYLIGHT AUTONOMY STUDY WITH DESIGNED SOUTH AND WEST WALL DESIGN

Page 13: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions

The graphs on the left illustrate the optimization analysis for appropriate window heights. As can be  seen,  as window  height  is  reduced  daylight levels  reduce  resulting  in  increased  lighting consumption. 

Although  there  is a  reduction  in  thermal  losses with  reduced windows,  there  is  an  increase  in cooling  energy  because  of  the  lighting associated heat gains. 

The  trade‐off  between  thermal  performance and  lighting  performance  was  analyzed  for various  window  heights  to  determine  the optimum window size. 

It was found that at window heights equal to 7’, there  is  minimum  total  energy  consumption along with comfortable day light levels inside. 

ENERGY CONSUMPTION WITH DIFFERENT WINDOW HEIGHTS

LIGHTING ELECTRICITY CONSUMPTION (MWh)

TOTAL ELECTRICITY CONSUMPTION WITH DIFFERENT WINDOW OPTIONS (MWh)

HVAC ELECTRICITY CONSUMPTION (MWh)

Page 14: INTRODUCTION TO BUILDING SIMULATION - Elcoma...building. 3. Daylight level analysis for both outdoor and indoor spaces illustrates that there may be potential discomfort conditions

INCIDENT SOLAR RADIATION Average Daily NEW DELHI, IND

INCIDENT SOLAR RADIATION Average Daily NEW DELHI, IND

g y ,