8/12/2019 InteliNano-AMF-1.5 - Fast User Guide
1/2
ComAp, a.s.Kundratka 2359/17180 00, Praha 8Czech Republic
InteliNano-NT AMF, SW version 1.5, ComApSeptember 2013 1InteliNano-NT-AMF-1.5-Fast User Guid.pdf
CAN INTERFACE
MAINS VOLTAGE
MEASUREMENT
T20 = Neutral
T21 = Phase 1
T22 = Phase 2
T23 = Phase 3
GENERATOR VOLTAGE
MEASUREMENT
T16 = Neutral
T17 = Phase 1
T18 = Phase 2
T19 = Phase 3
USB interface
L
COM
H
INTPUT TERMINALS
T10 = COM for analog inputs
T11 = binary input
T12 = binary input
T13 = binary/analog inputLow Fuel Level
T14 = binary/analog inputCoolan Temperature
T15 = binary/analog inputOil Pressure
OUTPUT TERMINALS
T04 = binary outputStarter (6A)
T05 = binary output - Fuel Solenoid (6A)
T06 = binary output (500 mA)
T07 = binary input/output (500 mA)
T08 = binary output (500 mA)
T09 = binary output (500 mA)
POWER SUPPLY, D+
T01 = BATT -
T02 = D+
T03 = BATT +
GECU
D IE SE L / GA SO LI NE EN GI NE G EN ER AT OR
LOAD
FuelSolenoid
Battery
Sarter
FuelLevelAnalog
CoolantTemperatureAnalog
OilPressureAnalog
D+
-
+
GCB MCB
GCB
MCB
Alarm
ReadyToLoad
FuelSolenoid
Starter
COM
RemoteStartAndLoad
EmergencyStop
CAN
LCOMHU
SB
Battery+
Battery-
D+
PC
L1
L2
L3
N
InteliNano NTAMF
Fast User Guide
Typical wiring diagram
Accessing the setup mode
Ensure the engine is stopped and the controller is in Manual mode (green LED above buttonAutois turned off).If you have not configured the custom initialization (init) screen then press and hold Stopbutton, then briefly press buttonand then Auto.
If you have already created your own init screen then press and hold Stopbutton and then briefly press , the custom init screen will appear, keep holding the Stop
button. Then pressto switch LCD to default init screen, and then press Auto.To move up and down in the setup menu useandbuttons. PressStartbutton to select orStopbutton for exit.
Basic set t ings Output set t ings
Engine parameters and protect ions Input set t ings
Generator protect ions ECU setting
AMF(Auto Mains Failure) set t ings Info
Outputs and inputs
Outputcode
Output source Type Terminal assignment
O00 Not Used binary T04, T05, T06, T07, T08, T09
O01 Starter binary T04
O02 Fuel Solenoid binary T04, T05, T06, T07, T08, T09
O03 Stop Solenoid binary T04, T05, T06, T07, T08, T09
O04 Alarm binary T04, T05, T06, T07, T08, T09
O05 GCB Close/Open binary T04, T05, T06, T07, T08, T09O06 MCB Close/Open binary T04, T05, T06, T07, T08, T09
O07 Ready To Load binary T04, T05, T06, T07, T08, T09
O08 Prestart binary T04, T05, T06, T07, T08, T09
O09 ECU Power Relay binary T04, T05, T06, T07, T08, T09
O10 Choke binary T04, T05, T06, T07, T08, T09
O11 Glow Plugs binary T04, T05, T06, T07, T08, T09
Normally Open ContactoutputNormally Open Contact - inputbutton
Normally Closed ContactoutputNormally Closed Contactinputbutton
User curves
I21 I23 I25
VDO Level % VDO 5 Bar VDO 40-120 C
Datcon Level % VDO 10 Bar VDO 50-150 C
Datcon 5 Bar Datcon High C
Datcon 7 Bar Datcon Low C
Datcon 10 Bar
Not selected Not selected Not selected
Inputcode
Input source Type Terminal assignment
I00 Not Used binary T07, T11, T12, T13, T14, T15
I01 Emergency Stop binary T07, T11, T12, T13, T14, T15
I02 Remote Start/Stop binary T11
I03 Remote Start And Load binary T11
I04 Access Lock binary T07, T11, T12, T13, T14, T15
I05 AMF Block ed binary T07, T11, T12, T13, T14, T15
I06 MCB Feedback binary T07, T11, T12, T13, T14, T15
I07 GCB Feedback binary T07, T11, T12, T13, T14, T15
I10 External Warning 1 binary T07, T11, T12, T13, T14, T15
I11 External Warning 2 binary T07, T11, T12, T13, T14, T15
I12 External Warning 3 binary T07, T11, T12, T13, T14, T15
I13 External Shutdo wn 1 binary T07, T11, T12, T13,T14, T15
I14 External Shutdo wn 2 binary T07, T11, T12, T13, T14, T15
I15 External Shutdo wn 3 binary T07, T11, T12, T13, T14, T15
I20 Low Fuel Level binary T07, T11, T12, T13, T14, T15
I21 Fuel Level Analog analog T13, T14, T15
I22 Low Oil Pressure binary T07, T11, T12, T13, T14, T15
I23 Oil Pressure Analog analog T13, T14, T15
I24 High Coolant Temperature binary T07, T11, T12, T13, T14, T15
I25 Coolant Temperature Analog analog T13, T14, T15
I29 Fuel Level SD Binary T07, T11, T12, T13, T14, T15
DimensionsCase dimensions:118mm x108mm x 40mm
Panel Cutout: 96mm x 96mm
WARNING!If D+ is not used, connect this terminal to battery positive!
8/12/2019 InteliNano-AMF-1.5 - Fast User Guide
2/2
ComAp, a.s.Kundratka 2359/17180 00, Praha 8Czech Republic
InteliNano-NT AMF, SW version 1.5, ComApSeptember 2013 2InteliNano-NT-AMF-1.5-Fast User Guid.pdf
Setpoints
Useandbuttons to move or change value. Startbutton to select setpoint or confirm changes and Stopbutton to go back.
Basic set t ings
Setpointcode
Setpoint name
B01 Nomin al Voltage Ph-N 80480 V
B02 Nomin al Voltage Ph-Ph 80600 V
B03 Nominal Frequency 50 Hz (1), 60 Hz (2)
B04 Connect ion Type
Mono Phase (1), SplitPhase (2),3Ph3Wire (3), 3Ph4Wire (4),
Autodetect (5)
B05 Units FormatMetric unit format (1), US unitformat (2)
B06 AMF Funct ion Disable (1), Enable (2)
B07 Zero Power Mode Delay 0-360 min
B08 Light Tower Mode Disable (1), Enable (2)
B09 Nomin al RPM 100-4000
Engine parameters and protect ions
Setpointcode
Setpoint name
E01 Prestart Time 0-600 s
E02 Maximum Cranking Time 0-60 s
E03 Cooling Time 0-3600 s
E04 Oil Pressure Shutdown 0-10 Bar
E05 Coolant Temperature Shutdown 0 -150 C
E15 Fuel Level Shutdown 020%
E06 Battery Undervo ltage 840 V
E07 Warnin g Maintenance 010000 h
E08 Oil Pressure Starter Disengagem ent Disable (1), Enable (2)
E09 Chok e Time 0 3600 s
E10 Minim al Stabilization Time 1 300 s
Generator protect ions
Setpointcode
Setpoint name
G01 Generator Overvoltage Shutdown G02200 %
G02 Generator Undervoltage Shutdown 0 - G01%
G03 Generator Overf requency Shutdown G04130 %
G04 Generator Underf requency Shutdown 0G03%
AMF(Auto Mains Failure) set t ings
Setpointcode
Setpoint name
A01 Emergenc y Start Delay 0600 s
A02 Mains Return Delay 13600 s
A03 Mains Overvoltage A04150 %
A04 Mains Undervoltage 50A03
A05 Mains Overf requency A06150 %A06 Mains Underf requency 50A05 %
To apply all changes return to the main setup menu and restart the controller by pressing theStopbutton.
Alarms and Events
Events
Mains Return
Mains Fail
Manual Start
Remote Start
AMF Start
Manual Stop
Remote Stop
AMF Stop
Auto On
Auto Off
Power On
Island Operation
Warnings
Warning Maintenance
Low Bat tery
Low Fuel Level
External Warning 1
External Warning 2
External Warning 3
ECU Communicat ion Error
MCB Fail
Mains CCW Rotat ion
Shutdowns
Emergency Stop
Overspeed
Underspeed
Low Oil Pressure
High Coolant temperature
External Shutdown 1
External Shutdown 2
External Shutdown 3
GCB Fail
Generator Overvoltage
Generator Undervoltage
Generator Overf requency
Generator Underf requency
Generator CCW Rotation
Start Fail
Stop Fail
Battery Flat
Voltage Autodetect
Fuel Level SD
ECU
For ECU configuration use PC software NanoEdit. For more details see InteliNano AMF Reference Guide.Technic al data
Power supply range 6-36 VDC
Power supply drop-out immunity 100 ms
Power consumption 35295 mA
Zero Power Mode consumption 52 - 344 A
Operating temperature -20... 70 C
Operating humidity 95 % non-condensing (IEC/EN 60068-2-30)
Protection degree (front panel)IP65 with GASKET 4x405 only
IP50 without gasket
Storage temperature -30... 80 C
Binary outputs (up to 6)
Low current outputs (4) 500 mA
High current output (2) 6 A (long term) / 10 A (short term)
Total output current 10 A (long term) / 16 A (short term)
Binary inputs (up to 6)
Input resistance 1,5 k
Closed contact voltage 3,5 V
Analog inputs (up to 3)
Galvanic insulation Not insulated
Electrical range 0 - 2500 k
Resolution 0,1
Precision 2 % 3
Charging alternator preexcitation circuit
Excitation current 100 mA
Charging fail threshold 80 %
Generator/Mains measurements
Measurement input 3ph generator voltage, 3ph mains voltage
Measurement type True RMS
Voltage range 480 V Ph-Ph (277 V Ph-N)
Max. measured voltage 340 V Ph-NVoltage accuracy 1 %
Frequency range 4070 Hz
Frequency accuracy 1 %