Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
1
Integrated control design of converters in power electronics embedded grids
Prof. Pericle Zanchetta
Power Electronics, Machines and control (PEMC) Group Faculty of Engineering
University of Nottingham – UK
ENER 2019 – University of Talca, Chile
Research Team
Prof. Pericle Zanchetta Prof. Patrick Wheeler Dr. Andrea Formentini
David Dewar
PhD student
Kang Li
PhD student
Power electronics in microgrids
• Large penetration of renewables in
the power system • Several power converters operating
in the same network • Each power converter has local
intelligence and control
The complex interactions
between control loops require
accurate design methods
More Electric Aircraft power distribution
The electrical system on aircraft
is supplied by a fixed voltage,
variable frequency generator.
AC and DC grids at different
voltage levels are generated
from the main distribution grid
by means of power electronics
systems.
Highlighted, the 400Hz grid is
main supply to many non-
propulsive loads, which need
more power converters.
Proposed solution:
Design system controls with full consideration to all system dynamics and sub-
system interactive behaviour.
Optimal Performance across sub-systems achieved.
Mitigation of sub-system interactions.
Reduction in required cross-controller communication through decentralized
approach.
These power electronics subsystems tend to interact with each other in an
undesired way.
To mitigate interactions, usually large passive filters are installed between
subsystems. THIS INCREASES WEIGHT, VOLUME and DECREASES
EFFICIENCY
Integrated Global control design
Analysed Test System (aircraft 400Hz)
A standard 3-phase active Voltage Source
Inverter (VSI).
LCR Filter connected to the output, and fed
by solid DC source on its input.
This generates the 3-phase grid @ Nominal
400Hz
A standard 3-phase active front end (AFE)
rectifier.
LR filter on 3-phase input. DC-Link
capacitor across output terminals.
The load (RL) can consist of either resistive
loads or a Constant Power Loads (CPL).
VSI System Modelling
In AC systems, the common approach to controller
design is to use the DQ reference frame.
The expressions for the VSI in DQ frame can be
represented in the state-space as:
vsi vsi vsi vsi vsi vsi vsi
vsi vsi vsi
x A x B u G d
y C x
d
vsi
q
mu
m
ad
vsi
aq
Id
I
𝑥𝑣𝑠𝑖 = 𝐼𝑖𝑑 𝑉𝑐𝑑 𝐼𝑖𝑞 𝑉𝑐𝑞 𝑇
AFE System Modelling
The expressions for the AFE in DQ frame can
be represented in the state-space as indicated
below
𝑥 𝑎𝑓𝑒 = 𝐴𝑎𝑓𝑒𝑥𝑎𝑓𝑒 + 𝐵𝑎𝑓𝑒𝑢𝑎𝑓𝑒 + 𝐺𝑎𝑓𝑒𝑑𝑎𝑓𝑒
𝑦𝑎𝑓𝑒 = 𝐶𝑎𝑓𝑒𝑥𝑎𝑓𝑒
cd
afe
cq
Vd
V
𝑥𝑎𝑓𝑒 = 𝐼𝑎𝑑 𝐼𝑎𝑞 𝑉𝑑𝑐𝑎𝑇
𝑢𝑎𝑓𝑒 =𝑝𝑑𝑝𝑞
H2 Global Optimization
A multivariable state feedback approach, and in particular H2 Optimal Control, was
chosen as the control design method for such a system with many interacting states.
1. H2 control is relatively simple to tune, in order to get the desired dynamic
performance across all states.
2. It has very close roots to Robust controls in that the use of Lyapunov functions are
employed to verify stability of the system. Also a version of this controller
synthesis called H2/H∞ could be applied if further system robustification is desired.
3. Wide variety of mathematical software tools can be used to synthesise this
control.
4. Design is simple and well understood. To the designer, only the knowledge of the
state-space system is required to develop this control.
H2 Global Optimization Controller Synthesis
P state-space plant of the system
to be controlled.
K global optimal controller to be
found.
x state of the system
u system inputs
y system outputs
w plant disturbances
z performance output
During the design, disturbances are generally
neglected, thus D11 , D21 are set to 0.
D22 is the feedforward matrix, and as no
feedforward is incorporated, it is also set to 0.
B1 is disturbance input matrix. As all states can be
influenced, it is therefore the identity matrix.
C2 is a matrix which describes all measurable
states. As all states can be measured directly,
this is made an identity matrix.
C1 & D12 are the tuning terms.
H2 Global Optimization Integral States and Inputs
𝑥 = 𝐼𝑖𝑑 𝑉𝑐𝑑 𝐼𝑖𝑞 𝑉𝑐𝑞 𝐼𝑎𝑑 𝐼𝑎𝑞 𝑉𝑑𝑐𝑎 𝝎𝑽𝒄𝒅𝝎𝑽𝒄𝒒
𝝎𝑰𝒊𝒒 𝝎𝑽𝒅𝒄𝒂
𝑇
It is important for systems to achieve zero-steady state error for critical control terms.
Integral states (ωx) are then incorporated as system states.
These states are used to force the smallest errors to the reference demands to be
corrected by the control over time.
𝑢 = 𝑚𝑑 𝑚𝑞 𝑝𝑑 𝑝𝑞
The inputs to the system are the modulation indexes defined as such in DQ frame
m → VSI duty, p → AFE Duty.
The aim of the optimization is to produce a
stable set of feedback gains to minimize
the effects an outside disturbance has on
overall the performance on the system.
H2 Controller Design – Problem Matrices
𝐴 =𝐴𝑣𝑠𝑖 𝐴𝑐𝑣
𝐴𝑐𝑎 𝐴𝑎𝑓𝑒
Avsi and Aafe details the state equation of the VSI and AFE, including integral
states for zero steady state error
Acv and Aca details the coupling terms between VSI and AFE
Bvsi and Bafe details the input equations equation of the VSI and AFE
𝐵2 =𝐵𝑣𝑠𝑖 00 𝐵𝑎𝑓𝑒
H2 Controller Design – Notional System
The control scheme for the H2 is nothing special as opposed to other controllers.
However, to avoid direct communication being required between converters, a
decentralized controller is a must.
Therefore, K in the optimization is constrained to take the form as shown.
This ensures each control is optimized to the system as a whole by H2 , but also each
control is dependant only on its states.
𝐾 =𝑲𝑽𝑺𝑰 00 𝑲𝑨𝑭𝑬
Experimental results
VSI AFE
C 10µF Cdc 100µF
R 300mΩ Ra 0.8Ω
L 1mH La 565µH
Vdci 290V Pl 1kW
Reference Values
Vcd-ref 100* 2 V Iaq-ref 0A
Vcq-ref 0V Vdc-ref 400V
fswitching 10kHz
fsample 20kHz
AC Grid Frequency
f 400Hz
H2 Controller Design Experimental Performance
At 0.05s, a 1kW step load is applied
across the AFE output terminals.
The dynamics of the H2 control in the
DQ frame are shown to be very fast,
with only slight overshoot across each
of the states.
1. DC-Link voltage dropped only 13V.
2. VSI voltages has a minor transient
of 3V, but the grid voltages are held
stiff. As expected from grid
generator.
3. The whole system reaches
equilibrium subject to large
disturbance after only 5ms.
System Scalability
The H2 controller synthesis allows easy integration of multiple other sub-systems to
be optimized to the global system
Requirements:
Expansion of states to incorporate new subsystem behaviour, and new inputs to
the system (Simple expansion of A and B matrices)
Expansion of the gain matrix K - Simple addition of new constraints to K for an
additional independent controller
System Scalability – Scaled Up Matrices
Green terms define new AFE being incorporated onto the grid
Please note for simplicity, the PLL has not been included in these state equations.
System Scalability – Performance
Systems can
run
independently
Little
interaction
between
subsystems
Fast dynamic
responses
Step loads on AFE1 of 1kW at 0.011s, and on AFE2 of 500W at 0.041s.
System Scalability – Comparison with PI
Vcd and Vcq
experience
noticeable
transient
fluctuations
interactions
can be
observed
across all
states during
transients
Clearly show
H2
improvement Step loads on AFE1 of 1kW at 0.011s, and on AFE2 of 500W at 0.041s.
Optimal H2 Controller Synthesis by System Identification
Optimization of converter in an a
pre-existent grid
System parameters could
be unknown
Other converter controllers
may have unknown
performances
Likely industrial implementation of the H2 Decentralized Controller
System identification
Newly installed converter can send out voltage and current perturbations
Analyse the systems transfer function characteristics to estimate a state-space
representation of system
Optimize controller using H2 based on estimated system response.
Optimal H2 Controller Synthesis by System Identification
Pseudo Random binary signals are injected from the VSI into the AFE to ideally
simulate an infinite frequency range. AFE input voltages and currents are recorded.
Transfer functions including cross-coupling terms are then obtained
State-space representations of the Transfer functions can then be extrapolated.
Optimal H2 Controller Synthesis by System Identification - Performance
Control synthesised from the
identification of the
experimental setup
outperforms the control
optimized with the nominal
model.
Where commercial system
parameters are not be
available, the process of
system identification allows
global optimal controls to be
developed when integrating
converters into unknown
electrical systems. Blue – VSI independently optimized H2 Red – VSI optimized with Nominal AFE
Yellow – VSI optimized with identified AFE
Conclusions
The H2 Optimization Technique has shown performance improvement over traditional
control methods
Increased Robustness
Faster Dynamic Performance
Maintain stability and performance under smaller passive filters (System
weight reduction)
Expandability to additional sub-systems and loads
Having developed a working system, one can easily expand on the optimization
matrices to incorporate additional subsystems
Each subsystem shares the effects of interaction mitigation and Increased
Performance and robustness
Applicability on a larger size grid
Inclusion of PLL in the control optimization
Proved implementation into real practical applications, with impedance estimation