Instrument Transformers 2009-7

Embed Size (px)

Citation preview

  • 7/28/2019 Instrument Transformers 2009-7

    1/80

    Instrument Transformers

    For currents greater than 100A and

    voltages higher than 500V, it is difficult to

    construct ammeters and current coils of

    wattmeters, energy meters and relays

    carrying alternating currents greater than

    100A.

    Specially designed transformers knownas instrument transformers are used

    for this purpose.

  • 7/28/2019 Instrument Transformers 2009-7

    2/80

    Instrument Transformers

    Protection or metering devices have to

    receive data on electrical values (current or

    voltage) from the equipment to be protected.

    For technical, economic and safety reasons,this data cannot be obtained directly on the

    equipments. Intermediary sensors have to be

    used. Current transformers and Voltage

    transformers.

    .

  • 7/28/2019 Instrument Transformers 2009-7

    3/80

    Instrument Transformers

    For currents greater than 100A and

    voltages higher than 500V, it is difficult to

    construct ammeters and current coils of

    wattmeters, energy meters and relays

    carrying alternating currents greater than

    100A.

    Specially designed transformers knownas instrument transformers are used

    for this purpose.

  • 7/28/2019 Instrument Transformers 2009-7

    4/80

    Instrument Transformers

    These devices carry out the functions of:

    Reducing the size of value to be measured

    Providing galvanic separation

    Supplying the power needed to process thedata, or even for the protection device to work.

  • 7/28/2019 Instrument Transformers 2009-7

    5/80

    Instrument Transformers-

    As transformers, they areelectromagnetic devices

    By using instrument transformers,

    electrical instruments have beenstandardized to operate on 110V and 5Aor 1A.

    They are essential parts of manyelectrical systems, and are used for

    Measuring (metering) and

    Monitoring (relaying) devices.

  • 7/28/2019 Instrument Transformers 2009-7

    6/80

    Instrument Transformers (DO)

    The quality of instrument transformers

    will affect directly the overall accuracy

    and performance of these metering

    and monitoring systems.

    Instrument transformer performance is

    critical in protective relaying, since the

    relays can only be as good as theinstrument transformers.

  • 7/28/2019 Instrument Transformers 2009-7

    7/80

    Basic Function of Instrument

    Transformers

    To change the magnitude (but not the

    nature) of the quality (voltage or current)

    being measured to a suitable level for

    use with standard instruments (protectiverelays, metering equipment, etc).

    To provide insulation between primary

    and secondary circuit for equipment andpersonnel safety

  • 7/28/2019 Instrument Transformers 2009-7

    8/80

    Types of Instrument

    Transformers

    Instrument transformers are oftwo

    types,depending upon whether it is used

    to excite the current or voltage coil of the

    measuring instrument

    Current Transformers- CTs

    Voltage Transformers VTs (also

    referred to as Potential Transformers,

    PTs).

  • 7/28/2019 Instrument Transformers 2009-7

    9/80

    Types of Instrument

    Transformers (Contd)

    Both of these types act as insulators betweenhigh-voltage primary and low-voltagesecondary.

    The primary of the VT is connected either line-to-line-to-neutral, and the current that flowsthrough its winding produces a flux in the core.

    The ratio of primary to secondary voltage is in

    proportion to the turns of ratio and will usuallyproduce 110-120V at the secondary terminalswith rated primary voltage applied.

  • 7/28/2019 Instrument Transformers 2009-7

    10/80

    Accuracy of Instrument

    Transformers

    To be a useful part of a measurement system,

    instrument transformers must change the

    magnitude of the quantity being measured

    without introducing any excessive unknownerrors.

    The accuracy of an instrument transformer

    must either be of a known value, so that errors

    may be allowed for, or the accuracy must besufficiently high that errors introduced by the

    instrument transformer may be ignored.

  • 7/28/2019 Instrument Transformers 2009-7

    11/80

    Factors Affecting Accuracy of

    Instrument Transformers

    Design of the instrument transformer

    Circuit conditions such as voltage,

    current and frequency

    Burden connected to the secondary

    circuit of the transformer

  • 7/28/2019 Instrument Transformers 2009-7

    12/80

    Burden of Instrument

    Transformers

    In instrument transformer operations, the

    primary quantities are reduced by the

    turns ratio to provide a secondary current

    or voltage to energize protective relaysand other equipment.

    The totality of the impedances of the

    loads connected to current or voltagetransformers are referred to as burden.

  • 7/28/2019 Instrument Transformers 2009-7

    13/80

    Burden of Instrument

    Transformers (Do)

    The burden consists of the impedances

    of the following:

    Secondary winding of the instrument

    transformer

    Interconnecting leads

    Relay and/or other connected devices.

  • 7/28/2019 Instrument Transformers 2009-7

    14/80

    Burden of Instrument

    Transformer (Do).

    For the devices, the burdens are usually

    expressed in volt-amperes at a specified

    current or voltage.

    Thus for CTs or VTs, if Zb is the total

    connected burden impedance and is the

    volt-ampere burden, then the following

    burdens are obtained for CTs and VTs.

  • 7/28/2019 Instrument Transformers 2009-7

    15/80

    Rated Characteristics of CTs

    Rated primary current.

    Rated short time current (primary)

    Rated secondary current. Rated exciting current.

    Rated burden.

    Insulation level (primary).

  • 7/28/2019 Instrument Transformers 2009-7

    16/80

    CTS Characteristics ( Do)

    Current error or ratio error.

    Phase angle error.

    Composite error. Accuracy class.

    Over current factor.

  • 7/28/2019 Instrument Transformers 2009-7

    17/80

  • 7/28/2019 Instrument Transformers 2009-7

    18/80

  • 7/28/2019 Instrument Transformers 2009-7

    19/80

  • 7/28/2019 Instrument Transformers 2009-7

    20/80

  • 7/28/2019 Instrument Transformers 2009-7

    21/80

  • 7/28/2019 Instrument Transformers 2009-7

    22/80

  • 7/28/2019 Instrument Transformers 2009-7

    23/80

  • 7/28/2019 Instrument Transformers 2009-7

    24/80

  • 7/28/2019 Instrument Transformers 2009-7

    25/80

  • 7/28/2019 Instrument Transformers 2009-7

    26/80

  • 7/28/2019 Instrument Transformers 2009-7

    27/80

  • 7/28/2019 Instrument Transformers 2009-7

    28/80

  • 7/28/2019 Instrument Transformers 2009-7

    29/80

  • 7/28/2019 Instrument Transformers 2009-7

    30/80

  • 7/28/2019 Instrument Transformers 2009-7

    31/80

  • 7/28/2019 Instrument Transformers 2009-7

    32/80

  • 7/28/2019 Instrument Transformers 2009-7

    33/80

  • 7/28/2019 Instrument Transformers 2009-7

    34/80

  • 7/28/2019 Instrument Transformers 2009-7

    35/80

  • 7/28/2019 Instrument Transformers 2009-7

    36/80

  • 7/28/2019 Instrument Transformers 2009-7

    37/80

  • 7/28/2019 Instrument Transformers 2009-7

    38/80

  • 7/28/2019 Instrument Transformers 2009-7

    39/80

  • 7/28/2019 Instrument Transformers 2009-7

    40/80

  • 7/28/2019 Instrument Transformers 2009-7

    41/80

  • 7/28/2019 Instrument Transformers 2009-7

    42/80

  • 7/28/2019 Instrument Transformers 2009-7

    43/80

  • 7/28/2019 Instrument Transformers 2009-7

    44/80

  • 7/28/2019 Instrument Transformers 2009-7

    45/80

  • 7/28/2019 Instrument Transformers 2009-7

    46/80

  • 7/28/2019 Instrument Transformers 2009-7

    47/80

  • 7/28/2019 Instrument Transformers 2009-7

    48/80

  • 7/28/2019 Instrument Transformers 2009-7

    49/80

  • 7/28/2019 Instrument Transformers 2009-7

    50/80

    Example 1: Sample Calculation

  • 7/28/2019 Instrument Transformers 2009-7

    51/80

    Example 1: Sample Calculation

    of CT Burden

    A current transformer rated 30VA has a

    secondary rated current of 5A and

    impedance of 0.211 ohms.

    If this CT supplies a relay through as

    lead of resistance 0.4 ohm, calculate the

    relay burden.

    Solution 1: Calculation of CT

  • 7/28/2019 Instrument Transformers 2009-7

    52/80

    Solution 1: Calculation of CT

    Burden

    The Permissible burden of the CT isZB=VA = 30 = 1.2

    12 52

    ZB= relay burden+ lead resistance + CTsecondary impedance

    Relay burden = ZBlead resistance-CT secondary

    impedances= 1.2-0.4-0.-0.211

    = 0.589

  • 7/28/2019 Instrument Transformers 2009-7

    53/80

    CTs For Relay Applications

    Current transformers, which step down

    primary currents to lower, safer,

    measurable values, are required for

    Indicating and graphic ammeters

    Energy meters and wattmeter (kWh and

    kW meters)

    Telemetering

    Protective relays.

  • 7/28/2019 Instrument Transformers 2009-7

    54/80

    CTs For Relay Application- (Do)

    A CT has a high-current primary winding

    which is connected in series with the line

    or load whose current is to be metered,

    Whilst its secondary winding isconnected in series with the current coil

    of the meter (e.g. ammeter, wattmeter,

    energy meter, relay, etc).

  • 7/28/2019 Instrument Transformers 2009-7

    55/80

    CTs For Relay Applications- (Do)

    The primary current rating should be

    selected from standardized values.

    The value of the rated secondary current

    shall be either 1A or 5A.

  • 7/28/2019 Instrument Transformers 2009-7

    56/80

    Some Standard CT Radios

    CT Ratio CT Ratio CT Ratio

    50:5 300:5 800:5

    100:5 400:5 900:5

    150:5 450:5 1000:5

    200:5 500:5 1200:5

    250:5 600:5

  • 7/28/2019 Instrument Transformers 2009-7

    57/80

    Selection Criterion For CT Ratio

    The major criterion for the selection is almost

    invariably the maximum load current

    In other words, the CT ratio should be selected

    such that the CT secondary current atmaximum load should NOT exceed the

    continuous current rating or the thermal limits

    of the connected relay and equipment.

    This is particularly applicable to phase-typerelays where the load current flows through

    the relays.

  • 7/28/2019 Instrument Transformers 2009-7

    58/80

  • 7/28/2019 Instrument Transformers 2009-7

    59/80

  • 7/28/2019 Instrument Transformers 2009-7

    60/80

  • 7/28/2019 Instrument Transformers 2009-7

    61/80

  • 7/28/2019 Instrument Transformers 2009-7

    62/80

  • 7/28/2019 Instrument Transformers 2009-7

    63/80

    VT F R l A li ti

  • 7/28/2019 Instrument Transformers 2009-7

    64/80

    VTs For Relay Applications

    Voltage transformers, which step down

    system voltages to sufficiently low, safer,

    measurable values, are required for

    Indication of the voltage conditions. Energy meters and watt meters (kWh

    and kW meters)

    Protective relays

    Synchronizing

    Types of VTs for Protective

  • 7/28/2019 Instrument Transformers 2009-7

    65/80

    Types of VTs for Protective

    Relaying.

    Voltage transformers have wound

    primaries that are

    Either connected directly to the power

    systems (VTs)

    Or across a selection of capacitor string

    connected between phase and ground,

    that is, coupling-capacitor voltagetransformers (CCVTs)

    P i t T N t Ab t VT

  • 7/28/2019 Instrument Transformers 2009-7

    66/80

    Points To Note About VTs

    VTs are used at all power system voltages,and

    are usually connected to the bus.

    Usually the CCTVs are connected to the line,

    rather than to the bus, because the couplingcapacitor devices may also be used to couple

    radio frequencies to the line for use in pilot

    relaying

    At about 115kV, the CCVT types becomesapplicable and generally more economical

    than VTs at the higher voltages.

  • 7/28/2019 Instrument Transformers 2009-7

    67/80

    TERMINAL DESIGNATION OF CTS

  • 7/28/2019 Instrument Transformers 2009-7

    68/80

    TERMINAL DESIGNATION OF CTS

  • 7/28/2019 Instrument Transformers 2009-7

    69/80

    Single Ratio

  • 7/28/2019 Instrument Transformers 2009-7

    70/80

    Single Ratio

    D bl ti ith it hi th i

  • 7/28/2019 Instrument Transformers 2009-7

    71/80

    Double ratio with switching on the primary

    D bl ti ith t th d i di

  • 7/28/2019 Instrument Transformers 2009-7

    72/80

    Double ratio with tap on the secondary winding

  • 7/28/2019 Instrument Transformers 2009-7

    73/80

  • 7/28/2019 Instrument Transformers 2009-7

    74/80

  • 7/28/2019 Instrument Transformers 2009-7

    75/80

    Instruments transformers

  • 7/28/2019 Instrument Transformers 2009-7

    76/80

    locations

    Double bus bar station

  • 7/28/2019 Instrument Transformers 2009-7

    77/80

    Double bus bar station

    Transfer bus bar station

  • 7/28/2019 Instrument Transformers 2009-7

    78/80

    Transfer bus bar station

    Double breaker arrangement

  • 7/28/2019 Instrument Transformers 2009-7

    79/80

    Double breaker arrangement

  • 7/28/2019 Instrument Transformers 2009-7

    80/80