  • INSTRUMENT TRANSFORMERS. LOW VOLTAGE.

    INSULATORS AND WALL BUSHINGS.

  • This document may be subject to changes. Contact ARTECHE to confi rm the characteristics and availability of the products described here.

    Moving together

  • Instrument transformers | Low voltage

    CONTENTS

    1. Instrument transformers. Low voltage. Current transformers

    › Metering. Indoor • IFG-5 | 6 • IFP-0 | 6 • IFW-4 / IFW-5 | 7 • IFX | 7

    › Metering and protection. Indoor • IFE | 8 • IFG-7 / IFG-8 | 9 • IFH-6 | 10 • IFP-1 | 11 • IFW-0-DS / IFW-4-DS | 11

    › Metering and protection. Indoor / Outdoor • IFH-0 | 12 • IFH-1 | 13 • IFH-3 | 14 • IFH-4 | 15 • IFH-5 | 16 • IFH-7 | 17 • IFH-10 | 18 • IFH-12 | 19

    › Protection. Split-core • BAT | 20 • BAR | 20 • BAS | 21

    › Homopolar. Indoor / Outdoor • BAR | 22 • IFH-3 | 23 • ICO-3 | 23

    › Window type for bushings • BUSHING CT | 24

    › Auxiliary • IRM | 24

    Voltage Transformers

    › Metering and protection. Indoor • URC | 25

    2. Insulators and wall bushings › Support insulators. Indoor • AR | 27

    › Signal insulators. Indoor • ARC | 28

    › Signalling box • LAF-1 | 28

    › Wall bushings. Indoor • PRU / PRP | 30 • PBD | 31 • PBE | 31 • PPL | 32

    › Wall bushings. Indoor • PPE-36 | 33

    3. Manufacturing and technology | 34

    4. Quality and environment | 36

    5. Service | 38

  • 4 Instrument transformers | Low voltage

    1. INSTRUMENT TRANSFORMERS. LOW VOLTAGE

    Current Transformers Voltage Transformers

  • 5Instrument transformers | Low voltage

    CURRENT TRANSFORMERS>> WINDOW TYPE

    Current transformers without primary winding intended to be used in low voltage bars or isolated cables.

    RANGE

    › Primary nominal currents up to 10,000 A. › Secondary currents 1 and 5 A. › Frequencies 50 Hz and 60 Hz.

    APPLICATIONS

    › Low voltage panels. › Motor control. › Primary distribution switchgear. › Secondary distribution switchgear. › Capacitor banks. › Power generation. › Dead tank circuit breaker. › Railway.

    ADVANTAGES

    › Wide range of models with different window sizes available.

    › Multi-ratio transformer for different transformation ratios available.

    › Sealable cover for secondary terminals. › Stainless steel screws available. › Designs for outdoor service available. › Transformer can be assembled in any position.

    › Split core current transformers to install without handling the primary bars or cables.

    >> SQUARE WINDOW TYPE

    Current transformers for installation in low voltage panel bars where available space is critical.

    RANGE

    › Primary nominal currents up to 3,000 A. › Secondary currents 1 and 5 A. › Frequencies 50 Hz and 60 Hz.

    APPLICATIONS

    › Low voltage panels.

    ADVANTAGES

    › Variety of models with diff erent window sizes available.

    › Sealable cover for secondary terminals.

    >> WITH PRIMARY BAR

    Transformers for installation in low voltage measuring panels.

    RANGE

    › Primary nominal currents up to 1,000 A. › Secondary currents 1 and 5 A. › Frequencies 50 Hz and 60 Hz.

    APPLICATIONS

    › Low voltage panels.

    ADVANTAGES

    › Mechanism for fastening the transformer onto the bar.

    › Sealable cover for secondary terminals. › Connection for voltage tap.

  • Instrument transformers | Low voltage6

    IFG-5

    1. CURRENT TRANSFORMERS > Metering > Indoor

    IFP-0

    145110 a 115

    = =

    145110 a 115

    6.5

    30 33

    3.5

    3.5

    63.

    52.

    262.

    26

    Secondary terminals M4

    8043

    E

    Sealable cover

    Secondary terminals M4

    ø 70101

    93.

    5 ø 22

    CHARACTERISTICS

    Primary current

    ACL0.2 VA CL0.5 VA CL1 VA

    5075 4

    100 7.5125 10150 15200 15 30250 20 40300 30 50400 30 35500 15 35 40600 20 50 60

    60

    627385

    CHARACTERISTICS

    Primary current

    A

    Marks A and B

    Mark C

    Cl 0.5 Fs5 VA5

    10 and 15

    102030405075

    100150200

    10 and 15300400500600

    Thermal Current: 60xIn

    DIMENSIONS

    Mark Current EA Up to 300 A 5B From 200 to 600 A 10

    Sealable cover

    9085

    90 10

    6

    40

    P1K

    P2L

    S1k

    S2l

    30.25

    10.2

    5

    With passing-through holeMARK C - From 200 to 600 A

    102

  • 7Instrument transformers | Low voltage

    IFW-4 • IFW-5

    1. CURRENT TRANSFORMERS > Metering > Indoor

    Secondary terminals M4

    D B

    A

    C

    Sealable cover

    H

    65

    G

    F

    E

    Screws to fi x transformer on busbar

    DIMENSIONS

    Type A B C D E F G HIFW-4 62 105 150 193 75 50 78 85.5IFW-5 95 105 190 200 75 50 78 85.5

    IFX Secondary terminals M4

    B D

    AC

    F

    DIMENSIONS

    Type A B C D E F GIFX-0 22 82 85 135 80 48 58IFX-1 22 102 88 168 74.5 50 55IFX-2 32 102 102 172 64 56 50

    CHARACTERISTICS

    TypePrimary current

    A

    CL0.5 VA

    CL1 VA

    IFW-43,000

    15 30

    3,5004,000

    IFW-53,5004,0005,000

    CHARACTERISTICS

    TypePrimary current

    A

    CL0.5FS 5 VA

    IFX-0

    400*

    10

    500*600*750*800*

    1,000*1,200*

    10 and 151,250*

    1,500*

    IFX-1

    750*

    10

    800*1,000*1,200*1,500*2,000*

    IFX-22,000*2,500*3,000*

    *Extended current rating up: 150%Thermal Current: 60xIn

    Sealable cover

    G

    E Screws to fi x

    transformer on busbar

  • Instrument transformers | Low voltage8

    IFE

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor

    DIMENSIONS

    Type Mark A B C D(±1.5) E F G H

    IFE-1 120 81 83.5 60 40 145 50 164.5

    IFE-3A

    120 103 10660

    35 190 55 209B 80

    Ø F

    B

    H

    Ø D

    C

    A

    1,5

    105= =

    25==

    Ø 7

    CHARACTERISTICS

    SINGLE PRIMARY RATIO AND ONE SECONDARY

    Inner diameterØ D= 60 mm

    Inner diameterØ D= 80 mm

    Type Primary current AClass and burden

    METERINGClass and burden

    PROTECTIONClass and burden

    METERINGClass and burden

    PROTECTION

    IFE-1

    200 5 VA CL1 2.5 VA 5P10250 12.5 VA CL1 2.5 VA 5P10300 5 VA CL0.5 2.5 VA 5P10400 12.5 VA CL0.5 5 VA 5P10

    500 5 VA CL0.225 VA CL0.55 VA 5P10

    2.5 VA 5P15

    600 10 VA CL0.250 VA CL0.55 VA 5P10

    2.5 VA 5P20

    800 20 VA CL0.280 VA CL0.57.5 VA 5P102.5 VA 5P15

    1000 40 VA CL0.2100 VA CL0.510 VA 5P102.5 VA 5P15

    1200 70 VA CL0.2120 VA CL0.510 VA 5P105 VA 5P15

    IFE-3

    150 35 VA CL3 2.5 VA 5P10 25 VA CL3 2.5 VA 5P10

    200 2.5 VA CL0.510 VA CL15 VA 5P105 VA 5P10

    5 VA CL130 VA CL3

    2.5 VA 5P102.5 VA 5P15

    250 5 VA CL0.520 VA CL17.5 VA 5P102.5 VA 5P20

    2.5 VA CL0.510 VA CL1

    5 VA 5P102.5 VA 5P15

    300 7.5 VA CL0.535 VA CL17.5 VA 5P102.5 VA 5P20

    5 VA CL0.520 VA CL1

    5 VA 5P102.5 VA 5P20

    400 5 VA CL0.220 VA CL0.510 VA 5P105 VA 5P20

    10 VA CL0.545 VA CL1

    7.5 VA 5P102.5 VA 5P20

    500 10 VA CL0.240 VA CL0.515 VA 5P105 VA 5P20

    5 VA CL0.225 VA CL0.5

    10 VA 5P102.5 VA 5P20

    600 15 VA CL0.275 VA CL0.515 VA 5P10

    7.5 VA 5P2010 VA CL0.240 VA CL0.5

    12.5 VA 5P105 VA 5P20

    800 40 VA CL0.2175 VA CL0.520 VA 5P1010 VA 5P20

    20 VA CL0.2100 VA CL0.5

    15 VA 5P105 VA 5P20

    1000 75 VA CL0.2200 VA CL0.530 VA 5P10

    12.5 VA 5P2045 VA CL0.2150 VA CL0.5

    20 VA 5P107.5 VA 5P20

    1200 100 VA CL0.2 30 VA 5P1012.5 VA 5P2070 VA CL0.2175 VA CL0.5

    25 VA 5P1010 VA 5P20

    1500 125 VA CL0.2 25 VA 5P1010 VA 5P20

    2000 200 VA CL0.2 35 VA 5P1010 VA 5P20

    G

    E

  • 9Instrument transformers | Low voltage

    IFG-7 • IFG-8

    DIMENSIONS

    Type AIFG-7 55IFG-8 85

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor

    CHARACTERISTICS

    SINGLE PRIMARY RATIO AND ONE SECONDARY

    Type Primary current AClass and burden

    METERINGClass and burden

    PROTECTION

    IFG-7

    200 2.5 VA CL0.5 2.5 VA 5P10250 5 VA CL0.5 2.5 VA 5P10300 7.5 VA CL0.5 2.5 VA 5P15

    400 2.5 VA CL0.220 VA CL0.55 VA 5P10

    2.5 VA 5P15

    500 7.5 VA CL0.240 VA CL0.55 VA 5P10

    2.5 VA 5P20

    600 15 VA CL0.260 VA CL0.57.5 VA 5P102.5 VA 5P20

    800 35 VA CL0.290 VA CL0.57.5 VA 5P102.5 VA 5P15

    1000 60 VA CL0.2120 VA CL0.512.5 VA 5P102.5 VA 5P20

    IFG-8

    100 25 VA CL3 2.5 VA 5P10150 7.5 VA CL1 2.5 VA 5P15200 5 VA CL0.5 2.5 VA 5P10

    250 5 VA CL0.520 VA CL15 VA 5P10

    2.5 VA 5P15

    300 2.5 VA CL0.215 VA CL0.510 VA 5P10

    2.5 VA 5P20

    400 7.5 VA CL0.240 VA CL0.512.5 VA 5P105 VA 5P20

    500 15 VA CL0.275 VA CL0.515 VA 5P105 VA 5P20

    600 30 VA CL0.2125 VA CL0.515 VA 5P10

    7.5 VA 5P20

    800 70 VA CL0.2180 VA CL0.520 VA 5P107.5 VA 5P20

    1000 125 VA CL0.2240 VA CL0.530 VA 5P1010 VA 5P20

    Ø 50

    147 16

    0

    1.5

    Ø 125 A

    90= =

    2.52.5

    33=

    =

    593.

    53.

    52.

    252.

    256.5

    110

    ==

    P2

    ==

    80

    › IFG-7

  • Instrument transformers | Low voltage10

    IFH-6

    Ø 260

    141

    325 Ø

    D

    290

    L

    195

    = =

    98

    ==

    Ø 9

    118

    220

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor

    DIMENSIONS & CHARACTERISTICS

    D L MarkPrimary current

    AMETERING PROTECTION METERING + PROTECTION

    60

    130 I

    100 5 VA CL1 5 VA 5P20200 10 VA CL0.5 12.5 VA 5P20 5 VA CL1 + 7.5 VA 5P20400 15 VA CL0.2 25 VA 5P20 10 VA CL0.5 + 15 VA 5P20600 15 VA CL0.2S 40 VA 5P20 15 VA CL0.2 + 15 VA 5P20

    1,000 70 VA CL0.2S 70 VA 5P20 15 VA CL0.2S + 30 VA 5P20

    180 B

    100 7.5 VA 5P20 5 VA CL3 + 5 VA 5P20200 20 VA 5P20 5 VA CL1 + 15 VA 5P20400 40 VA 5P20 15 VA CL0.5 + 25 VA 5P20600 60 VA 5P20 15 VA CL0.2S + 35 VA 5P20

    1,000 100 VA 5P20 15 VA CL0.2S + 60 VA 5P20

    225 E

    100 10 VA 5P20 5 VA CL3 + 7.5 VA 5P20200 25 VA 5P20 10 VA CL1 + 20 VA 5P20400 55 VA 5P20 20 VA CL0.5 + 40 VA 5P20600 85 VA 5P20 15 VA CL0.2 + 60 VA 5P20

    1,000 140 VA 5P20 15 VA CL0.2S + 90 VA 5P20

    80

    130 J

    100 15 VA CL3 5 VA 5P20200 5 VA CL0.5 12.5 VA 5P20 2.5 VA CL0.5 + 5 VA 5P20400 10 VA CL0.2 25 VA 5P20 12.5 VA CL0.5 + 12.5 VA 5P20600 35 VA CL0.2 40 VA 5P20 15 VA CL0.2 + 15 VA 5P20

    1,000 40 VA CL0.2S 70 VA 5P20 15 VA CL0.2S + 20 VA 5P202,000 300 VA CL0.2S 135 VA 5P20 15 VA CL0.2S + 65 VA 5P20

    180 C

    100 7.5 VA 5P20200 20 VA 5P20 2.5 VA CL0.5 + 12.5 VA 5P20400 40 VA 5P20 12.5 VA CL0.5 + 25 VA 5P20600 65 VA 5P20 15 VA CL0.2 + 35 VA 5P20

    1,000 100 VA 5P20 15 VA CL0.2S + 60 VA 5P202,000 200 VA 5P20

    225 F

    100 10 VA 5P20200 25 VA 5P20 10 VA CL1 + 20 VA 5P20400 55 VA 5P20 20 VA CL0.5 + 40 VA 5P20600 85 VA 5P20 12.5 VA CL0.2 + 60 VA 5P20

    1,000 140 VA 5P20 15 VA CL0.2S + 90 VA 5P20

    110 130 L

    100 15 VA CL3 5 VA 5P20200 5 VA CL0.5 12.5 VA 5P20 2.5 VA CL0.5 + 5 VA 5P20400 7.5 VA CL0.2 25 VA 5P20 12.5 VA CL0.5 + 12.5 VA 5P20600 35 VA CL0.2 40 VA 5P20 15 VA CL0.2 + 15 VA 5P20

    1,000 40 VA CL0.2S 70 VA 5P20 15 VA CL0.2S + 20 VA 5P20

    130

    130 A

    200 15 VA CL1 10 VA 5P20 5 VA CL1 + 5 VA 5P20400 30 VA CL0.5 20 VA 5P20 5 VA CL0.5 + 10 VA 5P20600 20 VA CL0.2 30 VA 5P20 7.5 VA CL0.2 + 15 VA 5P20

    1,000 25 VA CL0.2S 50 VA 5P20 20 VA CL0.2 + 25 VA 5P201,500 85 VA CL0.2S 75 VA 5P20 20 VA CL0.2 S + 25 VA 5P202,000 200 VA CL0.2S 100 VA 5P20 25 VA CL0.2S + 50 VA 5P20

    180 D

    200 15 VA 5P20 7.5 VA CL1 + 7.5 VA 5P20400 30 VA 5P20 15 VA CL0.5 + 15 VA 5P20600 45 VA 5P20 10 VA CL0.2 + 25 VA 5P20

    1,000 80 VA 5P20 10 VA CL0.2 S + 45 VA 5P20

    225 G

    200 20 VA 5P20 7.5 VA CL1 + 12.5 VA 5P20400 45 VA 5P20 15 VA CL0.5 + 25 VA 5P20600 65 VA 5P20 7.5 VA CL0.2 + 45 VA 5P20

    1,000 115 VA 5P20 7.5 VA CL0.2 S + 70 VA 5P20

    160 225 K

    200 7.5 VA CL1 10 VA 5P20400 15 VA CL0.5 20 VA 5P20 7.5 VA CL0.5 + 10 VA 5P20600 12.5 VA CL0.2 25 VA 5P20 20 VA CL0.5 + 15 VA 5P20

    1,000 10 VA CL0.2S 50 VA 5P20 25 VA CL0.2 + 25 VA 5P201,500 50 VA CL0.2S 55 VA 5P20 15 VA CL0.2 S + 40 VA 5P20

    205 180 H1,000 15 VA CL0.5 15 VA 5P10 10 VA CL0.5 + 10 VA 5P101,200 20 VA CL0.5 20 VA 5P10 15 VA CL0.5 + 15 VA 5P101,600 25 VA CL0.5 25 VA 5P10 10 VA CL0.5 + 10 VA 5P10

    70 225 M

    100 10 VA 5P20 5 VA CL3 + 7.5 VA 5P20200 25 VA 5P20 10 VA CL1 + 20 VA 5P20400 55 VA 5P20 20 VA CL0.5 + 40 VA 5P20600 85 VA 5P20 15 VA CL0.2 + 60 VA 5P20

    1,000 140 VA 5P20 15 VA CL0.2S + 90 VA 5P20

  • 11Instrument transformers | Low voltage

    IFP-1

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor

    147

    With passing - Through holeMARK B - From 250 to 1000 A

    MARK A - Up to 1,000 A

    IFW-O/DS • IFW-4/DS

    Sealable cover Secondary terminals M4

    D B 35

    AC

    E

    FG

    Screws to fi x transformer on busbar

    DIMENSIONS

    Type A B C D E F GIFW-0/DS 20 62 84 126 126 80 105IFW-4/DS 62 105 150 193 136 90 115

    125

    1025 25

    M12

    225175

    = =

    =145

    =

    50=

    =

    145

    120

    Ø6.5

    145

    72.5

    166

    6

    CHARACTERISTICS

    Type Ratio(A)Burden VA

    PROTECTIONRatio(A)

    Class and burdenMETERING + PROTECTION

    IFW-O/DS

    250/5 7.5 VA 10P5300/5 10 VA 10P5350/5 12.5 VA 10P5

    400/5 15 VA 10P5 or5 VA 5P10

    500/5 15 VA 10P5 or7.5 VA 5P10 500/5-510 VA CL1 + 5 VA 5P10

    5 VA 10P10

    600/5 20 VA 10P5 or10 VA 5P10 600/5-510 VA CL1 + 7.5 VA 5P10

    7.5 VA 10P10

    1,000/5 30 VA 10P5 or15 VA 5P10 1,000/5-515 VA CL0.5 + 10 VA 5P10

    10 VA 10P10

    1,250/5 30 VA 10P5 or15 VA 5P10 1,250/5-515 VA CL0.5 + 10 VA 5P10

    12.5 VA 10P10

    1,500/5 40 VA 10P5 or20 VA 5P10 1,500/5-515 VA CL0.5 + 15 VA 5P10

    15 VA 10P10

    IFW-4/DS

    2,000/5 45 VA 10P520 VA 5P10 2,000/5-515 VA CL0.5 + 15 VA 5P10

    20 VA 10P10

    2,500/5 40 VA 10P530 VA 5P10 2,500/5-515 VA CL0.5 + 20 VA 5P10

    25 VA 10P10

    3,000/5 40 VA 10P530 VA 5P10 3,000/5-515 VA CL0.5 + 25 VA 5P10

    30 VA 10P10

    3,500/5 40 VA 10P530 VA 5P10 3,500/5-515 VA CL0.5 + 25 VA 5P10

    30 VA 10P10

    4,000/5 45 VA 10P540 VA 5P10 4,000/5-515 VA CL0.5 + 30 VA 5P10

    35 VA 10P10

    10.2

    550.25

    CHARACTERISTICS

    Mark Primary current ACL0,2

    VASP10VA

    A

    5 to 250 30 20300 15 15400

    30

    20600 30800 35900 40

    1,000 45

    B

    300 15 15400

    30

    20500 25600 30800 35900 40

    1,000 45

    Thermal Current: 60xIn

  • Instrument transformers | Low voltage12

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

    IFH-0Ø

    60

    260

    Secondary terminals M6 (max. 6)

    Indoor serviceMark A

    M8

    226

    .5

    106

    PG 16

    113

    Secondary terminals M6 (max. 6)

    89

    .557

    .5

    Outdoor serviceMark B

    ==

    Ø 13

    60

    90

    170==

    200==

    ==

    PG 16

    45

    CHARACTERISTICS

    ONE SECONDARY TWO SECONDARIES

    Primary current A METERING PROTECTION METERING + PROTECTION

    100 5 VA 5P10150 10 VA CL1 10 VA 5P10200 25 VA CL1 10 VA 5P10 5 VA CL1 + 10 VA 5P5250 25 VA CL1 15 VA 5P10 15 VA CL1 + 5 VA 5P10300 20 VA CL0.5 15 VA 5P10 20 VA CL1 + 5 VA 5P10400 40 VA CL0.5 20 VA 5P10 15 VA CL0.5 + 10 VA 5P10500 50 VA CL0.5 30 VA 5P10 15 VA CL0.5 + 15 VA 5P10600 50 VA CL0.5 15 VA 5P20 20 VA CL0.5 + 20 VA 5P10750 65 VA CL0.5 20 VA 5P20 30 VA CL0.5 + 25 VA 5P10800 40 VA CL0.5 + 30 VA 5P10

    1,000 30 VA CL0.2 25 VA 5P20 50 VA CL0.5 + 35 VA 5P101,200 30 VA CL0.2 30 VA 5P20 50 VA CL0.5 + 45 VA 5P10

    Ø 165

  • 13Instrument transformers | Low voltage

    IFH-1

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

    CHARACTERISTICS

    INNER DIAMETER (ØD= 60 mm) INNER DIAMETER (ØD= 80 mm)

    ONE SECONDARY TWO SECONDARIES ONE SECONDARY TWO SECONDARIES

    Primary current

    AMETERING PROTECTION METERING + PROTECTION METERING PROTECTION METERING + PROTECTION

    75 15 VA CL3 7.5 VA 10P10 10 VA CL3 10 VA 10P5100 50 VA CL3 12.5 VA 5P10 40 VA CL3 7.5 VA 10P10150 20 VA CL1 15 VA 5P10 30 VA CL3 + 10 VA 5P10 10 VA CL1 12.5 VA 5P10 20 VA CL3 + 5 VA 5P10200 10 VA CL0.5 20 VA 5P10 10 VA CL1 + 12.5 VA 5P10 25 VA CL1 7.5 VA 5P20 5 VA CL1 + 7.5 VA 5P10250 20 VA CL0.5 25 VA 5P10 20 VA CL1 + 15 VA 5P10 12.5 VA CL0.5 10 VA 5P20 10 VA CL1 + 10 VA 5P10300 40 VA CL0.5 15 VA 5P20 10 VA CL0.5 + 20 VA 5P10 20 VA CL0.5 12.5 VA 5P20 15 VA CL1 + 12.5 VA 5P10400 90 VA CL0.5 25 VA 5P20 10 VA CL0.5 + 15 VA 5P20 50 VA CL0.5 15 VA 5P20 10 VA CL0.5 + 15 VA 5P10500 50 VA CL0.2 30 VA 5P20 20 VA CL0.5 + 25 VA 5P20 25 VA CL0.2 20 VA 5P20 12.5 VA CL0.5 + 5 VA 5P20600 75 VA CL0.2 35 VA 5P20 30 VA CL0.5 + 25 VA 5P20 40 VA CL0.2 20 VA 5P20 20 VA CL0.5 + 15 VA 5P20800 100 VA CL0.2 50 VA 5P20 15 VA CL0.2 + 35 VA 5P20 100 VA CL0.2 30 VA 5P20 40 VA CL0.5 + 20 VA 5P20

    1,000 100 VA CL0.2 60 VA 5P20 30 VA CL0.2 + 45 VA 5P20 100 VA CL0.2 35 VA 5P20 20 VA CL0.2 + 25 VA 5P201,200 100 VA CL0.2 60 VA 5P20 50 VA CL0.2 + 50 VA 5P20 100 VA CL0.2 45 VA 5P20 30 VA CL0.2 + 30 VA 5P201,500 100 VA CL0.2 50 VA 5P20 50 VA CL0.2 + 40 VA 5P202,000 100 VA CL0.2 75 VA 5P20 100 VA CL0.2 + 40 VA 5P20

    Ø 45

    25729

    0

    Secondary terminals M6 (max. 6)

    Indoor service

    M8

    PG 16

    125

    Secondary terminals M6 (max. 6)

    107.

    557

    .5

    Outdoor service

    PG 16

    Ø D Ø 120

    Ø 190

    20

    ==

    Ø 11

    60

    90

    170==

    200==

    ==

    45

    13567.5 67.5

    DIMENSIONS

    Mark Ø D (±1.5) Service

    A 60Outdoor

    B 80C 60

    IndoorD 80

    P1

  • Instrument transformers | Low voltage14

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

    IFH-3

    Ø 45°

    290

    323

    Secondary terminals M6 (max. 6)

    Indoor serviceMark A

    M8

    PG 16

    144

    Secondary terminals M6 (max. 6)

    121.5

    Outdoor serviceMark B

    PG 16

    Ø 110

    Ø 150

    Ø 220

    20

    ==

    Ø 11

    60

    90

    170==

    200==

    ==

    45

    CHARACTERISTICS

    ONE SECONDARY TWO SECONDARIES

    Primary current

    AMETERING PROTECTION METERING + PROTECTION

    150 5 VA CL1 5 VA 5P20

    200 15 VA CL1 5 VA 5P20

    250 5 VA CL0.5 10 VA 5P20300 12.5 VA CL0.5 10 VA 5P20 5 VA CL1 + 5 VA 5P20350 20 VA CL0.5 12.5 VA 5P20 5 VA CL0.5 + 5 VA 5P20400 20 VA CL0.5 15 VA 5P20 5 VA CL0.5 + 7.5 VA 5P20500 25 VA CL0.5 20 VA 5P20 10 VA CL0.5 + 10 VA 5P20600 50 VA CL0.5 20 VA 5P20 12.5 VA CL0.5 + 12.5 VA 5P20

    1,000 50 VA CL0.5 20 VA 5P201,500 50 VA CL0.5 20 VA 5P20 30 VA CL0.5 + 30 VA 5P202,000 50 VA CL0.5 20 VA 5P203,000 50 VA CL0.5 20 VA 5P20 30 VA CL0.5 + 30 VA 5P20

    57.5

    115= =

    M8 (on request)

    Ø 9

    P1

  • 15Instrument transformers | Low voltage

    IFH-4 Secondary terminals M5 (max. 9) Secondary terminals M6

    Indoor serviceMark A

    131

    289

    205

    Outdoor serviceMark B

    ==

    60 90

    170==

    200==

    ==

    Secondary terminals M5 (max. 9) Secondary terminals M6

    171= =

    125

    107

    Ø 190

    Ø 85

    PG 16

    M8

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

    CHARACTERISTICS

    ONE SECONDARY TWO SECONDARIES

    Primary current

    AMETERING PROTECTION METERING + PROTECTION

    100 5 VA CL1 5 VA 5P20150 15 VA CL1 10 VA 5P20 5 VA CL1 + 5 VA 5P20200 7.5 VA CL0.5 12.5 VA 5P20 15 VA CL1 + 7.5 VA 5P20300 30 VA CL0.5 20 VA 5P20 15 VA CL0.5 + 10 VA 5P20400 15 VA CL0.2 25 VA 5P20 7.5 VA CL0.2 + 10 VA 5P20500 30 VA CL0.2 30 VA 5P20 15 VA CL0.2 + 15 VA 5P20700 20 VA CL0.2 45 VA 5P20 10 VA CL0.2S + 20 VA 5P20

    1,000 60 VA CL0.2 65 VA 5P20 25 VA CL0.2S + 25 VA 5P202,000 400 VA CL0.2 100 VA 5P20 100 VA CL0.2S + 50 VA 5P20

    Ø 11

  • Instrument transformers | Low voltage16

    IFH-5

    › IFH-5. Side mounting on request installation horizontal or vertical.

    25735

    2

    Secondary terminals M6 (max. 6)

    Indoor service

    M8

    PG 16

    157

    137.

    557

    .5

    Outdoor service

    PG 16

    Ø D Ø 250

    Ø 15

    170

    DIMENSIONS

    Mark D (±1.5) ServiceA 100

    OutdoorB 130C 100

    IndoorD 130E 145 OutdoorF 145 Indoor

    ==

    Ø 11

    60 90

    170==

    200==

    ==

    45

    = =

    Secondary terminals M6 (max. 6)

    On request

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

    CHARACTERISTICS

    ONE SECONDARY TWO SECONDARIES

    Inner diameter(ØD= 100 mm)

    Inner diameter(ØD= 130 mm)

    Inner diameter(ØD= 145 mm)

    Inner diameter (ØD= 100 mm)

    Inner diameter(ØD= 130 mm)

    Primary current A PROTECTION METERING + PROTECTION

    200 20 VA 5P20 12.5 VA 5P20 5 VA 5P20 10 VA CL3 + 1 10 VA 5P20 7.5 VA CL1 + 7.5 VA 5P20250 25 VA 5P20 15 VA 5P20 7.5 VA 5P20 15 VA CL1 + 15 VA 5P20 15 VA CL1 + 10 VA 5P20300 30 VA 10P20 20 VA 5P20 10 VA 5P20 10 VA CL0.5 + 15 VA 5P20 5 VA CL0.5 + 10 VA 5P20500 45 VA 10P20 30 VA 5P20 15 VA 5P20 25 VA CL0.5 + 25 VA 5P20 20 VA CL0.5 + 20 VA 5P20750 50 VA 10P20 50 VA 5P20 25 VA 5P20 30 VA CL0.5 + 30 VA 5P20 25 VA CL0.5 + 30 VA 5P20

    1,000 50 VA 10P20 50 VA 5P20 30 VA 5P20 30 VA CL0.5 + 40 VA 5P20 30 VA CL0.5 + 40 VA 5P202,000 50 VA 10P20 50 VA 5P20 50 VA 5P20 30 VA CL0.5 + 40 VA 5P20 30 VA CL0.5 + 40 VA 5P203,000 50 VA 10P20 50 VA 5P20 50 VA 5P20 30 VA CL0.5 + 40 VA 5P20 30 VA CL0.5 + 40 VA 5P206,000 45 VA 5P20

  • 17Instrument transformers | Low voltage

    IFH-7

    200

    Ø D

    Ø 15

    Ø 270

    220

    DIMENSIONS

    Mark H D Weight(kg)1 166

    100

    402 231 553 296 754 361 90

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

    CHARACTERISTICS

    Mark Primary current A PROTECTION PROTECTION

    1

    100 15 VA 5P10 7.5 VA 5P20200 30 VA 5P10 15 VA 5P20300 50 VA 5P10 20 VA 5P20400 60 VA 5P10 30 VA 5P20500 75 VA 5P10 40 VA 5P20

    2

    50 7.5 VA 5P10 2.5 VA 5P2075 15 VA 5P10 5 VA 5P20

    100 25 VA 5P10 10 VA 5P20150 40 VA 5P10 15 VA 5P20250 60 VA 5P10 30 VA 5P20300 70 VA 5P10 35 VA 5P20600 100 VA 5P10 60 VA 5P20

    1,000 100 VA 5P10 100 VA 5P20

    3

    50 10 VA 5P10 5 VA 5P20100 30 VA 5P10 15 VA 5P20200 60 VA 5P10 30 VA 5P20300 100 VA 5P10 50 VA 5P20

    450 15 VA 5P10 7.5 VA 5P20100 40 VA 5P10 20 VA 5P20150 60 VA 5P10 30 VA 5P20

    PG 21 (on request)

    Secondary terminals M6 (max. 6)

    PG 21

    H15

  • Instrument transformers | Low voltage18

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

    IFH-10

    220

    Secondary terminals M6 (max. 6)

    562

    115

    PG 16

    Ø 2

    90

    255

    M8

    5

    Ø 450

    195= =

    Ø 9

    110

    90

    ==

    CHARACTERISTICS

    ONE SECONDARY TWO SECONDARIES

    Primary current

    AMETERING PROTECTION METERING + PROTECTION

    4,000

    30 VA CL0.5 30 VA 5P20 30 VA CL0.5 + 30 VA 5P205,0006,0008,00010,000

  • 19Instrument transformers | Low voltage

    1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

    IFH-12

    294

    168

    Ø 534

    Ø 30

    0

    M8

    Z 1:5

    8

    572 626

    Outdoor serviceMark A

    Indoor serviceMark B

    M8

    617

    Ø 14

    500

    470

    = =

    218

    188

    ==

    Outdoor serviceMark C

    10

    564 45

    168

    20

    Indoor serviceMark D

    10564 45

    M6

    719

    669

    650

    60

    0

    CHARACTERISTICS

    ONE SECONDARY TWO SECONDARIES

    Primary current A METERING PROTECTION METERING + PROTECTION

    4,000

    50 VA CL0.5 50 VA 5P20 50 VA CL0.5 + 50 VA 5P205,0006,,0008000

    10,000

  • Instrument transformers | Low voltage20

    BAT Secondary terminals M6 Metallic cover

    DIMENSIONSMark D

    A 130B 180

    CHARACTERISTICS

    Mark A Mark B

    Primary current A METERING PROTECTION METERING PROTECTION

    200 5 VA 10P10 2.5 VA 10P10

    300 2.5 VA CL1 12,5 VA 10P10 2 VA 10P20400 5 VA CL1 5 VA 5P20 2 VA CL1 2 VA 5P20600 5 VA CL0,5 15 VA 5P20 5 VA CL1 5 VA 5P20800 7,5 VA CL0.5 25 VA 5P20 2.5 VA CL0.5 7 VA 5P20

    1,000 15 VA CL0.5 30 VA 5P20 5 VA CL0.5 7.5 VA 5P201,200 25 VA CL0.5 35 VA 5P20 7.5 VA CL0.5 10 VA 5P201,500 45 VA CL0.5 45 VA 5P20 12.5 VA CL0.5 12.5 VA 5P201,800 75 VA CL0.5 55 VA 5P20 25 VA CL0.5 15 VA 5P202,000 100 VA CL0.5 65 VA 5P20 50 VA CL0.5 15 VA 5P20

    1. CURRENT TRANSFORMERS > Protection. Split-core > Indoor / Outdoor

    BAR

    CHARACTERISTICS

    Primary current A METERING PROTECTION

    200 4 VA 10P10300 2 VA 10P20400 2 VA CL1 2 VA 5P20500 5 VA CL1 4 VA 5P20600 7.5 VA CL1 5 VA 5P20800 3 VA CL0.5 7 VA 5P20

    1,000 7.5 VA CL0.5 7.5 VA 5P20

    S2S1

    P1

    4

    Ø 2

    70

    Ø D

    156

    155

    PG 16

    PAR DE APRIETETORQUE0.5 Kg.m 9

    5

    200

    =170

    =

    318

    R7

    TORQUEPAR DE APRIETE

    0.5 Kg.m

    P1

    Secondary terminals M6

    Metalic cover

    PG 16

    200

    Ø 190

    Ø 105

    112

    110

    230

    170

    95

    80

    50

    4

    R7

  • 21Instrument transformers | Low voltage

    1. CURRENT TRANSFORMERS > Protection. Split-core > Indoor / Outdoor

    BAS

    Metalic cover

    DIMENSIONS

    Mark DA 70B 105

    CHARACTERISTICS

    Mark A Mark B

    Primary current A METERING PROTECTION METERING PROTECTION

    150 5 VA 10P10200 7.5 VA 10P20 3 VA 10P20300 10 VA CL1 12.5 VA 10P20 5 VA 10P20400 5 VA CL0.5 15 VA 5P20 4 VA CL1 7.5 VA 5P20500 12.5 VA CL0.5 20 VA 5P20 12.5 VA CL1 8 VA 5P20600 20 VA CL0.5 30 VA 5P20 15 VA CL1 10 VA 5P20800 7.5 VA CL0.5 12.5 VA 5P20

    1,000 25 VA CL0.5 15 VA 5P20

    P1

    S1 S2

    PAR DE APRIETE

    0.5 Kg.mTORQUE

    200

    Ø 190

    Ø D

    113

    111

    230

    150

    80

    50

    17085=

    85=

    R7

    4

    Secondary terminals M6

  • Instrument transformers | Low voltage22

    1. CURRENT TRANSFORMERS > Homopolar > Indoor / Outdoor

    BAR Secondary terminals M6

    Metalic cover

    CHARACTERISTICS

    Ratio A Characteristics

    20/1Burden: 0.1 Oh. Error: at 0.05 In ±15%

    at In ±10% at 10 In ±15%

    20/1Burden: 0.3 Oh. Error: at 0.05 In ±15%

    at In ±10% at 5 In ±15%

    30/1Burden: 0.1 Oh. Error: at 0.05 In ±15%

    at In ±10% at 10 In ±15%

    30/1Burden: 0.3 Oh. Error: at 0.05 In ±15% at In ±10% at 5 In ±15%

    50/1Burden: 0.2 Oh. Error: at 0.05 In ±15% at In ±10% at 10 In ±15%

    50/1Burden: 1 and 1.5 Oh. Error: at 0.05 In ±15%

    at In ±10% at 10 In ±15%

    CCCCCCuuuuusssssttttttooooommmmiiiiizzzzeeeeedddddd sssssooooollllluuuuuttttttiiiiiooooonnnnsssss fffffooooorrrr aaaaaannnnnnyyyyyy rrrrrreeeeeeqqqqqquuuuuuiiiiiirrrrrreeeeeemmmmmmeeeeeennnnnntttttt....

    P1

    TORQUEPAR DE APRIETE

    0.5 Kg.m

    PG 16

    200

    Ø 190

    Ø 105

    112

    110

    4

    230

    170

    95

    80

    50

  • 23Instrument transformers | Low voltage

    Secondary terminals M6 (max. 6)

    Indoor service

    Secondary terminals M6 (max. 6)

    Outdoorservice

    IFH-3

    CHARACTERISTICS

    Ratio A Characteristics

    10/1Burden: 0.1 Oh. Error: at 0.05 In ±15%

    at In ±10% at 10 In ±15%

    20/1Burden: 0.1 and 0.3 Oh. Error: at 0.05 In ±15%

    at In ±10% at 10 In ±15%

    30/1Burden: 0.1 Oh. Error: at 0.05 In ±15%

    at In ±10% at 5 In ±15%

    50/1Burden: 1 Oh. Error: at 0.05 In ±15%

    at In ±10% at 10 In ±15%

    60/1Burden: 1 Oh. Error: at 0.05 In ±15%

    at In ±10% at 10 In ±15%

    1. CURRENT TRANSFORMERS > Homopolar > Indoor / Outdoor

    CHARACTERISTICS

    Ratio A Characteristics

    20/1Burden: 0.1 Oh. Error: at 0.01 In ±15%

    at In ±10% at 10 In ±15%

    30/1Burden: 0.1 Oh. Error: at 0.05 In ±15%

    at In ±10% at 5 In ±15%

    50/1Burden: 0.1 Oh. Error: at 0.05 In ±15%

    at In ±10% at 10 In ±15%

    60/1Burden: 0.1 Oh. Error: at 0.05 In ±15%

    at In ±10% at 10 In ±15%

    100/1Burden: 0.1 Oh. Error: at 0.05 In ±15% at In ±10% at 10 In ±15%

    Ø 45

    HA

    M8

    I

    PG 16

    BC

    E

    PG 16

    Ø D Ø F

    Ø G

    20

    ==

    Ø 11

    60

    90

    170==

    ==

    ==

    200

    45

    KV

    I.ter.I.din.

    Hz

    TIPOI.pnI.sn

    BORN.

    EXT.%CL

    TRANSFORMADOR DE INTENSIDAD

    MADE

    SPAIN IN

    VA

    Fs

    Kn= $07__$06__ $08__$11__

    $19__$15__

    $23__$27__$26__

    $10__$14__

    $22__$18__

    $16__$12__

    $24__$28__

    $20__

    $05___________________$02______$01____ N° $03_

    $35

    $32____

    $36__

    $33____$34 KA

    KAS

    P1

    ICO-3

    180150

    = =

    42 57

    20

    510

    470 310

    165

    145

    R45

    R90

    R45

    R90

    20

    Ø 11

    ==

  • Instrument transformers | Low voltage24

    Window type current transformers, bushing type, for installation in power transformers, dead tank circuit breakers or Gas Insulated Switchgears (GIS). They are custom made designed based on the each project requirements.

    BUSHING CT

    1. CURRENT TRANSFORMERS > Bushing CT > Indoor

    1. CURRENT TRANSFORMERS > Auxiliary > Indoor

    IRM

    CHARACTERISTICS

    Type Maximum current (A) METERING PROTECTION A B C D E F G H I J M N

    IRM-2Up to 15 A 30 VA CL0.5 10 VA 10P20 143 10 135

    80 102 112 108 5 90 72 90 M4From 15 to 100 A 60 VA CL1 10 VA 5P20 163 30 155

    IRM-3Up to 15 A 45 VA CL0.5 25 VA 10P20 157 10 150

    95 119 135 126

    7

    105 83 104

    M6

    From 15 to 100 A 90 VA CL1 20 VA 5P20 177 30 170

    IRM-4Up to 15 A 75 VA CL0.5 45 VA 1OP30 197 10 190

    120 136 152 150 125 100 125From 15 to 100 A 150 VA CL1 45 VA 5P20 217 30 210

    IRM-5Up to 15 A 100 VA CL0.5 60 VA 5P20 217 10 210

    From 15 to 100 A 100 VA CL0.5 60 VA 5P20 237 30 230

    F

    M

    A

    B6

    C

    Secondary terminals max. 2 of M10 or 5 of M4

    Secondary terminals max. 5 of M4

    GD

    I

    E K JHN

  • 25Instrument transformers | Low voltage

    1. VOLTAGE TRANSFORMERS > Metering and protection > Indoor

    URC

    DIMENSIONS

    Primary current A

    Burden VA Weight(kg)

    A B C D E F G H I J MClass 0.5 Class 1 Thermal

    URC-52 15 45 200 108 90 111 80 102112

    117 5 90 72

    M4URC-71 25 60 300

    126104

    11395

    120

    7

    105 83URC-72 30 70 450120 119 135

    127URC-80 10 20 6.2 105 128URC-91 75 150 600

    150 125

    131

    120 136 152

    138

    125 100 M6URC-92 150 300 900 161 168URC-93 200 400 1,300 181 188URC-100 30 70 13.5 161 169

    F

    C

    R

    G

    Terminals M4

    D

    I

    E B

    H

    M

    A

    J

    VOLTAGE TRANSFORMERSResin-cast low voltage transformers for measuring and protection.

    RANGE

    › Insulation level 0.72 kV. › Frequencies: 50 Hz, 60 Hz.

    APPLICATIONS

    › Low voltage panel.

    ADVANTAGES

    › Transformer can be assembled in any position.

    › Auxiliary services can be supplied.

  • 26 Instrument transformers | Low voltage

    2. INSULATORS & WALL BUSHINGS Support insulators Signal insulators Signalling box Wall bushings

  • 27Instrument transformers | Low voltage

    2. INSULATORS AND WALL BUSHINGS > Support insulators > Indoor

    AR

    CHARACTERISTICS AND DIMENSIONS

    Type

    Highest system voltage

    kV

    Rated insulation level Minimum breaking

    stress P (kg)

    No sheeds

    Weight(kg)

    Creepage distance

    H (±0.5)

    Ø Máx.

    Dd1 d2 t1 fLightning

    Impulse (BIL) kV

    Power frequency kV

    AR-8-60 7.2 60 80

    800

    3 0.7 200 95

    100

    56 M1626 35

    AR-8-75 12 7538

    4 0.98 272 130 64 M16AR-8-95 17.5 95 6 1.37 340 175 69 M20 35

    45AR-8-125 24 125 50 7 1.65 397 210 74 M20 45AR-8-170 36 170 70 11 2.57 555 300 84 M24 51 60

    View from X

    Pe

    24

    15

    70

    D

    H

    M10

    M16

    t1

    10d2d1

    46

    6.5f

    8

    X

  • Instrument transformers | Low voltage28

    2. INSULATORS AND WALL BUSHINGS > Signalling box > Indoor

    LAF-1

    1 - Test light2 - Fixed warning block3 - Insulators

    LAF-1 Application

    Assembly sketch

    ARC

    CHARACTERISTICS AND DIMENSIONS

    TypeHighest system

    voltage kV

    Lightning Impulse (BIL) kV

    Power frequency

    kV

    kVmin.

    kV max.

    Height(kg)

    Creepage distance

    H (±0.5) d1 f A B Ø C

    ARC-8-40 3.6 40 10 1.2 3.60.98 272 130 64 23 26 12

    16

    ARC-8-60 7.2 60 20 2.4 7.2ARC-8-75 12 75 28 4 12ARC-8-95 17.5 95 38 5.8 17.5

    1.65 397 210 7428 28 10ARC-8-125 24 125 50 8 24

    ARC-8-170 36 170 70 12 36 2.60 555 300 84

    View from B

    Minimum failing load: 4000 Newton

    2. INSULATORS AND WALL BUSHINGS > Signal insulators > Indoor

    View from A

    24

    36

    f

    M4

    24

    B

    Ø 70

    Ø 100

    H

    M12

    C10 M16

    d1

    M6

    A

    A

    B

    Pe

    41

    82

    110

    41

    120 58

    70

    12

    2 1 100

    110

    74

    Ø 4.5

    R S T

    LAF-1

    3

    Die-cast

  • 29Instrument transformers | Low voltage

    ARTECHE transformers are installed in over 150 countries.

  • Instrument transformers | Low voltage30

    2. INSULATORS AND WALL BUSHINGS > Bushings > Indoor

    PRU - PRP

    Detail (striped)Useful zone to place conductor elements

    Ø d

    BH

    10

    Ø J

    A

    Ø D

    120

    Ø C

    FE

    50

    Ø 180

    Detail (striped)Useful zone to place conductor elements

    Ø C

    F

    10B

    H

    Ø KØ J

    E

    G

    A

    Ø D

    T

    Ø S

    › PRU › PRP

    CHARACTERISTICS AND DIMENSIONS

    Type

    Highest system voltage

    kV

    Lightning Impulse

    (BIL) kV

    Barsmax.

    Currentmax.

    Weight

    (kg)A B C D d E F G H J K S T

    PRU-12/7512 75

    601,000

    2.3255 110

    115 115 68 160 200 16015 M10

    120 65 20

    PRU-12/115 100 3.5 160 160 110 205 250 200 165 105 40

    PRU-24/115 24 125 100 9 425 200 185 185 110 230 280 210 24 M12 190 105 402,500

    PRP-36 36 170 120 32.5 560 275 220 220 120 250 300 300 25 20 257

  • 31Instrument transformers | Low voltage

    2. INSULATORS AND WALL BUSHINGS > Bushings > Indoor

    PBD

    PBEP1

    40

    536

    014

    0

    Ø C

    360405

    Ø 4

    22

    Ø D

    M8

    290.5

    14

    Screw at screen potential

    B

    A8

    DIMENSIONS

    Type A B C DPBE-12 255 550 227 275PBE-24 230 500 225 200

    PBD-17

    P1

    380325

    162.5 162.5

    Ø 2

    85.5

    Ø D

    210 190400

    Screw at screen potential

    276

    210

    M8

    105

    105

    Ø 275

    230

    115

    115

    34

    P1

    PBD-24

    Ø 352

    192

    821

    536

    0

    355310

    R 191

    181

    355

    310

    120

    256

    14

    M8

    Screw at screen potential

    Ø 15

    0

    DIMENSIONS

    Type Mark Ø D Weight (kg)

    PBD-17A 100

    25B 130

    PBD-24 45

  • Instrument transformers | Low voltage32

    PPL

    2. INSULATORS AND WALL BUSHINGS > Bushings > Indoor

    AB B

    M12

    P1

    12 25

    C

    DE F G H

    230= =

    Ø 26

    0

    365

    210

    155

    Ø 16

    280

    260

    ==

    Mark D (Option)

    20 40 40

    Ø 16

    Ø 5

    0 40

    30 120130

    I

    1510

    120

    Ø 5

    0

    Mark E Only PPL-72

    (Option)

    30

    120130

    20 40 40

    Ø 16

    Ø 5

    0 40

    I

    Mark G (On request)

    DIMENSIONS

    Type A B C D E F G H IPPL-12 706 353 442 38.5

    157.5 207.538.5 706

    PPL-36 34 716 175.5 175.5 975PPL-72 1,270 451 159 209 451 1,530

    TTThhheee iiinnnnnnooovvvaaatttiiiooonnn uuunnndddeeerrrtttaaakkkeeennnbbbbyyy AAAARRRRTTTTEEEECCCCHHHHEEEE iiiinnn iiiinnnssstttrrruuummmeeennnttttttrraannssfffoorrmmeerrss ddduurriiinnggg ttthhheellllaaaatttteeee yyyyeeeeaaaarrrrssss hhhhaaaavvvveeee mmmmaaaaddddeeeettthhheeemmm mmmooorrreee eeeffiffiffi ccciiieeennnttt,, wwwiiittthhhcccooommmpppaaacccttt dddeeesssiiigggnnnsss fffooorrr aaannneasiier transport, store, anddinstallation and to minimizetheir visual impact.

  • 33Instrument transformers | Low voltage

    2. INSULATORS AND WALL BUSHINGS > Bushings > Outdoor

    PPE-36

    L

    605

    Ø 530

    Ø 500

    Ø 14

    With primary terminal

    E max

    50

    Ø 3

    63

    ØIn

    t. 2

    10

    25 44,5

    44

    ,510

    0

    128

    Ø 14,25

    Aluminium

    DIMENSIONS

    Type Mark Ø D E max L

    With primary terminal

    A 320 1,412B 400 1,492

    Without primary terminal

    A125

    320 1,125B 400 1,205C

    210320 1,125

    D 400 1, 205

    L460

    Without primary terminal

    E max

    Ø 3

    63

    ØIn

    t. 2

    10

    TIPO/TYPEN°

    AÑO/YEARPESO/WEIGHT

    $16___

    Ø 530

    Ø 500

    Ø 14

    Ø D

  • 34 Instrument transformers | Low voltage

    3. MANUFACTURING AND TECHNOLOGYWith 65 years of experience, ARTECHE guarantees the performance of its transformers regardless of altitude, weather, seismic or environmental conditions.

  • 35Instrument transformers | Low voltage

    › Equipment undergoing a continuous i n n ova t i o n p ro c e s s i n c l u d i n g : computerized systems for transformer calculation, analysis of the distribution of the electric field by FEM, automatic winding machines, casting in epoxy resin or polyurethane by gravity in vacuum tanks or pressurized gelifi cation, controlled polymerization in large ovens.

    › Own laboratories with modern equipment, approved for any routine or type test, either for new developments or for specifi c requirements from our customers in power generation, transmission, distribution or industry.

    › Approved in laboratories belonging to the International Metrology Committee: PTB (Germany), L.C.O.E (Spain), GOST (Russia), BEV (Austria), GUM (Poland) etc.

    › Large production capacity of more than 50,000 units per year in medium voltage and an almost unlimited number of devices in low voltage, insulators and wall bushings. This capacity allows us to give a quick answer to any requirement.

    › Flexible designs, adapted to any specification, as a result of our strong engineering team located in all our production facilities.

    › Maximum safety with res in-cast transformers in which the core and the winding form a compact block. The resin acts as a dielectric support, protective casing and thermal conductor for the transformer.

    › Equipment compliant to any international or domestic standard: IEC, IEEE, UNE, BS, VDE, SS, CAN, AS, UL, NBR, JIS, GOST, NF, etc.

    MANUFACTURING AND TECHNOLOGY

    › Physical and chemical laboratories conduct over 130 tests to certify the quality of raw materials.

    AAAARRRRTTTTEEEECCCCHHHHEEEE GGGGrroouuppp mmaakkkkeess aaa sssttttrrrooonnnggg cccooommmmmmiiiittttmmmeeennntttt ttttooo iiinnnnoovvaatttiiioonn ((((RRR++DDD++iii)))) wwiiittthhh aann iiiinnnvvveeesssttttmmmeeennntttt oooffff 3333,,3333%%%% ffffrrrooommm 222000111333 tttuuurrrnnnooovvveeerrr.

  • 36 Instrument transformers | Low voltage

    4. QUALITY & ENVIRONMENT

    Exceeding environmental regulations, ARTECHE has been able to minimize the use off hazardous materials, energy consumption and waste generation.

  • 37Instrument transformers | Low voltage

    QUALITY & ENVIRONMENTEveryone in the ARTECHE Group works under the criteria set out in our environmental and quality policy.

    A sum of regulated procedures based on communication, teamwork, prevention analysis and continuous improvement, common to the whole organization.

    › Advanced sustainability criteria in production and in the creation and development of new products.

    › Compact designs, manufactured with minimal energy consumption and enviromental-friendly materials.

    › Internal and external skill motivation programs.

    › Advanced development of knowledge management.

    › Quality agreements with utilities. › Phys ico-chemica l and e lect r ica l laboratories for testing under any International Standard.

    › Type test reports issued by KEMA, CESI, LAPEM, RENARDIÈRES, etc.

    › Final testing according to specific customer requirements.

    › Approvals in more than 100 electricity companies.

    › ISO 14001:2004. › ISO 9001:2008. › OHSAS 18001:2007.

    AAAARRRRTTTTEEEECCCCHHHHEEEE’’’ss fifififi nnaanncciiiiaallll aanndddd tttteeeccchhhhnnnooollllooogggiiiicccaaallll iiiinnnddddeeepppeeennnddddeeennnccceee gggiiivveess aa ppprriiivviiillleegggeeddd pppoossiiitttiiioonn aaahhhheeeaaadddd oooffff tttthhhheee ccchhhhaaalllllllleeennnggggeeesss iiiinnn ttthhheee ssseeeccctttooorrr.

  • 38 Instrument transformers | Low voltage

    5. SERVICE

    Over 70 technical/sales service centers with real knowledge about each customer provide fast and close service.

  • 39Instrument transformers | Low voltage

    SERVICE

    › The solutions ARTECHE has developed and expanded upon have made it a major player participating in the most signifi cant events and workgroups in the electricity sector.

    › ARTECHE’s service is based on a close relationship with the customers, refl ected in the integrated post-sale assistance plan and structured client opinion system.

    › In addition to ensuring rapid response, ARTECHE developed a continuous service improvement plan, which sustains an extensive training program with courses, publications, conferences, etc.

    › ARTECHE’s focus on service, with a broad experience leading us to be an active participant in the electrical organizations such as: IEC, IEEE, CIGRE, CIRED, ASINEL, etc.

    › ARTECHE has production facilities on four continents (North America, South America, Europe, Asia and Australia) and more than 70 technical/commercial offices. Thus ARTECHE provides effective responses to the requirements of any customer and situation, based on the global knowledge acquired. AAAARRRRTTTTEEEECCCCHHHHEEEE hhhhaass tttthhhhee