    MASTER DIGITAL CONTROL UNIT FORLOCAL AND REMOTE MANAGEMENT

    OF HEATING PLANTS

    EXPANSION MODULES - SLAVES

    MASTERASTERSLAVELAVE

    EV91A

    EV90

    2003/05

    EV91C

    FANBUS

    EV92

  • 7/30/2019 Instruction EV90

    2/12

    USE

    Remote control EV90 is used in particularly complex plants where several different devices are required to solveheat regulation problems.The system consists of a master device EV90, and one or more slave devices connected to the master

    through a communication bus called a FANBUS.

    OPERATION

    The device operates as a central control unit. Through its display and keyboard the user may display and modifyparameters of slave control units connected to the FANBUS. A probe detects the value of the outside temperaturewhich is sent by means of the FANBUS to all relevant control units thereby avoiding duplication.The hour and date, including standard time, may be set directly on the front of the device and used by all devicesconnected to the BUS.Just one modem (analogue or GSM) lets you remotely manage and modify the parameters of the Master EV90and all other control units. When an alarm is triggered by a slave, it is first transmitted to the master EV90 and thento a remote station or to an enabled mobile phone.Another function of EV90 is boiler regulation (with 1 or 2 stages); it maintains a high enough boilertemperature to provide all connected users with heat.

    CHOICE OF LANGUAGE

    During installation it is possible to select the language used to view the Menus. With the control unit off press andhold the + key (see figure hereunder)and switch on the power. When theSCELTA LINGUA icon appears, re-lease the + key and scroll the lan-guages using the + and keys. Uponreaching the language desired pressthe > key. The instrument will displaythe information in the chosen lan-guage.

    DESIGN CHARACTERISTICS

    DIN 144x144 container, rapid couplingcontrol unit on base with FASTONconnectors and see-through cover.Protruding, built-in or back-of-boardmounting possibility. All parametersare displayed on a 4-line alphanumericdisplay with 16 characters per line. Tofacilitate reading in bad light, press anykey to light the display; the light goesoff after about 60 seconds of being idle(no key pressed).

    FANBUSFANBUS

    You may connect 15 different types of control units to the FANBUS with at most 8 of the same type of control units(so 15x8 = max of 120 control units).You may connect the EV90 to the slave with a simple low voltage, polarity free bifilar duplex cable (both wires maybe inverted with each other without causing malfunction). All slaves must be connected in parallel to the BUS.

    ADDRESS OF CONTROL UNITS

    Each control unit is identified by two digits that determine its address. The first digit represents the model andcannot be modified. The second one may be set through jumpers on each slave's terminal board:EV91A first digit: 1EV91C first digit: 2EV92 first digit: 3If only one control unit per type is present on the BUS, no intervention is needed.Since the second digit is automatically set =0, the control units will have the addresses 10, 20 and 30 respectively.

    If 3 EV91A control units are needed on the same BUS, you'll have to set address 1 on the second control unit, andaddress 2 on

    EV90 MASTER DIGITAL CONTROLUNIT FOR HEATING AND TECHNOLOGICAL PLANTS

    2

    TX

    RX

    1

    2

    EV90

    +

    -

    Use the + and keysto modify parameters

    Use the < and > keysto go from one pageto another

    Use the UP andDOWN keys tomove over a pageand to go from oneparameter toanother

    Two Tx and Rxsignalling LEDsi n d i c a t ecommunicationto FANBUS

    Two LEDs indicatestatus of bothoutput relays

    4-line, 16-characteralphanumeric display

    SCELTA LINGUA:

    ENGLISH

  • 7/30/2019 Instruction EV90

    3/12

    So, the result will be:1 - EV91A address 10 (no bridge = address 0)2 - EV91A address 11 (set address 1)3 - EV91A address 12 (set address 2)1 - EV91C address 20 (no bridge = address 0)1 - EV92 address 30 (no bridge = address 0)This way every control unit will have an address that identifies it unambiguously.N.B. the two digits of the address must go in front of all remote management commands for faultlesscommunication with the desired device.1 - EV91C indirizzo 20 (nessun ponte = indirizzo 0)

    ADDRESS OF CONTROL UNIT EV90

    The master control unit EV90D should be considered in the same way as a slave with a fixed address : 00. So, ifyou have to change the current time, for instance, you must send the change command preceded by 00.

    HOW TO SET THE ADDRESSES

    The purpose of connector A on each device is to supply power and to set its address through jumpers.This is convenient when the device must be replaced because, instead of losing the address, it is memorised inthe terminal board and so the new device will automatically assume the address of the old one.Below we have indicated the jumpers to make to have all combinations

    AUTOMATIC RECOGNITION

    When a new device is added to the BUS it is automatically recognised. After about 60 seconds master EV90is able to display and communicate with it.

    A

    1 2 3 4 5 6 7 8

    A

    1 2 3 4 5 6 7 8

    A

    1 2 3 4 5 6 7 8

    ADDRESS "1"

    A

    1 2 3 4 5 6 7 8

    ADDRESS "5"

    ADDRESS "0"

    ADDRESS "4"

    A

    1 2 3 4 5 6 7 8

    A

    1 2 3 4 5 6 7 8

    ADDRESS "3"ADDRESS "2"

    A

    1 2 3 4 5 6 7 8

    A

    1 2 3 4 5 6 7 8

    ADDRESS "7"ADDRESS "6"

    3

    BOILER

    EV90

    BOILERPROBE

    RETURNPROBE

    EXTERNALPROBE

    2-STAGEBURNER

    SLAVE 1 SLAVE 2 SLAVE 3 SLAVE 4

    FANBUS

    GENERAL DIAGRAM

  • 7/30/2019 Instruction EV90

    4/12

    PLANT MANAGEMENT

    In normal conditions control unit EV90 shows a list of connected slaves.The first one on the list is EV90 itself, followed by a description of the devices and their address.This description may be modified as desired for every slave and it may be useful to easily identify the devices.Use the up and down keys to position the cursor on the desired slave. Press the > key to communicatewith the slave and display and modify its parameters.

    4

    MAIN MENU

    MASTER control unitList of SLAVE control units + address

    Device Type EV90 00GYM 10SOUTH BUILDING 11SANITARY 40BOILERS 1-2 20BOILERS 3-4 21INPUTS 50OUTPUTS 30.

    OPERATION AS CONTROL UNIT OF BOILER

    OPERATION

    Besides performing the function as the master of a plant, theEV90 may be used as the control unit of a boiler with eitherfixed temperature or sliding temperature, by directlycommanding a one- or two-stage burner.Through a measuring probe the device detects thetemperature value of the boiler. If the temperature value fallsbelow differential 1, the first stage is turned on, and if it fallsbelow differential 2 and stays there for a certain length of time,the second stage is also turned on.The command of the relays is visible on the front of thedevice.The boiler may be turned on and off according to a weeklyprogram that may be set on the same control unit.

    CALCULATED BOILER TEMPERATURE

    The boiler temperature the control unit calculates may be fixed or sliding. When it is fixed, the value set will notbe changed, but when it is sliding, the value set is added to the highest temperature value required byconnected slaves. This way it is possible to regulate the boiler with a temperature that continually variesdepending on the requirements of the entire plant.N.B. when you are setting the desired boiler temperature value, bear in mind that with fixed point regulation it isthe value the control unit uses, and with sliding regulation, it represents an increase with respect to the highestvalue decided by the various control units of the plant.

    LIMITS

    You may set the highest and lowest boiler temperature limits within which the calculated temperature mayvary.The control unit will ensure that these values are not exceeded.

    DIFFERENTIAL 1

    Differential of the first stage. It indicates the temperature difference with the one calculated by the control unitbelow which the first stage of the burner is turned on.

    DIFFERENTIAL 2

    Differential of the second stage. It indicates the temperature difference with the one calculated by the controlunit below which the second stage of the burner is turned on. To avoid useless or ill-timed interventions, thissituation should persist for a certain length of time (may be set on the control unit).

    BOILER T.

    DIFF. 190

    8070

    60

    50

    40

    30

    20

    100

    DIFF. 2

    CALCULATED T.

    STAGE 2 ON

    STAGE 1 ON

  • 7/30/2019 Instruction EV90

    5/12

    EXAMPLES OF PLANTSPlant 1

    -command of 2-stage boiler-two independent heating circuits-remote management with GSM modem-the devices' addresses are in brackets

    Plant 2

    -command of two cascaded boilers

    -two heating circuits-boiler regulation for sanitary hot water-Remote management with GSM modem

    BOILER

    EV90

    BOILERPROBE

    EXTERNALPROBE

    EXTERNALPROBE

    EXTERNALPROBE

    2 - STAGEBURNER

    MODEM

    ANTENNA

    EV91A

    FANBUS

    EV91A

    M

    (10) (11)

    (00)

    M

    SC

    B2B1

    V1 V2

    EV91A(11)

    SANITARY WATER

    EV91A(10)

    EV91B(30)

    ANTENNA

    EV91C(20)

    FANBUS

    FANBUS

    EV90MODEM(00)

    M

    M

    M

    BOILER

    1BOILER

    2

  • 7/30/2019 Instruction EV90

    6/12

    INSTALLATION

    INSTALLING THE CONTROL UNIT

    Fully loosen the tie rod to release the base of the control unit.Lever on the slots with a screwdriver to remove the base.After you have made the electric connections, press the FASTON connectors of the control unit into the couplingsof the base until they are fully inserted.Tighten the tie rod.

    EXTERNAL PROBE EC81

    Install the external probe in a vertical position onto the north or north-west side of the building at least 2.5m from the ground.Apply the probe far from heat sources (windows, aerators, flues, etc.) to detect a meaningful temperature for the whole plant.N.B. It's always possible to install one of the external probes on control unit EV91A. The device will automaticallyuse the value measured by its probe instead of the one transmitted by EV90 through the FANBUS.

    BOILER AND RETURN PROBE EC82-EC83

    Contact probe EC82 must be applied onto the water pipe with a special clamp. Put some thermal compoundbetween them to ensure good heat conductivity. For the same reason immersion probe EC83 must be inserted inthe sheath filled with mineral oil or silicone grease.

    CONNECTION TO THE FANBUS

    Connect the control units to the Master EV90 through the FANBUS. Bear in mind that the bus has low voltage andis not polarised, so the terminals may be inverted with each other without causing malfunction

    ADDRESS OF CONTROL UNITS

    The control units must be addressed to work properly and to be questioned by remote management.Make sure that they are properly configured.

    BACK-OF-BOARD

    138

    138

    BUILT-IN

    138

    138

    93WALL MOUNTING

    4,5

    55110

    60

    55

    DIMENSIONS OF CONTROL UNIT EV90 AND MOUNTING SYSTEMS

    TEMPERATURE PROBE

    14491

    110

    144

    136

    Fasteningscrewlo

    EC81 EC82 EC83

    EXTERNAL PROBE EC81

    TEMPERATURE RESISTANCE

    C W

    DELIVERY PROBE EC82 EC83

    TEMPERATURE RESISTANCE

    C W

    Resistance values based on the temperature:

    6

    12090

    8313582841613021222916691266973

    + 20

    + 30+ 40+ 50+ 60+ 70+ 80+ 90+100

    - 20

    - 15- 10- 5

    0+ 5+10+15+20

    5592

    44993650297924492024168414081184

  • 7/30/2019 Instruction EV90

    7/12

    WIRING DIAGRAM

    CALIBRATION AND ADJUSTMENT

    FACTORY SETTINGS

    The control unit leaves the factory with all parameters set for normal operation. If it is necessary to reset factoryparameters, proceed as follows: turn off the power supply, then turn it on again while pressing the + key on the front.All data entered will be lost, while factory parameters will be reset.

    CALIBRATION AND ADJUSTMENT

    Every time power is supplied to control unit EV90, a configuration procedure starts for all devices connected to thebus.After about 60 seconds you may use the unit's keyboard and display to connect with these devices for modificationsand readings since the device acts as if it were a display and remote keyboard for all

    MENUS RELEVANT TO CONTROL UNIT EV90COMMAND KEYS FOR MENU READING AND DATA MODIFICATION

    17

    21

    18

    3

    4

    5

    19

    6

    7

    8 16

    15

    14

    22

    13

    12

    11

    109

    21

    20

    N.B. RELAY CONTACTS ARE VOLTAGE FREE

    POWER SUPPLY

    RS232 TX

    RS 232 RX

    RS232 0V

    230V

    STAGE 1COMMAND

    STAGE 2COMMAND

    RETURN PROBE

    DELIVERY PROBE

    EXTERNAL PROBE

    AL MODEM

    FANBUS

    7

    +

    -

    Use the UP and DOWNkeys to move over a pageand to go from one

    parameter to another

    Use the < and > keys to gofrom one page to another

    Use the + and keys tomodifyparameters

  • 7/30/2019 Instruction EV90

    8/12

    MAIN MENU

    It contains a list of available submenus. To enter a submenu, press the -> key

    INFORMATION SUBMENU:

    01/APR/2003MONDAY 14.35Outside T.: -02.5Boiler T.: 58.5

    Plant Description:EV90 Control Unit

    FANTINI COSMIVia Dell'Osio, 6Caleppio MILANEV90 Rev.01

    Value of boiler temperature

    The user may modify the plant description.This may be useful to identify the plantcommanded by the control unit

    Device code and revision

    8

    List of submenus of

    ontrol unit EV90

    MENU EV90.

    >Information>Boiler Regulation>Programming Schedules>Set Current Time>Remote Management>Temperature Limit..................................

    Device Type.........................................

    EV90 00GYM 10SOUTH BUILDING 11

    SANITARY 40BOILERS 1+2 20BOILERS 3+4 21INPUTS 50OUTPUTS 30.

    Boiler programming:Always onmode: On

    Desired SlidingBoiler Temp.DTC:13.5

    Boiler Temp Limits:Highest :98.0Lowest: 10.0

    Sliding RegulationMaxT+DTC=Tcc12.0 13.5 25.5

    Stage 1 Differential :04.0Stage 2 Differential:0.8.5

    Auxiliary StageCommand AfterDelay of : 02.00Minutes

    To set boiler operation to always on, alwaysoff or according to programming schedule

    Desired temperature : fixed or slidingIf fixed, the value set is the one usedby the control unit (DBT). If sliding, it ishigher (DBT) than the highest value

    required by the plant's control units.

    Tcc represents the desired boilertemperature value. It takes accountof the highest and lowest limits, thehighest temperature of the plant, etc.

    Setting of boiler differentials

    The burner's second stage isturned off after this delay if thetemperature falls below differential 2.

    BOILER REGULATION SUBMENU:

  • 7/30/2019 Instruction EV90

    9/12

    MON. on-off Copy07.0 09.3017.0 22.30TUE. on-off Copy

    07.0 09.3017.0 22.30------- -------

    WED. on-off Copy07.0 09.3017.0 22.30

    ------- -------

    THU. on-off Copy

    07.0 09.3017.0 22.30------- -------

    FRI. on-off Copy07.0 09.3017.0 22.30------- -------

    SAT. on-off Copy07.0 09.3017.0 22.30------- -------

    SUN. on-off Copy07.0 09.3017.0 22.30------- -------

    Weekly programming of the boilerUse the keys to go to the desiredvalue and change it.Position the cursor on the word Copyand press the + key to copy a programto the next day

    9

    PROGRAMMING SCHEDULES SUBMENU:

    Set time

    Day: SundayTime: 17.45Date: 07/APR/2004

    Daylight Saving TimeStart: 17/MAREnd: 28/OCT

    To set current time and date

    To set the starting and ending date of daylight saving time.The control unit automatically updates the time.

    SET CURRENT TIME MENU:

    Device Triggering

    Alarm No.Send AlarmIn 00 Minutes

    Connection toSerial Bus withGSM Modem

    Operator No.1 Phone Number123456789

    Operator No. 2Phone Number123456789

    Operator No. 3Phone Number123456789

    It indicates the address of slave device currently triggering

    alarm and the time lapse before the next alarm call.

    To set modem type: GSM (for SMS management) or PSTN analog(for analog modem or GSM modem in data mode)

    To set the telephone numbers to send alarms to.Unused digits must be cancelled .

    N.B. an alarm is immediately sent to operatorNo. 1. and after 15 minutes to Nos. 1 and 2,and after another 15 minutes to Nos. 1, 2 and 3.

    REMOTE MANAGEMENT SUBMENU:

    Lowest TemperatureLimitSet : 45.5Measured: 56.0

    If the temperature falls below the set limit,all the slaves connected to the FANBUSreduce their heat requirement. To excludethis function, do not connect the limit probe.

    SOTTOMENU - TEMPERATURA LIMITE

  • 7/30/2019 Instruction EV90

    10/12

    CONNECTING THE MODEM

    Follow the diagram below to connect the EV90 to the modem.It's necessary to connect pins 7-8 and 4-6 to each other for faultless communication.

    PREPARING THE MODEM

    Both the GSM and the analogue modem supplied by Fantini-Cosmi will work properly. Another modem may be usedprovided that the communication speed is 2400bit/sec. To do this, use the command AT+IPR =2400 and save the newconfiguration with the command: AT&W.If a GSM modem is used, use and memorise the command AT+CMGF=1 to set the SMS message format to text mode.

    USING A SIM CARD

    The GSM modem works with any SIM card. Before using one, however, we recommend that you test it in a mobile phone

    to see if it's working. Particularly:-check that no PIN code has been set. If so, try to exclude it-Check the remaining credit-Send an SMS message and check if it arrives

    After these checks, install the SIM card in the modem connector

    OPERATION

    When a GSM or analogue modem is connected to the EV90, you may remotely read and change some of its data anddata of all devices connected to the FANBUS. To properly communicate with the desired device, every command mustbe preceded by two digits representing the device's address. So, to address commands to unit EV90, you must firstenter 00. All possible commands for each slave are described on the instruction sheets for each device.

    REMOTE MANAGEMENT SMS COMMANDS

    These commands may be used through a mobile phone by sending an SMS message containing the message to theunit's GSM modem. It answers with a reply SMS message to the phone number that requested the information.To facilitate message reading, the information is enclosed in a sign. And every reply message is preceded by

    a description of control unit EV90, at times followed by a description of the slave control unit to easily identify the sender.

    22

    13

    12

    11

    10

    9

    21

    20

    1

    2

    3

    4

    5

    6

    7

    8

    9

    TX

    RX

    0V

    EV90MODEM CONNECTORMALE CONNECTOR DB9

    N.B. this connection is availableas an accessory with code TCEV80

    10

    REMOTE MANAGEMENT

    DATA CONNECTION

    TELEPHONE LINE

    ANALOGOR GSM

    DATA MODEM

    DEDICATEDSOFTWARE+

    SMS GMSMODEM

    ANTENNA

    4

    1

    7

    5

    2

    8

    0

    6

    3

    9

    VD

    SI

    IAELLO

    O

    6

    CAL

    IC

    O

    DAI NBLOC

    A

    SMS CONNECTION

    By connecting the EV90 controller to a GSM modem, the significant parameters of the control unit can be set or read (see SMS remotecontrols). To connect the controller to an analog or GSM modem follow the instructions relative to the wiring diagram to connect the modemor use the TC EV85 cable.N.B. The maximum length between controller and modem is 15 metres. If management takes place via a GSM modem a mobile phone canbe used. If an analog or GSM modem in data mode is used, it is necessary to use a Personal Computer with dedicated control softwareavailable only in Italian provided by Fantini Cosmi or downloaded over the Internet.

    ANALOG OR GSMDATA MODEM

    RS232 SERIAL CABLE

    RS232SERIALCABLE

    RS232 SERIAL CABLE

  • 7/30/2019 Instruction EV90

    11/12

    -???It is used to know which SMS commands may be sent.-Reply: list of possible commands

    -STATUS=?-Reply: information about state of control unit such as temperatures read and set, current time and date

    -TIME=12.33It sets the current time

    -Reply: information about state of control unit such as temperatures read and set, current time and date

    -BOILERT=82.5It sets the desired boiler temperature without changing the fixed or slidingtemperature selection-Reply: information about the state of the control unit

    -BOILERT=82.5FIt sets the desired FIXED boiler temperature-Reply: information about the state of the control unit

    -BOILERT=82.5SIt sets the desired SLIDING boiler temperature

    -Reply: information about the state of the control unit

    -PROGx=?-It programs the day x, where x represents the day of the week 1 = Monday, 2 = Tuesday, etc.-Reply: all 6 programming schedules for that day

    -PROGx=07.00-09.30 17.30-22.00 --.----.--

    It sets a program schedule for the day there are 3 on and 3 off periods by specifying hours and minutes.

    Unscheduled periods should be filled in with dashes. Leave a dash or a space between two periods.

    -Reply: all 6 programming schedules for that day

    -PAUT It sets the automatic programming schedules-Reply: information about the state of the control unit

    -PONIt sets the always on program-Reply: information about the state of the control unit

    -POFFIt sets the always off program

    RESETIt deletes any alarms

    Reply: ALARMS DELETED

    11

    TECHNICAL CHARACTERISTICS

    Power supply 230V 50Hz

    Power consumption 5 VA (4W)

    Contact rating 5A-230Vac (Ohmic charge) voltage free contacts

    Ambient temperature: 0 50C

    Weekly programming clock, 5-year battery life, automatic management of daylight saving time

    (DST)

    Compliant with norm EN60730-1

    Measuring probes:

    - EC81 external probe

    - EC82 contact probe

    - EC83 immersion probe

  • 7/30/2019 Instruction EV90

    12/12

    12

    3 relays: 5A-250V ac (AC1)1 analogic input for temperaturemeasurement

    EV91B- Weekly programming with 6 on and offperiods per day

    - Water temperature regulation: 0+100C

    FIXED SANITARY HOT WATER TEMPERATUREREGULATION MODULE

    - 4 relays: 5A-250V ac (AC1)2 analogic inputs for temperaturemeasurement

    EV91C -Water temperature regulation: 0+100C- High and low limits for boiler temperature- At most 8 connected boilers

    REGULATION MODULE FOR TWO CASCADED BOILERS

    4 relays: 5A-250V ac (AC1)

    EV91D

    - Configuration of all 4 relays: RelayON- Relay OFF Timed Relay

    - daily programming for all 8 outputs

    GENERIC OUTPUT MODULE

    TEMPERATURE REGULATION MODULE WITHEXTERNAL PROBE

    EXPANSION MODULES (SLAVES)

    TYPE CHARACTERISTICS Input and outputs relays

    TYPE CHARACTERISTICS Input and outputs relays

    TYPE

    TYPE

    TYPE

    CHARACTERISTICS

    CHARACTERISTICS

    CHARACTERISTICS

    Input and outputs relays

    Input and outputs relays

    Input and outputs relays

    EV91A

    - 1 FANBUS communication channel for

    connecting Slaves to Master EV90- All parameters may be displayed and

    modified through the Master EV90

    DIGITAL INPUT MODULE

    8 voltage free digital inputs

    EV92

    - Setting of active state for all 8 inputs:opening- closing

    - Configuration for all 8 inputs:Activated breakdown Desactivatedbreakdown Timed breakdown

    - Daily programming for each input

    - Mounting on DIN rail, 6 modules

    - Power supply 230V 50Hz- Power consumption 7 VA- Removable terminal boards to facilitatewiring

    - Regulation curve broken by 4temperatures

    - Weekly programming with 6 on and offperiods per day

    - Optimisation of switch-on time

    4 relays: 5A-250V ac (AC1)1 analogic input for outside temperature(optional)1 analogic input for deliverytemperature