Innovative Solution for DC Traction Power Supply
Version 4.0
Remote evaluationvia modem orinternet(VPN)
Central evaluation system
Remote evaluationvia modem orinternet(VPN)
Central evaluation system
System Configuration of DC Traction Power Supply
ENTEC's Innovative Solution for DC Traction Power Supply 02 _ 03
ENTEC's advanced technology and endless innovation for DC Switchgear in DC Traction Power Systemwill contribute to a brighter approaching future. DC Switchgear is the essential equipment for SafeOperation in DC Traction Power System. ENTEC's DC Switchgears have been designed and optimizedfor DC Traction Power System and can also be utilized in heavy applications.
CharacteristicsWide Range Current Interruption
No dead zone
High quality componentsHSCB and Diconnector designed for frequent operation duty
Reliable protection relaySpecialized for Metro Power Traction Systemall information recorded
Outstanding arc quenching technologyPatented Boil Coil designFrame free from spewed-out arc
Rigid & Convenient DesignCompact design, easy installationwithdrawable HSCB truck, easy maintenance Strong cubicle structure by welding each part
DC Switchgear for DC Traction Power System
❶
❷
❼
❾
❿❽
❸
❹❺
❻
❷Surge ArresterSurge (Lightening Surge,Inductive surge) prevention.
❶DC HSCB(Incl. truck)Fast fault current clearing in a faultoccasion.Several Interlock funtions areapplied in Circuit Breaker.
❻DC Power meter (kWh)Power consumption calculation.
❺ 64P (Voltage type)Monitoring earth voltage potential increasing and protect system.
❹ 64HR (Current type)Monitoring between DC livebus and enclosure, Protectearth current.
❼DC DisconnectorPower line close and openwhen no load.
❸FaultselectiveRelay(50F)Determine faults and operateCircuit Breaker (Digital type).
❾DC PTPrimary voltage sensing.
❿Communication Device❽DC CTCurrent Sensing.
ENTEC's Innovative Solution for DC Traction Power Supply 04 _ 05
Nominal VoltageRated VoltageInsulation VoltageRated interrupting over voltageRated currentRated making and breaking capacityOperation dutydi/dt (Current rising rate vs time)Mechanical operationPower frequency withstand voltag (60Hz,1min.)Rated operation and control voltageOver current Release Pick-upMax. Ambient Temp / Avg. Temp.Altitude
Size [Width x Depth x Height mm]*
Weight [kg]IP protection (IEC 529)Applied standard
DC 750VDC 900V
DC 1,800V
8.3kV/6.9kV
650
1.5 ~ 2 x rated voltage3000A/4000A/6000A
178kAp/125kA 110kAp /76.8kAO-15sec-CO-15sec-CO-60sec-CO (max fault, max energy, distant fault)
30.7 x 106A/S 24.2 x 106A/S40,000 times
DC 110V / 220V2~8kA,6~12kA
40℃ / 35℃≤2,000m
> IP31IEC 61992
DC 1,500VDC 1,800VDC 3,000V
11kV/9.2kV
700
Model ETGR 21 ETGR 22Ratings
Option Size [Depth] : 1,900mm(When adding a function of automatic withdrawal, for other sizes, discuss with maker)
Rectifier, Feeder (600 x 1,800 x 2,200 / 600 x 1,500 x 2,200)Negative (1,500 x 1,800 x 2,200 / 1,200 x 1,200 x 2,200)
OperationElectrical operation Mechanical Operation
Manual closing device by requestClose HSCB without external power supply.
Manual Closing Device(DC HSCB)
Trip HSCB under emergencyMust be held when withdrawing or inserting HSCB
Manual Trip Device(DC HSCB)
Close or open Disconnection Switch(DS) without power supplyManual Close/Open(DC DS)
(Fault selective Relay, DC Ground Relay, Undervoltage Relay, Reverse Current Relay, OCR,Intertripping Signal Relay, Lock-Out Relay)
Trip by protection Relay System
Trip by Direct Fault CurrentLocal Close/OpenRemote Close/Open
Standard Type and Test Graph
Panel Type
DC HSCB 'CO' Test Oscillogram
Rectifier Feeder Spare Tie post Neg. DS
Widrg[mm] 600 600 600 600 1,500
Standard type
Type Test
Test Graph
Disconnector Test Oscillogram
Other application available upon user request.
ENTEC's Innovative Solution for DC Traction Power Supply 06 _ 07
DC HSCB is used to manage DC Power Feeding line and interrupt a fault current.EDB Series is designed with the most advanced technology in order to protectRailway system from abnormality of Power feeding system. Under high frequencyswitching and heavy load condition, EDB Series DC HSCB is the most reliable choice.EDB Series have rated voltage of DC 900V for light weight railway system (EDB-09)and rated voltage of DC 1800V for urban and heavy railway system(EDB-18).
DC High Speed Circuit Breaker(DC HSCB)
Nominal voltageRated voltageRated currentRated interrupting over voltage
Operation duty
Mechanical OperationRated making and breaking capacityRated operation voltage
Phase-Phase Phase-Ground Control Circuit
Over current trip device(76I)Size[Width x Depth x Height]Applied standard
DC 750VDC 900V
345×913×831.5
3000A / 4000A / 6000A1.5~2.5×Ue
O-15sec-CO-15sec-CO-60sec-CO(max fault, max energy, distant fault)
40,000 times178kAp / 125kA 110kAp / 76.8kA
DC 110V / 220VAC 11kV/1minAC 9.2kV/1minAC 2kV/1min
2~8kA, 6~12kA
IEC 61992
DC 1,500VDC 1,800V
345×913×881.5
Model EDB-09 EDB-18
Ratings
Insulationvoltage
Enhanced small current interruption0 ~ rated making and breaking current
High Durability and ReliabilityPMA Mechanism over 40,000 times of operationGuaranteed high speed overcurrent tripping
Quality AssuranceInternational authorized laboratory(IPH CESI, KERI) type tested
Sufficient current and thermal capacityHigh cooling efficiency 85 or lower under normal conditions.
High Insulation capacity and increased interruption capabilityTo ensure personnel safetyTo fulfill heavy interrupting duty
Optimized design with simple structureSimple installation, simple maintenance
Panel InterfaceSmart interface with protection relay
Characteristics
DC HSCB
DC Diconnector & Load Break Switch
1600A1000A1250A1600A6400A
13000A120 cycles/h
2500A20002500
-10000A20000A
60 cycles/h
DC Disconnector is used for no load switching in DC system. ET-DS design is compactand optimized to be integrated in DC switchgear and other applications. In addition, sufficient insulation capacity and electric current capacity increase thesafety level of the product. Fast operation time is also appealing in perspective of userconvenience.
Nominal voltageRated voltageRated currentRated short time currentOperation voltageOperation methodMechanical OperationOperation time
Phase-PhasePhase-Ground Control Circuit
Size[Width x Depth x Height]WeightApplied standard
DC 750/1500VDC 900/1800V4000 / 6000A
178kAp/125kADC 110V / 220VAuto / Manual100,000 times
Below 2secAC11kV/1minAC9.2kV/1minAC 2kV/1min
300×507×450mm32kg
IEC 61992
Model ET-DS
Ratings
Disconnector
Load Break Switch
Insulationvoltage
DC LBS has been developed to provide making and breaking capacity to suit differentsituations. The safety and reliability are ensured by fast operating speed, safeinterruption of the arc and so on.
Rated operational voltage UeRated insulation voltage UiRated impulse withstand voltage UimpNumber of polesFrame size
Rated breaking capacityRated short-time withstand current Icw (1sec)Maximum electrical switching frequencyOverall dimensionsOperation temperatureVersions
Mechanical durabilityRated control voltageStandard
1500V3.82kV12kV
3
Please consult us-25 ~ +70
Electric holding / Mechanical latch holding
Insulated / Network with earthed negative polarity /Network with the mid-point earthed
2 millionsDC 24, 48, 110, 220V, AC 220V
IEC 60947-1, 60947-4-1
Model ET-LBS
Ratings
Rated operational current
According to the type of DC network
ENTEC's Innovative Solution for DC Traction Power Supply 08 _ 09
VLD(Voltage Limiting Device)
Real time rail voltage monitoringProtection against rail and / or earth voltage increasingSelective Ground Fault Protection
Function of VLD (IEC62128-1)
Rating Voltage [ V]Rated Current [A]Rated short-timeWithstand current [kA]
HV contactorHV contactor + Thyristor
Mechanism Life [times]Control Voltage [V]Standard
1,250DC 900 DC 1,800
50(250ms)
DC 25 ~ 300V / 0~1,000sDC 300 ~ 1,000V / Inst.
1,000,000DC 110V or AC 220V
IEC61992-6, BS EN 50122
Model ETOVPD 22Configuration & Specification
Principle of VLD Maximum permissible touch voltage(IEC62128-1)
Pick-upVoltage range
Voltage limiting device
ETCPU200or
ETCPU300
Fault Lamps
V,A-Meter
Control S/W
Counter(Contactor & Thyristor)
❶
❷
❸
❹
❺
❷HV. contactor❶Driver
❹DCCT ❺DCPT
❸ Thyristor
Protection Relay ETCPU & Interface software ETIMS
ETCPU200 + ETHMI
ETCPU300
Various line protection functionVarious communication protocolsMonitoring function: Current, voltage, Delta-I, di/dt etc.Storage function: operation and fault event, fault waves etc.PLC functionMultiple language supportedInterface PC software
With Interface Software ETIMS, ETCPU can be connected to and exchange data with a computer very easily and variousother functions can also be realized.
System Setting
PLC Edit
System information
System event
Diagnostic event
Load profile Wave form (Hourly)
Load profile Wave form (Daily)
Fault event
Fault wave summary & Fault wave form
Features
Interface Software ETIMS
Control Voltage [ V]Digital InputDigital OutputAnalog InputCommunicationData Saving
SIZE(mm)
Protection
DC 110 V / AC 220 V
IEC61850, IEC60870-5-101/104, DNP 3.0, ModBus, etcSystem history(1,000), Fault event(100), Fault waves(16), Load waves (3years), etc
Fault elective relay(50F) / Over current relay(76D) / Voltage relay(45,80) /Ground fault relay(64P) / Reclosing relay(82)
Model ETCPU 300ETCPU 200
Ratings
40 points24 points
8 ch.((±20mA or ±10V)
36 points24 points
16 ch.((±20mA or ±10V)
W275 D180 H160 W300 D240 H270
Earth
Train location
Potential betwee
n
rail and earth
V(-)
V(+)
DC(+)
A S/S(Sub sta tion)
B S/S(Sub sta tion)
DC(-) DC(+)DC(-)
DC(+)
F2F1
DC(-)
A S/S
DC(+)
CloseF2F1
DC(-)
B S/S
Close
DC(+)
F2F1
DC(-)
C S/S
DC(+)
F2F1
DC(-)
D S/S
VLD VLD VLD VLD VLD VLD VLD
ENTEC's Innovative Solution for DC Traction Power Supply 10 _ 11
SCMS (Stray Current Monitoring System)
Generally, the amount of stray current can be estimated indirectly by measuring return circuit’s resistance value againstground or rail potential caused by rail operation because it is difficult to measure stray current directly.
IMAX = 2.5 mA/m
Principle of SCMS
Voltage data acquisition, recording, plotting and real time monitoringAnalyzing of voltage data and alarmingReporting voltage data and VLD status historyData transmission to SCADA(through communication)Localization of the fault location
Functions of SCMS
VLDETCPU200 CMS (Central monitoring server)
Line Overview Alarm Viewer Trade Page ManagerConfiguration of SCMS
Reference electrode (IEC62128-2)
Open formation GRE 0.5 S/km per trackVRE 5V
Closed formationGRE 2.5 S/km per trackVRE 1V
225-38 Choirubaekro, Bongdam-Eup, Hwaseong-City, Gyunggi-Do, Republic of KoreaPost Code : 18329TEL: +82-31-299-8400 FAX:+82-31-299-8401~2http://www.entecene.co.kr E-mail: [email protected]
*Note. Product structure and arrangement shall be modified without notice. 1609
High Efficiency ( 99%)Current Unbalance ratio less than +/- 10%Full Load Operation of the Diode n-1 Condition Graphic User Interface ApplicationReal-Time Monitoring System & AlertsCompact and Convenient Maintenance with design Rectifier Operation History Storage etc.
Key Features
Rated Input Voltage Rated Output Voltage
Rated CurrentRated Frequency Over-load RatingInput SystemOutput PulseCooling MethodPower Frequency Withstand VoltageDiode TypeDiode Max Unbalanced CurrentFull Load Efficiency Maximum Noise StandardRated Control Voltage
IP Protection (IEC 529)Apply standard
*Rated Capacity
Maximum Environmental Temperature/Avg. Temp(Days)/Avg. (Year)
Model ETSR22ETSR21
Ratings
AC 300V (1,200V) DC 750V
1,000/2,000kW
1,333/2,667A
2,350V
AC 600V (1,200V) DC 1,500V
2,000/3,000/4000kW
1,333/2,000/2,667A
4,140V
* other ratings : consultation with customer
50/60HzContinuous at 100% current / 2Hrs at 150% / 1Min at 300% (Class VI)
Rectifier Tr ( / ‚ or / -Y) 6P or 12P
Self-Cooling
Silicone+/- 10%
99% 60dB
DC 110V and others
40 /30 /25
IP 31IEC 60146-1-1, 146-2 etc.
Silicone Rectifier