Inertia Base Isolator Selection

Embed Size (px)

Citation preview

  • 8/18/2019 Inertia Base Isolator Selection

    1/1

    CALCULATION FOR INERTIA BASE

    1

    DIMENSON OF INERTIA BASE

    Length

    Width

    Height

    2.70 m

    0.86 m

    0.15 m

    2.

    VOLUME

    OF INERTIA BASE

    v LxW xH

    = 2.70 m x 0.86 m x 0.15 m

    = 0.348 m

    3

    or

    0.348 m

    3

    x 35 .31

    v = 12.28 Ft

    3

    3. WEIGHT OF INERTIA BASE, w

    w =

    weight

    Concrete

    +

    weight

    Steel

    wt

    Concrete = 12.28

    Ft

    3

    x 150

    bsl

    Ft

    3

    = 1,842

    Ibs or

    837

    kgs

    wt

    Steel = 160 Ibs

    or

    7

    kgs refer to

    Data Sheet)

    w = 837

    kgs +

    73

    kgs

    = 910

    kgs

    4. LOAD ON

    SPRING

    Total Load = wt Inertia Base

    +

    wt Pump and Motor

    +

    wt Fittings

    +

    Hydraulic Load

    .wt

    Inertia

    Base = 910

    kgs

    wt

    Pump and

    Motor

    assembly = 752 kgs

    wt

    Pipe and Fittings = 240

    kgs approximate)

    Hydraulic Load = Pump Head x Cross-sectional Area

    of

    pipe

    160

    ftH20

    x 0.0304

    kgjcm

     

    j

    feetH20

    x pi 10.12cmf =1,567

    kgs

    Total Load =910

    +

    752 + 240 + 1567 =

    A69

    kgs

    Load per

    spring

    =

    3,469

    kgsj 4 = 867 kgs

    Spring Capacity =1000 kgs x 4 nos