Industrial Motor Solutions Page 1 of 11 20120723 Industrial and Plant Protection Session Industrial Motor Solutions Available Data for SEL-710 Retrofit Motor Data Motor horsepower: 2700 hp Rated voltage: 4000 V Full load amperes (FLA): 359 A Service factor: 1.15 Locked rotor current: 2334 A Hot stall time: 18 seconds Overload time at 2 per unit (pu): unknown System Data System phase rotation: ABC Phase current transformer (CT) ratio: 500/5 Ground CT ratio: 50/5 (zero-sequence connection) Phase potential transformer (PT) ratio: 4200/120 Phase PT connection: open delta Maximum bus fault: 30841 A Maximum ground fault: 400 A Contactor interrupting rating: 720 A Fuse: CLF 38R Other Application Information Contactor to trip on: Overload Unbalance Ground overcurrent Phase rotation Load jam Resistance temperature detector (RTD) Acceleration Lockouts Single phase

Industrial Motor Solutions SEL 710

  • Upload
    long

  • View
    100

  • Download
    13

Embed Size (px)

DESCRIPTION

share from the training mat SEL

Citation preview

  • Industrial Motor Solutions Page 1 of 11 20120723

    Industrial and Plant Protection Session

    Industrial Motor Solutions

    Available Data for SEL-710 Retrofit

    Motor Data Motor horsepower: 2700 hp

    Rated voltage: 4000 V

    Full load amperes (FLA): 359 A

    Service factor: 1.15

    Locked rotor current: 2334 A

    Hot stall time: 18 seconds

    Overload time at 2 per unit (pu): unknown

    System Data System phase rotation: ABC

    Phase current transformer (CT) ratio: 500/5

    Ground CT ratio: 50/5 (zero-sequence connection)

    Phase potential transformer (PT) ratio: 4200/120

    Phase PT connection: open delta

    Maximum bus fault: 30841 A

    Maximum ground fault: 400 A

    Contactor interrupting rating: 720 A

    Fuse: CLF 38R

    Other Application Information Contactor to trip on: Overload

    Unbalance Ground overcurrent Phase rotation Load jam Resistance temperature detector (RTD) Acceleration Lockouts Single phase

  • Industrial Motor Solutions Page 2 of 11 20120723

    Solutions

    SEL-710 Main Settings

    Identifier UNIT ID LINE 1 (16 characters) RID := NAT GAS COMP A

    UNIT ID LINE 2 (16 characters) TID := I-44

    Configuration PHASE ROTATION (ABC, ACB) PHROT := ABC

    PHASE CT RATIO (1 to 5000) CTR1 := 100

    MOTOR FLA (0.20 to 5000.00 A) FLA1 := 359.00

    TWO SPEED ENABLE (Y, N) E2SPEED := N

    NEUTRAL CT RATIO (1 to 2000) CTRN := 10

    PHASE PT RATIO (1.00 to 250.00) PTR := 35.00

    LINE VOLTAGE (100 to 30000 V) VNOM := 4160

    XFMR CONNECTION (WYE, DELTA) DELTA_Y := DELTA

    SINGLE V INPUT (Y, N) SINGLEV := N

    Thermal Overload Settings: Function 49T

    Existing Relay Data Relay type: GE Multilin SR 269+

    Minimum pickup: 1.25 full load current (FLC)

    Custom curve enabled: no

    Selected overload curve: 3

    Initial start thermal capacity: 40 percent

    Start inhibit enabled: no

    FLC thermal capacity reduction: 15 percent

    Thermal capacity used (TCU) alarm level: off

    Defeat learned cool time: yes

    Running cool time: 15 minutes

    Stopped cool time: 30 minutes

    Defeat RTD thermal memory input: yes

  • Industrial Motor Solutions Page 3 of 11 20120723

    Your SEL-710 Relay Settings OVERLOAD ENABLE (Y, N) E49MOTOR := Y

    FULL LOAD SLIP (OFF, 0.0010 to 0.1000 pu) FLS := OFF

    THERMAL METHOD (RATING, RATING_1, CURVE) SETMETH := RATING

    OL RESET LEVEL (10 to 99 %TCU) 49RSTP := 75

    SERVICE FACTOR (1.01 to 1.50) SF := 1.15

    MOTOR LRA (2.50 to 12.00 xFLA) LRA1 := 6.50

    LOCKD RTR TIME 1 (1.00 to 600.00 seconds) LRTHOT1 := 6.00

    ACCEL FACTOR (0.10 to 1.50) TD1 := 1.00

    STATOR TC (AUTO, 1.00 to 2000.00 minutes) RTC1 := AUTO

    OL WARN LEVEL (OFF, 50 to 99 %TCU) TCAPU := OFF

    START INH. LEVEL (OFF, 1 to 99 %TCU) TCSTART := 40

    LEARN TCSTART? (Y, N) TCLRNEN := N

    STOP COOL TIME (1.00 to 6000.00 minutes) COOLTIME := 61.00

    LEARN COOLTIME? (Y, N) COOLEN := N

    OL RTD BIASING? (Y, N) ETHMBIAS := N

    FLS: This is not a high-inertia motor and therefore does not require this option for starting.

    SETMETH: Use the rating method for a retrofit.

    49RSTP: This setting maintains a 49T lockout until the stator thermal capacity is low enough to allow for a successful start. Set 49RSTP < 100/SF2.

    LRA1: 2334 A/359 A = 6.5

    LRTHOT1: Although the coordination curve provided a hot stall time of 18 seconds, the operate time of Curve 3 in the SR 269+ at the LRA is 6 seconds. Therefore, to maintain similarity to the installed settings that have been proven over the years, 6 seconds is selected for this setting.

    TD1: This setting should always be 1, unless you know that the load will accelerate in less than the locked rotor time.

    RTC1: Because no time constant data for the motor are available, set to AUTO. The relay calculates the motor RTC as follows: RTC = 1.2 6/(60 Ln((6.52 0.81 1.152)/6.52 1.152)) = 20 minutes.

    TCAPU: The TCU alarm is turned off in the SR 269+, so turn it off in the SEL-710 as well. Normally, this should be set as TCAPU > 100/SF2.

    TCSTART: This defines the rotor thermal capacity required for a successful start. The relay prevents a motor start until the rotor thermal capacity is less than 100 TCSTART. From the SR 269+ setting for initial start thermal capacity, set this to 40 percent.

    TCLRNEN: The SR 269+ setting for start inhibit enabled allows the relay to learn the thermal capacity required to start the motor and set the initial start thermal capacity setting in the relay. Because this is set to no in the SR 269+, the TCLRNEN setting in the SEL-710 should be set to N.

  • Industrial Motor Solutions Page 4 of 11 20120723

    COOLTIME: Although the SR 269+ is set with a running cool time of 15 minutes and a stopped cool time of 30 minutes, the SEL-710 requires that COOLTIME > 3 RTC. Therefore, set COOLTIME = 3 20 + 1 = 61 minutes.

    COOLEN: The SR 269+ setting for defeat learned cool time is set to yes.

    ETHMBIAS: The SR 269+ setting for defeat RTD thermal memory input is set to yes.

    Note: The SR 269+ setting for FLC thermal capacity reduction defines the thermal capacity the element drops to when the current equals the FLC. This setting is not required in the SEL-710, which accurately tracks temperature at and below the FLC.

    Immediate Overload Alarm Settings: Function 50P1

    Existing Relay Data Relay type: GE Multilin SR 269+

    Immediate overload level: 1.50 FLC

    Alarm time delay: 0 seconds

    Your SEL-710 Relay Settings PH OC WARN LVL (OFF, 0.10 to 20.00 xFLA) 50P2P := 1.50

    PH OC WARN DLAY (0.00 to 5.00 seconds) 50P2D := 0.00

    Neutral Overcurrent Settings: Function 50N1

    Existing Relay Data Relay type: GE Multilin SR 269+

    Element name: 50G

    Minimum alarm pickup: 0.6 CT

    Alarm time delay: 1 second

    Minimum trip pickup: 1.0 CT

    Trip time delay: 0.5 seconds

    Your SEL-710 Relay Settings NEUT OC TRIP LVL (OFF, 0.01 to 650.00 A) 50N1P := 50.00

    NEU OC TRIP DLAY (0.00 to 5.00 seconds) 50N1D := 0.50

    NEUT OC WARN LVL (OFF, 0.01 to 650.00 A) 50N2P := 30.00

    NEU OC WARN DLAY (0.00 to 120.00 seconds) 50N2D := 1.00

    50N1P: 1.0 50 = 50 A primary

    50N2P: 0.6 50 = 30 A primary

  • Industrial Motor Solutions Page 5 of 11 20120723

    Load Jam Settings: Function LJ

    Existing Relay Data Relay type: GE Multilin SR 269+

    Mechanical jam alarm level: off

    Rapid/mechanical jam trip level: 4.0 FLC

    Rapid trip delay: 4 seconds

    Your SEL-710 Relay Settings JAM TRIP LEVEL (OFF, 1.00 to 6.00 xFLA) LJTPU := 4.00

    JAM TRIP DELAY (0.00 to 120.00 seconds) LJTDLY := 4.00

    JAM WARN LEVEL (OFF, 1.00 to 6.00 xFLA) LJAPU := OFF

    Current Unbalance Settings: Function 46UB

    Existing Relay Data Relay type: GE Multilin SR 269+

    Alarm minimum pickup: 15 percent

    Alarm time delay: 5 seconds

    Trip minimum pickup: 20 percent

    Trip time delay: 5 seconds

    Your SEL-710 Relay Settings CI TRIP LEVEL (OFF, 5 to 80 percent) 46UBT := 20

    CI TRIP DELAY (0.00 to 240.00 seconds) 46UBTD := 5.00

    CI WARN LEVEL (OFF, 5 to 80 percent) 46ABT := 15

    CI WARN DELAY (0.00 to 240.00 seconds) 46ABTD := 5.00

  • Industrial Motor Solutions Page 6 of 11 20120723

    Starting Settings

    Existing Relay Data Relay type: GE Multilin SR 269+

    Acceleration time: 10 seconds

    Starts per hour: 3

    Single-shot restart enabled: no

    Special external reset enabled: no

    Backspin timer: off

    Time between starts: off

    Defeat speed switch input: yes

    Your SEL-710 Relay Settings START MOTOR TIME (OFF, 1.00 to 240.00 seconds) START_T := 10.00

    STAR-DELTA ENABL (Y, N) ESTAR_D := N

    STARTS/HR. (OFF, 1 to 15) MAXSTART := 3

    MIN. OFF TIME (OFF, 1.00 to 150.00 minutes) TBSDLY := OFF

    RESTART BLK TIME (OFF, 1.00 to 1500.00 minutes) ABSDLY := OFF

    SS TRIP DELAY (OFF, 1.00 to 240.00 seconds) SPDSDLYT := OFF

    SS WARN DELAY (OFF, 1.00 to 240.00 seconds) SPDSDLYA := OFF

    Phase Reversal Settings: Function 47T

    Existing Relay Data Relay type: GE Multilin SR 269+

    Enable voltage phase reversal: no

    Your SEL-710 Relay Settings PH REV. ENABLE (Y, N) E47T := N

  • Industrial Motor Solutions Page 7 of 11 20120723

    RTD Settings: Function 49RTD

    Existing Relay Data Relay type: GE Multilin SR 269+

    Sensor type: 100 platinum

    RTDs connected: yes

    RTD message display: Celsius

    Number of stator RTDs: 3

    RTD 1 alarm level: 130C

    RTD 1 high alarm level: off

    RTD 1 trip level: 140C

    RTD 2 alarm level: 130C

    RTD 2 high alarm level: off

    RTD 2 trip level: 140C

    RTD 3 alarm level: 130C

    RTD 3 high alarm level: off

    RTD 3 trip level: 140C

    RTD 7 alarm level: 130C

    RTD 7 trip level: 140C

    RTD 8 alarm level: 130C

    RTD 8 trip level: 140C

    RTDs 4, 6, 9, and 10 are not used.

    RTDs 7 and 8 are bearing RTDs.

    Enable stator RTD voting: yes

  • Industrial Motor Solutions Page 8 of 11 20120723

    Your SEL-710 Relay Settings RTD ENABLE (INT, EXT, NONE) E49RTD := INT

    RTD1 LOCATION (OFF, WDG, BRG, AMB, OTH) RTD1LOC := WDG

    RTD1 TYPE (PT100, NI100, NI120, CU10) RTD1TY := PT100

    RTD1 TRIP LEVEL (OFF, 1 to 250C) TRTMP1 := 140

    RTD1 WARN LEVEL (OFF, 1 to 250C) ALTMP1 := 130

    RTD2 LOCATION (OFF, WDG, BRG, AMB, OTH) RTD2LOC := WDG

    RTD2 TYPE (PT100, NI100, NI120, CU10) RTD2TY := PT100

    RTD2 TRIP LEVEL (OFF, 1 to 250C) TRTMP2 := 140

    RTD2 WARN LEVEL (OFF, 1 to 250C) ALTMP2 := 130

    RTD3 LOCATION (OFF, WDG, BRG, AMB, OTH) RTD3LOC := WDG

    RTD3 TYPE (PT100, NI100, NI120, CU10) RTD3TY := PT100

    RTD3 TRIP LEVEL (OFF, 1 to 250C) TRTMP3 := 140

    RTD3 WARN LEVEL (OFF, 1 to 250C) ALTMP3 := 130

    RTD7 LOCATION (OFF, WDG, BRG, AMB, OTH) RTD7LOC := BRG

    RTD7 TYPE (PT100, NI100, NI120, CU10) RTD7TY := PT100

    RTD7 TRIP LEVEL (OFF, 1 to 250C) TRTMP7 := 100

    RTD7 WARN LEVEL (OFF, 1 to 250C) ALTMP7 := 90

    RTD8 LOCATION (OFF, WDG, BRG, AMB, OTH) RTD8LOC := BRG

    RTD8 TYPE (PT100, NI100, NI120, CU10) RTD8TY := PT100

    RTD8 TRIP LEVEL (OFF, 1 to 250C) TRTMP8 := 100

    RTD8 WARN LEVEL (OFF, 1 to 250C) ALTMP8 := 90

    WIND TRIP VOTING (Y, N) EWDGV := Y

    BEAR TRIP VOTING (Y, N) EBRGV := Y

    EBRGV: Because the SR 269+ does not have an option for specifying bearing RTDs or voting for them, follow the same pattern as the stator winding RTDs.

  • Industrial Motor Solutions Page 9 of 11 20120723

    Analog Output

    Existing Relay Data Relay type: GE Multilin SR 269+

    Parameter: motor load as a percent of full load

    Scale: 4 to 20 mA

    Motor load full scale: 100 percent

    Your SEL-710 Relay Settings AOx01 ANALOG QTY (OFF, 1 analog quantity) AOx01AQ := MLOAD

    AOx01 TYPE (I, V) AOx01TYP := I

    AOx01 AQTY LOW (2147483647 to +2147483647) AOx01AQL := 0.000

    AOx01 AQTY HI (2147483647 to +2147483647) AOx01AQH := 1.000

    AOx01 LO OUT VAL (20.480 to +20.480 mA) AOx01L := 4.000

    AOx01 HI OUT VAL (20.480 to +20.480 mA) AOx01H := 20.000

    AOx01AQ: Select the MLOAD analog quantity from the table in Appendix J of the SEL-710 Instruction Manual. This gives the motor load in per unit of FLA.

    AOx01TYP: You need a current-based analog output.

    AOx01AQL: The lower end of the range is 0.000 pu.

    AOx01AQH: The upper end of the range is 1.000 pu.

    AOx01L: The lower end of the output current range is 4.000 mA.

    AOx01H: The upper end of the output current range is 20.000 mA.

    Contactor Trip, Alarm, and Output Logic for the SEL-710

    Existing Relay Data Relay type: GE Multilin SR 269+

    Relay alarm latch code: 1

    VALUE TRIP ALARM AUX. 1 AUX. 2

    1 Latched Unlatched Unlatched Latched

    2 or 3 Latched Latched Unlatched Latched

    4 or 5 Latched Unlatched Latched Latched

    6 or 7 Latched Latched Latched Latched

    (Latched = manual reset; unlatched = automatic reset)

  • Industrial Motor Solutions Page 10 of 11 20120723

    Relay fail-safe code: 1

    VALUE TRIP ALARM AUX. 1 AUX. 2

    1 FS NFS NFS FS

    2 NFS FS NFS FS

    3 FS FS NFS FS

    4 NFS NFS FS FS

    5 FS NFS FS FS

    6 NFS FS FS FS

    7 FS FS FS FS

    8 NFS NFS NFS FS

    (FS = fail-safe; NFS = nonfail-safe)

    Overload: trip

    Unbalance: trip

    Rapid trip: trip

    Stator RTD: trip

    RTD: trip

    Acceleration: trip

    Inhibit lockouts: trip

    Single phase: trip

    Overload warning: alarm

    Ground fault: alarm

    Unbalance: alarm

    Stator RTD: alarm

    Stator RTD high: no

    RTD: alarm

    RTD high: no

    No sensor: alarm

    Meter communications: alarm

    Self-test fail: alarm

  • Industrial Motor Solutions Page 11 of 11 20120723

    Your SEL-710 Relay Settings TRIP EQUATION (SELOGIC control equation) TR := 49T OR 50N1T OR JAMTRIP OR 46UBT

    OR BRGTRIP OR WDGTRIP OR SMTRIP

    UNLATCH TRIP EQN (SELOGIC control equation) ULTRIP := TRGTR

    OUT101 FAIL-SAFE (Y, N) OUT101FS := N

    OUT101 := HALARM OR SALARM OR 50P2P OR

    50N2P OR 46UBA OR BRGALRM OR

    WDGALRM OR RTDFLT

    OUT103 FAIL-SAFE (Y, N) OUT103FS := Y

    OUT103 := TRIP

    TR: The inhibit lockout functions are included in the trip logic by default and do not need to be included in the TR equation, as shown in the following trip logic from the SEL-710 Instruction Manual.

    ULTRIP: Relay Word bit TRGTR asserts when the {TARGET RESET} pushbutton on the front panel is manually pressed or the command is issued remotely via supervisory control and data acquisition (SCADA).