98
Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE

IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

  • Upload
    vannga

  • View
    214

  • Download
    2

Embed Size (px)

Citation preview

Page 1: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Automatic Fire Alarm Association

Webinar On Inspection, Testing, And Maintenance

Of Fire Alarm Systems

Your Presenter: Merton Bunker, PE

Page 2: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Inspections and Tests

Inspections and tests are intended to reduce or limit: Loss of life Loss of property

Page 3: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Inspections and Tests

Inspections and tests are required by NFPA 72, National Fire Alarm and Signaling Code Adopted by other codes Required by law

Page 4: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Definitions

Approved Authority Having Jurisdiction (AHJ) Code Listed Shall Should

Page 5: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Equivalency

“Nothing in this Code shall prevent the use of systems, methods, devices, or appliances of equivalent or superior quality, strength, fire resistance, effectiveness, durability, and safety over those prescribed by this Code.”

Page 6: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Performance Based Testing

As an alternate means of compliance, subject to the authority having jurisdiction, components and systems shall be permitted to be inspected and tested under a performance-based program.

Page 7: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Equivalency

Inspection, testing, and maintenance programs shall satisfy the requirements of this Code and conform to the equipment manufacturer’s published instructions.

Inspection, testing, and maintenance programs shall verify correct operation of the system.

Page 8: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Qualifications

NFPA 72 requires inspection, testing, and maintenance personnel to be “qualified and experienced”. Examples include, but are not limited to the following:(continued on next slides)

Page 9: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Examples of Qualifications

Personnel who are factory trained and certified for the specific type and brand of system being serviced

Page 10: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Examples of Qualifications

Personnel who are certified by a nationally recognized certification organization acceptable to the authority having jurisdiction

Page 11: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Examples of Qualifications

Personnel who are registered, licensed, or certified by a state or local authority to perform service on systems addressed within the scope of this Code

Page 12: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Examples of Qualifications

Personnel who are employed and qualified by an organization listed by a nationally recognized testing laboratory for the servicing of systems within the scope of this Code

Page 13: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Responsibilities

Who is responsible to ensure that inspections, tests, and maintenance are carried out? The property owner, or The system owner, or The building owner, or Their designated representative

Delegations must be in writing Must provide a copy for the AHJ when

requested

Page 14: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Required Documentation

Record (as-built) drawings Calculations Operations and Maintenance (OM) Manual Sequence of Operations Matrix of Operation Record of Completion NFPA 72 Previous Inspection and Test Report

Page 15: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Documentation

Page 16: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Questions?

Page 17: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Inspections

Inspections do NOT involve any physical operation of the system components.

Inspection: “To look at carefully;; examine critically”.

A checklist is recommended

Page 18: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Inspections

Things We Look for During Inspections Broken or damaged equipment Improperly located equipment Incorrect strobe ratings Incorrect heat detector rating Incorrect device/appliance spacing Poor wiring methods Missing equipment Building changes that affect operation Equipment blocked by building furnishings or other equipment

Page 19: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Inspections

Page 20: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Inspections

Page 21: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Inspections

Page 22: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Inspections

Page 23: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Inspections

Page 24: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Types of Inspections

Initial/Acceptance Re-Acceptance Periodic

Page 25: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Initial/Acceptance Inspections

Conducted when system is installed. Involve a 100% inspection Used to verify code compliance and

functionality

Page 26: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Re-Acceptance Inspections

Conducted when the system changes Addition of new devices or equipment Deletion of devices or equipment Inspect changes to system

Page 27: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Periodic Inspections

Conducted even if the system does not change.

NFPA 72 contains frequencies of inspection in Table 14.3.1

Page 28: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Questions?

Page 29: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Testing

Testing involves a physical manipulation of the component or equipment.

Test: “An examination or trial, as to prove the value or find out the nature of something”. Use a checklist Use drawings

Page 30: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Testing

Page 31: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Occupant Notification

Bulletin boards Signs E-mail Voice announcements Telephone calls Radios and pagers Text messages

Page 32: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Occupant Notification

Page 33: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Notification of Testing

Fire Marshal/Chief/Engineer Building Inspector Wiring Inspector (Electrical) Representative of Owner/Occupant Representative of Insurance Carrier Supervising Station

Page 34: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Required Documentation

Record (as-built) drawings Operations and Maintenance (OM) Manual Sequence of Operations Matrix of Operation Record of Completion NFPA 72 Previous Test Report (if applicable)

Page 35: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Required Tools and Equipment

Ladders Radios Smoke or listed

aerosol per manufacturer’s requirements

Keys/special wrenches

Hand tools Heat source NFPA 72

Manometer or Magnehelic

Volt-Ohm Meter (VOM)

Battery test meter Sound Pressure

Level (SPL) meter Stopwatch Highlighters,

pencils, and clipboard

Page 36: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Types of Tests

When testing, avoid occupant/owner disruption. Walk test (silent) Test during off-hours Simulate tests only where necessary

Page 37: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Types of Tests

Initial/Acceptance Re-Acceptance Periodic

Page 38: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Initial/Acceptance Tests

Conducted when system is installed. Involve a 100% test Used to verify code compliance and

correct operation

Page 39: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Initial/Acceptance Tests

Everything MUST be Tested

100%

Page 40: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Re-Acceptance Tests

Conducted when the system changes Addition of new devices or equipment Deletion of devices or equipment Changes in software programming

Page 41: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Re-Acceptance Tests

Site Specific Software changes Test all known changes, plus a functional test of 10% of initiating devices (up to 50)

Basic Input/Output Software (BIOS) or firmware changes Test 10% of entire system At least one device or appliance on each circuit

Page 42: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Periodic Tests

Periodic tests are conducted even if the system does not change.

NFPA 72 contains frequencies of testing in Table 14.4.5

Page 43: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Periodic Test Frequencies

Page 44: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Test Methods

NFPA 72 contains the methods of testing each component in Table 14.4.2.2

Page 45: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Tests

Control Units (monitored vs. unmonitored) Control functions Fuses Interfaced equipment Lamps & LED Primary/secondary power supply

45

Page 46: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Test battery charger annually

30 minute battery discharge test annually

Load voltage battery test semi-annually

Other testing depending on battery type

46

Tests

Page 47: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Verify signal receipt by operating the public emergency alarm reporting system box.

47

Tests

Page 48: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Verify correct operation and identification of all annunciator functions

48

Tests

Page 49: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Metallic conductors are tested only prior to initial tests: Measure stray voltage Measure voltage to ground Measure resistance to

ground Measure resistance

between conductors Measure loop resistance

49

Tests

Page 50: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Using a heat source, test 2 or more RESTORABLE detectors on each circuit annually

Test different RESTORABLE detectors each year

DO NOT use open flames

50

Tests

Page 51: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

DO NOT test NON-RESTORABLE detectors with heat

Electrically test contacts annually

Replace all detectors after 15 years or test statistical sample (2 per 100)

51

Tests

Page 52: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Other non-restorable heat detectors Line type Rate-of-Rise/Fixed Temperature

52

Tests

Page 53: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Smoke Detector Functional Test Ensure smoke entry

into sensing chamber and response

Use aerosol or real smoke acceptable to manufacturer

53

Tests

Page 54: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Too Close!!!54

Aerosol smoke may contain oils.

Use short puffs Keep a reasonable

distance

Page 55: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Testing smoke detectors with a magnet is NOT considered a functional test.

Use magnets for pre-testing.

NFPA 72 requires smoke entry!

55

Tests

Page 56: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Smoke detector sensitivity Tests Calibrated test method Manufacturer’s calibrated sensitivity test instrument

Listed control unit arranged for the purpose Smoke detector/control unit arrangement whereby the detector causes a signal at the control unit when its sensitivity is outside its listed sensitivity range

Other methods approved by the AHJ

56

Tests

Page 57: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Calibrated test methods

57

Tests

Page 58: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Manufacturer’s calibrated test instrument

58

Tests

Page 59: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Smoke detectors that report to the system controls when outside their listed and marked sensitivity range

Use printer or buffer to record sensitivity of each device

59

Tests

Page 60: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Sensitivity tests are conducted within one year after installation and every alternate year.

May be extended to 5 years Good records are essential!!!

60

Tests

Page 61: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Duct smoke detectors require the same functional and sensitivity tests as area smoke detectors

Test sampling tube pressure using a manometer

61

Tests

Page 62: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

A manometer or Magnehelic are required for testing pressure difference across sampling tubes per the manufacturer’s instructions.

Tests

Page 63: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Waterflow switches must actuate within 90 seconds of flow equal to the flow from a single sprinkler head

The device must not respond to surges and varying pressure

63

Tests

Page 64: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Operate manual fire alarm boxes using manufacturer’s recommended methods

It may be necessary to remove glass rods/plates

Keys/wrenches are required

64

Tests

Page 65: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Pressure Type Waterflow Switches Operate switch Used on dry-pipe,

preaction and deluge systems

May be used on wet-pipe systems

65

Tests

Page 66: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Water tank level Water tank

temperature

66

Tests

Page 67: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

67

• Off-normal within 2 revolutions or 1/5 the travel distance of the valve

• Restoration-to-normal only when valve is open

Tests

Page 68: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Consult NFPA 20, Standard for Stationary Fire Pumps

Diesel Pumps Running Controller in other than

automatic Failure to start Engine functions

Electric Pumps Running Loss of power Loss of phase Phase reversal

68

Tests

Page 69: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Radiant energy fire detectors

69

Tests

Page 70: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Bells Horns Speakers Lights Textual Displays Combination

70

Tests

Page 71: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Tests71

Source

Meter 5 feet above

floor

Page 72: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Tests

Public Mode Signaling 15 dBA above average ambient SPL, or 5 dBA

above the maximum SPL lasting a minute or more Measure 5 feet above the floor Test annually

Private Mode Signaling 10 dBA above average ambient SPL, or 5 dBA

above the maximum SPL lasting a minute or more Measure 5 feet above the floor Test annually

72

Page 73: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Tests

Sleeping Areas 15 dBA above average ambient SPL, or 5 dBA above the maximum SPL lasting a minute or more, or 75 dBA, whichever is greater

Test with barriers (doors, curtains, etc.) in place.

Measure at the pillow

73

Page 74: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Tests

Initial audible system tests Measure for conformity with NFPA 72

Periodic audible system tests Measure where building, system, or occupancy changes have occurred

Page 75: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Areas likely to require intelligibility tests Places of worship Atria Transportation

centers Covered malls Sporting venues Large assembly

75

Tests

Page 76: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Required for ECS Not required in all

areas Designer must

designate Acoustically Distinguishable Spaces (ADS)

Score of 0.50 on STI scale is required

76

Tests

Page 77: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Tests

Verify correct rating of visible notification appliances (strobes) during the inspection

Verify visible appliances operate Test annually

77

Page 78: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Tests

DACT Follow manufacturer’s instructions Verify connection to 2 separate means of communication, per NFPA 72

Verify line seizure capability Test loss of communications means and verify trouble signal is transmitted to supervising station within 4 minutes

78

Page 79: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Elevator recall and shutdown

HVAC shutdown Stair pressurization Smoke door

releasing Door unlocking

devices Damper control Smoke evacuation

79

Tests

Page 80: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Tests

Test “end-to-end” when possible. Test by operating or simulating alarm

signals when necessary Test at the same frequency as the

initiating device that causes the function to occur (most are annual)

80

Page 81: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Test Frequencies

Page 82: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Test Frequencies

Page 83: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Test Frequencies

Page 84: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Test Frequencies

Page 85: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Impairments and Deficiencies

Systems must be returned to service after testing is completed.

Notify AHJ when any system is down for more than 4 hours.

Fire watches may be required Verbally notify owner in writing of ANY

deficiencies and follow up in writing within 24 hours

Page 86: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Maintenance

Follow manufacturer’s requirements Environment may warrant more frequent

maintenance

Page 87: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Maintenance

Field repairs to boards and other equipment is generally not permitted by the manufacturer.

Only factory repairs are permitted.

Page 88: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Warranty

Most manufacturer warranties extend to 12 months

Warranties usually start on the day of acceptance

Warranties may be extended by contract

Page 89: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Service Contracts

Some jurisdictions require maintenance contracts

Systems that are not properly maintained will usually suffer from early failures

Page 90: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Records

Record of Completion (NFPA 72) New systems Changes to system

Record of Inspection, Test, and Maintenance (NFPA 72) All inspections and tests

Page 91: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Records

Other records As-built (record) drawings Operations and Maintenance (OM) manuals Site specific software Building permit

Page 92: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Records

For software-based systems, a copy of the site-specific software shall be provided to the system owner or owner’s designated representative.

A copy of the site-specific software shall be stored on-site in non-volatile, non-erasable, non-rewritable memory.

The system owner shall be responsible for maintaining these records for the life of the system for examination by any authority having jurisdiction. Paper or electronic media shall be permitted.

Page 93: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Documentation

Page 94: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Records

The owner must retain drawings and Record of Completion for the life of the system

All other records must be retained for one year after the next test

Keep at the FACU or in a separate enclosure labeled “FIRE ALARM DOCUMENTS”

Page 95: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Impairments

System defects and malfunctions shall be corrected.

If a defect or malfunction is not corrected at the conclusion of system inspection, testing, or maintenance, the system owner or the owner’s designated representative shall be informed of the impairment in writing within 24 hours.

Page 96: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Consequences

Be careful to avoid pitfalls that can cause liability.

Page 97: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Questions?

Page 98: IMSA Level I Interior Fire Alarmftp.afaa.org/Webinars/AFAA_ITM_Aug 2011.pdfLoad voltage battery test semi-annually Other testing depending on battery type 46 Tests Verify signal receipt

Contact Information

Thank You.

Merton Bunker, [email protected]@aol.com