4
Journal of ELECTRICAL ENGINEERING, VOL. 57, NO. 6, 2006, 365–368 COMMUNICATIONS IMPROVING POWER SYSTEM TRANSIENT STABILITY WITH AN OFF–CENTRE LOCATION OF SHUNT FACTS DEVICES Sidhartha Panda * — Ramnarayan N. Patel ** Shunt Flexible AC Transmission System (FACTS) devices, when placed at the mid-point of a long transmission line, play an important role in controlling the reactive power flow to the power network and hence both the system voltage fluctuations and transient stability. This paper deals with the location of a shunt FACTS device to improve transient stability in a long transmission line with predefined direction of real power flow. The validity of the mid-point location of shunt FACTS devices is verified, with different shunt FACTS devices, namely static var compensator (SVC) and static synchronous compensator (STATCOM) in a long transmission line using the actual line model. It has been observed that the FACTS devices, when placed slightly off-centre towards sending-end, give better performance in improving transient stability and the location depends on the amount of local/through load. Keywords: FACTS, STATCOM, SVC, transient stability 1 INTRODUCTION Recent development of power electronics introduces the use of FACTS devices in power systems. FACTS de- vices are capable of controlling the network condition in a very fast manner and this unique feature of FACTS de- vices can be exploited to improve the transient stability of a system. Reactive power compensation is an impor- tant issue in electrical power systems and shunt FACTS devices play an important role in controlling the reactive power flow to the power network and hence the system voltage fluctuations and transient stability [1]. SVC and STATCOM are members of FACTS family that are con- nected in shunt with the system. Even though the pri- mary purpose of shunt FACTS devices is to support bus voltage by injecting (or absorbing) reactive power, they are also capable of improving the transient stability by in- creasing (decreasing) the power transfer capability when the machine angle increases (decreases), which is achieved by operating the shunt FACTS devices in capacitive (in- ductive) mode [2]. Previous works on the topic prove that shunt FACTS devices give maximum benefit from their stabilized volt- age support when sited at the mid-point of the transmis- sion line [3]. The proof of maximum increase in power transfer capability is based on the simplified model of the line neglecting line resistance and capacitance. However, for long transmission lines, when the actual model of the line is considered, the results may deviate significantly from those found for the simplified model [4]. This paper consists of the comparison of various results found for the different locations of shunt FACTS device in a long transmission line considering the actual models of the line for a transient stability study. Computer simu- lation results under a severe disturbance condition (three phase fault) for different fault clearing times and differ- ent locations of FACTS devices are analyzed. It is shown that for the actual long transmission line model with a predefined direction of real power flow, shunt FACTS de- vice needs to be located slightly off-centre. Further the location of these devices depends on the amount of local load and through load. The paper is organized as follows. Section 2 gives a brief introduction of the shunt FACTS devices used. A two area system with a shunt FACTS device is described in Section 3. The computer simulation results for system under study are presented and discussed in Section 4 and in Section 5 conclusions are given. The various parameters of the system are listed in Appendix. 2 SHUNT FACTS DEVICES IN POWER SYSTEM Shunt FACTS devices are classified into two categories, namely variable impedance type (SVC) and switching converter type (STATCOM). A. SVC The SVC uses conventional thyristors to achieve fast control of shunt-connected capacitors and reactors. The configuration of the SVC is shown in Fig. 1 (a), which basically consists of a fixed capacitor (C) and a thyris- tor controlled reactor (L). The firing angle control of the Department of Electrical Engineering, Indian Institute of Technology, Roorkee. E-mails: [email protected], ∗∗ [email protected]. ISSN 1335-3632 c 2006 FEI STU

Improving Power System Transient Stabilitywith an Off–Centre Location of Shunt Facts Devices

  • Upload
    usefi

  • View
    215

  • Download
    2

Embed Size (px)

DESCRIPTION

Improving Power System Transient Stabilitywith an Off–Centre Location of Shunt Facts Devices

Citation preview

Page 1: Improving Power System Transient Stabilitywith an Off–Centre Location of Shunt Facts Devices

Journal of ELECTRICAL ENGINEERING, VOL. 57, NO. 6, 2006, 365–368

COMMUNICATIONS

IMPROVING POWER SYSTEM TRANSIENT STABILITY WITHAN OFF–CENTRE LOCATION OF SHUNT FACTS DEVICES

Sidhartha Panda∗— Ramnarayan N. Patel

∗∗

Shunt Flexible AC Transmission System (FACTS) devices, when placed at the mid-point of a long transmission line, playan important role in controlling the reactive power flow to the power network and hence both the system voltage fluctuationsand transient stability. This paper deals with the location of a shunt FACTS device to improve transient stability in a longtransmission line with predefined direction of real power flow. The validity of the mid-point location of shunt FACTS devicesis verified, with different shunt FACTS devices, namely static var compensator (SVC) and static synchronous compensator(STATCOM) in a long transmission line using the actual line model. It has been observed that the FACTS devices, whenplaced slightly off-centre towards sending-end, give better performance in improving transient stability and the locationdepends on the amount of local/through load.

K e y w o r d s: FACTS, STATCOM, SVC, transient stability

1 INTRODUCTION

Recent development of power electronics introducesthe use of FACTS devices in power systems. FACTS de-vices are capable of controlling the network condition ina very fast manner and this unique feature of FACTS de-vices can be exploited to improve the transient stabilityof a system. Reactive power compensation is an impor-tant issue in electrical power systems and shunt FACTSdevices play an important role in controlling the reactivepower flow to the power network and hence the systemvoltage fluctuations and transient stability [1]. SVC andSTATCOM are members of FACTS family that are con-nected in shunt with the system. Even though the pri-mary purpose of shunt FACTS devices is to support busvoltage by injecting (or absorbing) reactive power, theyare also capable of improving the transient stability by in-creasing (decreasing) the power transfer capability whenthe machine angle increases (decreases), which is achievedby operating the shunt FACTS devices in capacitive (in-ductive) mode [2].

Previous works on the topic prove that shunt FACTSdevices give maximum benefit from their stabilized volt-age support when sited at the mid-point of the transmis-sion line [3]. The proof of maximum increase in powertransfer capability is based on the simplified model of theline neglecting line resistance and capacitance. However,for long transmission lines, when the actual model of theline is considered, the results may deviate significantlyfrom those found for the simplified model [4].

This paper consists of the comparison of various resultsfound for the different locations of shunt FACTS devicein a long transmission line considering the actual models

of the line for a transient stability study. Computer simu-lation results under a severe disturbance condition (threephase fault) for different fault clearing times and differ-ent locations of FACTS devices are analyzed. It is shownthat for the actual long transmission line model with apredefined direction of real power flow, shunt FACTS de-vice needs to be located slightly off-centre. Further thelocation of these devices depends on the amount of localload and through load.

The paper is organized as follows. Section 2 gives abrief introduction of the shunt FACTS devices used. Atwo area system with a shunt FACTS device is describedin Section 3. The computer simulation results for systemunder study are presented and discussed in Section 4 andin Section 5 conclusions are given. The various parametersof the system are listed in Appendix.

2 SHUNT FACTS DEVICES

IN POWER SYSTEM

Shunt FACTS devices are classified into two categories,namely variable impedance type (SVC) and switchingconverter type (STATCOM).

A. SVC

The SVC uses conventional thyristors to achieve fastcontrol of shunt-connected capacitors and reactors. Theconfiguration of the SVC is shown in Fig. 1 (a), whichbasically consists of a fixed capacitor (C) and a thyris-tor controlled reactor (L). The firing angle control of the

Department of Electrical Engineering, Indian Institute of Technology, Roorkee.

E-mails:∗

[email protected],∗∗

[email protected].

ISSN 1335-3632 c© 2006 FEI STU

Page 2: Improving Power System Transient Stabilitywith an Off–Centre Location of Shunt Facts Devices

366 S. Panda — R. N. Patel: IMPROVING POWER SYSTEM TRANSIENT STABILITY WITH AN OFF-CENTRE LOCATION . . .

Fig. 1. (a) SVC connected to a transmission line, (b) STATCOMconnected to a transmission line.

thyristor banks determines the equivalent shunt admit-tance presented to the power system.

B. STATCOM

The STATCOM is based on a solid state synchronousvoltage source which generates a balanced set of threesinusoidal voltages at the fundamental frequency withrapidly controllable amplitude and phase angle. The con-figuration of a STATCOM is shown in Fig. 1 (b). Basi-cally it consists of a voltage source converter (VSC), acoupling transformer and a dc capacitor. Control of re-active current and hence the susceptance presented topower system is possible by variation of the magnitude ofoutput voltage (VVSC ) with respect to bus voltage (VB )and thus operating the STATCOM in inductive region orcapacitive region

3 TWO AREA SYSTEM WITH

SHUNT FACTS DEVICES

Consider a two area system (area 1 & area 2), con-nected by a single circuit long transmission line as shownin Fig. 2 (a). The direction of real power flow is fromarea 1 to area 2. The transmission line is divided in twosections (section 1 and section 2) and ‘s’ is the fractionof line length at which the FACTS device is placed.

For a long transmission line of length l , having a se-ries impedance of z ohm/km and shunt admittance ofy mho/km, the relationship between the sending-end andreceiving-end quantities with A, B, C, D constants of theline can be written as:

VS = AVR + BIR , (1)

IS = CVR + DIR . (2)

For the simplified model, where the line resistance andcapacitance are neglected, both sending end power (PS )and receiving end power (PR ) become maximum at power

angle δ = 90 . When a shunt FACTS device is connectedto a long line to increase the power transfer capability,the above simplifications may provide erroneous results.

The active power flows at the sending end and receiv-ing end for a long transmission line with distributed pa-rameters can be written as [5]:

PS = K1 cos(

θB − θA

)

−K2 cos(

θB + δ)

, (3)

PR = K2 cosθB − δ)

−K3 cos(

θB − θA

)

, (4)

where, K1 = AV 2

S

/

B , K2 = AVSVR

/

B , K3 = AVR

/

B ,

A = |A|∠θA , B = |B|∠θB , VR = |VR|∠0, VS = |VS |∠δ .

It is clear from Eqn. 4 that the receiving end powerPR reaches the maximum value when the angle δ be-comes θB . However, the sending end power PS of Eqn. 3becomes maximum at δ = (180 − θB).

Fig. 2. (a) Two area system with shunt FACTS device, (b) Sending-end and receiving-end power angle characteristics using actual line

model.

The power-angle characteristic of the line using theactual line model without FACTS device is shown inFig. 2 (b). It also represents the power angle character-istics of both line sections, if a large rating shunt FACTSdevice capable of maintaining the voltage constant isplaced at the centre. Assuming that the FACTS devicedoes not absorb or deliver any active power, the receiv-ing end power of section 1 must be equal to the sendingend power of section 2. If section 1 delivers the maximumpower at its receiving end (point a), the correspondingsending end power of section 2 can be represented by thesame power level (point c) and the total transmission an-gle at the maximum power point is δ = δ1 + δ3 . Thus,the maximum power transfer capability of the system islimited by the maximum receiving end power of section 1.

Page 3: Improving Power System Transient Stabilitywith an Off–Centre Location of Shunt Facts Devices

Journal of ELECTRICAL ENGINEERING 57, NO. 6, 2006 367

Fig. 3. MATLAB simulation model of two machine system for transient stability study with shunt FACTS devices.

The shape of the power angle curve depends on the linelength or fraction ‘s’. For lower values of s, the maxi-mum receiving end power of section 1 increases, whilethe maximum sending end power of section 2 decreases.Thus point a in Fig. 2 (b) moves upwards and point bgoes downwards. Both of the powers will be equal at avalue s < 0.5 because of the losses in the line.

4 SIMULATION STUDIES

The two area system as proposed in Section 3 is mod-elled with two hydraulic generating units of 1400 MVAand 700 MVA, respectively, in each area, connected viaa 500 km long transmission line as shown in Fig. 3 forour study [6]. The two machines are equipped with a hy-draulic turbine and governor (HTG), excitation systemand power system stabilizer (PSS).These components areincluded in ‘Reg M1’ and ‘Reg M2’ subsystem blocks, re-spectively, as shown in Fig. 3. Both SVC and STATCOMused for this model have the same rating of ±100 MVAand the reference voltage is set to 1 pu for both SVC andSTATCOM. Initial power outputs of the generators areP1 = 0.7 pu and P2 = 0.5 pu and the SEP and REP without the FACTS device are 894 MW and 864 MW respec-tively. A three phase fault occurs at sending end bus attime t = 0.1 s. The original system is restored upon theclearance of the fault.

Figure 4 (a) shows the variation of the rotor angle dif-ference of the two machines with respect to time, for afault clearing time (FCT) of 0.218 s. It is clear from thefigure that STATCOM is more effective in improving sta-bility, and if the location of the SVC is changed, the sys-tem is stable for the same fault clearing time. To show theeffectiveness of off-centre located STATCOM for transientstability improvement, FCT is increased to 0.22 s and theresponse is shown in Fig. 4 (b).

To illustrate the effect of local load and through loadon the optimal location of STATCOM, the loads in eacharea are changed keeping individual power generationconstant at P1 = 0.8 pu and P2 = 0.4 pu with differentline flows and the results are shown in Table 1.

Fig. 4. (a) — Variation of rotor angle difference with shunt differentlocations of FACTS devices for FCT = 0.218 s; (b) Variation of

rotor angle difference with STATCOM for FCT = 0.22 s.

In this work, the effectiveness of shunt FACTS deviceshas been studied in improving the transient stability of asample two-area power system with different locations ofthese devices in the transmission line. It also shows thatwhen there is a pre-defined direction of real power flow,the shunt FACTS devices need to be placed slightly off-centre towards the sending end for maximum benefit from

Page 4: Improving Power System Transient Stabilitywith an Off–Centre Location of Shunt Facts Devices

368 S. Panda — R. N. Patel: IMPROVING POWER SYSTEM TRANSIENT STABILITY WITH AN OFF-CENTRE LOCATION . . .

the stability point of view. The optimal location of these

devices also depends on the amount of local load and

through load and it is seen that as the amount of local

load increases the optimal location, from the transient

stability point of view, moves towards the sending-end.

Table 1. Optimal location of STATCOM for different local andthrough loads.

Load at Load atReceiving-end Sending-end Optimal

MW MW value of sMVAR MVAR

143 200 1485 500 0.45195 200 1400 500 0.44245 200 1322 500 0.434296 200 1250 500 0.428

Appendix

The data for various components used in the MAT-

LAB model of Fig. 3. (All data are in pu unless specified

otherwise; the notations used are as in Sim-Power-System

toolbox):

Generator parameters: M1 = 1400 MVA, M2 = 700 MVA,V = 13.8 KV, f = 60 Hz, Xd = 1.305, X1

d = 0.296,X ′′

d = 0.255, Xq = 0.474, X ′′

q = 0.243, X1 = 0.18

Transformer parameters: T1= 1400 MVA, T2= 700 MVA,

13.8/500 KV, R2 = 0.002, L2 = 0.12, Rm = 500 Ω,

Xm = 500 Ω.

Transmission line parameters per km: R1 = 0.1755 Ω,

R0 = 0.2758 Ω, L1 = 0.8737 mH, L0 = 3.22 mH,

C1 = 13.33 nF, C0 = 8.297 nF.

SVC parameters: 500 KV, ±100 MVAR, Td = 4 ms,

Vref = 1.0, Xs = 0.03, Kp = 3, Ki = 500.

STATCOM parameters: 500 KV, ±100 MVAR,

R = 0.071, L = 0.22, Vdc = 40 KV, Cdc = 375 ± µ F,

Vref = 1.0, Kp = 50, Ki = 1000.

References

[1] HINGORANI, N. G.—GYUGYI, L. : Understanding FACTS:

Concepts and Technology of Flexible AC Transmission System,

IEEE PRESS, 2000.

[2] GYUGYI, L. : Power Electronics in Electric Utilities: Static

Var Compensators, Proceedings of IEEE 76 No. 4 (April 1988),

483–494.

[3] KAZERANI, M.—MARCEAU, R.—WOLANSKI, Z.—GALIA-

NA, F. D.—MCGILLS, D.—JOOS, G. : Mid-Point Siting of

FACTS Devices in Transmission Lines, IEEE Trans. on Power

Delv. 12 No. 4 (Oct. 1997), 17171722.

[4] M. H. HAQUE, M. H. : IEE Proc. on Power Gen. Trans. and

Distrib..

[5] H. SAADAT, H. : Power System Analysis, Tata McGraw-Hill,

2002.

[6] SYBILLE, G.—GIROUX, P. : Simulation of FACTS Controllers

using the MATLAB Power System Blockset and Hypersim

Real-Time Simulator, IEEE PES, Panel Session Digital Simula-

tion of FACTS and Custom-Power Controllers Winter Meeting,

New York, January 2002, pp. 488–491.

Received 2 October 2005

Sidhartha Panda received the ME degree in Power Sys-

tems Engineering from University College of Engineering,

Burla, Sambalpur University, India in 2001. Currently, he is

a Research Scholar in Electrical Engineering Department of

Indian Institute of Technology Roorkee, India. He was an As-

sociate Professor in the Department of Electrical and Elec-

tronics Engineering, VITAM College of Engineering, Andhra

Pradesh, India and Lecturer in the Department of Electrical

Engineering, SMIT, Orissa, India. His areas of research include

power system stability, FACTS, optimization techniques, dis-

tributed generation and wind energy.

Ramnarayan N. Patel is working as a faculty in the

Electrical Engineering Department of SSCET, Bhilai. Prior

to this he has worked for BITS Pilani and Indian Institute of

Technology Roorkee, India. He received his Ph.D. degree from

Indian Institute of Technology, Delhi in the year 2003. He has

published many papers in reputed international journals and

conferences. His main research interests are in the areas of

power system transient stability, power system dynamics and

optimization, application of intelligent controls and modeling

and simulation.

E X P O R T - I M P O R T

of periodicals and of non-periodically

printed matters, books and CD - ROM s

Krupinská 4 PO BOX 152, 852 99 Bratislava 5,Slovakiatel.: ++ 421 2 638 39 472-3, fax.: ++ 421 2 63 839 485

e-mail: [email protected], http://www.slovart-gtg.sk

s.r.o.

GmbH

E X P O R T - I M P O R T

G.T.G.SLOVART s.r.o.

GmbH

E X P O R T - I M P O R T

G.T.G.SLOVART