EXCELLENCE THROUGH PRovEn PERFoRMAnCE

IMA Direct Gas-Fired Makeup Air Units

INDUSTRIAL COMMERCIAL

EQUIPMENT MANUFACTURING LTD.

®

US

46906_ICE_IMA_Manual_Covers.indd 2 1/9/08 1:54:46 PM

Page 2: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

INDUSTRIAL COMMERCIAL

EQUIPMENT MANUFACTURING LTD.

Originally founded as Bullocks Manufacturing during the post-war residential

housing boom, I.C.E. Manufacturing was recognized for innovation and

excellence early in our history. After the company established a reputation for

designing, manufacturing and installing natural gas conversion burners for oil

and coal-fired furnaces, founder Don Bullocks returned from an ASHRAE trade

show with a natural gas line burner. Inspired, he set out to manufacture the first

direct-fired makeup air unit in his home country of Canada.

Today, the natural gas revolution continues with I.C.E. Manufacturing at the

forefront of the commercial direct-fired industry. Don had the vision long before

many others by designing a product that has outlived his legend. Our BMA

Series is named for him (Bullocks Makeup Air). This forward thinking has carried

on through such advanced products as the HTDM, the gas valve technology

available on the BMA, and the industrial-quality GIDM product line.

All of our products have withstood the test of time. Many new products are on

the horizon to meet the ever-increasing concern over energy costs, consumption

and impact on our environment. We are building on our heritage to bring

exceptional gas-fired products to market.

I.C.E. is committed to success – the success of our customers and our

employees. To us, success is driven by loyalty that comes from service, quality

and innovation. With our vast experience in the HVAC industry, we continue to

listen to and understand the needs of our customers. And we trust we will be

able to serve you well into the future.

EXCELLENCE THROUGH PRovEn PERFoRMAnCE

46906_ICE_IMA_Manual_Covers.indd 3 1/9/08 1:54:49 PM

Page 3: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

Table of Contents

Why Direct-FireD Makeup air? / Selection GuiDe For Direct-FireD Makeup air ............................................................... 1

StanDarD FeatureS / optional FeatureS / aDDitional optionS ............................................................................................. 2

iM SerieS StanDarD teMperature control optionS / MiScellaneouS control optionS ............................................. 3

iM Direct-FireD SerieS perForMance SpeciFicationS ................................................................................................................ 4

Static preSSure Drop Due to acceSSorieS / GaS inlet SiZinG ............................................................................................... 6

iMa SerieS Direct-FireD heaterS hor. conFiGuration ............................................................................................................... 7

iMr SerieS 80/20 Direct-FireD heaterS hor. conFiGuration ................................................................................................... 8

iMa SerieS Direct-FireD heaterS hor. conFiGuration W/ V-Bank & inlet plenuM ........................................................... 9

iMa SerieS 80/20 Direct-FireD heaterS hor. conFiGuration W/ V-Bank & inlet plenuM .................................................10

iMa SerieS Direct-FireD heaterS W/ plenuM Fan hor. conFiGuration W/ V-Bank & inlet plenuM ............................ 11

iMa SerieS 80/20 Direct-FireD heaterS W/ plenuM Fan hor. conFiGuration W/ V-Bank & inlet plenuM .................. 12

iMa SerieS Direct-FireD heaterS Vertical conFiGuration .................................................................................................... 13

iMr SerieS 80/20 Direct-FireD heaterS Vertical conFiGuration ......................................................................................... 14

iMa SerieS Direct-FireD heaterS W/ eVap hor. conFiGuration ............................................................................................ 15

iMr SerieS 80/20 Direct-FireD heaterS hor. conFiGurtion W/ V-Bank & hor. coil plenuM ......................................... 16

iMr SerieS 80/20 Direct-FireD heaterS hor. conFiGuration W/ V-Bank, inlet & coil plenuM .......................................17

iMr SerieS Direct-FireD heaterS W/ conDenSor hor. conFiGuration W/ V-Bank, inlet plenuM & coil ................. 18

iMr SerieS 80/20 Direct-FireD heaterS hor. conFiG. W/ V-Bank, coil plenuM & Final FilterS .................................... 19

iMr SerieS 80/20 Direct-FireD heaterS hor. conFiG. W/ V-Bank, inlet & coil plenuM & Final FilterS ...................... 20

iMr SerieS heat recoVery Direct-FireD heaterS hor. conFiG. W/ V-Bank & plate-to-plate heater eXch. ............ 21

iMr SerieS heat recoVery Direct-FireD heaterS hor. conFiG. W/ V-Bank & heat recoVery Wheel ......................... 22

iM SerieS rooF curB .......................................................................................................................................................................... 23

iM SerieS acceSSorieS ...................................................................................................................................................................... 24

heat recoVery unit StanDarD Make-up & relieF operation ................................................................................................ 25

46906_ICE_IMA_Manual_Guts.indd 1 1/11/08 10:10:48 AM

Page 4: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

46906_ICE_IMA_Manual_Guts.indd 2 1/11/08 10:10:48 AM

Page 5: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

How To

- Determine whether the unit will be for heating and cooling, humidifying, dehumidifying, or any combination of the above. For cooling and humidifying visit www.ice-ww.com for design guide.

- Determine the maximum air volume requirement. this is generally 10% greater than the maximum air volume of the exhaust system for the space. this will allow the room to be positively pressurized. however, in some makeup systems this may be reversed in order to keep the space negatively pressurized, keeping odors, toxins, etc. confined to the conditioned space.

- once this is known, refer to the iMa Series performance Specifications to choose the model that can deliver this amount.

- the corresponding horse power (hp) can then be taken from the iMa performance Specification chart, given the external static pressure (eSp” Wc).note: add the necessary accessory pressure drop(s) to the eSp. Given the blower hp and line voltage, determine the running Motor amperage, inrush Motor amperage and Full load amps (Fla).

- knowing the unit Model number and MBh capacity the corresponding gas connection size can be taken from the iMa Series Specification table.

- Given the entering and leaving dry bulb temperatures or temperature rise, the equation below can also be used to calculate the required MBh capacity.

MBh capacity = (cFM x c x (lat-eat))/1000 MBh capacity: Btuh/1000 (British thermal units per hour). cFM: cubic Feet per minute of air. c: Gas constant of 1.188 based on an air density at 75 deg. F eat: entering air dry bulb temperature ( deg. F) lat: leaving air dry bulb temperature (deg. F)

Example

a room is exhausting 8000 cFM. the desired room temperature is 70 deg. F. the winter design condition for the area is -10 deg. F. the unit chosen is to be an outdoor Direct-FireD unit whose discharge is downwards. the eSp is 0.25” W.c. the line voltage to the unit is 600/3/60. Gas connection is on the right hand side.

Determine:

1. the supply air capacity required.

2. Which unit is capable of delivering the required supply air volume, while not exceeding a Bhp of 4.00. note: Because it is an outdoor unit you will require an inlet louver or hood and filter section. For this example, we will use an inlet hood with filters.

3. running Motor amperage.

4. the MBh capacity and corresponding gas connection size required.

5. unit configuration.

Selection

1. Since the exhaust air volume is 8000 cFM, the supply air capacity should be the same if no pressurization requirements were specified. therefore, the supply air capacity is 8000 cFM.

2. referring to the iMa performance Specification table, the iMa 118 and iMa 120 are capable of delivering the required 8000 cFM of supply air. the unit must have a maximum of 4.00 hp when the static pressures of the unit and eSp are added together and applied to the table.

therefore: eSp= 0.25” W.c. (Given) inlet hood w/filters = 0.4” W.c. 0.25+0.4= tSp 0.65= tSp use 0.75” W.c. on the chart to be conservative. the corresponding hp’s at 0.75” W.c. iMa118 . . . . . . . .5 hp IMA120 . . . . . . . .3 HP

the units that can be used are the iMa118 and the iMa120.

3. the running Motor amperage for a 5 hp motor at 600/3/60 is 5.50 amps .

4. the MBh input required for an eat of -10 deg. F and a lat of 70 deg. F (80 deg. F rise) is 760 MBh.

MBh = (cFM x 1.188 (lat - eat)) / 1000 MBh = (8000 x 1.188 (70-(-10)))/1000 = 760 MBh

the corresponding gas connection size required is 1 inch.

5. the unit configuration is hrB for a horizontal right hand unit with a bottom discharge.

Why Direct-Fired Makeup Air?Inexpensive to Operate Direct gas firing is 100% effective. in the majority of gas fired appliances which utilize heat exchanging devices approximately 20%, and usually more of the thermal content of the fuel is lost in vented flue gases as well as up to an additional 10-15% lost in piping or ducting. With direct firing, 100% of the fuel’s energy is absorbed by the makeup air.

Inexpensive to Install and Maintain only a gas line to the burner and an electrical hook-up to the air blower motor and controls are required. the burner does not require an air gas premixer, consequently, installation and maintenance are considerably simpler and more economical.

Completely Safe combustion is electronically supervised to provide shut down in the event of flame failure. an adequate supply of circulating air is ensured by an air velocity interlock switch or the burner is automatically shut down. excessive temperatures are guarded against by a manual reset high limit switch. the burner produces no harmful concentrations of carbon monoxide in the air stream. the nozzle design eliminates mechanical devices for mixing and controlling. no adjustment is required; it is impossible to maladjust.

Makeup Air Application a Direct-FireD Makeup air unit is a combination of elements designed to condition fresh air introduced into the unit. this air is then blown into the occupied or unoccupied space replacing the air that is exhausted, through powered exhaust fans.

Makeup air units may, therefore be required to heat, ventilate, cool, humidify, dehumidify, pressurize, and filter the air blown into the space (supply air). the supply airflow will be either fixed or variable, which can respond directly to different exhaust flow rates in order to achieve room pressurization control.

pressurization of a space eliminates:

- exhaust systems from exhausting incorrect air volumes - building perimeters being cold in the winter due to high infiltration - drafts at exterior doors - doors from being hard to open from the outside - uneven temperature conditions in the building space - gravity vented gas appliances from back venting

Selection Guide for Direct-Fired Makeup Air

Selection for 80/20 Units (available in uS only)

the iMa series unit can be used as a combination makeup air and heating unit. a minimum of 20% fresh air must be provided at all times and the balance (80%) is a combination of fresh and return air. With the dampers fixed for 80% recirculation the iMa series unit functions as a space heater.

1

46906_ICE_IMA_Manual_Guts.indd 3 1/11/08 10:10:48 AM

Page 6: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

Standard Features

Blowers Backward inclined, air foil, and plenum fans

DX Plenum coil located in vertical or horizontal airflow complete with drain pan when applicable.

Coil Plenums heating coils- steam, hot water, and glycol cooling coils- chilled water, DX coil

Evaporative Coolers industrial and commercial

Hinged Access Doors Door switches Special access door gasketing #310 ventlock fasteners

Mushroom Hood air velocity through the inlet ranges between approximately 450 and 550 feet per minute at maximum air capacities listed. complete with internal screen for debris

Louvered Inlet Manufactured by ice and sized for a maximum velocity of 500 FpM to minimize potential for precipitation entering the unit

4 Way Discharge Head the adjustable 4 way discharge head provides 4 equal quantities of air in the conditioned space

Horizontal Discharge Head 180 deg. vertical and horizontal adjustment with 360 deg. of free rotation

80/20 Mix Box Available in US only allows the recirculation of air to occur. this will provide a cost effective way of space heating. includes V-bank filter rack

Weatherhousing control and manifold enclosure

Inlet Hoods expanded metal screen inlet with optional 2” filters.

Inlet Hood & Filter Rack combination inlet hood with filter rack for 2” thick filters available on models iMa 109-122.

Filter Section V-bank filter section with side access suitable for 2” filters.

Winter Filter Section located on the discharge side of burner.

Filters 2” thick permanent, pleated and throwaway filters; various efficiency bag filters and hepa filters complete with filter gauge and/or indicating light.

Motorized Inlet & Discharge Damper parallel blade damper with a two-position spring return actuator and end switch.

Roof Curb prefabricated galvanized roof curb 16” or 24” high; full perimeter available on most units.

Internal Vibration Isolation Blower and motor isolated on separate frame with r.i.S. or spring c/w canvas connector

External Vibration Isolation Floor mounted or suspended isolation

Service Platform provides access to controls and gas train

Motors teFc and high-efficiency, meeting eee and cSa standards and 2-speed

Disconnect Switch Weatherproof enclosure; non-fused or fused

Fm Gas Train Meets Factory Mutual (FM) requirements

Iri Gas Train Meets industrial risk insurers requirements

High Gas Pressure Regulator required on natural gas with pressure in excess of 5 psig and lp applications in excess of 11 ” W.c.

High/Low Gas Pressure Switches Manual reset, gas pressure safety switches which lock out the burner in the event of gas pressure malfunction.

Control Panels neMa 4 or 12 custom, unit mounted or remote enclosures. explosion proof panels

Dual Volume inlet air volume damper to achieve two airflow capacities.

Standard Features

Optional Features

Burner/Manifold - Stainless steel mixing plates and cast iron gas manifold - 30:1 turndown ratio - intermittent pilot assembly with spark igniter and ignition transformer - Solid state flame monitoring system - adjustable profile plates - Burner observation port - choice of temperature control systems - Manifold pressure for natural gas 7-14” W.c. or 1-5 psig - Manifold pressure for propane 11” W.c. - Manifold includes: pilot regulator, gas valve and shutoff valve, safety shutoff valve, pressure regulator or combination modulating and pressure regulating valve, modulating gas valve, main test fire valve, manifold pressure taps.

Controls Enclosure - electronic flame safeguard relay manual reset - high and low airflow pressure switches - Manual reset high limit - Factory wired control panel with numbered terminal strip - Motor starter with overloads - control circuit transformer, 120 volt - control panel service switch - circuit breaker - terminal connections for exhaust interlock - nationally recognized components, service parts.

Assurance - etl & c-etl listed, conforms to anSi Z83.4B-2002 & cSa 3.7B-2002 - Factory wired, piped, and test fired.

Cabinet - Welded structural or formed channel base frame - lifting lugs - heavy gauge colorbond steel casing with rust-resistant grey enamel paint finish - one inch thick 1.5# density neoprene coated fiberglass. the insulation is glued and pinned

Blower/Motor - aMca rated forward curve DWDi centrifugal blower - polished steel shaft with rust inhibitor - Maximum operating speed less than 75% of first critical speed - Standard heavy-duty industrial bearings used on unit sizes iMa 120 and larger. - Sealed cartridge bearings provided on unit sizes iMa 118 and smaller. - oDp motor, 1800 rpM, t frame, 1.15 service factor mounted on adjustable base - Drives designed for 150% motor brake horsepower - adjustable V-belt drives used up to and including 5 hp; fixed drives on 7.5 hp and larger

Additional Options - auto low limit freeze protection control with bypass timer - 10 point electronic circuit analyzer with signal lights - exhaust interlock relay - proof of closure Valve - inlet air controller (burner economizer) - ultra violet flame supervision - audible alarm - Firestat

- 7-day programmable timeclock - purge timer - Delay exhaust start - 115 volt GFi service receptacle - Marine service light with 100 watt bulb, guard, and lighted switch - high density insulation - 2” thick and 4” thick insulation - Motor and bearings out of airstream - Jic wiring

- extended grease lines - Belt guards - checker plate floor - Walk-in service corridors - corrosion resistant two-step acrylic finish - Special coatings - Special construction: aluminum, stainless steel, heavier gauges2

46906_ICE_IMA_Manual_Guts.indd 4 1/11/08 10:10:48 AM

Page 7: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

IM Series Standard Temperature Control OptionsBuilding makeup air systems maintain a constant supply air temperature to the space using a discharge temperature controller. the burner output is modulated over a wide range to compensate for fluctuations in the incoming ambient air temperature. a gas valve regulates output according to the demand sensed by a discharge air sensor. the fan and heat system functions are typically controlled by a remote panel with a system and summer/winter switch or a building management system.

Discharge Air Temperature Control used predominantly for makeup air applications to maintain supply air at a constant temperature. the burner firing rate modulates in response to a discharge air controller.

A) Electronic Control the electronic modulating system consists of a discharge sensor, electronic amplifier and valve, which respond instantaneously to small fluctuations in temperature. the system is capable of close temperature control over a wide range. included with the system is a remote temperature selector; range 55 to 90 degrees F. the system is also available with leD temperature indication, as an available option.

Discharge Air Temperature Control With Room Override commonly used in applications requiring maintenance of space temperatures as well as a constant discharge temperature. typical applications include plants and kitchens, which may require a morning warm-up. the override feature provides auxiliary heat to a space as required and sensed by a room thermostat.

A) Electronic Control the electronic modulating system as described above, in addition to the rtS (remote temperature Sensor) is furnished with a space thermostat. if the thermostat setting is not satisfied, the discharge temperature will be increased until the thermostat is satisfied. the degree of override can be adjusted at the rtS. an outdoor reset thermostat is also an available option.

Space Temperature Control used primarily for space heating applications, i.e. maintaining the space temperature at a certain level. this is accomplished primarily by using a space thermostat.

A) Electronic Control the burner firing rate is modulated in response to an amplified signal from a room-mounted thermostat. the discharge temperature is maintained within preset maximum and minimum settings on the amplifier. the control package includes a thermostat with a temperature selector mounted either on the remote panel or in the space.

B) Electronic Control - Door Heater Applications the electronic modulating door heater system is similar to the standard makeup air system, with an added feature; adjustable high temperature override limit. activated by a door switch, the discharge temperature is indexed automatically to a higher setpoint compensating for the increased heat loss, the result of an open door.

Miscellaneous Control OptionsFreeze Protection Specified to protect against untempered air entering the space. the freeze thermostat, also known as an auto low limit, is located in the discharge air and is wired in parallel with a time delay relay. in the event that the discharge air temperature is not above the freeze thermostat setting, within a preset time during start-up and under normal operation the unit will shut down.

Inlet Air Controller Features an adjustable thermostat, which monitors outdoor air temperatures. When the temperature exceeds the setting of the thermostat, the burner will not operate even when the unit is in the winter mode.

Night Setback (Available in US only) this feature is available as an option on all temperature control systems. By lowering the discharge air temperature requirements during unoccupied periods the owner can realize operating economies and still provide heat to the space as required. During the occupied cycle, the unit will be brought on though an interlock, timeclock or switch. During the unoccupied period the timeclock provided, switches the system control to a single stage thermostat set at the desired unoccupied temperature. the unit will then be started intermittently to provide heat to maintain the space at the unoccupied temperature setpoint.

Maxitrol DFM Series provides complete anSi burner 80/20 capacity control. available with 7-Day night set back control. it is also compatible with building management control systems.

3

46906_ICE_IMA_Manual_Guts.indd 5 1/11/08 10:10:49 AM

Page 8: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

4

IM Series Direct FiredPerformance Specifications

Outlet Fan HP @ ESP in. w.c. Input Capacity (MBH) vs Temp Rise (F)

Model SCFM Velocity FPM 0.25 0.5 0.75 1 1.5 2 70 80 90 100 110 120 130 135

1000 1124 1/3** 1/3** 1/2** 1/2** 3/4** 3/4** 82 94 106 118 130 142 154 1581200 1435 1/2 1/2 3/4 3/4 1 1** 99 113 127 141 155 169 183 1901400 1675 0.5 0.5 0.75 0.75 1 1 1/2** 115 131 148 164 181 197 214 2221600 1914 3/4 3/4 3/4 1 1 1 1/2** 131 150 169 188 207 226 245 254

IM-109 1800 2153 0.75 0.75 1 1 1 1 1/2** 148 169 190 211 232 253 274 2852000 2392 1 1 1 1 1/2 1 1/2 2 164 188 211 235 258 282 305 3172200 2632 1 1 1.5 1.5 1.5 2 181 207 232 258 284 310 336 3492400 2871 1 1/2 1 1/2 1 1/2 1.5 2 3 197 225 254 282 310 338 366 3802600 3110 1.5 1.5 1.5 2 2 3 214 244 275 305 335 366 396 412

2000 1389 0.5 0.75 0.75 1 1/2* 1 1/2* 2* 164 188 211 235 258 282 305 3172500 1736 3/4 1 1 1 1/2 2* 3* 205 235 264 293 323 352 381 396

IM-112 3000 2083 1 1.5 1.5 2 2 3* 247 282 317 352 387 422 457 4753500 2431 1 1/2 1 1/2 2 2 2 3 288 329 370 411 452 493 534 5554000 2778 1.5 1.5 2 2 3 5 329 376 423 470 517 564 611 634

3000 1493 0.75 0.75 1 2* 2* 3* 247 282 317 352 387 422 457 4753500 1741 3/4 1 1 1 1/2 2* 3* 288 329 370 411 452 493 534 5554000 1990 1 1.5 1.5 2 2 5* 329 376 423 470 517 564 611 634

IM-115 4500 2239 1 1/2 2 2 2 3 5* 370 423 475 528 581 634 687 7135000 2488 2 2 3 3 3 5 411 470 528 587 646 705 764 7925500 2736 3 3 3 3 5 5 452 517 581 646 710 775 839 8726000 2985 3 3 3 5 5 5 493 563 634 704 775 845 916 9516500 3234 3 5 5 5 5 7 1/2 534 610 687 763 840 916 993 1030

5000 1742 1.5 1.5 2 2 3 5* 411 470 528 587 646 704 763 7925500 1916 1 1/2 2 2 3 3 5* 452 517 581 646 710 775 839 8726000 2091 2 3 3 3 5 5* 493 563 634 704 775 845 916 951

IM-118 7000 2439 3 3 3 5 5 7 1/2 575 657 740 822 904 986 1068 11098000 2787 3 5 5 5 5 7.5 657 751 845 935 1025 1115 1205 12689000 3136 5 5 5 7 1/2 7 1/2 10 740 845 951 1056 1162 1267 1373 142610000 3484 5 7.5 7.5 7.5 7.5 10 822 939 1056 1173 1290 1407 1524 1585

7000 1667 1.5 2 3 3 5 7 1/2* 575 657 740 822 905 987 1070 11098000 1905 3 3 3 5 5 7 1/2* 657 751 845 939 1033 1127 1221 12689000 2143 3 3 3 5 5 10* 740 845 951 1056 1162 1267 1373 1426

IM-120 10000 2381 3 5 5 5 7 1/2 10 822 939 1057 1174 1292 1409 1527 158511000 2619 5 5 5 7.5 7.5 10 904 1033 1162 1291 1420 1549 1678 174312000 2857 5 7 1/2 7 1/2 7 1/2 7 1/2 10 986 1127 1268 1409 1550 1691 1832 190213000 3095 7.5 7.5 7.5 10 10 15 1068 1221 1373 1526 1678 1831 1983 206014000 3333 7 1/2 10 10 10 10 15 1150 1315 1479 1644 1808 1973 2137 2219

10000 1961 5 5 5 5 7.5 10* 822 939 1057 1174 1292 1409 1527 158511000 2157 5 5 7 1/2 7 1/2 7 1/2 10* 904 1033 1162 1291 1420 1549 1678 174312000 2353 5 5 7.5 7.5 10 10 986 1127 1268 1409 1550 1691 1832 1902

IM-122 13000 2549 7 1/2 7 1/2 10 10 10 15 1068 1221 1373 1526 1678 1831 1983 206014000 2745 7.5 7.5 10 10 10 15 1150 1315 1479 1644 1808 1973 2137 221915000 2941 10 10 10 15 15 15 1233 1409 1585 1761 1937 2113 2289 237716000 3137 10 10 10 15 15 15 1315 1503 1690 1878 2065 2253 2440 253617000 3333 15 15 15 15 15 20 1397 1597 1796 1996 2195 2395 2594 2694

14000 2086 5 5 7.5 7.5 7.5 15* 1150 1315 1479 1644 1808 1973 2137 221915000 2235 5 5 7 1/2 7 1/2 10 15* 1233 1409 1585 1761 1937 2113 2289 237716000 2385 7.5 7.5 7.5 7.5 10 15* 1315 1503 1690 1878 2065 2253 2440 2536

IM-125 17000 2534 7 1/2 7 1/2 10 10 10 15 1397 1597 1796 1996 2195 2395 2594 269418000 2683 7.5 7.5 10 10 15 15 1479 1690 1902 2113 2325 2536 2747 285319000 2832 7 1/2 7 1/2 10 10 15 15 1561 1784 2007 2230 2453 2677 2900 301120000 2981 10 10 15 15 15 20 1643 1878 2113 2348 2583 2818 3053 317022000 3279 15 15 15 15 15 20 1808 2066 2324 2582 2840 3098 3356 3487

* Previous size blower required

** Backward Incline blower required

INDUSTRIALCOMMERCIAL

EQUIPMENT

I.C.E. (US), INC.

IM Direct-Fired Series Performance Specifications

46906_ICE_IMA_Manual_Guts.indd 6 1/11/08 10:10:49 AM

Page 9: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

5

IM Series Direct FiredPerformance Specifications

Outlet Fan HP @ ESP in. w.c. Input Capacity (MBH) vs Temp Rise (F)

Model SCFM Velocity FPM 0.25 0.5 0.75 1 1.5 2 70 80 90 100 110 120 130 135

20000 2151 7.5 7.5 10 10 15 15 1643 1878 2113 2348 2583 2818 3053 317022000 2366 10 10 10 15 15 20 1808 2066 2324 2582 2840 3098 3356 348724000 2581 10 10 15 15 20 20 1972 2254 2536 2818 3100 3382 3664 3803

IM-130 26000 2796 15 15 15 15 20 20 2137 2442 2747 3052 3357 3662 3967 412028000 3011 15 15 20 20 20 25 2301 2630 2958 3287 3615 3944 4272 443730000 3226 15 20 20 20 20 25 2465 2817 3170 3522 3875 4227 4580 475432000 3441 15 20 20 20 25 30 2630 3005 3381 3756 4132 4508 4883 5071

26000 2158 10 15 15 15 15 20 2137 2442 2747 3052 3357 3662 3967 412028000 2324 15 15 15 15 20 25 2301 2630 2958 3287 3615 3944 4272 443730000 2490 15 15 15 20 20 25 2465 2817 3170 3522 3875 4227 4580 4754

IM-133 32000 2656 15 15 20 20 20 25 2630 3005 3381 3756 4132 4508 4883 507134000 2822 20 20 20 20 20 30 2794 3193 3592 3991 4390 4789 5188 538836000 2988 20 20 25 25 30 30 2958 3381 3803 4226 4648 5071 5493 570538000 3153 20 25 25 30 30 40 3123 3569 4015 4461 4907 5353 5799 6022

30000 2344 15 15 15 15 20 25 2465 2817 3170 3522 3875 4227 4580 475432500 2539 15 15 20 20 25 25 2671 3052 3434 3815 4197 4578 4960 515135000 2734 20 20 20 20 25 30 2876 3287 3698 4109 4520 4931 5342 5753

IM-136 37500 2929 20 20 25 25 30 30 3082 3522 3962 4402 4842 5282 5722 594340000 3125 25 25 25 30 30 40 3287 3757 4226 4696 5165 5635 6104 633942500 3320 25 30 30 30 35 40 3492 3991 4490 4989 4490 3991 3492 673545000 3515 30 30 40 40 40 40 3698 4226 4754 5282 5810 6338 6866 7131

37500 2711 20 25 25 25 30 30 3082 3522 3962 4402 4842 5282 5722 594340000 2892 25 25 30 30 30 40 3287 3757 4226 4696 5165 5635 6104 6339

IM-138# 42500 3073 30 30 30 40 40 40 3492 3991 4490 4989 4490 3991 3492 673545000 3254 30 40 40 40 40 50 3698 4226 4754 5282 5810 6338 6866 713147500 3435 40 40 40 40 50 50 3903 4461 5018 5576 6133 6691 7249 752850000 3615 40 50 50 50 50 60 4109 4696 5283 5870 6457 7044 7631 7924

47500 2749 30 30 30 40 40 40 3903 4461 5018 5576 6133 6691 7249 752850000 2894 30 40 40 40 40 50 4109 4696 5283 5870 6457 7044 7631 7924

IM-140# 52500 3038 40 40 40 40 50 50 4314 4930 5547 6163 6779 7396 8012 832055000 3183 40 40 50 50 50 60 4520 5165 5811 6457 7102 7748 8393 871657500 3328 50 50 50 50 60 60 4725 5400 6075 6750 7425 8100 8775 911360000 3472 50 50 50 60 60 60 4930 5635 6339 7043 7748 8452 9157 9509

57500 2806 30 30 40 40 40 50 4725 5400 6075 6750 7425 8100 8775 911360000 2928 40 40 40 40 50 50 4930 5635 6339 7043 7748 8452 9157 9509

IM-145# 62500 3050 40 40 40 50 50 60 5136 5870 6603 7337 8071 8804 9538 990565000 3172 40 40 50 50 50 60 5341 6104 6867 7630 8393 9156 9919 1030167500 3294 50 50 50 50 60 60 5547 6339 7132 7924 8716 9509 10301 1069770000 3416 50 50 50 60 60 75 5752 6574 7396 8218 9040 9862 10684 11093

60000 2414 25 30 30 40 40 50 4930 5635 6339 7043 7748 8452 9157 950965000 2616 30 40 40 40 50 50 5341 6104 6867 7630 8393 9156 9919 10301

IM-148# 70000 2817 40 40 50 50 50 60 5752 6574 7396 8218 9040 9862 10684 1109375000 3018 50 50 50 50 60 75 6163 7043 7924 8804 9685 10565 11446 1188680000 3219 50 50 60 60 75 75 6574 7513 8452 9391 10330 11270 12209 12678

65000 2134 30 30 30 40 40 50 5341 6104 6867 7630 8393 9156 9919 1030170000 2298 40 40 40 40 50 50 5752 6574 7396 8218 9040 9862 10684 1109375000 2462 40 40 40 40 50 60 6163 7043 7924 8804 9685 10565 11446 11886

IM-154# 80000 2626 50 50 50 50 60 60 6574 7513 8452 9391 10330 11270 12209 1267885000 2791 50 50 50 50 60 75 6985 7983 8980 9978 10976 11974 12972 1347190000 2955 60 60 60 60 75 75 7396 8452 9509 10565 11622 12678 13735 14263

* Previous size blower required

# Backward Inclined Blower -Standard

INDUSTRIALCOMMERCIAL

EQUIPMENT

I.C.E. (US), INC.

IM Direct-Fired Series Performance Specifications

46906_ICE_IMA_Manual_Guts.indd 7 1/11/08 10:10:50 AM

Page 10: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

IM Direct-Fired Series Performance Specifications

6

IM Series Direct FiredPerformance Specifications

Outlet Fan HP @ ESP in. w.c. Input Capacity (MBH) vs Temp Rise (F)

Model SCFM Velocity

FPM 0.25 0.5 0.75 1 1.5 2 70 80 90 100 110 120 130 135

85000 2281 na na 40 50 50 60 6985 7983 8980 9978 10976 11974 12972 1347195000 2550 40 40 50 60 60 75 7807 8922 10037 11152 12267 13382 14498 15055

IM-160# 105000 2818 40 50 60 75 75 100 8628 9861 11093 12326 13559 14791 16024 16640115000 3086 75 75 75 100 100 100 9450 10800 12150 13500 14850 16200 17550 18225125000 3355 100 100 100 100 100 125 10272 11739 13207 14674 16141 17609 19076 19810

115000 2551 60 60 75 75 100 100 9450 10800 12150 13500 14850 16200 17550 18225120000 2662 60 75 75 75 100 100 9861 11270 12678 14087 15496 16904 18313 19017125000 2773 75 75 75 100 100 100 10272 11739 13207 14674 16141 17609 19076 19810

IM-166# 130000 2884 75 75 100 100 100 125 10683 12209 13735 15261 16787 18313 19839 20602135000 2995 75 100 100 100 100 125 11093 12678 14263 15848 17433 19018 20603 21395140000 3106 100 100 100 100 125 125 11504 13148 14791 16435 18078 19722 21365 22187145000 3217 100 100 100 100 125 125 11915 13617 15320 17022 18724 20426 22128 22979150000 3327 100 100 125 125 125 150 12326 14087 15848 17609 19370 21131 22892 23772

125001 2267 60 60 75 75 100 100 10272 11739 13207 14674 16141 17609 19076 19810135000 2448 60 75 75 75 100 100 11093 12678 14263 15848 17433 19018 20603 21395

IM-175# 145000 2629 75 75 100 100 100 125 11915 13617 15320 17022 18724 20426 22128 22979155000 2811 75 100 100 100 125 125 12737 14557 16376 18196 20015 21835 23654 24564165000 2992 100 100 100 100 125 150 13559 15496 17433 19370 21307 23244 25181 26149175000 3173 100 125 125 125 150 150 14380 16435 18489 20543 22598 24652 26707 27734

# Backward Inclined Blower -Standard

1. Specifications subject to change without notice

2. ETL listed units available up to 3 in. w.c. ESP

3. ETL listed LP units available up to 110 F

INDUSTRIALCOMMERCIAL

EQUIPMENT

I.C.E. (US), INC.

acceSSorieSStatic pressure Drop

(in incheS Water coluMn

FreSh air inlet plenuM anD BirDScreen 0.2

inlet hooD W/ FilterS 0.25

inlet hooD W/o FilterS 0.1

eVaporatiVe cooler (coMMercial) 0.3

eVaporatiVe cooler (inDuStrial) 0.3

inlet DaMper 0.1

DX plenuM anD coil 0.45

Winter Filter (V-Bank) 0.4

norMal Filter (V-Bank) 0.4

80/20 MiX BoX W/ FilterS 0.4

horiZontal DiScharGe heaD 0.5

MuShrooM hooD 0.5

4-Way DiScharGe heaD 0.5

NOTE: ACCESSORY STATIC PRESSURE DROPS ARE CALCULATED AT MAXIMUM CFM LOADS

Static Presssure Drop Due to AccessoriesGaS input (MBh) 8-14 in. W.c 1-5 pSi

to 275 1/2" 1/2"

276-400 3/4" 3/4"

401-660 1" 1"

661-1000 1" 1"

1001-1375 1-1/4" 1"

1376-1650 1-1/4" 1"

1651-1925 1-1/2" 1-1/4"

1926-3575 2" 1-1/2"

3576-5225 2-1/2" 2"

5226-5500 3" 2"

5501-6050 3" 2"

6051-6875 3" 2-1/2"

6876-9900 n/a 2-1/2"

9901-14520 n/a 3"

NOTE: CONTACT FACTORY FOR WEIGHTS AND FILTER SIZES

Gas Inlet Sizing

46906_ICE_IMA_Manual_Guts.indd 8 1/11/08 10:10:50 AM

Page 11: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

G

AOPTIONAL S/A

I4"TYP.

EF

MOTOR COMPARTMENTCONTROL CABINET

CONTROL CABINET

MANIFOLD COMPARTMENT

GAS CONNECTION

(FIELD BOLTING REQUIRED)ARE SPLIT FOR SHIPMENTUNIT SIZE 138 THRU 175

P

R

K

D

G

OPTIONAL S/A

BURN

ER

INLE

T DA

MPE

R

N

U

T

BLOWER

H

C

S/A

I

J

G

L

B

E

F

EF

G

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

UNIT SIZE A B C D E F G H I J K L N P R T U

109-112 72 45 28 1/2 — 7 20 18 1/2 18 4 4 16 3 21 19 4 4 1 3/8

115-118 79 60 39 — 10 24 26 26 4 4 20 3 34 28 4 3 1 3/8

120-122 91 78 49 — 14 36 36 28 4 4 20 3 50 32 7 4 1 3/8

125-130 101 90 64 — 15 40 40 35 4 1/2 4 20 4 60 50 5 5 1 1/2

133-136 116 101 72 — 17 1/2 48 48 35 1/2 4 1/2 4 20 4 72 60 4 4 1/2 1 1/2

138-140 132 110 89 78 19 1/2 53 53 37 1/2 5 4 25 5 76 74 5 4 1/2 1 3/4

145-148 158 140 101 96 25 72 72 43 5 5 25 5 105 72 12 5 1 3/4

154-160 188 170 124 1/2 118 31 90 90 49 6 6 25 6 135 96 12 5 2

166-175 224 200 144 144 38 110 90 52 6 6 30 8 144 120 12 13 2 1/2

7ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

IMA SERIES DIRECT-FIRED HEATERSHORIZONTAL CONFIGURATION

TITLE

NOTEinDuStrial coMMercial

eQuipMent ManuFacturinG ltD.

46906_ICE_IMA_Manual_Guts.indd 9 1/11/08 10:10:51 AM

Page 12: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

E

E

Y

W GOPTIONAL S/A

A

R/AX I

4"TYP.F

CONTROL CABINET

MANIFOLD COMPARTMENT

CONTROL CABINET

GAS CONNECTION

UNIT SIZE 138 THRU 175 ARE SPLIT FOR SHIPMENT(FIELD BOLTING REQUIRED)

P

R

K

U

N

T

UIN

LET

DAM

PER

BURN

ER

G

D

MOTOR COMPARTMENT

OPTIONAL S/A

C

J

G

I

H

S/A

R/ADAMPER F

E

BLOWER

L

F

B

Z R/A

G

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

8ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

IMR SERIES 80/20 DIRECT-FIRED HEATERSHORIZONTAL CONFIGURATION

TITLE

NOTE

UNIT SIZE A B C D E F G H I J K L N P R T U W X Y Z

109-112 72 45 28 1/2 — 7 20 18 1/2 18 4 4 16 3 21 19 4 4 1 3/8 20 10 21 4

115-118 79 60 39 — 10 24 26 26 4 4 20 3 34 28 4 3 1 3/8 20 12 34 3

120-122 91 78 49 — 14 36 36 28 4 4 20 3 50 32 7 4 1 3/8 28 14 50 4

125-130 101 90 64 — 15 40 40 35 4 1/2 4 20 4 60 50 5 5 1 1/2 19 22 60 5

133-136 116 101 72 — 17 1/2 48 48 35 1/2 4 1/2 4 20 4 72 60 4 4 1/2 1 1/2 20 24 72 4 1/2

138-140 132 110 89 78 19 1/2 53 53 37 1/2 5 4 25 5 76 74 5 4 1/2 1 3/4 20 31 76 4 1/2

145-148 158 140 101 96 25 72 72 43 5 5 25 5 105 72 12 5 1 3/4 29 30 105 5

154-160 188 170 124 1/2 118 31 90 90 49 6 6 25 6 135 96 12 5 2 30 36 135 5

166-175 224 200 144 144 38 110 90 52 6 6 30 8 144 120 12 13 2 1/2 30 44 160 5

46906_ICE_IMA_Manual_Guts.indd 10 1/11/08 10:10:51 AM

Page 13: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

N

CONTROL CABINET

A

MANIFOLD COMPARTMENT

G

S/A

I4"TYP.

L

C

GOPTIONAL S/A

G

EF

V-BA

NK F

ILTER

S

INLE

T PL

ENUM

INLE

T DA

MPE

R

OPTIONAL INLET PLENUM

K

CONTROL CABINET

GAS CONNECTION

UNIT SIZE 138 THRU 175 ARE SPLIT FOR SHIPMENT(FIELD BOLTING REQUIRED)

BURN

ER

B

J

I

H

G

D

OPTIONAL S/A

MOTOR COMPARTMENT

EF

F

E

UU

BLOWER

Standard: Right hand configuration shownOptional: Left hand configuration oppositeDimensions are subject to change

9ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

IMA SERIES DIRECT-FIRED HEATERSHORIZONTAL CONFIGURATION WITH V-BANK AND INLET PLENUM

TITLE

NOTEinDuStrial coMMercial

eQuipMent ManuFacturinG ltD.

UNIT SIZE A B C D E F G H I J K L N U

109-112 97 45 28 1/2 — 7 20 18 1/2 18 4 4 25 3 30 1 3/8

115-118 104 60 39 — 10 24 26 26 4 4 25 3 35 1 3/8

120-122 121 78 49 — 14 36 36 28 4 4 30 3 42 1 3/8

125-130 131 90 64 — 15 40 40 35 4 1/2 4 30 4 60 1 1/2

133-136 146 101 72 — 17 1/2 48 48 35 1/2 4 1/2 4 30 4 72 1 1/2

138-140 162 110 89 78 19 1/2 53 53 37 1/2 5 4 30 5 75 1 3/4

145-148 188 140 101 96 25 72 72 43 5 5 30 5 80 1 3/4

154-160 218 170 124 1/2 118 31 90 90 49 6 6 30 6 96 2

166-175 254 200 144 144 38 110 90 52 6 6 30 8 96 2 1/2

46906_ICE_IMA_Manual_Guts.indd 11 1/11/08 10:10:52 AM

Page 14: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

MOTOR COMPARTMENT

MANIFOLD COMPARTMENT

XR/A

AOPTIONAL S/A

GW

OPTIONAL S/A

D

G

(FIELD BOLTING REQUIRED)ARE SPLIT FOR SHIPMENTUNIT SIZE 138 THRU 175

GAS CONNECTION

CONTROL CABINET

CONTROL CABINET

BLOWERDAMPERR/A

BURN

ER

INLE

T DA

MPE

R

UU

C

L

4"TYP.I

R/AZ

F

Y

E

S/A

H

I

G

J

G

F E

B

E

F

INLE

T PL

ENUM

V-BA

NK F

ILTER

S

N

K

OPTIONAL INLET PLENUM

Standard: Right hand configuration shownOptional: Left hand configuration oppositeDimensions are subject to change

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

IMA SERIES 80/20 DIRECT-FIRED HEATERSHORIZONTAL CONFIGURATION WITH V-BANK & INLET PLENUM

TITLE

10NOTE

UNIT SIZE A B C D E F G H I J K L N U W X Y Z

109-112 97 45 28 1/2 — 7 20 18 1/2 18 4 4 25 3 30 1 3/8 45 10 21 4

115-118 104 60 39 — 10 24 26 26 4 4 25 3 35 1 3/8 45 12 34 3

120-122 121 78 49 — 14 36 36 28 4 4 30 3 42 1 3/8 58 14 50 4

125-130 131 90 64 — 15 40 40 35 4 1/2 4 30 4 60 1 1/2 49 22 60 5

133-136 146 101 72 — 17 1/2 48 48 35 1/2 4 1/2 4 30 4 72 1 1/2 50 24 72 4 1/2

138-140 162 110 89 78 19 1/2 53 53 37 1/2 5 4 30 5 75 1 3/4 50 31 76 4 1/2

145-148 188 140 101 96 25 72 72 43 5 5 30 5 80 1 3/4 59 30 105 5

154-160 218 170 124 1/2 118 31 90 90 49 6 6 30 6 96 2 60 36 135 5

166-175 254 200 144 144 38 110 90 52 6 6 30 8 96 2 1/2 60 44 160 5

46906_ICE_IMA_Manual_Guts.indd 12 1/11/08 10:10:53 AM

Page 15: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

NOPTIONAL S/A

G I

A

INLE

T PL

ENUM

UU

OPTIONAL S/A

D

G I

B

BURN

ER

(FIELD BOLTING REQUIRED)ARE SPLIT FOR SHIPMENTUNIT SIZE 138 THRU 175

GAS CONNECTION

CONTROL CABINET

KIN

LET

DAM

PER

V-BA

NK F

ILTER

S

MANIFOLD COMPARTMENT

CONTROL CABINET

C

L

F

E

OPTIONAL S/A

H

J

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

OPTIONAL S/A

OPTIONAL S/A

TITLE

NOTEinDuStrial coMMercial

eQuipMent ManuFacturinG ltD. 11

IMA SERIES DIRECT-FIRED HEATERS WITH PLENUM FANHORIZONTAL CONFIGURATION WITH V-BANK & INLET PLENUM

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

UNIT SIZE A B C D E F G H I J K L N U

109-112 112 45 28 1/2 — 4 37 12 15 1/2 4 5 25 3 30 1 3/8

115-118 130 60 39 — 4 52 20 26 4 5 25 3 35 1 3/8

120-122 151 78 49 — 4 70 25 36 4 5 30 3 42 1 3/8

125-130 178 90 64 — 4 1/2 81 38 50 4 1/2 5 30 4 60 1 1/2

133-136 206 101 72 — 4 1/2 92 48 58 4 1/2 5 30 4 72 1 1/2

138-140 219 110 89 135 5 100 58 74 5 5 30 5 75 1 3/4

145-148 245 140 101 153 5 130 60 86 5 5 30 5 80 1 3/4

154-160 292 170 124 1/2 192 6 158 84 109 1/2 6 5 30 6 96 2

166-175 320 200 210 144 6 188 87 126 6 5 30 8 96 2 1/2

46906_ICE_IMA_Manual_Guts.indd 13 1/11/08 10:10:53 AM

Page 16: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

CONTROL CABINET

H

L

OPTIONAL S/AG I

A

MANIFOLD COMPARTMENT

C

N

J

E

OPTIONAL S/A

OPTIONAL S/A

G I

BURN

ER

(FIELD BOLTING REQUIRED)ARE SPLIT FOR SHIPMENTUNIT SIZE 138 THRU 175

GAS CONNECTION

CONTROL CABINET

K

INLE

T DA

MPE

R

V-BA

NK F

ILTER

S

UU

D

BFIN

LET

PLEN

UM

R/ADAMPER

R/AXW

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

OPTIONAL S/A

OPTIONAL S/A

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

IMA SERIES DIRECT-FIRED HEATERS WITH PLENUM FANHORIZONTAL CONFIGURATION WITH V-BANK & INLET PLENUM

TITLE

12NOTE

UNIT SIZE A B C D E F G H I J K L N U W X

109-112 112 45 28 1/2 — 4 37 12 15 1/2 4 5 25 3 30 1 3/8 45 10

115-118 130 60 39 — 4 52 20 26 4 5 25 3 35 1 3/8 45 12

120-122 151 78 49 — 4 70 25 36 4 5 30 3 42 1 3/8 58 14

125-130 178 90 64 — 4 1/2 81 38 50 4 1/2 5 30 4 60 1 1/2 49 22

133-136 206 101 72 — 4 1/2 92 48 58 4 1/2 5 30 4 72 1 1/2 50 24

138-140 219 110 89 135 5 100 58 74 5 5 30 5 75 1 3/4 50 31

145-148 245 140 101 153 5 130 60 86 5 5 30 5 80 1 3/4 59 30

154-160 292 170 124 1/2 192 6 158 84 109 1/2 6 5 30 6 96 2 60 36

166-175 320 200 210 144 6 188 87 126 6 5 30 8 96 2 1/2 60 44

46906_ICE_IMA_Manual_Guts.indd 14 1/11/08 10:10:54 AM

Page 17: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

S

SHIPMENT SPLIT(UNIT SIZE 138 THRU 175 ONLY)

GJ

S/AOPTIONAL

E

R P

D

V

3'OR 5'

M

BURNER

INLET DAMPER (OPTIONAL)

B

G

I

S/A

ELECTRICALCONNECTION

GAS CONNECTION

A

H F

MANIFOLDCOMPARTMENT

COMPARTMENTMOTOR

CABINETCONTROL

K

C

Q

TN

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

TITLE

NOTEinDuStrial coMMercial

eQuipMent ManuFacturinG ltD. 13

IMA SERIES DIRECT-FIRED HEATERSVERTICAL CONFIGURATION

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

3'-STAND 5'-STAND

UNIT SIZE A A B C D E F G H I J K M N P Q R S T V

109-112 133 157 72 45 27 — 20 18 1/2 18 4 4 16 49 21 19 7 4 31 4 25

115-118 140 164 79 60 36 — 24 26 26 4 4 20 64 34 28 10 4 40 3 25

120-122 157 181 91 78 46 — 36 36 28 4 4 20 82 50 32 14 7 50 4 30

125-130 167 191 101 90 60 — 40 40 35 4 4 20 94 60 50 15 5 64 5 30

133-136 182 206 116 101 68 — 48 48 35 1/2 4 4 20 105 72 60 17 1/2 4 72 4 1/2 30

138-140 198 222 132 110 84 78 53 53 37 1/2 4 6 25 114 76 74 19 1/2 5 88 4 1/2 30

145-148 224 248 158 140 96 96 72 72 43 5 5 25 146 105 72 25 12 102 5 30

154-160 256 280 188 170 120 118 90 90 49 6 6 25 176 135 96 31 12 126 5 30

166-175 290 314 224 200 144 144 110 90 52 6 6 30 206 144 120 38 12 150 13 30

46906_ICE_IMA_Manual_Guts.indd 15 1/11/08 10:10:54 AM

Page 18: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

GAS CONNECTION

V

3'OR 5'

S

OPTIONAL

(UNIT SIZE 138 THRU 175 ONLY)SHIPMENT SPLIT

E

J

R

S/A

S/A

I

G

B

P

W

X

G

D

M

COMPARTMENT

ELECTRICALCONNECTION CONTROL

CABINET

MOTOR

COMPARTMENTMANIFOLD

A

K

H

RETURN AIR DAMPER

INLET DAMPER (OPTIONAL)

BURNER

F Q

N

Y

C

T

Z

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

IMR SERIES 80/20 DIRECT-FIRED HEATERSVERTICAL CONFIGURATION

TITLE

14NOTE

3'-STAND 5'-STAND

UNIT SIZE A A B C D E F G H I J K M N P Q R S T V W X Y Z

109-112 133 157 72 45 27 — 20 18 1/2 18 4 4 16 49 21 19 7 4 31 4 25 20 10 21 4

115-118 140 164 79 60 36 — 24 26 26 4 4 20 64 34 28 10 4 40 3 25 20 12 34 3

120-122 157 181 91 78 46 — 36 36 28 4 4 20 82 50 32 14 7 50 4 30 28 14 50 4

125-130 167 191 101 90 60 — 40 40 35 4 4 20 94 60 50 15 5 64 5 30 19 22 60 5

133-136 182 206 116 101 68 — 48 48 35 1/2 4 4 20 105 72 60 17 1/2 4 72 4 1/2 30 20 24 72 4 1/2

138-140 198 222 132 110 84 78 53 53 37 1/2 4 6 25 114 76 74 19 1/2 5 88 4 1/2 30 20 31 76 4 1/2

145-148 224 248 158 140 96 96 72 72 43 5 5 25 146 105 72 25 12 102 5 30 29 30 105 5

154-160 256 280 188 170 120 118 90 90 49 6 6 25 176 135 96 31 12 126 5 30 30 36 135 5

166-175 290 314 224 200 144 144 110 90 52 6 6 30 206 144 120 38 12 150 13 30 30 44 160 5

46906_ICE_IMA_Manual_Guts.indd 16 1/11/08 10:10:55 AM

Page 19: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

L

N

LOUV

ERED

INTA

KEFL

AT F

ILTER

SEC

TION

OPTIONAL S/A

A

S/A

MANIFOLD COMPARTMENT

CONTROL CABINET

IG

G

I

OPTIONAL S/A

G

J

C

F

E

BLOWER

INLE

T DA

MPE

R

BURN

ER

D

GAS CONNECTION

CONTROL CABINET

MOTOR COMPARTMENT

B

S/A

KM

EVAP

COO

LING

SEC

TION

UNIT SIZE 138 THRU 175 ARE SPLIT FOR SHIPMENT(FIELD BOLTING REQUIRED)

Standard: Right hand configuration shownOptional: Left hand configuration oppositeDimensions are subject to change

TITLE

NOTEinDuStrial coMMercial

eQuipMent ManuFacturinG ltD. 15

IMA SERIES DIRECT-FIRED HEATERS WITH EVAPHORIZONTAL CONFIGURATION

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

UNIT SIZE A B C D E F G I J K L M N U MAX CFM *

109-112 146 55 28 1/2 — 7 20 18 1/2 4 4 — 3 — 40 1 3/8 4000 CFM

115-118 153 70 39 — 10 24 26 4 4 — 3 — 50 1 3/8 10000 CFM

120-122 165 91 49 — 14 36 36 4 4 — 3 — 60 1 3/8 17000 CFM

125 175 104 64 — 15 40 40 4 1/2 4 — 4 — 64 1 3/4 20000 CFM

130 175 104 64 — 15 40 40 4 1/2 4 — 4 — 84 1 3/4 26000 CFM

133 190 116 72 — 17 1/2 48 48 4 1/2 4 — 4 — 84 1 3/4 32000 CFM

136 190 116 72 — 17 1/2 48 48 4 1/2 4 — 4 — 96 1 3/4 37500 CFM

138 206 148 89 78 19 1/2 53 53 5 4 84 5 74 100 1 3/4 47500 CFM

140 206 148 89 78 19 1/2 53 53 5 4 84 5 74 106 1 3/4 55000 CFM

145 232 160 101 96 25 72 72 5 5 92 5 74 118 2 67500 CFM

148 232 160 101 96 25 72 72 5 5 92 5 74 123 2 70000 CFM

154 262 200 124 1/2 118 31 90 90 6 6 92 6 74 124 1/2 2 80000 CFM

160 262 200 124 1/2 118 31 90 90 6 6 92 6 74 138 2 95000 CFM

166 298 230 144 144 38 110 110 6 6 110 6 74 144 2 1/2 105000 CFM

175 298 254 144 144 38 110 110 6 6 110 6 74 144 2 1/2 115000 CFM

* IF CFM EXCEEDS MAX CFM LISTED IN CHART USE NEXT SIZE CABINET

46906_ICE_IMA_Manual_Guts.indd 17 1/11/08 10:10:56 AM

Page 20: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

R/A

V-BA

NK F

ILTER

S

O/A

MANIFOLD

S/A

UNIT SIZE 138 THRU 175 ARE SPLIT FOR SHIPMENT(FIELD BOLTING REQUIRED)

N

T

L

R

A

XW

CONTROLCABINET G C

I

ACCESS DOORACCESS DOOR

CABINETCONTROL

ACCESS DOOR ACCESS DOOR

MD JK

P

INLE

T DA

MPE

R

BURN

ER

R/A DAMPER

ACCESS DOOR

BLOWER

DIFF

USER

COOL

ING

COIL

S

DRAI

N PA

N

F B

E

U

COMPARTMENT

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

IMR SERIES 80/20 DIRECT-FIRED HEATERSHORIZONTAL CONFIGURATION WITH V-BANK & HORIZONTAL COIL PLENUM

TITLE

16NOTE

UNIT SIZE A B C D E F G I J K L M N P R T U V X MAX CFM *

109 157 45 32 — 4 37 10 4 — 25 3 — 21 37 4 4 1 3/8 45 10 2000 CFM

112 157 55 37 — 4 47 24 5 — 25 3 — 26 47 4 4 1 3/8 45 10 3500 CFM

115 169 60 45 — 4 52 14 4 — 25 3 — 35 52 4 4 1 3/8 50 12 5000 CFM

118 169 70 59 — 4 62 25 15 — 25 3 — 47 62 4 4 1 3/8 50 12 8000 CFM

120 183 78 68 — 4 1/2 69 22 5 — 30 4 — 55 69 4 1/2 4 1/2 1 1/2 58 14 11000 CFM

122 183 91 74 — 4 1/2 82 30 20 — 30 4 — 61 82 4 1/2 4 1/2 1 1/2 58 14 15000 CFM

125 201 90 89 — 5 80 28 5 — 40 5 — 84 80 5 5 1 3/4 49 22 18000 CMF

130 201 104 107 — 5 94 48 27 — 40 5 — 92 94 5 5 1 3/4 49 22 26000 CFM

133 224 101 119 — 5 91 36 5 — 30 5 — 94 91 5 5 1 3/4 50 24 30000 CFM

136 224 116 127 — 5 106 60 30 — 30 5 — 112 106 5 5 1 3/4 50 24 37500 CFM

138 240 110 139 78 5 100 38 5 84 30 5 78 124 100 5 5 1 3/4 50 30 40000 CFM

140 240 148 140 78 5 138 62 31 84 30 5 78 125 138 5 5 1 3/4 50 30 50000 CFM

145 278 140 144 96 6 128 42 5 92 30 6 90 126 128 6 6 2 59 30 52500 CFM

148 278 160 144 96 6 148 66 32 92 30 6 90 126 148 6 6 2 59 30 60000 CFM

154 320 170 144 118 6 158 45 5 100 30 6 102 126 158 6 6 2 59 40 65000 CFM

160 320 200 144 118 6 188 45 5 100 30 6 102 126 188 6 6 2 59 40 80000 CFM

166 368 230 144 144 6 218 45 5 110 30 6 114 124 218 6 6 2 1/2 59 40 90000 CFM

175 368 254 144 144 6 242 45 5 110 30 6 114 124 242 6 6 2 1/2 59 40 100000 CFM

* IF CFM EXCEEDS MAX CFM LISTED IN CHART USE NEXT SIZE LARGER CABINET

46906_ICE_IMA_Manual_Guts.indd 18 1/11/08 10:10:56 AM

Page 21: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

ACCESS DOOR

DJ

B

N

DIFF

USER

ACCESS DOOR

COOL

ING

COIL

S

DRAI

N PA

N

V-BA

NK F

ILTER

S

INLE

T PL

ENUM

ACCESS DOOR

BLOWER

ACCESS DOOR

INLE

T DA

MPE

R

BURN

ER

ACCESS DOOR

CONTROL CABINET

DAMPERR/A

L

C

OPTIONAL S/A

O/A R/A

O/A

W X

OM

K

U

E

F

A

G I

COMPARTMENTMANIFOLD

CABINETCONTROL

UNIT SIZE 138 THRU 175 ARE SPLIT FOR SHIPMENT

(FIELD BOLTING REQUIRED)

G OPTIONAL S/A

I

Standard: Right hand configuration shownOptional: Left hand configuration oppositeDimensions are subject to change

TITLE

NOTEinDuStrial coMMercial

eQuipMent ManuFacturinG ltD. 17

IMR SERIES 80/20 DIRECT-FIRED HEATERSHORIZONTAL CONFIGURATION WITH V-BANK, INLET PLENUM & COIL PLENUM

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

UNIT SIZE A B C D E F G I J K L M N O U V X MAX CFM *

109 195 45 32 — 4 37 10 4 — 25 3 — — — 1 3/8 45 10 2000 CFM

112 197 55 37 — 4 47 12 4 — 25 3 — — — 1 3/8 45 10 3500 CFM

115 203 60 45 — 4 52 14 4 — 25 3 — — — 1 3/8 50 12 5000 CFM

118 209 70 59 — 4 62 20 4 — 25 3 — — — 1 3/8 50 12 8000 CFM

120 235 78 68 — 4 1/2 69 22 4 1/2 — 30 4 — — — 1 1/2 58 14 11000 CFM

122 238 91 74 — 4 1/2 82 25 4 1/2 — 30 4 — — — 1 1/2 58 14 15000 CFM

125 267 90 89 — 5 80 28 5 — 40 5 — — — 1 3/4 49 22 18000 CMF

130 269 104 107 — 5 94 30 5 — 40 5 — — — 1 3/4 49 22 26000 CFM

133 295 101 119 — 5 91 32 5 — 30 5 — — — 1 3/4 50 24 30000 CFM

136 299 116 127 — 5 106 36 5 — 30 5 — — — 1 3/4 50 24 37500 CFM

138 338 110 139 78 5 100 38 5 84 30 5 78 124 100 1 3/4 50 30 40000 CFM

140 340 148 140 78 5 138 40 5 84 30 5 78 125 138 1 3/4 50 30 50000 CFM

145 390 140 144 96 6 128 42 6 92 30 6 90 126 128 2 59 30 52500 CFM

148 393 160 144 96 6 148 45 6 92 30 6 90 126 148 2 59 30 60000 CFM

154 440 170 144 118 6 158 45 6 100 30 6 102 126 158 2 59 40 65000 CFM

160 440 200 144 118 6 188 45 6 100 30 6 102 126 188 2 59 40 80000 CFM

166 493 230 144 144 6 218 45 6 110 30 8 114 124 218 2 1/2 59 40 90000 CFM

175 493 254 144 144 6 242 45 6 110 30 8 114 124 242 2 1/2 59 40 100000 CFM

* IF CFM EXCEEDS MAX CFM LISTED IN CHART USE NEXT SIZE LARGER CABINET

46906_ICE_IMA_Manual_Guts.indd 19 1/11/08 10:10:57 AM

Page 22: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

O/A

O/A

CONTROLCABINET

MANIFOLDCOMPARTMENT

IG OPTIONAL S/A

L

INLE

T PL

ENUM

N

I OPTIONAL S/A

G

(FIELD BOLTING REQUIRED)ARE SPLIT FOR SHIPMENTUNIT SIZE 138 THRU 175

F

E

U

K

CONTROL CABINET

ACCESS DOOR

BURN

ER

INLE

T DA

MPE

R

ACCESS DOOR

BLOWER

ACCESS DOOR

V-BA

NK F

ILTER

S

DRAI

N PA

N

COOL

ING

COIL

S

ACCESS DOOR

DIFF

USER

J D

ACCESS DOOR

W

M X

Y

A X

B

C

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

IMR SERIES DIRECT-FIRED HEATERS WITH CONDENSORHORIZONTAL ONFIGURATION WITH V-BANK, INLET PLENUM & COIL PLENUM

TITLE

18NOTE

UNIT SIZE A B C D E F G I J K L M N U MAX CFM *

109 225 45 32 — 6 33 10 4 — 25 3 — — 1 3/8 2000 CFM

112 227 55 37 — 6 43 12 4 — 25 3 — — 1 3/8 3500 CFM

115 233 60 45 — 6 48 14 4 — 25 3 — — 1 3/8 5000 CFM

118 239 70 58 — 6 58 20 4 — 25 3 — — 1 3/8 8000 CFM

120 265 78 68 — 6 66 22 4 1/2 — 30 4 — — 1 1/2 11000 CFM

122 268 91 74 — 6 79 25 4 1/2 — 30 4 — — 1 1/2 15000 CFM

125 297 90 89 — 6 78 28 5 — 40 5 — — 1 3/4 18000 CMF

130 299 104 107 — 6 92 30 5 — 40 5 — — 1 3/4 26000 CFM

133 325 101 119 — 6 89 32 5 — 30 5 — — 1 3/4 30000 CFM

136 329 116 127 — 6 104 36 5 — 30 5 — — 1 3/4 37500 CFM

138 368 110 139 78 6 98 38 5 84 30 5 156 50 1 3/4 40000 CFM

140 370 148 140 78 6 136 40 5 84 30 5 158 50 1 3/4 50000 CFM

145 420 140 144 96 6 128 42 6 92 30 6 172 60 2 52500 CFM

148 423 160 144 96 6 148 45 6 92 30 6 175 60 2 60000 CFM

154 470 170 144 118 6 158 45 6 100 30 6 187 65 2 65000 CFM

160 470 200 144 118 6 188 45 6 100 30 6 187 65 2 80000 CFM

166 523 230 144 144 6 218 45 6 110 30 8 199 70 2 1/2 90000 CFM

175 523 254 144 144 6 242 45 6 110 30 8 199 70 2 1/2 100000 CFM

* IF CFM EXCEEDS MAX CFM LISTED IN CHART USE NEXT SIZE LARGER CABINET

CONDENSOR* V X Y

5 TON 34 45 39

7 1/2 TON 42 45 39

10 TON 42 45 39

12 1/2 TON 40 76 44

15 TON 40 76 44

20 TON 40 76 44

25 TON 56 128 67

30 TON 56 128 67

40 TON 79 100 89

50 TON 79 100 89

60 TON 79 100 89

70 TON 84 123 89

80 TON 84 123 89

90 TON 92 135 92

100 TON 92 135 92

— — — —

— — — —

— — — —

* CONDENSOR SIZES MAY VARY

46906_ICE_IMA_Manual_Guts.indd 20 1/11/08 10:10:58 AM

Page 23: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

P

R

V-BA

NK F

ILTER

S

FINA

L FI

LTER

S

DIFF

USER

COOL

ING

COIL

S

DRAI

N PA

N

ACCESS DOOR ACCESS DOOR

BLOWER

D

R/A DAMPER

BURN

ER

INLE

T DA

MPE

RACCESS DOOR

CONTROLCABINET

ACCESS DOOR

XW

J

ACCESS DOOR

O/A

R/A

CONTROLCABINET

B

S/A

UNIT SIZE 138 THRU 175 ARE SPLIT FOR SHIPMENT

(FIELD BOLTING REQUIRED)

CG

I

A

N

T

M O

F

E

L

COMPARTMENTMANIFOLD

U

K

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

TITLE

NOTEinDuStrial coMMercial

eQuipMent ManuFacturinG ltD. 19

IMR SERIES 80/20 DIRECT-FIRED HEATERSHORIZONTAL CONFIGURATION WITH V-BANK, COIL PLENUM & FINAL FILTERS

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

UNIT SIZE A B C D E F G I J K L M N O P R T U W X MAX CFM *

109 172 45 32 — 4 37 10 4 — 25 3 — 21 — 37 4 4 1 3/8 45 10 2000 CFM

112 172 55 37 — 4 47 24 5 — 25 3 — 26 — 47 4 4 1 3/8 45 10 3500 CFM

115 179 60 45 — 4 52 14 4 — 25 3 — 35 — 52 4 4 1 3/8 50 12 5000 CFM

118 179 70 58 — 4 62 25 15 — 25 3 — 47 — 62 4 4 1 3/8 50 12 8000 CFM

120 201 78 68 — 4 1/2 69 22 5 — 30 4 — 55 — 69 4 1/2 4 1/2 1 1/2 58 14 11000 CFM

122 201 91 74 — 4 1/2 82 30 20 — 30 4 — 61 — 82 4 1/2 4 1/2 1 1/2 58 14 15000 CFM

125 221 90 89 — 5 80 28 5 — 40 5 — 84 — 80 5 5 1 3/4 49 22 18000 CMF

130 221 104 107 — 5 94 48 27 — 40 5 — 92 — 94 5 5 1 3/4 49 22 26000 CFM

133 242 101 119 — 5 91 32 5 — 30 5 — 94 — 91 5 5 1 3/4 50 24 30000 CFM

136 242 116 127 — 5 106 60 30 — 30 5 — 112 — 106 5 5 1 3/4 50 24 37500 CFM

138 289 110 139 78 5 100 38 5 84 30 5 78 124 49 100 5 5 1 3/4 50 30 40000 CFM

140 289 148 140 78 5 138 62 31 84 30 5 78 125 49 138 5 5 1 3/4 50 30 50000 CFM

145 328 140 144 96 6 128 42 5 92 30 6 90 126 50 128 6 6 2 59 30 52500 CFM

148 328 160 144 96 6 148 66 32 92 30 6 90 126 50 148 6 6 2 59 30 60000 CFM

154 370 170 144 118 6 158 45 5 100 30 6 102 126 50 158 6 6 2 59 40 65000 CFM

160 370 200 144 118 6 188 45 5 100 30 6 102 126 50 188 6 6 2 59 40 80000 CFM

166 418 230 144 144 6 218 45 5 110 30 8 114 124 50 218 6 6 2 1/2 59 40 90000 CFM

175 418 254 144 144 6 242 45 5 110 30 8 114 124 50 242 6 6 2 1/2 59 40 100000 CFM

* IF CFM EXCEEDS MAX CFM LISTED IN CHART USE NEXT SIZE LARGER CABINET

46906_ICE_IMA_Manual_Guts.indd 21 1/11/08 10:10:59 AM

Page 24: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

FINA

L FI

LTER

S

ACCESS DOORACCESS DOORACCESS DOORACCESS DOOR

CONTROLCABINET

INLE

T PL

ENUM

DRAI

N PA

N

COOL

ING

COIL

S

V-BA

NK F

ILTER

S

DIFF

USER

BLOWER R/A

DAMPER

BURN

ER

INLE

T DA

MPE

R

ACCESS DOOR

O/A

R/A O/A

CONTROLCABINET

MANIFOLD

UNIT SIZE 138 THRU 175 ARE SPLIT FOR SHIPMENT

(FIELD BOLTING REQUIRED)

A

W X G IL

C

MD JN OK

E

F B

COMPARTMENT

G I

OPTIONAL S/A

OPTIONAL S/A

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

IMR SERIES 80/20 DIRECT-FIRED HEATERSHORIZONTAL CONFIGURATION WITH V-BANK, INLET PLENUM, COIL PLENUM & FINAL FILTERS

TITLE

20NOTE

UNIT SIZE A B C D E F G I J K L M N O U W X MAX CFM *

109 215 45 32 — 4 37 10 4 — 25 3 — — — 1 3/8 45 10 2000 CFM

112 217 55 37 — 4 47 24 4 — 25 3 — — — 1 3/8 45 10 3500 CFM

115 223 60 45 — 4 52 14 4 — 25 3 — — — 1 3/8 50 12 5000 CFM

118 229 70 58 — 4 62 25 4 — 25 3 — — — 1 3/8 50 12 8000 CFM

120 253 78 68 — 4 1/2 69 22 4 1/2 — 30 4 — — — 1 1/2 58 14 11000 CFM

122 256 91 74 — 4 1/2 82 30 4 1/2 — 30 4 — — — 1 1/2 58 14 15000 CFM

125 284 90 89 — 5 80 28 5 — 40 5 — — — 1 3/4 49 22 18000 CMF

130 286 104 107 — 5 94 48 5 — 40 5 — — — 1 3/4 49 22 26000 CFM

133 312 101 119 — 5 91 32 5 — 30 5 — — — 1 3/4 50 24 30000 CFM

136 316 116 127 — 5 106 60 5 — 30 5 — — — 1 3/4 50 24 37500 CFM

138 373 110 139 78 5 100 38 5 84 30 5 78 50 83 1 3/4 50 30 40000 CFM

140 375 148 140 78 5 138 62 5 84 30 5 78 50 85 1 3/4 50 30 50000 CFM

145 425 140 144 96 6 128 42 6 92 30 6 90 60 87 2 59 30 52500 CFM

148 428 160 144 96 6 148 66 6 92 30 6 90 60 90 2 59 30 60000 CFM

154 475 170 144 118 6 158 45 6 100 30 6 102 65 90 2 59 40 65000 CFM

160 475 200 144 118 6 188 45 6 100 30 6 102 65 90 2 59 40 80000 CFM

166 528 230 144 144 6 218 45 6 110 30 8 114 70 90 2 1/2 59 40 90000 CFM

175 528 254 144 144 6 242 45 6 110 30 8 114 70 90 2 1/2 59 40 100000 CFM

* IF CFM EXCEEDS MAX CFM LISTED IN CHART USE NEXT SIZE LARGER CABINET

46906_ICE_IMA_Manual_Guts.indd 22 1/11/08 10:11:00 AM

Page 25: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

BURN

ER

V-BA

NK F

ILTER

S

FACE

DAM

PER

FACE

DAM

PER

COMPARTMENTMANIFOLD

CONTROLCABINET

EXHAUST BLOWERS

PLATE-TO-PLATEHEAT EXCHANGER

R/A

DAM

PER

O/A

O/A

R/A

SUPPLY AIR

EXHAUST AIR

BYPASS DAMPER

ACCESS DOORACCESS DOORACCESS DOOR

ACCESS DOOR

ACCESS DOOR

ACCESS DOOR

(FIELD BOLTING REQUIRED)ARE SPLIT FOR SHIPMENTUNIT SIZE 138 THRU 175

K

DMJ

P

R

U

E

B

F

AXW

T

G I

L

C

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

TITLE

NOTEinDuStrial coMMercial

eQuipMent ManuFacturinG ltD. 21

IMR SERIES HEAT RECOVERY DIRECT-FIRED HEATERSHORIZONTAL CONFIGURATION WITH V-BANK & PLATE-TO-PLATE HEAT EXCHANGER

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

UNIT SIZE A B C D E F G I J K L M P R T U W X

109-112 204 64 68 70 10 18 28 4 1/2 60 32 4 74 55 4 1/2 32 1 1/2 4 1/2 10

115-118 224 76 84 86 12 26 34 4 1/2 64 40 4 74 67 4 1/2 40 1 1/2 4 1/2 14

120-122 279 88 97 98 16 32 39 5 72 46 5 109 78 5 46 1 3/4 5 22

125-130 325 124 125 110 18 43 47 5 72 60 5 143 114 5 60 1 3/4 5 22

133-136 357 148 144 135 20 52 53 6 80 69 6 143 136 6 69 2 6 30

138-140 375 196 144 142 26 58 58 6 90 69 6 143 184 6 69 2 6 40

145-148 — — — — — — — — — — — — — — — — — —

154-160 — — — — — — — — — — — — — — — — — —

166-175 — — — — — — — — — — — — — — — — — —

46906_ICE_IMA_Manual_Guts.indd 23 1/11/08 10:11:01 AM

Page 26: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

AIR FLOWFRESH

SUPPLYAIR FLOW

AIR FLOWRETURN

CABINETCONTROL

COMPARTMENTMANIFOLD

HEAT

WHE

EL

EXHAUSTAIR FLOW

W

B

EU

DJ

L

M

N

C

A

IG

F

X

T

K

Optional: Left hand configuration oppositeStandard: Right hand configuration shown

Dimensions are subject to change

BURN

ER

V-BA

NK F

ILTER

S

ACCESS DOOR ACCESS DOOR

ACCESS DOORACCESS DOORACCESS DOORACCESS DOORACCESS DOOR

22ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

IMR SERIES HEAT RECOVERY DIRECT-FIRED HEATERSHORIZONTAL CONFIGURATION WITH V-BANK & HEAT RECOVERY WHEEL

TITLE

NOTE

UNIT SIZE A B C D E F G I J K L M N T U W X

109-112 199 52 68 70 4 1/2 43 28 4 1/2 129 32 4 10 11 32 1 1/2 18 10

115-118 222 76 84 86 4 1/2 67 34 4 1/2 136 40 4 15 12 1/2 40 1 1/2 26 12

120-122 242 94 97 98 5 84 39 5 144 46 5 20 13 46 1 3/4 32 16

125-130 258 134 137 110 5 124 47 5 148 66 5 25 20 1/2 66 1 3/4 43 18

133-136 292 157 158 134 6 145 53 6 158 76 6 30 24 76 2 52 20

138-140 300 157 158 142 6 145 58 6 160 76 6 40 19 76 2 58 26

145-148 — — — — — — — — — — — — — — — — —

154-160 — — — — — — — — — — — — — — — — —

166-175 — — — — — — — — — — — — — — — — —

46906_ICE_IMA_Manual_Guts.indd 24 1/11/08 10:11:01 AM

Page 27: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

ROOF CURB CROSS SECTION

RIGID INSULATION

TAR AND GRAVEL

CANT STRIP

TYPICAL ASSEMBLY DETAIL

ROOF CURB

UNIT BOTTOM PAN

1/4" X 2" NEOPRENE

2" X 4" WOODEN NAILER

UNIT BASE FRAME

ROOFING PAPER

FLASHING

1 3/4

16

B

A

G

F

E

C

D

TITLE

NOTEinDuStrial coMMercial

eQuipMent ManuFacturinG ltD. 23

IM SERIESROOF CURB

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

UNIT SIZE A1 A2 B C D E F G

109-112 68 93 41 23 3/4 44 1/4 4 22 15

115-118 75 100 56 29 3/4 45 1/4 7 28 21

120-122 87 117 74 39 3/4 47 1/4 11 38 25

125-130 96 1/2 126 1/2 85 1/2 43 3/4 52 3/4 11 3/4 42 31 3/4

133-136 111 1/2 141 1/2 96 1/2 51 3/4 59 3/4 14 1/4 50 32 1/4

138-140 127 157 105 56 3/4 70 1/4 16 55 34

145-148 153 183 135 75 3/4 77 1/4 21 1/2 74 39 1/2

154-160 182 1/2 212 1/2 164 1/2 93 3/4 88 3/4 27 1/4 92 45 1/4

166-175 218 1/2 248 1/2 194 1/2 93 3/4 124 3/4 34 1/4 112 48 1/4

A1 - W/O V-BANK FILTERS A2 - W/O V-BANK FILTERS

46906_ICE_IMA_Manual_Guts.indd 25 1/11/08 10:11:02 AM

Page 28: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

SERVICE PLATFORM4-WAY DISCHARGE HEAD

HORIZONTAL DISCHARGE HEAD DISCHARGE DAMPER

A

B C

36

42

H

1 1/2"

I

1 1/2"

J10F

E

AD

24ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

IM SERIESACCESSORIES

TITLE

NOTE ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

UNIT SIZE A B C D E F H I J

109-112 25 22 22 30 24 18 72 22 22

115-118 30 28 28 35 30 20 79 28 28

120-122 40 38 38 44 40 28 91 38 38

125-130 42 42 42 50 42 34 101 42 42

133-136 46 50 50 60 50 44 116 50 50

138-140 46 55 55 88 75 68 132 56 56

145-148 46 74 74 136 78 116 158 74 74

154-160 48 92 92 166 96 146 188 92 92

166-175 48 92 112 196 96 176 224 92 112

46906_ICE_IMA_Manual_Guts.indd 26 1/11/08 10:11:02 AM

Page 29: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

OUTSIDE AIR

SUPPLY AIRRETURN AIR RETURN AIR INTRODUCEDAFTER THE BURNER

LOUVEREDINLET

FILTERS FACE & BYPASSDAMPERS

PLATE-TO-PLATEHEAT EXCHANGER

EXHAUSTFANS

SLOPEDROOF

FRESHAIRFLOW

FRESHAIRFLOW

RETURNAIRFLOW

SIDE VIEW SUPPLYAIRFLOW

RETURN AIROPENING

W/ GRATE

FILTERS ISOLATORSFACE & RETURNDAMPERS

SUPPLYBLOWER

VFD CABINETCONTROL

PANEL

TITLE

NOTEinDuStrial coMMercial

eQuipMent ManuFacturinG ltD. 25

HEAT RECOVERY UNITSTANDARD MAKE-UP & RELIEF OPERATION

ALL DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND TO MANUFACTURING TOLERANCES

46906_ICE_IMA_Manual_Guts.indd 27 1/11/08 10:11:05 AM

Page 30: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

Unit Casing unit construction is to be of industrial quality heavy gauge bonderized steel. the unit design shall incorporate a full base pan supported by an integral welded channel iron base. Bases are to be of industrial welded structural iron integrity, formed sheet metal bases are unacceptable. all structural iron base supports are to be treated with an industrial epoxy primer enriched with a rust inhibitor.

to ensure the casings are airtight and weatherproof, all panels are to be caulked during assembly. all casings are to be hand fitted and secured with gasketed self-tapping tek screws. roof casing are to feature three-break standing seam panel design. roof casings are to be sloped on outdoor units to prevent standing water. Sloped roofs are to be ¼ in. per foot and feature full drain troughs.

entire unit casing and accessories are to be insulated with fiberglass insulation with hard neoprene facing. (1 or 2 in. thick 1-1/2# or 2# density) insulation is to be secured with industrial glue and welded pin spots. insulation is to be certified to fire and flamespread ratings as outlined by the anSi code. the entire floor of the unit is to feature a steel liner sandwiching the insulation.

units are to be equipped with access doors to all serviceable components. access doors are to have full-length stainless steel piano hinges. all access doors are to be equipped with an insulation liner, positive seal latches and gasketing . access doors are to open outward on negative pressure sections and inward on positive pressure sections. access doors to feature 6 in. handles with locking roller mechanism for ease of latching. all outdoor unit access doors are to be equipped with drain troughs.

units are to be finished with an industrial grade chain stop alkyd enamel paint. the medium grey finish coat is to be a mimum of 3 mils thick and provide 100% coverage.

Blower/Motor Section unit(s) shall be supplied with a single aMca rated centrifugal backward inclined insdustrial statically and dynamically balanced blower. the fan shall be mounted on a heavy duty machined and polished shaft. the shafts maximum operating speed is not to exceed 75% of its first critical speed. the bearings and motor shall be mounted in the airstream. the t-frame motor shall be mounted in a motor compartment on a fully adjustable base. the bearings are to be industrial pillow block type supplied with extended grease lines. the blower is to be driven with an (adjustable) (fixed) 1.25 s.f. V-belt drive package concealed in a belt guard. outdoor units shall have hinged door(s) to provide easy access to maintain and inspect motor, belts & bearings.

Burner Section each unit shall be equipped with a wide range fully modulating direct gas-fired burner capable of 30:1 turndown. the burner shall have stainless steel combustion baffles, non-clogging gas ports, spark-ignited intermittent pilot and flame safeguard system. Burner combustion must be clean and odorless. combustion efficiency must limit the products of combustion to a maximum of 5 ppm carbon monoxide and 0.5 ppm nitrogen dioxide. the burner profile is to be equipped with adjustable profile plates. a heat treated glass observation port shall provide a full view of flame. hinged access door(s) are to be provided to allow easy maintaince and inspection for burner, ignitor and flamerod.

Control/Manifold Compartment unit control enclosure to have hinged access. terminal strip and all wiring shall be numbered. the controls for the heater shall include:

• blower motor starter w/ambient compensated overloads and auxiliary contact(s). • primary to 120v control transformer • 6,ooo volt ignition transformer • control circuit breaker and service switch • manual reset temperature high limit • flamesafeguard relay w/ LED status and flamerod • discharge temperature control sensor • differential air proving safety switch • automatic low temperature limit (optional)

all wiring external to control enclosure shall be run in conduit. the gas manifold shall include:

• main gas pressure regulator • high gas pressure regulator (optional) • manual shutoff & test firing valve • main gas automatic shutoff valve • auxiliary main gas automatic shutoff valve • modulating control system • pilot pressure regulator • pilot automatic shutoff valve • pilot manual shutoff valve • pilot needle valve • multiple test ports

outdoor units shall have hinged doors to provide easy access to maintain and inspect valves and controls.

inDuStrial coMMercial eQuipMent ManuFacturinG ltD.

Supply an ice (uS), inc. Direct-FireD make-up unit designed for (indoor) (outdoor) installation. the capacity and configuration shall be as detailed on the drawings. the unit shall be cGa and etl certified and listed to be in compliance with the current anSi Z83.18 standard.

the line burner, gas train and controls are to be in accordance with (anSi) (FM) (iri) (FM and iri) requirements. Both burner and blower shall be compensated for altitude of operation.

the unit is to be completely factory test fired to verify proper operation. the unit capacity is to be validated with an instantaneous flow meter. a complete electrical circuit analysis is to be conducted and all systems operated and measured. a combustion analyzer is to be employed while unit is operating at full capacity to verify combustion emissions. Burner combustion must be clean and odorless and no aliphatic aldahydes are to be detectable. combustion efficiency must limit the products of combustion to a maximum of 5 ppm carbon monoxide and 0.5 ppm nitrogen dioxide.

26

46906_ICE_IMA_Manual_Guts.indd 28 1/11/08 10:11:05 AM

Page 31: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

INDUSTRIAL COMMERCIAL

EQUIPMENT MANUFACTURING LTD.

EXCELLENCE THROUGH PRovEn PERFoRMAnCE

IMA Direct Gas-Fired Makeup Air Units

46906_ICE_IMA_Manual_Covers.indd 4 1/9/08 1:54:52 PM

Page 32: IMA Direct Gas-Fired Makeup Air Unitsice-us.com/site/1853ice_/IMA_Manual.pdf · EXCELLENCE THROUGH PRovEn PERFoRMAnCE IMA Direct Gas-Fired Makeup Air Units INDUSTRIAL COMMERCIAL EQUIPMENT

BMADirect Gas-Fired makeup Air Units

OSDDirect Fired Makeup Air/

Curing Units

IMAIndustrial

Gas-Fired Units

GIDMIndirect

Gas-Fired Units

h100% makeup air and 80/20 units

hStainless steel burner

hDX or evaporative cooling section option

h30:1 turndown ratio

hRecirculating & Dual Air Dual Temperature Sequence

hExceptional spray booth control packages using PLCs

hBooth balancing option with variable frequency drive on exhaust

hPremium makeup air/curing units for the refinishing industry

h100% makeup air & 80/20 units

hSuitable for any automotive or high-end industrial applications

hBackward inclined blowers standard on sizes 140 and up

hFour-pass drum and tube industrial grade stainless steel heat exchanger

hIndustrial quality forced draft power burner

hHigh efficiency (80%) and excellent durability

hJIC wiring available for the automotive industry

HTDMHigh Turndown

Indirect-Fired Units

MTIIndirect

Gas-Fired Units

ACAir Turnover Units

CUSTOM BUILTUNITS

hStainless steel two-pass drum and tube heat exchanger with forced draft power burner

hBest turndown ratio for power burners in the industry (Up to 60:1)

hInputs of 200, 400, 600, 1000 & 1500 MBH

hUp to 85% (minimum efficiency)

hIndoor or Outdoor packaged indirect-fired heating systems

hStainless steel heat exchanger suitable for 100% outside air

hExcellent temperature control through brand name components

hWide variety of configuration options

hSuperior serviceability through design and simplistic operation

hVertical air turnover heating systems

hAn effective and economical solution to heating, ventilating or conditioning large spaces

hFour-pass indirect-fired heat exchanger

hOptional A-coil cooling section

hICE has the capability to build a wide variety of custom-built units for any type of commercial or industrial application

hSpecializing in heat recovery and custom air handler with heating or cooling coils

INDUSTRIAL COMMERCIAL

EQUIPMENT MANUFACTURING LTD.

ICE MANUFACTURING LTD.

51 Aikins Street

Winnipeg, Manitoba

Canada R2W 4E3

Tel: (204) 586-8565

Fax: (204) 589-7682

www.ice-ww.com

ICE (U.S.) INC.

Industrial Park

Bolivar, Tennessee

United States 38008

Tel: (731) 658-7000

Fax: (731) 658-3090

www.ice-us.com

Printed in Canada

EXCELLENCE THROUGH

PRovEn PERFoRMAnCE

46906_ICE_IMA_Manual_Covers.indd 1 1/9/08 1:54:42 PM