Indoor Environment Quality IEQ-4 Daylight Glare Control Points Available Points Claimed CIR Submitted
2 1 N
Credit Criteria Up to two points are awarded where it is demonstrated that glare is reduced, as follows: • 1 point is awarded where automated blinds/screens with a Visual Light Transmittance (VLT) of less than 10% and a manual override function are installed by either the tenant or the base building owner to reduce glare associated with natural lighting and eliminate all direct sun penetration; • 1 point is awarded where all workstation monitors provided as part of the tenancy fitout are flat-screen and are mounted on an adjustable arm that enables the monitor to be pivoted and adjusted horizontally and vertically. Documents Provided
As-built architectural drawings that show the location of blinds/screens included in the tenancy fitout and marked up to show how all direct sunlight penetration is controlled;
A copy of the data sheet that shows the VLT properties for the installed blinds/screens;
Information confirming the installed blinds/screens are connected to an automated control system with a manual override function that enables occupant control; and
Information from the supplier/installer that quantifies all products supplied and installed in fitout.
Discussion
• Verosol blinds have been installed in all perimeter windows to control daylight glare. They are connected to the Dynalite touch screen and are automated with manual override.
• An as-built architectural plan has been provided to show that blinds have been installed on all windows. An elevation as-built drawing has been provided to show how blinds prevent direct sunlight penetration. An electrical as-built drawings has been provided to demonstrate that all blinds are connected to a relay controller for automation and manual override function.
• The VLT data sheet demonstrates that blinds used have a VLT of 5%. • The letter from Dynalite demonstrates that blinds have been automated to raise and lower on
a preset schedule with manual override from the Dynalite touch screen. • Finally, supplier/installer invoices from Verosol demonstrate that the 68 roller blinds have been
supplied and installed.
A
09.11.07A
A-J-01
01
PERIMETER PLAN
1:100
FOR CONSTRUCTION
BOARDROOMMEETING ROOMMEETING ROOM
AS BUILT
FOR CONSTRUCTION
BLI
BLI
BLI
BLI
BLI
BL
I
BL
I
BL
I
BL
I
BL
I
BL
I
BL
I
BL
I
BL
I
BL
I
BL
I
BL
I
BL
I
BLI
BLI
BLI
BLI
BLI
BL
I
BLI BLI
LEGEND
PERIMETER BLINDS
TYPE: AMBIENCE MOTORISED
FABRIC: SILVER SCREEN
SUPPLIER: VEROSOL
A-J-02
01
PERIMETER BLIND PLAN
BLI
BLI
BLI
27/02/2009P:\07\m0709010.gbs\Cad\_Active\plot\CD-J-01_Perimeter Plan.dgn
CLIENT
CLIENT PROJECT No.
PROJECT
BVN PROJECT NUMBER
STATUS
SCALE
DRAWING NUMBER ISSUE
DRAWING
GRAPHIC SCALE
CONSULTANT
CONSULTANT
TRUE NORTH PROJECT NORTH
DO NOT SCALE1:100 at A2
0 2000 5000
ISSUE DATE FOR
M0709010
GBCA
L15, 179 ELIZABETH STREET
SYDNEY NSW 2000
GREEN BUILDING COUNCIL
OF AUSTRALIA
DAVIS LANGDON
tel 02 9956 8822 fax 02 9956 8848
LINCOLNE SCOTT
tel 02 8907 0900 fax 02 9957 4127
MALE PLANT
CHW
TATTERSALLS
CLUB RISER
TELECOM PLUMBING FH/FHR
FIRE
STAIR
LIFT 18 LIFT 19 LIFT 20
SE
DA
FEMALE PLANT
TWC
RISERS
SMOKE SPILL SHAFT
FIRE
STAIR
A B C D
1
2
3
4
5
A
09.11.07A
A-J-02
FOR CONSTRUCTION
AS BUILT
FOR CONSTRUCTION
PERIMETER BLIND ELEVATION PLAN
BLI BLI BLI BLI BLI BLI BLI BLI BLI BLI
01
PERIMETER BLIND ELEVATION - WEST FACADE
1:100
HATCHED AREA REPRESENTS
PERIMETER BLINDS.
BLINDS ARE TO EXTEND TO COVER
WINDOW FRAMES AND DROP FROM
ABOVE WINDOW TO WINDOW SILL
GLAZED PARTITION
TO BOARDROOM
2700
WINDOW SILL
27/02/2009P:\07\m0709010.gbs\Cad\_Active\plot\CD-J-02_Perimeter Blind Elevation.dgn
CLIENT
CLIENT PROJECT No.
PROJECT
BVN PROJECT NUMBER
STATUS
SCALE
DRAWING NUMBER ISSUE
DRAWING
GRAPHIC SCALE
CONSULTANT
CONSULTANT
TRUE NORTH PROJECT NORTH
DO NOT SCALE1:100 at A2
0 2000 5000
ISSUE DATE FOR
M0709010
GBCA
L15, 179 ELIZABETH STREET
SYDNEY NSW 2000
GREEN BUILDING COUNCIL
OF AUSTRALIA
DAVIS LANGDON
tel 02 9956 8822 fax 02 9956 8848
LINCOLNE SCOTT
tel 02 8907 0900 fax 02 9957 4127
06 March 2009
Joe Karten Green Building Council of Australia Level 15, 179 Elizabeth St Sydney, NSW 2000
Dear Joe,
Following the final programming and commissioning of all lighting and blinds in the GBCA Sydney Office fitout at 179 Elizabeth Street, I confirm the following:
• Board Room default lighting levels are at a 320-400 LUX average – and lighting controls reset to these levels (or off) when video conferencing equipment is not in operation.
• The lighting has been grouped into the zones called out on the E001 Lighting plan produced by KLM and no zone exceeds 100m2.
• Switching for task based lighting at workstations is controlled via staff computers at the location. Switching for general lighting is controlled via the touch screen near reception. Switching for circulation lighting controlled via PIR and photo-electric sensors. Switching for meeting room lighting is controlled via PIR and through a manual override switch in each meeting room.
• Window blinds have been programmed for full automation with manual override function controllable from the touch screen near reception and from within the Board Room for Board Room window blinds.
The lighting has been fully programmed and commissioned in accordance with the GBCA Fitout Lighting Control document produced by Vision Design.
Feel free to contact me with any further queries you may have.
Kind regards, Joseph Gebaily Technical Leader NSW Commissioning
Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia t +61 2 8338 9899 d +61 2 9019 8845 m +61 419 748 847 f +61 2 9019 8899 [email protected] dynalite-online.com