122
IDR-C LCT Local Craft Terminal Application (Version 02.09.02) User’s Manual Manual Code: GDC-001/75 Manual Edition: 4

Idr c Lct User Manual 04

  • Upload
    telmee

  • View
    52

  • Download
    9

Embed Size (px)

DESCRIPTION

local craft tool guide

Citation preview

Page 1: Idr c Lct User Manual 04

IDR-C LCT

Local Craft Terminal Application (Version 02.09.02)

User’s Manual

Manual Code: GDC-001/75

Manual Edition: 4

Page 2: Idr c Lct User Manual 04

INTRACOM S.A. TELECOM SOLUTIONS 19,7 km Markopoulou Ave., 19002 Peania, Athens, Greece,

Tel: (+30 210) 66 79 000, Fax: (+30 210) 66 79 001, http://www.intracom.com

INTRACOM TELECOM, 2006. All rights reserved. All copyright, intellectual and industrial rights in this document and in the technical knowledge it contains are owned by INTRACOM TELECOM and/or their respective owners. This document is made available to the end users only for their internal use. No part of this document nor any data herein may be published, disclosed, copied, reproduced, redistributed by any form or means, electronically or mechanically, or used for any other purpose whatsoever without the prior written approval of INTRACOM TELECOM. Information as well as drawings and specifications contained in this document are subject to change without prior notice. All trademarks and copyrights mentioned herein are the property of INTRACOM TELECOM and/or their respective owners. Any rights not expressly granted herein are reserved. Printed in Greece.

Page 3: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

i

Table of Contents

Chapter 1: Introduction.......................................................................................................................... 1 About this Document.............................................................................................1 Target Audience....................................................................................................1

Chapter 2: About IDR-C LCT ................................................................................................................. 2

Chapter 3: Basic Guidelines.................................................................................................................. 4 Screen Terminology..............................................................................................4 Conventions..........................................................................................................6 Common Actions...................................................................................................7

Chapter 4: Getting Started..................................................................................................................... 8 Installing the Management Application (IDR-C MASTER) ....................................9 Installing the Manufacturer Driver and creating a dial-up Connection to the IDR-C (Automatic Procedure) ........................................................................................10 Connecting the Local Craft Terminal to the IDR-C..............................................16 Launching the Application...................................................................................17 Upgrading the Application...................................................................................18 Getting connected to the IDR-C..........................................................................19 Setting the IDR-C Clock......................................................................................22 Configuring the IDR-C (Procedure Overview).....................................................23 Logging out .........................................................................................................24

Chapter 5: Configuring the IDR-C....................................................................................................... 25 Setting the Transmission/Reception Channel .....................................................25 Setting the transmitted Power.............................................................................26 Setting the RSSI Alarm Threshold ......................................................................27 Setting the ODU Temperature Alarm Threshold .................................................28 Enabling the ATPC Feature ................................................................................29 Deactivating the LOS Alarm for the unconnected Tributaries .............................30 Setting the Link Identification Number ................................................................31 Changing the Ethernet Communication ..............................................................32 Changing the IDR-C Capacity.............................................................................33 Changing the IDR-C Modulation .........................................................................33

Chapter 6: Monitoring the IDR-C......................................................................................................... 34 Monitoring the IDR-C Configuration ....................................................................34 Monitoring the Radio Measurements and Other ODU Information .....................36 Monitoring the IDR-C Version .............................................................................38 Optimizing the Link .............................................................................................40 Monitoring the Ethernet Link ...............................................................................41

Chapter 7: Monitoring the IDR-C Alarms ........................................................................................... 42 ODU Alarms........................................................................................................44 Framer/Modem/CI Alarms...................................................................................47 Mux Alarms.........................................................................................................48 Power Supply Alarms..........................................................................................49 Tributaries/Service Channels Alarms..................................................................50 Ethernet Alarms ..................................................................................................50 User Alarms Inputs/Outputs................................................................................51

Page 4: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

ii

Monitoring the History of Alarms ......................................................................................... 52 Changing the Alarms Attributes .......................................................................................... 55

Chapter 8: Service Calls ...................................................................................................................... 60 Changing the Station Call Id for a Service Call ...................................................60 Performing a Service Call ...................................................................................61

Chapter 9: Loopbacks, Performance Monitoring & Other Tests ..................................................... 62 Changing the Transmission and/or Reception Path............................................62 Loopbacks ..........................................................................................................64 Monitoring the Performance of the RF Link ........................................................67 Enabling the AIS Transmission at the Tributaries Outputs..................................69 Imposing SinCos Demodulation..........................................................................69

Chapter 10: Upgrading the IDR-C Firmware ...................................................................................... 70

Annex A: Installing the Manufacturer Driver at the LCT and creating a dial-up Connection to the IDR-C (Manual Procedure) ................................................................................................................... 72

Installing the Manufacturer Driver (Win 2000, XP).............................................................. 73 Creating a dial-up Connection to the IDR-C........................................................................ 81

Creating a dial-up Connection to the IDR-C (Win 2000) .....................................81 Creating a dial-up Connection to the IDR-C (Win XP) ........................................91

Annex B: Changing the Station Name, the Link Name and the Station IP Address.................... 102 IDR-C IP Addressing.........................................................................................102 Finding out the IP Address of your Station........................................................103 Changing the Station Name, the Link Name and the IP Address of your Station..........................................................................................................................104

Annex C: Example of Router Configuration .................................................................................... 108

Annex D: Default Alarms Attributes ................................................................................................. 110 1+0 Topology ....................................................................................................110 1+1 Topology ....................................................................................................111

Annex E: Changing the IDR-C Capacity and Modulation (for the advanced User only) ............. 112 Downloading the required Files to the CMS Unit ..............................................116 Updating the ODU Version ...............................................................................118

Page 5: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

1

Chapter 1: Introduction

About this Document

This document is a User Manual for INTRACOM’s IDR-C LCT (Local

Craft Terminal). The document informs the user how to use the LCT to configure and monitor the IDR-C. The document enables the audience that reads this manual to get familiar with the LCT and its operation.

Target Audience

This manual is intended for Radio Technicians with experience in the

operation of Radio Telecommunication Systems.

Page 6: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

2

Chapter 2: About IDR-C LCT

General You can use the IDR-C LCT to easily configure and monitor the IDR-C

at the local and the remote station. The user-friendly GUI of the application gives you the possibility to perform all the essential procedures concerning the configuration and monitoring of the IDR-C stations. Furthermore, you can use the LCT to type the appropriate IP addresses, to get connected, to monitor and configure up to 10 stations (i.e. 5 radio links) as shown in the following figure:

LCT

IDR-C IDR-C

1 2

IDR-C

3

IDR-C IDR-C IDR-C

1

10

5

. . . 98

Even if the IDR-C are interconnected as shown in the figure below, the total number of stations you can configure and monitor is still 10 (i.e. 5 links).

LCT

IDR-C IDR-C

1 2

IDR-C

3 65

IDR-C IDR-C IDR-C1

9

IDR-CIDR-C

4

IDR-CIDR-C

7 8 10

2

3

4

5

Note: Each time you can monitor and configure only a pair of IDR-C systems. Always consider as Home IDR-C the system of the pair closest to the LCT (yet not necessarily physically connected to it).

IDR-C ports The IDR-C has two asynchronous RS-232 ports (NMS1 and NMS2)

with baud rate 57600 bit/s for the connection of the LCT and the NMS and one virtual synchronous serial port (over the RF link). All three ports run RIP v2 and active PPP with PPP MTU size 400 bytes.

Continued on next page

Page 7: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

3

About IDR-C LCT, Continued

System files In the CMS unit of the IDR-C the following files that you may need

while working with the LCT of the IDR-C are stored: • alrm.nme & alrm.attr • boot.sys • config.sys • idrc_xxx.bin (where xxx is the version of the file) • idrc_xxx.mib (where xxx is the version of the file) • system.ini

Important Note: You are recommended to treat the aforementioned files with extreme care, only when required and provided you are an experienced user!

Page 8: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

4

Chapter 3: Basic Guidelines

Screen Terminology

Menu, Tab

When you click a tab, you open the corresponding tabbed sheet. Example: When you click ODU (and provided you are connected), the ODU tabbed sheet appears:

Box, Drop-down list, Alarm indication

Continued on next page

Tab Menu

Box

Drop-down list

Alarm Indication

Page 9: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

Screen Terminology, Continued

Group-box, Option button, Command button

Status bar

Commandbutton

Group-box

Optionbutton

Statusbar

IDR-C Clock

Your PC Clock

Local Station IP Address

Remote Station IP Address

5

Page 10: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

6

Conventions

Bold fonts In the document the bold fonts denote names of the following:

• Tabbed sheet • Group-box • Drop-down list • Command button • Menu • Menu command • Box • Indication Example: In the Radio Transmitter Power group-box, click EDIT.

Note: We also use bold fonts to emphasize something.

Italic fonts In the document, the italic fonts denote message text or text you type.

Example: In the File name box, type alrm.attr and click Save.

Page 11: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

7

Common Actions

Save configuration

After each configuration modification you make, on the System menu, point to Configuration, Home or Remote and select Save if you want to save the configuration of the local or the remote station respectively.

Page 12: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

8

Chapter 4: Getting Started

Getting started

To get started, follow the steps below:

Step Action

1 Install the management application (IDR-C MASTER) in the Local Craft Terminal (page 9).

2 Install the manufacturer driver in the Local Craft Terminal and create a dial-up connection between the Local Craft Terminal and the IDR-C of the station (page 9).

NOTE

Through the creation of the dial-up connection, the IDR-C assigns the LCT an IP address equal to the IDR-C station IP address + 1 (e.g. if the IDR-C station IP address is the 192.168.59.37, the LCT IP address will be the 192.168.59.38).

3 Connect the Local Craft Terminal to the IDR-C of the station (page 16).

4 Change the IP address of the station (page 102, Annex B: Changing the Station Name, the Link Name and the Station IP Address).

5 Repeat steps 2, 3 and 4 for all the IDR-C stations. 6 Launch the IDR-C MASTER (page 17). 7 Get connected to the IDR-C you want to configure (page

19). 8 Set the IDR-C clock (page 22). 9 Proceed to the configuration of the IDR-C (page 23).

Special case: IDR-C connected to a router

You can connect the NMS1 or NMS2 port of the IDR-C to an asynchronous serial interface of a router but you should configure the router serial interface baud rate fixed at 57600 bit/s and assign the router interface an IP address in the same subnet as the IDR-C which is not used in the IDR-C network. Example: If the IP address of the IDR-C is 192.168.59.5, assign the IP address 192.168.59.253 to the router serial interface (if you assign the IP address 192.168.59.6 to the router interface, the RIP will be deactivated for this port as the IDR-C considers it is an LCT and not a router port thus deactivating RIP transmissions). Find an example of a router configuration on page 108, Annex C: Example of Router Configuration.

NOTE

The only route the router needs to advertise towards the IDR-C stations is the default route. Please note that each station routing table can store up to 10 station routes (IDR-C stations) and one default route.

Page 13: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

9

Installing the Management Application (IDR-C MASTER)

Hardware and software requirements

To get connected to the IDR-C you want to monitor/configure you should fulfill the following platform requirements: • SP4 for Windows 2000 • SP1 or SP2 for Windows XP • Screen resolution 1024x768 • Serial port RS-232 with port speed 57600 bit/s

Installation procedure

To install the application, follow the steps below:

Step Action

1 Insert the IDR-C Operation CD-ROM in the disk drive. 2 Click Welcome. 3 In the Main Menu click Install Link Management (IDR-C

MASTER). The following window appears:

4 To install the application, follow the wizard instructions.

Page 14: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

10

Installing the Manufacturer Driver and creating a dial-up Connection to the IDR-C (Automatic Procedure)

Why to install the manufacturer driver

You need to install the manufacturer driver at your LCT because during the installation a virtual modem is created making possible the exchange of IP packets (needed by the LCT management application which is IP based) through the RS-232 ports of the LCT and the IDR-C.

Automatic Procedure

To install the manufacturer driver in the Local Craft Terminal and create a dial-up connection between the Local Craft Terminal and the IDR-C of the station, follow the steps below taking into consideration the following two Notes:

NOTE

Before proceeding to the automatic procedure, make sure the IDR-C and the LCT are not connected.

NOTE

In case of problems with the automatic procedure described below, refer to Annex A: Installing the Manufacturer Driver at the LCT and creating a dial-up Connection to the IDR-C (Manual Procedure) on page 72.

Step Action

1 Insert the IDR-C Operation CD-ROM in the disk drive. 2 Click Welcome. 3 In the Main Menu point to the Install Driver & Create Dial-

up Connection arrow. 4 In the submenu that appears click Win2K or Windows XP

depending on the Windows version of your LCT. 5 In the submenu that appears click Automatic Installation.

The following window appears:

Continued on next page

Page 15: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

11

Installing the Manufacturer Driver and creating a dial-up Connection to the IDR-C (Automatic Procedure), Continued

Automatic Procedure (continued)

Step Action 6 Click Install. The following window appears:

7 Select the Don’t detect my modem; I will select it from a list check box and click Next. The following window appears:

Continued on next page

Page 16: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

12

Installing the Manufacturer Driver and creating a dial-up Connection to the IDR-C (Automatic Procedure), Continued

Automatic Procedure (continued)

Step Action 8 Select the manufacturer and model of your modem and click

Next:

9 In the window that appears, select an available

communication port (e.g. COM1) and click Next:

Continued on next page

Page 17: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

13

Installing the Manufacturer Driver and creating a dial-up Connection to the IDR-C (Automatic Procedure), Continued

Automatic Procedure (continued)

Step Action 10 In the window that appears, click Yes (if you have Windows

2000) or click Continue Anyway (if you have Windows XP) to continue the installation:

Windows 2000

Windows XP

Continued on next page

Page 18: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

14

Installing the Manufacturer Driver and creating a dial-up Connection to the IDR-C (Automatic Procedure), Continued

Automatic Procedure (continued)

Step Action 11 When the installation is completed, the following window

appears. Click Finish.

Continued on next page

Page 19: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

15

Installing the Manufacturer Driver and creating a dial-up Connection to the IDR-C (Automatic Procedure), Continued

Automatic Procedure (continued)

Step Action 12 In the window that appears, click OK:

The following window appears:

Continued on next page

Page 20: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

16

Installing the Manufacturer Driver and creating a dial-up Connection to the IDR-C (Automatic Procedure), Continued

Automatic Procedure (continued)

Step Action 13 Click Reboot now. 14 After the rebooting completion, the following shortcut icon

appears on your desktop:

Windows 2000

Windows XP 15 Double-click the shortcut icon. The following window

appears:

16 After the completion of the process, the following icon in the

circle appears in the status bar:

Connecting the Local Craft Terminal to the IDR-C

Connection To connect the Local Craft Terminal to the IDR-C, follow the steps

below:

Step Action 1 Plug the one end of the cable into the NMS1 or the NMS2

receptacle of the IDR-C. 2 Plug the other end of the cable into the appropriate DB9

receptacle of the Local Craft Terminal.

Page 21: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

17

Launching the Application

Launching the application

To launch the application, double-click the application icon:

The Main Window of the application appears:

Page 22: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

18

Upgrading the Application

Version of the application

To find out the version of your currently installed software application, in the menu bar click About:

The following window appears:

Upgrading the Application

To upgrade the application, replace the old LCT_IDR_C.exe file with the new one.

Page 23: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

19

Getting connected to the IDR-C

Procedure To get connected to the IDR-C, follow the steps below:

Step Action 1 Open the SYSTEM tabbed sheet.

2 In the WAN-LAN Connections group box, from the Home IDR drop-down list select or type the IP address of the IDR-C you want to get connected to.

Note: All the IP addresses of the Home IDR drop-down list are stored in the last_ip.nmt file in the same folder with the management application. Do not delete this file otherwise you will lose the history of the IP addresses you have been connected to.

Continued on next page

Page 24: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

20

Getting connected to the IDR-C, Continued

Procedure (continued)

Step Action 3 Click Connect. When you get connected, the box of the

connection between the Host LCT and the Home IDR becomes green and the message Connected appears:

Note 1: If the IDR-C of the local station is connected to the IDR-C of the remote station through an RF link or through the management channel, the box of the connection between the Home IDR and the Remote IDR becomes green and the message Connected appears.

Note 2: If the following message appears, the IDU cannot communicate with the ODU.

In this case, follow the steps below:

Step Action 1 Press the reset button RST on the IDU front

panel to reset the IDU.

2 Open the ODU tabbed sheet. 3 Click Reset ODU to reset the ODU. 4 Wait for about 35 seconds for the

communication between the IDU and the ODU to be established.

Continued on next page

Page 25: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

21

Getting connected to the IDR-C, Continued

Getting connected to an IDR-C in a chain of 10 stations

You can use your LCT and get connected to an IDR-C even if your LCT is not physically connected to it. Supposing in the example below you want to configure and monitor the IDR-C 3 and the IDR-C 4. Perform the procedure mentioned before selecting or typing the IP address of the IDR-C 3 from the Home IDR drop-down list. In this case, your local station will be the IDR-C 3 and your remote station will be the IDR-C 4.

LCT

IDR-C IDR-C

1 2

IDR-C

3

IDR-C IDR-C IDR-C

1

10

5

. . . 98

Note: You can configure and monitor up to 10 stations or else 5 radio links. For more information, see also page 2.

Page 26: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

22

Setting the IDR-C Clock

Info With this setting, you synchronize the IDR-C clock to the LCT clock. It

is important to proceed to this setting so that the time of the alarms at the alarm history list will be correct.

When to make the setting

Set the IDR-C clock in the following cases: • When you configure the IDR-C for the first time • At the periodical maintenance of the station • If the IDR-C shuts down

Procedure To set the IDR-C clock, on the System menu click Set Time. In the

status bar, the System Time becomes equal to the PC Time.

Page 27: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

23

Configuring the IDR-C (Procedure Overview)

To configure the IDR-C, follow the steps below:

If, during the configuration or the operation of the IDR-C, you need to extract the Power Supply Unit or the Framer/Modem/CI Unit, make sure you only loosen and

not completely extract the Allen screw (shown with the arrow in the figure below)! If, by mistake, you completely extract the Allen screw, you will harm the right placement of the special metallic sheets and thus the passive system thermal loss!

Step Action 1 Set the transmission/reception channel (page 25). 2 Set the transmitted power (page 26). 3 Deactivate the LOS alarm for the unconnected tributaries

(page 30). 4 Set the link identification number (page 31). 5 In case of 1+1 topology, repeat steps 1,2 and 4 for the

second ODU. 6 Save the configuration you made (page 7). 7 Repeat steps 1 to 6 at the remote station. 8 Align the antennas of the two stations. 9 After the establishment of the link between the two stations,

proceed to the optimization of the link to achieve max RSSI level (page 38).

10 Set the RSSI and ODU temperature alarms thresholds for both the local and remote station (optional, pages 27 and 28).

11 Open the System tabbed sheet and confirm the link settings for both the local and the remote station (page 34).

12 Set the ATPC level and enable the ATPC feature (optional, page 29).

13 Open the different tabbed sheets and check if there are any alarm signals (page 42).

14 Save the modifications you made (page 7). 15 Log out of the application (page 24).

Page 28: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

24

Logging out

Prerequisites Before logging out of the application, make sure that you have

saved all your changes!

Logging out To log out of the application click the Exit button .

Page 29: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

25

Chapter 5: Configuring the IDR-C

Setting the Transmission/Reception Channel

Before making the setting

Before setting the transmission/reception channel, open the System tabbed sheet, click Home Config and check if the Channel Step value is half the Channel Size value.

If so, select the RF Channels Numbers as follows: 1, 3, 5, 7 etc. or 2, 4, 6, 8 etc. depending on the desired transmission frequency to avoid the existence of common frequencies between two different RF Channels Numbers!

Procedure To set the transmission/reception channel, follow the steps below:

Step Action 1 Open the ODU tabbed sheet. 2 Select between the following, the ODU whose

transmission/reception channel you want to set: • LOCAL ODU A • LOCAL ODU B • REMOTE ODU A • REMOTE ODU B

3 In the Radio Frequency group box, click EDIT.

Continued on next page

Page 30: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

26

Setting the Transmission/Reception Channel, Continued

Procedure (continued)

Step Action 4 From the RF Channel number drop-down list, select the

number of the RF transmission and reception channel. Notice the values of the Tx Frq. and Rx Frq. boxes change accordingly. Note: The total number of the drop-down list RF channels depends on the specific ODU channel bandwidth and the number of E1 tributaries the ODU should serve.

5 Click COPY to apply the setting. Notice how the colours of the RF Channel number drop-down list and the Tx Frq. and Rx Frq. boxes change.

Setting the transmitted Power

Procedure To set the transmitted power, follow the steps below:

Step Action 1 Open the ODU tabbed sheet. 2 Select between the following, the ODU whose transmitted

power you want to set: • LOCAL ODU A • LOCAL ODU B • REMOTE ODU A • REMOTE ODU B

3 In the Radio Transmitter Power group-box, click EDIT.

4 From the TX PWR (dbm) drop-down list, select the

transmitted power. 5 Click COPY to apply the setting.

Page 31: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

27

Setting the RSSI Alarm Threshold

Info If the reception level falls below the RSSI alarm threshold you set, an

alarm will be generated.

Procedure To set the RSSI alarm threshold, follow the steps below:

Step Action 1 Open the ODU tabbed sheet. 2 Select between the following, the ODU whose RSSI alarm

threshold you want to set: • LOCAL ODU A • LOCAL ODU B • REMOTE ODU A • REMOTE ODU B

2 In the Radio Thresholds group-box, click EDIT.

3 From the RSSI Thres. (dBm) drop-down list, select the

threshold. 4 Click COPY to apply the setting.

Note: In the Threshold Alarms group-box, the RSSI threshold alarm indication turns ON if the reception level falls below the RSSI alarm threshold you set.

Page 32: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

28

Setting the ODU Temperature Alarm Threshold

Info The internal temperature of the ODU is approximately 25 °C to 30 °C

higher than the environmental temperature. The ODU can work properly at an environmental temperature range –45 °C to +90 °C. The application permits you to set an upper temperature threshold. If the internal temperature of the ODU exceeds this threshold, an alarm will be generated.

Procedure To set the ODU temperature alarm threshold, follow the steps below:

Step Action 1 Open the ODU tabbed sheet. 2 Select between the following, the ODU whose temperature

alarm threshold you want to set: • LOCAL ODU A • LOCAL ODU B • REMOTE ODU A • REMOTE ODU B

3 In the Radio Thresholds group-box, click EDIT.

4 From the Upper Temp. Thres. (°C) drop-down list, select

the threshold. 5 Click COPY to apply the setting.

Note: In the Threshold Alarms group-box, the Temperature threshold alarm becomes red if the internal temperature of the ODU exceeds the alarm threshold you set.

Page 33: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

29

Enabling the ATPC Feature

Info When you enable the ATPC (Automatic Transmission Power Control)

feature, you make the transmitter at the local station adjust its output power so that the receiver at the remote station constantly receives the desired level you have set.

Procedure To enable the ATPC feature, follow the steps below:

Step Action 1 Open the System tabbed sheet. 2 Click Home Config or Remote Config. 3 From the ATPC (dBm) drop-down list, select the desired

reception level (dBm) of the remote station.

4 Click Enable ATPC to enable the ATPC feature. Notice the

led turns ON.

Page 34: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

30

Deactivating the LOS Alarm for the unconnected Tributaries

Why to deactivate the LOS alarm for the unconnected tributaries

Deactivate the LOS alarm for the unconnected (not cabled) tributaries for the ALM led, on the front panel of the IDU MUX Unit, to indicate real LOS when it occurs.

Note: The manufacturer provides the IDR-C with the LOS alarm activated for all the tributaries.

Procedure To deactivate the LOS alarm for an unconnected tributary, follow the

steps below:

Step Action 1 Open the Tributaries tabbed sheet. 2 Select between the following the quadrate of tributaries:

• Ho 1-4 • Re 1-4 • Ho 5-8 • Re 5-8 • Ho 9-12 • Re 9-12 • Ho 13-16 • Re 13-16

3

Click LOS to deactivate the LOS alarm for the specific tributary. After a while, the LOS Alarm Deactivated led turns on.

Page 35: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

31

Setting the Link Identification Number

Info The link identification number is a number in the range 0 to 15 the

operator selects through the LCT to identify in a unique way a link between a local and a remote IDR-C. The link identification number is extremely useful in cases of multiple links existing between two stations as it prevents the stations from demodulating data belonging to some other link if, by mistake, the stations lock into the frequency of this link.

Procedure To set the link identification number, follow the steps below:

Step Action 1 Open the Modem tabbed sheet. 2 Select between the following, the remote IDR-C modem

whose link id you want to set: • REMOTE A • REMOTE B

3 In the Link Id Configuration group-box, from the drop-down list select the link id you want in the range 0 to 15 and click Send Link Id. The link id you selected appears in the Framer Link Id box.

4 Select between the following, the local IDR-C modem whose

link id you want to set: • LOCAL A • LOCAL B

5 Repeat step 3 to set the same id. 6 Click Enable so that, in case the link id of the remote IDR-C

is other than the link id of the local IDR-C, an AIS alarm is enabled at the tributaries outputs. The led beside the Enable button becomes yellow.

Page 36: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

32

Changing the Ethernet Communication

Procedure Note: The Ethernet interface is by default configured (AUTO option

button) to negotiate with the corresponding port of the remote device concerning the rate (10 Mbit/s or 100 Mbit/s) and mode (half or full duplex) of communication. To change the default configuration of the Ethernet communication (i.e. the auto-negotiation, follow the steps below.

Step Action

1 Open the Ethernet tabbed sheet. 2 In the Ethernet Configuration Settings group-box, select

the appropriate option button depending on the rate and mode of communication you want to achieve.

3 Click Send Configuration to apply the setting.

Page 37: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

33

Changing the IDR-C Capacity

The manufacturer configures and provides the IDR-C with capacity

from 2 x E1 to 16 x E1 depending on the customer’s request. If you want to change the system capacity, refer to Annex E: Changing the IDR-C Capacity and Modulation (for the advanced User only) on page 112.

Changing the IDR-C Modulation

The manufacturer configures and provides the IDR-C with QPSK or

16QAM modulation depending on the customer’s request. If you want to change the system modulation, refer to Annex E: Changing the IDR-C Capacity and Modulation (for the advanced User only) on page 112.

Page 38: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

34

Chapter 6: Monitoring the IDR-C

Monitoring the IDR-C Configuration

To monitor the IDR-C configuration, open the System tabbed sheet

and then click Home Config or Remote Config if you want to monitor the local or the remote IDR-C configuration, respectively.

Group box Parameter Description

System Type • HOT STBY: the ODU A and B use the same RF Channel Number to transmit and receive providing radio redundancy.

• F.DIVERSITY: the ODU A and B use different RF Channel Numbers to transmit and receive providing radio redundancy.

• UNPROTECTED: 1+0 topology

System Capacity The number of tributaries the System serves.

Modulation The modulation/demodulation scheme of baseband signals. Can be QAM or QPSK.

Call Id The station phone number for a service call

Station Name The name of the station Link Name The name of the link IP Address The IP Address of the station

General

ATPC Drop-down list to select the ATPC reception level (dBm) of the remote station.

Continued on next page

Page 39: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

35

Monitoring the IDR-C Configuration, Continued

Group box Parameter Description Radio Type • xxC is the standard IDR-C

• xxCHP is the High Power IDR-C

where xx is the transmission frequency (GHz) of the IDR-C Note: This parameter is fully related to the Output Power Range Allowed (see further down in this table).

Radio Band The transmission band (High or Low) of the ODU A or B

Radio Tx The frequency (MHz) in which the ODU is transmitting at this moment.

Radio Rx The frequency (MHz) in which the ODU is receiving at this moment.

Start Frq The start frequency (MHz) of the ODU A or B transmission band

Stop Frq The stop frequency (MHz) of the ODU A or B transmission band

Output Power Range Allowed

The allowed range of the ODU A or B output power (dBm)

Channel Size The RF channel bandwidth (kHz)

Radio A or B

Channel Step How many kHz exist between two successive RF channel numbers.

Page 40: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

36

Monitoring the Radio Measurements and Other ODU Information

Radio measure-ments

To monitor the radio measurements, follow the steps below:

Step Action

1 Open the ODU tabbed sheet. 2 Select between the following the ODU whose radio

measurements you want to view: • LOCAL ODU A • LOCAL ODU B • REMOTE ODU A • REMOTE ODU B

3

Measurement Description Pif The power (dBm) of the Tx

IF signal

Rx In The ODU reception level (dBm)

Pout

The power (dBm) at the ODU output i.e. the transmission power

Temperature The temperature inside the ODU

+12 V, +6,5 V, +5 V, -12 V

The output voltages of the corresponding ODU internal power supply units

Continued on next page

Page 41: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

37

Monitoring the Radio Measurements and Other ODU Information, Continued

Other ODU information

Information Description ODU S/N The serial number of the ODU ODU Id The identification number of the ODU

fctx The central frequency (MHz) of the duplexer transmission filter

fcrx The central frequency (MHz) of the duplexer reception filter

bw The duplexer bandwidth (MHz) bm The duplexer bandwidth margin (MHz)

which is the margin between the duplexer bandwidth start frequency and the duplexer first fc.

Spectrum Inversion For manufacturer use only

Page 42: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

38

Monitoring the IDR-C Version

Info The application gives you the ability to monitor a great amount of

information concerning the version of the LCT application, the firmware version of the ODU, the versions of the mux, CMS, framer pcbs etc.

Procedure To monitor the IDR-C version, open the Versions tabbed sheet.

Group-box Field Description

LCT.Exe Version LCT Version The version of the LCT application file

ODU A ODU Versions ODU B

The firmware version of the ODU

PCB Version of the Mux pcb

MUX Versions

FPGA Version of the Mux FPGA

Continued on next page

Page 43: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

39

Monitoring the IDR-C Version, Continued

Group-box Field Description

BIN Version of the CMS bin file

PCB Version of the CMS pcb

FPGA Version of the CMS FPGA

CMS Type Type of the CMS

CMS Version

System.ini System.ini file FPGA Version of the

Framer/Modem FPGA

FPGA Mod./BitRate The code type of the Framer/Modem FPGA

PCB Version of the Framer/Modem pcb

FRAMER A or B Versions

TxIF The Tx IF frequency

Page 44: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

40

Optimizing the Link

Info To achieve reliable transmission in a microwave link, the transmitted

power plus the gain of the transmitter and receiver antennas should exceed the attenuation at the transmission path and the sensitivity of the receiver. The attenuation at the transmission path is given in the following formula:

A=92.4+20logD+20logF A is the attenuation at the transmission path in dB D is the distance between the antennas in km F is the frequency of the microwave signal in GHz

Prerequisites If you use the LCT to observe the reception level or the RSSI, you will

need another person to move the antenna.

Procedure To optimize the link, while performing minor horizontal and vertical

movements of the antenna, do one of the following: • Open the ODU tabbed sheet and check the reception level in the Rx

In box in the Radio Measurements group box:

• Open the IDR View tabbed sheet and check the reception level in

the Rx In box in the appropriate ODU Home group box:

Page 45: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

41

Monitoring the Ethernet Link

To monitor the Ethernet link, follow the steps below:

Step Action 1 Open the Ethernet tabbed sheet. 2 In the Ethernet Interface group-box, you monitor the

Ethernet link state. If the led Link is on, the Ethernet link is up.

Parameter Description Speed The current speed of the link. Can be

10 Mbps or 100 Mbps.

Duplex The current communication mode. Can be HALF or FULL.

AUTO Shows if the auto-negotiation between the IDR-C Ethernet interface and the corresponding port of the remote end is enabled (YES) or not (NO).

Page 46: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

42

Chapter 7: Monitoring the IDR-C Alarms

Monitoring the IDR-C alarms

To monitor the IDR-C alarms at the local or the remote station, follow the steps below:

Step Action

1 Open the IDR View tabbed sheet.

Item Description 1Q, 2Q, 3Q, 4Q Quadrate of tributaries Tloops Not used PS A, B Power Supply Units (lower and

upper)

EOW Engineering Order Wire MUX Multiplexer User I/O User Inputs/Outputs Mod. A, B Framer/Modem/Cable Interface Unit

(lower and upper)

IDU Indoor Unit ODU A, B Outdoor Unit

Continued on next page

Page 47: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

43

Monitoring the IDR-C Alarms, Continued

Step Action

2 Check if any of the blocks (units, paths, cable or RF links) appears red. If so, open the corresponding tabbed sheet to view the alarms detected. In the example below, you should open the Local and Remote Modem A and ODU A tabbed sheets. Find in the next paragraphs a full description of the alarms appearing in the different tabbed sheets.

Note 1: If the User I/O block appears red, open the System tabbed sheet and click Home or Remote I/O Status to view the alarms detected. Note 2: If the EOW block appears red, contact the manufacturer as the corresponding card should be replaced. Note 3: The red exclamation mark indicates the LCT cannot communicate with the corresponding ODU.

Note 4: The value in the Rx In box is the ODU reception level (dBm). The value in the PA Out box is the output power (dBm) of the transmitter. The red backround instead of the green one denotes alarm. For more details, see page 44.

Page 48: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

44

ODU Alarms

To monitor the ODU alarms, open the ODU tabbed sheet.

General Alarms

Alarm Generated when: Rx In The reception level falls below a threshold the

manufacturer has set for a reliable RF link performance. This threshold depends on the bit rate and the modulation type according to the following table:

Modulation Bit Rate (Mbit/s)

Threshold (dBm)

QPSK/SQPSK 2 x 2 -79 16QAM 4 x 2 -80

QPSK/SQPSK 4 x 2 -76 16QAM 8 x 2 -77

QPSK/SQPSK 8 x 2 -73 16QAM 16 x 2/E3 -74

QPSK/SQPSK 16 x 2/E3 -73 128QAM STM1 -64

The Rx In threshold alarm also appears in the IDR View tabbed sheet as follows. The value in the box is the current Rx In level (dBm) of the ODU.

PA Out There is no RF signal at the output of the ODU

Power Amplifier and consequently at the output of the ODU.

Continued on next page

Page 49: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

45

ODU Alarms, Continued

Threshold Alarms

Alarm Generated when: RSSI The reception level falls below the RSSI threshold

you have set (refer to page 27). Temperature The temperature inside the ODU exceeds the

threshold you have set (see page 28). Pif The power of the Tx IF signal falls below

–20 dBm. +5 V The output voltage of the ODU internal power

supply unit falls below +4,5 V. +6,5 V The output voltage of the ODU internal power

supply unit falls below +6 V. +12 V The output voltage of the ODU internal power

supply unit falls below +11 V. -12 V The output voltage of the ODU internal power

supply unit falls below –11 V.

Continued on next page

Page 50: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

46

ODU Alarms, Continued

Radio Locks Alarms

Alarm Generated when: LD DDS

(Lock Detect Digit Direct

Synthesizer)

The Digit Direct Synthesizer is unlocked with consequence no RF signal at the Power Amplifier output and the generation of the PA Out alarm. Contact the manufacturer for ODU replacement.

LD Lback (Lock Detect Loopback)

The Loop Back Synthesizer is unlocked. This alarm can be generated during the RF loopback test (ODU LOOP command button of the LOCAL ODU tabbed sheet). The ODU LOOP command activates the Loop Back Synthesizer which loops the Tx signal in the Rx path.

LD MW Not used

LD RX (Lock Detect

Rx) The Rx Synthesizer is unlocked.

LD TX (Lock Detect

Tx)

The Tx Synthesizer is unlocked with consequence no RF signal at the Power Amplifier output and the generation of the PA Out alarm as well. Contact the manufacturer for ODU replacement.

Page 51: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

47

Framer/Modem/CI Alarms

FRAMER/ MODEM/CI Alarms

To monitor the Framer/Modem/CI Unit alarms, open the Modem tabbed sheet.

Alarm Generated when:

Tx PLL

The Tx Synthesizer of the Framer/Modem/Cable Interface Unit is unlocked. Check the Framer/Modem/Cable Interface Unit of the other path and if the problem persists, contact the manufacturer for card replacement.

Rx PLL The Rx Synthesizer of the Framer/Modem/Cable Interface Unit is unlocked.

BER3 BER ≥ 10-3

BER6 BER ≥ 10-6

Dmod (Demodulator

Alarm)

The Modem cannot demodulate the carrier information.

LFA (Lost Frame Alignment

Alarm)

The alignment of the frame has been lost.

TxIF A hardware error has occurred in the card. Contact the manufacturer for card replacement.

LnkId (Link

Identification Alarm)

The Framer/Modem/Cable Interface Unit cannot recognize the Identification Number of the link.

Page 52: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

48

Mux Alarms

To monitor the Mux alarms, open the Mux tabbed sheet.

Alarm Generated when: LOS CLK A

Path (Loss of Signal Clock A Path)

The clock coming from the Framer/Modem/CI Unit A has been lost. Consequently, the hitless switching cannot be performed.

LOS CLK B Path

(Loss of Signal Clock B Path)

The clock coming from the Framer/Modem/CI Unit B has been lost. Consequently, the hitless switching cannot be performed.

FIFO A A hardware error has occurred in the A path in the card. Contact the manufacturer for card replacement.

FIFO B A hardware error has occurred in the B path in the card. Contact the manufacturer for card replacement.

LOS Align (Loss of Signal

Align)

The synchronization between the signals coming from the demodulators A and B has been lost. Consequently, the hitless switching cannot operate properly.

SYNC (Synchroniza-

tion)

The frame coming from the Framer/Modem/CI Unit has been lost or has BER ≥ 10-6.

RAI (Remote Alarm

Indication)

The remote station cannot receive the signal transmitted or receives it with BER ≥ 10-6. As a consequence, the remote station sends the RAI alarm to the local station.

Page 53: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

49

Power Supply Alarms

To monitor the Power Supply alarms, open the Power Supply tabbed

sheet.

Alarm Generated when: Power Supply

Alarm There is no input voltage at the Power Supply Unit.

Card Extracted Card extracted

Page 54: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

50

Tributaries/Service Channels Alarms

To monitor the Tributaries or the Service Channels alarms, open the

Tributaries tabbed sheet.

Alarm Generated when:

IN AIS

The AIS pattern (all ones sequence) is applied at the specific tributary input.

Note: When no AIS is applied at the input, the optical indication is green.

LOS (Loss of Signal) There is no signal at the specific tributary input.

Note: To monitor the service channels alarms, click the Service Channels tab in the Tributaries tabbed sheet.

Ethernet Alarms

To monitor the Ethernet alarms, open the Ethernet tabbed sheet.

Alarm Generated when: SYNC

(Synchroniza-tion)

The MUX in the local station is not locked in the incoming MUX frame.

RAI (Remote Alarm

Indication)

The MUX in the remote station is not locked in the incoming MUX frame.

Page 55: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

51

User Alarms Inputs/Outputs

The AUX connector on the front panel of the IDU CMS provides four

user alarms inputs and four user alarms outputs. In the inside of the system, as soon as an alarm input/output appears at the pin of the connector, a micro-switch connects or disconnects the pin of this alarm input/output and the input/output GND. To monitor the indications of the user alarms inputs and outputs, open the System tabbed sheet and then click Home I/O Status or Remote I/O Status depending on which you want to monitor. If you want to change the alarms names (UserInput_1 etc. ) with other more convenient names (e.g. Station Door Open), see par. “Changing the Alarms Attributes” on page 55.

Page 56: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

52

Monitoring the History of Alarms

Info The application gives you the ability to monitor the history of alarms

that were generated in the system. More specifically, you can select to monitor the last 20 or 50 alarms or you can select to monitor all the alarms (up to 999). When you select to monitor the alarms, the system creates a text type alarm log file with the name Log_<date>. When you close the management application, the system saves this alarm log file in the LCT in the same folder with the management application. Note: Do not delete the alarm log file as the manufacturer may request it in case of troubleshooting. The manufacturer provides the system with a list of alarms with default name, severity and polarity. He has also set which alarms will appear at the users outputs and which alarms will be logged. Although the application gives you the ability to change these attributes, you are recommended to wait until you become an experienced operator of the system.

Monitoring the history of alarms

To monitor the history of alarms, follow the steps below:

Step Action

1 On the System menu, point to Alarm Log, then point to Activation, and then select one of the following: • Last 20 if you want to monitor the last 20 alarms • Last 50 if you want to monitor the last 50 alarms • All if you want to monitor all the alarms (the application

can log up to 999 alarms)

Continued on next page

Page 57: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

53

Monitoring the History of Alarms, Continued

Step Action

2

Attribute Description Count Alarm counting number

The most recent alarm appears at the end of the list. Up to 999 alarms can appear in the list. On receipt of the 1000th alarm, the oldest alarm is automatically deleted and the new alarm appears at the end of the list.

Time Time and day (according to the IDR-C clock) the alarm was generated.

State • ON: the alarm is enabled. • OFF: the alarm is disabled.

Continued on next page

Page 58: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

54

Monitoring the History of Alarms, Continued

Step Action

Severity The alarm severity • Minor • Major

Polarity • Normal is the Normal Open (default). With this setting, as soon as an alarm appears at the input/output pin of the AUX connector, the micro-switch in the internal of the system connects this alarm input/output pin to the alarm input/output GND of the connector.

• Reverse is the Normal Close. As soon as an alarm appears at the input/output pin of the AUX connector, the micro-switch in the internal of the system disconnects this alarm input/output pin from the alarm input/output GND of the connector.

Output The alarm input/output at the AUX connector

Name The alarm name

Page 59: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

55

Changing the Alarms Attributes

Info The alarms attributes are recorded in the alrm.nme and alrm.attr files

stored in the CMS Unit. If you want to change the alarm attributes, you should upload these files from the CMS Unit, make the changes you want, delete the old files from the CMS Unit and then download the new files to the CMS Unit.

Note: Although the application gives you the ability to change the alarms attributes, you are recommended not to do this unless you are an experienced user.

Default alarms attributes

See Annex D.

Changing the alarms attributes

To change the alarms attributes, follow the steps below:

Step Action

1 Create two folders. You will use the one folder to store the current alrm.nme and alrm.attr files of the CMS unit and the other folder to store the new alrm.nme and alrm.attr files you will create.

2 On the System menu, select FTP Tool. The following window appears:

Continued on next page

Page 60: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

56

Changing the Alarms Attributes, Continued

Step Action

3 In the Host box, type the address of the IDR-C from which you want to upload the alrm.nme and alrm.attr files and click FTP Connection. In the Files list (NMU) list, the current files of the CMS Unit appear.

4 From the Files list (Local) list, select the folder where you want to move the alrm.nme and alrm.attr files.

5 From the Files list (NMU) list, select the alrm.nme file and click Upload from NMU.

6 Browse the folder to which you want to move the file and click Save.

7 In the window that appears, click OK to confirm the uploading.

8 Repeat steps 5, 6 and 7 for the alrm.attr file. 9 Click Close FTP. 10 On the System menu, point to Alarm Log, and then select

Alarm Tool.

11 On the File menu of the Alarm Tool window, select Open to open the alrm.nme and alrm.attr files.

12 Open the appropriate tabbed sheet. The current attributes appear.

13 In the Alarm Name box, type the new name of the alarm.

Continued on next page

Page 61: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

57

Changing the Alarms Attributes, Continued

Step Action 14 From the Severity drop-down list, select the severity of the

alarm between Minor and Major. 15 From the Polarity drop-down list, select the polarity of the

alarm at the user output between Normal and Reverse taking into consideration the following Note: Note: You are recommended not to change the polarity unless this alarm appears at the user output and you want to change the default status of the alarm (Normal Open which is the default or Normal Close).

16 Select the Output check box if you want the alarm to appear at the user output.

17 Select the Logged check box if you want the alarm to be stored in the alarm log file and thus appear in the alarms history list.

18 Repeat for as many alarms as needed. 19 Click OK. 20 On the File menu of the Alarm Tool window, select Save.

The following window appears:

21 Select the folder you have created in step 1 for the new files.

Continued on next page

Page 62: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

58

Changing the Alarms Attributes, Continued

Step Action 22 In the File name box, type alrm.nme and click Save. The

following window appears:

23 In the File name box, type alrm.attr and click Save. 24 On the File menu of the Alarm Tool window, select Exit. 25 On the System menu, select FTP Tool. The following

window appears:

26 In the Host box, type the address of the IDR-C to which you want to download the new alrm.nme and alrm.attr files and click FTP Connection.

27 From the File list (NMU) list, select the alrm.nme and alrm.attr files and click Delete from NMU to delete them.

Continued on next page

Page 63: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

59

Changing the Alarms Attributes, Continued

Step Action 28 From the Files list (Local) list, select the alrm.nme and

alrm.attr files you created and click Download to NMU. 29 Click Close FTP. 30 On the System menu, select Sys Restart to activate the

new files or press the RST button on the front panel of the IDU CMS Unit.

Page 64: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

60

Chapter 8: Service Calls

Changing the Station Call Id for a Service Call

Procedure To change the Station Call Id number, follow the steps below:

Step Action 1 On the System menu click Call ID Change. The following

window appears:

2 From the New Call Id drop-down list in the Home Terminal

Call Id group-box or/and in the Remote Terminal Call Id group-box, select the new Call Id of the local station or/and the remote station respectively. The available range is 0 to 99.

3 In the group-box(es) you changed the Call Id, click Apply to apply the new Call Id.

4 On the System menu, point to Configuration, Home or Remote and select Save to save the new Call Id.

5 Click Close to close the window.

Note: You do not need to reset the IDR-C for the change to apply.

Page 65: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

61

Performing a Service Call

Prerequisites • To perform a service call to the remote station, you should know its

Call Id number. If you do not know the number, open the System tabbed sheet, click Remote Config and view the value of the Call Id in the General group-box.

• For the local and remote stations to be able to communicate through a service call, you should have connected the handsets to the local and remote stations IDUs.

Performing a selective service call

To perform a service call to the remote station, hook-off the handset, press #, dial the Call Id number of the remote station and then press *.

Performing a general service call

To perform a service call to all the stations of the NMS network, press #, then press 0 and then press *.

Page 66: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

62

Chapter 9: Loopbacks, Performance Monitoring & Other Tests

Changing the Transmission and/or Reception Path

When to change the default selection

Change the default selection (auto) if you want to set free of traffic a path for service purposes (e.g. you will select to transmit and receive through the A path if you want to perform measurements on the B path). In this case, the hitless switching and thus the radio redundancy will not operate.

Procedure To change the transmission and/or reception path, follow the steps

below:

Step Action 1 Open the IDR View tabbed sheet.

2 Click the appropriate option button to select the transmission

and/or the reception path.

Continued on next page

Page 67: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

63

Changing the Transmission and/or Reception Path, Continued

Note 1: With the default selection (auto option button clicked), you allow the system to select the transmission and/or reception path. The system makes the selection according to the voltages Pif, Rx In and Pout levels of the Radio Measurements group box and according to the detection or not of the following alarms: • Alarms for the transmission path

• PA OUT • LD DDS • LD TX • RAI

• Alarms for the reception path

• RSSI • LD DDS • LD Rx • BER3 • BER6

Note 2: You can select the transmission and/or reception path by opening the MUX tabbed sheet as well.

Page 68: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

64

Loopbacks

Info The application gives you the ability to perform the following

loopbacks:

• LLOOP: Line Loop (Local and Remote Station) • DLOOP: Digital Loop (Local Station) • ODU LOOP (Local Station) • RLOOP: Radio Loop (Local and Remote Station) The following figure represents the above mentioned loopbacks graphically:

RF Link

LocalODU

LocalMux

LocalFramer/Modem/

CI

LLOOP DLOOPRLOOP ODU LOOP

RemoteODU

RemoteMux

RemoteFramer/Modem/

CI

LLOOPDLOOP RLOOPODU LOOP

Loopbacks order

You are recommended to perform the loopbacks in the following order:

Step Action

1 LLOOP 2 DLOOP 3 ODU LOOP 4 RLOOP

Performing the LLOOP

To perform the LLOOP, follow the steps below:

Step Action

1 Open the Tributaries tabbed sheet. 2 Click LLOOP in the Tributaries Control group-box of the

tributary you want to test:

Continued on next page

Page 69: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

65

Loopbacks, Continued

Performing the DLOOP

To perform the DLOOP, follow the steps below:

Step Action

1 Open the Modem tabbed sheet. 2 Click DLOOP in the Control group-box of the

Framer/Modem/CI Unit you want to test:

Performing the ODU LOOP

To perform the ODU LOOP, follow the steps below taking into consideration the following important Note:

Important Note: Switch-off the remote station and then proceed to the ODU LOOP!

Step Action

1 Open the ODU tabbed sheet. 2 In 1+1 topology, in the Radio Control group-box, click ODU

MUTE to mute the ODU you don’t want to test (e.g. if the ODU A seems to have problems and you want to test it, mute the ODU B).

Continued on next page

Page 70: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

66

Loopbacks, Continued

Performing the ODU LOOP (continued)

Step Action 3 Open the MUX tabbed sheet and change the transmission

and reception path accordingly (e.g. continuing the example of step 2, click the A options buttons in the TxSW and RxSW group-boxes).

4 Click ODU LOOP in the Radio Control group-box of the

ODU you want to test:

Performing the RLOOP

To perform the RLOOP, follow the steps below:

Step Action

1 Open the Tributaries tabbed sheet. 2 Click RLOOP in the Tributaries Control group-box of the

tributary you want to test:

Page 71: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

67

Monitoring the Performance of the RF Link

Info You can monitor the performance of the RF link by performing the

G.826 block error analysis test (ITU-T Recommendation G.826: “End-to-end error performance parameters and objectives for international, constant bit-rate digital paths and connections”).

Performing the G.826 test

To perform the G.826 test, follow the steps below:

Step Action

1 Open the System tabbed sheet. 2 Click Home G826. The following window appears:

Continued on next page

Page 72: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

68

Monitoring the Performance of the RF Link, Continued

Performing the G.826 test (continued)

Step Action 3 If the Test Running led is on, click STOP TEST and then

click START TEST otherwise click START TEST. Wait a few milliseconds for the internal error counters to reset. Then the test starts. Find below the description of the error performance parameters (according to G.826):

Parameter Description ES Errored Second, a one-second

period with one or more errored or lost blocks

SES Severely Errored Second, a one-second period which contains ≥ 30 % errored blocks or at least one defect; one-second period which has a bit error ratio ≥ 10-3 or during which Loss of Signal or Alarm Indication Signal is detected; SES is a subset of ES.

BBE Background Block Error, an errored block not occurring as part of a SES.

Unavailable Time The Unavailable Time (s) starts when 10 consecutive severely errored seconds have been detected. These 10 seconds are part of the Unavailable Time. If a bidirectional path is considered, the Unavailable Time is if one or both directions are unavailable.

Available Time The Available Time (s) starts after 10 consecutive non-SES seconds have passed.

Total Time Unavailable Time + Available Time

Page 73: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

69

Enabling the AIS Transmission at the Tributaries Outputs

Open the Mux tabbed sheet and then click Toggle AIS to enable

(default) / disable the AIS transmission at the tributaries outputs in case of RF link failure so that if there are systems connected to the IDR-C, they will continue to be synchronized with it. The led turns on if you have enabled the AIS transmission.

Imposing SinCos Demodulation

Open the Modem tabbed sheet and then click SinCos to interrupt the

QAM or QPSK demodulation and impose the SinCos demodulation. Then you will be able to check the central transmission frequency fc during laboratory testing.

Page 74: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

70

Chapter 10: Upgrading the IDR-C Firmware

Prerequisite The manufacturer provides you an xxx.bin file with the new IDR-C

firmware.

Procedure To upgrade the IDR-C firmware, follow the steps below:

Step Action 1 Launch the LCT application. 2 Get connected to the IDR-C. 3 On the System menu, select FTP Tool. The following

window appears:

4 In the Host box type the IP address of the IDR-C you want to change the firmware and click FTP Connection to get connected.

5 In the Files list (Local) select the IDR-C firmware upgrading file (xxx.bin) and click Download to NMU.

6 After the downloading procedure has been completed, in the Files list (NMU) select the config.sys and the boot.sys files and click Upload from NMU.

7 In the Files list (Local) select the folder in which you want to save the two files. Pay attention not to select the folder where the config.sys and boot.sys files of Windows are saved because if you do so, the Windows files will be overwritten by the NMU files.

8 Use a text editor to open the two files and change the name of the xxx.bin file with the new one.

Continued on next page

Page 75: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

71

Upgrading the IDR-C Firmware, Continued

Procedure (continued)

Step Action 9 Save the files. 10 From the Files list (NMU) list, delete the current config.sys

and boot.sys files. 11 From the Files list (Local) list, select the new config.sys file

and click Download to NMU. Do the same for the new boot.sys file.

12 To activate the new files, do one of the following to reset the IDR-C: • On the System menu, select Sys Restart. • Press the RST button on the front panel of the IDU CMS

Unit. • Switch-off and on again the IDR-C PSU(s).

Page 76: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

72

Annex A: Installing the Manufacturer Driver at the LCT and creating a dial-up Connection to the IDR-C (Manual

Procedure)

Why to install the manufacturer driver

You need to install the manufacturer driver at your LCT because during the installation a virtual modem is created making possible the exchange of IP packets (needed by the LCT management application which is IP based) through the RS-232 ports of the LCT and the IDR-C.

When to perform the procedure

You need to install the manufacturer driver at your LCT and create a dial-up connection to the IDR-C of the station before launching the IDR-C management application (IDR-C MASTER) and getting connected to the IDR-C.

Page 77: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

73

Installing the Manufacturer Driver (Win 2000, XP)

Accessory CD with the manufacturer driver (provided)

Procedure To install the manufacturer driver at your LCT, follow the steps below:

Step Action 1 Select Start > Settings > Control Panel > Phone and

Modem Options. The following window appears:

Continued on next page

Page 78: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

74

Installing the Manufacturer Driver (Win 2000, XP), Continued

Step Action

2 Open the Modems tabbed sheet. The following window appears:

Continued on next page

Page 79: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

75

Installing the Manufacturer Driver (Win 2000, XP), Continued

Step Action

3 Click Add. The following window appears:

4 Select the Don’t detect my modem; I will select it from a list check box and click Next. The following window appears:

Continued on next page

Page 80: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

76

Installing the Manufacturer Driver (Win 2000, XP), Continued

Step Action

5 Click Have Disk….The following window appears:

6 From the drop-down list select the CD disk drive, click Browse, select the nmudirwin2000.inf file (if you have Windows 2000) or the directxp.inf file (if you have Windows XP), click Open and then OK. The following window appears:

Continued on next page

Page 81: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

77

Installing the Manufacturer Driver (Win 2000, XP), Continued

Step Action

7 Select the model and click Next. The following window appears:

Continued on next page

Page 82: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

78

Installing the Manufacturer Driver (Win 2000, XP), Continued

Step Action

8 Select an available communication port (e.g. COM1) and click Next. The following window appears:

Windows 2000

Windows XP

9 Click Yes (if you have Windows 2000) or click Continue Anyway (if you have Windows XP) to continue the installation.

Continued on next page

Page 83: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

79

Installing the Manufacturer Driver (Win 2000, XP), Continued

Step Action 10 When the installation is completed, the following window

appears:

Continued on next page

Page 84: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

80

Installing the Manufacturer Driver (Win 2000, XP), Continued

Step Action 11 Click Finish. The following window appears:

12 Click OK.

Page 85: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

81

Creating a dial-up Connection to the IDR-C

Creating a dial-up Connection to the IDR-C (Win 2000)

Prerequisite Before proceeding to the creation of the dial-up connection, you

should first have installed the driver provided by the manufacturer at your LCT.

Procedure To create a dial-up connection between the LCT and the IDR-C, follow

the steps below:

Step Action 1 Select Start > Settings > Control Panel > Network and

Dial-up Connections > Make New Connection. The following window appears:

Continued on next page

Page 86: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

82

Creating a dial-up Connection to the IDR-C (Win 2000), Continued

Step Action

2 Click Next. The following window appears:

3 Click the Connect directly to another computer option button and then click Next. The following window appears:

Continued on next page

Page 87: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

83

Creating a dial-up Connection to the IDR-C (Win 2000), Continued

Step Action

4 Click the Guest option button and then click Next. The following window appears:

5 Select the virtual modem you created during the installation of the PPP driver and click Next. The following window appears:

Continued on next page

Page 88: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

84

Creating a dial-up Connection to the IDR-C (Win 2000), Continued

Step Action

6 Click the For all users option button and click Next. The following window appears:

7 Type the name you want to use for this connection (e.g. CMS) and click Finish. The following window appears:

Continued on next page

Page 89: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

85

Creating a dial-up Connection to the IDR-C (Win 2000), Continued

Step Action

8 Leave the User name and Password boxes empty and click Properties. The following window appears:

Continued on next page

Page 90: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

86

Creating a dial-up Connection to the IDR-C (Win 2000), Continued

Step Action

9 From the Select a device drop-down list, select the virtual modem you created during the installation of the manufacturer driver and click Configure. The following window appears:

Continued on next page

Page 91: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

87

Creating a dial-up Connection to the IDR-C (Win 2000), Continued

Step Action 10 From the Maximum speed drop-down list select 57600.

Make sure that all the check boxes are not selected. Click OK. The following window appears:

Continued on next page

Page 92: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

88

Creating a dial-up Connection to the IDR-C (Win 2000), Continued

Step Action 11 Open the Options tabbed sheet and select the Display

progress while connecting check box:

12 Click OK. The following window appears:

Continued on next page

Page 93: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

89

Creating a dial-up Connection to the IDR-C (Win 2000), Continued

Step Action 13 When the connection to the IDR-C is created, the following

window appears:

14 Double-click the icon of the connection in the status bar:

The following window appears:

Continued on next page

Page 94: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

90

Creating a dial-up Connection to the IDR-C (Win 2000), Continued

Step Action 15 Open the Details tabbed sheet to view details concerning

the connection:

Page 95: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

91

Creating a dial-up Connection to the IDR-C (Win XP)

Prerequisite Before proceeding to the creation of the dial-up connection, you

should first have installed the driver provided by the manufacturer at your LCT.

Procedure To create a dial-up connection between the LCT and the IDR-C, follow

the steps below:

Step Action 1 Select Start > Settings > Control Panel > Network

Connections. In the Network Tasks pane of the window that appears click Create a new connection:

The following window appears:

Continued on next page

Page 96: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

92

Creating a dial-up Connection to the IDR-C (Win XP), Continued

Step Action

2 Click Next. The following window appears:

3 Click the Set up an advanced connection option button and then click Next. The following window appears:

Continued on next page

Page 97: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

93

Creating a dial-up Connection to the IDR-C (Win XP), Continued

Step Action

4 Click the Connect directly to another computer option button and then click Next. The following window appears:

5 Click the Guest option button and then click Next. The following window appears:

Continued on next page

Page 98: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

94

Creating a dial-up Connection to the IDR-C (Win XP), Continued

Step Action

6 In the Computer Name box, type the name you want to use for this connection (e.g. CMS) and click Next. The following window appears:

7 From the Select a device drop-down list, select the virtual

modem you created during the installation of the manufacturer driver and click Next. The following window appears:

Continued on next page

Page 99: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

95

Creating a dial-up Connection to the IDR-C (Win XP), Continued

Step Action

8 Select the Add a shortcut to this connection to my desktop check box if you want a shortcut and then click Finish. The following window appears:

Continued on next page

Page 100: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

96

Creating a dial-up Connection to the IDR-C (Win XP), Continued

Step Action

9 Leave the User name and Password boxes empty and click Properties. The following window appears:

Continued on next page

Page 101: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

97

Creating a dial-up Connection to the IDR-C (Win XP), Continued

Step Action 10 From the Select a device drop-down list, select the virtual

modem you created during the installation of the manufacturer driver and click Configure. The following window appears:

Continued on next page

Page 102: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

98

Creating a dial-up Connection to the IDR-C (Win XP), Continued

Step Action 11 From the Maximum speed drop-down list select 57600.

Make sure that all the check boxes are not selected. Click OK. The following window appears:

Continued on next page

Page 103: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

99

Creating a dial-up Connection to the IDR-C (Win XP), Continued

Step Action 12 Open the Options tabbed sheet and select the Display

progress while connecting check box if not selected. Leave the other check boxes unselected:

13 Click OK. The following window appears:

Continued on next page

Page 104: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

100

Creating a dial-up Connection to the IDR-C (Win XP), Continued

Step Action 14 When the connection to the IDR-C is created, the following

window appears:

15 Double-click the icon of the connection in the status bar:

The following window appears:

Continued on next page

Page 105: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

101

Creating a dial-up Connection to the IDR-C (Win XP), Continued

Step Action 16 Open the Details tabbed sheet to view details concerning

the connection:

Page 106: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

102

Annex B: Changing the Station Name, the Link Name and the Station IP Address

IDR-C IP Addressing

Each station with an IDR-C system is assigned an IP address so that it

can be identified in a network. The IP address of each station has to be unique in the network to which the station belongs. You can use the LCT, type the appropriate IP addresses and get connected, monitor and configure up to 10 stations. All stations should belong to the same subnet with subnet mask 255.255.255.0 As four IP addresses should be reserved for each station (the IDR-C station address, the broadcast address, the network address and the LCT address assigned to the LCT through the creation of the dial-up connection between the LCT and the IDR-C), the IP address of the station should have the following format: A.B.C.D/30 with D=4n+1 where n is an integer from 1 to 62. See below an example of IP addressing:

Station IP Address Station 1 192.168.59.5 Station 2 192.168.59.9 Station 3 192.168.59.13 Station 4 192.168.59.17

… … Station 10 192.168.59.41

Page 107: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

103

Finding out the IP Address of your Station

Prerequisite Before proceeding to the procedure, you should create a dial-up

connection between your LCT and the IDR-C.

Procedure To find the IP address of your station, follow the steps below:

Step Action 1 Double-click on the icon of the dial-up connection that you

created for the communication of your LCT with the IDR-C. 2 Select Start>Run. 3 In the Open box, type command (Windows 2000 or XP). In

the DOS prompt, type ipconfig.

You view the IP address of your LCT.

4 To find the IP address of the station, reduce the IP address of your LCT by one. In the example, the IP address of the station is 192.168.59.37

Page 108: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

104

Changing the Station Name, the Link Name and the IP Address of your Station

Info The name of the link and the name and IP address of the station are

stored in the config.sys file that is kept in the CMS card of each station. The IP address of the station is also stored in the boot.sys file of the system. If you want to change the IP address of a station, you should change the contents of the boot.sys and config.sys files accordingly. If you want to change the link name and the station name, you should change the contents of the config.sys file.

Prerequisite Before proceeding to the procedure, you should create a dial-up

connection between your LCT and the IDR-C.

Procedure To change the link name and the name and IP address of a station,

follow the steps below:

Step Action 1 Upload the config.sys and boot.sys files from the IDR-C to

your LCT. 2 With a text editor open the files and change the name of the

link and the name and IP address of the station. 3 Delete the old config.sys and boot.sys files from the IDR-C. 4 Download the modified files from your LCT to the IDR-C. 5 Reset the IDR-C.

Find the detailed description of the preceding steps in the following paragraphs.

Continued on next page

Page 109: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

105

Changing the Station Name, the Link Name and the IP Address of your Station, Continued

Uploading from IDR-C

To upload the config.sys and boot.sys files from the IDR-C to your LCT, follow the steps below:

Step Action

1 Create a folder in the disk of your LCT (e.g. idrc). 2 Double-click on the icon of the dial-up connection that you

created for the communication of the local terminal with the IDR-C.

3 Select Start>Run and type command in the Open box. 4 At the DOS prompt, type FTP xxx where xxx is the current

IP address of the station, and then press ENTER. 5 Type the username and the password, and then press

ENTER. By default, the username is aris and the password is akand.

6 Type lcd dirname where dirname is the name of the folder you created (e.g. lcd c:\idrc), and then press ENTER.

7 Type get config.sys, and then press ENTER to upload the config.sys file from the IDR-C to the folder of the LCT.

8 Type get boot.sys, and then press ENTER to upload the boot.sys file from the IDR-C to the folder of the LCT.

9 Type bye, and then press ENTER to return to the DOS prompt.

10 Type exit, and then press ENTER to return to Windows.

Continued on next page

Page 110: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

106

Changing the Station Name, the Link Name and the IP Address of your Station, Continued

Editing the config.sys and boot.sys files

To edit the config.sys and boot.sys files, follow the steps below:

Step Action

1 With a text editor open the config.sys and boot.sys files. The file format will be similar to the one below (depending of course on the frequency and the type of the station): • The config.sys file boot id180203.bin 0xa000400 MANAGER_IPADDRESS 146.124.12.75 MANAGER_PORT 16205 MY_IPADDRESS 192.168.50.31 SUBNET_MASK 255.255.255.252 lnkname LowSyst The station name sysname Intracom The Link name systype 1 1+1 • The boot.sys file boot id180203.bin 0xa000400 MANAGER_IPADDRESS 146.124.12.75 MANAGER_PORT 16205 MY_IPADDRESS 192.168.50.31 SUBNET_MASK 255.255.255.252

2 In both files, replace the IP address next to the MY_IPADDRESS record with the new one. Note: If you want, you can also change the name of the station that appears on the display of the CMS and the name of the link. To do so, in the sixth line of the config.sys file, change the name of the station from the LowSyst of the example to the one you want to appear on the display of the CMS. In the seventh line of the config.sys file, change the name of the link from Intracom of the example to the one you want.

3 Save the config.sys and boot.sys files and close the text editor.

Continued on next page

Page 111: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

107

Changing the Station Name, the Link Name and the IP Address of your Station, Continued

Downloading to IDR-C

To download the config.sys and boot.sys files from the LCT to the IDR-C, follow the steps below:

Step Action

1 Select Start>Run and type command in the Open box. 2 At the DOS prompt, enter FTP xxx where xxx is the current

IP address of the station, and then press ENTER. 3 Type the username and the password, and then press

ENTER. By default, the username is aris and the password is akand.

4 Type del config.sys, and then press ENTER to delete the config.sys file that is stored in the IDR-C.

5 Type del boot.sys, and then press ENTER to delete the boot.sys file that is stored in the IDR-C.

6 Type lcd dirname, where dirname is the name of the folder you have created in the disk of your LCT, and then press ENTER.

7 Type put config.sys, and then press ENTER to transfer the modified config.sys file from the folder of the LCT to the IDR-C and store it in the IDR-C.

8 Type put boot.sys, and then press ENTER to transfer the modified boot.sys file from the folder of the LCT to the IDR-C and store it in the IDR-C.

9 Type bye, and then press ENTER to return to the DOS prompt.

10 Type exit, and then press ENTER to return to Windows. 11 Press the reset button on the front panel of the IDR-C to

reset the IDR-C or switch-off the IDR-C. The IP address of the station will be the one you typed in the relevant field of the config.sys and boot.sys files. The link name and the station name will have also been changed accordingly.

Page 112: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

108

Annex C: Example of Router Configuration

Example scenario

The scenario of the example is the following: We want to connect an LCT to a chain of IDR-C stations through an IP network. The IP address of the router in the example is 146.124.34.141 while the IP address of the IDR-C system connected to the router through the asynchronous port NMS1 is 192.168.51.29.

IDR-C1

IPNetwork

Router

EthernetConnection

EthernetConnection

NMS1Port

IDR-C2

IDR-C4 3

IDR-C

NMS1Port

NMS1Port

146.124.34.141

192.168.51.29

LCT

Configuring the router

In the aforementioned configuration, the router is equipped with the WIC-2T card and is connected to the IDR-C station through its Serial0 port and to the IP network through its Fast Ethernet0 port. To configure the router, type the following commands: ! Commands for the FastEthernet0 interface configuration: interface FastEthernet0 ip address 146.124.34.141 255.255.255.0 no ip redirects no ip proxy-arp speed auto ! Commands for the Loopback0 interface configuration; to ensure unified ip addressing on the asynchronous serial ports: interface Loopback0 ip address 192.168.51.254 255.255.255.255 ! Commands for the Serial0 interface configuration (the Serial0 interface has been configured to use the IP address of the Loopback0 interface): interface Serial0 physical-layer async mtu 400 ip unnumbered Loopback0

Continued on next page

Page 113: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

109

Annex C: Example of Router Configuration, Continued

Configuring the router (continued)

encapsulation ppp keepalive 10 async default routing async mode dedicated line 1 transport input all stopbits 1 speed 57600 router rip version 2 redistribute connected redistribute static passive-interface FastEthernet0 network 192.168.51.0 ! Command to inject the default route information across the RIP enabled nodes: default-information originate ! no auto-summary no ip classless ! Command to configure the default route (gateway of last resort): ip route 0.0.0.0 0.0.0.0 146.124.34.100 ! no ip http server line con 0 login transport input none ! Commands to configure the Serial0 interface. The interface baud rate should be fixed at 57600 bit/s. line 1 transport input all stopbits 1 speed 57600 ! line aux 0 line vty 0 4 password idr-test login end

Page 114: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

110

Annex D: Default Alarms Attributes

1+0 Topology

Group Name Sent to Output

Logged Severity Polarity

Radio LD_RX 3 Yes Minor Reverse Radio LD_TX 3 Yes Minor Reverse Radio RSSI_RX 3 Yes Minor Reverse Radio LD_DDS 3 Yes Minor Reverse Radio ALC 3 Yes Minor Normal Radio LDLoopBack 3 Yes Minor Reverse Radio RSSI_Thrs 3 Yes Minor Normal Radio Tmprt_Thrs 3 Yes Minor Normal

Framer BERR6 2 Yes Minor Normal Framer LFA 2 Yes Minor Normal General Radio_comm 1 Yes Minor Normal General PS 1 Yes Minor Normal External inputs 1,2,3,4 4 Yes Minor Normal

Continued on next page

Page 115: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

111

Annex D: Default Alarms Attributes, Continued

1+1 Topology

Group Name Sent to Output

Logged Severity Polarity

Radio Α RALD_RX 3 Yes Minor Reverse Radio Α RALD_TX 3 Yes Minor Reverse Radio Α RARSSI_RX 3 Yes Minor Reverse Radio Α RALD_DDS 3 Yes Minor Reverse Radio Α RA_ALC - Yes Minor Normal Radio Α RALDLoopBack 3 Yes Minor Reverse Radio Α RA_RSSI_Thrs 3 Yes Minor Normal Radio Α RA_Tmprt_Thrs 3 Yes Minor Normal Radio Β RBLD_RX 3 Yes Minor Reverse Radio Β RBLD_TX 3 Yes Minor Reverse Radio Β RBRSSI_RX 3 Yes Minor Reverse Radio Β RBLD_DDS 3 Yes Minor Reverse Radio Β RB_ALC - Yes Minor Normal Radio Β RBLDLoopBack 3 Yes Minor Reverse Radio Β RB_RSSI_Thrs 3 Yes Minor Normal Radio Β RB_Tmprt_Thrs 3 Yes Minor Normal

Framer Α FABERR6 2 Yes Minor Normal Framer Α FALFA 2 Yes Minor Normal Framer Β FBBERR6 2 Yes Minor Normal Framer Β FBLFA 2 Yes Minor Normal General Radio_comm1 1 Yes Minor Normal General Radio_comm2 1 Yes Minor Normal General PS1 1 Yes Minor Normal General PS2 1 Yes Minor Normal

External inputs 1,2,3,4 4 Yes Minor Normal

Page 116: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

112

Annex E: Changing the IDR-C Capacity and Modulation (for the advanced User only)

Prerequisites Before changing the IDR-C capacity and modulation, do the following:

Step Action 1 Use the FTP Tool of the System menu and check the

following files are stored in the CMS unit of your IDR-C. If the files are not stored in the CMS unit, download them from the IDR-C Operation CD-ROM as described on page 116. • bin files

• sdhv139_chk.bin • idrc_2.3.1.bin

• xsvf files • fload_v1.xsvf • qam16_16x2_v2.xsvf • qam16_8x2_v2.xsvf • qam16_4x2_v2.xsvf • qpsk_16x2_v2.xsvf • qpsk_8x2_v2.xsvf • qpsk_4x2_v2.xsvf

• sys files • config.sys • boot.sys

• mib files • idrc_v0.8.mib

2 Open the Versions tabbed sheet and check the ODU version(s) is(are) the 0139. If the version is not the 0139, update the ODU(s) version, as described on page 118.

Continued on next page

Page 117: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

113

Changing the IDR-C Capacity and Modulation (for the advanced User only), Continued

Prerequisites (continued)

Step Action 3 Remove the IDR-C back cover and strap the pins at the

backplane connector as shown in the figure below. Place the cover back on again.

Continued on next page

Page 118: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

114

Changing the IDR-C Capacity and Modulation (for the advanced User only), Continued

Procedure To change the IDR-C capacity and modulation, follow the steps below:

Step Action 1 Get connected to the IDR-C. 2 Select Start>Run and in the Open box, type telnet <ip

address> where <ip address> is the ip address of the IDR-C station whose the capacity and modulation you want to change.

3 Type nick as login and nman as password and press ENTER.

4 Type ls and press ENTER. You view all the files of the CMS card.

5 Type Xupdate <xsvf file> a where <xsvf file> is one of the following files depending on the required capacity & modulation and a is 1 for modem A and 2 for modem B. With this command, you download the appropriate code file to the modem(s) ROM. • qam16_16x2_v2.xsvf • qam16_8x2_v2.xsvf • qam16_4x2_v2.xsvf • qpsk_16x2_v2.xsvf • qpsk_8x2_v2.xsvf • qpsk_4x2_v2.xsvf Example: If the capacity and modulation you require is 16 x 2 Mbit/s QAM, you should type: Xupdate qam16_16x2_v2.xsvf 1

The procedure lasts about 10 minutes.

Continued on next page

Page 119: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

115

Changing the IDR-C Capacity and Modulation (for the advanced User only), Continued

Procedure (continued)

Step Action 6 Type Xupdate fload_v1.xsvf a where a is 1 for modem A and

2 for modem B. With this command, you make the modem(s) operate with the specific capacity and modulation.

7 Type exit and press ENTER to exit telnet. 8 Delete from the CMS unit the existing system.ini file and

download to the CMS unit the appropriate system.ini file relative to the new modulation and capacity as described on page 116.

9 Switch-off and on the IDR-C to reset the system. 10 Open the ODU tabbed sheet and click Reset ODU to reset

the ODU. 11 Open the System tabbed sheet and confirm the values of

the System Capacity and Modulation boxes have changed properly.

Page 120: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

116

Downloading the required Files to the CMS Unit

To download the required files to the CMS unit, follow the steps below:

Step Action 1 Create a folder in the disk of your LCT (e.g. temp1). 2 Insert the IDR-C Operation CD-ROM in the disk drive and

copy the files you want to download to the CMS unit from the System Files folder of the CD-ROM to the folder you created in the previous step. Especially for the system.ini file, select to copy the system.ini file appropriate for the capacity and modulation you want to achieve and for the topology (1+0 or 1+1) you have. Note: The format of the system.ini file is as follows: <capacity>_<modulation>_<topology>_system.ini (e.g. 4x2_qpsk_1+0_system.ini) After you copy it to the LCT folder you must rename it to system.ini file (i.e. do not maintain the name <capacity>_<modulation>_<topology>_system.ini).

3 Select Start>Run and type command in the Open box. 4 At the DOS prompt, type FTP xxx where xxx is the IP

address of the station, and then press ENTER. 5 Type the username (aris) and the password (akand), and

then press ENTER. 6 Type lcd dirname where dirname is the name of the folder

you created (e.g. lcd c:\temp1), and then press ENTER. 7 Type hash to have a dotted view of the process progress.

Continued on next page

Page 121: Idr c Lct User Manual 04

IDR-C_LCT_UserManual_04 IDR-C – LCT User Manual

117

Downloading the required Files to the CMS Unit, Continued

Step Action

8 Type del <filename> where filename is one of the following, and then press ENTER to delete the specific file from the CMS unit. • bin files

• sdhv139_chk.bin • idrc_2.3.1.bin

• xsvf files • fload_v1.xsvf • qam16_16x2_v2.xsvf • qam16_8x2_v2.xsvf • qam16_4x2_v2.xsvf • qpsk_16x2_v2.xsvf • qpsk_8x2_v2.xsvf • qpsk_4x2_v2.xsvf

• sys files • config.sys • boot.sys

• mib files • idrc_v0.8.mib

• ini files • system.ini

9 Type put <filename>, and then press ENTER to download the specific file from the folder of the LCT to the CMS unit. Note: You do not need to download all the xsvf files to the CMS unit. Download only the fload_v1.xsvf and the xsvf of the capacity and modulation you want to achieve.

10 Repeat steps 8 and 9 for as many files as needed. 11 Type bye, and then press ENTER to return to the DOS

prompt. 12 Type exit, and then press ENTER to return to Windows. 13 Press the reset button on the front panel of the IDR-C to

reset the IDR-C or switch-off the IDR-C.

Page 122: Idr c Lct User Manual 04

IDR-C – LCT User Manual IDR-C_LCT_UserManual_04

118

Updating the ODU Version

To update the ODU version to 0139, follow the steps below:

Step Action 1 Download the sdhv139_chk.bin file from the IDR-C

Operation CD-ROM to the CMS unit as described on page 116.

2 Select Start>Run and in the Open box, type telnet <ip address> where <ip address> is the ip address of the IDR-C station whose the ODU version you want to update.

3 Type nick as login and nman as password and press ENTER.

4 Type ls and press ENTER. You view all the files of the CMS card.

5 Type ODUupdate sdhv139_chk.bin 0 (for ODU A) or 1 (for ODU B) and press ENTER.

The ODU update process lasts about 7 minutes. After the process completion, the following screen appears: