    Reference guide

    InteliDrive

    IDDCU Marine

    Expandable engine controller

    with electronic engines support

    Single speed applicationsVariable speed application

    AUX, EME, CMBPRP

    SW version 2.1, February 2012

  • 7/30/2019 Id Dcu Marine 2.1

    2/152

    Table of Contents

    Table of Contents............................................................................................................................................ 2Abbreviations ............................................................................................................................................... 5

    General description.......................................................................................................................................... 7Physical component and interface Descriptions...........................................................................................8Corresponding documentation.....................................................................................................................8

    Terminal and dimensions................................................................................................................................. 9ID-DCU Marine............................................................................................................................................. 9ID-DCU Marine terminals........................................................................................................................... 10ID-DCU xx -LT version with display preheating..........................................................................................10ID-RPU terminals........................................................................................................................................ 11ID-COM terminals....................................................................................................................................... 11ID-SCM Speed control module...................................................................................................................12ID-SCM1..................................................................................................................................................... 13InteliVision 8............................................................................................................................................... 14InteliVision 5 CAN....................................................................................................................................... 15

    How to use remote display Function keys..................................................................................................16Communication lines wiring........................................................................................................................ 19I-RD-CAN (Remote Panel)......................................................................................................................... 19ID DCU Marine dimensions........................................................................................................................ 23I-RB.. technical description......................................................................................................................... 23ECU............................................................................................................................................................ 24IS-BIN16/8.................................................................................................................................................. 24IS-AIN8....................................................................................................................................................... 25IS-AIN8TC.................................................................................................................................................. 26IGL-RA15 Remote annunciator..................................................................................................................27IGS-PTM.................................................................................................................................................... 27I-AOUT8..................................................................................................................................................... 28I-LB+ Communication Bridge...................................................................................................................... 30

    IG-IB Internet bridge................................................................................................................................... 31I-CB communication bridge........................................................................................................................ 31

    Recommended wiring.................................................................................................................................... 32ID-RPU wiring............................................................................................................................................. 32Wiring example........................................................................................................................................... 33Complete system without RPU...................................................................................................................33Electronic engine without redundancy line.................................................................................................34Engine without ECU (mechanical engine)..................................................................................................34Scania S6 wiring example.......................................................................................................................... 35Bus/Communication architecture................................................................................................................35I-CB wiring and configuration...................................................................................................................... 36

    Getting started............................................................................................................................................... 37How to install.............................................................................................................................................. 37

    ID-DCU Analog inputs hardware configuration...........................................................................................39ID-DCU Analog inputs software configuration............................................................................................40Hardware connection.................................................................................................................................. 46Analog inputs on IS-AIN8........................................................................................................................... 46Analog inputs on IS-AIN8TC...................................................................................................................... 48Binary inputs / outputs on ID-DCU..............................................................................................................49Binary inputs on IS-BIN16/8....................................................................................................................... 49Binary outputs on IS-BIN16/8..................................................................................................................... 50Binary output separation............................................................................................................................. 50IS-AIN8(TC), IS-BIN8/16 address setting...................................................................................................50IS-AIN8(TC), IS-BIN8/16 SW version check...............................................................................................50IGS-PTM and IGL-RA15 module connection..............................................................................................51

    Binary Inputs.................................................................................................................................................. 52Binary inputs from J1939 configuration......................................................................................................58Binary inputs protection.............................................................................................................................. 58

    ID-DCU-Marine-2.1, ComAp February 2012 2ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    3/152

    Binary outputs................................................................................................................................................ 60Source: Log Bout........................................................................................................................................ 60Source: Info................................................................................................................................................ 65Source: RPU unit........................................................................................................................................ 65Source: Prg.states...................................................................................................................................... 66Source: Ana protections............................................................................................................................. 68Source: Bin protections.............................................................................................................................. 69

    Source: Binary Inputs CU........................................................................................................................... 69Source: RPU unit........................................................................................................................................ 69Source: Binary Inputs................................................................................................................................. 69Source: J1939............................................................................................................................................ 69Binary output to J1939 configuration: Source-Value...................................................................................70

    Analog and Binary values.............................................................................................................................. 71Logical analog inputs list............................................................................................................................ 71Analog inputs from J1939 configuration.....................................................................................................73Analog inputs protection............................................................................................................................. 73

    Analog outputs............................................................................................................................................... 81InteliDrive Engine ECU communication......................................................................................................82Setpoints........................................................................................................................................................ 83

    Password.................................................................................................................................................... 83

    Access code............................................................................................................................................... 83Engine commands and Statistics protection...............................................................................................84Basic settings............................................................................................................................................. 84Engine params........................................................................................................................................... 87Engine protect............................................................................................................................................ 90RPMdep protect (PRP only)..................................................................................................................... 93Load sharing (PRP only).......................................................................................................................... 94Analog inputs.............................................................................................................................................. 97Active call/SMS........................................................................................................................................... 97Date and time............................................................................................................................................. 98ID-SCM unit................................................................................................................................................ 98Protections................................................................................................................................................. 99

    Operator Interface ....................................................................................................................................... 100

    Pushbuttons and LEDs............................................................................................................................. 100How to select engine mode?.................................................................................................................... 101Display menus.......................................................................................................................................... 101How to view measured data?................................................................................................................... 101How to view and edit set points?..............................................................................................................101How to view the HISTORY menu?...........................................................................................................101How to change the display contrast?........................................................................................................101How to check the serial number and software revision?...........................................................................102How to change the display backlight intensity?........................................................................................102How to change controller language?........................................................................................................102How to find active alarms?....................................................................................................................... 102Main screen indication.............................................................................................................................. 103Controller screens.................................................................................................................................... 104

    Functions available from ID-DCU Marine front panel keys.......................................................................108ID-DCU functions......................................................................................................................................... 109

    Default archives........................................................................................................................................ 109Operational modes................................................................................................................................... 109Function description details...................................................................................................................... 111Universal states........................................................................................................................................ 115

    ID-RPU........................................................................................................................................................ 116ID-RPU functions...................................................................................................................................... 117ID-RPU over speed setting....................................................................................................................... 119

    PLC - programmable functions.................................................................................................................... 120PLC functions description......................................................................................................................... 124PLC configuration example...................................................................................................................... 137

    Controller configuration and monitoring.......................................................................................................141

    Direct connection to the PC...................................................................................................................... 141DriveConfig............................................................................................................................................... 141Configuration steps................................................................................................................................... 142

    ID-DCU-Marine-2.1, ComAp February 2012 3ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    4/152

    DriveMonitor............................................................................................................................................. 143Password protection................................................................................................................................. 144Modbus protocol....................................................................................................................................... 144

    Technical data............................................................................................................................................. 145ID-DCU ................................................................................................................................................... 145I-RD-CAN................................................................................................................................................. 146ID-RPU ................................................................................................................................................... 147

    ID-SCM..................................................................................................................................................... 147ID-SCM1................................................................................................................................................... 148CAN bus interface.................................................................................................................................... 148IS-BIN16/8................................................................................................................................................ 149IS-AIN....................................................................................................................................................... 150IGL-RA15................................................................................................................................................. 150IGS-PTM ................................................................................................................................................. 151I-AOUT8................................................................................................................................................... 152I-RBxx....................................................................................................................................................... 152I-LB+......................................................................................................................................................... 152IG-IB......................................................................................................................................................... 152

    ID-DCU-Marine-2.1, ComAp February 2012 4ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    5/152

    Abbreviations

    aid Archive file extension for InteliDrive controller

    AIN Controller or extension module Analog input

    Alarm General term for any active engine protection Warning, Shutdown, etc.

    Alarm list Controller or PC DriveMonitor screen with list of active and unaccepted alarmsdetected from ID controller.

    ECU Alarm list Controller or PC DriveMonitor screen with list of active and unaccepted alarmsdetected from engine ECU.

    AOUT Controller Analog OUTput or outputs group.

    Archive Usually aid file that contains all controller data: configuration, setpoints setting andhistory records.

    AUX Controller application (archive, operational mode) for Auxiliary engines.

    BI Controller binary input.

    BIN Controller binary inputs group.

    BO Controller binary output.

    BOUT Controller binary outputs group.

    CAN Control Area Network serial data link.Cd Cool down protection, cooling period is included before engine stops.

    CMB Controller Combined mode.

    D+ Controller function for battery charging function check and/or engine runningindication.

    DC DriveConfig, PC software for InteliDrive configuration.

    DM DriveMonitor, PC software for InteliDrive monitoring.

    DriveConfig PC software for InteliDrive configuration.

    DriveMonitor PC software for InteliDrive monitoring.

    ECU Engine Electronic (injection) Control Unit.

    ECU alarm Alarm detected in engine electronic control unit that is received via J1939.

    EFI Electronic fuel injection

    EME InteliDrive Emergency operational mode.

    EMS I. Electronic Management System version I.

    EMS II. Electronic Management System version II.

    Fls Sensor fail alarm prefix.

    FMI Failure Mode Identifier.

    GSM modem Modem for Global System of Mobile communication

    History List of alarms and operational states with Reason, Date and Time and adjustablevalues set that is stored in controller, can be listed from the screen or DriveMonitor.

    HRB Controller Harbor mode.

    I-AOUT8 Controller extension module with 8 analog outputs: 10V or 20mA.

    I-CB Inteli Communication bridge = controller interface for other electronic engines likeMTU, CAT etc.. that are not supported yet.

    I-LB, I-LB+ Modem Unit = one point interface for multiple controllers connected via CAN2 bus.

    InteliVision5InteliVision8 ComAp color display 5 or 8 inch.

    ID InteliDrive controller.

    ID-COM InteliDrive communication module with interface to J1939, J1587 and to othercontrollers.

    ID-DCU InteliDrive DieselControlUnit.

    ID-MCU InteliDrive Industrial Controller Unit with Volvo Penta front panel modification.

    ID-RPU InteliDrive Redundancy Protection Unit = ID backup unit for Over speed andEmergency stop protection in Marine applications.

    ID-SCMID-SCM1 InteliDrive Speed Control Module = interface unit for InteliDrive controller.

    IG-IB InteliGen Internet Bridge = controller interface for internet communication.

    IGL-RA15 Remote Annunciator = external 15 LED indication panel (three colors, configurable).

    ID-DCU-Marine-2.1, ComAp February 2012 5ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    6/152

    IG-MU InteliGen Modem Unit (older type) = controller interface for multiple enginesapplication one point communication with group of controllers connected via CAN2.

    IGS-PTM Controller extension module with 8 binary inputs and outputs and 4 analog inputs.

    I-RB Inteli Relay board = interface board with 16 free contact relays.

    I-RB16 Inteli Relay board = interface board with 16 free contact relays.

    I-RD Inteli Remote Display (Remote Panel) = the same panel like on controller, all datareceived via CAN2 bus.

    I-RD-CAN Inteli Remote Display (Remote Panel) = the same panel like on controller, all datareceived via CAN2 bus.

    I-RP Inteli Remote Display (Remote Panel) = the same panel like on controller, all datareceived via CAN2 bus.

    IS-AIN8 InteliSys Analog input module = extension module with 8 analog inputs.

    IS-AIN8TCInteliSys Thermocouple analog input module = extension module with 8thermocouple analog inputs.

    IS-BIN16/8 InteliSys Binary input/output module = extension module with 16 binary inputs and8 binary outputs.

    J1587 The J1587 bus is mainly used for redundant signals; system diagnosis and softwaredownload on after market tools.

    J1587/J1708 See J1587

    J1939 The J1939 bus in mainly used for engine controls and engine monitoring.KWP2000 Scania Communication protocol.

    mhx Extension for controller firmware (Motorola HeX file).

    MID Message Identification Assignments.

    OFF Controller mode when power supply is switched on, but all binary outputs and startcommands are disabled = engine start is blocked.

    PID J1939 Parameter Identification Assignments.

    PPID J1939 Proprietary Parameter Identification Assignments.

    PRP Controller Propulsion mode.

    RPM Engine Revolution Per Minute engine speed.

    PCB Printed Circuit Board

    PSID J1939 Proprietary Parameter Identification Assignments.

    RS232 Standard serial data line for PC or Modem connection (controller programming ormonitoring).

    Sd Shut down protection.

    SID J1939 Subsystem Identification Assignments.

    Wrn Warning protection.

    ID-DCU-Marine-2.1, ComAp February 2012 6ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    7/152

    General description

    InteliDrive ID-DCU Industrial is a specialized engine controller for Industrial and Marine applications. Itcontrols, monitors and protects the engine in single (Auxiliary) or variable (propulsion) speed operational

    modes. The controller can communicate with Engine Management System via the CAN serial line usingstandard J1939 or another (KWP2000) communication protocol.

    InteliDrive controllers are equipped with a powerful graphic display with icons, symbols and bar-graphs forintuitive operation, which together with high functionality sets new standards in engine controls.

    Engine functions

    Engine sequencing and control (start/stop, warm-up and cool-down, pre-lubrication etc.)

    Engine monitoring and protections (2 or more level analog inputs protection, adjustable delays)

    Speed measurement from magnetic pick-up or from ECU

    Running hours meter, number of starts counter

    Configurable 14 Binary inputs and Outputs and 8 Analog inputs

    Setpoints are adjustable via InteliDrive panel or via PC software

    3 level password protection

    On screen Alarm and ECU Alarm indication

    Event and time driven engine history for back tracing

    Two or more languages selectable in controller

    Communication

    RS232 / Modbus RTU

    Analog or GSM modem

    Internet

    Engines with Engine Electronic Control Unit: J1939, J1587, KWP2000

    Extension units for more I/O and Remote Display panel.

    Physical

    180x120 mm front panel mounted case

    Graphic back-lit LCD display 128x64 pixel resolution with icons and bar graphs

    LED status indicators / Lamp test

    ID RPU Redundant Protection Unit

    1 Emergency stop input

    5 Shutdown inputs

    1 RPM input

    Common warning and common shutdown output terminals

    Stop solenoid, fuel solenoid outputs

    Redundant power supply

    I/O broken wire detection

    Conformity declaration

    Following described machine complies with the appropriate basic safety and healthrequirement of the EC Low Voltage Directive No: 73/23 / EEC and EC ElectromagneticCompatibility Directive 89/336 / EEC based on its design and type, as brought intocirculation by us.

    ID-DCU-Marine-2.1, ComAp February 2012 7ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    8/152

    Note:ComAp believes that all information provided herein is correct and reliable and reserves the right to updateat any time. ComAp does not assume any responsibility for its use unless otherwise expressly undertaken.

    Physical component and interface Descriptions

    ModuleID-DCU Central unit InteliDrive central unit:

    14 BIN, 14BOUT, 8 AIN,1xRS232, 1xCAN1 (full), 1xCAN2 (TTL), 1x Sync.Data line (TTL)

    ID-RPU Redundancyunit

    InteliDrive Redundancy Protection Unit with 5 SD and one Emergencystop input one Wrn, Sd Fuel solenoid and one Stop solenoid output.

    ID-SCM Interface Controller interface with two RPM inputs, two impulse inputs, twoanalog outputs and one Sped governor (V, mA or pwm) output.

    ID-COM Communicationinterface

    InteliDrive Communication interface for inter-controller or Remotedisplay CAN2 line and for Redundancy synchronous J1708/1587 dataline.

    I-RB16 Relay board 16 relays with free NO/NC contacts 24VDC for binary outputsseparation

    I-RB8 Relay board 8 relays with free NO/NC contacts 24VDC for binary outputsseparation

    I-RD-CAN Remote display InteliDrive Remote display (Slave panel), CAN or RS232 interface

    InteliVision 8 Remote display 8 inch color display

    InteliVision 5 CAN Remote display 5 inch color display

    I/O extension

    ECU Configurable Engine Electronic control unit

    IS-AIN8 8 analog inputs Configurable for VDO, PT100, PT1000, Thermocouples, mA, Volts

    IS-AIN8TC 8 analog inputs Configurable for Thermocouples

    IS-BIN16/8 Extensionmodule

    16 Binary inputs, 8 Binary outputs

    IGS-PTM Extensionmodule

    8 BIN, 8 BOUT, 4 AIN, 1 AOUT

    I-AOUT8 Extensionmodule

    8 Analog outputs selectable to 10VDC, 20 mA, pwm (2,4kHz)

    IGL-RA15 External LEDindication panel

    Configurable 15 LED and Horn signal.

    Communication

    I-LB+ Communication bridge.

    IG-IB Internet interface

    I-CB ECU communication interface

    Hint:IG-IOM extension unit is not compatible with ID-DCU controller.

    Corresponding documentation

    1 DriveConfig-2.2.pdf (June 2006) PC configuration software

    2 DriveMonitor-2.8.pdf (Jan 2011) PC monitoring software

    3 ID-DCU-Industrial-2.8.pdf (Feb 2011) ID-DCU Industrial branch

    4 InteliCommunicationGuide April 06.pdf Communication guide

    ID-DCU-Marine-2.1, ComAp February 2012 8ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    9/152

    Terminal and dimensions

    ID-DCU Marine

    The front panel of the InteliDrive controller is intended for installation in an overall enclosure rubber seal forIP 65 - see chapter Technical data.

    Front panel LED

    Right RED Active alarm indication Blinks when new alarm is activated.Steady lights after Fault reset confirmation - when alarmis still active.Disappears after Fault reset confirmation when alarmis inactive.

    Right GREEN Engine running indication Light when engine is running.

    Left GREEN Indication of Binary outputClose load state

    Light when output is Closed.

    Hint:Please check the last software version.

    ID-DCU-Marine-2.1, ComAp February 2012 9ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    10/152

    ID-DCU Marine terminals

    Grounding

    Terminal

    BOOT

    JUMPER

    BINARY INPUTSRP

    M

    BINARY INPUTS

    ANALOG

    INPUTS

    BINARY

    OUTPUTS

    POWE

    R8 - 36 V DC

    EXTENSION

    MODULE

    ID-R

    PU

    RS232

    LB

    1

    EXTENSION

    MODULE

    ID-C

    OM

    + -RPMGND

    RPM

    IN

    BI1

    BI2

    BI3

    BI4

    BI5

    SHIELD

    COM

    D+

    BO1

    BO2

    BO3

    BO4

    BO5

    BO8

    BO6

    BO12

    BO13

    BO14

    BO9

    BO7

    BO10

    BO11

    AIN1

    AIN2

    AIN3

    AIN4

    AIN6+

    AIN5+

    AIN8+

    AIN8

    -

    AIN6

    -

    AIN5

    -

    AIN7+

    AIN7

    -

    BI6

    BI7

    BI8

    BI9

    BI10

    BI11

    BI13

    BI12

    BI14

    ID-DCU-Marine

    RPM Primary RPM

    BI1 to BI14 Binary inputs, active when closed to minus power supply

    BO1 to BO14 Binary outputs; Low side switch; 0,5 Amps each;

    D+ D plus terminal

    AIN1 to AIN4 Analog inputs group 1AIN5+, AIN5-AIN6+, AIN6-AIN7+, AIN7-AIN8+, AIN8-

    Analog inputs group 2

    ID-DCU xx -LT version with display preheating

    LT is an option for extending of operating temperature range from -20 to -40 C. Heating foil is not part of

    standard ID-DCU and ID-MCU (without -LT extension).

    Board temperature

    +5 C- 40 C

    Preheating

    3,5 W

    The only one low temperature sensitive part is the controllerdisplay.ID-DCU-Industrial-LT version contains a preheating foil on thedisplay activated below +5C (measured on the PCB). Heatingis switched off when controller power supply is below 10VDC(together with display backlight).

    ID-DCU-Marine-2.1, ComAp February 2012 10ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    11/152

    ID-RPU terminals

    Redundant Protection Unit. ID-RPU is mounted directly to ID-DCU box.

    RPM Secondary RPM

    +SOL Common power supply for galvanic separated Fuel solenoid and Stop solenoidoutputs.

    FUEL SOL Fuel solenoid output, High side switch (8 Amps), BW detection in open state or above1 amp load

    STOP SOL Stop solenoid output, High side switch (8 Amps), BW detection in open state or above

    1 amp loadGND SOL Common GND for Fuel and Stop solenoid outputs

    COMM.SD Common Shut down output, Low side switch (0,5 Amps)

    COMM.WRN Common Warning output, Low side switch (0,5 Amps)

    SD1 to SD5 Shut down inputs, BW detection, Normally open

    EM.STOP Emergency stop input, Normally closed

    A+, A- Primary battery

    B+, B- Secondary battery

    COM+, COM- Battery A, B output to ID-DCU

    Hint:

    10 k resistor must be connected in parallel to SD1 to SD5 inputs.

    ID-COM terminalsCommunication interface ID-COM is mounted directly to ID-DCU Marine box.

    ID-DCU-Marine-2.1, ComAp February 2012 11ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    12/152

    CAN1 Extension modules: EMS, IS-AIN8(TC), IS-BIN16/8, IGS-PTM, IGL-RA15

    CAN2 Intercontroller: I-RD-CAN, I-LB+, IG-IB, others ID-DCU

    ID-DCU ID-COM

    INTERFACE

    INTERFACE

    INTERFACE

    CAN1

    J1939

    J1587

    CAN2PROCES

    SOR

    TTL

    TTL

    TTL

    120 ohms

    120 ohms

    Hint:

    Put jumper to connect the internal 120 terminating resistor for CAN2 interface.ID-COM module is not required when inter-controller CAN2 and J1587 lines are not used. In this caseconnect Extension modules CAN1 directly to Extension modules port ID-COM on ID-DCU (9-pin connector:5=H, 9=L).

    ID-SCM Speed control module

    ID-SCM module is interface module for InteliDrive controller application. Module is mounted directly to ID-DCU controller case. Module power supply: 8 to 36VDC.

    InputsRPM1, RPM2: Two inputs for frequency (e.g. flow) measuring. Expected sensor is magnetic pickup withmaximal frequency range up to 8 kHz. The output values SCM Freq1, SCM Freq2 calculation use setpointsFreqRate1 and FreqRate2 - see below.Closed jumper divides input frequency by 16 - recommended for higher frequency (>1000Hz) measuring.Jumper position does not influence output value range.

    Jumper RPM input nominal frequency range

    Closed > 1000 Hz

    Closed or Opened 500 1000 HzOpened < 500 Hz

    IMP1, IMP2: Two impulse inputs for integral (e.g. consumption) measuring. It is expected NPN opencollector (active) impulse sensor with maximal frequency range up to 60 Hz. Minimal pulse duration is 1ms.The output values SCM Imp1, SCM Imp2 calculation use setpoints TransferRate1 and TransferRate2 - seebelow.

    ID-SCM inputs wiring example

    RPM IN

    RPM GND

    Magnetic pickup

    RPM1, RPM2

    Magnetic pickup wiring toRPM1 and RPM2 inputs.

    PWR

    INGND

    Contact

    IMP1, IMP2

    Contact sensor wiring toIMP1 and IMP2 inputs.

    Active NPN

    sensor

    +24VDC

    GND

    IMP1, IMP2

    PWR

    IN

    GND

    Active NPN sensor wiring toIMP1 and IMP2 inputs.

    OutputsAOUT1, AOUT2: Two configurable analog outputs for indication or any loop control. Outputs are jumperadjustable between 0 to 10VDC and 0 to 20 mA.

    ID-DCU-Marine-2.1, ComAp February 2012 12ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    13/152

    AOUT3 - Speed governor: Configurable analog voltage interface to engine speed governor for mechanical

    engines (without ECU). Output is jumper selectable between 10VDC and 10VDC via 10 k or PWM(1600Hz / 5V, 10mA max).

    Default jumpers setting: AOUT1 and AOUT2 ~ 0-10VDC; Speed governor ~ 10VDC; RPM1 andRPM2 ~ opened jumper (divides input frequency by 1).

    ID-SCM1ID-SCM cost effective version with just one Speed governor output. ID-SCM1 module is one analog outputmodule for InteliDrive industrial or marine applications. Module is mounted directly to ID-DCU controller case.

    Technical dataPower supply: internal supply from ID-DCU (8 to 36 VDC)Operating temperature range: -40C to +70CNumber of analog outputs: 1, no galvanic separationAnalog output refreshment: 100 ms

    Analog output optionsa) PWM 1600 Hz (fix), 5V level, max 10 mA

    b) 0 to 10VDC 1%, 10 k output resistancec) 0 to 10VDC 1%, max 5 mA (voltage output)

    Configuration in DriveConfiga) Module = SCMb) I/O Analog outputs SCM - AOUT1 (only)

    a. Sourceb. Low convert limitc. Hi convert limit

    ID-DCU-Marine-2.1, ComAp February 2012 13ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    14/152

    InteliVision 8

    Terminals and Dimension

    ID-DCU-Marine-2.1, ComAp February 2012 14ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    15/152

    InteliVision 5 CAN

    5 color display. InteliVision 5 CAN is offered in two hardware modifications: InteliVision 5 CAN

    InteliVision 5 CAN Backlit

    The only HW difference between two versions is presence of standard or backlight keyboard version, i.e. ifthere is present a feature of back-lighted buttons or not. Both versions are IP65 protected from all sides,equipped with binary output switch for HORN signaling, CAN interface is galvanically separated.

    The InteliVision 5 CAN version is intended to use with InteliDrive controllers only (ID-DCU, ID-DCU-Marine,ID-Mobile, ID-Mobile Logger), Backlit version supports also InteliGen-NT and InteliSys-NT controllers.

    Depending on customer preferences there can be used optional accessories:

    InteliVision 5 Harness-2 - 2m prefabricated cable with unassigned wires at the end

    InteliVision 5 IP 65 Connector - connector set containing connector body and 10 correspondingterminal female pins

    ECU Simulator - set containing supported USB/CAN converter and variouscabling, for new firmware / font / logo download into theInteliVision 5 CAN

    ID-DCU-Marine-2.1, ComAp February 2012 15ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    16/152

    170 (6.7")

    110

    (4.3")

    InteliVision5CAN connector wiring

    1 GND 5 UBatt

    2 A/B IN 6 CAN-L

    3 BO-A 7 COM

    4 BO-B 8 CAN-H

    1 - 5 Power supply 8 36VDC6 - 8 CAN bus (with galvanic separation)3 - 4 Binary output configured for Horn function. It is Solid State Relay with galvanic separation. Max

    36VDC/0,5A (like free contact).2 1 Analog/Binary Input for display and buttons backlit control. Connect resistive pot for continuous

    backlit change: 0 ~ 0%; 2400 ~ 100%. Or just place contact to switch between 0% and 100%intensity.

    Note:It is possible to connect up to five InteliVision 5 CAN or four InteliVision 8 displays to common CAN2 bus.The display addresses must be different in this case.

    How to use remote display Function keys

    The screen specification file is possible to download in DriveConfig application File -> Export Screens.The result is xxxxx.ISC file in XML format which is text editable. Notepad application can be used for fileediting, but recommended and much more comfortable is to use some advanced editor as for examplePSPad - a freeware code editor, available on http://www.pspad.com. After ISC file editing it is possible toupload the screen specification back into ID-DCU-Marine in DriveConfig application File ->

    Import Screens and use Write to controllercommand .

    ID-DCU-Marine-2.1, ComAp February 2012 16ID-DCU-Marine-2.1.pdf

    http://www.pspad.com/http://www.pspad.com/http://www.pspad.com/
  • 7/30/2019 Id Dcu Marine 2.1

    17/152

    The screen specification ISC file has following important parts for configuration of buttons:

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    ..

    ID-DCU-Marine-2.1, ComAp February 2012 17ID-DCU-Marine-2.1.pdf

    functionality definition of InteliVision8 bottom buttons

    functionality definition of InteliVision5 bottom buttons

    definition of displayed text for given button

  • 7/30/2019 Id Dcu Marine 2.1

    18/152

    Buttons are internally identified by key parameter in ISC file

    There is an example above for configuration of second button from the left (key=1).

    command="62" is a command to assign the button functionality to LBO User Button 1 .. 5. Which User ButtonLBO will be assigned to the button and which type of functionality will have the button is given by argumentparameter.

    argument

    LBO User Button 1 1 11 21 31

    LBO User Button 2 2 12 22 32

    LBO User Button 3 3 13 23 33

    LBO User Button 4 4 14 24 34

    LBO User Button 5 5 15 25 35

    The argument="13" means that given button will be assigned to LBO User Button 3 and the button will workswith toggle function.The textid="scrtext27" defines displayed buttons text on InteliVision display, scrtextxx has to be named in section of ISC file.

    ID-DCU-Marine-2.1, ComAp February 2012 18ID-DCU-Marine-2.1.pdf

    key=0

    key=1

    key=2

    key=3

    key=0

    key=1

    key=2

    key=3

    key=4

  • 7/30/2019 Id Dcu Marine 2.1

    19/152

    Communication lines wiring

    I-RD-CAN (Remote Panel)

    ID-DCU-Marine-2.1, ComAp February 2012 19ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    20/152

    Hint:The ID-DCU-Marine controller can be used as an I-RD-CAN remote display after uploading of the I-RD-CANfirmware

    Remote Display I-RD-CAN (Remote Panel) works as a remote control panel for the ID-DCU mastercontroller.

    All panel buttons works the same way as corresponding buttons on master controller. All LEDs displaysthe same state as corresponding LEDs on master controller.

    Start, Stop buttons and setpoint changes are not active when master ID-DCU controller is in LOC (Local)mode.

    I-RD-CAN screen listing does not influence screen on master controller.

    Interruption of the serial line between master device and I-RD-CAN will have no effect to the engine.Master device will always be able to work without connected Remote display.

    I-RD-CAN displays the same screens as its master controller and can be switched to the samelanguages. The user interface is identical as the master controller.

    I-RD-CAN is the same mechanical and electronic design (the same box but some electronic componentswere removed). No inputs and outputs are available on I-RD-CAN only.

    It is possible to connect I-RD-CAN to ID-DCU via RS232 (38,4kbps) or via CAN bus (50 or 250 kBd).

    I-RD-CAN automatically downloads new configuration table from master controller if the CRC doesntmatch the CRC of the stored configuration table.

    I-RD-CAN uses separate mhx firmware different from controller firmware compatible with both ID-DCU-Industrial and ID-VP-Industrial.

    I-RD-CAN firmware can be reprogrammed via Boot load procedure only.

    I-RD-CAN backlight can be switched to full intensity when middle power supply terminal (D+ in DCU) isclosed to + power supply.

    I-RD-CAN wiringRS232 interface: three wire cable (2-3, 3-2, 5-5), max. cable length up to 10 meters.

    ID-CU I-RDRS232 RS232

    Contr.addr 1

    CAN addr. 1

    Contr.addr 1

    Using converters to RS485 or RS422 increases distance up to 1000 meters.Recommend external converter: ADVANTECH ADAM 4520: RS232 to RS422/485 converter, DIN rail,automatic RS485 bus supervision, no external data flow control signals, galvanic isolated, baud rate38400bps.

    ID-DCU-Marine-2.1, ComAp February 2012 20ID-DCU-Marine-2.1.pdf

    BL

    Jumper (under cover) toconnect I-RD-CAN internal120 resistor for CAN busline terminating

    . .

  • 7/30/2019 Id Dcu Marine 2.1

    21/152

    ID-CU I-RDRS232 RS232RS232 /

    RS422/485

    RS232 /

    RS422/485

    RS422/485Converter Converter

    Contr.addr 1

    CAN addr. 1

    Contr.addr 1

    CAN bus connection requires ID-COM module on ID-DCU. Use I-RD-CAN Central unit 9-pin connector

    (5=CAN H, 9=CAN L) to connect CAN bus. Put jumper to connect I-RD-CAN internal 120 resistor for CANbus line terminating.

    ID-CUCAN2

    ID-COM

    I-RD

    Contr.addr 1

    CAN addr. 1

    Contr.addr 1

    5 - CAN H

    9 = CAN L120ohm

    I-RD-CAN can monitor any ID-DCU controller on the CAN2 bus based on I-RD-CAN Contr. address setting.

    1.ID-CU

    CAN2

    ID-COM

    I-RD

    2.ID-CU

    ID-COM

    `

    `

    Contr.addr 1

    Contr.addr 2

    CAN addr. 1

    Contr.addr 2

    5 - CAN H

    9 = CAN L 120

    ohm

    It is possible to connect up to five I-RD-CAN to common CAN2 bus. The I-RD-CAN addresses must bedifferent in this case.

    1.ID-CU

    CAN2

    ID-C

    OM

    I-RD

    2.ID-CU

    ID-COM

    I-RD

    CAN addr. 1

    CAN addr. 2

    Contr.addr 1

    Contr.addr 2

    Contr.addr 1

    Contr.addr 2

    5 - CAN H

    9 = CAN L120

    ohm

    120ohm

    Hint:There is no connection between ID-DCU and Remote panel during ID-DCU controller programming and inINIT state.

    How to establish ID-DCU to I-RD-CAN connection

    Following screen appears after I-RD-CAN power supply is switched on and there is no connection to ID-DCUestablished.

    Screen rows Meaning / selection range I-RD front panel button to change

    I-RD-Industrial 1.x I-RD firmware branch and version

    ComAp 2004 Copyright

    SN: xxxxxxxx Controller serial number

    Contr. Addr: 1 Controller address: 1 to 32 and AUTO Up, Down

    Connection: CAN addr.1 Connection: CAN addr.1, CAN addr.2,RS232

    Page

    NO CONNECTION TRYING. , PROGRAMMING I-RD status during Init state.

    1. Connect selected communication line between ID-DCU controller and I-RD-CAN panel.2. Switch ID-DCU and I-RD-CAN power supply on.

    ID-DCU-Marine-2.1, ComAp February 2012 21ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    22/152

    3. After I-RD-CAN Initialization screen appears: Use front panel Up/Down buttons to change Controlleraddress in the range 1 to 32 or AUTO. I-RD-CAN automatically increases the controller address andtries to open connection. This I-RD-CAN Controller address must correspond to connected ID-DCUMarine Basic setting: Controller address setpoint.

    4. Use Page button to set I-RD-CAN connection: CAN addr.1, CAN addr.2 or RS232.5. Then press Enter button to start data download. Message TRAYING appears on the I-RD-CAN

    screen. Unsuccessful attempt to read data is repeated each 15 sec.

    6. The Programming bargraph appears on I-RD-CAN screen after connection is opened.7. Standard ID-DCU screen appears after complete configuration is loaded to I-RD-CAN.

    Hint:To switch to Init screen press Page button for more than 2 sec when CFG table error message appears onthe I-RD-CAN screen.

    I-RD-CAN backlight-brightness intensity change(the same procedure for ID-DCU Marine and I-RD-CAN)1. Enter+Page buttons = switch to Info screen and then2. Enter+Up/Down button increases/decreases the display backlight (it is stored - until the next change).3. The setpoint Basic setting: LightTimeOff in I-RD-CAN works locally for I-RD-CAN (this is only exception)and it is not transferred to the central unit. Backlight is after this time switched off from current level. Any key

    touch activates the backlight.

    That means it is possible to set I-RD-CAN backlight level and LightTimeOff independently to ID-DCU Marine.

    From I-RD firmware version 1.2 and hardware version 2.0 from s.n. xxxx0006 is possible to change Remotepanel display backlight between adjustable and full level via external switch see drawing below.

    POWER

    8-36VDC

    + -

    POWER

    SUPPLY

    BACKLITESWITCH

    REMOTE PANEL

    Opened switch = Backlight is adjustable by Enter-Up/Enter-Down panel keys from INFO screen (Enter-Page)

    Closed switch = full backlight like in ID-DCU

    Hint:It is not possible to control I-RD backlight continuously via analog input like on ID-DCU.

    ID-DCU-Marine-2.1, ComAp February 2012 22ID-DCU-Marine-2.1.pdf

    BL

  • 7/30/2019 Id Dcu Marine 2.1

    23/152

    ID DCU Marine dimensions

    ID-COM and ID-SCM are mounted directly to ID-DCU Marine case.I-RD-CAN (Slave panel) has the same dimensions.

    ID-RPU

    ID-CU

    ID-COM

    183 (7,2")

    80(3,1")

    42,5(1,7")

    24(0,9")

    47(1,8")

    ~110(4,3")

    170 (8,87")

    RS232

    123(4,8")

    110(4,4")

    Cutout

    for InteliDrive

    113 x 175 mm

    (4.4 x 6,9)

    ID-DCU box is fixed using four screw clips.

    I-RB.. technical description

    Relay board contains 16 or 8 relays for ID-DCU binary (open collector) output separation. All relays areplaced in sockets.

    Product options

    I-RB16 16 relays, load 24 VDC

    I-RB8 8 relays, load 24 VDC

    I-RB16-231 16 relays, load 231 VAC

    I-RB8-231 8 relays, load 231 VAC

    Number relays: 16 or 8 in socketsNominal voltage: 24 VDCVoltage range: 16,8 36 VDCRelay opens at: 10% of nominal voltageElectric / mechanic cycles: 100 000 / 10 000 000Operating temperature range: - 40C to 70CMaximal load: 6 A resistive load at 24VDC

    4 A inductive load at 24 VDC2 A at 231VAC

    Contacts protection: varistor 14DK390 between 1-2 and 1-3

    1

    K

    2 3

    1.2 n.o.1.3 n.c.

    ID-DCU-Marine-2.1, ComAp February 2012 23ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    24/152

    Mechanical dimension

    I-RB16 is 35 mm DIN rail mounted. One unit contains two parts (separate PCB) 8 relays each on commonplastic base.

    I-RB16, I-RB8 is 60mm high from DIN rail base.

    16

    X17

    11 1 11 1 11

    1 +

    X18

    11 1 11 1 11

    RE1

    RE2

    RE3

    ER4

    RE5

    RE6

    RE7

    RE8

    RE9

    RE10

    RE11

    ER12

    RE13

    RE14

    RE15

    RE16

    X3 X1X2X6 X4X5X8 X7X11 X9X10X14 X12X13X16 X15

    9 + 8

    16 X18 9 +View B

    X18

    8 X17 1 +

    View B

    3 X1 1

    X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X14 X15 X16

    View A

    3 X2 1 3 X3 1 3 X4 1 3 X5 1 3 X6 1 3 X7 1 3 X8 1 3 X9 1 3 X10 1 3 X11 1 3 X12 1 3 X13 1 3 X14 1 3 X15 1 3 X16 1

    View A

    300

    95

    X17

    Hint:I-RB16 contains two separate boards, 8 relay each.

    ECU

    Electronic Control Unit (fuel injection unit) is kind of extension module connected to CAN1 bus andcommunicating via J1939 protocol. Generally can read up to 16 binary and analog values from engine(inputs) and transmit up to 16 binary outputs (e.g. Start, Stop commands) and four Analog outputs (e.g.Speed request). ECU Size = Large is extended version of electronic control unit containing doubled numberof inputs / outputs in respect of Standard ECU.

    IS-BIN16/8

    Extension module with 16 binary inputs and 8 binary outputs. All I/O can be configured to any logical functionor protection - see chapter Binary inputs and Binary outputs. RPM1 and RPM2 inputs are not supported inInteliDrive.

    IS-BIN16/8 module is connected on InteliDrive CAN1 bus. The corresponding module Address must be seton module and in controller configuration. Communication fail is indicated in controller Alarm list and bybinary outputs Comm BIN fail, Comm BOUT fail. Use DriveConfig PC tool for controller configuration.

    The Binary I/O specification see in chapter Technical data.

    ID-DCU-Marine-2.1, ComAp February 2012 24ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    25/152

    45 (1,8")146 (5,7")

    160(6,3") 40 (1,6")

    25 (1,0")

    IN1-

    RPM+

    IN2

    IN1+

    RPM-

    IS-BIN16/8 unit is DIN rail mount (35mm)

    IS-AIN8

    Extension module with 8 analog inputs. All inputs can be configured to any logical function or protection - seechapter Analog inputs.

    IS-AIN8 module is connected on InteliDrive CAN1 bus. The corresponding module Address must be set onmodule and in controller configuration. Communication fail is indicated in controller Alarm list and by binaryoutput Comm AIN fail. Use DriveConfig PC tool for controller configuration.

    The analog inputs specification see in chapter Technical data.

    ID-DCU-Marine-2.1, ComAp February 2012 25ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    26/152

    46,4 (18,3")

    40 (15,7")

    25 (9,8")

    70 (27,5")

    146 (57,5")

    160(63")

    POWER8 - 36V DC

    COM

    COMCAN CAN

    RS 232

    H HL L

    +

    iS-AIN8

    IS-AIN8 unit is DIN rail mount (35mm)

    IS-AIN8TC

    Extension module with 8 thermocouple analog inputs, i.e. it is simplified IS-AIN8 module with the samedimensions. Thermocouple types J, K, L are supported.

    ID-DCU-Marine-2.1, ComAp February 2012 26ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    27/152

    IGL-RA15 Remote annunciator

    Remote (CAN1 bus, up to 200 meters) 15 LEDs states indicator. One iGL-RA15 unit can be connected to ID-DCU via CAN1 as Binary output group of addresses 5 and 6. Detail descriptions see in IGL-RA15.pdf userguide.Communication fail is indicated in controller Alarm list and by binary outputs Comm BOUT fail. UseDriveConfig PC tool for controller configuration.

    165 (6,5)

    38(1,5)

    40(1,6)

    ~75(3,0)

    ~35(1,4)

    180 (7,1)

    185 (7,3)

    106(4,2)

    44 (1,7)

    54 (2,1)

    ~25(1,0)

    120(4,7)

    125(4,9)

    Cutoutfor Remote Annunciator

    167 x 108 mm(6,6 x 4,3)

    IGS-PTM

    Extension module with 4 analog inputs, 8 Binary I/O. All I/O can be configured to any logical function orprotection - see chapter Binary inputs, Binary outputs and Analog inputs.

    IGS-PTM module is connected on InteliDrive CAN1 bus. The corresponding module Address (1 to 4) mustbe set on module and in controller configuration. Communication fail is indicated in controller Alarm list andby binary output CommBIN fail, CommBOUT fail, CommAIN fail. Use DriveConfig PC tool for controllerconfiguration.

    Any analog input can be configured for range:

    0 250 (suitable for Pt100, Ni100),

    0 100 mV (suitable for thermocouples),

    0 20 mA.

    Detail description see in IGS-PTM-1.0.pdf manual.

    ID-DCU-Marine-2.1, ComAp February 2012 27ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    28/152

    95 mm(3,7)

    43 mm(1,7)

    9

    6mm

    (3,8)

    COMPENSATION

    GND

    POWER

    8-36V DC

    BINARY OUTPUTS

    BINARY INPUTS ANALOG INPUTS

    AI4

    BI8

    BI7

    BI6

    BI5

    BI4

    BI3

    BI2

    BI1

    0-20 mA

    ANALOG OUT

    BO8

    BO1

    BO2

    BO3

    BO4

    BO5

    BO6

    BO7

    CAN

    Rx

    Tx

    CAN

    L

    H

    COM

    LB 4

    AO-

    AO+

    iGS-PTM

    IGS-PTM unit is DIN rail (35mm) mounted.

    I-AOUT8

    Extension module with 8 analog outputs. All outputs can be configured to any logical function - see chapterAnalog outputs.

    I-AOUT8 module is connected on InteliDrive CAN1 bus. The corresponding module Address 1 to 4 (default1) must be set on module (by Adr.1 and Adr.2 jumpers) and in controller configuration. Communication fail isindicated in controller Alarm list and by binary output Comm AOUT fail. Use DriveConfig PC tool forcontroller configuration.

    Each analog output can be switched by jumper for.- 0 to 20 mA- 0 to 10 VDC (default)- Pwm (Pulse Width Modulation on 1,2 kHz)

    Module is 35 mm DIN rail mounted. CAN1 terminating 120 resistor jumper is connected in default. AGNDterminals are on the same potential.

    95 mm (3,7)43 mm(1,7)

    96mm(3,8

    ')

    Power

    supply

    I-AOUT8ComAp

    HW:

    SW:

    +8-36VDC

    GND

    AGND

    AOUT5

    AGND

    AOUT6

    AGND

    AOUT7

    AGND

    AOUT8

    ANALOG OUT PUT S

    AOUT1

    AGND

    AOUT2

    AGND

    AOUT3

    AGND

    AOUT4

    AGND

    ANALOG OUT PUT S

    CANL

    CCOM

    CANH

    CAN

    U - I - p U - I - p U - I - p U - I - p

    p - I - U p - I - U p - I - U p - I - U

    1 2 Pwr

    120 ohm

    ID-DCU-Marine-2.1, ComAp February 2012 28ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    29/152

    FunctionsNumber of analogoutputs

    8, no galvanic separation

    Type of analog outputs(jumper selectable)

    UIp

    0 to 10VDC 1% , max 5 mA

    0 to 20 mA 1% , max 500 - defaultpwm 1200 Hz, 5V level, max 10 mA

    Power supply 8 to 36 VDC

    Current consumption 100 300 mA at 24 VDCCommunication interface CAN1, with jumper selectable address 1 to 4

    Jumper selectable terminating resistor 120 .

    RS232 interface TTL, firmware upgrade via AT-link.

    Operating temperaturerange

    -40C to +70C

    Analog outputsrefreshment

    Max. 300 ms

    CAN address jumper settingUp to four modules can be connected to one controller. Set module CAN address corresponding toconfiguration according table below.

    CAN Address Jumper 1 Jumper 21 No No

    2 Yes No

    3 No Yes

    4 Yes Yes

    Analog output hardware modificationFollow the p-I-I-U symbols on the module sticker. There are two equivalent positions for mA measuring.

    AOUTjumper

    Symbol Function

    p PwmPuls-With-Modulation

    I 0 to 20 mA

    U 0 to 10 VDC

    LED indicationGreen LED is located near the power supply connector.

    I-AOUT8 module state LED Pwr

    No power supply Dark

    Memory fail Fast blink (100/100 ms)

    Communication fail Slow blink (300/300 ms)

    OK Continuous light

    ID-DCU-Marine-2.1, ComAp February 2012 29ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    30/152

    Wiring and jumper setting exampleVoltage output0 to 10 VDC

    Current output0 to 20 mA

    Current output0 to 20 mA

    Pwm output

    5V, max 10 mA

    AGND

    AOUT

    AGND

    AOUT

    max 500ohm

    +

    +

    +

    max 5 mA

    +

    AGND

    AOUT

    max 500ohm

    AGND

    AOUTPwm output1200 Hz

    Current output0 to 20 mA

    Current output0 to 20 mA

    Voltage output0 to 10 VDC

    Hint:Extension module communication fail can be configured in DriveConfig to No protection, Warning, Shutdown.

    I-LB+ Communication BridgeI-LB+ is communication modules for communication with all devices connected to CAN2 bus. I-LB+ issuccessors of the IG-MU unit designed to be used with ComAp controllers. It therefore provides additionalcommunication port and higher communication speed. Speed for direct/modem connection can be up to57600 bps (IG-MU only 19200 bps). I-LB+ can be connected with PC via USB, RS232 or RS485.

    For more details seeAccessory Modules for IG-NT, IS-NT and ID-DCUdocument on ComAp web pageshttp://www.comap.cz/.

    ID-DCU-Marine-2.1, ComAp February 2012 30ID-DCU-Marine-2.1.pdf

    http://www.comap.cz/http://www.comap.cz/
  • 7/30/2019 Id Dcu Marine 2.1

    31/152

    IG-IB Internet bridge

    Internet interface unit for single or multiple engines.

    95 mm(3,7)

    43 mm(1,7)

    96mm

    (3,8)

    It is recommended to use IG-IB firmware version 2.0IG-IB unit is DIN 35 mm rail mounted.

    I-CB communication bridge

    I-CB (Communication bridge) is programmable CAN1 bus interface between InteliDrive and Engine ControlUnits (like MTU, CAT etc.) without standard J1939 communication protocol. Engine values from ECU (RPM,Oil pressure and other) are converted to standard InteliDrive I/O protocol.

    Use ICBEdit software for I-CB configuration.

    ID-DCU-Marine-2.1, ComAp February 2012 31ID-DCU-Marine-2.1.pdf

    POWER

    8-36V DC

    COM

    RS

    232

    LB 4i-CB

    95 mm(3,7)

    43 mm(1,7)

    96mm

    (3,8)

  • 7/30/2019 Id Dcu Marine 2.1

    32/152

    Recommended wiring

    ID-RPU wiring

    14

    BATT A BATT B

    + + --

    +24VDC

    0VDC

    Max8A

    Max8A

    2

    2

    n.o.n.c.

    + -

    K17 K18

    I-RB16

    9 9

    1 2 3

    16x

    K1-K16

    5x10kohm

    Hint:BW protection of the ID-RPU outputs Fuel solenoid and Stop solenoid is active in open state only.

    To avoid BW detection configure not wired inputs or outputs of ID-RPU as Not used by DriveConfig sw.

    Battery minus terminals are separated.

    ID-DCU-Marine-2.1, ComAp February 2012 32ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    33/152

    Wiring example

    14

    L H

    H

    -

    A

    B

    12345678

    H

    L

    A

    B

    CAN2

    CAN1

    ID-COM

    +

    L

    CAN2

    J1587

    J1939

    K 17 K 18

    I-RB16

    9 9

    1 2 3

    16x

    K1-K16

    120 ohm

    120ohm

    CAN2

    59

    HL

    IS-BIN

    L

    H

    IS-AIN

    L

    H

    IGS-PTM

    L

    H

    120ohm

    + -POWER

    + -POWER

    + -POWER

    120 ohm

    IG-IBIG-MU

    + -POWER

    + -POWER

    L HL H

    120ohm

    Complete system without RPU

    14

    L H

    H

    -

    A

    B

    12345678

    H

    L

    A

    B

    CAN2

    CAN1

    ID-COM

    +

    L

    CAN2

    J1587

    J1939

    K17 K18

    I-RB16

    9 9

    1 2 3

    16x

    K1-K16

    120 ohm

    120ohm

    CAN2

    59

    HL

    IS-BIN

    L

    H

    IS-AIN

    L

    H

    IGS-PTM

    L

    H

    120ohm

    + -POWER

    + -POWER

    +-

    POWER

    120 ohm

    IG-IBIG-MU

    + -POWER

    + -POWER

    L HL H

    120ohm

    ID-DCU-Marine-2.1, ComAp February 2012 33ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    34/152

    Electronic engine without redundancy line

    14-

    12345678

    H

    L

    A

    B

    +

    J1

    939

    K17 K18

    I-RB16

    9 9

    1 2 3

    16x

    K1-K16

    CAN1

    59

    HL

    120ohm

    IS-BIN

    L

    H

    IS-AIN

    L

    H

    IGS-PTM

    L

    H

    120ohm

    + -POWER

    + -POWER

    + -POWER

    120 ohm

    Engine without ECU (mechanical engine)

    14

    K17 K18

    I-RB16

    9 9

    1 2 3

    16x

    K1-K16

    CAN1

    59

    HL

    1

    20ohm

    IS-BIN

    L

    H

    IS-AIN

    L

    H

    IGS-PTM

    L

    H

    120ohm

    + -POWER

    + -POWER

    + -POWER

    120 ohm +-

    ID-DCU-Marine-2.1, ComAp February 2012 34ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    35/152

    Scania S6 wiring example

    CAN L

    CAN H

    STARTER LOCK

    KEY

    +24V

    GND

    +24VStarter

    relay

    STARTER LOCK KEY B1-3 pin can be used for engine Emergency stop when ID-RPU unit is used. ConnectB1-3 to ID-RPU Binary output Fuel solenoid and configure this output to CPU ready (to avoid lost ofcommunication during each engine stop).

    Function in ID-DCU operational mode: engine Start/Stop is processed via J1939 CAN bus and STARTERKEY LOCK is all time on +24 volts (CPU ready on Fuel solenoid output is still closed).

    Function in ID-RPU backup mode: Hard-wired Fuel solenoid function is activated in the RPU backup mode.In the case of engine shut down is this Fuel solenoid output switched off and activates engine Emergencystop (deactivation of STARTER LOCK KEY).

    The starter must be operated via A1-6 pin according drawing above when EDC control unit is configured tostart engine via J1939 CAN bus.

    Bus/Communication architecture

    RS232One of following possibilities is available:

    PC software interface (DriveConfig, DriveMonitor).Modbus protocol option for SCADA systems.Analog or GSM Modem interface.IG-IB internet interface.

    ID-DCU-Marine-2.1, ComAp February 2012 35ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    36/152

    CAN1 / J1939 / KWP2000CAN1 is data line for controller Inputs/Outputs extension. It is possible to connect following extensionmodules:

    ECU (Engine Control Unit),IGS-PTM (8 BI, 8BO, 4AI, 1AO),IS-AIN (8AI),IS-BIN (16BI, 8BO).

    Full physical CAN interface on ID-DCU is available, no ID-COM interface needed. Maximal CAN bus lengthis up to 200m.

    CAN2Inter-controller CAN for multiple engines applications. ID-COM module is necessary. It is possible to connect

    ID-DCU Marine controllers and/orIG-MU (Direct cable, analog modem or GSM modem interface) and/orIG-IB (Internet interface) and/orI-RD-CAN remote display (Slave panel).

    There are some limits for number of modules connected to CAN2 see Rules for I-RD, I-LB+ and IG-IB CANaddress setting. The data rate is selectable in two levels: 250 kBd for 200 meters line and 62 kBd for 900meters line.

    Redundancy line (e.g.J1708)There are 2 datelines in the system, one CAN SAE J1939 datalink and one SAE J1708/J1587 datalink. TheJ1939 datalink is used for control and monitoring data. The J1708/J1587 datalink is used for redundancycontrol and monitoring.

    The ID-COM interface is necessary to use for synchronous J1708/1587 data line.

    CAN bus Connection rulesCAN bus line must be connected in series, from one unit to the next (no star, no cable stubs,no branches)

    both ends must by the 120 (internal or external) resistor terminated.Maximal CAN2 bus length is up to 200 meters when Basic settings: CAN bus mode = 250 kBd or up to 900

    meters when Basic settings: CAN bus mode = 50 kBd.For CAN data cables details see chapter Technical data Communication interface. CAN cable shieldingconnect to ID-DCU case.

    ID-DCU contains internal fix 120 resistor on CAN1 bus. Use D SUB9 male connector: CAN H = 5, CAN L =9, COMMON = 3 and 8. ID-DCU must be on the CAN bus end.

    IGS-PTM units contains internal jumper-removable 120 resistor. To be sure check resistor presence byohmmeter. Unit with internal resistor should be connected to the end of CAN2 line.

    I-CB wiring and configuration

    CAN H

    CAN L

    Engine

    Control Unit

    120ohm

    Controller

    CAN H

    CAN LCANL

    CANHCO M

    CANL

    CAN HCO M

    CAN H

    CAN L

    I-CB

    CAN 1 CAN ECU

    ECU

    12

    0ohm

    CAN1

    CAN2

    1. Configure I-CB using I-CBEdit software. Configured I-CB behaves like fictive IS-AIN and IS-BIN units. I-CB configuration associates selected values (from ECU database) received from Engine Control Unit toselected CAN addressees (fictive IS-AIN, IS-BIN inputs and outputs).

    2. Configure corresponding CONTROLLER CAN addresses in PC configuration tool.3. Configure separate inputs and outputs in corresponding Analog, Binary inputs, outputs in PC

    configuration tool.

    Hint:In case of CAT engines, there is RS232 connection between I-CB and CCM.

    ID-DCU-Marine-2.1, ComAp February 2012 36ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    37/152

    Getting started

    How to install

    Hint:All components shall be used within marked electrical ratings see chapter Technical data.

    GeneralTo ensure proper function:

    Use grounding terminals.Wiring for binary inputs and analog inputs must not be lead parallel with high voltage/current cables.Analog and binary inputs should be provided with shielded cables, especially when length >3m.

    Power supplyUse min. power supply cable of 1.5 mm2 to ensure proper function.Maximum continuous DC power supply voltage is 36VDC. Maximum allowable power supply voltage is

    39VDC see chapter Technical data.

    For redundancy power supply use ID-RPU module see chapter Recommended wiring.

    +

    +

    Battery

    -

    -

    controllerand load

    HUGELOADS

    STARTER

    T2,5 A

    Hint:The InteliDrive controller should be grounded properly in order to protect against atmospheric discharges!Install separate conductors for signal and power inputs. Allow for conductor voltage drop when determiningconductor size. All power supplies must have common ground.When there is a potential risk of the controller being subjected to conditions outside its capabilities - an

    outside protection device should be used.

    Power supply fusingExternal fuse rated max. 2.5A shall be used to limit current from the power supply to the controller andmodules. Controller and I/O modules should never be connected directly to the starting battery.Fuse value and type depends on number of connected devices and wire length.Recommended fuse (not fast) type - due to internal capacitors charging during power up.

    Binary output protectionsDo not connect binary outputs directly to DC relays without protection diodes. Use protection diodes even ifthe relays are not connected directly to controller outputs. Use a fast recovery 3A / 50V diodes.

    ID-DCU-Marine-2.1, ComAp February 2012 37ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    38/152

    +

    -

    K1K1

    K2K2

    24VDC+-

    controller

    Fuse

    Fuse

    Battery

    DC relays

    Fuse

    Example of controller protectionHint:External fuse rated max. 2.5A shall be used to limit current from the binary outputs.

    GroundingTo ensure proper function:

    The shortest possible piece of wire should be used when grounding the controller.Use cable min. 2,5mm2 .The - terminal of the battery has to be properly grounded.

    Magnetic pick-upTo ensure proper function use a shielded cable.

    +

    Battery

    -

    GA CSpeed Control Unit

    ESD 5500

    MAGNETICPICK-UP

    CD

    Signal

    Signal

    +

    +-

    -PowerSupply

    PowerSupply

    GN D

    RPM-IN

    controller

    Be aware of interference signal from Speed governor when one speed pick-up is used.

    ID-DCU-Marine-2.1, ComAp February 2012 38ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    39/152

    ID-DCU Analog inputs hardware configuration

    Configure Analog inputs AI1-AI8 connection by jumpers on PCB (remove cover).

    Controller default jumper setting from production

    AI1 to AI4 Current sensorAI5 to AI8 Resistance sensor

    Grounding Terminal

    BOOT JUMPER

    BINARYINPUTSRPM

    BINARYINPUTSANALOG INPUTS

    BINARY OUTPUTS POWER

    8 -36 VDC

    EXTENSIONMODULE

    ID-R

    PU

    RS232

    LB1

    EXTENSION

    MODULE

    ID-C

    OM

    + -RPM

    GND

    RPM

    IN

    BI1

    BI2

    BI3

    BI4

    BI5

    SHIELD

    COM

    D+

    BO1

    BO2

    BO3

    BO4

    BO5

    BO8

    BO6

    BO12

    BO13

    BO14

    BO9

    BO7

    BO10

    BO11

    AIN1

    AIN2

    AIN3

    AIN4

    AIN6+

    AIN5+

    AIN8+

    AIN8-

    AIN6-

    AIN5-

    AIN7+

    AIN7-

    BI6

    BI7

    BI8

    BI9

    BI10

    BI11

    BI13

    BI12

    BI14

    1234

    AI1AI2AI3AI4

    1234 A

    I5+

    AI6+

    AI7+

    AI8+

    Jumpers setting

    1234 Current

    Measurement Jumper on pins 1-2.

    1234

    Voltage (thermocouplesAI5-AI8) measurement Jumper on pins 2-3.

    1234 Resistance

    measurement- Jumper on pins 3-4.

    Hint:Maximal voltage on controller Differential analog inputs AI5 to AI8 is in the range 2 to +5 VDC againstminus power supply terminal!

    ID-DCU-Marine-2.1, ComAp February 2012 39ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    40/152

    ID-DCU Analog inputs software configuration

    See table below

    Protections:

    No protection

    Warning

    Sensor fail

    Colldown

    Shutdown

    Alarm only

    HistRecord only

    Protections:

    No protection

    Warning

    Sensor fail

    Colldown

    Shutdown

    Alarm onlyHistRecord only

    Protections:

    No protection

    Warning

    Sensor fail

    Colldown

    ShutdownAlarm only

    HistRecord only

    Sensor

    characteristics

    +

    RI

    Analog inpu t

    Protections:

    No protection

    Warning

    Sensor fail

    Colldown

    Shutdown

    Alarm only

    HistRecord only

    Logical analog

    input list

    Analo g outpu t

    Binary outputs

    State machine

    Hardware

    jumper

    ID-DCU

    Value

    Bargraph

    Hint:ID-DCU hardware jumper must correspond with software configuration.

    ConfigurationSee drawing above.

    Property Value

    Name Value name is displayed on the screens and in the Alarm list and History record.

    Enter up to 14 ASCII characters.Name is automatically set to Function name if function is selected from the Logicalfunction list see Function item.

    Dim Dimension is displayed on the screens. Select dimension from the list or add a new one.

    Sensor Select sensor from the list or create a customer sensor characteristics in User sensorwindow. There must be corresponding analog input hardware jumper setting inInteliDrive controller. See Sensor availability in table below.

    Resolution Output value (reading) resolution. DriveConfig indicates when Resolution is out of thevalue range.

    Sensor range Full output value (reading) range for 20 mA (current), 250 , 2400 (resistive), 1 V, 100mV (voltage) sensor.

    Protection type Select from the list. Configure two levels protection as standard or more levels (window)protection in Expert mode.

    Active when Configure direction Over or Under limit when protection is activated.Block type Configure protection activity: All the time or Engine running with three different adjustable

    delays when protection is active after engine start (RPM > Starting RPM).

    Bargraph 100% Value for bargraph full scale.

    Function Select from the list if function is required or leave free if input is a protection only.

    Hint:Some configuration items (e.g. Protection) stay without change when Property - Sensor is changed to None.

    ID-DCU-Marine-2.1, ComAp February 2012 40ID-DCU-Marine-2.1.pdf

    20mA = 10,0 Bar

  • 7/30/2019 Id Dcu Marine 2.1

    41/152

    Sensors availabilitySensors available on ID-DCU AI1 AI4 Resolution Sensor range HW jumper

    Pt1000/C, Ni1000/C,Pt1000/F, Ni1000/F

    Fix, not configurable Resistance: 3-4

    4-20 mA active,20 mA active (measures + only)

    Adjustable -see Hintbelow.

    For 20 mA input Current: 1-2

    0-250 , 0-2400 For 250 or 2400

    Input

    Resistance: 3-4

    Tristate Resistance: 3-4

    0 to 4VDC Adjustable Voltage: 2-3

    Sensors available on ID-DCU AI5 AI8 Resolution Sensor range HW jumper

    Pt100/C, Pt1000/C, Ni100/C, Ni1000/C,Pt100/F, Pt1000/F, Ni100/F, Ni1000/F Fix, not configurable

    Resistance: 3-4

    Thermocpl J/C, Th. K/C, ThL/C,Thermocpl J/F, Th. K/F, ThL/F Fix, not configurable Voltage: 2-3

    4-20 mA active, 20 mA active Adjustable -see Hintbelow.

    For 20 mA input Current: 1-2

    0-250 , 0-2400 For 250 or 2400 input

    Resistance: 3-4

    1 V, 0-100mV For 1V or 100mV Voltage: 2-3

    Tristate Resistance: 2-3

    Hint:Out of range resolution (e.g. 100,000) is indicated in DriveConfig.

    ID-DCU-Marine-2.1, ComAp February 2012 41ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    42/152

    Configuration examples Conversion from 4-20mA to 6,0 Bar Oil pressure sensor (Wrn+Sd protection and Oil pressure function)

    Conversion from 1V input to engine speed request 0 to 100%Step 1. Create new User sensor

    Hint:HW configuration: CU 0-1V can be used for characteristics 1V, but this characteristics can be configuredto AI5 to AI8 inputs only!Sensor range (gray background) automatically follows the User sensor characteristics (zero value in drawingabove is not important).

    ID-DCU-Marine-2.1, ComAp February 2012 42ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    43/152

    Conversion from 20mA to 100% request

    Request[%]

    -20mA

    20mA

    +100%

    mA

    0mA

    -100%

    Sensorfail

    Sensorfail

    Bargraph

    0% +100%

    Sensor characteristics 20mA works in full range on ID-DCU AI5 toAI8 only. ID-DCU AI1 to AI4 measures 0 to 20 mA range only.

    Default sensor characteristics creates conversion to 100%.

    Bargraph indicates only positive values 0 to +100%.

    ID-DCU-Marine-2.1, ComAp February 2012 43ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    44/152

    Conversion from 20mA to +100% request with User sensor

    -20mA

    20mA

    +100%

    mA

    0mA

    0%

    +50%Request[%]

    Sensorfail

    Sensorfail

    Bargraph indication

    0% 100%

    Sensor characteristics 20mA works in full range on ID-DCU AI5 toAI8 only. ID-DCU AI1 to AI4 measures 0 to 20 mA range only.

    Step 1. Create User sensor like below.

    Step 2. Configure user sensor instead default 20mA sensor.Step 3. Configure Bargraph 100% to correspond User sensor.

    Bargraph indicates full 0 to 100% range in this case.

    1. Step: Create User sensor like below.

    2. Step: Configure user sensor instead default 20mA sensor.

    ID-DCU-Marine-2.1, ComAp February 2012 44ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    45/152

    User sensor examples

    Availability Configuration

    AI1 to AI4AI5 to AI8

    Analog inputjumper = 1-2(current)

    0 - 20mA / 600

    AI1 to AI4AI5 to AI8

    4 - 20mA / 100,0

    AI5 to AI8

    Analog inputjumper = 2-3(voltage)

    0 1V / 10,000

    AI5 to AI80 - 100mV / 100,00

    AI1 to AI4AI5 to AI8

    Analog inputjumper = 3-4(resistance)

    0 1200 / 100

    Hint:It is possible to set up to 30 points non-linear sensor characteristics.Connect external resistors (voltage divider) to extend input voltage range.

    ID-DCU-Marine-2.1, ComAp February 2012 45ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    46/152

    Hardware connection

    Connection of ID-DCU analog inputs

    ID-CU

    COM

    -POWER

    AI4

    AI3

    AI2

    AI1

    AI6-

    AI6+

    AI5-

    AI5+

    AI8-

    AI8+

    AI7-

    AI7+

    All jumpers in position (3-4)

    Standard connection of resistive sensors to ID-DCUanalog inputs AI1 to AI8. The COM terminal mustbe always connected to the negative powerterminal.

    v

    +

    v+

    -

    COM

    -POW

    ER

    AI1(3-4)

    AI4

    AI3(2-3)

    AI2(1-2)

    AI6-

    AI6+

    AI5-

    AI5+

    AI8-

    AI8+

    AI7-

    AI7+(

    3-4)

    (

    1-2)

    (

    1-2)

    (

    2-3)

    +

    Different sensors connection to ID-DCU. AIconfiguration jumpers must be in corresponding

    position and corresponding DriveConfigconfiguration according to used sensor.

    Analog input common terminal COM has to beconnected to ID minus Power supply terminal.

    Mixed connection of ID-DCU analog inputs:AI2, AI7 current sensorAI1, AI5 resistive sensorAI3, AI8 voltage inputAI6 thermocouple (voltage)AI4 Not used

    ID-CU

    COM

    -POWER

    AI4

    AI3

    AI2

    AI1

    AI6-

    AI6+

    AI5-

    AI5+

    AI8-

    AI8+

    AI7-

    AI7+

    All jumpers in posit ion (3-4)

    2x470ohms

    2x470ohms

    Mixed connection of InteliDrive analog inputs:

    AI1, AI2, AI5, AI6 resistive sensorAI3, AI7 binary inputAI4, AI8 three state input

    Analog input common terminal COM has to beconnected to ID minus Power supply terminal.

    To ensure a proper function use shielded cables, especially for length over >3m.

    Analog inputs on IS-AIN8

    IS-AIN8 analog inputs can be configured to

    Resistor two wire input

    Resistor three wire input

    Current input

    Thermocouple input

    Voltage input

    Select sensor characteristic from the list or define user sensor characteristic in DriveConfig.

    ID-DCU-Marine-2.1, ComAp February 2012 46ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    47/152

    A

    B

    C

    D

    Resistor sensor input two wire connection.

    Range 0 to 2400 .Pt100, Pt1000, Ni100, Ni1000D terminal is shielding

    A

    B

    C

    D

    Resistor sensor input three wire connection.

    Range 0 to 2400 .Pt100, Pt1000, Ni100, Ni1000 recommended.D terminal is shielding

    A

    B

    C

    D

    Passive current sensor (current source is in IS-AIN8)Range 0 to + 20 mA or 4 to + 20 mA

    D terminal is shielding

    A

    B

    C

    D

    + +24 VDC

    0 VDC

    Sensor

    mA

    A

    B

    C

    D

    +

    +24 VDC

    0 VDC

    SensormA

    Active current sensor (current source is in sensor)Range 20mA to +20 mA or 4 to + 20 mA

    D terminal is shielding

    A

    B

    C

    D

    + Thermocouple J, K, LD terminal is shielding

    From IS-AIN8 hardware version 5.1 can be B thermocoupleterminal connected to frame.

    A

    B

    C

    D

    +

    Voltage inputRange 0 to + 2500 mV.Voltage range is 0 to 1000 mV.

    D terminal is shielding

    A

    B

    C

    D

    +

    R1

    R2

    For 10V input voltage range connect external resistors R1, R2and select sensor characteristic 10V.

    R1=10 k, R2=2,7 k

    D terminal is shielding

    HintThermocouples connected to IS-AIN8 hardware versions below 5.0 must be galvanically separated from theframe.

    If the thermocouples are connected to IS-AIN8, appropriate jumpers must be removed (see rear sticker).

    ID-DCU-Marine-2.1, ComAp February 2012 47ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    48/152

    Analog inputs on IS-AIN8TC

    IS-AIN8TC analog inputs can be configured to Thermocouple input only.

    Select sensor characteristic from the list or define user sensor characteristic in DriveConfig.

    A

    BC

    D

    +Thermocouple J, K, LD terminal is shielding

    Analog Sensor availabilityTable of supported sensors on various modules. Do not configure sensors that are not supported on theinput.

    ID AI1-4 ID AI5-8 IGS-PTM IS-AIN8 IS-AIN8TC

    PT100/C Y Y Y

    PT1000/C Y Y Y

    NI100/C Y Y YNI1000/C Y Y Y

    PT100/F Y Y Y

    PT1000/F Y Y Y

    NI100/F Y Y Y

    NI1000/F Y Y Y

    Thermo J/C Y Y Y

    Thermo K/C Y Y Y

    Thermo L/C Y Y Y

    Thermo J/F Y Y Y

    Thermo K/F Y Y Y

    Thermo L/F Y Y Y

    4-20mA passive Y4-20mA active Y Y Y Y

    0-20mA passive Y

    +-20mA active Y Y Y Y

    0-250 Y Y Y Y

    0-2400 Y Y Y

    0-2.4V Y

    0 4V Y

    Tristate Y Y

    +-1V Y Y

    0-10V Y

    0-100mV Y Y Y

    Hint:Fahrenheit sensors are supported from IS-AIN8 of sw version 2.2 only.

    Analog as Binary inputTo use Analog input as binary configure following characteristics:

    Primary Converted

    0 0

    1000 1

    Analog as three state (tristate) binary inputOpen, close and failure (broken wire, short wire) states are detected. Threshold level is 750 , failure is

    detected when circuit resistance is 2400 .

    ID-DCU-Marine-2.1, ComAp February 2012 48ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    49/152

    Binary inputs / outputs on ID-DCU

    Use wiring cables min. of 1.0 mm2 to ensure proper function.

    +24VDC

    0VDC

    BI1

    BI2

    BI3

    BI4

    BI5

    BI6

    BI7

    BI8

    BI9

    BI10

    BI12

    BI13

    BI14

    BI11

    +

    BO7

    BO8

    BO9

    BO10

    BO12

    BO13

    BO14

    BO11

    ID-DCU

    BO1

    BO2

    BO3

    BO4

    BO5

    BO6

    Hint:Incorrect polarity of the binary output connection may cause a damage of the binary outputs.

    Binary inputs on IS-BIN16/8

    There are two groups of eight Binary inputs BI1 to BI8 and BI9 to BI16. Each group has a separate Commonterminal COM1 and COM2. The Common terminal can be connected to positive or negative pole seefollowing drawing. Binary inputs are galvanically separated from IS-BIN16/8 power supply.

    A Binary inputs Common terminal is connected topositive supply terminal, Binary inputs contacts areclosed to negative supply terminals.

    Binary inputs common terminal is connected tonegative supply terminal, Binary inputs contacts areclosed to positive supply terminals.

    BI 1 (BI 9)

    BI 2 (BI 10)

    BI 3 (BI 11)

    BI 8 (BI 16)

    COM 1 (COM 2) +

    8 - 36 V

    -

    IS-BIN1

    6/8

    +

    8 - 36 V

    -

    BI 1 (BI 9)

    BI 2 (BI 10)

    BI 3 (BI 11)

    BI 8 (BI 16)

    COM 1 (COM 2)

    IS-BIN1

    6/8

    Input voltage range for opened contact is from 8 VDC to Power supply VDC. Input voltage range for closed

    contact is from 0 to 2 VDC. Voltage level is defined between Binary input and Binary input COM terminal anddoes not depend on positive or negative connection.

    Hint:It is recommended to separate inputs by diodes when two or more binary inputs are connected in parallel toavoid wrong input activation when one controller is switched off.

    controller

    BIBI

    controller

    ID-DCU-Marine-2.1, ComAp February 2012 49ID-DCU-Marine-2.1.pdf

  • 7/30/2019 Id Dcu Marine 2.1

    50/152

    Binary outputs on IS-BIN16/8

    IS-BIN16/8 binary outputs are galvanically separated from IS-BIN16/8 power supply. It is necessary toconnect plus 24 VDC (power supply) to IS-BIN16/8 terminal according to following drawing.The maximum load values are 0.5 A / 36V for one output.

    IS-BIN1

    6/8

    BO