Page 1: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

I-CB/Modbus

1/ Fields of application

Page 2: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Fields of application

PLC

Breaker

FlowmeterECU

Gauge

ModbusRTU

Page 3: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Fields of application

ModbusDevices

ComApRemote

monitoring (BMS)

I-CB/Modbus IG/IS-NT InteliMonitor SCADA

Modbus Master

Page 4: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Advantages

Save money for extra

converters

One connection point for remote

monitoring

Easy configuration

All data in InteliMonitor

SCADA

Fully configurable

interface

Page 5: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Connection

CAN1IG/IS-NT

Peripheral CAN bus

RS232RS485

Page 6: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Connection

JumperTerminating

resistor

JumperSelection RS232/RS485

JumperTerminating

resistor

Page 7: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

LED indications

Page 8: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Configuration

ICBEdit

Page 9: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Configuration

File

New

Select protocol window

Protocol = MODBUS

Subprotocol

Page 10: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Configuration

Subprotocol

Predefined

CAT EMCP

Cummins PCC

Schneider

TemplateEmpty

configuration (any device)

Page 11: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Advanced configuration

Config

Advanced config

Advanced configuration window

Page 12: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Advanced configuration

Baud rateSelect baud rate for your device (9600 / 19200 / 38400 bps)

Set number of stop bits

Set parity (None, Odd, Even)

Maximal length of data that can be

read by one request in bytes

Enables optimization, i.e.

reading of neighbouring

registers in one request

Maximum number of registers that can

be read by one request

I-CB sets communication

drop out alarm after it doesn’t receive answer within this

timeout

Not to be changed by user

Request delay – after this time next request is issued

after receiving previous answer

Not to be changed by user

Page 13: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Reading procedure

Wait for Refresh

period of any register

Read that register

Period time – no reading

Page 14: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Analog inputs

Factor multiplies the read numberRegister Name is

shown in ICBEdit

Device Addr. is address of Modbus

device

Modbus register address (e.g. 4xxxx for holding registers)

Length of value in registers (i.e. 2 for a

4-byte value)

Value type – signed/unsigned and

byte length

Offset is added to the value read from Modbus device after

it was multiplied by factor

Period of request sent from I-CB to Modbus device

Page 15: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Binary inputs

Length of value in registers (1 for binary inputs)

Mask selects bit(s)Value is then compared to selected bits and if they

match the binary input to the controller is activated

Error mask selects error bit(s)

Error Value says which values means that the

binary signal is not valid

Page 16: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Binary inputs

ExampleRegister read from the device:0000 0010 0110 1100

Mask = $0040 (0000 0000 0000 0100)Value = $0040 (0000 0000 0000 0100)

0000 0010 0110 1100 read registerAND

0000 0000 0000 0100 Mask0000 0000 0000 0100 compared read register with Mask1 compared previous line with Value

Page 17: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Commands

Possible to write registersAnalog outputsBinary outputs

Refresh of binary outputs – every 1 second

Page 18: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

Documentation

Page 19: I-CB/ Modbus

Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.

How to get it

Order code „I-CB/MODBUS“