WARNING • Read and understand all instructions before attempting to install any Victaulic AquaFlex ® products. • Wear safety glasses, hardhat, and foot protection during installation. Failure to follow these instructions could cause improper sprinkler operation, resulting in serious personal injury and/or property damage. WARNING • These installation instructions are intended for an experienced, trained installer. • The user must understand the purpose of these products, common industry standards for safety, and the potential consequences of improper product installation. Failure to follow these instructions could cause improper sprinkler operation, resulting in serious personal injury and/or property damage. INTRODUCTION AquaFlex Stainless Steel Sprinkler Fittings connect the branch line to the sprinkler using a flexible stainless steel hose and reducer. The flexible stainless steel hose and fittings are intended for direct connection to the sprinkler and are particularly suited for use in suspended ceiling applications. Each drop assembly comes with one stainless steel flexible hose, one branch line connection nipple, one sprinkler reducing nipple, and the 1BEE 2 One-Piece Bracket or the Hat Channel Bracket. Victaulic AquaFlex unbraided flexible stainless steel hoses are cULus Listed, City of Los Angeles (RR5659) Approved, and accepted for use by the City of New York Department of Buildings (MEA 60-05-E). Victaulic AquaFlex braided flexible stainless steel hoses are FM Approved, City of Los Angeles (RR5659) Approved, and accepted for use by the City of New York Department of Buildings (MEA 60-05-E). Flexible stainless steel hoses are available in lengths from 31 - 72 inches/787 - 1829 mm with either -inch or -inch NPT threaded outlets. TECHNICAL DATA Maximum Working Pressure: 200 psi/1375 kPa (FM Approval for Braided System) 175 psi/1206 kPa (UL Listing for Unbraided System) Maximum Ambient Temperature: 225° F/107° C Connection to Branch Line: 1-inch NPT/BSPT Minimum Bend Radius of Flexible Stainless Steel Hose: 7 inches/178 mm (FM Approval for Braided System) 4 inches/102 mm (UL Listing for Unbraided System) Maximum Number of 90° Bends Per Flexible Stainless Steel Hose: Refer to the “Friction Loss Data” section on page 2. NOTE: The flexible stainless steel hose should not be bent within 2 inches/64 mm of the connection nut at both ends. Maximum K-Factor of Sprinkler to be Connected to Sprinkler Reducing Nipple for Unbraided System: 5.6 for -inch 8.0 for -inch Maximum K-Factor of Sprinkler to be Connected to Sprinkler Reducing Nipple for Braided System: 5.6 for -inch 14.0 for -inch IMPORTANT INSTALLATION INFORMATION Victaulic AquaFlex products must be installed according to current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards or equivalent standards for wet or dry systems. Deviations from these standards or alterations to AquaFlex products or sprinklers will void any Victaulic warranty. In addition, installations must meet provisions of the local authority having jurisdiction and local codes, as applicable. If intended for use with drop ceilings, reference must be made to specific ceiling constructions, such as intermediate and heavy- duty ceilings as described in the Standard Specification for the Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-In Panel Ceilings (ASTM C635) when installed in accordance with the Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels (ASTM C636). Victaulic AquaFlex Stainless Steel Sprinkler Fittings and/or the 1BEE 2 One-Piece Bracket or Hat Channel Bracket must not be intermixed with other manufacturer’s products. Refer to the specific product submittal for applications and listing information. These submittals are located in Sections 10 and 40 of the Victaulic G-100 Catalog or on the Victaulic website at www.victaulic.com. In addition, when installing Victaulic FireLock® Automatic Sprinklers with Victaulic AquaFlex Stainless Steel Sprinkler Fittings, refer to the I-40 Installation and Maintenance Instructions for details on sprinkler installation requirements. Size the piping system to provide the minimum required flow rate for the sprinkler system. Flush the system to remove foreign material. Continue to flush the system until water runs clear. DO NOT install sprinkler system piping through heating ducts. DO NOT connect sprinkler system piping to domestic hot water systems. DO NOT install sprinklers where they will be exposed to temperatures that exceed the maximum ambient temperature rating for the sprinkler. The flexible stainless steel hose should not be bent or fluctuated up-and-down or side-to-side when it is pressurized for test. The flexible stainless steel hose should not be bent within 2 inches/64 mm of the connection nut at both ends. Flexible stainless steel hose and fittings have limited flexibility and are intended only to be installed with bends at their respective minimum bend radii. Protect wet piping systems from freezing temperatures. “Important Installation Information” continued on the following page AquaFlex ® Stainless Steel Sprinkler Fittings I-AQUAFLEX INSTALLATION INSTRUCTIONS www.victaulic.com VICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_C

I AquaFlex

Embed Size (px)

Citation preview

Page 1: I AquaFlex

WARNING• Read and understand all instructions

before attempting to install any Victaulic AquaFlex® products.

• Wear safety glasses, hardhat, and foot protection during installation.

Failure to follow these instructions could cause improper sprinkler operation, resulting in serious personal injury and/or property damage.

WARNING

• These installation instructions are intended for an experienced, trained installer.

• The user must understand the purpose of these products, c ommon industry standards for safety, and the potential consequences of improper product installation.

Failure to follow these instructions could cause improper sprinkler operation, resulting in serious personal injury and/or property damage.

INTRODUCTIONAquaFlex Stainless Steel Sprinkler Fittings connect the branch line to the sprinkler using a flexible stainless steel hose and reducer. The flexible stainless steel hose and fittings are intended for direct connection to the sprinkler and are particularly suited for use in suspended ceiling applications. Each drop assembly comes with one stainless steel flexible hose, one branch line connection nipple, one sprinkler reducing nipple, and the 1BEE2 One-Piece Bracket or the Hat Channel Bracket.

Victaulic AquaFlex unbraided flexible stainless steel hoses are cULus Listed, City of Los Angeles (RR5659) Approved, and accepted for use by the City of New York Department of Buildings (MEA 60-05-E).

Victaulic AquaFlex braided flexible stainless steel hoses are FM Approved, City of Los Angeles (RR5659) Approved, and accepted for use by the City of New York Department of Buildings (MEA 60-05-E).

Flexible stainless steel hoses are available in lengths from 31 - 72 inches/787 - 1829 mm with either 1/2-inch or 3/4-inch NPT threaded outlets.

TECHNICAL DATAMaximum Working Pressure:

200 psi/1375 kPa (FM Approval for Braided System) 175 psi/1206 kPa (UL Listing for Unbraided System)

Maximum Ambient Temperature: 225° F/107° C

Connection to Branch Line: 1-inch NPT/BSPT

Minimum Bend Radius of Flexible Stainless Steel Hose:7 inches/178 mm (FM Approval for Braided System) 4 inches/102 mm (UL Listing for Unbraided System)

Maximum Number of 90° Bends Per Flexible Stainless Steel Hose:Refer to the “Friction Loss Data” section on page 2. NOTE: The flexible stainless steel hose should not be bent within 2 1/2 inches/64 mm of the connection nut at both ends.

Maximum K-Factor of Sprinkler to be Connected to Sprinkler Reducing Nipple for Unbraided System: 5.6 for 1/2-inch 8.0 for 3/4-inch

Maximum K-Factor of Sprinkler to be Connected to Sprinkler Reducing Nipple for Braided System: 5.6 for 1/2-inch 14.0 for 3/4-inch

IMPORTANT INSTALLATION INFORMATION• Victaulic AquaFlex products must be installed according to

current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards or equivalent standards for wet or dry systems. Deviations from these standards or alterations to AquaFlex products or sprinklers will void any Victaulic warranty. In addition, installations must meet provisions of the local authority having jurisdiction and local codes, as applicable.

• If intended for use with drop ceilings, reference must be made to specific ceiling constructions, such as intermediate and heavy-duty ceilings as described in the Standard Specification for the Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-In Panel Ceilings (ASTM C635) when installed in accordance with the Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels (ASTM C636).

• Victaulic AquaFlex Stainless Steel Sprinkler Fittings and/or the 1BEE2 One-Piece Bracket or Hat Channel Bracket must not be intermixed with other manufacturer’s products.

• Refer to the specific product submittal for applications and listing information. These submittals are located in Sections 10 and 40 of the Victaulic G-100 Catalog or on the Victaulic website at www.victaulic.com. In addition, when installing Victaulic FireLock® Automatic Sprinklers with Victaulic AquaFlex Stainless Steel Sprinkler Fittings, refer to the I-40 Installation and Maintenance Instructions for details on sprinkler installation requirements.

• Size the piping system to provide the minimum required flow rate for the sprinkler system.

• Flush the system to remove foreign material. Continue to flush the system until water runs clear.

• DO NOT install sprinkler system piping through heating ducts. DO NOT connect sprinkler system piping to domestic hot water systems. DO NOT install sprinklers where they will be exposed to temperatures that exceed the maximum ambient temperature rating for the sprinkler.

• The flexible stainless steel hose should not be bent or fluctuated up-and-down or side-to-side when it is pressurized for test.

• The flexible stainless steel hose should not be bent within 2 1/2 inches/64 mm of the connection nut at both ends.

• Flexible stainless steel hose and fittings have limited flexibility and are intended only to be installed with bends at their respective minimum bend radii.

• Protect wet piping systems from freezing temperatures.

“Important Installation Information” continued on the following page

AquaFlex® Stainless Steel Sprinkler Fittings

I-AQUAFLEXINSTALLATION INSTRUCTIONS

www.victaulic.comVICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_C

Page 2: I AquaFlex

• If construction is altered, refer to applicable standards to determine if additional sprinklers are required.

• The owner is responsible for maintaining the fire protection system in proper operating condition.

• For minimum maintenance and inspection requirements, refer to NFPA 25 and the NFPA pamphlet that describes the care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional maintenance, testing, and inspection requirements that must be followed.

WARNING• Re-location of AquaFlex products MUST be performed by

qualified personnel familiar with the system’s original design criteria, sprinkler listings/approvals, and state and local codes (including NFPA 13 standards).

Failure to re-locate this AquaFlex product properly could affect its performance during a fire, resulting in serious personal injury and property damage.

STAINLESS STEEL FLEXIBLE HOSE BEND CHARACTERISTICS

Minimumbend radius

90°

Minimumbend radius

Minimumbend radius

2XMinimum

bend radius

OR

Minimumbend radius

Minimumbend radius

Minimumbend radius

2XMinimum

bend radiusMinimum

bend radius

OR

NOTE: For out-of-plane (three-dimensional) bends, care must be taken to avoid imparting torque on the flexible stainless steel hose.

FRICTION LOSS DATA

Length of Stainless Steel Flexible Hose

Actual Length of Stainless Steel Flexible Hose inches/mm Outlet Size

Equivalent Length of 1-inch/33.7-mm Schedule 40 Pipe

feet/meters

Maximum Number of 90° Bends at 4-inch/102-mm Bend Radius §inches FM UL inches FM* UL‡

24 N/A 28700

1/2 N/A 18

25.5

3/4 N/A 329.8

31 31790

31780

1/2 9.6 27

22.9 8.2

3/4 8.2 332.5 10.1

36 36915

401000

1/2 11.0 44

33.4 13.4

3/4 9.9 483.0 14.6

48 481220

481220

1/2 17.1 53

35.2 16.2

3/4 16.5 555.0 16.8

60 601525

611540

1/2 21.4 68

36.5 20.7

3/4 20.1 636.1 19.2

72 721830

721830

1/2 27.3 73

38.3 22.3

3/4 26.2 767.9 23.2

‡ Series AQU at 4-inch/102-mm minimum bend radius and straight reducers * Series AQB at 7-inch/178-mm minimum bend radius and straight reducers § A higher number of bends may be permitted, provided the sum of degrees is equal to or less than the total maximum allowable degrees of bend (e.g. Two 90° bends equal 180°. Three 90° bends equal 270°). For friction loss data for elbows, refer to Victaulic submittal 10.85. EXAMPLE: A 48-inch Series AQU hose installed with two 30° bends and two 90° bends at a 4-inch bend radius is permitted and considered equivalent to the data in the table shown above. In this example, the total number of degrees is 240°, which is less than the allowable 270°. NOTE: Differences in equivalent lengths are due to varying test methods, per UL 2443 and FM 1637 standards. Refer to these standards for additional information regarding friction loss test methods.

I-AQUAFLEX_2

AquaFlex® Stainless Steel Sprinkler Fittings

I-AQUAFLEXINSTALLATION INSTRUCTIONS

www.victaulic.comVICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_C

Page 3: I AquaFlex

ASSEMBLY DRAWINGS – 1BEE2 ONE-PIECE BRACKET

ASSEMBLY DRAWINGS – HAT CHANNEL BRACKET

2

1

Item Description 1 24-inch/610-mm or 48-inch/1219-mm Long Square Bar 2 Center Gate Assembly with Wing Nut 3 Wing Nut Bolt with Cup Point 4 Hat Channel End Bracket 5 Wing Nut Bolt with Cone Point 6 Self-Drilling Screw (#10-16 x ½-inch)

3

4

56

Branch LineStainless Steel Flexible Tube

Connection Nut

Connection Nut

Center Gate Assembly with

Wing Nut

Sprinkler

ASTM C635 Ceiling/Rail Assembly

Sprinkler Reducing Nipple

Wing Nut

1BEE One-Piece Bracket AssemblyBranch Line

Connection Nipple

#8 x ½-inchSelf-Drilling Screw

34

2

1

4

3

Item Description 1 24-inch/610-mm or 48-inch/1219-mm Long Square Bar 2 Center Gate Assembly with Wing Nut 3 End Bracket Assembly with Wing Nut 4 Sheet Metal Screw

I-AQUAFLEX_3

AquaFlex® Stainless Steel Sprinkler Fittings

I-AQUAFLEXINSTALLATION INSTRUCTIONS

www.victaulic.comVICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_C

Page 4: I AquaFlex

INSTALLATION FOR ASTM C635 METAL CEILING SUSPENSION SYSTEMS INSTALLED IN ACCORDANCE WITH ASTM C636 STANDARDS

WARNING• The flexible stainless steel hose should not be bent or

fluctuated up-and-down or side-to-side when it is pressurized for test.

• The flexible stainless steel hose should not be bent within 2 1/2 inches/64 mm of the connection nut at both ends.

Failure to follow these instructions could cause improper sprinkler operation, resulting in serious personal injury and/or property damage.

1. Apply pipe joint compound or Teflon* tape to the tapered threads of the branch line connection nipple. NOTE: DO NOT use a combination of pipe joint compound and tape. Using a pipe wrench, tighten the branch line connection nipple into the branch line.

2. Connect the nut of the flexible stainless steel hose to the branch line connection nipple, as shown above. DO NOT use pipe joint compound or Teflon* tape on the threads of the branch line connection nipple, since the flat gasket on the end of the flexible stainless steel hose provides the leak-proof connection. Tighten the connection to a maximum torque of 15 ft-lbs/20 N•m. NOTE: To prevent damage to the seal, DO NOT exceed the specified torque on the nut.

3. Connect the nut of the flexible stainless steel hose to the sprinkler reducing nipple. DO NOT use pipe joint compound or Teflon* tape on the fine threads of the sprinkler reducing nipple, since the flat gasket on the end of the flexible stainless steel hose provides the leak-proof connection. Tighten the connection to a maximum torque of 15 ft-lbs/20 N•m. NOTE: To prevent damage to the seal, DO NOT exceed the specified torque on the nut.

4. Attach the end brackets of the 1BEE2 One-Piece Bracket to the rails of an ASTM C635 metal ceiling suspension system installed in accordance with ASTM C636 standards. Make sure the ends of the 1BEE2 One-Piece Bracket engage the rails, as shown above. Tighten the wing nuts to a torque of 3 ft-lbs/4 N•m to secure the ends to the rails.

* Teflon is a registered trademark of the DuPont Company

I-AQUAFLEX_4

AquaFlex® Stainless Steel Sprinkler Fittings

I-AQUAFLEXINSTALLATION INSTRUCTIONS

www.victaulic.comVICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_C

Page 5: I AquaFlex

5. For installations that must meet cULus Listing requirements, or for added tamper resistance, tighten a #8 x 1/2-inch self-drilling screw through the 1BEE2 One-Piece Bracket and ceiling grid at the two locations on the bracket. NOTE: A tamper-evident label is available and can be applied to one or both of the end brackets.

6. Move the center gate assembly of the 1BEE2 One-Piece Bracket to the desired location, then slide the sprinkler reducing nipple into the center gate assembly.

6a. Close the gate around the sprinkler reducing nipple. Swing the pivot screw into the slot on the gate, and tighten the wing nut to a torque of 3 ft-lbs/4 N•m to secure the sprinkler reducing nipple in the desired location. NOTE: The pivot screw is staked to prevent the wing nut from being backed off/removed completely.

7. Apply pipe joint compound or Teflon* tape to the male threads of the sprinkler. Install the sprinkler into the sprinkler reducing nipple by following the sprinkler manufacturer’s installation instructions.

8. After installation is complete, test the system for leaks in accordance with NFPA guidelines.

* Teflon is a registered trademark of the DuPont Company

I-AQUAFLEX_5

AquaFlex® Stainless Steel Sprinkler Fittings

I-AQUAFLEXINSTALLATION INSTRUCTIONS

www.victaulic.comVICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_C

Page 6: I AquaFlex

2 X 4 WOOD JOIST/STUD INSTALLATION (FM ONLY)1. Perform steps 1 - 3 of the “Installation for ASTM C635 Metal

Ceiling Suspension Systems Installed in Accordance with ASTM C636 Standards” section.

2. Remove the sheet metal screw from only one end bracket assembly of the 1BEE2 One-Piece Bracket.

2a. Remove the wing nut from each of the end bracket assemblies.

3. Place the end bracket assembly (with the sheet metal screw still installed) up against the outside surface of the wood joist/stud with the square bar resting on top of the wood joists/studs.

3a. Slide the end bracket assembly (with the sheet metal screw removed in step 2) toward the outside surface of the opposite wood joist/stud, as shown in the graphic below.

1½-inch/38-mm Long #10 Wood Screw

(4 Total)

4. Install the modified 1BEE2 One-Piece Bracket assembly to the wood joists/studs by using four, 1 1/2-inch/38-mm long #10 wood screws in the locations noted in the graphic shown above.

5. Using an 1/8-inch/3-mm drill bit, drill a hole down through the end bracket assembly (with the sheet metal screw removed in step 2) and into the square bar to accommodate re-installation of the sheet metal screw.

6. Re-install the sheet metal screw into the end bracket assembly/square bar.

7. Perform steps 6 - 8 of the “Installation for ASTM C635 Metal Ceiling Suspension Systems Installed in Accordance with ASTM C636 Standards” section to complete the installation.

NOTE: For wood joists/studs larger than 2 x 4, longer sprinkler reducing nipples should be used.

2 X 4 METAL JOIST/STUD INSTALLATION (FM ONLY)1. Perform steps 1 - 3 of the “Installation for ASTM C635 Metal

Ceiling Suspension Systems Installed in Accordance with ASTM C636 Standards” section.

2. Remove the sheet metal screw from only one end bracket assembly of the 1BEE2 One-Piece Bracket. Slide the end bracket assembly toward the center of the square bar.

2a. Remove the wing nut from each of the end bracket assemblies.

3. Place the end bracket assembly (with the sheet metal screw still installed) up against the outside surface of the metal joist/stud with the square bar resting on top of the metal joists/studs.

3a. Slide the end bracket assembly (with the sheet metal screw removed in step 2) toward the inside, flat surface of the opposite metal joist/stud, as shown in the graphic below.

1¼-inch/32-mm Long #10

Self-Drilling Sheet Metal

Screws(4 Total)

4. Install the modified 1BEE2 One-Piece Bracket assembly to the metal joists/studs by using four, 1 1/4-inch/32-mm long #10 self-drilling sheet metal screws in the locations noted in the graphic shown above.

5. Using an 1/8-inch/3-mm drill bit, drill a hole down through the end bracket assembly (with the sheet metal screw removed in step 2) and into the square bar to accommodate re-installation of the sheet metal screw.

6. Re-install the sheet metal screw into the end bracket assembly/square bar.

7. Perform steps 6 - 8 of the “Installation for ASTM C635 Metal Ceiling Suspension Systems Installed in Accordance with ASTM C636 Standards” section to complete the installation.

NOTE: For metal joists/studs larger than 2 x 4, longer sprinkler reducing nipples should be used.

I-AQUAFLEX_6

AquaFlex® Stainless Steel Sprinkler Fittings

I-AQUAFLEXINSTALLATION INSTRUCTIONS

www.victaulic.comVICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_C

Page 7: I AquaFlex

ALTERNATIVE WOOD JOIST/STUD INSTALLATION (FM ONLY)1. Perform steps 1 - 3 of the “Installation for ASTM C635 Metal

Ceiling Suspension Systems Installed in Accordance with ASTM C636 Standards” section.

2. Remove the sheet metal screw from only one end bracket assembly of the 1BEE2 One-Piece Bracket. Remove the end bracket assembly from the square bar.

2a. Remove the wing nut from each of the end bracket assemblies.

3. Measure the distance between the wood joists/studs.

3a. Cut the square bar to the length needed to fit between the two wood joists/studs. This length must be measured from the outside of the end bracket assembly (with the wing nut removed) to the point on the square bar that will butt up against the other wood joist/stud.

4. Place the end bracket assembly, removed in step 2, onto the end of the square bar so that the square bar is flush with the outside of the end bracket assembly. Mark the new location where the sheet metal screw will be re-installed. Drill an 1/8-inch/3-mm hole at the mark on the square bar to accommodate re-installation of the sheet metal screw.

5. Re-install the end bracket assembly to the square bar with the sheet metal screw removed in step 2.

1½-inch/38-mm Long #10 Wood Screw

(4 Total)

6. Install the modified 1BEE2 One-Piece Bracket assembly between the wood joists/studs by using four, 1 1/2-inch/38-mm long #10 wood screws in the locations noted in the graphic shown above.

7. Perform steps 6 - 8 of the “Installation for ASTM C635 Metal Ceiling Suspension Systems Installed in Accordance with ASTM C636 Standards” section to complete the installation.

ALTERNATIVE METAL JOIST/STUD INSTALLATION (FM ONLY)1. Perform steps 1 - 3 of the “Installation for ASTM C635 Metal

Ceiling Suspension Systems Installed in Accordance with ASTM C636 Standards” section.

2. Remove the sheet metal screw from only one end bracket assembly of the 1BEE2 One-Piece Bracket. Remove the end bracket assembly from the square bar.

2a. Remove the wing nut from each of the end bracket assemblies.

3. Measure the distance between the metal joists/studs.

3a. Cut the square bar to the length needed to fit between the two metal joists/studs. This length must be measured from the outside of the end bracket assembly (with the wing nut removed) to the point on the square bar that will butt up against the other metal joist/stud.

4. Place the end bracket assembly, removed in step 2, onto the end of the square bar so that the square bar is flush with the outside of the end bracket assembly. Mark the new location where the sheet metal screw will be re-installed. Drill an 1/8-inch/3-mm hole at the mark on the square bar to accommodate re-installation of the sheet metal screw.

5. Re-install the end bracket assembly to the square bar with the sheet metal screw removed in step 2.

1¼-inch/32-mm Long #10

Self-Drilling Sheet Metal

Screws(4 Total)

6. Install the modified 1BEE2 One-Piece Bracket assembly between the metal joists/studs by using four, 1 1/4-inch/32-mm long #10 self-drilling sheet metal screws in the locations noted in the graphic shown above.

7. Perform steps 6 - 8 of the “Installation for ASTM C635 Metal Ceiling Suspension Systems Installed in Accordance with ASTM C636 Standards” section to complete the installation.

I-AQUAFLEX_7

AquaFlex® Stainless Steel Sprinkler Fittings

I-AQUAFLEXINSTALLATION INSTRUCTIONS

www.victaulic.comVICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_C

Page 8: I AquaFlex

INSTALLATION FOR ASTM C645 HAT FURRING CHANNEL CEILING SYSTEMS INSTALLED IN ACCORDANCE WITH ASTM C754 STANDARDS (FM ONLY)

WARNING

• The flexible stainless steel hose should not be bent or fluctuated up-and-down or side-to-side when it is pressurized for test.

• The flexible stainless steel hose should not be bent within 2 1/2 inches/64 mm of the connection nut at both ends.

Failure to follow these instructions could cause improper sprinkler operation, resulting in serious personal injury and/or property damage.

1. Apply pipe joint compound or Teflon* tape to the tapered threads of the branch line connection nipple. NOTE: DO NOT use a combination of pipe joint compound and tape. Using a pipe wrench, tighten the branch line connection nipple into the branch line.

2. Connect the nut of the flexible stainless steel hose to the branch line connection nipple, as shown above. DO NOT use pipe joint compound or Teflon* tape on the threads of the branch line connection nipple, since the flat gasket on the end of the flexible stainless steel hose provides the leak-proof connection. Tighten the connection to a maximum torque of 15 ft-lbs/20 N•m. NOTE: To prevent damage to the seal, DO NOT exceed the specified torque on the nut.

3. Connect the nut of the flexible stainless steel hose to the sprinkler reducing nipple. DO NOT use pipe joint compound or Teflon* tape on the fine threads of the sprinkler reducing nipple, since the flat gasket on the end of the flexible stainless steel hose provides the leak-proof connection. Tighten the connection to a maximum torque of 15 ft-lbs/20 N•m. NOTE: To prevent damage to the seal, DO NOT exceed the specified torque on the nut.

4. Attach the end brackets to the ASTM C645 hat furring channel ceiling system installed in accordance with ASTM C754 standards. Make sure the end brackets engage the hat furring channels, as shown above. Tighten the wing nuts loosely to maintain engagement with the hat furring channels. The wing nuts will be tightened completely in later steps.

* Teflon is a registered trademark of the DuPont Company

I-AQUAFLEX_8

AquaFlex® Stainless Steel Sprinkler Fittings

I-AQUAFLEXINSTALLATION INSTRUCTIONS

www.victaulic.comVICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_C

Page 9: I AquaFlex

5. Place the center gate assembly onto the square bar, as shown above.

6. Insert the square bar/center gate assembly into each end bracket, as shown above.

7. Adjust the bracket assembly to the appropriate location on the hat furring channel.

8. Tighten the wing nut on the side of each end bracket to a torque of 3 ft-lbs/4 N•m to secure the end brackets to the hat furring channels.

9. Tighten the wing nut on the top of each end bracket to a torque of 3 ft-lbs/4 N•m to secure the end brackets to the square bar.

I-AQUAFLEX_9

AquaFlex® Stainless Steel Sprinkler Fittings

I-AQUAFLEXINSTALLATION INSTRUCTIONS

www.victaulic.comVICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

REV_C

Page 10: I AquaFlex

10. Tighten a #10-16 x 1/2-inch self-drilling screw through the two locations on each end bracket and into the hat furring channels.

11. Move the center gate assembly to the desired location, then slide the sprinkler reducing nipple into the center gate assembly.

11a. Close the gate around the sprinkler reducing nipple. Swing the pivot screw into the slot on the gate, and tighten the wing nut to a torque of 3 ft-lbs/4 N•m to secure the sprinkler reducing nipple in the desired location. NOTE: The pivot screw is staked to prevent the wing nut from being backed off/removed completely.

12. Apply pipe joint compound or Teflon* tape to the male threads of the sprinkler. Install the sprinkler into the sprinkler reducing nipple by following the sprinkler manufacturer’s installation instructions.

13. After installation is complete, test the system for leaks in accordance with NFPA guidelines.

* Teflon is a registered trademark of the DuPont Company

I-AQUAFLEX_10

AquaFlex® Stainless Steel Sprinkler Fittings

I-AQUAFLEXINSTALLATION INSTRUCTIONS

www.victaulic.comVICTAULIC AND AQUAFLEX ARE REGISTERED TRADEMARKS OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.