35
HYDRAULICS BRANCH OFFICIAL FILE COP Y UNITED STATES DEPARTMENT OF THE INTERIOR BUREAU OF RECLAMATION COMPOUND WEIR STUDY Hydraulic Laboratory Report No. Hyd. 505 DIVISION OF RESEARCH OFFICE OF CHIEF ENGINEER DENVER, COLORADO April 5, 196 3

HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

HYDRAULICS BRANCH OFFICIAL FILE COPY

UNITED STATES DEPARTMENT OF THE INTERIOR

BUREAU OF RECLAMATION

COMPOUND WEIR STUDY

Hydraulic Laboratory Report No. Hyd. 505

DIVISION OF RESEARCH

OFFICE OF CHIEF ENGINEER DENVER, COLORADO

April 5, 196 3

Page 2: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

The information contained in this re -port may not be used in any publica­tion, advertising, or other promotion in such a manner as to constitute an endorsement by the Government or the Bureau of Reclamation, either explicil or implicit, of any material, product, device, or process that may be re­ferred to in the report.

(,

Page 3: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

CONTENTS

Summary and Conclusions ............................. . Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Laboratory Installation ................................ . Weir Calibration ..................................... . Data Analysis ........................................ .

Page

1 2 2 3 3

Horizontal Extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Sloping Extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

References ........................................... 8

Figure

Field and Laboratory Installation of Compound Weirs • . . • . . 1 Laboratory Test Facility . . . . • • • . • . . . . . . . . . . . . . . . • . . . . . . 2 Weir Crests........................................... 3 V-notch with Horizontal Extensions . . • . • • . . • . • . . . • • . . . • . . 4 V-notch with 2-foot Horizontal Extensions . . . . • • . . . . • . . . . . 5 V -notch· with 1-foot Horizontal Extensions . . . • . • • • . . • • • . . . 6 V-notch with Vertical Extensions , • • . . • • . • . . . . . • . • . • . . . • . 7 V -notch with 15° slope. 1-foot Extensions . . • . . • . . . . . . • • • . 8 V -notch Data Comparison with Cohe Equation . • • . . . . . . . • . . 9 Calibration Data for 90° V-notch with Vertical and

Horizontal Extensions . • . . • • . . . . . . • .. . . . . • . . . . . • • • . . . . • 10 Head-Discharge Curves for 90° V-notch Weirs with

Vertical and Horizontal Extensions . . • . • . . . . . • . . . • . • . . • • 11 Constant Determination Curves •....•..••....•••••••..... Calibration Curve for Vertical Extensions •..•.•.......... Calibration Curve for Horizontal Extensions ...••.•....••. Calibration Data for 90° V-notch Weirs with Sloping

12 13 14

Extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Head-Discharge Curves for Weirs with Sloping

Extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Table

Calibration Data for V -notch with 2-foot Horizontal Extensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Calibration Data for V -notch with 1-foot Horizontal Extensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Calibration Data for V-notch with Vertical Extensions . • • . . 3 Calibration Data for V -notch with 15° slope 1-foot

Extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Calibration Data for V-notch with 15° slope 2-foot

Extensions . .............. ~ . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 4: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

FOREWORD

The studies discussed in this report were performed during

November 1959 to February 1960 by the Special Investigations

Unit of the Hydraulics Branch. Laboratory experiments were

made by W. B. McBirney, S. G. Parker and J. L. Harper under

the supervision of J. C. Schuster. The data and analysis con­

tained were compiled for the report by J. M. Bergmann. The

Special Investigations Unit is in the Special Investigations Section

headed by A. J. Peterka. H. M. Martin is Chief of the Hydraulics

Branch •

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 5: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

UNITED STATES DEPARTMENT OF. THE INTERIOR

BUREAU OE RECLAMATION

Office of Chief Engineer Division of Research Hydraulics Branch Denver. Colorado

Laboratory Report No. Hyd. 505. Compiled by: J. M. Bergmann Checked by: J. C. Schuster Reviewed by: A. J. Peterka Submitted by: H. M. Martin April 5, 1963

COMPOUND WEIR STUDY

SUMMARY AND CONCLUSIONS

Experiments on five weirs, each composed of a 1-foot-deep V-notch weir with vertical, 1- and 2-foot horizontal or 15° upward sloping extensions (Figure 3) were performed to determine the flow charac­teristics in terms of head-discharge (H-Q) relationships. An anal­ysis of the data was made to obtain correlations between the (H-Q) relationships that could be used to determine the discharge of 1-foot­deep V-notch weirs having other lengths of extensions.

The V -notch weirs with horizontal extensions produced a smooth head-discharge curve except in the transition zone where the head just exceeded the depth of the V-notch portion of the weir, i.e •• heads from 1. 0 to 1. 1 feet. The thin sheet of water tended to dribble over the extension because the vertical component of veloc­ity at the weir crest was not sufficient to establish a true contrac­tion.

Weirs with sloping extensions from the V-notch produced better contractions of the lower surface of the nappe for very low heads resulting in a more uniform head discharge curve.

At points of change in the slope of the crest, the rates of discharge change in the H-Q relationships were not completely definable. Therefore, compound weirs should be set so that discharge deter­mination in the transition regions will be of minimum importance. In other ranges of flow the compound weirs; were as accurate as any weir can be. The head-discharge relationships in the form of equations are cumbersome, but simple graphs and tables can be prepared for determining discharge.

Generalized head-discharge equations derived in this report from the test data need to be confirmed by further testing before they are extended to applications outside the range of the data.

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 6: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

INTRODUCTION

Frequently, a single water-measuring device is desired that will accurately measure a wide range of discharges, e. g. , both the normal and flood flows of streams, Figure lA. Proportional weirs and specially shaped flumes, can be designed to be generally acceptable but these devices are often complicated and may cost more to construct than is warranted by the value of the data obtained. The compound weir resolves the cost problem but introduces the problem of complicated head-discharge relationships.

Five compound weirs were tested in the Bureau's Laboratory to define the flow characteristics in terms of the H-Q relationships and to possibly correlate the discharge equations. The weirs, sharp crested and tested under free flow, contracted conditions, consisted of a 90° V-notch 1 foot deep with one of the following extensions:

1. Vertical

2. Horizontal

a. 1 foot in length on each side and vertical sides

b. 2 feet in length on each side and vertical sides

3. Sloping (15° above horizontal)

a. 1-foot horizontal length each side and vertical sides

b. 2-foot horizontal length each side and vertical sides

Accurate head and discharge measurements were used to calibrate the weirs. Equations determined by mathematical and graphical methods, were used to generalize the H-Q relationships. The sloping extensions were tested in an attempt to obtain a uniform transition of the flow from the V..;notch weir to the compound shape.

LABORATORY INSTALLATION

The weir crests were installed in the side of a 20-foot by 18-foot 9-inch head box, with the root of the V-notch portion of the Weir set 3 feet O inch above the floor of the box, Figures lB and 2. This arrangement provided a minimum of 60 square feet iri the· approach cross-section and allowed the velocity of approach for the discharges used in the study to be neglected in determining the total head on the crest. A 6-inch-thick rock baffle, 13 feet

2

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 7: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

..,

9 inches upstream from the crest, was placed across the head box to stabilize the flow in the weir pool. Calibrated Venturi meters were used to measure the flows from three pumps discharging up to a total of 32 cubic feet per second into the head box. The pumps and Venturi meters are permanent installations of the laboratory. Static head measurements were made with a hook gage in a stilling well located outside the head box. The stilling well connection was tapped into the side of the head box about 8 feet upstream of the weir bulkhead.

The crests, shown in Figure 3, were formed from 2-1/4- by 1/4-inch brass strips and were bolted to a 3/4-inch plywood bulkhead. The top edge of the strips was beveled to 1/8-inch thickness to form the sharp crest.

WEIR CALIBRATION

The weir·s were calibrated by measuring and recording the heads over the weir crest when steady conditions existed in the weir pool for known discharges_. The data were plotted as they were obtained ·to determine the coherency of the tests and to verify the recorded head-discharge relationship. The data, thus obtained, are pre­sented in Tables 1 through 5. Discharges and heads for the V -notch portion of the weirs were measured in conjunction with the first weir tested, Table 1, and periodically checked at random thereafter.

A pictorial record, partially presented as Figures 4 through 8, was kept during the tests. Of particular interest are the photographs shown as Figure 4, where the head on the V -notch portion of the weir is slightly in excess of 1. 0 foot and flow is just beginning to pass over the horizontal portion of the weir. It was noted that for heads from approximately 1. 0 to 1. 1 feet, the discharge over the horizontal crests was neither uniform nor stable due to the draw­down over the V -notch. Figures 5 through 8 show four of the five weirs before and during testing.

DATA ANALYSIS

For analytical purposes, the V-notch weir with vertical extensions was considered a V-notch weir with zero-length horizontal exten­sions. Thus, two types of compound weirs were analyzed:

1. V-notch with extensions horizontal

2. V-notch with extensions 15° above horizontal

3

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 8: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

Further. the data for the 90° V-notch portion of the weirs shows good agreement. Figure 9 with the Cone Equation

Q = 2. 49H2. 48 (1)

therefore. Equation (1) was considered to be representattve of the V-notch data in the following analyses.

Horizontal Extensions

The data for the V-notches with horizontal extensions were plotted. head versus discharge. on rectangular and log-log graph paper. From the log-log plot. Figure 10. and observations during the tests. it was noted that a transition zone existed at heads between 1. 0 and 1. 1 feet for the 1- and 2-foot extensions. caused by the change from a simple weir to a compound weir. Therefore. these data were not included in determining H-Q relationships for the upper portion of the weirs. Next. it was assumed that the H-Q relationship for the remaining data was a polynomial of the form.

(2)

Successive differences of discharges at equally spaced. increasing heads indicated that the polynomial was of the second degree. Thus. Equation (2) becomes

2 Q = a1 + a2H + a3H ( 3)

The constants were determined from the data in Tables 1 through 3 for heads greater than 1.1 feet by the method of least squares. which resulted in the following equations:

1. Q0 (zero extensions) = -2. 420 + 2. 661H + 2. 126H2 (4)

2. Q1 (1-foot extensions) = -4. 579 + 1. 792H + 4. 732H2 (5)

3. Q2 (2-foot extensions) = -5. 589 -0. 859H + 8. 005H2 (6)

These equations are shown graphically on Figure 11.

Correlation of the horizontal crest lengths with the constants in Equations ( 4). (5). and ( 6). corresponding to al. a2, and a3 of Equation (3). was performed by plotting the constants against the corresponding length of horizontal crests. Figure 12. Th~ indi­cated trends of the constants are speculative. since there are only three points. and should not be relied on for accurate formulation. However. if horizontal weir extensions are used. in conjunction with a 1-foot V-notch. a:p. estimate of the constants in Equation (3) may be obtained from Figure 12.

4

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 9: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

As an alternative to the use of Equation. (3) which requires a determination of the constants, a general equation was derived for the head-discharge relationship of V-notch weirs with hori­zontal extensions when flows exceed the capacity of the V-notch. To derive the _g-eneral equation1 head-discharge relationships were determined for the V-notch with vertical extensions and for the discharge per foot of horizontal extension regardless of total length •.

The head-discharge relationship for the V-notch weir with vertical extensio'ns was assumed to be of the form.

Q + b = aHm (7)

By trial-and error. 1. 5 cubic feet per second was chosen for b in order to produce a linear relationship between the logarithms of the heads and the corresponding "adjusted" (Q plus b). discharges. Figure 13. The constants a and m of Equation (7) were deter­mined from this graph. The resulting equation is:

Q = 3. 9H1. 72 -1. 5 (8)

Eleven discharges for the V-notch with vertical extensions were subtracted from the total discharges over the weirs with 1- and 2-foot extensions when under the same head. The remaining frac­tion of the discharge was then divided by the total length of hori­zontal crest. This gave a discharge per foot of horizontal crest, q. for various heads above the horizontal crest. h. Equation (9) is the resulting relationship determined from the head-discharge., log-log plot. Figure 14.

q = 3. 3 hl. 5 (9)

A general equation for computing discharges over weirs with hori­zontal extensions results from the combining of Equations (8). and (9). into Equation (10)

Q = 3. 9Hl. 72 -1. 5 + 3. 3Lhl. 5 (10)

where L is the total length of the horizontal extensions.

Equation (9) is in good agreement with equations determined by various investigators as reported by King (Reference 1) •

(11)

where K depends on the velocity of approach and weir pool shape.

5

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 10: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

Discharges· in the transition zone, heads between 1. 0 and 1. 1 feet, are affected by the approach flow characteristics and weir crest sharpness and roughness. The laboratory tests indicated the simple V-notch Equation (1) to be applicable for heads up to 1. 05 feet when the V was 1. 00 foot deep. However, in a field installa1;ion, where weir crest imperfections and small waves are more likely to occur, the decision as to when Equation (1) no longer applies may not be well defined. Therefore, the size and vertical placement of the compound weir, based on anticipated flows, should be such that heads of 1. 0 foot to 1.1 feet will be in minimum usage.

The discharge over a compound weir composed of a 1. 0-foot V -notch with horizontal extensions may be computed by either Equation (3) or Equation (10). Equation (3) requires the use of Figure 12 for determining constants in addition to knowing the head over the weir and the length of the horizontal extensions, which is required when Equation (10) is used.

Two example problems follow. The first illustrates the use of Figure 11 and the second illustrates the use of Equations (3) and (10).

Example 1. Determine from Figure 11, the discharge over a 1-foot V -notch weir with 1-foot horizontal extensions on each side, when the head is 1. 8 feet.

The discharge is obtained by going horizontally from H = 1. 8 until the 1-foot horizontal extension line is intersected. At the intersection, go vertically down to read Q = 14 cubic feet per second.

Example 2. Determine the discharge over a 1-foot V -notch weir with 18-inch horizontal extensions on both sides of the V-notch when operating under a 2. 0-foot head.

From Figure 12, for L = 3. 0 feet a1 = -5.13 a2 = 0. 69 a3 = 6. 30

therefore, by Equation (3) for H = 2.0 feet Q = -5. 13 + o. 69(2) + 6. 30(4) = 21. 45

cubic feet per second

By Equation (10), for H = 2. 0 feet, h = 1. 0 foot and L = 3. 0 feet,

Q = 3.9(2)1. 72 -1.5 + 3.3(3)(1)1. 5 = 21.28 cubic feet per second

6

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 11: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

Sloping Extensions

Compound weirs with sloping extensions necessitate the use of three equations to adequately express the head-discharge relation­ship of the weir. The three relationships correspond to the follow­ing portions of the weir:

1. The V -notch, previously discussed

2. The sloping extensions, a straight-line plot on log-log paper

3. The portion above the sloping extensions, which was assumed to be of the same form as Equation (3).

The H-Q relationship for the sloping extension portion of these com­pound weirs was found to be

Q = 2. 22H3· 21 (12)

from a log-log plot of the test data, Figure 15.

The relationship for the portion of the weirs above the sloping exten­sions was computed by the method of least squares after the form of the equation was assumed. The equations for the two weirs are

1. Q1 (1-foot extensions)= -11.345 + 7.484H + 3.360H2 (13)

2. Q2 (2-foot extensions) = -14.106 + 6. 943H + 5, llOH2 (14)

Equations (12), (13), and (14) are shown graphically on Figure 16.

There was no apparent advantage in sloping the, extensions in com­parison with having them horizontal, therefore~ no further analysis of the data was undertaken. The sloping extensions do produce a more uniform transition zone at the top of ,the V-notch; however, another transition zone, at the top of the sloping extension, is en­countered. Both transition zones cover a larger range of heads than the one transition zone for the horizontal extensions.

Example 3 illustrates the use of Figure 16.

Example 3. Determine, from Figure 16, the discharge over a 1-foot V-notch weir with 1-foot, 15° upward sloping extensions on each side, when the head is 1, 8 feet.

The discharge is obtained by going horizontally from H = 1. 8 until the 1-foot sloping extension line is intersected. At the intersection, go vertically down to read Q = 13. 2 cubic feet per second.

7

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 12: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

REFERENCES

1. King. H. W.. Handbook of Hydraulics. Third Edition, McGraw­Hill Book Company, Inc .• 1939.

2. USBR. Water Measurement Manual. First Edition. U.S. Gov­ernment Printing Office, Washington. 1953.

8

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 13: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

Table 1 ·

CALIBRATION .OF COMPOUND WEIR 1-FOOT DEPTH 90° V-NOTCH

WITH 2-FOOT HORJZONTAL BLADE Head Flow·

Date run (H ft) (Q cfs) Remarks

October 29. 1959 0.670 0.903 0.040 0.0148 0.339 · 0.166 0.555 0.560 0.379 0.216 0.495 0.424 0.272 0.096 0.201 0.037

October 30, 1959 0.670 0.903 0.879 l. 779 0.384 0~216 0.772 1.287 0.956 2.209

November 2, 1959 1.014 2.552 SurfaGe tension holding bead above crest

1.021 2.599 Bead above crest 1.027 2.625 Flow over part of crest 1. 031 2.688 Flow over all of crest except

near V -notch draw down 1. 038 2.764 1.049 2.888 1~058 2.986 Flow over entire crest

November 3. 1959 1.075 ·3. 193 1.095 3.442 1.107 3.589· 1.142 4.096 1.182 4.769 1.207 5.041 1. 236 5.656 1. 267 6.207 1. 311 7.031 1. 372 8.292 1.479 10. 607 1. 479 10.621

November 4. 1959 1.537 11. 712 1. 577 12.928 Hook gage difficult to set be-

cause of head box vibration 1.633 14.261 1.671 15.177 1. 713 16.319

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 14: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

Table 1--Continued

Head Flow Date run (H ft) (C> cfs) Remarks

November 4, 1959 1.752 17.420 1. 819 19.301 l.877 20.978 1. 919 22.189 1.982 24.209 Head box not vibrating 2.028 25.648 2.079 27.158 2.127 28.788 2.183 31.152 2.214 31. 619 Columns of air noted to form

in the nappe from floor at discharge back into the t ank through the V -notch. The columns would collapse and then dissipate into the dis-charge with an audible noise.

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 15: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

Table 2

CALIBRATION OF COMPOUND WEIR 1-FOOT OEPTH 90° V-NOTCH

WITH 1-FOOT HORIZONTAL BLADES Head Flow

Date run (H ft) (Q cfs) Remarks

December 1, 1959 1.027 2.60 Impending fl.ow over horizon tal crest

1.047 2.758 · Flow over horizontal crest 1.064 2.914 1.084 3.095 1.101 3.261 1.102 3.263 1.143 3.703 1.193 4.294 1.247 4.967 1. 293 5.577 1.344 6.283 1.398 7.098 1.449 7. 894. 1. 497 8.649 1.542 9.363 1.594 10.258 1. 647 11. 159 1. 697 12.041 1.748 13.003 1.798 13.918 1.842 14.743 1. 897 16.066 1. 963 17.174

December 2, 1959 1. 991 17.814 2.040 18.851 2.088 19.835 2.148 21. 197 2.218 22.728 2.274 24.003 2.314 25.044 2.378 26.437 2.444 28.007 2.507 29.529 2.550 30.660

Note: V-notch portion not run.

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 16: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

Table 3

CALIBRATION OF COMPOUND WEIR 1-FOOT DEPTH 90° V-NOTCH WITH VERTICAL EXTENSION

·Head Flow .

Date run (H ft) (Q cfs) Remarks ..

December 21, 1959 1.026 2.596 1.048 2.736 1.093 3.023 1. 113 3.167 1.143 3.382 1.179 3.631 1.241 4. 114 · 1.294 4.537 1.291 4.517 1. 360 5.091 1.414 5.549 1.485 6.182 1.546 6.737 1. 615 7.396 1.661 7.845

-1. 730 8.548 1. 805 9.308 1.843 9.823 1.917 10.515

December 22, 1959 1.739 8.533 1. 954 10.868 2.095 12.521 2.239 14.231 2.383 16.043 2.534 17.992 2.655 19.627 2.804 21. 682

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 17: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

Table4.

CALIBRATION OF COMPOUND WEIR 1-FOOT DEPTH. 90° V-NOTCH 2-FOOT 15° BLADE

Head· Flow Date run (H ft) (Q cfs) . Remarks

January 21, 1960 0.990 2.390 Check point .on V -notch weir 0.715 1.032 Check point on V-notch weir 1.008 2.464 1.031 2.628 1. 051 2.753 Flow drawn down through V 1.074 2.918 Flow drawn over 15° weir.

Nappe is drawn back agains · V-notch

1.104 3.149 1.206 4.051 1.276 4.834 1.368 6.017 N appe getting sufficient air.

but is clinging 1.451 7.307 1.533 8.755 _Top of trapezoidal weir 1. 607 10.263 Rectangular portion of weir 1.654 11. 280 1.683 ll.972 N appe has sufficient air not

clinging 1. 810 15.012 1.924 17.949 High ridge in center of draw

down 2.036 20.944 Beautiful nappe, no clinging 2.111 23.171 2.211 26.469 2.329 30.149 2.427 33.205

t

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 18: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

Table 5

CALIBRATION OF COMPOUND WEIR. 1-FOOT DEPTH 90° V-NOTCH

WITH 1-FOOT 15° BLADES Head Flow

.Da,te run (H·ft) (Q cfs) ,Remarks

February 25 1 1960 1.041 2.716 Well aerated nappe 1.088 2.933 Nappe began clinging on edge

-of 15° blade 1.134 3.418 Nappe clinging 1.184 3.874 N appe clinging slightly 1.233 4.366 1.286 4.951 Nappe springing free 1.334 5.563 1.385 6.220 t.434 6.935 l.485 7.674 1.534 8.435 1.585 9.263 1.634 10.040 1.684 10.901 1. 734 11. 789

February 26 1 1960 1.809 13.138 1. 869 14.262 1.944 15.747 2.013 17.104 2.108 19. 292 · Head box surging noted 2_. 183 20.991 Head box surging noted 2.220 21. 719 Head box surging noted 2.247 22.324 2.319 24.808 Surging in head box1 difficult

to read head accurately 2.532 28.992 Surging in head box1 difficult

to read head accurately

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 19: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

A. Compound weir, 90° V-notch with horizontal extensions, used to measure stream flows by the United States Department of Agricul­ture Forest Service •

B. A general view of test facility used to study the compound weir.

COMPOUND WEIR STUDY

Field and Laboratory Weir Installations

Figure 1 Report Hyd. 505

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 20: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

c:>

"' .. 0.

'­.. .., .. .. "­I I

I I

l\ I /\ ', ....... ___ ,~_,,,,, I \ I I \ /

i I

I

I

I I

I

I I

I I

I

y-----1

I

I ' I I -~,.._.~_.._..,_ ___ ~v I I I ; I /

:/ V

/1 / I

/ 'l'~_,__._ ___ ___,r • I c:>

f'

I I

I I

I

I I

I I

I

-f----\ ' ' ' ' ' \ \

\ \ -,-

655

\ \

\ \ \ \

\ \ \ \

\ \ \ \

-=-~ \ ' \

-~ \ ' \

\ ""a'I

\ ' \-~ ' \ \ \

\ ' \ \ \ \

' \ \ ' \ \\

\ \ \ \

\ \ \ \

\ \

' \ ' \ _\. __ "\. __ _

FIGURE 2 REPORT HYO. 505

>-1--...J

~o => <t I- LL U)

a: 1-­_ (/)

UJ LI.I ~ .... Q >-~ a:: 00 a. 1-­::E <t go::

0 ID <t ...J

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 21: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

655

~----------24.00 ''.._ __________ .,.;

i"---12.00 ----- I I I

--,..--r-: " 1 : I I --r -

• I

,I 0 0

I

) 0 LO

<D N

I I I I I I I I

_I 0 0 ,t­N

I I I I

<D

~ -- -:- -12 00 "---

I

I " t.._l

' I ,I

/'\.!" / __ J..::::-,

~7!..•'y6

157f"'/ ... 2 ·,9 >,,

/"', 1/_

<!',,.

~'(, I '-

-l,. ______ ..:,'_450:. _J_____ ',,

',

'",,,

'

', / y

k---------------------48 00" I

I r- -- ------24.00"----------l

--x_--,._---' ----x_-1 I 1

I I I I I I

l : : I I 1 I , I I I I I I ~

I I cp \ = ~ I O 0

I'- N

: N : =. N I

0 1 j 11 1 II

~ : -;12.00 ----+---12.00---~

~ : 1--,;_,,_ : I I -/~

: I 1' <. 42"- I I I -- - --,j,.,I I ~ I//"" I --1-- 11 / ' I o I.,. ii'

52 !.. ~£( - -,75 ' I 2 I 150 I 'z

I _j_______ 6

, .... ___ /j ·.9,:,,,

IJ,6?" /\ct , ----~,

' '

_y__ ------- -- -----

':I.: <96'

0,.

--x_---,._--

,<----- ----24.00" I I ! --T

~~~ 00 ' - . . - - - . 7 1 I I I I I I I

I I I I I

I I I I I I I I I

,I 0 0

0 LO

<D N I

I I I I I I

' ,' 0 0 ,t­N

I I I

I

<D .,, I I I

I 0" -~ 12 11 - 1 -12.0 -- -, I · -- .00 - ---1 I I

I I I I I I I I

I I I I I I I I

I I I I I

I I I I ,

l 67b~ : /"'-' I

I ,'IL_.,-' _J_ __ ¥ /1 45•,t I / I

I ·""'-,:

: 6" s,.,'i-... J-E----13.4 -----,19 ·v.,-,,

' '

' ' /6 '.9;,<

' ' '

j __ _ -- ----~,-- -

' ',,45<!/

' '}/'

I

FIGURE 3 REPORT HYO. 505

~------------------'

---------72.00 ·~-- ------------ ' --------- >t

-i-r-' I I I I I I I I I I I I I

I o I LO

0 0

<D .,,

<D N

I K------- -36.00" ------1 1 I

I ---r I I

0 0 ~ N I I I l II I II

--t--------24'00 -------->r<---12 00----

: I I I

I Io l 1 ~

I I I I I I I I I I I I

~ t 672,1. I/ ',,

I 1 1

~ '~ /_ 1 I ' 6

4~ /7 ~ - - I / ·,9

I II / I r-------25.46---------,--~-:-,

I I

'{s.,,. l,',,

I _! __________ _ ' ' ', 45°­, ' ' ' ' / y/

I

A -<7

_ _J A

--~ 1

1 k- .!." I I 4

I" : ) I

8 :-irt· I I I

- --- --------~ I I I I I I

!

~--- ------------ ---- -- ---- -12 .oo" ---- - ---- -- -- - ' -- ->--1 ·1---~' ,'+--r 1 I I

·r -T-1 I

I I I I

I i

I I I

I I

=1 ~ !!:! I I I

0 :

~--L­~ 52½°/, I I I I I ' I ti-«_

I I I I I I I I

I

~ - -- -- -- - --- --36.oo"------- -- ----

' I ---,._-I I I I I

!'­LO

~

I II I " --1-----24.00---------:>-o<----l2.00--~

I I i """- I I

/ l-- _ I __ J_ --2 I

- 4-85"----- I/ -t-, /

,,/'\,_ •/ ' -~75a---,

/6

--26.to·:.___ /I /I

~/ -----'>-Jz

. .9 >,,

' 6' ·<Jl V,,

' ' ' ' ' ' ' I

',

_y__ _____ --- - -- -------- -- --- - - --,--::-4s~Y-' ' ' ' /

~/

/

I I I I I

I / ! I 1 ,, I I 1 / I = I

1 ,,/1

-IN N I I I

/ /

TYPICAL SECTION A-A

COMPOUND WEIR

WEIR STUD.Y CRESTS

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 22: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

A. 2-foot horizontal extensions.

Head = 1. 02 feet Discharge = 2. 60 cfs

Note that surface tension reduces flow over ex­tensions.

B. 1-foot horizontal extensions.

Head = 1. 12 feet Discharge = 3. 50 cfs

COMPOUND WEIR STUDY

90° V-notch 1-foot deep with horizontal exten­sions. Note that head exceeds capacity of V-notch but flow over horizontal extensions is not fully developed.

Figure 4 Report Hyd. 505

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 23: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

A. No fl.ow.

B. Head = 1. 6 feet Discharge = 13 cfs COMPOUND WEIR STUDY

90° V-notch 1-foot deep with 2-foot horizontal extensions.

C. Head = 1. 6 feet

Discharge = 13 cfs

~1%J CD ~·· "O~ ~ '1 .+ ID

l:Il CJ1

p. CJ1 0 CJ1

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 24: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

-A. No flow.

B. Head = 1. 7 feet Discharge .. 12 cfs

COMPOUND WEIR STUDY

90° V-notch 1-foot deep with 1-foot horizontal extensions.

C. Head = 1. 7 feet Discharge = 12 cfs

~ ltj Cl) ....

'ti Otl 0 i::: ""l ""l .+ Cl)

tI: 0)

'< p. C11 0 C11

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 25: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

A. No flow.

B. Head= 1. 9 feet Discharge = 9. 8 cfs COMPOUND WEIR STUDY

C. Head = 1. 9 feet Discharge = 9. 8 cfs

90° V-notch 1-foot deep with vertic·al extensions.

!:d l'%j (1) ....

'8~ '1 '1 .... (1)

t:r::--1 « p. c.n 0 c.n

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 26: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

A. No flow.

B. Head= 1.2 Discharge = 3. 7

COMPOUND WEIR STUDY

90° V-notch 1-foot deep with extensions on 15° slope.

C. Head= 1,2 Discharge = 3. 7

:;c ltj (1) ....

"d~ 0 '1 ::t.(1)

::i::oo ~ p. CJ1 C CJ1

Page 27: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

0, UI GI 1.5

.... l&J l&J IL I --:c --

0 ~ l&J :c

1.0

.90

.80

.70

. 60

.50

.40

.30 ~

.25

.20

.15 .10

_,,. ~ ~

__,,. ~

v---~

~ .. ~

~

__. K ,.,,,,.- ~ ...... 'Q= 2.49H 2•48

o-OATA FOR 90° V-NOTCH

.15 .20 .25 .30 '4-0 .50 .60 .70 .80 .90 1.0 us 2.0 2.5 3.0

DISCHARGE (Q)-CFS

COMPOUND WEIR STUDY

V-NOTCH DATA COMPARISON WITH CONE EQUATION

4.0

::v 111 "II o."TI :u--1 G)

C: :r :::u -< 1:1'1 p

<JI CD 0 OI

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 28: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

• GI GI 3.0

2.5 I

2D

1.5

I-II.I II.I .... I -:I: 0 <t 1.0 II.I :I:

.9

.8

.7

.6

.5

.4

,/ l..-"°

In

/ /

~x-~ ~ ~.,;.-

V ~ -_,r:;A

~ .... x--x

l/ ~_.......x

/ .LI" LP--

~~ ...., ~ --- ~ ~-~~--- x..-... ~x

~~x:..-X-TOP OF V-NOTCH-----,

::--- !

I I __ / ~- -x

..,____ ___ ·-VT '

--.!!!' I

1E XPLANATI ON -;- v- NOTCH

o VERTICAL

D 1'-HORIZONTAL

X 2°-HC>RIZONTAL

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 15.0 20.0 30.0 DISCHARGE (Q)-CFS

COMPOUND WEIR STUDY

CALIBRATION DATA 90° V-NOTCH WITH VERTICAL AND HORIZONTAL EXTENSIONS

40.0

:,a Ill

~"II :u--tG>

C: :z::u ~I'll

~a 0 GI

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 29: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

a,

"' 2.8 "'

2.7

2.6

2.5

2.4

2.3

2.2

2.1

2.0

1.9

1,8

. I-Ill 1.7 Ill ...

• 1.6 ~ - 1.5 C

"' 111 1.4 :c

1.3

1.2

I.I

1.0 .

.9

.8

- 7 .7 I

. ,.. __

IS J

.5

.4

.3 0

/',I" v~ CD 0 = -2.420 + 2.661 H + 2.126 He / _,,. .. @ Q = -4.579 + 1.792H + 4.732 Hee / __,,.,,.. V @ Q = -5.589 - 0.859 H + 8.005 H /

/" V ~

I/ v_ ...... ©vertical- --- @1 Foot Horizonol- --.. V / 1--""'" -__,,.. --_...V / V

i..--,.......,......

V V L,..,-- ... / _/ i..--

.,..v _,/ V ..,.... < ...

/' V .,...... ~ ---@2 Foot Horizonal / ---/'I" V V ~ ./

/" v"" __,,.. v'"" /' /

,,,,. ........ ~

'I' V / V V

~, V ...-v/ ~ V 1.2

t:--<-@ I- ~ ~ ; .....-, Ill I ~ I.I p ,,,..

b# I

I :c --...--:::: ..... / I I -- i,.,

~ 1.0 .... ,_ .... / --- --- ___ J

/v-notch Ill :c

.9 ., I

3 4 5 I 2 -v- notch Portion OISCHARGE(Q), G.F.S.

5.0 10.0 15.0 20.0 25.0 30.0 35.0 ::a Ill .. "II o-

D ISCH AR GE (Q), 0. F. S. ~~ COMPOUND WEIR STUDY ~:

HEAD -.DISCHARGE CURVES ~ _ 90° V-NOTCH WITH VERTICAL ANO HORIZONTAL EXTENSIONS :-

- - . 0

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 30: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

I-z <r: I-(/)

z 0 0

II.. 0

l&.I :::, ..J <r: >

655

9

8

1

6

5

4

3

T 2 ii

0

-I

-2

-3 '"' -4

-5

-6

-1 0

...... FIGURE 12

REPORT HYD. 505

I

/ •.

/ /

/~",03 . /

/~

/ /

/ ------- .......,~ .,.J.12 lit!'

' ~ ~I

.EQUATIONS 0o=-2.420+2.661H + 2.126H2

01 •-4.579+1.792H+4.732H2

~ '"

02 = -5.589-0.859H+8.005H2

~ .:...91 F-. --~

1.0 2.0 3.0 4.0 5.0

TOTAL LENGTH OF HORIZONTAL CREST(L),FEET

GENERAL FORM OF EQUATION: Q = a1 + a2 H+ a3 H2

COMPOUND WEIR STUDY

VARIATION OF THE CONSTANTS IN THE DISCHARGE EQUATIONS FOR V-NOTCH WEIRS

WITH HORIZONTAL EXTENSIONS

6.0

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 31: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

en CII (II 5.0

4.0

3.0

2.5

I-L&J 2.0 L&J u. I -::c --

0 <( L&J :c

1.5

. 1.0

.9

.8

.7

.6

.5 1.5

I

' 2.0

V -

V ~

IV'--- ·Q=3.9H'-72

V V

V I/ .,,

3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 15.0 20.0

DISCHARGE (AJUSTED)-(Q)-CFS

COMPOUND WEIR STUDY

CALIBRATION CURVE OF VERTICAL EXTENSIONS A.BOVE 90° V-NOTCH

30.0 40.0 50,0 60.0

:::u ITI "lJ O"TI :::o­-t Ci)

C: :c ::0 < 1'11 C

(JI (>I

0 (JI

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 32: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

0) (II

CJI

... LaJ LaJ IL I --.s= -

0 ~ LaJ

' :I:

1.0

.9

.8

.7

• 6

.5

.4

• 3

.25

.2

1 Q.H ~ i--f-,.--- Al I I I I .-+-__j_ I 2 flv Q I , , I ...!!. I h I

L--- 2 I I H ---t-+-A~ I --, I ' ' ,--- -/2--'>4 I ___ _j __ y_ I --+--•-1 ~ L , - I • I

I I 1 - I

___ ·: : 1 /)0,.-T·+-L I r<--L/2--~ I

~QT-QV - - - - ----~t- -~- ! ---r---1----

t-----t--+-----+---+- •

EXPLANATION o L: 2 FEET X L :4 FEE'T

----•r---,-,---1---t-t--t-+----t---+--'-:--.---.------,,----l----t--J-J

•, .15 ,___.....___...._ _ __., __ .._____.. _ _,__.....___.____.. ___ __._ __ _....._ _ __._ _____ ...._ ____ ....___._,_,,

.2 .25 .3 .4 .5 .6 .7 .8 .9 1.0 1.5 2 2.5 3 4 5 6 7 8

DISCHARGE (Q) - CFS PER FT.

COMPOUND WEIR STUDY

CALIBRATION CURVE OF HORIZONTAL EXTENSIONS ABOVE 90° V-NOTCH WEIR

:u f'l'I "U O"TI ::a --f Ci)

C: :::c ::u -< ITI 0

U'I~ 0 (JI

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 33: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

0, ca ca 3.0

2.5

2.0

1.5

I-.... .... ... I -J::

0 ct 1.0 i.iJ J:

,9

.8

.7

.6

.5

.4

[]

~/ .... {"x--

__,,,,u ~x_.......x ~x.-

TOP OF 15°-2' EXTEN.----- - ~x .... ' ~ ' ~ -- _ .i, -- n.x•

~~ ~

TOP OF 15°-1' EXTEN.----- - _

---~ ,.,.,.-,o,c•---) /~

___ .l::,·

_,~

~

EXPLANATION 0 V- NOTCH 4 15° EXTENSIONS D ABOVE 1' EXTEN, X ABOVE 2' EXTEN.

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 15,0 20.0 30.0 DIS CHARGE (QI-CFS

COMPOUND WEIR STUDY

CALIBRATION DATA OF 90° V-NOTCH WITH· 15° UPWARD SLOPING EXTENSIONS

40.0 ;u

"' .,, 0"11 ;u--1G>

C: ::c::u -<1"11 ?_ (JI (11

0 (JI

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 34: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated

~ m c.>

"' "' "' 0

"' en en

2.6

2.5

2.4

2.3

2.2

2.1

2.0

1.9

1.8

1.7

I-. l&.I 1.6 l&.I ... ,..: 1.5

J: - 1.4 Q C( l&.I 1.3 J:

1.2

I.I

1.0

.9

.8

.7

~~ 0

I

I I ""-V-notch

l5

® © ®

~ Q 2.22H3.21 Q -11.345 +7.484H + 3.360H 2

Q -14.106 +6.943H + 5.IIOH2

~ © I-Foot Sloping~ ~

~II~ ~ ~ 2 - Foot Sloping

.A"11~

I- 1.2 (----+----.-,.£----+----1-----1---...V l&.I l&.I ... ~ui-----t,,~--+----+----1------V

0 C( l&.I

J...----r-

.,___J.-f

·:i: 1.o 2 I I I I I I I I I I I I I

3 4 5 6

I I I

10

DISCHARGE (Q), C.F.S.

I I I I I I I I 15 20

DI SCH A R G E (Q), C. F. S.

COMPOUND WEIR STUDY

HEAD - DISCHARGE CURVES

25

90° V NOTCH ·WITH 15° UPWARD SLOPING EXTEN,SIONS

30 35

::u ITI "U 'Tl . o­::UG) -t c:: :z:::U -c 1"11 ~ CIICJ> 0 CII

Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Sam Peng
Sticky Note
None set by Sam Peng
Sam Peng
Sticky Note
MigrationNone set by Sam Peng
Sam Peng
Sticky Note
Unmarked set by Sam Peng
Page 35: HYDRAULICS BRANCH OFFICIAL FILE COP YTable Calibration Data for V -notch with 2-foot Horizontal ... This arrangement provided a minimum of 60 square feet iri the· ... heads indicated