DesignRemote Area Name
Remote Area Location
Occupancy Classification
Density (gpm/ft²)
Area of Application (ft²)
Coverage per Sprinkler (ft²)
Number of Calculated Sprinklers
In-Rack Demand (gpm)
Special Heads
Hose Streams (gpm)
Total Water Required (incl. Hose Streams) (gpm)
Required Pressure at Source (psi)
Type of System
Volume - Entire System (gal)
2
Manual Wet Standpipe
Residential
N/A (In-Rack)
1
N/A (In-Rack)
2
0
501.9
158.2
Wet
176.1 gal
Water Supply InformationDate
Location
Source
HYDRAULIC CALCULATIONSfor
11/29/2014
On Site Hydrant
W1
500 gpm @ 100 psi
Project Name : Silverleaf Ambassador Bldg. 4
Contract No. : 302-15
Project Location: 121 Emerald Loop
City: Davenport, FL
Date: 1/30/2015
Name of Contractor: Southern Fire Protection
Address: 3801 E. SR 46
Phone Number: 407-323-4200
Name of Designer: MS
Authority Having Jurisdiction: Polk County Fire Rescue
City: Sanford, FL 32771
E-mail:
Job Information
Contractor Information
Notes
Date 1/30/2015 Page 1Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Diagram for Design Area : 2(Optimized Hydraulic Simplified)
Node Labels:Pipe Labels:
OffOff
Date 1/30/2015 Page 2Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 2
Water Supply Parameters
Calculation InfoCalculation ModeHydraulic ModelFluid NameFluid Weight, (lb/ft³)Fluid Dynamic Viscosity, (lb·s/ft²)
DemandHazen-WilliamsWater @ 60F (15.6C)N/A for Hazen-Williams calculation.N/A for Hazen-Williams calculation.
Supply 1 : W1 Flow (gpm) Pressure (psi)0 56
750 30
Inside Hose Flow / Standpipe Demand (gpm)
Outside Hose Flow (gpm)
Additional Outside Hose Flow (gpm)
Other (custom defined) Hose Flow (gpm)
Total Hose Flow (gpm)
501.9
501.9
Hoses
Ovehead Sprinkler Flow (gpm)
InRack Sprinkler Flow (gpm)
Other (custom defined) Sprinkler Flow (gpm)
Total Sprinkler Flow (gpm)
Required Margin of Safety (psi)
BOR - Pressure (psi)
BOR - Flow (gpm)
Demand w/o System Pump(s)
0
137.5
501.9
N/A
Sprinklers
Other
Date 1/30/2015 Page 3Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 2
Supply System Demand
Flow, gpm
Pres
sure
, psi
200
180
160
140
120
100
80
60
40
20
0
S1
S226.703
D1
D2
0 300 400 500 600 700 800
Date 1/30/2015 Page 4Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 2
Pressure (psi)Label
Graph Labels
Flow (gpm)Values
Description
0S1 56Supply point #1 - Static750S2 30Supply point #2 - Residual
0D1 13.8Elevation Pressure501.9D2 158.2System Demand
Pressure (psi)Curve Name
Curve Intersections & Safety Margins
Flow (gpm)Safety MarginIntersection
Pressure (psi) @ Flow (gpm)247Supply 52.7 -114.6 501.9
Open Heads
Head Ref.DensityDensity
K-FactorPressureFlow Pressure
(gpm/ft²)(gpm/ft²)(gpm/psi½) (psi)(gpm) (psi)
Flow
(gpm)
Coverage
(ft²)
Required CalculatedHead Type
H1 0 250 100 0 1002500StandpipeDemand
H2 0 250 100 0 101.5251.90StandpipeDemand
Date 1/30/2015 Page 5Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Node Data
Hydraulic Calculations / Fluid Delivery Time Analysis
Node#Elev
ft
TypeHgroup
K-Fact.Open/Closed
gpm/psi½
DischargeOverdischarge
gpmgpm
CoverageDensity
ft²gpm/ft²
Tot. Pres.Elev. Pres.
psipsi
Req. Pres.Req. Discharge
psigpm
H128.75
Standpipe DemandSDNODE Open
2500
100-13.8
100250
H228.75
Standpipe DemandSDNODE Open
251.91.9
101.5-13.8
100250
SP229.25
NodeNODE
121.3-14
CV4-O4.47
NodeNODE
133.4-3.2
CV4-I3.67
NodeNODE
135.5-2.9
BV4-I3.5
NodeNODE
136.2-2.8
BOR1
NodeNODE
137.5-1.7
BFP-O2
NodeNODE
146.2-2.2
BFP-I2
NodeNODE
154.2-2.2
W1-3
SupplySUPPLY -501.9 158.2
0
Date 1/30/2015 Page 6Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Hydraulic Calculations / Fluid Delivery Time AnalysisJob : Silverleaf Ambassador Bldg. 4
Pipe DataPipe Ref. Start End Size Total Len.
ft
Schedule Velocity
ft/s
0005 SP2 H1 2.5 137.36 CPVC 17.4
0006 CV4-O SP2 4 26.09 10 11.3
0750 CV4-I CV4-O 4 CV-1 FR Check 0
0749 BV4-I CV4-I 4 BFV-N 0
0009 BOR BV4-I 4 3.82 10 11.3
0014 BFP-O BOR 4 228.99 DI350 11.09
0751 BFP-I BFP-O 4 Watts 757 DCDA 0
0017 W1 BFP-I 4 46.86 DI350 11.09
0545 SP2 H2 2.5 125.71 CPVC 17.53
Date 1/30/2015 Page 7Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Hydraulic CalculationsJob : Silverleaf Ambassador Bldg. 4
PIPE INFORMATIONNode 1Node 2
Elev 1Elev 2
(ft)
K-Factor 1K-Factor 2
(gpm/psi½)
Flow added (q)Total flow (Q)
(gpm)
Nominal IDActual ID
(in)
Fittingsquantity x (name) = length
(ft)
LFT
(ft)
C FactorPf per ft
(psi)
total (Pt)elev (Pe)frict (Pf)
(psi)
NOTES
1Path No: H1SP2
28.7529.25
250250
2.52.423
1x(us.Tee-Br)=16.534x(BM.90)=48
72.8264.53
137.36
1500.1564
100-0.221.5
SP2CV4-O
29.254.47
251.9501.9
44.26
1x(coupling)=1.32 24.781.32
26.09
1200.0551
121.310.71.4
CV4-OCV4-I
4.473.67
0501.9
40
0.80
0.8
02.1004
133.40.31.7
CV-1 FRCheck
CV4-IBV4-I
3.673.5
0501.9
40
0.170
0.17
04.0937
135.50.10.7
BFV-N
BV4-IBOR
3.51
0501.9
44.26
1x(coupling)=1.32 2.51.323.82
1200.0551
136.21.10.2
BORBFP-O
12
0501.9
44.3
1x(coupling)=1.834x(us.90)=73.31
153.8575.14
228.99
1400.0395
137.5-0.49.1
BFP-OBFP-I
22
0501.9
40
3.170
3.17
02.5451
146.20
8.1
Watts 757DCDA
BFP-IW1
2-3
0501.9
44.3
2x(us.90)=36.66 10.236.6646.86
1400.0395
154.22.21.9
W1 158.2
2Path No: H2SP2
28.7529.25
251.9251.9
2.52.423
1x(us.Tee-Br)=16.534x(BM.90)=48
61.1764.53
125.71
1500.1586
101.5-0.219.9
SP2 121.3
* Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding.
* Maximum Velocity of 17.53 ft/s occurs in the following pipe(s): (SP2-H2)
Date 1/30/2015 Page 8Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Design
Remote Area Name Remote Area Location Occupancy Classification Density (gpm/ft²) Area of Application (ft²) Coverage per Sprinkler (ft²) Number of Calculated Sprinklers In-Rack Demand (gpm) Special Heads Hose Streams (gpm) Total Water Required (incl. Hose Streams) (gpm) Required Pressure at Source (psi) Type of System Volume - Entire System (gal)
5 3rd Floor Breezeway Residential 0.104 447 144 4 0 100 170.2 44.8 Wet 159.1 gal
Water Supply Information
Date Location Source
HYDRAULIC CALCULATIONSfor
11/29/2014 On Site Hydrant W1
Four Head Calc
Project Name : Silverleaf Ambassador Bldg. 4 Contract No. : 302-15 Project Location: 121 Emerald Loop
City: Davenport, FL Date: 1/30/2015
Name of Contractor: Southern Fire Protection Address: 3801 E. SR 46 Phone Number: 407-323-4200 Name of Designer: MS Authority Having Jurisdiction: Polk County Fire Rescue
City: Sanford, FL 32771 E-mail:
Job Information
Contractor Information
Notes
Date 2/3/2015 Page 1Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\desktop\my folder\autocad backup\302-15 FP Hyd_1_1_1762.sv$
Job : Silverleaf Ambassador Bldg. 4
Diagram for Design Area : 5(Optimized Hydraulic Simplified)
Node Labels:Pipe Labels:
OffOff
Date 2/3/2015 Page 2Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\desktop\my folder\autocad backup\302-15 FP Hyd_1_1_1762.sv$
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 5
Water Supply Parameters
Calculation Info
Calculation ModeHydraulic ModelFluid NameFluid Weight, (lb/ft³)Fluid Dynamic Viscosity, (lb·s/ft²)
DemandHazen-WilliamsWater @ 60F (15.6C)N/A for Hazen-Williams calculation.N/A for Hazen-Williams calculation.
Supply 1 : W1 Flow (gpm) Pressure (psi)0 56
750 30
Inside Hose Flow / Standpipe Demand (gpm) Outside Hose Flow (gpm) Additional Outside Hose Flow (gpm) Other (custom defined) Hose Flow (gpm) Total Hose Flow (gpm)
100 100
Hoses
Ovehead Sprinkler Flow (gpm) InRack Sprinkler Flow (gpm) Other (custom defined) Sprinkler Flow (gpm) Total Sprinkler Flow (gpm)
70.2 0 0 70.2
Required Margin of Safety (psi) BOR - Pressure (psi) BOR - Flow (gpm) Demand w/o System Pump(s)
0 35.5 70.2 N/A
Sprinklers
Other
Date 2/3/2015 Page 3Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\desktop\my folder\autocad backup\302-15 FP Hyd_1_1_1762.sv$
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 5
Supply System Demand Add. Out. Hose
Flow, gpm
Pre
ssu
re, p
si60
50
40
30
20
10
0
S1
S2
26.703
D1
D2D2 D3
0 300 400 500 600 700 800
Date 2/3/2015 Page 4Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\desktop\my folder\autocad backup\302-15 FP Hyd_1_1_1762.sv$
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 5
Pressure (psi)Label
Graph Labels
Flow (gpm)Values
Description
0S1 56Supply point #1 - Static
750S2 30Supply point #2 - Residual
0D1 13.3Elevation Pressure
70.2D2 44.8System Demand
170.2D3 44.8System Demand + Add.Out.Hose
Pressure (psi)Curve Name
Curve Intersections & Safety Margins
Flow (gpm)Safety MarginIntersection
Pressure (psi) @ Flow (gpm)82.3Supply 55.6 9.5 170.2
Open Heads
Head Ref.DensityDensity
K-FactorPressureFlow Pressure
(gpm/ft²)(gpm/ft²)(gpm/psi½) (psi)(gpm) (psi)
Flow
(gpm)
Coverage
(ft²)
Required CalculatedHead Type
S50 5.6 0.1 14.4 7.2 0.151 15.121.7144OverheadSprinkler
S51 5.6 0.1 14.4 7.2 0.128 10.918.5144OverheadSprinkler
S52 5.6 0.1 14.4 7.2 0.104 7.215144OverheadSprinkler
S53 5.6 0.1 14.4 7.2 0.104 7.215144OverheadSprinkler
Date 2/3/2015 Page 5Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\desktop\my folder\autocad backup\302-15 FP Hyd_1_1_1762.sv$
Job : Silverleaf Ambassador Bldg. 4
Node Data
Hydraulic Calculations / Fluid Delivery Time Analysis
Node#Elev
ft
TypeHgroup
K-Fact.Open/Closed
gpm/psi½
DischargeOverdischarge
gpmgpm
CoverageDensity
ft²gpm/ft²
Tot. Pres.Elev. Pres.
psipsi
Req. Pres.Req. Discharge
psigpm
S5327.58
Overhead SprinklerHEAD
5.6Open
150.6
1440.104
7.2-13.3
7.214.4
S5227.58
Overhead SprinklerHEAD
5.6Open
150.6
1440.104
7.2-13.3
7.214.4
S5127.58
Overhead SprinklerHEAD
5.6Open
18.54.1
1440.128
10.9-13.3
7.214.4
S5027.58
Overhead SprinklerHEAD
5.6Open
21.77.3
1440.151
15.1-13.3
7.214.4
31328.42
NodeNODE
7.2-13.6
31128.42
NodeNODE
7.2-13.6
31228.42
NodeNODE
7.9-13.6
30928.42
NodeNODE
11.1-13.6
31028.42
NodeNODE
12.5-13.6
30528.42
NodeNODE
15.5-13.6
30628.42
NodeNODE
19-13.6
30728.42
NodeNODE
19.1-13.6
30028.42
NodeNODE
22.2-13.6
CV3-O26.92
NodeNODE
23.1-13
CV3-I26.92
NodeNODE
23.6-13
BV3-O26.92
NodeNODE
23.6-13
BV3-I26.92
NodeNODE
23.7-13
SP326.92
NodeNODE
24-13
CV4-O4.47
NodeNODE
33.8-3.2
CV4-I3.67
NodeNODE
34.3-2.9
BV4-I3.5
NodeNODE
34.4-2.8
BFP-O2
NodeNODE
35.3-2.2
BOR1
NodeNODE
35.5-1.7
BFP-I2
NodeNODE
42.6-2.2
W1-3
SupplySUPPLY -70.2 44.8
0
Date 2/3/2015 Page 6Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\desktop\my folder\autocad backup\302-15 FP Hyd_1_1_1762.sv$
Hydraulic Calculations / Fluid Delivery Time AnalysisJob : Silverleaf Ambassador Bldg. 4
Pipe Data
Pipe Ref. Start End Size Total Len.
ft
Schedule Velocity
ft/s
0002 313 S53 1 5.03 40 5.57
0004 312 313 1 16.83 CPVC 5.05
0011 310 312 1 32.16 CPVC 10.11
0019 307 310 1 18.85 CPVC 16.33
0168 300 307 2 84.24 CPVC 7.15
0170 CV3-O 300 2.5 8.93 40 4.7
0750 CV3-I CV3-O 2.5 CV-1F Check 0
0171 BV3-O CV3-I 2.5 1.18 40 4.7
0749 BV3-I BV3-O 2.5 BFV-N 0
0172 SP3 BV3-I 2.5 12.6 40 4.7
0173 CV4-O SP3 4 23.76 10 1.58
0752 CV4-I CV4-O 4 CV-1 FR Check 0
0751 BV4-I CV4-I 4 BFV-N 0
0175 BOR BV4-I 4 3.82 10 1.58
0180 BFP-O BOR 4 228.99 DI350 1.55
0753 BFP-I BFP-O 4 Watts 757 DCDA 0
0183 W1 BFP-I 4 46.86 DI350 1.55
0007 311 S52 1 5.03 40 5.57
0005 312 311 1 16.28 CPVC 5.06
0017 309 S51 1 5.03 40 6.85
0013 310 309 1 24.27 CPVC 6.22
0530 305 S50 1 5.03 40 8.07
0522 306 305 1 44.12 CPVC 7.33
0485 307 306 2 23 CPVC 2.21
Date 2/3/2015 Page 7Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\desktop\my folder\autocad backup\302-15 FP Hyd_1_1_1762.sv$
Hydraulic CalculationsJob : Silverleaf Ambassador Bldg. 4
PIPE INFORMATION
Node 1Node 2
Elev 1Elev 2
(ft)
K-Factor 1K-Factor 2
(gpm/psi½)
Flow added (q)Total flow (Q)
(gpm)
Nominal IDActual ID
(in)
Fittingsquantity x (name) = length
(ft)
LFT
(ft)
C FactorPf per ft
(psi)
total (Pt)elev (Pe)frict (Pf)
(psi)
NOTES
1Path No:
S53313
27.5828.42
5.6 1515
11.049
2x(us.90)=4 1.034
5.03
1200.0761
7.2-0.40.4
313312
28.4228.42
015
11.101
1x(BM.Tee-Br)=51x(BM.90)=5
6.8310
16.83
1500.0398
7.20
0.7312310
28.4228.42
1530
11.101
1x(BM.Tee-Br)=51x(BM.90)=5
22.1610
32.16
1500.1437
7.90
4.6310307
28.4228.42
18.548.5
11.101
2x(BM.Tee-Run)=21x(BM.Tee-Br)=5
11.857
18.85
1500.3491
12.50
6.6307300
28.4228.42
21.770.2
22.003
1x(us.90)=6.481x(BM.90)=106x(BM.Tee-Run)=61x(BM.Tee-Br)=10
51.7632.4884.24
1500.0376
19.10
3.2
300CV3-O
28.4226.92
070.2
2.52.469
1x(coupling)=11x(us.90)=6
1.937
8.93
1200.0205
22.20.60.2
CV3-OCV3-I
26.9226.92
070.2
2.50
0.670
0.67
00.7842
23.10
0.5
CV-1F Check
CV3-IBV3-O
26.9226.92
070.2
2.52.469
1x(coupling)=1 0.181
1.18
1200.0205
23.60
0.0BV3-OBV3-I
26.9226.92
070.2
2.50
0.150
0.15
00.8365
23.60
0.1
BFV-N
BV3-ISP3
26.9226.92
070.2
2.52.469
1x(us.Tee-Br)=12 0.612
12.6
1200.0205
23.70
0.3SP3CV4-O
26.924.47
070.2
44.26
1x(coupling)=1.32 22.441.32
23.76
1200.0014
249.70.0
CV4-OCV4-I
4.473.67
070.2
40
0.80
0.8
00.2381
33.80.30.2
CV-1 FRCheck
CV4-IBV4-I
3.673.5
070.2
40
0.170
0.17
00.1239
34.30.10.0
BFV-N
BV4-IBOR
3.51
070.2
44.26
1x(coupling)=1.32 2.51.323.82
1200.0014
34.41.1
0BORBFP-O
12
070.2
44.3
1x(coupling)=1.834x(us.90)=73.31
153.8575.14
228.99
1400.001
35.5-0.40.2
BFP-OBFP-I
22
070.2
40
3.170
3.17
02.2992
35.30
7.3
Watts 757DCDA
Date 2/3/2015 Page 8Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\desktop\my folder\autocad backup\302-15 FP Hyd_1_1_1762.sv$
Hydraulic CalculationsJob : Silverleaf Ambassador Bldg. 4
PIPE INFORMATION
Node 1Node 2
Elev 1Elev 2
(ft)
K-Factor 1K-Factor 2
(gpm/psi½)
Flow added (q)Total flow (Q)
(gpm)
Nominal IDActual ID
(in)
Fittingsquantity x (name) = length
(ft)
LFT
(ft)
C FactorPf per ft
(psi)
total (Pt)elev (Pe)frict (Pf)
(psi)
NOTES
1Path No:
BFP-IW1
2-3
070.2
44.3
2x(us.90)=36.66 10.236.6646.86
1400.001
42.62.20.0
W1 44.8
2Path No:
S52311
27.5828.42
5.6 1515
11.049
2x(us.90)=4 1.034
5.03
1200.0763
7.2-0.40.4
311312
28.4228.42
015
11.101
1x(BM.Tee-Br)=51x(BM.90)=5
6.2810
16.28
1500.0399
7.20
0.6312 7.9
3Path No:
S51309
27.5828.42
5.6 18.518.5
11.049
2x(us.90)=4 1.034
5.03
1200.1117
10.9-0.40.6
309310
28.4228.42
018.5
11.101
1x(BM.Tee-Run)=12x(BM.90)=10
13.2711
24.27
1500.0584
11.10
1.4310 12.5
4Path No:
S50305
27.5828.42
5.6 21.721.7
11.049
2x(us.90)=4 1.034
5.03
1200.1514
15.1-0.40.8
305306
28.4228.42
021.7
11.101
4x(BM.Tee-Run)=41x(BM.Tee-Br)=52x(BM.90)=10
25.1219
44.12
1500.0791
15.50
3.5306307
28.4228.42
021.7
22.003
3x(BM.Tee-Run)=3 203
23
1500.0043
190
0.1307 19.1
* Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding.
* Maximum Velocity of 16.33 ft/s occurs in the following pipe(s): (307-310)
Date 2/3/2015 Page 9Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\desktop\my folder\autocad backup\302-15 FP Hyd_1_1_1762.sv$
Design
Remote Area Name Remote Area Location Occupancy Classification Density (gpm/ft²) Area of Application (ft²) Coverage per Sprinkler (ft²) Number of Calculated Sprinklers In-Rack Demand (gpm) Special Heads Hose Streams (gpm) Total Water Required (incl. Hose Streams) (gpm) Required Pressure at Source (psi) Type of System Volume - Entire System (gal)
4 3rd Floor Unit Residential 0.057 341 400 3 0 100 170.7 48.8 Wet 160.8 gal
Water Supply Information
Date Location Source
HYDRAULIC CALCULATIONSfor
11/29/2014 On Site Hydrant W1
3 Head Calc in Single Compartment
Project Name : Silverleaf Ambassador Bldg. 4 Contract No. : 302-15 Project Location: 121 Emerald Loop
City: Davenport, FL Date: 1/30/2015
Name of Contractor: Southern Fire Protection Address: 3801 E. SR 46 Phone Number: 407-323-4200 Name of Designer: MS Authority Having Jurisdiction: Polk County Fire Rescue
City: Sanford, FL 32771 E-mail:
Job Information
Contractor Information
Notes
Date 1/30/2015 Page 1Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Diagram for Design Area : 4(Optimized Hydraulic Simplified)
Node Labels:Pipe Labels:
OffOff
Date 1/30/2015 Page 2Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 4
Water Supply Parameters
Calculation Info
Calculation ModeHydraulic ModelFluid NameFluid Weight, (lb/ft³)Fluid Dynamic Viscosity, (lb·s/ft²)
DemandHazen-WilliamsWater @ 60F (15.6C)N/A for Hazen-Williams calculation.N/A for Hazen-Williams calculation.
Supply 1 : W1 Flow (gpm) Pressure (psi)0 56
750 30
Inside Hose Flow / Standpipe Demand (gpm) Outside Hose Flow (gpm) Additional Outside Hose Flow (gpm) Other (custom defined) Hose Flow (gpm) Total Hose Flow (gpm)
100 100
Hoses
Ovehead Sprinkler Flow (gpm) InRack Sprinkler Flow (gpm) Other (custom defined) Sprinkler Flow (gpm) Total Sprinkler Flow (gpm)
70.7 0 0 70.7
Required Margin of Safety (psi) BOR - Pressure (psi) BOR - Flow (gpm) Demand w/o System Pump(s)
0 39.5 70.7 N/A
Sprinklers
Other
Date 1/30/2015 Page 3Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 4
Supply System Demand Add. Out. Hose
Flow, gpm
Pre
ssu
re, p
si60
50
40
30
20
10
0
S1
S2
26.703
D1
D2D2 D3
0 300 400 500 600 700 800
Date 1/30/2015 Page 4Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 4
Pressure (psi)Label
Graph Labels
Flow (gpm)Values
Description
0S1 56Supply point #1 - Static
750S2 30Supply point #2 - Residual
0D1 13.4Elevation Pressure
70.7D2 48.8System Demand
170.7D3 48.8System Demand + Add.Out.Hose
Pressure (psi)Curve Name
Curve Intersections & Safety Margins
Flow (gpm)Safety MarginIntersection
Pressure (psi) @ Flow (gpm)77.7Supply 55.6 5.5 170.7
Open Heads
Head Ref.DensityDensity
K-FactorPressureFlow Pressure
(gpm/ft²)(gpm/ft²)(gpm/psi½) (psi)(gpm) (psi)
Flow
(gpm)
Coverage
(ft²)
Required CalculatedHead Type
S40 5.8 0.05 20 15.7 0.061 17.724.4400OverheadSprinkler
S41 5.8 0.05 20 15.7 0.057 15.723400OverheadSprinkler
S42 5.8 0.05 20 15.7 0.058 16.123.3400OverheadSprinkler
Date 1/30/2015 Page 5Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Node Data
Hydraulic Calculations / Fluid Delivery Time Analysis
Node#Elev
ft
TypeHgroup
K-Fact.Open/Closed
gpm/psi½
DischargeOverdischarge
gpmgpm
CoverageDensity
ft²gpm/ft²
Tot. Pres.Elev. Pres.
psipsi
Req. Pres.Req. Discharge
psigpm
S4127.92
Overhead SprinklerHEAD
5.8Open
233
4000.057
15.7-13.4
15.720
S4227.92
Overhead SprinklerHEAD
5.8Open
23.33.3
4000.058
16.1-13.4
15.720
S4027.92
Overhead SprinklerHEAD
5.8Open
24.44.4
4000.061
17.7-13.4
15.720
30128.42
NodeNODE
17.2-13.6
30228.42
NodeNODE
21.7-13.6
30328.42
NodeNODE
22.2-13.6
30028.42
NodeNODE
26.3-13.6
CV3-O26.92
NodeNODE
27.1-13
CV3-I26.92
NodeNODE
27.6-13
BV3-O26.92
NodeNODE
27.6-13
BV3-I26.92
NodeNODE
27.8-13
SP326.92
NodeNODE
28-13
CV4-O4.47
NodeNODE
37.8-3.2
CV4-I3.67
NodeNODE
38.3-2.9
BV4-I3.5
NodeNODE
38.4-2.8
BFP-O2
NodeNODE
39.3-2.2
BOR1
NodeNODE
39.5-1.7
BFP-I2
NodeNODE
46.6-2.2
W1-3
SupplySUPPLY -70.7 48.8
0
Date 1/30/2015 Page 6Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Hydraulic Calculations / Fluid Delivery Time AnalysisJob : Silverleaf Ambassador Bldg. 4
Pipe Data
Pipe Ref. Start End Size Total Len.
ft
Schedule Velocity
ft/s
0028 301 S41 1 19.04 CPVC 7.74
0027 302 301 1 14.21 CPVC 15.59
0017 303 302 2 28.88 CPVC 4.71
0195 300 303 2 106.31 CPVC 7.2
0197 CV3-O 300 2.5 8.93 40 4.74
0750 CV3-I CV3-O 2.5 CV-1F Check 0
0198 BV3-O CV3-I 2.5 1.18 40 4.74
0749 BV3-I BV3-O 2.5 BFV-N 0
0199 SP3 BV3-I 2.5 12.6 40 4.74
0200 CV4-O SP3 4 23.76 10 1.59
0752 CV4-I CV4-O 4 CV-1 FR Check 0
0751 BV4-I CV4-I 4 BFV-N 0
0202 BOR BV4-I 4 3.82 10 1.59
0207 BFP-O BOR 4 228.99 DI350 1.56
0753 BFP-I BFP-O 4 Watts 757 DCDA 0
0210 W1 BFP-I 4 46.86 DI350 1.56
0036 301 S42 1 13.96 CPVC 7.85
0014 303 S40 1 47.58 CPVC 8.23
Date 1/30/2015 Page 7Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Hydraulic CalculationsJob : Silverleaf Ambassador Bldg. 4
PIPE INFORMATION
Node 1Node 2
Elev 1Elev 2
(ft)
K-Factor 1K-Factor 2
(gpm/psi½)
Flow added (q)Total flow (Q)
(gpm)
Nominal IDActual ID
(in)
Fittingsquantity x (name) = length
(ft)
LFT
(ft)
C FactorPf per ft
(psi)
total (Pt)elev (Pe)frict (Pf)
(psi)
NOTES
1Path No:
S41301
27.9228.42
5.8 2323
11.101
2x(BM.Tee-Run)=21x(BM.Tee-Br)=51x(BM.90)=5
7.0412
19.04
1500.0877
15.7-0.21.7
301302
28.4228.42
23.346.3
11.101
1x(BM.Tee-Br)=5 9.215
14.21
1500.3203
17.20
4.6302303
28.4228.42
046.3
22.003
4x(BM.Tee-Run)=4 24.884
28.88
1500.0174
21.70
0.5303300
28.4228.42
24.470.7
22.003
1x(us.90)=6.481x(BM.90)=109x(BM.Tee-Run)=91x(BM.Tee-Br)=10
70.8335.48
106.31
1500.0381
22.20
4.1
300CV3-O
28.4226.92
070.7
2.52.469
1x(coupling)=11x(us.90)=6
1.937
8.93
1200.0208
26.30.60.2
CV3-OCV3-I
26.9226.92
070.7
2.50
0.670
0.67
00.7909
27.10
0.5
CV-1F Check
CV3-IBV3-O
26.9226.92
070.7
2.52.469
1x(coupling)=1 0.181
1.18
1200.0208
27.60
0.0BV3-OBV3-I
26.9226.92
070.7
2.50
0.150
0.15
00.8484
27.60
0.1
BFV-N
BV3-ISP3
26.9226.92
070.7
2.52.469
1x(us.Tee-Br)=12 0.612
12.6
1200.0208
27.80
0.3SP3CV4-O
26.924.47
070.7
44.26
1x(coupling)=1.32 22.441.32
23.76
1200.0015
289.70.0
CV4-OCV4-I
4.473.67
070.7
40
0.80
0.8
00.2397
37.80.30.2
CV-1 FRCheck
CV4-IBV4-I
3.673.5
070.7
40
0.170
0.17
00.125
38.30.10.0
BFV-N
BV4-IBOR
3.51
070.7
44.26
1x(coupling)=1.32 2.51.323.82
1200.0015
38.41.1
0BORBFP-O
12
070.7
44.3
1x(coupling)=1.834x(us.90)=73.31
153.8575.14
228.99
1400.001
39.5-0.40.2
BFP-OBFP-I
22
070.7
40
3.170
3.17
02.2987
39.30
7.3
Watts 757DCDA
BFP-IW1
2-3
070.7
44.3
2x(us.90)=36.66 10.236.6646.86
1400.001
46.62.20.0
W1 48.8
Date 1/30/2015 Page 8Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Hydraulic CalculationsJob : Silverleaf Ambassador Bldg. 4
PIPE INFORMATION
Node 1Node 2
Elev 1Elev 2
(ft)
K-Factor 1K-Factor 2
(gpm/psi½)
Flow added (q)Total flow (Q)
(gpm)
Nominal IDActual ID
(in)
Fittingsquantity x (name) = length
(ft)
LFT
(ft)
C FactorPf per ft
(psi)
total (Pt)elev (Pe)frict (Pf)
(psi)
NOTES
2Path No:
S42301
27.9228.42
5.8 23.323.3
11.101
1x(BM.Tee-Br)=51x(BM.90)=5
3.9610
13.96
1500.0898
16.1-0.21.3
301 17.2
3Path No:
S40303
27.9228.42
5.8 24.424.4
11.101
2x(BM.Tee-Run)=22x(BM.Tee-Br)=102x(BM.90)=10
25.5822
47.58
1500.0982
17.7-0.24.7
303 22.2
* Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding.
* Maximum Velocity of 15.59 ft/s occurs in the following pipe(s): (302-301)
Date 1/30/2015 Page 9Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Design
Remote Area Name Remote Area Location Occupancy Classification Density (gpm/ft²) Area of Application (ft²) Coverage per Sprinkler (ft²) Number of Calculated Sprinklers In-Rack Demand (gpm) Special Heads Hose Streams (gpm) Total Water Required (incl. Hose Streams) (gpm) Required Pressure at Source (psi) Type of System Volume - Downstream DPV (gal)
3 4th Floor Breezeway Residential 0.1 479 182 4 0 100 178.2 47.2 Dry 115.2 gal
Water Supply Information
Date Location Source
HYDRAULIC CALCULATIONSfor
11/29/2014 On Site Hydrant W1
Project Name : Silverleaf Ambassador Bldg. 4 Contract No. : 302-15 Project Location: 121 Emerald Loop
City: Davenport, FL Date: 1/30/2015
Name of Contractor: Southern Fire Protection Address: 3801 E. SR 46 Phone Number: 407-323-4200 Name of Designer: MS Authority Having Jurisdiction: Polk County Fire Rescue
City: Sanford, FL 32771 E-mail:
Job Information
Contractor Information
Notes
Date 2/3/2015 Page 1Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FPHyd.dwg
Job : Silverleaf Ambassador Bldg. 4
Diagram for Design Area : 3(Optimized Hydraulic Simplified)
Node Labels:Pipe Labels:
OffOff
Date 2/3/2015 Page 2Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FP Hyd.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 3
Water Supply Parameters
Calculation Info
Calculation ModeHydraulic ModelFluid NameFluid Weight, (lb/ft³)Fluid Dynamic Viscosity, (lb·s/ft²)
DemandHazen-WilliamsWater @ 60F (15.6C)N/A for Hazen-Williams calculation.N/A for Hazen-Williams calculation.
Supply 1 : W1 Flow (gpm) Pressure (psi)0 56
750 30
Inside Hose Flow / Standpipe Demand (gpm) Outside Hose Flow (gpm) Additional Outside Hose Flow (gpm) Other (custom defined) Hose Flow (gpm) Total Hose Flow (gpm)
100 100
Hoses
Ovehead Sprinkler Flow (gpm) InRack Sprinkler Flow (gpm) Other (custom defined) Sprinkler Flow (gpm) Total Sprinkler Flow (gpm)
78.2 0 0 78.2
Required Margin of Safety (psi) BOR - Pressure (psi) BOR - Flow (gpm) Demand w/o System Pump(s)
0 37.9 78.2 N/A
Sprinklers
Other
Date 2/3/2015 Page 3Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FPHyd.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 3
Supply System Demand Add. Out. Hose
Flow, gpm
Pre
ssu
re, p
si60
50
40
30
20
10
0
S1
S2
26.703
D1
D2D2 D3
0 300 400 500 600 700 800
Date 2/3/2015 Page 4Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FPHyd.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 3
Pressure (psi)Label
Graph Labels
Flow (gpm)Values
Description
0S1 56Supply point #1 - Static
750S2 30Supply point #2 - Residual
0D1 18.1Elevation Pressure
78.2D2 47.2System Demand
178.2D3 47.2System Demand + Add.Out.Hose
Pressure (psi)Curve Name
Curve Intersections & Safety Margins
Flow (gpm)Safety MarginIntersection
Pressure (psi) @ Flow (gpm)89.6Supply 55.5 7 178.2
Open Heads
Head Ref.DensityDensity
K-FactorPressureFlow Pressure
(gpm/ft²)(gpm/ft²)(gpm/psi½) (psi)(gpm) (psi)
Flow
(gpm)
Coverage
(ft²)
Required CalculatedHead Type
S30 5.6 0.1 18.2 10.6 0.1 10.618.2182OverheadSprinkler
S31 5.6 0.1 18.2 10.6 0.105 11.619.1182OverheadSprinkler
S32 5.6 0.1 10.8 7 0.185 12.820108OverheadSprinkler
S33 5.6 0.1 10.8 7 0.194 13.920.9108OverheadSprinkler
Date 2/3/2015 Page 5Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FPHyd.dwg
Job : Silverleaf Ambassador Bldg. 4
Node Data
Hydraulic Calculations / Fluid Delivery Time Analysis
Node#Elev
ft
TypeHgroup
K-Fact.Open/Closed
gpm/psi½
DischargeOverdischarge
gpmgpm
CoverageDensity
ft²gpm/ft²
Tot. Pres.Elev. Pres.
psipsi
Req. Pres.Req. Discharge
psigpm
S3038.67
Overhead SprinklerHEAD
5.6Open
18.20
1820.1
10.6-18.1
10.618.2
S3138.67
Overhead SprinklerHEAD
5.6Open
19.10.9
1820.105
11.6-18.1
10.618.2
S3238.67
Overhead SprinklerHEAD
5.6Open
209.2
1080.185
12.8-18.1
710.8
S3338.67
Overhead SprinklerHEAD
5.6Open
20.910.1
1080.194
13.9-18.1
710.8
40740.17
NodeNODE
11.7-18.7
40840.17
NodeNODE
13-18.7
40940.17
NodeNODE
14.2-18.7
40040.17
NodeNODE
19.4-18.7
DV1-O33
NodeNODE
23.5-15.6
DV1-I31.98
NodeNODE
24-15.2
BV1-I31.83
NodeNODE
24.2-15.1
CV4-O4.47
NodeNODE
36.1-3.2
CV4-I3.67
NodeNODE
36.7-2.9
BV4-I3.5
NodeNODE
36.8-2.8
BFP-O2
NodeNODE
37.7-2.2
BOR1
NodeNODE
37.9-1.7
BFP-I2
NodeNODE
44.9-2.2
W1-3
SupplySUPPLY -78.2 47.2
0
Date 2/3/2015 Page 6Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FPHyd.dwg
Hydraulic Calculations / Fluid Delivery Time AnalysisJob : Silverleaf Ambassador Bldg. 4
Pipe Data
Pipe Ref. Start End Size Total Len.
ft
Schedule Velocity
ft/s
0549 407 S30 1 16.5 40Galv 6.76
0548 408 407 1.25 40Galv 7.99
0547 409 408 1.5 40Galv 9.02
0123 400 409 2 88.1 40Galv 7.47
0128 DV1-O 400 2.5 39.95 40Galv 5.24
0750 DV1-I DV1-O 2.5 DPV-1 0
0749 BV1-I DV1-I 2.5 BFV-N 0
0130 CV4-O BV1-I 4 28.68 10 1.76
0752 CV4-I CV4-O 4 CV-1 FR Check 0
0751 BV4-I CV4-I 4 BFV-N 0
0134 BOR BV4-I 4 3.82 10 1.76
0139 BFP-O BOR 4 228.99 DI350 1.73
0753 BFP-I BFP-O 4 Watts 757 DCDA 0
0142 W1 BFP-I 4 46.86 DI350 1.73
0747 407 S31 1 6.5 40Galv 7.08
0746 408 S32 1 6.5 40Galv 7.43
0550 409 S33 1 6.5 40Galv 7.76
Date 2/3/2015 Page 7Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FPHyd.dwg
Hydraulic CalculationsJob : Silverleaf Ambassador Bldg. 4
PIPE INFORMATION
Node 1Node 2
Elev 1Elev 2
(ft)
K-Factor 1K-Factor 2
(gpm/psi½)
Flow added (q)Total flow (Q)
(gpm)
Nominal IDActual ID
(in)
Fittingsquantity x (name) = length
(ft)
LFT
(ft)
C FactorPf per ft
(psi)
total (Pt)elev (Pe)frict (Pf)
(psi)
NOTES
1Path No:
S30407
38.6740.17
5.6 18.218.2
11.049
1x(us.90)=2 14.52
16.5
1200.1089
10.6-0.61.8
407408
40.1740.17
19.137.3
1.251.38
11.50
11.5
1200.108
11.70
1.2408409
40.1740.17
2057.3
1.51.61
110
11
1200.1129
130
1.2409400
40.1740.17
20.978.2
22.067
3x(us.Tee-Br)=30 58.130
88.1
1200.0595
14.20
5.2400DV1-O
40.1733
078.2
2.52.469
1x(coupling)=13x(us.90)=18
20.9519
39.95
1200.025
19.43.1
1DV1-ODV1-I
3331.98
078.2
2.50
1.020
1.02
00.0142
23.50.40.0
DPV-1
DV1-IBV1-I
31.9831.83
078.2
2.50
0.150
0.15
01.0421
240.10.2
BFV-N
BV1-ICV4-O
31.834.47
078.2
44.26
1x(coupling)=1.32 27.361.32
28.68
1200.0018
24.211.90.1
CV4-OCV4-I
4.473.67
078.2
40
0.80
0.8
00.2643
36.10.30.2
CV-1 FRCheck
CV4-IBV4-I
3.673.5
078.2
40
0.170
0.17
00.1423
36.70.10.0
BFV-N
BV4-IBOR
3.51
078.2
44.26
1x(coupling)=1.32 2.51.323.82
1200.0018
36.81.1
0BORBFP-O
12
078.2
44.3
1x(coupling)=1.834x(us.90)=73.31
153.8575.14
228.99
1400.0013
37.9-0.40.3
BFP-OBFP-I
22
078.2
40
3.170
3.17
02.2759
37.70
7.2
Watts 757DCDA
BFP-IW1
2-3
078.2
44.3
2x(us.90)=36.66 10.236.6646.86
1400.0013
44.92.20.1
W1 47.2
2Path No:
S31407
38.6740.17
5.6 19.119.1
11.049
1x(us.Tee-Br)=5 1.55
6.5
1200.1186
11.6-0.60.8
407 11.7
Date 2/3/2015 Page 8Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FPHyd.dwg
Hydraulic CalculationsJob : Silverleaf Ambassador Bldg. 4
PIPE INFORMATION
Node 1Node 2
Elev 1Elev 2
(ft)
K-Factor 1K-Factor 2
(gpm/psi½)
Flow added (q)Total flow (Q)
(gpm)
Nominal IDActual ID
(in)
Fittingsquantity x (name) = length
(ft)
LFT
(ft)
C FactorPf per ft
(psi)
total (Pt)elev (Pe)frict (Pf)
(psi)
NOTES
3Path No:
S32408
38.6740.17
5.6 2020
11.049
1x(us.Tee-Br)=5 1.55
6.5
1200.1297
12.8-0.60.8
408 13
4Path No:
S33409
38.6740.17
5.6 20.920.9
11.049
1x(us.Tee-Br)=5 1.55
6.5
1200.1407
13.9-0.60.9
409 14.2
* Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding.
* Maximum Velocity of 9.02 ft/s occurs in the following pipe(s): (409-408)
Date 2/3/2015 Page 9Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FPHyd.dwg
Design
Remote Area Name Remote Area Location Occupancy Classification Density (gpm/ft²) Area of Application (ft²) Coverage per Sprinkler (ft²) Number of Calculated Sprinklers In-Rack Demand (gpm) Special Heads Hose Streams (gpm) Total Water Required (incl. Hose Streams) (gpm) Required Pressure at Source (psi) Type of System Volume - Downstream DPV (gal)
1 4th Floor Unit Residential 0.056 341 324 4 0 100 173.1 48.3 Dry 120.3 gal
Water Supply Information
Date Location Source
HYDRAULIC CALCULATIONSfor
11/29/2014 On Site Hydrant W1
4 Head Design Area
Project Name : Silverleaf Ambassador Bldg. 4 Contract No. : 302-15 Project Location: 121 Emerald Loop
City: Davenport, FL Date: 1/30/2015
Name of Contractor: Southern Fire Protection Address: 3801 E. SR 46 Phone Number: 407-323-4200 Name of Designer: MS Authority Having Jurisdiction: Polk County Fire Rescue
City: Sanford, FL 32771 E-mail:
Job Information
Contractor Information
Notes
Date 1/30/2015 Page 1Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Diagram for Design Area : 1(Optimized Hydraulic Simplified)
Node Labels:Pipe Labels:
OffOff
Date 1/30/2015 Page 2Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15 FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 1
Water Supply Parameters
Calculation Info
Calculation ModeHydraulic ModelFluid NameFluid Weight, (lb/ft³)Fluid Dynamic Viscosity, (lb·s/ft²)
DemandHazen-WilliamsWater @ 60F (15.6C)N/A for Hazen-Williams calculation.N/A for Hazen-Williams calculation.
Supply 1 : W1 Flow (gpm) Pressure (psi)0 56
750 30
Inside Hose Flow / Standpipe Demand (gpm) Outside Hose Flow (gpm) Additional Outside Hose Flow (gpm) Other (custom defined) Hose Flow (gpm) Total Hose Flow (gpm)
100 100
Hoses
Ovehead Sprinkler Flow (gpm) InRack Sprinkler Flow (gpm) Other (custom defined) Sprinkler Flow (gpm) Total Sprinkler Flow (gpm)
73.1 0 0 73.1
Required Margin of Safety (psi) BOR - Pressure (psi) BOR - Flow (gpm) Demand w/o System Pump(s)
0 39 73.1 N/A
Sprinklers
Other
Date 1/30/2015 Page 3Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 1
Supply System Demand Add. Out. Hose
Flow, gpm
Pre
ssu
re, p
si60
50
40
30
20
10
0
S1
S2
26.703
D1
D2D2 D3
0 300 400 500 600 700 800
Date 1/30/2015 Page 4Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Hydraulic Analysis for : 1
Pressure (psi)Label
Graph Labels
Flow (gpm)Values
Description
0S1 56Supply point #1 - Static
750S2 30Supply point #2 - Residual
0D1 18.1Elevation Pressure
73.1D2 48.3System Demand
173.1D3 48.3System Demand + Add.Out.Hose
Pressure (psi)Curve Name
Curve Intersections & Safety Margins
Flow (gpm)Safety MarginIntersection
Pressure (psi) @ Flow (gpm)82.2Supply 55.6 6 173.1
Open Heads
Head Ref.DensityDensity
K-FactorPressureFlow Pressure
(gpm/ft²)(gpm/ft²)(gpm/psi½) (psi)(gpm) (psi)
Flow
(gpm)
Coverage
(ft²)
Required CalculatedHead Type
S1 4.9 0.05 16.2 13.5 0.057 1418.3324OverheadSprinkler
S2 4.9 0.05 16.2 13.5 0.057 1418.3324OverheadSprinkler
S3 4.9 0.05 16.2 13.5 0.056 13.518324OverheadSprinkler
S4 4.9 0.05 16.2 13.5 0.057 14.218.5324OverheadSprinkler
Date 1/30/2015 Page 5Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Job : Silverleaf Ambassador Bldg. 4
Node Data
Hydraulic Calculations / Fluid Delivery Time Analysis
Node#Elev
ft
TypeHgroup
K-Fact.Open/Closed
gpm/psi½
DischargeOverdischarge
gpmgpm
CoverageDensity
ft²gpm/ft²
Tot. Pres.Elev. Pres.
psipsi
Req. Pres.Req. Discharge
psigpm
S338.67
Overhead SprinklerHEAD
4.9Open
181.8
3240.056
13.5-18.1
13.516.2
S138.67
Overhead SprinklerHEAD
4.9Open
18.32.1
3240.057
14-18.1
13.516.2
S238.67
Overhead SprinklerHEAD
4.9Open
18.32.1
3240.057
14-18.1
13.516.2
S438.67
Overhead SprinklerHEAD
4.9Open
18.52.3
3240.057
14.2-18.1
13.516.2
40140.17
NodeNODE
14.5-18.7
40540.17
NodeNODE
14.6-18.7
40240.17
NodeNODE
14.7-18.7
40340.17
NodeNODE
16.3-18.7
40440.17
NodeNODE
16.5-18.7
40040.17
NodeNODE
20.7-18.7
DV1-O33
NodeNODE
24.7-15.6
DV1-I31.98
NodeNODE
25.1-15.2
BV1-I31.83
NodeNODE
25.3-15.1
CV4-O4.47
NodeNODE
37.2-3.2
CV4-I3.67
NodeNODE
37.8-2.9
BV4-I3.5
NodeNODE
37.9-2.8
BFP-O2
NodeNODE
38.8-2.2
BOR1
NodeNODE
39-1.7
BFP-I2
NodeNODE
46-2.2
W1-3
SupplySUPPLY -73.1 48.3
0
Date 1/30/2015 Page 6Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Hydraulic Calculations / Fluid Delivery Time AnalysisJob : Silverleaf Ambassador Bldg. 4
Pipe Data
Pipe Ref. Start End Size Total Len.
ft
Schedule Velocity
ft/s
0002 405 S3 1 16 40Galv 6.68
0003 404 405 1.25 18.44 40Galv 7.82
0034 400 404 2 79.94 40Galv 6.99
0071 DV1-O 400 2.5 39.95 40Galv 4.9
0750 DV1-I DV1-O 2.5 DPV-1 0
0749 BV1-I DV1-I 2.5 BFV-N 0
0073 CV4-O BV1-I 4 28.68 10 1.65
0752 CV4-I CV4-O 4 CV-1 FR Check 0
0751 BV4-I CV4-I 4 BFV-N 0
0077 BOR BV4-I 4 3.82 10 1.65
0082 BFP-O BOR 4 228.99 DI350 1.62
0753 BFP-I BFP-O 4 Watts 757 DCDA 0
0085 W1 BFP-I 4 46.86 DI350 1.62
0016 401 S1 1 10.9 40Galv 6.81
0011 402 401 1.25 40Galv 3.93
0010 403 402 1.25 15.21 40Galv 7.87
0004 404 403 2 40Galv 3.51
0018 402 S2 1 11.96 40Galv 6.81
0549 405 S4 1 9 40Galv 6.85
Date 1/30/2015 Page 7Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Hydraulic CalculationsJob : Silverleaf Ambassador Bldg. 4
PIPE INFORMATION
Node 1Node 2
Elev 1Elev 2
(ft)
K-Factor 1K-Factor 2
(gpm/psi½)
Flow added (q)Total flow (Q)
(gpm)
Nominal IDActual ID
(in)
Fittingsquantity x (name) = length
(ft)
LFT
(ft)
C FactorPf per ft
(psi)
total (Pt)elev (Pe)frict (Pf)
(psi)
NOTES
1Path No:
S3405
38.6740.17
4.9 1818
11.049
2x(us.90)=4 124
16
1200.1067
13.5-0.61.7
405404
40.1740.17
18.536.5
1.251.38
1x(us.Tee-Br)=6 12.446
18.44
1200.1037
14.60
1.9404400
40.1740.17
36.773.1
22.067
1x(us.Tee-Br)=10 69.9410
79.94
1200.0526
16.50
4.2400DV1-O
40.1733
073.1
2.52.469
1x(coupling)=13x(us.90)=18
20.9519
39.95
1200.0221
20.73.10.9
DV1-ODV1-I
3331.98
073.1
2.50
1.020
1.02
00.0089
24.70.4
0
DPV-1
DV1-IBV1-I
31.9831.83
073.1
2.50
0.150
0.15
00.9092
25.10.10.1
BFV-N
BV1-ICV4-O
31.834.47
073.1
44.26
1x(coupling)=1.32 27.361.32
28.68
1200.0016
25.311.90.0
CV4-OCV4-I
4.473.67
073.1
40
0.80
0.8
00.2478
37.20.30.2
CV-1 FRCheck
CV4-IBV4-I
3.673.5
073.1
40
0.170
0.17
00.1306
37.80.10.0
BFV-N
BV4-IBOR
3.51
073.1
44.26
1x(coupling)=1.32 2.51.323.82
1200.0016
37.91.1
0BORBFP-O
12
073.1
44.3
1x(coupling)=1.834x(us.90)=73.31
153.8575.14
228.99
1400.0011
39-0.40.3
BFP-OBFP-I
22
073.1
40
3.170
3.17
02.2944
38.80
7.3
Watts 757DCDA
BFP-IW1
2-3
073.1
44.3
2x(us.90)=36.66 10.236.6646.86
1400.0011
462.20.1
W1 48.3
Date 1/30/2015 Page 8Copyright © 2002-2012 Tyco Fire Protection Products
File: C:\Users\Michael\Desktop\My Folder\Michael Smith JOBS\302-15 Silverleaf Ambassador #4\FP\302-15FP.dwg
Hydraulic CalculationsJob : Silverleaf Ambassador Bldg. 4
PIPE INFORMATION
2Path No:
S1401
38.6740.17
4.9 18.318.3
11.049
1x(us.Tee-Br)=51x(us.90)=2
3.97
10.9
1200.1104
14-0.61.2
401402
40.1740.17
018.3
1.251.38
4.180
4.18
1200.029
14.50
0.1402403
40.1740.17
18.336.7
1.251.38
1x(us.Tee-Br)=6 9.216
15.21
1200.1048
14.70
1.6403404
40.1740.17
036.7
22.067
14.020
14.02
1200.0146
16.30
0.2404 16.5
3Path No:
S2402
38.6740.17
4.9 18.318.3
11.049
1x(us.Tee-Br)=51x(us.90)=2
4.967
11.96
1200.1104
14-0.61.3
402 14.7
4Path No:
S4405
38.6740.17
4.9 18.518.5
11.049
1x(us.Tee-Br)=51x(us.90)=2
279
1200.1118
14.2-0.6
1405 14.6
* Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding.
* Maximum Velocity of 7.87 ft/s occurs in the following pipe(s): (403-402)