HVDCTMT&D provides the best and most economical HVDC system.In 1955, TMT&D started the development of HVDC

and is the leading HVDC supplier in Japan.

TMT&D has continued to develop HVDC technology

and is now an international supplier of conventional

HVDC systems and Voltage-Sourced Converter

HVDC systems.

TMT&D has the experience to provide world-class

HVDC system engineering.

TMT&D is the world pioneer of light triggered thyristor (LTT) valves.In 1983, field operation of the LTT valve was

performed for the first time in the world.

In 1992, TMT&D installed DC125kV-300MW LTT

valves in the Shin-Shinano frequency converter

station, as the world's first commercial application.

Since 1983, a great number of LTTs have been

installed in many systems around the world. TMT&D

is the world's leader in LTT valve technology.

High reliability, high flexibility, excellent performanceand easy maintenance are realized by intelligent controllers based on microcomputer technology.Since 1987, TMT&D has applied microcomputer

based controllers widely in various HVDC and SVC

systems.

TMT&D provides high quality HVDC systems.TMT&D's LTT valves and microcomputer based

controllers offer highly reliable HVDC systems.

TMT&D holds certificates in quality assurance control

systems in accordance with the standards

ISO9001/EN29001/BS5750/JISZ9901.

TMT&D

Page 3: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

2

Page 4: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

3

The TMT&D System Engineering Department is in the center of the whole engineering project to

establish the optimum HVDC system. Works' laboratories as well as its production departments are

active in developing reliable HVDC systems.

SYSTEM ENGINEERING

Engineering meeting and discussion. Power system simulator as well as digital analysis using super computers are conducted to evaluate the complex phenomena of the AC and DC systems.

System engineers are familiar with today's power transmission systems and equipment as well as tomorrow's technology.

Advanced control strategy and tactics are realized by production designers for each HVDC system.

OPTIMUM HVDC SYSTEM

HVDCTMT&D

Page 5: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

4

System engineering and equipment manufacturing are supported by many researchers from various

fields.

RESEARCH AND DEVELOPMENT

Works' laboratory is active in the development of new operation and control technology.

This picture shows the thyristor stack development to study the application technologies of power electronics devices.

±2000kVDC generation testing facility in the Ultra High Voltage Laboratory is used for the DC high voltage test and the voltage reversal test.

6000kV, 600kJ impulse generator in the Ultra High Voltage Laboratory.

Page 6: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

5

HVDC SYSTEM ENGINEERING FLOW DIAGRAMHVDCTMT&D

REQUIREMENTS

REQUIREMENTS

SYSTEMENGINEERING

RATED POWER

REACTIVEPOWER

AC VOLTAGE DEVIATION

OVERVOLTAGE LIMIT

EQUIPMENTDESIGN

CONTROL & PROTECTION SYSTEM DESIGN

VALVE RATING

CONTROL STRATEGY

HARMONICS DISTORTION EMI

AC SYSTEM IMPEDANCE CONDITION

OPERATION FUNCTION

SYSTEMPERFORMANCE

CONVERTER TRANSFORMER

RATING

PRELIMINARY SYSTEM

CONFIGURATION

BASICRATING DESIGN

FILTER RATING

SYSTEM STABILITY STUDY

HARMONICS STUDY

OVERVOLTAGE STUDY

Page 7: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

6

TMT&D complies with customers' specifications and forwards economic alternatives by cultivated HVDC system engineering art.The following diagram shows the typical system engineering flow.

OPTIMUMDESIGN

ENVIRONMENTAL CONDITION

MINIMUMCOST

RADIONOISE

MINIMUMCOST

AVAILABILITY RELIABILITY

PROTECTIONSTRATEGY

OPERATION SYSTEM

SYSTEMCONFIGURATION

DESIGN

REACTIVECOMPENSATION

RATING

SURGE ARRESTER RATING

SWITCHGEARRATING

EQUIPMENTOUTLINE

LAYOUT DESIGN

RADIONOISESTUDY

VALVE HALL

DESIGN

COSTEVALUATION

RELIABILITYSTUDY

CONTROL AND PROTECTION

CONFIGURATION DESIGN

PLANNING OF CIVIL AND

CONSTRUCTIONWORK

LOSSEVALUATION

RATING

EQUIPMENT

CONTROL

PROTECTION

LAYOUT

COST

LOSS

SWITCHING DUTY STUDY

INSULATION COORDINATION STUDY

Page 8: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

7

TMT&D has developed and supplied various equipment for AC and DC power systems.

EQUIPMENTHVDCTMT&D

CONTROL &PROTECTION

TMT&D has supplied a lot of switchgear covering voltages from 72kV to 1100kVAC.The picture shows 550kV Gas Insulated switchgear with three phase encapsulated main busbar.

The picture shows an AC harmonic filter for an HVDC project.

TMT&D produces telecontrol devices, man-machine devices, programmable controllers, power system controllers, converter controllers, and protection relays.The picture shows a supervisory control and data acquisition (SCADA) system.

Page 9: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

8

The picture shows a DC smoothing reactor and a DC surge arrester for an HVDC link.

TMT&D has supplied many transformers up to 1100kV since 1894. The picture shows converter transformers for an HVDC link.

The LTT valve is the most advanced thyristor valve. The picture shows 250kV DC LTT valves for an HVDC link.

Page 10: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

9

Basic control functions

TMT&D provides a wide variety of control and protection technology, and utilizes optimum strategies for each HVDC project. The optimum control and protection systems are designed with careful attention to the interaction between DC and AC systems to which converters are to be connected. TMT&D's intelligent controllers flexible operation is guaranteed to meet your requirements.Typical technologies are as follows:

Constant power controlConstant DC voltage controlConstant current controlExtinction angle controlVoltage dependent current order control

Automatic Frequency ControlWhen you require to improve frequency deviation in normal operation and after large disturbances, application of Automatic Frequency Control(AFC) function is recommended.Basic AFC executes proportional control by taking into account frequency differences between two-systems, which are connected via an HVDC link.The multi-variable AFC, based on modern control theories has many advantages. It produces better control response because it contains the observer. Furthermore, it is sufficiently robust to allow stable control even when there are large changes in the AC power systems.

CONTROL & PROTECTION TECHNOLOGYHVDCTMT&D

Frequency control performance of the multi-variable AFC when there are load variations of normal magnitudes.

Page 11: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

10

The modulation control of the DC power improves power swing stability and effectively dampes power oscillations.

Power Swing Damping Control

When an HVDC system is connected to the isolated generator at the sending end, the system has to be started up in coordination with the governor action of the generator.When bipoler operation is available, overall transmitted power can be built up smoothly from zero to the rated value by having two poles transmit power in opposite directions.

Starting Up the Generator

During transient phenomena, a very large charge or discharge current flows on the stray capacitance of the transmission line, especially in a cable transmission system.TMT&D's high-speed differential protective relay is provided with a special compensation function to avoid maloperation. The relay eliminates the difficulty of distinguishing between internal and external fault that existed in traditional system.

High Speed Protection of DC Line fault

Charge current compensation Algorithm

Charge Voltage of cable terminal

Charge current compensation

Page 12: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

11

High Reliability and EasyMaintenance

Control and protection systemTMT&D's control and protection equipment for HVDC consists of fully digitalized components, based on microcomputer technology using a full graphics code generating tool or high level programming language. Control parameters can be easily modified on the setting panel.

Duplicated or triplicated control and protection systemsYou can choose the optimum system from many technical and economical alternatives, e.g., duplicated, dual, and triplicated.For example, with the dual system, if the power supply of the operating fails, the back-up system instantaneously takes over, without causing disturbance to either AC or DC system. Repair work of the faulty system can be easily done without interrupting the operation.

Test waveform showing automatic change over to the back-up system from the operating system when power failure occurs.

Page 13: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

12

Directly Light-triggeredThyristor Valve

The world largest LTT 8kV-3,500A

Improved reliabilityElectrically-Triggered Thyristor (ETT) valves require many thyristor level electronic parts. LTT valves eliminate 90% of these parts, resulting in higher reliability.

Improved operational flexibilityThe LTT valve can start to operate immediately after it is energized, since it does not have any thyristor level electronics to be charged. The LTT valve also can be fired when the AC system voltage drops.

Improved electromagnetic noise immunityA triggering signal is sent to the LTT in the form of light energy. This gives the LTT valve much better noise immunity than a conventional ETT valve.

Page 14: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

13

Overvoltage protection strategyThere are two causes of overvoltages(1) From outside the valve--- Switching or lightening surges from AC or   DC side(2) From inside the series string of thyristors--- Dynamic voltage unbalance among series   connected thyristors caused by partial turn-  off, etc.The valve protection means are shown in the table below.

VBO free LTTAlthough performance of our protective firing mentioned above is good, TMT&D has already developed a Voltage Break Over (VBO) free thyristor which implements an overvoltage self-protection function. This system has been applied to several commercial systems.

TMT&D Thyristor ValveTechnology

Overvoltage

From outside

From inside

Protection means

Valve arrester directly connected across each valve

Protection firing provided to all thyristors connected in series simultaneously when forward voltage (FV) appears during thyristors should be turned on.

FV : Forward Voltage RV : Reverse VoltageLG : Light Guide PHS : Phase SignalO / E : Optical signal to Electrical signal converter

Timing chart of protective gate pulse

Page 15: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

14

Seismic designTMT&D's thyristor valve is a floor-mounted, stand alone type.Superior features of the stand-alone type are:● Reinforcement of valve hall structure is not necessary.● High quality verified in the factory is transferred to the  site, because disassembly for transportation is minimized.● The installation period is short.● Displacement of valve in case of earthquake is small  and wiring around the valves is simple.TMT&D's thyristor valve is designed using highly accurate computer analysis and vibration test of a full-scaled thyristor valve model.

Valve cooling systemTMT&D has experience in manufacturing oil cooled, air cooled and water cooled valves.TMT&D proposes water cooled valves because water has the most efficient cooling properties, which provides the following advantages.● Compact design● High current conduction of the thyristors● Low auxiliary losses

Seismic vibration test of full scaled quadruple valve

Stress analysis of thyristor valve

Page 16: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

15

TMT&D has established a hierarchical quality assurance system, and carries out a rigorous quality control program at each manufacturing step.

Quality assurance ofTMT&D HVDC

Control and protection equipmentControl and protection equipment is tested individually.

SiteA performance test is carried out,● combining all control and protection● equipment with all AC and DC equipment

Power system simulatorPerformance of control and protection equipment is fully verified using the power system simulator.

Approval of ISO9001/ISO14001

TMT&D is one of the first companies to conform to ISO9001, an international standard for quality assurance.To further improve reliability and protect the environment, TMT&D continues to utilize leading edge technology and facilities to maximize quality and efficiency, and to meet the requirements of environmental standards ISO14001.

Page 17: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

16

SiteThyristor valves are transported as a whole unit with disassembling parts minimized.

PartsTo ensure high performance and high reliability of the thyristor valve, TMT&D is also making every effort to develop highly reliable parts. Each part is subjected to rigorous verification. Each parts of the valve module is also subjected to inspection and testing in accordance with quality assurance program.

Valve moduleAll valve modules are tested according to IEC60700 in module testing line.

ValveAll thyristor valves are assembled at factory. Insulation and operation tests are carried out to confirm production quality.

Page 18: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

17

Hokkaido-Honshu HVDC LinkThe HVDC Link between Hokkaido Island and Honshu Island of Japan was up-graded in 1993 from 300MW to 600MW.This facility has performed the following functions:● Efficient power interchange in Japan● A rational reduction in power supply reserves● Improved frequency deviation of two AC systems during   normal conditions and in the event of a fault in the   AC systems

Kii Channel HVDC LinkKii Channel HVDC Link is the first 500 kVdc HVDC project to interconnect the 500 kVac networks in the western area of Japan. The first stage of 1400 MW (250 kVdc, 2800 A, Bipole) transmission capacity was commissioned in June 2000. All the facilities have been designed considering the future expansion to the transmission capacity of 2800 MW (500 kVdc, 2800 A, Bipole) at the second stage. TMT&D also manufactured the proto-type valve for the 2nd stage. The current rating was 2800 A and 3500 A at overload. 8 kV-3500 A LTT (150 mm diameter) was applied.

Durnrohr SVCThis SVC is provided to absorb overvoltages which occur when the HVDC converter is suddenly shut down.When an overvoltage occurs, it consumes 580Mvar instantaneously, and the overvoltage is suppressed to less than 1.3pu.

HVDC LINK

TYPICAL PROJECTS

SVC FOR HVDC

Page 19: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

18

Shin-Shinano Frequency ConverterThe power system in Japan operates with two frequencies: 50Hz in the eastern area and 60Hz in the western area. These two frequency areas are inter-connected by a Shin-Shinano frequency converter.The converter started operation with a capacity of 300MW in December 1977, and was up-graded to 600MW by the world's first LTT valves in 1992.

Sakuma Frequency ConverterSakuma was commissioned as the world's first frequency converter station in 1965, and its mercury arc valves were replaced with LTT valves in 1993.This frequency converter also inter-connects two frequency areas in Japan same as the Shin-Shinano frequency converter.

Uruguaiana Frequency ConverterThe Uruguaiana frequency converter station interconnects Brazil and Argentina.This system has a very weak AC power system and is equipped with unique control functions, such as Black Start, Automatic Frequency Control, Automatic Speed Control of Synchronous compensator, Automatic Voltage Control and Voltage Dependent Active Power Control.

BACK TO BACK STATION

Page 20: HVDC - NCCMS Courses Platformecourses.dbnet.ntua.gr/fsr/14734/HVDC2.pdf · HVDC systems and Voltage-Sourced Converter HVDC systems. ... CONVERTER TRANSFORMER RATING PRELIMINARY

03-09 A 2030601-1Printed in Japan●TMT&D is a joint venture of Toshiba and Mitsubishi Electric.