Upload
ali-osman
View
221
Download
1
Embed Size (px)
Citation preview
8/10/2019 HVAC Lecture 2
1/36
Air Conditioning Systems
(Comparison /Application /Selection)
8/10/2019 HVAC Lecture 2
2/36
Air Conditioning Systems (Comparison/ Application/ Selection) 2
Contents
1. Introduction
2. System Classifications and Categories
2.1 All-Air System
2.1.1 Constant volume single zone system
2.1.2 Constant volume zoned reheat system
2.1.3 Constant volume bypass system
2.1.4 Variable volume all-air system
2.2 Air-And- Water System
2.3 All-Water System
2.3.1 Gravity convection system
2.3.2 Forced convection system (Fan coil system)
2.3.3 Ventilation systems
2.4 Unitary Refrigerant-Based System
3. Selection of Air Conditioning System
3.1 System Options Constraints
3.2 Selection Report as a Part of the Design Concept Report
3.3 Inquiries required in system selection report
References
1. Introduction
The goal of any air conditioning system is to maintain a desired
environmental condition (temperature, relative humidity, air purity, noise level,
pressurization) within a closed space. Almost in each building or application,
8/10/2019 HVAC Lecture 2
3/36
Air Conditioning Systems (Comparison/ Application/ Selection) 3
there are different air conditioning system options available to the HVAC
designer to satisfy these desired environmental conditions. However,
maintaining the desired inside environmental conditions inside the space has notto be the only goal of the HVAC designer. The designer must be aware of and
account for specific goals that the owner may require other than merely
providing a desired environment. The HVAC designer is the only responsible
for considering various HVAC systems options for a certain application and
recommending the one or two systems that will perform as desired and satisfy
the specific goals of the owner and at the same time maintain the desired
environmental conditions inside the space. Then, the designer and the owner
must be collaborating to select the best design form these options. The owner
can make appropriate value judgments if the designer provides complete
information regarding the advantages and disadvantages of each option. Just as
the owner does not usually know the relative advantages and disadvantages of
different systems, the designer rarely knows all the owners financial and
functional goals. Hence, it is important to involve the owner in selecting the
system. This stage of design is called design concept stage. In this stage, the
following activities have to be carried out by the HVAC designer:
Determination of the inside design conditions suitable for the application.
Study of the architectural and the structural of the building. This stage is
important to know the available spaces and shafts and their sizes that can
be utilized by the HVAC equipment and installations.
Cooling load calculation. Rules of sump can be used in this stage. The
building cooling capacity is required to know the approximate sizing of
the HVAC equipment and installations. At the end of this stage and based
on the available building spaces for the HVAC equipment and
installations, the HVAC designer can reject many HVAC system options.
8/10/2019 HVAC Lecture 2
4/36
8/10/2019 HVAC Lecture 2
5/36
Air Conditioning Systems (Comparison/ Application/ Selection) 5
Then each of these systems is sub classified according to the method of control
cooling in the conditioned area.
Air Conditioning Systems
All Air Air-and-Water All Water Unitary Equipment
Single zone Fan coil Fan coil units Window
Reheat Induction Unit Ventilator Through wall
Bypass Radiant Valance Unit Rooftop
Variable air vol. Two-pipe Unitary
Dual Duct Three-pipe Air Heat pumps
Multi zone Four-pipe Water Heat Pumps
2.1 AllAir System
In all-air system, complete sensible and latent cooling capacity of the
zone is removed by cold air supplied to the space. This air is centrally cooled
outside the conditioned space and supplied to the space via a duct system. No
additional cooling is required at the zone. Heating may be accomplished by the
same air stream either in the central system or at a particular zone. The heating
is accomplished in the central system if the required purpose of heating is either
winter heating of the conditioned zones or control of the RH inside the space.
The heating is accomplished at a particular zone in case of a required separate
control to the temperature and relative humidity of the space.
All-Air system can be classified as single-path systems and dual-path
systems. Single-path systemscontains the main cooling and heating coils in a
series air flow path, and use a common duct distribution system at a commonair temperature to feed all terminal air distribution devices. In a dual-path
8/10/2019 HVAC Lecture 2
6/36
Air Conditioning Systems (Comparison/ Application/ Selection) 6
system, the main cooling and heating coils are in parallel flow and uses a
separate cold and warm air duct distribution systems. The use of the dual-path
system is limited due to its disadvantages of high cost of the duct system, moresizes and spaces are needed for the dual duct system and the bade energy
utilization.
Single duct system may be further classified according to the method of
control as follows:
Single Duct All-Air System
Constant Volume Variable Air Volume
Single Zone Reheat
Multiple Zoned Reheat Induction
Bypass Fan Powered
Variable Diffusers
2.1.1 Constant Volume Single zone system
This is the simplest all-air system where a supply unit is used to serve a
single temperature control zone. The zone may consist of a single room or
multiple rooms as shown in Fig. 1.
8/10/2019 HVAC Lecture 2
7/36
Air Conditioning Systems (Comparison/ Application/ Selection) 7
Fig. 1 Single zone constant air volume system
Methods of Sizing
Two methods can be used to size a constant air volume system:
Zone air flow rate is calculated based on the sum of spaces airflow rates
calculated at the individual's peak load of each space (Sum of peaks).
3
AHU
R3R2R1
Space 1 Space2 Space 3
0 21
8/10/2019 HVAC Lecture 2
8/36
Air Conditioning Systems (Comparison/ Application/ Selection) 8
Zone air flow rate is calculated based on the zone peak load (peak of
sums).
The second method gives smaller equipment and duct sizing for the system but
may be lead to insufficient air change per hours inside each space and high
temperature levels at the peck load time of each space.
Method of Control:
Change the supply air temperature in response to the zone load. The thermostat
is commonly located in the common return of the different spaces of the zone.
The supply air temperature is changed either by regulating the flow rate of the
cooling medium (chilled water) to the cooling unit.
Disadvantages
No separate control of the different rooms of the zone.
Additional duct clearance requirements can reduce usable floor space and
building height as a result of duct risers, fan rooms and duct work.
Longer fan operating hours are required to take care of unoccupied
periods.
Air balancing is difficult and may have to be done several times when a
common air system serves areas that are not rented simultaneously.
Accessibility to terminal devices demands close cooperation between
architectural, mechanical and structural designers.
Advantages
8/10/2019 HVAC Lecture 2
9/36
Air Conditioning Systems (Comparison/ Application/ Selection) 9
Low cost of the system.
Centrally located equipment concentrate the operation and maintenance in
unoccupied areas and this permits maximum choice of filtration system,
odor and noise control level and high-quality, durable equipment.
Complete absence of conditioned area drain piping, electrical equipment
power wring and filters.
Ease of construction and operation of the system
Precise control of the temperature and humidity of the zone if the zoneconsists of single room.
The possibility of completely turning off the HVAC system of a certain
zone when required.
Adaptable to automatic seasonal changeover and to winter humidification.
Zoning of the building rooms
Two factors must take in account during grouping of multiple rooms in a single
zone:
The rooms must have similar cooling load profile along the day. This
narrows the temperature variation of each room in the zone.
The orientation and locations of the group of rooms in each zone must
lead to simple, short, ease with construction air duct routing. This reduces
the duct cost and the fan power.
Cross contaminations must be taken in account.
2.1.2 Constant Volume zoned reheat system
8/10/2019 HVAC Lecture 2
10/36
8/10/2019 HVAC Lecture 2
11/36
8/10/2019 HVAC Lecture 2
12/36
8/10/2019 HVAC Lecture 2
13/36
8/10/2019 HVAC Lecture 2
14/36
Air Conditioning Systems (Comparison/ Application/ Selection) 14
High diversity of load between spaces.
The fresh air requirements are not a critical issue.
Precise control of the RH is not required.
Applications of high sensible heat ratio.
Advantages
Separate temperature control of the different rooms/zones of the building.
Smaller equipment can be used, especially when the diversity of the load
is high.
Operating cost of the variable volume systems are generally the lowest
cost as compared to the other systems. Since the volume of air is reduced
with a reduction in load, the refrigeration and fan power closely follow
the actual air-conditioning load of the building.
Efficient system for energy conservation.
No balancing is required; the system is virtually self balancing.
The system has low initial cost as compared to other systems that have
individual spaces control, because it requires only single runs of ducts and
simple control at the terminal.
Disadvantages
Dramatically Reduction of the fresh air supplied to a certain zone at part
load conditions.
Humidity control is very difficult when VAV system is used. In the
applications where the humidity level is critical, systems may have to
8/10/2019 HVAC Lecture 2
15/36
Air Conditioning Systems (Comparison/ Application/ Selection) 15
limited to constant air volume. In the applications of low sensible heat
ratio, such as in conference rooms, the VAV box minimum set point is
usually limited to 50%, and reheat is added as necessary to keep humiditylevel low during part load.
Low air change per hours at part load
More complicated control system
Higher capital cost as compared to the constant air volume.
To overcome on the disadvantages of the reduction of the air change per hours atpart load, variable air volume terminal devices of different configurations are
used, including reheat, induction unit, and fan-powered systems as shown in Fig.
4.
Fig. 4 Various VAV systems
Also primary/Secondary air systems can be used to overcome on the reduction
of the percentage of the fresh air at part load. In this case the primary system
supply the conditioned outside air requirements directly to the space and the
secondary system provide additional cooling with VAV box for space load
control, see Fig. 5. Normally the second cooling coil is designed to be dry (i.e.,
sensible cooling only) to reduce the possibility of bacterial growth which can
create air quality problem.
8/10/2019 HVAC Lecture 2
16/36
Air Conditioning Systems (Comparison/ Application/ Selection) 16
Fig. 5 Primary/Secondary VAV system
2.2 Air-And- Water System
In an air-and-water system, both air and water are distributed to each
space to cool the space, see Fig. 6. Both cooling and heating are carried out by
changing the air or water temperatures, or both, to control the space temperature
throughout the year. The air and water are cooled or heated in central
mechanical equipment room. The air supplied is called primary air; the water
supplied is called secondary water. Both air and waters shares the cooling load
of the building.
Fig. 6 Air-and-water system
The air side of air-and-water systems is comprised of central air-
conditioning equipment, a duct distribution system, and a room terminal unit.
The air supplied is constant volume and is called primary air, to distinguish it
8/10/2019 HVAC Lecture 2
17/36
Air Conditioning Systems (Comparison/ Application/ Selection) 17
from room air, which is circulated over the room coil. It provides filtered
outdoor air for ventilation. In the cooling season, air is dehumidified in the
central conditioning unit to achieve comfort humidity conditions throughout thespace served and to avoid condensation due to normal room latent load on the
room cooling coil. The primary air normally controls space humidity. Therefore,
the moisture content of the supply air must be low enough to offset the room
latent heat gain and to maintain a room dew point sufficiently low to preclude
condensation on the secondary cooling surface. While some systems operate
successfully without a secondary coil drain system, a condensate drain is
recommended for all air-and-water system. In winter, moisture is frequently
added centrally to limit dryness. As the air is dehumidified, it is also sensible
cooled to offset a portion of the room sensible loads.
The water side consists of a pump and piping to convey water to a heat
transfer surface within each conditioned space. The heat transfer surface in the
form of a coil may be an integral part of the air terminal (as in induction units), acompletely separate component within the conditioned space (radiant panel), or
either (as can be the case in fan-coil units). The water is cooled by direct
refrigeration or by introducing chilled water from the primary chilled water
circuit; the water side is called the secondary water loop.
Method of Control
Each room temperature is controlled by varying the capacity of the coils
within the room by regulating either the water flow through it or the air flow
over it by the following techniques:
The room thermostat signal controls the chilled water control valve.
Also fan speed is used to control the room temperature. Fan speed controlmay be automatic or manual.
8/10/2019 HVAC Lecture 2
18/36
8/10/2019 HVAC Lecture 2
19/36
Air Conditioning Systems (Comparison/ Application/ Selection) 19
Sizing Method
The quantity of primary air to each space is determined by the fresh air
requirement for this space.
The fan of the primary air AHU unit and the main duct system are sized
based on the sum of the primary air flow rates to all the spaces served by
this air handling unit.
The cooling capacity of the primary air AHU is calculated based on theair enthalpy difference across the coil. In practice to eliminate the water
condensation on the room chilled water coil, the air is strongly cooled to
make dry as possible to maintain the room dew point below the room coil
surface temperature. In this case, the primary air offset all the room latent
heat and part of the room sensible load. In this case the capacity of the
cooling coil of the terminal unit equal the room cooling load minus the
room load that was offset by the primary air system. The disadvantage of
this deep cooling of the primary air is the loss of large amount of energy
(the energy that paid in cooling the primary air) during the off position of
the room terminal unit when the room becomes empty or unused.
The chillers capacity is calculated based on the peak of sum of the entire
space load taken by the secondary units plus the load of the AHU of theprimary system.
Applications
High rise building where no space is available for large duct works.
Applications that has no enough spacing for large sizes of air handling
units if all air system is used.
8/10/2019 HVAC Lecture 2
20/36
8/10/2019 HVAC Lecture 2
21/36
Air Conditioning Systems (Comparison/ Application/ Selection) 21
Building load rather than sum of rooms peaks determine capacity
requirements which leads to small capacity.
Low operating cost.
When all primary air is taken from outdoor, recirculation occurs only
within the room, which reduces the possibility of cross contamination.
System components are long lasting. The room's terminal units operating
dry have anticipated life of 15-25 years. The piping and ducting system
longevity should equal that of the building.
Disadvantages
The primary air supply usually is constant with no provision of shutoff.
This is disadvantages in residential applications, where tenants or hotel
room guests may prefer to turn off the air conditioning, or where
management may desire to do so to reduce operating cost.
Secondary air flow can cause the terminal units coils to become dirty
enough to affect performance. Line screen or low efficiency filters used to
protect these terminals required frequent in room maintenance and reduce
unit thermal performance.
A low chilled water temperature is needed to control space humidity
adequately and to prevent condensate on the terminal units.
Controls tends to be numerous and complex than those for many all air
systems.
The system should not be used in spaces with high exhaust requirements.
The system is inefficient if the outdoor air requirements are high.
The initial cost of the system is higher than that of the all air system.
8/10/2019 HVAC Lecture 2
22/36
Air Conditioning Systems (Comparison/ Application/ Selection) 22
Humidity control is difficult.
Classifications
Air-and-water system can be classified to three types according to the terminal
unit type of the secondary water system. These types, as shown in Fig. 7, are
Air-and-water induction unit
Air-and-water fan coil unit
Air-and-water panel system
(a) Air-Water induction unit (b) Fan coil unit
Ceiling panel system
Fig. 7 Types of terminal units of air-and-water system
8/10/2019 HVAC Lecture 2
23/36
Air Conditioning Systems (Comparison/ Application/ Selection) 23
2.3 All-Water System
In all water system, the room is heated or cooled by direct heat transfer
between the room circulated air and the chilled or hot water through the heat
transfer surface of the terminal unit. In this system all the room load is carried
out by the circulated water at the terminal unit. The system can be classified
according to the method of the heat transfer between the room and the circulated
water as follows,
2.3.1 Gravity Convection System
In this system hot/cold water system delivers heat/cool to a space by
water that is hotter/cooler than the air in contact with the heat transfer surface. In
this system air moves past the heat transfer surface because of the density
difference of air caused by heated or cooled surfaces. This system also transfer
large amount of heat by radiation to cold surfaces. Although this system
provides good comfort conditions, the system is suitable for heating but caution
should be exercised in their application of cooling. Examples of such systems
include the following:
Baseboard radiation
Free Standing Radiators
Wall or Floor Radiant
Bare Pipe (racked on wall)
2.3.2 Forced Convection System (Fan Coil System)
8/10/2019 HVAC Lecture 2
24/36
Air Conditioning Systems (Comparison/ Application/ Selection) 24
In this system (including cooling as well as heating), the air room is
moves by fan through the room, the circulated air room is filtered and the
outside ventilation air is introduced.
Terminal units (Fan coil units) with chilled water coil, heating coil,
blowers, replaceable air filters, drain pan for condensate are designed for
this purpose.
The room fan coil units are available in many configurations to fit under
windowsills, floor mounted, ceiling mounted, and floor-to-ceiling chase
enclosed unit.
2.3.3 Ventilation Systems
Uncontrolled Local Ventilation System
In this system the outdoor air was provided to the room through the
infiltration, wall opening or window opening. In this case the amount of the
fresh air is affected by the infiltration and the stack effect. This system has many
disadvantages and does not meet the ventilation requirement of ASHRAE
Standard 62.
Central Ventilation System
In this case a central outside air pretreatment system, which maintain
fresh air at about 18-21 C, is used.
Ventilation air may then be introduced to the room either through the fan
coil unit or through a separate air outlets.
The ventilation load is carried out by this central ventilation system.
8/10/2019 HVAC Lecture 2
25/36
8/10/2019 HVAC Lecture 2
26/36
Air Conditioning Systems (Comparison/ Application/ Selection) 26
By regulating the water flow through it by modulating the chilled water
control valve. The fan of the speed is selected high, medium or low. This
method of control leads to high RH in the space.
Two position control (on/off) of the chilled water valve with using
variable speed fan. This system gives bitter RH but it cost much.
Applications
High rise building where no space is available for large duct works
Applications that has no enough spacing for large sizes of air handling
units if all air system is used.
The system is working well in offices buildings, hotels, apartment houses
and other applications that need separate control of each space and
separate on/off control of the system for every space.
Fan coil system are used in numbers of hospitals but are less desirable
because of the low efficiency of the filtration system and difficulty of
maintaining adequate cleanliness in the space.
Applications that have great variation in the sensible heat loads.
Applications that have high diversity of loads between spaces.
Advantages
Separate temperature control of the different rooms/zones of the building
with the possibility of adjusting each thermostat for a different
temperature at relatively low cost.
8/10/2019 HVAC Lecture 2
27/36
Air Conditioning Systems (Comparison/ Application/ Selection) 27
Separate heating and cooling sources in the primary air and secondary
water gives the occupant in each space the possibility of choice of heating
or cooling.
Less space is required for the distribution system.
The sizes of the central air handling units are smaller compared with those
of other systems.
The ability to shut off local terminals in unused areas.
No cross contamination from circulated air between rooms.
The system can be use for existing building retrofitting.
Ventilation air supply is positive and may accommodate recommended
outside air quantity.
Spaces can be heated without operating the ventilation air system via the
secondary water system.
Building peak load rather than sum of rooms peaks determine capacity
requirements which leads to small capacity.
Low operating cost.
Disadvantages
All-Water-System requires much more maintenance then central all air
system and this work must be done in occupied area.
Condensate pan and drain system is required and this must be cleaned and
flushed periodically, condensate disposal can be difficult and costly.
Filters are small, low in efficiency, and required frequent changing to
maintain air volume.
8/10/2019 HVAC Lecture 2
28/36
Air Conditioning Systems (Comparison/ Application/ Selection) 28
Summer room humidity level tends to be relatively high
Low filtration efficiency leads to unclean coil and low performance of it.
It is also difficult to clean the coil if necessary.
The system is inefficient if the outdoor air requirements are high.
The initial cost of the system is higher than that of the all air system.
2.4 Unitary Refrigerant-Based System
Unitary air conditioning equipment is an assembly of factory matched
refrigerant cycle components for inclusion in filed designed air-conditioning
systems. Some of the many types of unitary air conditioners available include
the following characteristics:
Arrangement: single or split
Heat rejection: air cooled, evaporative condenser, water cooled.
Unit exterior: decorative for in space applications, functional for
equipment room and ducts, weather proofed for outdoors.
Placement: Floor standing, wall mounted, ceiling suspended, roof
mounted.
Indoor air: vertical up flow, counterflow, horizontal, 90 and 180 turns
or for use with forced air furnaces.
Locations:
Indoor- exposed with plenums or furred in ductwork concealed in closest,
attic, crawl spaces, basements garages, utility rooms, or equipment room,
wall built in, window.
Outdoor- roof top, wall mounted, or on ground.
8/10/2019 HVAC Lecture 2
29/36
Air Conditioning Systems (Comparison/ Application/ Selection) 29
Unitary air conditioner, in contrast to room air-conditioner, includes fans
capable for operating with ductwork, although some unit may be applied with
plenum.
Central unitary air conditioner tends to serve zoned systems, with each
zone served by its own unit. For large single spaces where central systems are at
their best advantages, multiple units are often advantageous because as load
sources move within the large space, the many smaller interlocked and
independent systems have more flexibility than one central system.
Applications
Building that need air conditioning of only small numbers of rooms that
are far away from each other.
Applications that need metering and accounting of energy to each tenant.
Applications of small cooling capacities
Applications of intermitted use of the rooms.
Air conditioning of existing building.
Apartment and dormitories
Control
The control of the unitary units is on-off control to the refrigeration machine via
a thermostat in the zone or in the return air duct.
8/10/2019 HVAC Lecture 2
30/36
Air Conditioning Systems (Comparison/ Application/ Selection) 30
Advantages of multiple units systems.
Simple and inexpensive individual room control.
Individual air distribution for each room, usually with convenient and
simple adjustment by the occupant.
Heating and cooling capability at all times, independent of the mode of
operation of other spaces in the building.
Individual ventilation air, normally operating whenever the conditioner
operates.
Consistent performance assured by manufacture-matched components.
Usually some space saving.
Usually lower initial cost
Only one terminal zone is affected in the even of equipment malfunction.
Usually quick availability and installation are possible.
Equipment serving spaces that become vacant can be turned off locally or
from a central point, without affecting occupied spaces.
High quality and reliability because manufacture assembles components.
System operation is simple.
Energy can be metered directly to each tenant.
Equipment locations allows for shorter duct runs, reduced duct space
requirements, and ease of service access.
Disadvantages
Operating sound level can be high
8/10/2019 HVAC Lecture 2
31/36
8/10/2019 HVAC Lecture 2
32/36
Air Conditioning Systems (Comparison/ Application/ Selection) 32
How much area and volume from the building can be taken for the HVAC
equipment.
How the HVAC service is sale or rented to the tenant of the spaces of the
project.
What are the parameters that required to be controlled and what are
precision and accuracy of the control system.
What are the special equipments of the HVAC system, ACH, clean spaces
or not, sound level, fresh air requirements, etc.
Since these factors are interrelated, the owner and the designer must consider
how each affects the other. The relative importance of these factors differs with
different owners and often changes from one project to another.
3.1 System Option Constraints
The first step in selecting a system or rejecting other systems is to
determine and documents constraints dictated by performance, capacity,
available space and other factors. These constraints narrow the choice to systems
that can fit the applications. Examples of these constraints are:
Cooling load
Known the cooling load often narrows the choice of the system that can fit
within the available space and are compatible with the building architectural.
Zoning Requirements
The required zoning of the building, the degree of control required in each zone
and the equipment space required for individual zones also narrows the system
choice. The factors that must be taken in account in zoning a building are:
8/10/2019 HVAC Lecture 2
33/36
8/10/2019 HVAC Lecture 2
34/36
Air Conditioning Systems (Comparison/ Application/ Selection) 34
The required special support forms the stricture for the major components.
The heavy of the major components and the stricture can hold it or not.
Space available to house the equipments and its location relative to the
occupied space.
The acceptability of the components obtruding into the occupied space,
both physically and visually.
The space available in the false ceiling to pass the duct and piping system
or inserting the terminal devices.
First and operating cost
The first and the operating cost of the HVAC system can narrow the selection of
the system. These cots must be within the budget limit of the project. The major
factors that affect the cost of each of the HVAC system are:
The operating energy source of the system; electricity or natural gas and
the price of each source, and the possibility and cost of extending these
sources to the building.
The control system, accuracy and the number of variables required to be
controlled.
Centralize the system or using individual components. The cost of a
central unit is smaller than the cost if individual units are used.
Maintenance cost of the HVAC system.
Cost of the spare parts of the system.
3.2 Selection Report as a Part of the Design Concept Report
The last step of the system selection is preparing a report, by HVAC
designer, containing a summary of the design and selection criteria. This report
8/10/2019 HVAC Lecture 2
35/36
8/10/2019 HVAC Lecture 2
36/36
2. How much will the system cost to own compared to others considered?
What are the recovery time of the initial investment, and the future cost of
replacement equipment?
3. Will the system deliver the desired uniform temperature under varying
whether and solar conditions?
4. What are the operating costs-energy costs, maintenance, operating labor
and supplies of this system compared to the others?
5. What reliability can the owner expect compared to other systems.
6. If the system flexible enough to meet changes in the owner's needs? What
is required to add a new zone? Can it meet the increased capacity
requirements of space when new equipment (load) is added?
Finally the system selection report should conclude with a recommended
system choice along with reasons for the choice.
References
1. ASHRAE HANDBOOK, Fundamentals
2. ASHRAE HANDBOOK, HVAC Systems and Equipment
3. Harry J. Sauer and Ronald H. Howell, Principles of heating ventilation and
air conditioning, a text book supplemented to the 1989 ASHRAE Handbook-
Fundamental.