HVAC Lecture 2

Embed Size (px)

Citation preview

  • 8/10/2019 HVAC Lecture 2

    1/36

    Air Conditioning Systems

    (Comparison /Application /Selection)

  • 8/10/2019 HVAC Lecture 2

    2/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 2

    Contents

    1. Introduction

    2. System Classifications and Categories

    2.1 All-Air System

    2.1.1 Constant volume single zone system

    2.1.2 Constant volume zoned reheat system

    2.1.3 Constant volume bypass system

    2.1.4 Variable volume all-air system

    2.2 Air-And- Water System

    2.3 All-Water System

    2.3.1 Gravity convection system

    2.3.2 Forced convection system (Fan coil system)

    2.3.3 Ventilation systems

    2.4 Unitary Refrigerant-Based System

    3. Selection of Air Conditioning System

    3.1 System Options Constraints

    3.2 Selection Report as a Part of the Design Concept Report

    3.3 Inquiries required in system selection report

    References

    1. Introduction

    The goal of any air conditioning system is to maintain a desired

    environmental condition (temperature, relative humidity, air purity, noise level,

    pressurization) within a closed space. Almost in each building or application,

  • 8/10/2019 HVAC Lecture 2

    3/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 3

    there are different air conditioning system options available to the HVAC

    designer to satisfy these desired environmental conditions. However,

    maintaining the desired inside environmental conditions inside the space has notto be the only goal of the HVAC designer. The designer must be aware of and

    account for specific goals that the owner may require other than merely

    providing a desired environment. The HVAC designer is the only responsible

    for considering various HVAC systems options for a certain application and

    recommending the one or two systems that will perform as desired and satisfy

    the specific goals of the owner and at the same time maintain the desired

    environmental conditions inside the space. Then, the designer and the owner

    must be collaborating to select the best design form these options. The owner

    can make appropriate value judgments if the designer provides complete

    information regarding the advantages and disadvantages of each option. Just as

    the owner does not usually know the relative advantages and disadvantages of

    different systems, the designer rarely knows all the owners financial and

    functional goals. Hence, it is important to involve the owner in selecting the

    system. This stage of design is called design concept stage. In this stage, the

    following activities have to be carried out by the HVAC designer:

    Determination of the inside design conditions suitable for the application.

    Study of the architectural and the structural of the building. This stage is

    important to know the available spaces and shafts and their sizes that can

    be utilized by the HVAC equipment and installations.

    Cooling load calculation. Rules of sump can be used in this stage. The

    building cooling capacity is required to know the approximate sizing of

    the HVAC equipment and installations. At the end of this stage and based

    on the available building spaces for the HVAC equipment and

    installations, the HVAC designer can reject many HVAC system options.

  • 8/10/2019 HVAC Lecture 2

    4/36

  • 8/10/2019 HVAC Lecture 2

    5/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 5

    Then each of these systems is sub classified according to the method of control

    cooling in the conditioned area.

    Air Conditioning Systems

    All Air Air-and-Water All Water Unitary Equipment

    Single zone Fan coil Fan coil units Window

    Reheat Induction Unit Ventilator Through wall

    Bypass Radiant Valance Unit Rooftop

    Variable air vol. Two-pipe Unitary

    Dual Duct Three-pipe Air Heat pumps

    Multi zone Four-pipe Water Heat Pumps

    2.1 AllAir System

    In all-air system, complete sensible and latent cooling capacity of the

    zone is removed by cold air supplied to the space. This air is centrally cooled

    outside the conditioned space and supplied to the space via a duct system. No

    additional cooling is required at the zone. Heating may be accomplished by the

    same air stream either in the central system or at a particular zone. The heating

    is accomplished in the central system if the required purpose of heating is either

    winter heating of the conditioned zones or control of the RH inside the space.

    The heating is accomplished at a particular zone in case of a required separate

    control to the temperature and relative humidity of the space.

    All-Air system can be classified as single-path systems and dual-path

    systems. Single-path systemscontains the main cooling and heating coils in a

    series air flow path, and use a common duct distribution system at a commonair temperature to feed all terminal air distribution devices. In a dual-path

  • 8/10/2019 HVAC Lecture 2

    6/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 6

    system, the main cooling and heating coils are in parallel flow and uses a

    separate cold and warm air duct distribution systems. The use of the dual-path

    system is limited due to its disadvantages of high cost of the duct system, moresizes and spaces are needed for the dual duct system and the bade energy

    utilization.

    Single duct system may be further classified according to the method of

    control as follows:

    Single Duct All-Air System

    Constant Volume Variable Air Volume

    Single Zone Reheat

    Multiple Zoned Reheat Induction

    Bypass Fan Powered

    Variable Diffusers

    2.1.1 Constant Volume Single zone system

    This is the simplest all-air system where a supply unit is used to serve a

    single temperature control zone. The zone may consist of a single room or

    multiple rooms as shown in Fig. 1.

  • 8/10/2019 HVAC Lecture 2

    7/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 7

    Fig. 1 Single zone constant air volume system

    Methods of Sizing

    Two methods can be used to size a constant air volume system:

    Zone air flow rate is calculated based on the sum of spaces airflow rates

    calculated at the individual's peak load of each space (Sum of peaks).

    3

    AHU

    R3R2R1

    Space 1 Space2 Space 3

    0 21

  • 8/10/2019 HVAC Lecture 2

    8/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 8

    Zone air flow rate is calculated based on the zone peak load (peak of

    sums).

    The second method gives smaller equipment and duct sizing for the system but

    may be lead to insufficient air change per hours inside each space and high

    temperature levels at the peck load time of each space.

    Method of Control:

    Change the supply air temperature in response to the zone load. The thermostat

    is commonly located in the common return of the different spaces of the zone.

    The supply air temperature is changed either by regulating the flow rate of the

    cooling medium (chilled water) to the cooling unit.

    Disadvantages

    No separate control of the different rooms of the zone.

    Additional duct clearance requirements can reduce usable floor space and

    building height as a result of duct risers, fan rooms and duct work.

    Longer fan operating hours are required to take care of unoccupied

    periods.

    Air balancing is difficult and may have to be done several times when a

    common air system serves areas that are not rented simultaneously.

    Accessibility to terminal devices demands close cooperation between

    architectural, mechanical and structural designers.

    Advantages

  • 8/10/2019 HVAC Lecture 2

    9/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 9

    Low cost of the system.

    Centrally located equipment concentrate the operation and maintenance in

    unoccupied areas and this permits maximum choice of filtration system,

    odor and noise control level and high-quality, durable equipment.

    Complete absence of conditioned area drain piping, electrical equipment

    power wring and filters.

    Ease of construction and operation of the system

    Precise control of the temperature and humidity of the zone if the zoneconsists of single room.

    The possibility of completely turning off the HVAC system of a certain

    zone when required.

    Adaptable to automatic seasonal changeover and to winter humidification.

    Zoning of the building rooms

    Two factors must take in account during grouping of multiple rooms in a single

    zone:

    The rooms must have similar cooling load profile along the day. This

    narrows the temperature variation of each room in the zone.

    The orientation and locations of the group of rooms in each zone must

    lead to simple, short, ease with construction air duct routing. This reduces

    the duct cost and the fan power.

    Cross contaminations must be taken in account.

    2.1.2 Constant Volume zoned reheat system

  • 8/10/2019 HVAC Lecture 2

    10/36

  • 8/10/2019 HVAC Lecture 2

    11/36

  • 8/10/2019 HVAC Lecture 2

    12/36

  • 8/10/2019 HVAC Lecture 2

    13/36

  • 8/10/2019 HVAC Lecture 2

    14/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 14

    High diversity of load between spaces.

    The fresh air requirements are not a critical issue.

    Precise control of the RH is not required.

    Applications of high sensible heat ratio.

    Advantages

    Separate temperature control of the different rooms/zones of the building.

    Smaller equipment can be used, especially when the diversity of the load

    is high.

    Operating cost of the variable volume systems are generally the lowest

    cost as compared to the other systems. Since the volume of air is reduced

    with a reduction in load, the refrigeration and fan power closely follow

    the actual air-conditioning load of the building.

    Efficient system for energy conservation.

    No balancing is required; the system is virtually self balancing.

    The system has low initial cost as compared to other systems that have

    individual spaces control, because it requires only single runs of ducts and

    simple control at the terminal.

    Disadvantages

    Dramatically Reduction of the fresh air supplied to a certain zone at part

    load conditions.

    Humidity control is very difficult when VAV system is used. In the

    applications where the humidity level is critical, systems may have to

  • 8/10/2019 HVAC Lecture 2

    15/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 15

    limited to constant air volume. In the applications of low sensible heat

    ratio, such as in conference rooms, the VAV box minimum set point is

    usually limited to 50%, and reheat is added as necessary to keep humiditylevel low during part load.

    Low air change per hours at part load

    More complicated control system

    Higher capital cost as compared to the constant air volume.

    To overcome on the disadvantages of the reduction of the air change per hours atpart load, variable air volume terminal devices of different configurations are

    used, including reheat, induction unit, and fan-powered systems as shown in Fig.

    4.

    Fig. 4 Various VAV systems

    Also primary/Secondary air systems can be used to overcome on the reduction

    of the percentage of the fresh air at part load. In this case the primary system

    supply the conditioned outside air requirements directly to the space and the

    secondary system provide additional cooling with VAV box for space load

    control, see Fig. 5. Normally the second cooling coil is designed to be dry (i.e.,

    sensible cooling only) to reduce the possibility of bacterial growth which can

    create air quality problem.

  • 8/10/2019 HVAC Lecture 2

    16/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 16

    Fig. 5 Primary/Secondary VAV system

    2.2 Air-And- Water System

    In an air-and-water system, both air and water are distributed to each

    space to cool the space, see Fig. 6. Both cooling and heating are carried out by

    changing the air or water temperatures, or both, to control the space temperature

    throughout the year. The air and water are cooled or heated in central

    mechanical equipment room. The air supplied is called primary air; the water

    supplied is called secondary water. Both air and waters shares the cooling load

    of the building.

    Fig. 6 Air-and-water system

    The air side of air-and-water systems is comprised of central air-

    conditioning equipment, a duct distribution system, and a room terminal unit.

    The air supplied is constant volume and is called primary air, to distinguish it

  • 8/10/2019 HVAC Lecture 2

    17/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 17

    from room air, which is circulated over the room coil. It provides filtered

    outdoor air for ventilation. In the cooling season, air is dehumidified in the

    central conditioning unit to achieve comfort humidity conditions throughout thespace served and to avoid condensation due to normal room latent load on the

    room cooling coil. The primary air normally controls space humidity. Therefore,

    the moisture content of the supply air must be low enough to offset the room

    latent heat gain and to maintain a room dew point sufficiently low to preclude

    condensation on the secondary cooling surface. While some systems operate

    successfully without a secondary coil drain system, a condensate drain is

    recommended for all air-and-water system. In winter, moisture is frequently

    added centrally to limit dryness. As the air is dehumidified, it is also sensible

    cooled to offset a portion of the room sensible loads.

    The water side consists of a pump and piping to convey water to a heat

    transfer surface within each conditioned space. The heat transfer surface in the

    form of a coil may be an integral part of the air terminal (as in induction units), acompletely separate component within the conditioned space (radiant panel), or

    either (as can be the case in fan-coil units). The water is cooled by direct

    refrigeration or by introducing chilled water from the primary chilled water

    circuit; the water side is called the secondary water loop.

    Method of Control

    Each room temperature is controlled by varying the capacity of the coils

    within the room by regulating either the water flow through it or the air flow

    over it by the following techniques:

    The room thermostat signal controls the chilled water control valve.

    Also fan speed is used to control the room temperature. Fan speed controlmay be automatic or manual.

  • 8/10/2019 HVAC Lecture 2

    18/36

  • 8/10/2019 HVAC Lecture 2

    19/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 19

    Sizing Method

    The quantity of primary air to each space is determined by the fresh air

    requirement for this space.

    The fan of the primary air AHU unit and the main duct system are sized

    based on the sum of the primary air flow rates to all the spaces served by

    this air handling unit.

    The cooling capacity of the primary air AHU is calculated based on theair enthalpy difference across the coil. In practice to eliminate the water

    condensation on the room chilled water coil, the air is strongly cooled to

    make dry as possible to maintain the room dew point below the room coil

    surface temperature. In this case, the primary air offset all the room latent

    heat and part of the room sensible load. In this case the capacity of the

    cooling coil of the terminal unit equal the room cooling load minus the

    room load that was offset by the primary air system. The disadvantage of

    this deep cooling of the primary air is the loss of large amount of energy

    (the energy that paid in cooling the primary air) during the off position of

    the room terminal unit when the room becomes empty or unused.

    The chillers capacity is calculated based on the peak of sum of the entire

    space load taken by the secondary units plus the load of the AHU of theprimary system.

    Applications

    High rise building where no space is available for large duct works.

    Applications that has no enough spacing for large sizes of air handling

    units if all air system is used.

  • 8/10/2019 HVAC Lecture 2

    20/36

  • 8/10/2019 HVAC Lecture 2

    21/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 21

    Building load rather than sum of rooms peaks determine capacity

    requirements which leads to small capacity.

    Low operating cost.

    When all primary air is taken from outdoor, recirculation occurs only

    within the room, which reduces the possibility of cross contamination.

    System components are long lasting. The room's terminal units operating

    dry have anticipated life of 15-25 years. The piping and ducting system

    longevity should equal that of the building.

    Disadvantages

    The primary air supply usually is constant with no provision of shutoff.

    This is disadvantages in residential applications, where tenants or hotel

    room guests may prefer to turn off the air conditioning, or where

    management may desire to do so to reduce operating cost.

    Secondary air flow can cause the terminal units coils to become dirty

    enough to affect performance. Line screen or low efficiency filters used to

    protect these terminals required frequent in room maintenance and reduce

    unit thermal performance.

    A low chilled water temperature is needed to control space humidity

    adequately and to prevent condensate on the terminal units.

    Controls tends to be numerous and complex than those for many all air

    systems.

    The system should not be used in spaces with high exhaust requirements.

    The system is inefficient if the outdoor air requirements are high.

    The initial cost of the system is higher than that of the all air system.

  • 8/10/2019 HVAC Lecture 2

    22/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 22

    Humidity control is difficult.

    Classifications

    Air-and-water system can be classified to three types according to the terminal

    unit type of the secondary water system. These types, as shown in Fig. 7, are

    Air-and-water induction unit

    Air-and-water fan coil unit

    Air-and-water panel system

    (a) Air-Water induction unit (b) Fan coil unit

    Ceiling panel system

    Fig. 7 Types of terminal units of air-and-water system

  • 8/10/2019 HVAC Lecture 2

    23/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 23

    2.3 All-Water System

    In all water system, the room is heated or cooled by direct heat transfer

    between the room circulated air and the chilled or hot water through the heat

    transfer surface of the terminal unit. In this system all the room load is carried

    out by the circulated water at the terminal unit. The system can be classified

    according to the method of the heat transfer between the room and the circulated

    water as follows,

    2.3.1 Gravity Convection System

    In this system hot/cold water system delivers heat/cool to a space by

    water that is hotter/cooler than the air in contact with the heat transfer surface. In

    this system air moves past the heat transfer surface because of the density

    difference of air caused by heated or cooled surfaces. This system also transfer

    large amount of heat by radiation to cold surfaces. Although this system

    provides good comfort conditions, the system is suitable for heating but caution

    should be exercised in their application of cooling. Examples of such systems

    include the following:

    Baseboard radiation

    Free Standing Radiators

    Wall or Floor Radiant

    Bare Pipe (racked on wall)

    2.3.2 Forced Convection System (Fan Coil System)

  • 8/10/2019 HVAC Lecture 2

    24/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 24

    In this system (including cooling as well as heating), the air room is

    moves by fan through the room, the circulated air room is filtered and the

    outside ventilation air is introduced.

    Terminal units (Fan coil units) with chilled water coil, heating coil,

    blowers, replaceable air filters, drain pan for condensate are designed for

    this purpose.

    The room fan coil units are available in many configurations to fit under

    windowsills, floor mounted, ceiling mounted, and floor-to-ceiling chase

    enclosed unit.

    2.3.3 Ventilation Systems

    Uncontrolled Local Ventilation System

    In this system the outdoor air was provided to the room through the

    infiltration, wall opening or window opening. In this case the amount of the

    fresh air is affected by the infiltration and the stack effect. This system has many

    disadvantages and does not meet the ventilation requirement of ASHRAE

    Standard 62.

    Central Ventilation System

    In this case a central outside air pretreatment system, which maintain

    fresh air at about 18-21 C, is used.

    Ventilation air may then be introduced to the room either through the fan

    coil unit or through a separate air outlets.

    The ventilation load is carried out by this central ventilation system.

  • 8/10/2019 HVAC Lecture 2

    25/36

  • 8/10/2019 HVAC Lecture 2

    26/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 26

    By regulating the water flow through it by modulating the chilled water

    control valve. The fan of the speed is selected high, medium or low. This

    method of control leads to high RH in the space.

    Two position control (on/off) of the chilled water valve with using

    variable speed fan. This system gives bitter RH but it cost much.

    Applications

    High rise building where no space is available for large duct works

    Applications that has no enough spacing for large sizes of air handling

    units if all air system is used.

    The system is working well in offices buildings, hotels, apartment houses

    and other applications that need separate control of each space and

    separate on/off control of the system for every space.

    Fan coil system are used in numbers of hospitals but are less desirable

    because of the low efficiency of the filtration system and difficulty of

    maintaining adequate cleanliness in the space.

    Applications that have great variation in the sensible heat loads.

    Applications that have high diversity of loads between spaces.

    Advantages

    Separate temperature control of the different rooms/zones of the building

    with the possibility of adjusting each thermostat for a different

    temperature at relatively low cost.

  • 8/10/2019 HVAC Lecture 2

    27/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 27

    Separate heating and cooling sources in the primary air and secondary

    water gives the occupant in each space the possibility of choice of heating

    or cooling.

    Less space is required for the distribution system.

    The sizes of the central air handling units are smaller compared with those

    of other systems.

    The ability to shut off local terminals in unused areas.

    No cross contamination from circulated air between rooms.

    The system can be use for existing building retrofitting.

    Ventilation air supply is positive and may accommodate recommended

    outside air quantity.

    Spaces can be heated without operating the ventilation air system via the

    secondary water system.

    Building peak load rather than sum of rooms peaks determine capacity

    requirements which leads to small capacity.

    Low operating cost.

    Disadvantages

    All-Water-System requires much more maintenance then central all air

    system and this work must be done in occupied area.

    Condensate pan and drain system is required and this must be cleaned and

    flushed periodically, condensate disposal can be difficult and costly.

    Filters are small, low in efficiency, and required frequent changing to

    maintain air volume.

  • 8/10/2019 HVAC Lecture 2

    28/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 28

    Summer room humidity level tends to be relatively high

    Low filtration efficiency leads to unclean coil and low performance of it.

    It is also difficult to clean the coil if necessary.

    The system is inefficient if the outdoor air requirements are high.

    The initial cost of the system is higher than that of the all air system.

    2.4 Unitary Refrigerant-Based System

    Unitary air conditioning equipment is an assembly of factory matched

    refrigerant cycle components for inclusion in filed designed air-conditioning

    systems. Some of the many types of unitary air conditioners available include

    the following characteristics:

    Arrangement: single or split

    Heat rejection: air cooled, evaporative condenser, water cooled.

    Unit exterior: decorative for in space applications, functional for

    equipment room and ducts, weather proofed for outdoors.

    Placement: Floor standing, wall mounted, ceiling suspended, roof

    mounted.

    Indoor air: vertical up flow, counterflow, horizontal, 90 and 180 turns

    or for use with forced air furnaces.

    Locations:

    Indoor- exposed with plenums or furred in ductwork concealed in closest,

    attic, crawl spaces, basements garages, utility rooms, or equipment room,

    wall built in, window.

    Outdoor- roof top, wall mounted, or on ground.

  • 8/10/2019 HVAC Lecture 2

    29/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 29

    Unitary air conditioner, in contrast to room air-conditioner, includes fans

    capable for operating with ductwork, although some unit may be applied with

    plenum.

    Central unitary air conditioner tends to serve zoned systems, with each

    zone served by its own unit. For large single spaces where central systems are at

    their best advantages, multiple units are often advantageous because as load

    sources move within the large space, the many smaller interlocked and

    independent systems have more flexibility than one central system.

    Applications

    Building that need air conditioning of only small numbers of rooms that

    are far away from each other.

    Applications that need metering and accounting of energy to each tenant.

    Applications of small cooling capacities

    Applications of intermitted use of the rooms.

    Air conditioning of existing building.

    Apartment and dormitories

    Control

    The control of the unitary units is on-off control to the refrigeration machine via

    a thermostat in the zone or in the return air duct.

  • 8/10/2019 HVAC Lecture 2

    30/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 30

    Advantages of multiple units systems.

    Simple and inexpensive individual room control.

    Individual air distribution for each room, usually with convenient and

    simple adjustment by the occupant.

    Heating and cooling capability at all times, independent of the mode of

    operation of other spaces in the building.

    Individual ventilation air, normally operating whenever the conditioner

    operates.

    Consistent performance assured by manufacture-matched components.

    Usually some space saving.

    Usually lower initial cost

    Only one terminal zone is affected in the even of equipment malfunction.

    Usually quick availability and installation are possible.

    Equipment serving spaces that become vacant can be turned off locally or

    from a central point, without affecting occupied spaces.

    High quality and reliability because manufacture assembles components.

    System operation is simple.

    Energy can be metered directly to each tenant.

    Equipment locations allows for shorter duct runs, reduced duct space

    requirements, and ease of service access.

    Disadvantages

    Operating sound level can be high

  • 8/10/2019 HVAC Lecture 2

    31/36

  • 8/10/2019 HVAC Lecture 2

    32/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 32

    How much area and volume from the building can be taken for the HVAC

    equipment.

    How the HVAC service is sale or rented to the tenant of the spaces of the

    project.

    What are the parameters that required to be controlled and what are

    precision and accuracy of the control system.

    What are the special equipments of the HVAC system, ACH, clean spaces

    or not, sound level, fresh air requirements, etc.

    Since these factors are interrelated, the owner and the designer must consider

    how each affects the other. The relative importance of these factors differs with

    different owners and often changes from one project to another.

    3.1 System Option Constraints

    The first step in selecting a system or rejecting other systems is to

    determine and documents constraints dictated by performance, capacity,

    available space and other factors. These constraints narrow the choice to systems

    that can fit the applications. Examples of these constraints are:

    Cooling load

    Known the cooling load often narrows the choice of the system that can fit

    within the available space and are compatible with the building architectural.

    Zoning Requirements

    The required zoning of the building, the degree of control required in each zone

    and the equipment space required for individual zones also narrows the system

    choice. The factors that must be taken in account in zoning a building are:

  • 8/10/2019 HVAC Lecture 2

    33/36

  • 8/10/2019 HVAC Lecture 2

    34/36

    Air Conditioning Systems (Comparison/ Application/ Selection) 34

    The required special support forms the stricture for the major components.

    The heavy of the major components and the stricture can hold it or not.

    Space available to house the equipments and its location relative to the

    occupied space.

    The acceptability of the components obtruding into the occupied space,

    both physically and visually.

    The space available in the false ceiling to pass the duct and piping system

    or inserting the terminal devices.

    First and operating cost

    The first and the operating cost of the HVAC system can narrow the selection of

    the system. These cots must be within the budget limit of the project. The major

    factors that affect the cost of each of the HVAC system are:

    The operating energy source of the system; electricity or natural gas and

    the price of each source, and the possibility and cost of extending these

    sources to the building.

    The control system, accuracy and the number of variables required to be

    controlled.

    Centralize the system or using individual components. The cost of a

    central unit is smaller than the cost if individual units are used.

    Maintenance cost of the HVAC system.

    Cost of the spare parts of the system.

    3.2 Selection Report as a Part of the Design Concept Report

    The last step of the system selection is preparing a report, by HVAC

    designer, containing a summary of the design and selection criteria. This report

  • 8/10/2019 HVAC Lecture 2

    35/36

  • 8/10/2019 HVAC Lecture 2

    36/36

    2. How much will the system cost to own compared to others considered?

    What are the recovery time of the initial investment, and the future cost of

    replacement equipment?

    3. Will the system deliver the desired uniform temperature under varying

    whether and solar conditions?

    4. What are the operating costs-energy costs, maintenance, operating labor

    and supplies of this system compared to the others?

    5. What reliability can the owner expect compared to other systems.

    6. If the system flexible enough to meet changes in the owner's needs? What

    is required to add a new zone? Can it meet the increased capacity

    requirements of space when new equipment (load) is added?

    Finally the system selection report should conclude with a recommended

    system choice along with reasons for the choice.

    References

    1. ASHRAE HANDBOOK, Fundamentals

    2. ASHRAE HANDBOOK, HVAC Systems and Equipment

    3. Harry J. Sauer and Ronald H. Howell, Principles of heating ventilation and

    air conditioning, a text book supplemented to the 1989 ASHRAE Handbook-

    Fundamental.