POWER SUPPLY UP TO 1000 V HAKEL Ltd. Bri Stefanu 980 500 03 Hradec Kralove Czech Republic HS55 GB DE RU F PL VN CZ INSTALLATION INSTRUCTIONS Safety instructions Sicherheitshinweise Consignes de securité Instrukcja bezpieczeństwa EN 61643-11/A11: 2007-08 EN 62305-4: 2006-1 BACK-UP FUSE APPLICATION TECHNICAL DATA BLOCK DIAGRAM N(PEN) L Phone: +420 494 942 300 Fax: +420 494 942 303 [email protected] www.hakel.com TN-C, TN-S, TT TYPE 1 CLASS I LPZ 0 1 IP -40°C +80°C J 20 INDUSTRY TN-C TN-S F1 max. 500 A S2 S3 S2 S3 F1 > 500 A F2 =500 A TT TEST LIGHTNING ARRESTER 2 25 mm 2 35 mm TEST VOLTAGE U = 250 VDC . . . . . . . . W R > 500 kW ISO MEASUREMENT ok . . . . . . . . W R <500 kW ISO MEASUREMENT L PEN TN-C + + PEN L EP L N TN-S, TT + + N L PE Type HS55 Test class according to EN 61643-11 and IEC 61643-11 TYPE 1, CLASS I Max. continuous operating voltage U C 440 V AC Lightning impulse current (10/350) I imp 50 kA - charge Q 25 As - specific energy W/R 600 kJ/Nominal discharge current (8/20) I n 50 kA Voltage protection level at I imp U P < 2,5 kV Temporary overvoltage (TOV) U T 690 V/5 s Response time t A < 100 ns Follow current interrupting rating at U C I fi 3 kA rms Max. back-up fuse 500 A gL/gG Short-circuit withstand capability at max. back-up fuse I p 25 kA rms LPZ 0-1 Housing material Polyamid PA6, UL94 V-0 Protection type IP20 Operating temperature range J -40°C ... +80 °C Cross-section of the connected conductors (at tightening moment of clamps 4 Nm) 35 mm (solid) 25 mm 2 (wire) Mounting on DIN rail 35 mm Lifetime min.100 000 h Weight m 225 g Article number 10 055

HS55 - Hakel

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HS55 - Hakel

POWER SUPPLY UP TO 1000 V

HAKEL Ltd.Bri Stefanu 980500 03 Hradec KraloveCzech Republic

HS55

GB

DE

RU

F

PL

VN

CZ

INSTALLATION INSTRUCTIONS

Safety instructions

Sicherheitshinweise

Consignes de securité

Instrukcja bezpieczeństwa

EN 61643-11/A11: 2007-08EN 62305-4: 2006-1

BACK-UP FUSE APPLICATION

TECHNICAL DATA

BLOCK DIAGRAM

N(PEN)

L

Phone: +420 494 942 300Fax: +420 494 942 [email protected]

TN-C, TN-S, TT

TYPE1

CLASSI

LPZ0 1

IP

-40°C

+80°C

J

20 INDUSTRY

TN-CTN-S

F1 max. 500 A

S2

S3

S2

S3

F1 > 500 A

F2 =500 A

TT

TEST

LIGHTNING ARRESTER

225 mm 235 mm

TEST VOLTAGEU = 250 VDC

.. ... ... W

R > 500 kWISO

MEASUREMENT

ok

.. ... ... W

R <500 kWISO

MEASUREMENT

L

PEN

TN-C

+

+PEN

L

EP

L

N

TN-S, TT

+

+N

L

PE

Type HS55

Test class according to EN 61643-11 and IEC 61643-11 TYPE 1, CLASS I

Max. continuous operating voltage UC

440 V AC

Lightning impulse current (10/350) Iimp

50 kA

- charge Q 25 As

- specific energy W/R 600 kJ/Ω

Nominal discharge current (8/20) In

50 kA

Voltage protection level at Iimp

UP

< 2,5 kV

Temporary overvoltage (TOV) UT

690 V/5 s

Response time tA

< 100 ns

Follow current interrupting rating at UC

Ifi

3 kArms

Max. back-up fuse 500 A gL/gG

Short-circuit withstand capability at max. back-up fuse Ip

25 kArms

LPZ 0-1

Housing material Polyamid PA6, UL94 V-0

Protection type IP20

Operating temperature range J -40°C ... +80 °C

Cross-section of the connected conductors (at tightening moment of clamps 4 Nm)

35 mm (solid)

25 mm2 (wire)

Mounting on DIN rail 35 mm

Lifetime min.100 000 h

Weight m 225 g

Article number 10 055

Page 2: HS55 - Hakel

The device may only be connected and installed by an electrically skilled staff. National standards and safety regulations must be abided The device must be checked for external damage prior to installation. If any damage or other defects are found, the device must not be installed.Its use is only permitted within the l imits stated in these installation instructions. If the device is overloaded above the given values, it can be destroyed a n d a l s o o t h e r e q u i p m e n t connected to the device can be damaged. Opening or otherwise tampering with the device invalidates the warranty.

Меры безопасности

Подключение и установка устройства м о ж е т п р о и з в о д и т ь с я т о л ь к о персоналом, допущенным к работе с электроустановками. При этом должны с о б л ю д а т ь с я п р а в и л а т е х н и к и безопасности и требования стандартов и других нормативных документов Перед установкой необходимо проверить имеет ли устройство внешние повреждения. При наличии таких повреждений установка у с т р о й с т в а н е д о п у с к а е т с я . Эксплуатация устройства допускается только в пределах электрических п а р а м е т р о в и х а р а к т е р и с т и к о к р у ж а ю щ е й с р е д ы , у к а з а н н ы х в паспортных данных на данный тип устройств. Эксплуатация устройства при других электрических параметрах и характеристиках окружающей среды может привести к его повреждению или к повреждению другого связанного с ним оборудования . При самовольном вскрытии корпуса устройства, или ином вмешательстве в его нормальную работу аннулируются гарантийные о б я з а т е л ь с т в а п р о и з в о д и т е л я устройства.