HART

HARThighway addressable remote transducerRavikumar Koturwar 13MAC0038Rahul S Kore 13MAC0041Parth M Mehta 13MAC0048

VIT Control and Automation13-14VIT UNIVERSITY, SELECT1

Why its Popular nowThe HART protocol directly contributes to these business goals by providing cost savings in: Commissioning and installationPlant operations and improved quality Maintenance Analog 420 mA and digital signals provide flexibility not available with any other communication technology. Hand Held Communicators are often used to perform device set-up, calibration, commissioning and periodic maintenance

VIT Control and Automation13-14VIT UNIVERSITY, SELECT2

Improved plant operations

VIT Control and Automation13-14VIT UNIVERSITY, SELECT3

Operational FlexibilityMulti-master Operation? Primary master ---- control systemSecondary master ---- A hand-held communicator or a maintenance computer.

VIT Control and Automation13-14VIT UNIVERSITY, SELECT4

Instrumentation investment protection

Wiring, analog controllers, barriers, analog or smart instrumentation exists widely

The HART communication protocol enables you to retain your previous investments in existing hardware and personnel. VIT Control and Automation13-14VIT UNIVERSITY, SELECT5

Digital communication The HART protocol enhances the capabilities of digital instruments by providing communication access and networking

VIT Control and Automation13-14VIT UNIVERSITY, SELECT6

HART Vs. FieldbusHART is compatible with existing wiring in older plants.Hart is understood, accepted and appreciated by virtually everyone involved.Fieldbus costs a lot more to implement, especially for existing equipment.Lot of instruments not radially available with Fieldbus.

VIT Control and Automation13-14VIT UNIVERSITY, SELECT7

HART specifications?

Physical form of transmissionTransaction Procedures Message structures Data formatsSet of commands to perform required operation.

VIT Control and Automation13-14VIT UNIVERSITY, SELECT8

Communication Modes of HART?

Master Slave Mode (Poll---Response Mode) Maximum communication speed --- 2 messages/sec. Configuration ---- Point-to-point or Multi-point Master sends command (request) , slave responds (replies)

RequestReplyVIT Control and Automation13-14VIT UNIVERSITY, SELECT9

Burst Mode ( Broadcast Mode) Slave transmits messages continuously (e.g. values of a measurand). The communication speed --- 3 message/sec. A slave device repeatedly sends a data message. Used for fast updation of the value of a measured variable

Continuous ReplyVIT Control and Automation13-14VIT UNIVERSITY, SELECT10

HART Signal Levels?HART protocol specifies that master device transmit a voltage signal whereas slave device transmits a current signal. The current signal is converted in to corresponding voltage by a loop load resistor(250 ohms), so all devices use voltage sensitive receiver circuits. The wave shape is sinusoidal, but trapezoidal waveform is acceptable. A square wave is not acceptable. Master Slave Operation? The each message transaction is originated by the master station, the slave device only replies only when it receives a command message. The reply from the slave device acknowledges that the command has been received and may contain data requested by the master.

VIT Control and Automation13-14VIT UNIVERSITY, SELECT11

Different HART networks? Point-to-point ModeBoth analog and digital communications are supported. 420 mA signal is used to communicate one process variable.Additional process variables, configuration parameters, and other device data are transferred digitally using the HART protocol

VIT Control and Automation13-14VIT UNIVERSITY, SELECT12

VIT Control and Automation13-14VIT UNIVERSITY, SELECT13

Multidrop ModeOnly digital communication is supportedRequires only a single pair of wiresIn case safety barriers and an auxiliary power supply for up to 15 field devicesAll field device polling addresses are >0, and the current through each device is fixed to a minimum value (typically 4 mA).

VIT Control and Automation13-14VIT UNIVERSITY, SELECT14

VIT Control and Automation13-1415

Different Groups of HART commands?

Universal : Provides functions which are implemented in all field devices. Examples : Read model Read serial number Read range Common Practice : Provides functions common to many field devices but not all. If a device uses these functions, these commands should be used to perform them. Examples : Read (up to 4) variables Perform calibration check Perform self-testDevice specific : Provides functions which are more or less unique to a particular filed device . Examples : Select 0C/0F (temperature sensor) Tune a control parameter (control device) Write alarm set point (relay)

VIT Control and Automation13-14VIT UNIVERSITY, SELECT16

Command Summary

VIT Control and Automation13-14VIT UNIVERSITY, SELECT17

Types of Frame Formats in HART protocol? Short frame format ---- Older HART instruments(Version4) used short frame format. In this the address of the slave device is o.Long frame format ---- HART version 5 introduced Long frame format. In this the address of the slave device is world wide unique identifier. It is a 38 bit number derived from the manufacturer code. It contains the device code and device id no Long frame format gives extra security against the possible reception and acceptance of command meant for another device, either due to external interference or due to excessive cross talk

VIT Control and Automation13-14VIT UNIVERSITY, SELECT18

Some More Pointspass-through feature? DD?Interoperability?

VIT Control and Automation13-14VIT UNIVERSITY, SELECT19

Wireless HART

VIT Control and Automation13-14VIT UNIVERSITY, SELECT20

Introduction

Wireless HART is a wireless mesh network communication protocol.It is designed to meet the needs for process automation applicationsIt is a KEY part of the HART field communication protocol Version 7Less than 10% of the installed HART instruments have a direct communications link back to a host system. The addition of low-cost wireless connectivity provides a pathway for remote host systems to read process and maintenance information from field instruments, both old and new.

VIT Control and Automation13-14VIT UNIVERSITY, SELECT21

Wireless HART Network Structure

VIT Control and Automation13-14VIT UNIVERSITY, SELECT22

Wireless Mesh

VIT Control and Automation13-14VIT UNIVERSITY, SELECT23

Time Synchronization

Report by Exception Time- and Condition-based Alerts

VIT Control and Automation13-14VIT UNIVERSITY, SELECT24

Time Stampsynchronized clock enabling it to transmit data at the correct time. Used to stamp time and date

Wireless Co-existence Uses channel assessment and short message sizes to coexist with neighboring networks

Wireless Diagnostics Ensures the health of the networkInclude indicators of battery life remaining, devices present, network join attempts and other network management indicators.

VIT Control and Automation13-14VIT UNIVERSITY, SELECT25

Wireless SecurityJoin KeyUnique Message Integrity Code (MIC)Message Encryption

VIT Control and Automation13-14VIT UNIVERSITY, SELECT26

Loop TestingNo 4 to 20 mA signalIt checks that the process data is displayed correctly at the host and also tests other control functions.

Wireless HART Adapter New HART device can be added to wired device to provides wireless FeatureLoop - Powered

VIT Control and Automation13-14VIT UNIVERSITY, SELECT27

WIRELESS NETWORK

28

PART 2FSKHART signalHART protocolMUXComparison

VIT Control and Automation13-14VIT UNIVERSITY, SELECT29

CHARACTERISTICSSimultaneously supports two communications channels. 4-20mA "analog" communications and Modulated two-way "digital" communications. Additional process data in Multi-Variable devices used to improve plant operation Field devices can continuously publish their process data. Operators alerted to impending problems before negative impact to the process = Real time device diagnostics.

VIT Control and Automation13-14VIT UNIVERSITY, SELECT30

FSK

Bell 202 Frequency Shift Keying (FSK) standard to superimpose digital communication signals at a low level on top of the 4-20mA.

VIT Control and Automation13-14VIT UNIVERSITY, SELECT31

HART SIGNAL in Physical layer

HART allows additional information to be carried on the same pair of wires with the 4-20 mA Analog SignalVIT Control and Automation13-14VIT UNIVERSITY, SELECT32

TWO COMMUNICATION CHANNEL

4-20mA "Analog" Channel HART"Digital"Channel 4-20mA Analog support large part of Protocol Specifications One-way communication of one process value Simple Low Pass Filter isolates 4- 20mA signalCompliments 4-20mABased on Analog Telephone Modems Long Cable Runs High Noise Immunity You can "hear" HARTTwo-way CommunicationsVIT Control and Automation13-14VIT UNIVERSITY, SELECT33

ExampleFig : Two Communication Channels

Connecting a PC to a HART device or network PC application development tools > PC configuration softwareUniversal handheld communicator >275 Universal Reading HART data into non-HART systemsCommissioning HART networks > HART multidrop networksControl system interfaces > Control in field devicesMultiplexersDevice status and diagnosticsIntrinsic safety(IS)The following sections contain information that can help you to get the most from your HART system:

VIT Control and Automation13-14VIT UNIVERSITY, SELECT34

CABLE LENGTHTABLE: Allowable cable lengths for(#18 AWG) shield twisted pair

Theoretical Length max. : Affected by: electrical characteristics ( mostly Capacitance) & Combination of connected devices It is also a good idea to buy a cable designed for HART. Belden 3105A is an example of such a cable.3,000 meter (10,000 ft)VIT Control and Automation13-14VIT UNIVERSITY, SELECT35

HART PROTOCOL LAYERS

VIT Control and Automation13-14VIT UNIVERSITY, SELECT36

Controlled by HCF Open and Available to AnyoneEasy-to-Read LanguageConsistent and well-defined terms

Organization of HART SpecificationsVIT Control and Automation13-14VIT UNIVERSITY, SELECT37

Protocol StructureVIT Control and Automation13-14VIT UNIVERSITY, SELECT38

LONG FRAME FORMAT

39VIT Control and Automation13-14

Packet Structure

VIT Control and Automation13-14VIT UNIVERSITY, SELECT40

RESPONSE

VIT Control and Automation13-14VIT UNIVERSITY, SELECT41

General device status is always returned with COMMAND32 bytes of status info.

HART COMMAND 3

VIT Control and Automation13-14VIT UNIVERSITY, SELECT42

STATUS MESSAGES ARE:

Status MessagesField device malfunction (Bit 7) Configuration changed (Bit 6)Cold start (Bit 5)More status available (Bit 4)Analog output current fixed (Bit 3)Analog output saturated (Bit 2)Non-primary variable out of limits (Bit 1) Primary variable out of limits (Bit 0)

VIT Control and Automation13-14VIT UNIVERSITY, SELECT43

COMMAND 48Device specific information is always returned with COMMAND4825 bytes of additional status information*Not necessary to use all the bytes Ex. Honeywell STT250 uses only first 3 bytes.

VIT Control and Automation13-14VIT UNIVERSITY, SELECT44

VIT Control and Automation13-14VIT UNIVERSITY, SELECT45

Multiplexers

To interface numerous HART devicesSupport point-to-point and all-digital (multidrop)

Communication between a multiplexer and host depends on the multiplexer capabilities

RS232C, RS485, Modbus, TCP/IP Ethernetcan be used as primary I/O front end for aHART-based control or monitoring systemWhen installing HART multiplexer systems, the following capabilities should be considered:

Number of HART channels supported Number of HART channels that share a HART modem Burst mode support Multidrop support Method of communication with the host computer or control systemVIT Control and Automation13-14VIT UNIVERSITY, SELECT46

1. PARALLEL MONITORING WITH A MULTIPLEXER

VIT Control and Automation13-14VIT UNIVERSITY, SELECT47

PC acts as the host, providing the human-machine interface & perform high-level functions.Mux passes HART commands from the host computer to the field devices.continuously monitors the field devices, reports the current readings and instrument status to the host,

Figure: HART Multiplexer as the Primary I/O System2. MULTIPLEXER AS THE PRIMARY I/O SYSTEMVIT Control and Automation13-14VIT UNIVERSITY, SELECT48

Multiplexer refresh time > function of no. of devices connected per channelRefresh time = 0.8sec / device / modem

VIT Control and Automation13-14VIT UNIVERSITY, SELECT49

3. CONTROL FIELD DEVICES

Figure: Transmitter with PID (HART Slave)

VIT Control and Automation13-14VIT UNIVERSITY, SELECT50

Wireless HART vs. Bluetooth vs. ZigbeeRangeData security = Reliable message deliveryIndustrial grade robustness = Industry acceptance Reliability. *No HART device use Bluetooth connectivity with data load.VIT Control and Automation13-14VIT UNIVERSITY, SELECT51

No frequency diversity > Entire network shares same static channel Static Channel also susceptible to interference with wireless LAN Makes it susceptible to both intended and unintended jammingCan stop entire network communication Designed from start for robust and secure CommunicationNetwork works 24*7 > no option to turn it completely offMesh networking with graph routing > provide redundancy and self healingZigBeeWireless HARTVIT Control and Automation13-14VIT UNIVERSITY, SELECT52

Comparison at layer level

VIT Control and Automation13-14VIT UNIVERSITY, SELECT53

Versions

VIT Control and Automation13-14VIT UNIVERSITY, SELECT54

Industry Apps

PART 3VIT Control and Automation13-14VIT UNIVERSITY, SELECT55

VIT Control and Automation13-14VIT UNIVERSITY, SELECT56

Reading HART Data into Non-HART Systems Many HART products are able to perform more than one measurement oroutput function (e.g., make multiple process measurements, calculateprocess information, and provide positioner feedback information). All ofthis information can be easily accessed digitally. However, existingcontrollers or interface equipment may not have the ability to read digitalHART data. Products are available that can read HART digital signals andconvert them to analog or contact information, which enables anytraditional analog/digital I/O to take full advantage of the benefits ofHART-communicating devices. VIT Control and Automation13-14VIT UNIVERSITY, SELECT57

The Tri-Loop module monitors a HART loop for a bursting message andconverts three of the four possible variables in HART communicator.

VIT Control and Automation13-14VIT UNIVERSITY, SELECT58

The site programmable alarm( SPA )module continuously communicates with any HART-capabledevice and provides contact closure outputs (alarm trips) based on theinformation received (Figure 14). For example, the SPA can be configured to monitor the device-status information inherent in the HART communication protocol and trigger events such as local on/off applications or alarms. The SPA can also initiate emergency shutdown action if problems are detected with a field device in critical loop applications

VIT Control and Automation13-14VIT UNIVERSITY, SELECT59

Industrial Application Many companies in a wide variety of industries have already realized the advantages of using the HART communication protocol. This section describes some applications in detail and outlines the tangible benefits that result. The applications have been grouped into the following sections: Inventory-management applications Cost-saving applications Remote-operation applications Open-architecture applicationsVIT Control and Automation13-14VIT UNIVERSITY, SELECT60

Inventory-Management ApplicationsAccurate measurements for inventory management are essential in all industries. The HART communication protocol enables companies to make sure inventory management is as efficient, accurate, and low cost as possible.Tank level and inventory management is an ideal application for a HART multidrop network . The HART network digital update rate of two PVs per second is sufficient for many tank-level applications. A multidrop network provides significant installation savings by reducing the amount of wiring from the field to the control room as well as the number of I/O channels required.VIT Control and Automation13-14VIT UNIVERSITY, SELECT61

VIT Control and Automation13-14VIT UNIVERSITY, SELECT62

VIT Control and Automation13-14VIT UNIVERSITY, SELECT63

UNDERGROUND PETROLEUM STORAGE WITH HART COMMUNICATION FOR ACCURACYUnderground salt caverns are frequently used for crude oil storage. One customer pumps oil from barges into the storage caverns. An ultrasonic flow-meter records the total flow. To get the oil out of the caverns, a brine solution is pumped into the cavern through a magnetic flow-meter. Brine and crude oil flowing in both directions are measured and reported to the DCS using the HART communication protocol for accuracy.VIT Control and Automation13-14VIT UNIVERSITY, SELECT64

VIT Control and Automation13-14VIT UNIVERSITY, SELECT65

Cost-saving applicationsA Texas wastewater treatment plant replaced stand-alone flow meters and chart recorder outstations that required daily visits for totalization with a HART system. HART-based magnetic flow meters were multidropped into HART RTUs to create a cost-effective SCADA network. The use of HART technology reduced system and cable costs, enhanced measurement accuracy, and eliminated time-consuming analog calibration proceduresVIT Control and Automation13-14VIT UNIVERSITY, SELECT66

A consumer appliance manufacturer used the networking capability of the HART protocol to ensure level, flow, and pressure HART multidrop provided substantial wiring and installation savings as well as digital accuracy with the elimination of the analog to digital (A/D) and digital to analog (D/A) conversions of the instrument and PLC I/O. Figure shows pressure transmitters connected to a PLC via smart transmitter interface multiplexers.VIT Control and Automation13-14VIT UNIVERSITY, SELECT67

VIT Control and Automation13-14VIT UNIVERSITY, SELECT68

Remote-Operation Applications Choosing the HART communication protocol for all-digital communicationin a wide-area network enabled one company to have real-time monitoringand control, access to diagnostics, and maintenance capabilitiesall from aremote location.

Each platforms RTU provided a link to approximately 50 temperature,pressure, and flow transmitters. The RTU used the multi-mastercapability of the HART protocol to enable the second RTU to act as a hotstandby, which monitored activity and was able to take over if a failureoccurred. The RTUs provided links with the emergency and safety systemsand a local interface for maintenance personnel. The Modbus protocol wasused for communication to the central SCADA systemVIT Control and Automation13-14VIT UNIVERSITY, SELECT69

VIT Control and Automation13-14VIT UNIVERSITY, SELECT70

In a Venezuela gas-lift project, HART multidrop technology was used for remote operation of offshore gas-lift production wells at considerable savings: 30% decrease in installation costs 16:1 reduction of input modules Reduced cost of I/O cards in the RTU Remote re-rangingRemote access to the transmitter status for improved process uptimeVIT Control and Automation13-14VIT UNIVERSITY, SELECT71

Open-Architecture Applications The best way to judge the openness of a communication protocol is by thenumber of products supported. By this standard, the HART protocol isperhaps the most open of any field-communication protocol availabletoday.

In a major refinery expansion, an oil company weighed the advantages ofusing either a proprietary system or a HART-based system. The resultsindicated that the company could use HART digital instruments in 92% oftheir applications, compared to only 33% with the proprietary system.Choosing HART products resulted in an incremental $23,000 in savingsdue to commissioning efficiencies and ongoing maintenance and diagnosticcapabilities.

VIT Control and Automation13-14VIT UNIVERSITY, SELECT72

VIT Control and Automation13-14VIT UNIVERSITY, SELECT73

VIT Control and Automation13-14VIT UNIVERSITY, SELECT74

Intrinsic Safety Intrinsic safety (IS) is a method of providing safe operation of electronicprocess-control instrumentation in hazardous areas. IS systems keep theavailable electrical energy in the system low enough that ignition of thehazardous atmosphere cannot occur. No single field device or wiring isintrinsically safe by itself (except for battery-operated, self-containeddevices), but is intrinsically safe only when employed in a properlydesigned IS system.

HART-communicating devices work well in applications that require ISoperation. IS devices (e.g., barriers) are often used with traditionaltwo-wire 420 mA instruments to ensure an IS system in hazardous areas.With traditional analog instrumentation, energy to the field can be limitedwith or without a ground connection by installing one of the following ISdevicesVIT Control and Automation13-14VIT UNIVERSITY, SELECT75

Shunt-diode (Zener) barriers that use a high-quality safety groundconnection to bypass excess energy

Isolators, which do not require a ground connection, that repeat theanalog measurement signal across an isolated interface in the safe-sideload circuit Both Zener barriers and isolators

VIT Control and Automation13-14VIT UNIVERSITY, SELECT76

VIT Control and Automation13-14VIT UNIVERSITY, SELECT77

When designing an IS loop using shunt-diode barriers, two additionalrequirements must be considered:

The power supply must be reduced by an additional 0.7 V to allowheadroom for the HART communication signal and yet not approachthe Zener barrier conduction voltage.

The load resistor must be at least 230 (typically 250 ).

VIT Control and Automation13-14VIT UNIVERSITY, SELECT78

HART is a backward compatible enhancement to 4-20mA instrumentation that allows two way communication with smart, microprocessor-based field devices. Continuously Validate Integrity of Control Information Ensure accuracy of system data/ Automatically detect any deviation between device and system Continuous Real Time Diagnostics Device Problems/ Loop Current Faults Device Needs Maintenance Unlock additional information in Multi-Variable devices

CONCLUDEVIT Control and Automation13-14VIT UNIVERSITY, SELECT79

Wireless HART is designed based on a set of funda- mental requirements: it must be simple (e.g., easy to use and deploy) Self-organizing and self-healing. flexible (e.g., support different applications)Scalable (i.e., fit both small and large plants) Reliable, secure, and support existing HART technology (e.g., HART commands, configuration tools, etc.)