Alaska Native Medical Center Anchorage, AK Mercy Franciscan Hospital Cincinnati, OH United Hospital St. Paul, MN The Miriam Hospital Providence, RI Bassett Army Community Hospital Fort Wainwright, AK Eisenhower Medica l Center Rancho Mirage, CA VA Connecticut Healthcare System West Haven, CT Foxdale Village State College, PA Albany Stratton VA Medical Center Albany, NY Milford Regional Medical Center Milford, MA St. John’s Hospital Maplewood, MN Minneapolis VA Health Care System Minneapolis, MN Mount Sinai Hospital Toronto Ontario, Canada Northern Westchester Hospital Mount Kisko, NY Robert Wood Johnson Hospital New Brunswick, NJ The Hospital for Sick Children Toronto Ontario, Canada St. Mary’s Medical Center Apple Valley, CA Tampa General Hospital* Tampa, FL TriPoint Medical Center Concord Twp., OH The Children’s Hospital of Philadelphia Philadelphia, PA Parkview Health Fort Wayne, IN
Over the past 20 years, Pathway Lighting has provided high-performance lighting systems for some of the nation’s top healthcare facilities.
Healthcare facilities are comprised of complex spaces that put heavy demands on lighting systems.
Demanding projects deserve Pathway's MultiCare healthcare lighting solutions - a full line of 4"- and 6"- aperture fixtures, including:
waiting rooms
receptionnurses' stations -
corridors
emergency entrance
conference rooms
MRI suites
atria
showers
cafeterias
patient rooms
|4 Healthcare Lightingpathwaylighting.com 5|
4VLMRI- a non-ferrous, MRI downlight
6SQLBEX- a high-output exam light
4VTWRL and 4VTWWL- tunable white downlights
LED downlights with semi-regressed (RL) lens
LED downlights with flat, non-conductive (WL)shower lens
The MultiCare collection offers you choice of:
Round- and Square- aperture downlights
5 LED modules Lumen packages up to 8000 lumens
Color rendering up to 98 CRI
Narrow, medium and wide beam distributions
0-10V, Lutron, DMX, DALI, Power Vector 1%, eldoLED 0.1% dimming
Flat, Semi-Regressed or Regressed lens
Optional Anti-Microbial finish and Tamper-proof fasteners
LED downlight with flat, non-conductive shower lens
MRI Exam Light LED downlight with semi-regressed lens
Tunable White
Introducing MultiCare™ Healthcare Lighting Solutions
Philips Philips4" 4VLFSRL 4VLFTWL
4VLRL 4VLFSWL
4VLEDWL
6" 6VLFSRL 6VLFSWL
6VLRL 6VLEDWL
6SQLED-LF8
Bridgelux Bridgelux4" 4VLBRL 4VLBWL
6" 6VLBRL 6VLBWL
Philips4" 4VTWRL
4VTWWL
Bridgelux6" 6SQLBEX
|6 Healthcare Lightingpathwaylighting.com 7|
Tunable White LED module delivers white light between 2700-6500K, allowing staff and patients to custom tailor their lighting at any time
Semi-regressed (RL) lenses in clear polycarbonate, clear tempered glass or frosted acrylic available for dust management
Flat, non-conductive (WL) polycarbonate lens for wet applications
Compatible with eldoLED dimwheel, DMX and DALI
Available with anti-microbial finish for germ management
Optional tamper-proof fasteners keep fixture secure from unauthorized access
High-performance 4" and 6" downlights for healthcare applications
Semi-regressed (RL) lenses in clear polycarbonate, clear tempered glass or frosted acrylic available for dust management
Dimming to 1%
Available with anti-microbial finish for germ management
Optional tamper-proof fasteners keep fixture secure from unauthorized access
Listed for Wet Location Under Covered Ceiling
High-performance 4" and 6" downlights for healthcare applications
Flat, non-conductive (WL) polycarbonate lens for wet applications
Dimming to 1%
Optional tamper-proof fasteners keep fixture secure from unauthorized access
Listed for Wet Location Under Covered Ceiling
High-performance exam light ideal for applications where medical professionals routinely examine patients
Regressed clear polycarbonate lens for dust management
0-10V dimming to 1% Available with anti-microbial
finish for germ management
4" 4VLMRI Downlight or Wall Wash made
of non-ferrous aluminum construction suitable for MRI room installation
Available with a Medical Grade Driver for projects requiring Safety Standard 60601-1 compliance
56 high-performance LED's coupled with a mixing chamber ensures color consistency from fixture to fixture
0-10V dimming to 10% standard
Available with anti-microbial finish for germ management
Optional tamper-proof fasteners:
semi-regressed lens detail
flat, non-conductive lens detail
15'
PRODUCT PIC HERE
Plan - area under entrance canopy
16'
20'
5' OC
7' OC
Plan
20'
8' OC
5' OC
|8 Healthcare Lightingpathwaylighting.com 9|
Design Considerations Use high CRI and 3500K CCT sources to create a more inviting and less
institutional feel at the entrance Determine the nighttime outdoor lighting zone designation within which the
facility is located to help establish appropriate light levels
Emergency Entrance
Pathway Solution
IES Recommendations/ASHRAE 90.1-2010 Requirement
Average Illuminance (fc) 19.6 15
Uniformity (avg:min) 2.3:1 3:1
LPD (W/sq.ft.) 0.46 0.9
Calculation details :
Luminaire Used : Standard Open Downlight 6VLED1100 with 6VLEDMD TrimLuminaire Wattage : 16.3
Number of Luminaires : 9
Total Wattage : 146.7
Room Area (sq.ft.) : 320
LLF : 0.8
Reflectances : 80/50/10
Ceiling Height : 10'-0"
Luminaire Mounting Height : 10'-0"
Workplane : 3'-0" AFG
Calculations
Standard 6" Open Downlight6VLED1100 with 6VLEDMD Trim
Design Considerations Provide light levels and employ lighting design techniques typically used in
living room settings, to support reading, television viewing, portable computing or gaming, and conversation
Consider the use of accent lighting on artwork in the space for visual interest and to create a more inviting and relaxing space
Pathway Solution
IES Recommendations/ASHRAE 90.1-2010 Requirement
Average Illuminance (fc) 38 30
Uniformity (avg:min) 1.68:1 4:1
LPD (W/sq.ft.) 0.99 1.07
Calculations
Waiting Room
4" Downlight4VLRL30003K
with 4VLRL1 Trim - Clear Polycarbonate Lens
Calculation details :
Luminaire Used : 4VLRL30003K with 4VLRL1 Trim - Clear Polycarbonate LensLuminaire Wattage : 37.4
Number of Luminaires : 8
Total Wattage : 299.2
Room Area (sq.ft.) : 300
LLF : 0.8
Reflectances : 80/50/20
Ceiling Height : 9'-0"
Luminaire Mounting Height : 9'-0"
Workplane : 2'-6" AFF
MultiC
are Perfo
rman
ce
MultiC
are Perfo
rman
ce
Plan
15'
24'
7' OC
See Bathroom/Shower
Calculation page 12.
7'
3'
Luminaire A
Luminaire B
4' OC
3' OC4' OC
5'-6" OC
9' OC
Patient Bed
|10 Healthcare Lightingpathwaylighting.com 11|
Pathway Solution
IES Recommendations/ASHRAE 90.1-2010
Requirement
Average Illuminance (fc) 100 50
Uniformity (avg:min) 2.3:1 1.5:1
LPD (W/sq.ft.) exempt when separately switched and independent from general illumination
Design Considerations Avoid excessive glare - whenever possible, avoid mounting harsh and bright
luminaires directly above patient beds, including typical 2x4 fixtures that may cause discomfort glare and create an intimidating space with an institutional feel
Consider using small aperture recessed fixtures, strategically located relative to the bed such that there is no direct view of the lamp, or use lensed fixtures to further mitigate glare
Reading is a common visual task for patients. Wall- or ceiling-mounted luminaires with minimum of 3-level switched control are recommended, dimmable preferred
Provide patient access to lighting controls, typically done through the patient bed adjustment and/or nurse calls, to improve patient comfort and satisfaction
Provide nightlights for patient and caregiver circulation that are connected to occupancy sensors on timers or photocells and emit long wavelength light between 600-620 nm, to limit circadian rhythm disruption during the sleep cycle
Patient Room General Illumination and Exam Light
CalculationsPatient Room - Exam Light
Patient Room and Exam Light
Exam Light6SQLBEX80 with 6SQLBEX Trim - Regressed Clear Polycarbonate Lens
Calculation details :
Luminaire Used : A. 6SQLBEX80 with 6SQLBEX Trim - Regressed Clear Polycarbonate Lens Luminaire Wattage : 93.5
Number of Luminaires : 1
Total Wattage : 93.5
Bed Area (sq.ft.) : 21
LLF : 0.8
Reflectances : 80/50/20
Ceiling Height : 8'-6"
Luminaire Mounting Height : 8'-6"
Workplane : 3' AFF
Pathway Solution
IES Recommendations/ASHRAE 90.1-2010 Requirement
Average Illuminance (fc) 8 5
Uniformity (avg:min) 2.1:1 4:1
LPD (W/sq.ft.) 0.33 0.62
Patient Room - General Illumination
Calculation details :
Luminaire Used : B. 4VLRL1100 with 4VLRL3 Trim - Frosted Lens Luminaire Wattage : 16.3
Number of Luminaires : 6
Total Wattage : 97.8
Room Area (sq.ft.) : 300
LLF : 0.8
Reflectances : 80/50/20
Ceiling Height : 8'-6"
Luminaire Mounting Height : 8'-6"
Workplane : Floor
4" Downlight4VLRL1100
with 4VLRL3 Trim - Frosted Lens
MultiC
are Perfo
rman
ce
MultiC
are Perfo
rman
ce
5' minimum
2' 6"minimum
8'
8'
2' 6"
1' 3"
Shower Area
|12 Healthcare Lightingpathwaylighting.com 13|
Design Considerations Over the shower area, use a wet-location downlight with a flat, non-conductive
front lens for safety and cleanability Highlight specific areas where plumbing fixtures are located to provide
task lighting without overlighting the entire room
Shower and Bathroom General Illumination
Shower and Bathroom
6" Downlight6VLEDWL3000 with 6VLEDWL Trim - Flat, Non-Conductive Polycarbonate Lens
PlanBathroom
ShowerPathway Solution
IES Recommendations/ASHRAE 90.1-2010 Requirement
Average Illuminance (fc) 11 10
Uniformity (avg:min) 1.22:1 2:1
LPD (W/sq.ft.) 0.85 0.98
Calculation details :
Luminaire Used : 6VLEDWL3000 with 6VLEDWL Trim - Flat, Non-Conductive Polycarbonate LensLuminaire Wattage : 51
Number of Luminaires : 1
Total Wattage : 51
Room Area (sq.ft.) : 60
LLF : 0.8
Reflectances : 80/50/20
Ceiling Height : 8'-0"
Luminaire Mounting Height : 8'-0"
Workplane : Floor
Calculations
Shower
Pathway Solution
IES Recommendations/ASHRAE 90.1-2010 Requirement
Average Illuminance (fc) 8 5
Uniformity (avg:min) 1.8:1 2:1
LPD (W/sq.ft.) 0.85 0.98
Bathroom General Illumination
6" Downlight6VLEDWL3000
with 6VLEDWL Trim - Flat, Non-Conductive
Polycarbonate Lens
MultiC
are Perfo
rman
ce
MultiC
are Perfo
rman
ce
Plan
30'
20'
Location of MRI Equipment.
Area Excluded from "Procedure" Light Level
Calculation.
6' OC
4' OC6' OC
4' OC
7' OC
|14 Healthcare Lightingpathwaylighting.com 15|
Pathway Solution
IES Recommendations/ASHRAE 90.1-2010 Requirement
Average Illuminance (fc) 23 10
Uniformity (avg:min) 1.39:1 3:1
LPD (W/sq.ft.) 0.58 1.32
Calculations
MRI Suite
Design Considerations Use luminaires made of non-ferrous materials Consider providing lower light levels and placing backlighted art or photomurals
on the ceiling to create a calm environment during diagnostic procedures Avoid excessive glare- proper placement and shielding of fixtures are required
for visual comfort Provide switching and/or dimming to allow for multiple light levels for patient
comfort during medical treatments
MRI Suite
4" MRI Downlight4VLMRI1300 with 4VLMRI Trim
Calculation details :
Luminaire Used : 4VLMRI1300 with 4VLMRI TrimLuminaire Wattage : 24.7
Number of Luminaires : 14
Total Wattage : 345.8
Room Area (sq.ft.) : 600
LLF : 0.8
Reflectances : 80/50/20
Ceiling Height : 10'-0"
Luminaire Mounting Height : 10'-0"
Workplane : 3' AFF
4" MRI Downlight4VLMRI1300 with
4VLMRI Trim
MultiC
are Perfo
rman
ce
MultiC
are Perfo
rman
ce
6" Downlight6VLRL in 3 outputs with 6VLRL2 Trim - Clear Tempered Glass Lens
6" Downlight6VLRL in 2 outputs with 6VLRL2 Trim -
Clear Tempered Glass Lens
Plan
40'
20'
6' OC
2' OC 2' OC
5' OC
7'6" OC
10'
3' OC
5' OC
4'6" OC
Luminaire A
Luminaire B
Luminaire C
|16 Healthcare Lightingpathwaylighting.com 17|
Design Considerations Task lighting- work surface lighting within nurses' stations must be kept
constant day and night to support 24/7 visual tasks Avoid extreme contrasts- careful planning is required to ensure that light levels
are coordinated between corridors and adjacent spaces Avoid excessive glare- proper placement and shielding of fixtures are required
for visual comfort Day/Night cycles- corridors adjacent to patient rooms must have high light
levels during the day and low light levels at night to support patient recovery
Nurses' Station / Corridor
Nurses' Station / Corridor
Calculations
Nurses' Station – Work Surface for In-Patient, Intensive Care or Surgery
Pathway Solution
IES Recommendations/ASHRAE 90.1-2010
Requirement
Average Illuminance (fc) 50 50 (day);
10 or 30 (night)
Uniformity (avg:min; max:min)
1.5:1; 4.7:1
1.5:1 task area; 5:1 for room
LPD (W/sq.ft.) 0.78 0.87
Calculation details :
Luminaire Used : A. 6VLRL2000 with 6VLRL2 Trim - Clear Tempered Glass LensB. 6VLRL1500 with 6VLRL2 Trim - Clear Tempered Glass LensC. 6VLRL1100 with 6VLRL2 Trim - Clear Tempered Glass LensLuminaire Wattage : A. 28.87 B. 21.13 C. 16.3Number of Luminaires : A. 3 B. 1 C. 3Total Wattage : 156.64
Room Area (sq.ft.) : 200
LLF : 0.8
Reflectances : 80/50/20
Ceiling Height : 9'-0"
Luminaire Mounting Height : 9'-0"
Workplane : 2'-6" AFF
Adjacent Corridor
Pathway Solution
IES Recommendations/ASHRAE 90.1-2010 Requirement
Average Illuminance (fc) 19 Avg >_ 0.2 x adjacent Eh req; or >_ to 1 fc min.
Uniformity (avg:min) 1.9:1 3:1
LPD (W/sq.ft.) 0.58 0.89
Calculation details :
Luminaire Used : B. 6VLRL1500 with 6VLRL2 Trim - Clear Tempered Glass LensC. 6VLRL1100 with 6VLRL2 Trim - Clear Tempered Glass LensLuminaire Wattage : B. 21.13 C. 16.3Number of Luminaires : B. 1 C. 13Total Wattage : 233.03
Room Area (sq.ft.) : 400
LLF : 0.8
Reflectances : 80/50/20
Ceiling Height : 9'-0"
Luminaire Mounting Height : 9'-0"
Workplane : Floor
Nurse Station Work Surface
Seatin
g A
rea
MultiC
are Perfo
rman
ce
MultiC
are Perfo
rman
ce
10'
Plan
20'
40'
Plan
14'
4' OC
5' – 8.6" OC
6' OC
1'3"
2'3' – 6" OC
6' OC
2' – 6" OC
PRODUCT PIC HERE
|18 Healthcare Lightingpathwaylighting.com 19|
Design Considerations Consider using daylight whenever possible to provide daytime
circulation lighting Electric lighting used to support circulation at night or when insufficient
daylight is available must be dimmable, to reduce light levels and save energy after nighttime curfews
Atrium
Pathway Solution A
Pathway Solution B
IES Recommendations/ASHRAE 90.1-2010 Requirement
Average Illuminance (fc) 13 14 10 (day); 5 (night)
Uniformity (avg:min) 2.1:1 2:1 4:1
LPD (W/sq.ft.) 0.47 0.47 0.9
Calculation details :
Luminaire Used : A.6VLRL1500 with 6VLRL1 Trim - Clear Polycarbonate LensB.Standard Cylinder C65SLED1500 with 6VLEDMD TrimLuminaire Wattage : A. 21.1 B. 21.1
Number of Luminaires : A. 18 B. 18
Total Wattage : A. 379.8 B. 379.8
Room Area (sq.ft.) : 800
LLF : 0.8
Reflectances : 80/50/20
Ceiling Height : 30'-0"
Luminaire Mounting Height : 30'-0"
Workplane : Floor
Calculations
6" Downlight6VLRL1500 with 6VLRL1 Trim - Clear Polycarbonate Lens
Standard Cylinder C65SLED1500 with 6VLEDMD Trim
Design Considerations Provide vertical illuminance at face height to support common tasks,
including greeting visitors and informal conversations Consider letting the specific facility or area function inform the lighting
design effects and luminaire styling
Pathway Solution
IES Recommendations/ASHRAE 90.1-2010 Requirement
Average Illuminance (fc) 15 15
Uniformity (avg:min) 2.46:1 4:1
LPD (W/sq.ft.) 0.88 1.07
Calculation details :
Luminaire Used : 4VLRL1100 with 4VLRL3 Trim - Frosted LensLuminaire Wattage : 16.3
Number of Luminaires : 7
Total Wattage : 114.1
Room Area (sq.ft.) : 130
LLF : 0.8
Reflectances : 80/50/20
Ceiling Height : 10'-0"
Luminaire Mounting Height : 10'-0"
Workplane : 3'-6" AFF
Calculations
Reception
4" Downlight 4VLRL1100 with
4VLRL3 Trim - Frosted Lens
MultiC
are Perfo
rman
ce
MultiC
are Perfo
rman
ce
Conference Room
Cafeteria
PRODUCT PIC HERE
6" Downllight6VLRL3000 with
6VLRL3 Trim - Frosted Lens
Plan
20'
30'
Plan
40'
40'
2'
8' OC
4'
6' OC2'3'
5' OC
6' OC
5' OC
|20 Healthcare Lightingpathwaylighting.com 21|
Design Considerations Identify the level of formality of the setting and the types of "conferencing"
activities that will be conducted to determine the overall lighting scheme Provide switching and/or dimming to allow for multiple light levels that
support various tasks, including formal presentations, informal meetings and video conferencing
Pathway Solution
IES Recommendations/ASHRAE 90.1-2010 Requirement
Average Illuminance (fc) 38 30
Uniformity (max:min) 1.82:1 5:1
LPD (W/sq.ft.) 1.06 1.23
Calculation details :
Luminaire Used : 4VLRL30003K with 4VLRL1 Trim - Clear Polycarbonate LensLuminaire Wattage : 37.4
Number of Luminaires : 17
Total Wattage : 635.8
Room Area (sq.ft.) : 600
LLF : 0.8
Reflectances : 80/50/20
Ceiling Height : 12'-0"
Luminaire Mounting Height : 12'-0"
Workplane : 2'-6" AFF
Calculations
Design Considerations Consider the use of accent lighting on artwork in the space for visual interest
and to create a more inviting and relaxing space Avoid excessive glare- proper placement and shielding of fixtures are
required for visual comfort
Pathway Solution
IES Recommendations/ASHRAE 90.1-2010 Requirement
Average Illuminance (fc) 31 15
Uniformity (avg:min) 2.31:1 3:1
LPD (W/sq.ft.) 0.76 0.89
Calculation details :
Luminaire Used : 6VLRL3000 with 6VLRL3 Trim - Frosted LensLuminaire Wattage : 38
Number of Luminaires : 32
Total Wattage : 1216
Room Area (sq.ft.) : 1600
LLF : 0.8
Reflectances : 80/50/20
Ceiling Height : 12'-0"
Luminaire Mounting Height : 12'-0"
Workplane : 2'-6" AFF
Calculations
4" Downlight 4VLRL30003K with 4VLRL1 Trim and Clear Polycarbonate Lens
MultiC
are Perfo
rman
ce
MultiC
are Perfo
rman
ce
Reflector/Trim Finish Options Available for all round- and square-aperture luminaires
Glass Options Available for non-lensed downlights only
ESSEX DECO LUNA PARK AVENUE
MIRIAM ICERound
Aperture ICE
ICSquare
Aperture ICE
CYLINDER
Example Catalog Number: Exam Light
|22 Healthcare Lightingpathwaylighting.com 23|
6 SQ LBEX 8 0 3 K D M X / 6 S Q L B E X - A M
Nominal Aperture Size in Inches
Aperture Shape: V= Round, SQ = Square
Specific LED Module: LB = Bridgelux Vero
Rated Lumen Output
Dimming Option
Trim Trim Finish
CCT
SWTPF SSTPF SPWPF SCLPF SBZPF EBZPF
Soft Specular Wheat
Soft Specular Straw
Soft Specular Pewter
Soft Specular Clear
Soft Specular Bronze
Diffused Bronze
SBLPF MWH HAZPF EWTPF ESTPF EPWPF
Soft Specular Black
Matte White Finish
Haze Diffused Wheat
Diffused Straw
Diffused Pewter
Pathway Lighting Products, Inc.P.O. Box 591, Old Saybrook, CT 06475-0591voice: 800.342.0592 or 860.388.6881fax: 800.207.0090 or 860.388.5766email: [email protected]