Functional Description
Electric Drivesand Controls Pneumatics Service
Linear Motion and Assembly TechnologiesHydraulics
Hall Sensor BoxSHL02.1
R911292537Edition 04
Hall Sensor BoxSHL02.1
Functional description
DOK-SUPPL*-SHL********-FK04-EN-P
RS-6bf26e99d40f45140a6846a001b3c723-2-en-US-7
The description of the Hall sensor box contains...● technical data of a Hall sensor box,● notes to handle and mount,● notes to electrical connection
Edition Release Date Notes
DOK-SUPPL*-SHL********-FK01-EN-P 07/2001 First editionDOK-SUPPL*-SHL********-FK02-EN-P 09/2001 Revision / supplementDOK-SUPPL*-SHL********-FK03-EN-P 04/2008 Revision / supplementDOK-SUPPL*-SHL********-FK04-EN-P 07/2008 Revision of the connec‐
tion cables
© 2008 Bosch Rexroth AGCopying this document, giving it to others and the use or communication of thecontents thereof without express authority, are forbidden. Offenders are liablefor the payment of damages. All rights are reserved in the event of the grant ofa patent or the registration of a utility model or design (DIN 34-1).The specified data is for product description purposes only and may not bedeemed to be guaranteed unless expressly confirmed in the contract. All rightsare reserved with respect to the content of this documentation and the availa‐bility of the product.Bosch Rexroth AGBgm.-Dr.-Nebel-Str. 2 ■ 97816 Lohr a. Main, GermanyPhone +49 (0)93 52 / 40-0 ■ Fax +49 (0)93 52 / 40-48 85http://www.boschrexroth.com/Dept. BRC/EDM1(fs)This document has been printed on chlorine-free bleached paper.
Title
Type of Documentation
Document Typecode
Internal File Reference
Purpose of Documentation
Record of Revision
Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Copyright
Validity
Published by
Note
Table of ContentsPage
1 Introduction to the Product............................................................................................. 11.1 General Information................................................................................................................................ 11.2 Schematic Assembly.............................................................................................................................. 21.3 Designation of SHL................................................................................................................................. 21.4 Ordering Information............................................................................................................................... 31.5 About this Documentation....................................................................................................................... 31.6 Your Feedback....................................................................................................................................... 3
2 Technical Information..................................................................................................... 52.1 Data Sheet SHL02.1............................................................................................................................... 52.2 Type Code SHL02.1............................................................................................................................... 52.3 Dimension Sheet SHL02.1..................................................................................................................... 6
3 Application Notes........................................................................................................... 73.1 General Information................................................................................................................................ 73.2 Notes to Define the Assembly Position................................................................................................... 73.2.1 Basic Notes......................................................................................................................................... 73.2.2 Permitted Arrangement....................................................................................................................... 83.2.3 Not Permitted Arrangements............................................................................................................... 93.2.4 Mounting Position at MLFxx0-motors.................................................................................................. 93.3 Definition of the Mounting Positíon....................................................................................................... 103.3.1 Observe the Mounting Conditions..................................................................................................... 103.3.2 Notes for Mounting............................................................................................................................ 113.4 Parameter Adjustment.......................................................................................................................... 123.4.1 P-0-0074 "Encoder Type 1 (Motor Encoder)".................................................................................... 123.4.2 P-0-0508 "Commutation Offset"........................................................................................................ 123.5 Signal Specification for Hall Sensor Boxes........................................................................................... 17
4 Connection Technique................................................................................................. 194.1 Connection Cable on the SHL Box....................................................................................................... 194.2 Encoder Cable SHL ⇒ IndraDrive (with Encoder Card EN1)................................................................ 204.2.1 Encoder Cable IKS4042.................................................................................................................... 204.2.2 Ordering Designation for IKS4042..................................................................................................... 204.3 Encoder Cable SHL ⇒ IndraDrive (with Encoder Card ENS)............................................................... 214.3.1 Encoder Cable RKG0027.................................................................................................................. 214.3.2 Ordering Designation RKG0027........................................................................................................ 214.4 Encoder Cable SHL ⇒ Diax.................................................................................................................. 214.4.1 Encoder Cable IKS4042.................................................................................................................... 214.5 Encoder Cable SHL ⇒ EcoDrive........................................................................................................... 224.5.1 Encoder Cable IKS4374.................................................................................................................... 224.5.2 Ordering Designation IKS4374.......................................................................................................... 22
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG I/II
Table of Contents
Page
5 Service and Support.................................................................................................... 235.1 Helpdesk............................................................................................................................................... 235.2 Service Hotline...................................................................................................................................... 235.3 Addresses............................................................................................................................................. 235.4 Helpful Information................................................................................................................................ 23
Index............................................................................................................................ 25
II/II Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Table of Contents
1 Introduction to the Product1.1 General Information
To drive synchronous motors, an absolute position information regarding polepairs or pole pair width is necessary to recognize the position of the permanentmagnets to the motor windings.
Only in connection with an electrical commutation angle offset,which must be determined at initial start up of a synchronous motor,it is possible for the controller to remember the current with correctphasing to the magnetic field so that the motor can its maximumtorque or maximum force
When using an incremental length measuring system a commutation of theaxes has to result from every step up of the phases of the drive device. Thisresults from an drive-internal procedure. After this, a force processing of themotor is possible.
The commutation is determined automatically during the phasestep up by the SHL-Box. Therefore, no power switch-on (this meansno motor movement) is necessary.
The SHL02.1 replaces the SHL01.1. It is mechanically, and in its connectiontechnique completely compatible.The Hall sensor box SHL02.1 of Rexroth is an optional accessory for drive sys‐tems with incremental measuring systems and synchronous motors, like In‐draDynL or LSF of Rexroth, for example.The SHL box offers special advantages, for example at commutation of linearmotors...● in Gantry arrangement● on vertical axis,● in mechanical safe state,● which are not allowed to be driven during the commutation process for
safety reasons.
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 1/25
Introduction to the Product
1.2 Schematic Assembly
① Control unit② Drive device③ Linear scale④ Secondary part⑤ Primary part⑥ SHL with connection cable⑦ Connection cable for SHL / drive deviceFig.1-1: Schematic assemblyA drive control system with a Hall sensor box preferably consists of...● a Rexroth drive controller with appropriate firmware● a start-up software IndraWorks● a Rexroth synchronous linear motor● a connection cable to connect the SHL onto the drive controller● a lengths measuring system (not in the scope of delivery of Rexroth)● a superior controller● technical documentation about all used products for this system
1.3 Designation of SHLA type plate is fixed outside on the housing on each SHL. An additional typeplate is delivered loosely. Store this type plate on a well accessible place onthe machine.
Fig.1-2: Type plate on the SHL box
2/25 Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Introduction to the Product
1.4 Ordering InformationWhen ordering a Hall sensor box as accessory, the following positions must begiven:
Pos. Product Material number Comment1 SHL 02.1-0xx-S-120 R911321893 2 Connection cable (see fig. 4-2 "SHL connection cable overview" on page 19)
3 DOK-SUPPL*-SHL********-FK0x-DE-P R911306588 German editionDOK-SUPPL*-SHL********-FK0x-EN-P R911292537 English edition
Fig.1-3: Information for ordering
1.5 About this DocumentationThis functional description of the Hall sensor box SHL02.1 is part of the syn‐chronous linear motors developed by Rexroth and describes technical data,product characteristics and gives application notes.For further notes, especially about handling synchronous linear motors and thecorresponding safety notes, see the appropriate documentation of the usedsynchronous linear motor and drive controller.To project planning manual the drive-systems it is possible that you need ad‐ditional documentation referring the used devices. Rexroth provides for theoverall product documentation in the Bosch Rexroth media directory athttp://www.boschrexroth.com/various/utilities/mediadirectory/index.jsp in PDF for‐mat.
1.6 Your FeedbackYour experiences are an essential part of the process of improving both theproduct and the documentation.Please do not hesitate to inform us of any mistakes you detect in this docu‐mentation or of any modifications you might desire. We would appreciate yourfeedback.Please send your remarks to:Bosch Rexroth Electric Drives and Controls GmbHDep. BRC/EDM1Buergermeister-Dr.-Nebel-Strasse 297816 Lohr, GermanyFax +49 (0) 93 52 / 40-43 80
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 3/25
Introduction to the Product
Additional Documentation
Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
2 Technical Information2.1 Data Sheet SHL02.1
Description Symbol Unit SHL02.1Operating voltage U VDC 7...12
Max. current consumption I mA 250Permissible ambient temperature TA °C 0...45
Degree of protection IP65Length of the connection cable m 2Mass (with cable and coupling) m kg 0,4
Fig.2-1: Data Sheet SHL02.1
2.2 Type Code SHL02.1
Fig.2-2: Type Code SHL02.1
● The selecting pole width must comply with the pole width ofthe referring linear motor.
● Generally, the SHL02.1 is delivered with a 2 m long connectioncable including coupling.
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 5/25
Technical Information
2.3 Dimension Sheet SHL02.1
Fig.2-3: Dimension sheet SHL02.1
6/25 Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Technical Information
3 Application Notes3.1 General Information
WARNING
Injuries and/or damages due to errors in trigger motors and moving el‐ements!● The Hall sensor box is part of a drive system which consists of a drive
controller and a motor at the minimum. Therefore, heed all documentationof all used products in this system. See chapter"Additional Documenta‐tion" on page 3,
● Absolutely heed all safety notes in the referring documentation.
The assembly and start up of the SHL must be done only by skilled personnel.Skilled personnel are persons, for the purpose of safety-related notes, that havethe right to start up devices, systems and circuits according to the standards ofthe safety technique.The SHL may only be operated under consideration of the notes in this func‐tional description and in connection with permitted components by Rexroth.
3.2 Notes to Define the Assembly Position3.2.1 Basic Notes
The SHL must be positioned in a defined distance to the front end of a syn‐chronous linear motor.
① Secondary part② Primary part③ Hall sensor box SHL④ Active magnet breadth⑤ Cable outputDimension "d" Assembly distanceDimension "e" Assembly distance (only in connection with MLFxx0)Fig.3-1: Possible configuration of the SHL Positioning the SHL must be done according to the following criteria:● Same position of the cable output of the SHL and the primary part. There‐
fore, also note the design under fig. 3-2 "Permitted mounting position" onpage 8,
● The SHL must always be mounted completely over the active breadth ofthe secondary partException:
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 7/25
Application Notes
Heed the additional dimension "e" when mounting the Hall sensor box inconnection with MLF motors. For further information see chapter 3.2.4 "Mounting Position at MLFxx0-motors" on page 9,
● The individual assembly distance (dimension "d") of the SHL box must bedetermined for each machine after mounting.
3.2.2 Permitted ArrangementThere are two different possibilities to arrange the Hall sensor box within themachine or beside the primary part:● Position 1 ⇒ SHL on the front end of the primary part with the cable output● Position 2 ⇒ SHL in opposite of the cable output on the primary part
Precondition of each mounting position is that the cable output ofthe SHL is according to the cable output of the primary part.
The following figure makes the relation clear:
Fig.3-2: Permitted mounting position
8/25 Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Application Notes
3.2.3 Not Permitted Arrangements
Fig.3-3: Not permitted mounting position● Position 3 ⇒ cable output of the SHL in reverse direction to the cable output
of the primary part● Position 4 ⇒ SHL with correct cable output, but partly mounted outside of
the active breadth of the secondary part
3.2.4 Mounting Position at MLFxx0-motorsIs a Hall sensor box used in connection with motors in design MLFxx0, it isnecessary to position the box in certain areas over the active breadth of thesecondary part. For this motor design, a complete covering of the sensors withthe magnets of the secondary part can be made sure only in specified areas.Subsequently you can find an overview about the permitted areas (dimension"e") over the secondary part MSLxx0 in accordance to the motor frame size.
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 9/25
Application Notes
d Assembly dimensione Assembly dimension (only in connection with MLFxx0)① Example Dimension "e" ⇒ negative area② Example Dimension "e" ⇒ positive areaFig.3-4: Schematic diagram dimension "e"
Secondary part design Dimension "e" [mm]MLS040 -2.5 ... -5.5MLS070 +3.5 ... +26.5
MLS100-2.5 ... +12.5
+47.5 ... +62.5
MLS140+3.5 ... +26.5
+73.5 ... +96.5
MLS200
-2.5 ... +12.5+47.5 ... +62.5
+97.5 ... +112.5+147.5 ... +162.5
MLS300
-2.5 ... +12.5+47.5 ... +62.5
+97.5 ... +112.5+147.5 ... +162.5+197.5 ... +212.5+247.5 ... +262.5
Fig.3-5: Table dimension "e" in connection with MLFxx0-motors
3.3 Definition of the Mounting Positíon3.3.1 Observe the Mounting Conditions
The exact mounting position of the SHL into the machine is influenced by dif‐ferent factors. This factors have to be determined and noticed by the user whenmounting the motor.
10/25 Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Application Notes
① Primary part② Secondary part③ MachineL3 Air gap between SHL and secondary partDimension "d" Assembly distanceDimension "e" Assembly distance (only in connection with MLFxx0)Fig.3-6: Mounting position of the SHL
3.3.2 Notes for Mounting1. The air gap L3 between SHL and the secondary part must lie in a defined
area to reach an optimal sensor signal strength.● L3 = 12.4 mm ± 0.5 mm
2. It is independent whether the SHL is mounted on the left or right side ofthe primary part on the machine, the Mounting distance "d" always refersto the specified reference holes.Therefore, note the follwing figure and fig. 3-6 "Mounting position of theSHL" on page 11,
① Reference holes onto the primary part② Reference holes on the SHL box
Fig.3-7: Reference holes for the mounting distance "d"3. You can find detailed information about position and dimension of both
mounting holes (threades hole M6) in the dimension sheet of the SHL box.
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 11/25
Application Notes
The M6 fastening screws may be tightened with a torque moment of 4.3...4.8 Nm.Coat the fastening screws with a screw locking varnish, e.g. Loctite 243before screwing in.
4. The dimension of the mounting distance "d" significantly influences theparameter P-0-508 (commutation offset).Therefore, note the following notes regarding parameter adjustment.
3.4 Parameter Adjustment3.4.1 P-0-0074 "Encoder Type 1 (Motor Encoder)"
In accordance to the used drive controller, assign the parameter P-0-0074 avalue from the following table:
Control device Encoder card P-0-0074
IndraDrivefrom firmware version
MPx05
EN1 14
ENS 15
IndraDrivefrom firmware version
MPx04
EN1 14
ENS 15
DIAX04 --- 14
ECODRIVE --- 14
Fig.3-8: SHL parameter values for P-0-0074
3.4.2 P-0-0508 "Commutation Offset"The parameter P-0-0508 creates a reference from the electric field of the pri‐mary part to the magnetic field of the secondary part. This is called identificationof pole position or commutation adjustment.For further notes regarding commutation adjustment refer to the particular mo‐tor project planning.The evaluation of the parameter P-0-0508 needs the following product specificcharacteristics:
Designation Value Note
Base value of P-0-0508 1024 1024 = 1 round (360°) ofthe electric field
Pole width LP
MLFxx0 37.5 mm
Pole width of the motorMLFxx2 30.0 mm
LSF 37.5 mm
PK-constant depends on the mo‐tor heed the following table
Fig.3-9: Determine the parameter P-0-0508
12/25 Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Application Notes
Notes for determine the parameterP-0-0508
PK-constant for MLFxx0 linear motors
Primary part design PK-constantMLP040A-_S 813MLP040A-_S 540MLP040B-_S 813MLP040B-_T 540MLP070A-_S 813MLP070A-_T 540MLP070B-_S 130MLP070B-_T 881MLP070C-_S 813MLP070C-_T 540MLP100A-_S 130MLP100A-_T 881MLP100B-_S 813MLP100B-_T 540MLP100C-_S 130MLP100C-_T 881MLP140A-_S 130MLP140A-_T 881MLP140B-_S 813MLP140B-_T 540MLP140C-_S 130MLP140C-_T 881MLP200A-_S 130MLP200A-_T 881MLP200B-_S 813MLP200B-_T 540MLP200C-_S 130MLP200C-_T 881MLP200D-_S 813MLP200D_T 540MLP300A-_S 130MLP300A-_T 881MLP300B-_S 813MLP300B-_T 540MLP300C-_S 130MLP300C-_T 881MLP300Z_T 540
Fig.3-10: PK constant to determine the parameter P-0-0508 for MLFxx0 linearmotors
PK-constant for MLFxx2 linear motors
Secondary part design PK-constantin preparation
Fig.3-11: PK constant to determine the parameter P-0-0508 for MLFxx2 linearmotors
PK-constant for linear motors
Secondary part design PK-constantLSP040K-RU2-_ _ 713LSP040L-RU2-_ _ 542LSP080K-RU2-_ _ 627
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 13/25
Application Notes
Secondary part design PK-constantLSP080L-RU2-_ _ 969LSP080M-RU2-_ _ 627LSP080N-RU2-_ _ 969LSP080S-RU2-_ _ 600LSP080T-RU2-_ _ 600LSP080U-RU2-_ _ 600LSP080V-RU2-_ _ 600LSP120K-RU2-_ _ 627LSP120L-RU2-_ _ 969LSP120M-RU2-_ _ 627LSP120N-RU2-_ _ 969LSP120S-RU2-_ _ 600LSP120T-RU2-_ _ 600LSP120U-RU2-_ _ 600LSP120V-RU2-_ _ 600LSP140L-RU2-_ _ 713LSP140N-RU2-_ _ 201LSP160K-RU2-_ _ 627LSP160L-RU2-_ _ 286LSP160M-RU2-_ _ 627LSP160N-RU2-_ _ 286LSP160S-RU2-_ _ 600LSP160T-RU2-_ _ 600LSP160U-RU2-_ _ 600LSP160V-RU2-_ _ 600LSP200K-RU2-_ _ 627LSP200L-RU2-_ _ 286LSP200M-RU2-_ _ 627LSP200N-RU2-_ _ 286LSP200S-RU2-_ _ 600LSP200T-RU2-_ _ 600LSP200U-RU2-_ _ 600LSP200V-RU2-_ _ 600LSP240K-RU2-_ _ 627LSP240L-RU2-_ _ 969LSP240M-RU2-_ _ 627LSP240N-RU2-_ _ 969LSP240S-RU2-_ _ 600LSP240T-RU2-_ _ 600LSP240U-RU2-_ _ 600LSP240V-RU2-_ _ 600
Fig.3-12: PK constant to determine the parameter P-0-0508 for linear motors
14/25 Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Application Notes
Mounting position of the SHL on the primary part side with the cable output.
d Assembly distanceFig.3-13: Mounting position of the SHL on the primary part side with cable output
P0508 Parameter P-0-0508PK Motor specific constant to determine the parameter P-0-05081024 Base value of P-0-0508LP Pole width of the motord Measured mounting distanceFig.3-14: Determination of the P-0-0508 parameter (for mounting position 1)Example:● PK constant of the primary part LSP080K-RU2-_ _ = 627
(see fig. 3-10 "PK constant to determine the parameter P-0-0508 forMLFxx0 linear motors" on page 13)
● Measured mounting distance d= 146 mm● Pole width TP of the motor = 37.5 mm
(see fig. 3-9 "Determine the parameter P-0-0508" on page 12) Calculation:P0508 = 627 - [1.024 / (2 • 37.5 mm)] • 146 mmP0508 = -1,366.4
The parameter P-0-508 can only be allocated with a whole number(rounded without comma) between 0 and + 1,024,Is the determined value not within this range of the aforementionedexample, add or subtract the value of 1,024 until a permissible pa‐rameter value within the specified range is reached,
P0508 = -1,366.4 + 1,024 + 1,024P0508 = 681.6 ≙ 682⇒ Result: P-0-0508 = 682
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 15/25
Application Notes
Example to determine the mountingposition 1
Mounting position of the SHL on the primary part side in opposite of the cableoutput.
d Assembly distanceFig.3-15: Mounting position of the SHL on the primary part side in opposite of the
cable output.
P0508 Parameter P-0-0508PK Motor specific constant to determine the parameter P-0-05081024 Base value of P-0-0508LP Pole width of the motord Measured mounting distanceFig.3-16: Determination of the P-0-0508 parameter (for mounting position 2)Example:● PK constant of the primary part LSP0120K-RU2-_ _ = 969
(see fig. 3-12 "PK constant to determine the parameter P-0-0508 for linearmotors" on page 13)
● Measured mounting distance d= 529.5 mm● Pole width TP of the motor = 37.5 mm
(see fig. 3-9 "Determine the parameter P-0-0508" on page 12) Calculation:P0508 = 969 + [1,024 / (2 • 37.5 mm)] • 529.5 mmP0508 = 8,198.4
The parameter P-0-508 can only be allocated with a whole number(rounded without comma) between 0 and + 1,024,Is the determined value not within this range of the aforementionedexample, add or subtract the value of 1,024 until a permissible pa‐rameter value within the specified range is reached,
P0508 = 8,198.4 - 1,024 - 1,024 - 1,024 - 1,024 - 1,024 - 1,024 - 1,024 - 1,024P0508 = 6,4 ≙ 6⇒ Result: P-0-0508 = 6
16/25 Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Application Notes
Example to determine the mountingposition 2
3.5 Signal Specification for Hall Sensor BoxesThe following figure shows the form of the output signals of a moving Hall sensorbox.
Fig.3-17: Specification of the Hall sensor signalsThe output signals only then consist to this, if the SHL box and the primary partare moved as shown.
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 17/25
Application Notes
Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
4 Connection Technique4.1 Connection Cable on the SHL Box
Each Hall sensor box has a 2 m long connection cable for electrical connection.
Fig.4-1: Connection cable on the Hall sensor boxThe connection cable of the Hall sensor box must be connected via the con‐nector INS0716 onto an encoder cable on the used control device (see fig.1-1 "Schematic assembly" on page 2).Depending on the used control device, the following connection cable is neededto connect the Hall sensor box:
Control device Encoder card Encoder cables Slot
IndraDrivefrom firmware versionMPx05
EN1 IKS4042alternativelyX4, X8 or X10
ENS RKG0027 X8
IndraDrivefrom firmware versionMPx04
EN1 IKS4042 X8
ENS RKG0027 X8
Diax --- IKS4042 X8
EcoDrive --- IKS4374 X8
Fig.4-2: SHL connection cable overview
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 19/25
Connection Technique
4.2 Encoder Cable SHL ⇒ IndraDrive (with Encoder Card EN1)4.2.1 Encoder Cable IKS4042IKS4042
Encoder connec‐tor
Bulk cable Drive device con‐nector
INS0713/C01 INK0448 INS0760/C01
Connection plan
© Bosch Rexroth AG, 2007
Fig.4-3: Single parts of IKS4042
4.2.2 Ordering Designation for IKS4042Ordering type Material number
IKS4042 / xxx,x R911290940xxx.x = space for detailed cable length in m (max. cable length 50 m)Fig.4-4: Ordering designation IKS4042
20/25 Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Connection Technique
4.3 Encoder Cable SHL ⇒ IndraDrive (with Encoder Card ENS)4.3.1 Encoder Cable RKG0027RKG0027
Encoder connec‐tor
Bulk cable Drive device con‐nector
INS0713/C01 INK0448 INS0760/C01
Connection plan
© Bosch Rexroth AG, 2007
Fig.4-5: Single parts RKG0027
4.3.2 Ordering Designation RKG0027Ordering type Material number
RKG0027 / xxx.x R911321429xxx.x = space for detailed cable length in m (max. cable length 50 m)Fig.4-6: Ordering designation RKG0027
4.4 Encoder Cable SHL ⇒ Diax4.4.1 Encoder Cable IKS4042
Refer to chapter 4.2.1 "Encoder Cable IKS4042" on page 20.
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 21/25
Connection Technique
4.5 Encoder Cable SHL ⇒ EcoDrive4.5.1 Encoder Cable IKS4374IKS4374
Encoder Connec‐tion
Bulk cable Drive device con‐nector
INS0713/C01 INK0448 INS0760/C01
Connection plan
© Bosch Rexroth AG, 2007
Fig.4-7: Single parts of IKS4374
4.5.2 Ordering Designation IKS4374Ordering type Material number
IKS4374 / xxx.x R911277697xxx.x = space for detailed cable length in m (max. cable length 50 m)Fig.4-8: Ordering designation IKS4374
22/25 Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Connection Technique
5 Service and Support5.1 Helpdesk
Our service helpdesk at our headquarters in Lohr, Germany, will assist you withall kinds of inquiries.Contact us:● By phone through the Service Call Entry Center
Monday to Friday: 7:00 am - 6:00 pm Central European Time+49 (0) 9352 40 50 60
● By fax+49 (0) 9352 40 49 41
● By e-mail: [email protected]
5.2 Service HotlineOut of helpdesk hours please contact our German service department directly:+49 (0) 171 333 88 26or+49 (0) 172 660 04 06Hotline numbers for other countries can be found in the addresses of eachregion on the Internet (see below).
5.3 AddressesFor the current addresses of our sales and service offices, seehttp://www.boschrexroth.comOn this website you will find additional notes regarding service, maintenance(e.g. delivery addresses) and training.Outside Germany please contact our sales/service office in your area first.
5.4 Helpful InformationFor quick and efficient help please have the following information ready:● Detailed description of the fault and the circumstances● Information on the type plate of the affected products, especially type co‐
des and serial numbers● Your phone and fax numbers and e-mail address, so we can contact you
in case of questions
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 23/25
Service and Support
Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
IndexAAddresses 23Air gap 11
DDesignation of the SHL-Box 2Determination of the P-0-0508 parameter (formounting position 1) 15Determination of the P-0-0508 parameter (formounting position 2) 16Determine the parameter P-0-0508 12
EEncoder cable IKS4042 20, 21Encoder cable IKS4374 22Encoder cable RKG0027 21Encoder card EN1 20Encoder card EN1S 21
HHelpdesk 23
IIKS4042 20
IKS4374 22
MMounting distance 11
OOrdering Information 3
PParameter values for P-0-0074 12pole width 5Positioning the SHL 7
Definition 10Not permitted mounting position 9Permitted mounting position 8
RRKG0027 21
SSchematic assembly 2Service hotline 23Specification of the Hall sensor signals 17
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG 25/25
Index
Bosch Rexroth AG | Electric Drivesand Controls
Hall Sensor Box | Functional description
Notes
Functional description | Hall Sensor Box Electric Drivesand Controls
| Bosch Rexroth AG
Printed in GermanyDOK-SUPPL*-SHL********-FK04-EN-PR911292537