Upload
vikas-razdan
View
217
Download
0
Embed Size (px)
Citation preview
8/12/2019 GTP.xls
1/152
A.
132 kV 33 kV
1 Manufacturers Name and Country
2 Manufacturers type designation
3 Applicable Technical Standards
4 (a) Type of circuit breaker
(b) Type of tank (live/dead)
5 Rated frequency (Hz)
6 Number of poles (Nos.)
7 Whether 3 pole or single pole unit
8 No. of breaks per pole
9 Type -Outdoor
10 Rated continuous current at designtemperature of 38 deg. C
(Amp)
11 Rated short circuit breaking current
a) RMS value of AC component (kA)
b) Percentage DC component (%)
c) Asymmetrical breaking current at
highest system voltage
(kA)
d) Is it possible to increase the rupturing
capacity at a later date
(Yes/No)
12 Short time current rating for 1 sec. (kA)
13 Rated operating duty cycle14 Rated short circuit making current (kA peak)
15 First pole to clear factor
16 Rated characteristics for short time
faults and rated breaking capacity
(kA peak)
17 Rated line charging breaking current
with temporary over voltage upto 1.4
p.u.
(kA)
18 Rated out of phase breaking current
and corresponding transient recovery
voltage
(kA, kV)
19 Rated small inductive breaking current
with corresponding switching over
voltage
(Amp, p.u)
Sl.
No.Description Unit
Guaranteed Particulars
CIRCUIT BREAKERS
Section - IX : Guaranteed & other Technical Particulars
-1-
8/12/2019 GTP.xls
2/152
132 kV 33 kV
Sl.
No.Description Unit
Guaranteed Particulars
20 Rated cable charging breaking current
and corresponding over voltages
recorded during test
(Amp, p.u)
21 (a) Maximum period between first
contact and last contact in a pole
(b) Maximum pole descrepancy
22 Rated (single) capacitor bank breaking
current and corresponding over
voltages recorded during test
(Amp, p.u)
23 Data on re-striking voltage for terminal
faults
a) Amplitude factor
100% capacity
60% capacity
30% capacity
10% capacity
b) Phase factor
100% capacity
60% capacity
30% capacity
10% capacity
c) Rate of rise of re-striking voltage
100% capacity
60% capacity
30% capacity
10% capacity
d) Transient recovery voltage
100% capacity (kV peak)
60% capacity (kV peak)
30% capacity (kV peak)
10% capacity (kV peak)
24 a) Is circuit breaker re-strike free under
all conditions of operation.
(Yes/No)
b) Means adopted if any to check thevoltage rise
25 Max. arcing time under any duty
condition with limiting conditions of
voltage and pressure
(ms)
Section - IX : Guaranteed & other Technical Particulars
-2-
8/12/2019 GTP.xls
3/152
132 kV 33 kV
Sl.
No.Description Unit
Guaranteed Particulars
26 Maximum total break time under any
duty condition for any current up to
rated breaking current with limiting
conditions of voltage and pressure
(ms)
27 Maximum closing time (ms)
28 Minimum opening time under any duty
condition with limiting voltage and
pressure
(ms)
29 Maximum close open time under any
condition with limiting voltage and
pressure
(ms)
30 Minimum re-closing time at rated
interrupting capacity from instant of
trip coil energisation
(ms)
31 Minimum dead time fora) Three phase reclosing (ms)
b) Single phase reclosing (ms)
c) Limits of adjustment of dead time for
three phase reclosing
(ms)
32 Difference in the instants of closing
opening of contacts at rated voltage
and pressure
a) Within a pole (ms)
b) Between poles (ms)
33 Type of device, if any, used to obtain
uniform voltage distribution betweencontacts
34 Maximum temperature rise for
a) Main contacts over ambient
temperature at site
(Deg.C)
b) Terminals to be connected to the
external conductor
(Deg.C)
35 One minute power frequency
withstand test voltage for complete
a) Between line terminal and ground
objects with circuit breaker contacts
closed
(kV rms)
b) Between terminals with breaker
contacts open
(kV rms)
36 1.2/50 microsecond lightning impulse
withstand test voltage for complete
circuit breaker
a) Between line terminal and ground with
circuit breaker contacts closed
(kV peak)
Section - IX : Guaranteed & other Technical Particulars
-3-
8/12/2019 GTP.xls
4/152
132 kV 33 kV
Sl.
No.Description Unit
Guaranteed Particulars
b) Across terminals with circuit breaker
contacts open
- one terminal lightning impulse (kV peak)
- opposite terminal power frequency (kV peak)37 Corona extinction voltage (kV rms)
38 i) Radio Interference Voltage at
a) 0.5 MHz (mV)
b) 1.0 MHz (mV)
c) 1.5 MHz (mV)
d) 2.0 MHz (mV)
ii) Partial discharge level (mC)
39 Whether the circuit breaker is fixed
trip or trip free
Yes/No
40 a) Rated voltage of closing coils (Volts)
b) Range of pick up value (Volts)
41 a) Rated voltage of tripping coil (Volts)
b) Range of pick up value (Volts)
42 Normal power consumption at rated
voltage for
a) Trip coil (Watts)
b) Closing coil (Watts)
43 Number of trip coils (Nos.)
44 Type of main contact
45 Whether arcing contact provided (Yes/No)
46 Material of
a) Main contact
b) Arcing contact
c) Whether contacts silver plated (Yes/No)
d) Minimum thickness of silver plating (mm)
e) Contact pressure of main contact (kg/sq. cm)
47 Number of auxiliary contacts per pole
provided for Purchasers use.
a) NO (Nos.)
b) NC (Nos.)
48 Rated voltage of auxiliary contacts (Volts)
49 Current capacity of auxiliary contacts
a) Continuous (Amp)
b) Breaking (Amp)
50 Whether auxiliary contacts silver
plated
(Yes/No)
51 SF6 circuit breakers
Section - IX : Guaranteed & other Technical Particulars
-4-
8/12/2019 GTP.xls
5/152
132 kV 33 kV
Sl.
No.Description Unit
Guaranteed Particulars
(a) Quantity of SF6 gas required for
each pole of circuit breaker
(kg)
(b) Guaranteed maximum leakage rate
of SF6 gas per year
(%)
(c) Rated pressure of SF6 in opeerating
chamber
(kg/sq. cm)
(d) SF6 density monitor provided (Yes/No)
(e) Limits of pressure of SF6 gas at
which breaker operate correctly
(kg/sq. cm)
52 Number of operations after which SF6
gas replacement is necessary
a) At full rupturing capacity (Nos.)
b) At 50% of rated rupturing capacity (Nos.)
c) At 10% of rated rupturing capacity (Nos.)
d) At rated current (Nos.)53 Number of operations after which
main and auxiliary contacts
replacement is necessary.
a) At full rupturing capacity (Nos.)
b) At 50% of rated rupturing capacity (Nos.)
c) At 10% of rated rupturing capacity (Nos.)
d) At rated current (Nos.)
54 Number of operations at rated current
after which routine inspection /
maintenance of breaker is necessary.
(Nos.)
55 Number of operations at full rupturingcapacity after which routine
inspection/maintenance of circuit
breaker is necessary.
(Nos.)
56 Parameters of SF6 gas required for
initial filling and satisfactory operation
a) Density (kg/sq. cm)
b) Dielectric strength (kV/mm)
c) Acidity (ppm)
d) Water content (ppm)
e) Oil content (ppm)
f) Condensation temperature (Deg. C)
g) Resistivity (Ohm-m)
57 Support insulators column/units
a) Make and type
b) Numbers per pole (Nos.)
c) Weight (Kg)
Section - IX : Guaranteed & other Technical Particulars
-5-
8/12/2019 GTP.xls
6/152
132 kV 33 kV
Sl.
No.Description Unit
Guaranteed Particulars
d) Transport dimensions (mm x mm xmm)
e) One minute power frequency
withstand voltage
(kV rms)
f) Lightning impulse withstand voltage (kV peak)
g) Corona extinction voltage (kV rms)
h) Creepage distance (mm)
i) Permissible safe cantilever strength (Kg)
j) Insulation class
k) Flash over voltage (kV)
58 Type of operating mechanism for
a) Closing
b) Opening
59 Rated pressure and limits of pressure
of operating mechanism in case ofpneumatic and hydraulic mechanism
(kg/sq. cm)
60 Pneumatic operating mechanism
a) Rated operating pressure (kg/sq. cm)
b) Range of pressure for
i) Closing (kg/sq. cm)
ii) Opening (kg/sq. cm)
c) Air consumption at rated pressure for
i) Closing (m3)
ii) Opening (m3)
iii) Close - Open (m3)
d) Number and capacity of local airreceiver
(m3)
e) Time required for filling the air
receiver to its rated pressure from
atmospheric pressure
(minutes)
f) Design pressure of air receiver (kg/cm2 )
g) Number of closing opening operations
possible without charging the air
receiver
(Nos.)
h) Arrangement provided for preventing
the operation of breaker with
insufficient air pressurei) Compressor
i) Make and type
ii) Number of compression stages (Nos.)
iii) Compression pressure (kg/sq. cm )
Section - IX : Guaranteed & other Technical Particulars
-6-
8/12/2019 GTP.xls
7/152
132 kV 33 kV
Sl.
No.Description Unit
Guaranteed Particulars
iv) Whether compressor is provided
with its own filter. If so give type and
make
(Yes/No)
v) Effectively delivered air in litersper hr. at atmospheric pressure.
(Ltr/hr)
j) Compressed air piping
i) Material
ii) Inner & outer diameter (mm, mm)
iii) Working pressure (kg/sq. cm )
61 Spring charged mechanism
a) Name of Manufacturer
b) Rating of motor (Volts)
c) Time required for charging the closingspring
(Sec)
d) Number of CO operation possible after
failure of auxiliary supply
(Nos.)
e) Whether indication for spring charged
condition provided in central control
cabinet.
(Yes/No)
62 Hydraulic operating mechanism
a) Rated pressure of oil in operating
cylinder
(kg/sq. cm )
b) Limits of operating pressure (kg/sq. cm )
c) Specification of oil and quantityrequired per breaker
(litres)
d) Number of CO operation possible after
loss of hydraulic pressure.
(Nos.)
e) Details of arrangement to prevent
change of position of breaker in the
event of loss of hydraulic pressure.
f) Details of motoring arrangement for
hydraulic pressure
g) Details of hand pump set provided for
emergency operation
63 Control cabineta) Manufacturers Name
b) Thickness of sheet steel (mm)
c) Degree of protection provided
d) Colour of finish paint
i) Outside
Section - IX : Guaranteed & other Technical Particulars
-7-
8/12/2019 GTP.xls
8/152
132 kV 33 kV
Sl.
No.Description Unit
Guaranteed Particulars
ii) Inside
e) Control wiring
i) Rated voltage (Volts)
ii) Size (Sq. mm)
f) Terminal Block
i) Make
ii) Current rating (Amp)
64 Terminal clamps and connector
a) Manufacturers Name
b) Applicable standard
c) Material
i) Clamp body
ii) Bolts and nuts
iii) Spring washer
iv) Liner if any
d) Rated current (Amp)
e) i) Rated terminal load (Kg orN)
ii) Factor of Safety
f) Radio interference voltage (mV)
g) Corona extinction voltage (kV rms)
h) Maximum allowable span for
aluminum tube of 114.2 mm outer
diameter and 97.18 mm inside
diameter on equipment terminal padwith rated fault current and 7 m and
(m)
65 Over all dimensions
a) Height (mm)
b) Width (mm)
c) Length (mm)
66 Clearances
a) Between poles (mm)
b) Between live part and earth (mm)
67 Weight of
a) Each pole (Kg)b) Complete Breaker for foundation (Kg)
69 Impact loading on foundation design
70 Noise level
a) At base (dB)
b) At 50 m distance from base (dB)
Section - IX : Guaranteed & other Technical Particulars
-8-
8/12/2019 GTP.xls
9/152
132 kV 33 kV
Sl.
No.Description Unit
Guaranteed Particulars
71 Seismic level for which breaker is
designed
72 Compliance to technical specification
w.r.t. parameters specified for(a) Control cabinet Yes/No
(b) Bushing/support insulator Yes/No
(c) Terminal connector Yes/No
(d) SF6 Gas Yes/No
72 Enclosures
Whether the following are enclosed:
i) Type test reports for mainequipment and auxiliaries
(Yes/No)
ii) Drawings as per specification (Yes/No)
iii) Technical literature for circuit
breaker, SF6 gas, support insulators
and operating mechanism
(Yes/No)
Section - IX : Guaranteed & other Technical Particulars
-9-
8/12/2019 GTP.xls
10/152
8/12/2019 GTP.xls
11/152
3 /2/1 Pole
Guaranteed ParticularsSl.
No.Description Unit
17 Rated mechanical terminal loads for
horizontal break isolator
a) Longitudinal (N)
b) Transverse (N)
18 Total operating time of Isolator &
earth switch
a) Opening time (Sec)
b) Closing time (Sec)
20 Dielectric withstand capacity of
completely assembled isolator/earth
switch
21 Main contacts (fixed and moving)
a) Type
b) Material
c) Whether contacts are silver plated (Yes/No)
d) Thickness of silver coating(Microns)
e) Contact area (Sq. mm)
f) Contact pressure (kg/sq. cm)
g) Max. Current density under normal
current carrying capacity
(A/sq. cm)
h) Number of operations which the
isolator can make without
deterioration of contacts.
(Nos.)
22 Auxiliary contacts
a) Isolator
i) Total number of spare contacts
provided for purchasers use
a) NO (Nos.)
b) NC (Nos.)
ii) Rated voltage (Volts)
iii) Rated continuous current (Amp)
iv) Rated breaking current (Amp)
b) Earth Switch
i) Total number of spare contacts
provided for Purchasers use
a) NO (Nos.)
b) NC (Nos.)
ii) Rated voltage (Volts)
iii) Rated continuous current (Amp)
iv) Rated breaking current (Amp)
c) Whether arcing contacts provided and
if so give type and material used.
(Yes/No)
23 Insulators
Section - IX : Guaranteed & other Technical Particulars
-17-
8/12/2019 GTP.xls
12/152
3 /2/1 Pole
Guaranteed ParticularsSl.
No.Description Unit
a) Make
b) Type (solid core)
c) Applicable Standard
d) Number of insulator stacks per pole (Nos.)
e) Number of insulators per stack (Nos.)
f) 1 minute power frequency withstand
voltage
(kV rms)
g) Lightning impulse withstand voltage (kV peak)
h) Visible corona extinction voltage (kV rms)
i) Creepage distance (mm)
j) Weight of each post insulator per (Kg)
k) Tensile strength (Kg)
l) Compressive strength (Kg)
m) Torsional strength (Kg-m)
n) Cantilever strength (Kg)
o) Bolt circle dia (mm)
24 Minimum phase to phase clearance (mm)
25 a) Minimum phase to ground (mm)
b) Minimum distance between phases
when isolator is open
(mm)
26 Types of bearings
27 Locations of bearings
28 Type of lubricant for bearings
29 Terminal Clamps & Connectors
a) Manufacturers name
b) Applicable standard
c) Materiali) Clamp body
ii) Bolts and nuts
iii) Spring washer
iv) Liners if any
d) Rated current (Amp)
e) Rated terminal load (Kg)
f) Weight of clamp complete with
hardware
(Kg)
g) Radio Interference Voltage (mV)
h) Corona extinction voltage (kV rms)
i) Maximum allowable span foraluminum tube with applicable size
with rated fault current and applicable
phase to phase spacing for
(m)
30 Operating Mechanism
a) Type of operating mechanism
b) Name of manufacturer
Section - IX : Guaranteed & other Technical Particulars
-18-
8/12/2019 GTP.xls
13/152
3 /2/1 Pole
Guaranteed ParticularsSl.
No.Description Unit
c) Whether inter-pole cabling included
in scope of supply
(Yes/No)
d) Whether separate operating
mechanism provided for operation of
isolator pole and earthing switch.
(Yes/No)
e) Electrical operation
i) Motor type (AC/DC)
ii) Applicable standard
iii) Rated voltage and current (V, A)
iv) Type of enclosure and method of
cooling
v) Power required for closing and
opening operation
(Watts)
vi) Running time of motor for
closing and opening operation
(Sec)
vii) Control supply for motor control
center
(Volts)
f) Type of manual operating mechanism
for isolator pole
g) Force required to operate manual
operating mechanism
(Kg)
h) Whether padlocking included as per
the specification
(Yes/No)
i) Type of manual device for Earthing
Switch
j) Force required to operate manual
device for earthing switch
(Kg)
31 Interlocking
a) Details of mechanical interlock
between isolator and earth switch
(Yes/No)
b) Details of electrical interlock for
isolator and earth switch enclosed
(Yes/No)
c) Details of electrical interlock
provided to satisfy relevant clause of
Section-Major Substation Equipment.
(Yes/No)
d) Details of electrical scheme to provide
remote alarm for pole discrepancy.
(Yes/No)
e) Details of electrical interlock to bring
back all three poles to open position
in case any pole fails to close withinspecified time
(Yes/No)
f) Details of provisions to cut off supply
to the motor during manual operation
and provision for declutching the
(Yes/No)
Section - IX : Guaranteed & other Technical Particulars
-19-
8/12/2019 GTP.xls
14/152
3 /2/1 Pole
Guaranteed ParticularsSl.
No.Description Unit
g) Arrangement provided to prevent
electrical or manual operation unless
interlock conditions are satisfied.
(Yes/No)
32 Control Cabinets / Marshalling box
a) Manufacturers name
b) Thickness of sheet (mm)
c) Degree of protection provided
d) Colour of finish paint
i) Outside
ii) Inside
e) Control wiring
i) Voltage rating (Volts)
ii) Size and material of conductor (Sq. mm /SWG)
f) Terminal block
i) Make
ii) Current rating (Amp)g) Space heater rating at 240 volts (Watts)
h) Whether all cabling for wiring out
contacts to control cabinet included in
scope of supply
(Yes/No)
33 Size and Weight
a) Weight of each pole (Kg)
b) Space requirement i.e. length. (mm)
c) Height of 3 phase isolator without
earth switch.
(mm)
d) Dimension of the isolators
i) without earthing switch (mm x mm xmm)
ii) with earth switch on one side (mm x mm xmm)
iii) with earth switch on both sides (mm x mm xmm)
34 Enclosures
Whether the following are enclosed
i) Type test report for main
equipment and auxiliaries
(Yes/No)
ii) Drawings as per specification (Yes/No)
iii) Technical literature for isolator,
operating mechanism and support
insulators.
(Yes/No)
35 Compliance to Technical
Specification w.r.t.
(a) MOM box Yes/No
(b) Support insulators Yes/No
Section - IX : Guaranteed & other Technical Particulars
-20-
8/12/2019 GTP.xls
15/152
3 /2/1 Pole
Guaranteed ParticularsSl.
No.Description Unit
(c) Terminal connectors Yes/No
36 A. Tandem Pipe
a) Size ( internal diameter) (mm)
b) Class
c) MaterialB. Down pipe
a) Internal dia. (mm)
b) Class
c) Material
Section - IX : Guaranteed & other Technical Particulars
-21-
8/12/2019 GTP.xls
16/152
C.
Sl.
No.Description Unit
Guaranteed
Particulars
1 Manufacturers Name and Address
2 Manufacturers type designation
3 Type of CT (Live or dead tank type)
4 Rated voltage (kV)
5 Max. Continuous rated voltage (kV)
6 Standards applicable
7 Rated frequency (Hz)
8 Core Details - Core 1
a) Rated primary current (Amp)
b) Rated secondary current (Amp)
c) Rated output (Burden) (VA)
d) Rated output at 0.8 lagging power (VA)
e) Class of accuracy
f) Accuracy limit factorg) Saturation factor
h) Knee point voltage at different taps (Volts)
i) C.T. Resistance of secondary winding
corrected to 70 Deg. C
(Ohms)
j) Magnetizing current at knee-point (mA)
k) Secondary limiting voltage (kV)
l) Instrument Security Factor (ISF)
Core Details - Core 2
a) Rated primary current (Amp)
b) Rated secondary current(Amp)
c) Rated output (Burden) (VA)
d) Rated output at 0.8 lagging power (VA)
e) Class of accuracy
f) Accuracy limit factor
g) Saturation factor
h) Knee point voltage at different taps (Volts)
i) C.T. Resistance of secondary winding
corrected to 70 Deg. C
(Ohms)
j) Magnetizing current at knee-point (mA)
k) Secondary limiting voltage (kV)
l) Instrument Security Factor (ISF)
Core Details - Core 3
a) Rated primary current (Amp)
b) Rated secondary current (Amp)
c) Rated output (Burden) (VA)
d) Rated output at 0.8 lagging power (VA)
CURRENT TRANSFORMERS (145 kV & 36 kV)
Section - IX : Guaranteed & other Technical Particulars
-33-
8/12/2019 GTP.xls
17/152
Sl.
No.Description Unit
Guaranteed
Particulars
e) Class of accuracy
f) Accuracy limit factor
g) Saturation factor
h) Knee point voltage at different taps (Volts)
i) C.T. Resistance of secondary windingcorrected to 70 Deg. C
(Ohms)
j) Magnetizing current at knee-point (mA)
k) Secondary limiting voltage (kV)
l) Instrument Security Factor (ISF)
Core Details - Core 4
a) Rated primary current (Amp)
b) Rated secondary current (Amp)
c) Rated output (Burden) (VA)
d) Rated output at 0.8 lagging power (VA)
e) Class of accuracy
f) Accuracy limit factor
g) Saturation factor
h) Knee point voltage at different taps (Volts)
i) C.T. Resistance of secondary winding
corrected to 70 Deg. C
(Ohms)
j) Magnetizing current at knee-point (mA)
k) Secondary limiting voltage (kV)
l) Instrument Security Factor (ISF)
Core Details - Core 5
a) Rated primary current (Amp)
b) Rated secondary current (Amp)
c) Rated output (Burden) (VA)
d) Rated output at 0.8 lagging power (VA)
e) Class of accuracy
f) Accuracy limit factor
g) Saturation factor
h) Knee point voltage at different taps (Volts)
i) C.T. Resistance of secondary winding
corrected to 70 Deg. C
(Ohms)
j) Magnetizing current at knee-point (mA)
k) Secondary limiting voltage (kV)
l) Instrument Security Factor (ISF)
9 One minute power frequency
withstand test voltage of
i) Primary winding (kVrms )
ii) Secondary winding (kV)
Section - IX : Guaranteed & other Technical Particulars
-34-
8/12/2019 GTP.xls
18/152
Sl.
No.Description Unit
Guaranteed
Particulars
10 1.2/50 microsecond lightning impulse
wave withstand voltage of primary
winding
(kV peak)
11 One minute dry power frequency
withstand voltage
(kV rms)
12 Creepage distance (mm)
13 Rated continuous thermal current (Amp)
14 Ratios available at different taps
15 Rated short time thermal current (kA rms)
16 Rated time for above (Sec)
17 Rated dynamic current for primary (kA peak)
18 Class of insulation
19 Maximum temperature rise over
ambient of 38 Deg. C at any part or oil
(Deg. C)
20 a) Corona extinction voltage (kV rms)
b) Radio Interference Voltage at 1 (mV)c) Partial discharge level (pC)
21 Total weight (Kg)
d) Standard to which oil conforms
24 Quantity of oil (litres)
25 Overall dimensions (mm x mmx mm)
26 Heights of supporting structure (mm)
27 Drawings enclosed
i) Magnetization curve (Yes/No)
ii) Ratio and phase angle characteristics at
least up to accuracy limit factor
(Yes/No)
iii) Ratio Correction Factor curve (Yes/No)
iv) Limits of composite error at rated
primary saturation current (for
(Yes/No)
v) Base plan (Yes/No)
vi) Maximum safe loading as per drawing (Yes/No)
vii) Foundation plan showing details of
foundation bolts
(Yes/No)
viii) Foundation loading (Yes/No)
ix) Support structure (Yes/No)
28 Temperature Rise after passing short
time Thermal current for one second
(Deg. C)
29 Current density in primary winding
a) Normal rating at different taps (A/ sq. m)
b) Short time rating of 1 sec (A/ sq. m)
c) Dynamic rating (A/ sq. m)
30 Type of primary winding
31 Number of primary turns (Nos.)
Section - IX : Guaranteed & other Technical Particulars
-35-
8/12/2019 GTP.xls
19/152
Sl.
No.Description Unit
Guaranteed
Particulars
32 Number of secondary turns (Nos.)
33 Flux density at knee point voltage
(knee point defined at the point at
which 10% increase in voltage
produces a 50% increase in
(Tesla)
34 Radio interference voltage
a) With terminal connector mounted (mV)
b) Under test condition (mV)
35 Variation in ratio and phase angle error
due to variation in
a) Voltage by 1% (%, %)
b) Frequency by 1 Hz (%, %)
36 Source/grade of oil and standard with
which it complies
37 Whether pressure relief device is
provided
(Yes/No)
38 Mounting details (Yes/No)
39 Whether the following are enclosed
with tender:
a) All type test reports (Yes/No)
b) Drawings as per the specification (Yes/No)
c) Technical literature for current
transformer and marshalling box.
(Yes/No)
40 Weight of CT with oil (Kg)
Section - IX : Guaranteed & other Technical Particulars
-36-
8/12/2019 GTP.xls
20/152
D.
Sl.
No.Description Unit Guaranteed Particulars
1 Manufacturers Name and address
2 Manufacturers type designation
3 Applicable standard
4 Rated voltage
a) Nominal (KV rms)b) Maximum (KV rms)
5 Rated frequency (Hz)
6 Number of secondary windings (Nos. )
7 No. of phases (Nos.)
8 Maximum temperature rise over ambient
of 38 Deg.C
(Deg. C)
9 Reference range of frequency (Hz)
10 Reference range of temperature (Deg. C)
11 Rated primary burden (VA)
12 Winding details - Windings 1
a) Rated primary voltage (kV)
b) Rated secondary voltage (V)
c) Rated secondary burden (VA)d) Accuracy class
13 Winding details - Windings 2
a) Rated primary voltage (kV)
b) Rated secondary voltage (V)
c) Rated secondary burden (VA)
d) Accuracy class
14 Winding details - Windings 3
a) Rated primary voltage (kV)
b) Rated secondary voltage (V)
c) Rated secondary burden (VA)
d) Accuracy class
15 Rated voltage factor and corresponding
rated time
16 Rated total thermal burden (VA)
17 Rated insulation levels
a) 1.2/50 micro-second Lightning impulse
withstand voltage
(kV peak)
b) 1 minute dry power frequency withstand
test voltage
(kV rms)
18 Creepage distance (mm)
19 Radio Interference Voltage at 1 MHz at
105 kV rms for 132 kV system
(V)
20 Corona extinction voltage (kV rms)
21 Overall dimensions & weights
a) Width (mm)
b) Height (mm)
c) Weight (Kg)
22 Rated total thermal burden (Attach curve
& state curve reference numbers)
(VA)
POTENTIAL TRANSFORMERS (145 kV and 36 kV)
Section - IX : Guaranteed & other Technical Particulars
-40-
8/12/2019 GTP.xls
21/152
Sl.
No.Description Unit Guaranteed Particulars
23 Temperature rise at 1.2 times rated
primary voltage Continuous with rated
burden after steady state conditions at
normal rated voltage and burden
(Deg. C)
24 Temperature rise at 1.5 times rated
voltage for 30 sec.
(Deg. C)
25 One minute power frequency withstand
voltage on secondaries
a) Winding No. I (kV rms)
b) Winding No. II (kV rms)
c) Winding No. III (kV rms)
35 One minute power frequency withstand
voltage of HF terminal
36 Partial discharge level (pC)
37 Value of pressure for sealing test (kN/sq. m)
38 Weight of oil and the standard to which it
conforms
a) In measuring unit (Kg)
39 Quantity of oil (litres)
40 Total weight (Kg)41 Minimum center to center recommended
spacing between PTs.
(mm)
42 Clearance required from grounded
equipment at various heights of PTs.
(mm)
43 Mounting flange dimensional details
44 Compliance to technical specification
(a) Bushing insulator (Yes/No)
(b) Control cabinet (Yes/No)
(c) Terminal connectors (Yes/No)
45 Enclosures:
Whether the following are enclosed with
the tenderi) All type test reports (Yes/No)
ii) Drawings as per specification (Yes/No)
iii) Technical literature for potential
transformer and marshalling box.
(Yes/No)
Section - IX : Guaranteed & other Technical Particulars
-41-
8/12/2019 GTP.xls
22/152
F.
Sl.
No.Description Unit
Guaranteed
Particulars
1 Manufacturers Name and Address
2 Manufacturers type designation
3 Applicable technical standard
4 Arrester class and type
5 Rated voltage of arrester (kV rms)
6 Rated system voltage (kV rms)
7 Rated frequency (Hz)
8 Continuous Operating Voltage (COV) (kV rms)
9 Nominal Discharge Current (8/20 micro sec.) (kA)
10 a) No. of units in complete arrester (Nos.)
b) Voltage rating of each unit (kV rms)
c) Height of longest unit (mm)
11 Long duration discharge class
12 a) Minimum energy dissipation capability (kJ/kV of
rated voltage of arrester)
(kJ/kV)
b) Power frequency over voltage withstand capability
immediately after discharging energy equivalent to
the minimum capability of arrester .
(kV rms)
13 Leakage current at COV and ambient temperature
a) Resistive component (mA)
b) Capacitive component (mA)
c) Total (mA)
14 Reference voltage and corresponding reference
current guaranteed by manufacturer
(kV rms,
kA rms)
15 Watt loss per kV at COV (Watts)
16 Temporary power frequency over voltage withstand
capability
a) 0.03 sec (for 390 kV only) (kV rms)
b) 0.1 sec (kV rms)
c) 1.0 sec (kV rms)
d) 10 sec (kV rms)
e) 100 sec (kV rms)
17 Maximum residual voltage for
a) Lightning impulse current (8/20 micro sec.) of
- 5 kA (kV peak)
- 10 kA (kV peak)
- 20 kA (kV peak)
b) Steep current impulse (1/20 micro sec) at Nominal
Discharge Current
(kV peak)
18 High current short duration impulse (4/10 micro sec)
value
(kApeak)
19 Low current long duration impulse current (2000
microsec.)
20 Whether pressure relief devices provided (Yes/No)
21 Current for pressure relief test (kA)
METAL OXIDE SURGE ARRESTERS (120 kV & 30 kV)
Section - IX : Guaranteed & other Technical Particulars
-46-
8/12/2019 GTP.xls
23/152
8/12/2019 GTP.xls
24/152
8/12/2019 GTP.xls
25/152
Sl.
No.Description Unit Guaranteed Particulars
23 Weight of cell complete with electrolyte (Kg)
24 Size and material of connectors with method of
connectingcells
(mm)
25 Recommended period of storage before first
charging
(hr)
26 Size of cable recommended for connections ofbattery-to-battery charger, DC distribution
(sq. mm)
27 Insulator material for rack and cells.
28 Battery racks
i) Type of material
ii) Whether anti-acid coating provided (Yes/No)
iii) Net weight (Kg)
29 Short circuit current at battery terminals (Amps)
30 Recommended maximum rating of fuse for
protection of battery
(Amps)
31 Time for which the battery can withstand short
circuit at terminals
(Sec)
32 Amount of hydrogen evolved during boost
33 Recommended interval at which battery should
be discharged at 10 hour discharge rate and
boost charged.
34 AH efficiency (%)
35 WH efficiency (%)
36 Equalizer charging current and frequency of
equalizing charge recommended
(Amp, Hz)
37 a) Type of inter cell connector (bolted/burnt)
b) Material of inter cell connector
38 During initial charging
a) Recommended starting rate of charge
b) Recommended finishing rate of charge
c) Voltage of cell at the end of charge at finishing (Volts)
39 Enclosures
a) Whether all the drawings and technical literature
of Battery enclosed
(Yes/No)
b) Whether type test reports enclosed (Yes/No)
Section - IX : Guaranteed & other Technical Particulars
-95-
8/12/2019 GTP.xls
26/152
II
FloatFloat cum
Boost
1 Manufacturer's Name and Address
2 Charger rated output current(Amp)
3 Charger rated output voltage (Volts)
4 Capacity of battery chargers (AH)
5 Rectifier assembly
a) Type of semi conductor material
b) Rated direct current (Amp)
c) Rated direct voltage (Volts)
d) Continuous rating (Amp)
e) Rated input voltage (Volts)
f) Type of connection of rectifier elements (Full wave
half/full controlled bridge)
g) Maximum temperature rise over ambient of 38 Deg. C
outside
(Deg. C)
h) Short time rating and duration (Amp, Sec)
i) Short circuit current on the output terminal (Amps)
j) Peak inverse voltage of rectifier elements (Volts)
k) Overload capacity (%)
l) Applicable standard
6 Load limiter current setting range for float charger (Amp, %)
7 Automatic voltage regulator (Float/Boost charger)
a) Type
b) Percentage stabilisation of the out put DC voltage (%)
c) Voltage setting range (Volts, %)
d) Response time (ms)
8 Manual voltage regulator (Float/Boost charger).
a) Type
b) Voltage setting range
9 a) Boost charging current setting range (Amp, %)
b) Boost charging voltage limit setting range (Volts, %)
10 Rectifier transformer
a) Type
b) Rated kVA and % impedance (kVA, %)
c) Turns ratio
d) Primary winding connection in vector representation
e) Secondary winding connection in vector representation
f) Class of insulation
g) One minute power frequency withstand voltage (kV rms)
h) Over load capacity (%)i) Applicable standard
j) Whether short circuit test has been conducted (Yes/No)
11 Instruments
a) Type
b) DC voltmeter range (Volts)
c) DC Ammeter range (Amp)
d) Accuracy class as per IS
e) Dial size (mm x mm)
DC STATION BATTERY AND BATTERY CHARGERS
BATTERY CHARGER
Sl.
No.Unit
Guaranteed Particulars
Description
Section - IX : Guaranteed & other Technical Particulars
-96-
8/12/2019 GTP.xls
27/152
FloatFloat cum
Boost
Sl.
No.Unit
Guaranteed Particulars
Description
12 Contactor
a) Type
b) Rated voltage (Volts)
c) Rated current (Amp)
d) No. of Power contactse) Number, type and rating of auxiliary contacts (V, A, AC/DC)
f) Operating coil voltage (Volts)
g) Dropout voltage (Volts)
13 Thermal over load relay
a) Tripping current range (Amp)
b) Whether single phasing protection provided (Yes/No)
c) Applicable standard
14 Air break switches
a) Type
b) Rated voltage (Volts)
c) Rated current (Amp)
d) Type and material of contacts
e) Applicable Standardsf) Maximum through fault current withstand (kA)
g) Rated making and breaking capacity (kA)
15 Fuses
a) Type
b) Rupturing capacity (kA)
c) Applicable standard
16 Blocking diode
a) Continuous rating (Amp)
b) Short time current rating (Amp)
c) Peak inverse voltage (Volts)
d) Type of semi conducting material
17 Ripple content in DC output
a) With battery (%)
b) Without battery (%)
18 Guaranteed efficiency at rated load (%)
19 Whether chargers provided with following features
a) Automatic voltage regulators (Yes/No)
b) Automatic current regulators (Yes/No)
c) Soft start feature (Yes/No)
d) Smoothing resistor/capacitor filter circuit (Yes/No)
e) Selector switch for automatic and manual mode of
operation
(Yes/No)
f) Load linking circuitory (Yes/No)
g) Necessary RC network for protection of rectifier
elements
(Yes/No)
20 Enclosure :
a) Whether all the drawings and technical literature for
chargers enclosed
(Yes/No)
b) Whether type test reports enclosed (Yes/No)
Section - IX : Guaranteed & other Technical Particulars
-97-
8/12/2019 GTP.xls
28/152
8/12/2019 GTP.xls
29/152
Sl.
No.Description Unit Guaranteed Parameters
iii) Connecting Links
iv) Support springs
v) Cover
vi) Label
vii) End stop
8 Weight in kgs. (Kg)9 Minimum No. of conductors of area 2.5 sq. mm
suitable for connection
i) All circuits except CT (Nos.)
ii) CT circuits (4 sq. mm) (Nos.)
10 % of spare terminals on each panels (%)
11 Whether shrouding provided for terminals of
voltages more than 110 V AC / DC
(Yes/No)
12 Whether stud type brass terminals provided (Yes/No)
13 Marking
14 Descriptive literature/ leaflet enclosed (Yes/No)
15 Ref. No. and date of type test certificate
D. CONTROL SWITCHES1 Make
2 Type of the switch
3 Type of handle (stay put or otherwise)
4 No. of possible positions of the handle with
a) No. of contacts available in each position
i) Open (Nos.)
ii) Close (Nos.)
b) Maximum No. of contacts which can be
accommodated for each position
(Nos.)
5 Rating of contacts
a) Voltage (Volts)
b) Make and carry current continuously (Amp)c) Make and carry current for 0.5 sec (Amp)
d) Break resistive load (Amp)
e) Break inductive load with L/R = 40 m. sec (Amp)
6 Whether locking arrangement provided (Yes/No)
7 Mounting details and Drawing No.
8 Dimensions (mm)
9 Other information, if any
10 No. of slip contacts (lost motion type)
a) After close (Nos.)
b) After trip (Nos.)
c) Maximum No. of slip contacts possible (Nos.)
11 Standard to which it conforms12 Detailed technical literature furnished (Yes/No)
13 Ref. No. and date of type test certificate
E. INDICATING LAMPS
1 Make
2 Type
3 Ratings
a) Current (Amp)
b) Voltage (Volts)
Section - IX : Guaranteed & other Technical Particulars
-54-
8/12/2019 GTP.xls
30/152
Sl.
No.Description Unit Guaranteed Parameters
c) Wattage (Watts)
4 Colour of lamp
5 Permissible voltage variation (%)
6 Whether series resistance is provided, if so (Yes/No)
a) Ohmic value (Ohms)
b) Power loss (Watts)7 Life of lamp in burning hours (Hours)
8 Other information, if any
9 Size of lens (mm)
10 Identification inscription
11 Dimension and mounting details (mm)
12 Voltage withstand on continuous basis as a
percentage of rated voltage
(%)
13 Descriptive literature/ leaflet enclosed (Yes/No)
14 Ref. No. and date of type test certificate
15 Standard to which it conforms
F. PUSH BUTTONS
1 Make2 Contact type (momentary/maintained)
3 Whether shrouding provided to prevent
inadvertent operation
(Yes/No)
4 Whether integral engraved inscription plates (Yes/No)
5 No. of NO/NC contacts (Nos.)
6 Make and carry capacity at 250 VDC (Amp)
7 Break inductive load capacity (Amp)
8 Descriptive literature/ leaflet enclosed (Yes/No)
9 Ref. No. and date of type test certificate
10 Standard to which it conforms
G. ANNUNCIATORS1 Make and type
2 No. of windows (Nos.)
3 Dimensions of each window (length x height x (mm x mmx mm)
4 No. of lamps per window (Nos.)
5 Auxiliary supply voltage (Volts)
6 Power consumption (Watt)
7 Details of auxiliary equipment such as relays etc.
furnished
(Yes/No)
8 Required instantaneous making capacity of
initiating contacts
(Amp)
9 Type of reset - (manual / self)
10 Over all dimensions of annunciator (mm x mmx mm)
11 Particulars of wiring enclosed (Yes/No)
12 Technical literature enclosed (Yes/No)
13 Brief write up of the scheme furnished (Yes/No)
14 Applicable standard
H. INDICATING METERS
1 Make and type
2 Type of movement
Section - IX : Guaranteed & other Technical Particulars
-55-
8/12/2019 GTP.xls
31/152
Sl.
No.Description Unit Guaranteed Parameters
3 Type of mounting
4 Range
a) Effective range
5 CT ratio
6 PT ratio
7 Details of shunt, if anya) Rated current (Amp)
b) Rated voltage drop (Volts)
8 Accuracy class
9 Total deflection angle (Degrees)
10 Total scale length
11 Dimension (mm)
12 Reference condition of influencing quantities
13 Limits of influencing quantities for its application
14 Limit of error for variation of each of the
influencing quantities
15 Limits of error in effective range
16 Power consumptiona) Current coil (Watts)
b) Potential coil (Watts)
17 Burden
a) Current coil (VA)
b) Voltage coil (VA)
18 Short time rating
a) Current coil (Amp)
b) Voltage coil (Volts)
c) Time (Sec)
19 Other details
20 Detailed literature furnished (Yes /No)
21 Weight (Kg)22 Whether magnetically shielded or not (Yes /No)
23 Continuous over loading
a) Current coil (Amp)
b) Potential coil (Volts)
24 Temperature at which the instruments are (Deg. C)
25 Ref. No. and date of type test certificate
26 Standard to which the instrument conforms.
27 Descriptive literature/ leaflet enclosed (Yes /No)
I. ENERGYMETERS
1 Make and size
2 Type of measurement
3 Measuring range4 CT ratio
5 PT Ratio
6 Current coil rating (Amp)
7 Voltage coil rating (Volts)
8 Accuracy at 125% , 10% and 25% of rated
a) Active energy measurement
b) Reactive energy measurement
9 Power Consumption
Section - IX : Guaranteed & other Technical Particulars
-56-
8/12/2019 GTP.xls
32/152
Sl.
No.Description Unit Guaranteed Parameters
a) Current coil (Watts)
b) Potential coil (Watts)
10 VA burden of current coil (VA)
11 VA burden of potential coil (VA)
12 Limits of error at UPF and
a) Rated currentb) 125% of rated current
c) 25% of rated current
d) 10% of rated current
13 Limits of error at 0.5 PF (lag) and
a) Rated current
b) 125% of rated current
c) 25% of rated current
d) 10% of rated current
14 Continuous overload rating of current coil
a) For thermal limit (Amp)
b) For accuracy limit (Amp)
15 Short time overload rating of current coil
a) Current (Amp)
b) Time (Sec)
16 Continuous over voltage rating of potential coil (Volts)
17 Reverse running stop provided (Yes/No)
18 Short time over voltage rating of potential coil (Volts, Sec)
19 Standard to which it conforms
20 Mounting details
21 Whether tropicalized (Yes/No)
22 Auxiliary supply (Volts)
23 Suitability for measurement on unbalanced 3
phase, 3wire System
(Yes/No)
24 No. of digits on the meter (Nos.)25 Starting watts at UPF (Watts)
26 Reference condition of influencing quantities
27 Limits of influencing quantities for its application
28 Temperature at which calibrated (Deg. C)
29 Weight (Kg)
30 Whether magnetically shielded or not? (Yes/No)
31 Limits of error in the effective range
32 Descriptive literature/ leaflets submitted (Yes/No)
33 Testing facilities and other details, if any.
34 Ref. No. & date of type test certificate submitted.
J. RECORDING INSTRUMENTS
1 Make and type
2 Type of mounting
3 Range of parameter that can be recorded
4 Range of basic movement (in case of transducer
operated system)
5 Accuracy
6 Range and choice of speeds
Section - IX : Guaranteed & other Technical Particulars
-57-
8/12/2019 GTP.xls
33/152
Sl.
No.Description Unit Guaranteed Parameters
7 Paper width (mm)
8 Length of chart (mm)
9 Auxiliary supply
a) Voltage (Volts)
b) Current (Amp)
c) Watts (Watts)10 Permissible variation in auxiliary supply (%)
11 Burden (VA)
12 Type of case (draw out/non draw out)
13 Detailed technical literature furnished (Yes/No)
14 Particulars of drive
15 Form of reserve drive
16 Details of arrangement for time synchronization
17 Standard to which the recorder conforms
K. DISTURBANCE RECORDER
1 Name of manufacturer
2 Manufacturers type designation
3 Standards according to which disturbancerecorders and event recorder are manufactured
4 Over rated voltage (Volts)
5 Frequency (Hz)
6 Data Acquisition Unit
i) Resolution time for data acquisition (ms)
ii) Whether micro processor based or not (Yes/No)
iii) Rate of scanning of analogue and digital (Hz /Channel)
iv) Analysis of recording of analogue quantities
Type of channel
AC/DC Current
AC/DC Volts
Watts / VAR / carrier
Zero seq. voltage
Multiphase voltage
Period/frequency
Negative sequence voltage
v) Rate of sampling
7 Sensor details
a) i) Current swing
ii) Voltage swing
iii) 3 phase under voltage
iv) 3 phase over voltage
v) 1 phase under voltage
vi) 1 phase over voltagevii) 3 & 1 phase over current
viii) Rate of change of voltage
ix) 3 phase. Neg. sequence voltage
x) 3 phase zero sequence voltage
xi) Over/under frequency
xii) DC over/under level
b) Stability of sensor trip setting (%)
8 Recorder:
Section - IX : Guaranteed & other Technical Particulars
-58-
8/12/2019 GTP.xls
34/152
Sl.
No.Description Unit Guaranteed Parameters
i) Type
ii) Type of paper used
iii) Recorder chart speed (% of rated speed for
prefault & postfault period)
Section - IX : Guaranteed & other Technical Particulars
-59-
8/12/2019 GTP.xls
35/152
Sl.
No.Description Unit Guaranteed Parameters
iv) Response time
a) Transient response time suitable to resolve
breaker pole timing and restrike wave forms
(ms)
b) % over shoot (%)
v) Phase accuracy at 50 Hz (%)
vi) 50 Hz interference (P-P)vii) Fluctuations due to zero trace noise (peak to
viii) Full scale & division
ix) Trace width (mm)
x) Record clarity
xi) Gain stability (%)
xii) Linearity & distortion
xiii) Amplitude resolution
L. Details of event Logger/ Recorder
i) Type
ii) Width space occupied on chart
iii) Operating input current
1 Isolation levelsi) Isolation levels
ii) Circuit breaker
iii) AC input
iv) Events
v) DC power
vi) Alarms
vii) AC sync.
2 Overload ratings of Channel
i) AC Current
a)Continuous Rating (Amp)
b)1 min. Rating (Amp)
c)1 sec. Rating (Amp)
ii) AC Potential
a)Continuous Rating (Volts)
b)1 min. Rating (Volts)
c)1 sec. Rating (Volts)
3 Printer Characteristics
i) Type
ii) Type of paper used
iii) Test frequency of oscillation (Hz)
iv) Test pulse repetition period (ms)
v) Test duration (Sec)
vi) Peak test voltage (kV)
4 Calibration Devices
i) Currentii) Voltage
iii) Accuracy
5 Real time clock
a) Type
b) Accuracy
6 Type of controls provided for maintenance and
calibration
7 Power supply
Section - IX : Guaranteed & other Technical Particulars
-60-
8/12/2019 GTP.xls
36/152
Sl.
No.Description Unit Guaranteed Parameters
i) Power Consumption (Watts)
ii) Frequency Variation (%)
iii) Voltage Fluctuation
for AC - % and (%)
for DC - % (%)
8 Service life of the equipment (Years)9 Overall dimensions of the equipment (mm)
10 Weight (Kg)
11 Whether type test certificates submitted (Yes/No)
12 Whether details of principles, details of
individual equipment have been submitted
(Yes/No)
13 Descriptive literature/ leaflets enclosed. (Yes/No)
M. FAULT LOCATORS
1 Make
2 Type
3 Reference standards
4 Rated current & or voltage (A, V)
5 Rated DC voltage (V DC)6 Operating principle
7 Solid state / electro mechanical / Numerical
8 Thermal rating (Amp)
9 Number of contacts
i) Normally Open (Nos.)
ii) Normally Closed (Nos.)
10 Contacts self reset / hand reset
11 Burden (VA)
12 Operation indicator provided (Yes/No)
13 Contact rating
i) Make and carry continuously (Amp)
ii) Make and carry for 0.5 sec (Amp)
iii) Break
a) Resistive load (Amp)
b) Inductive load (with L/R = 40 milli sec.) (Amp)
14 i)Maximum registering time (ms)
ii) Time to locate Fault (ms)
15 Whether direct display unit provided? If so,
details to be given.
(Yes/No)
16 Whether a printer included? If so, details to be
given
(Yes/No)
17 DC/DC converter included? (Yes/No)
18 Separate phase and each fault features provided (Yes/No)
19 Descriptive literature enclosed (Yes/No)
N.DIRECTIONAL COMPARISON RELAY
1 Scheme Type/Designation
2 Operating time (min & max.) (ms)
3 VA burden
a) Current circuits (VA)
b) Voltage circuits (VA)
c) DC Circuits (VA)
Section - IX : Guaranteed & other Technical Particulars
-61-
8/12/2019 GTP.xls
37/152
Sl.
No.Description Unit Guaranteed Parameters
4 Type of Directional comparison provided -
(Continuous / Discontinuous)
5 Full details of literature, illustrations &
application checks submitted
(Yes/No)
6 Type of carrier channel required.
7 Particulars of carrier channel requireda) Transmitter frequency range (Hz)
b) Center frequency (Hz)
c) Transmitter output power (Watts)
8 Power supply required with variation tolerance (Volts, %)
9 Size of the equipment (mm)
10 Weight of the equipment (kg)
11 Type of operational phase selector
12 Ambient temperature range (Deg. C)
13 Dielectric test voltage (kV)
14 Impulse withstand test voltage (kV)
15 Disturbance test voltage (kV)
16 Type of operation mode of relay (independent /dependent)
17 The following details for Main I & II protection
schemes shall be submitted with the tender.
i) Detailed block diagram (Yes/No)
ii) Detailed internal Circuit diagram with terminal
details for external wiring and power supply
(Yes/No)
iii) Drawings giving details of dimensions & (Yes/No)
iv) Type test reports (Yes/No)
v) Is it suitable for 220 V DC (Yes/No)
vi) Phase selector distance included for single and
three phase tripping?
(Yes/No)
vii) DC/DC converter included? (Yes/No)
viii) Operating time (maximum ) of phase selector
relays for Zs/Z1 = 15.
(ms)
18 The relay shall not mal operate for CVT (Yes/No)
19 Stability angle limit range (Degrees)
20 Particulars of time/current, voltage setting ranges
and steps etc. as well as any other data required
for guaranteeing performance of the remaining
relays included in the specification (inclusive of
dead line charging relays, synchronizing check
relays, neutral displacement relays, over fluxing
relays etc.) shall be submitted herein.21 Standards to which the relays conform.
22 The Sensitivity and selectivity of receiver.
O. DISTANCE RELAYS
1 Make
2 Type
3 Type of distance measuring and number of
measuring elements
4 Starting unit
Section - IX : Guaranteed & other Technical Particulars
-62-
8/12/2019 GTP.xls
38/152
Sl.
No.Description Unit Guaranteed Parameters
a) Is a separate directional relay provided or (Yes/No)
b) The distance element is directional (Yes/No)
c) Type and number of starting unit
5 a)Number of zones
b) First zone element taps are variable in steps of
6 Second zone element taps are variable in steps of7 Third zone element taps are variable in steps of
8 If Mho unit has any OFF SET setting possible
and if so, range
(Yes/No)
9 Operating time
a) First zone timing (ms)
b) Second zone timing adjustable between (ms)
c) Third zone time adjustable between (ms)
10 Contact ratings
a) First zone (V, A,AC/DC)
b) Second zone (V, A,AC/DC)
c) Third zone (V, A,AC/DC)11 VA burden of each phase
a) Current coil (VA)
b) Potential coil (VA)
c) DC circuits (VA)
12 Whether seal in contacts are provided? (Yes/No)
13 Technical literature furnished (Yes/No)
14 Setting range of characteristic angle (Degrees)
15 Whether under voltage relays are provided (Yes/No)
16 Continuously variable ohmic range (Ohms)
17 Maximum resetting time (ms)
18 Range of adjustable offset features (%)
19 Residual compensation range (%)20 Continuous current rating (Amp)
21 Short time current rating and time (Amp, Sec)
22 Continuous voltage rating (Volts)
23 Whether high- speed trip relays are included. (Yes/No)
24 Whether power swing blocking incorporated. (Yes/No)
25 Whether CVT fuse failure protection included. (Yes/No)
26 Whether out of step tripping relays included. (Yes/No)
27 Number of potential free contacts provided. (Nos.)
28 Whether continuous DC supply supervision
provided.
(Yes/No)
29 Standard to which the relays conform.
P. AUTO RECLOSE RELAY1 Make
2 Type
3 Reference standards
4 Rated current and/or voltage (A, V)
5 Rated DC voltage (Volts)
6 Operating principle
7 Electromechanical/static/Numerical
8 Thermal rating (Amp)
Section - IX : Guaranteed & other Technical Particulars
-63-
8/12/2019 GTP.xls
39/152
Sl.
No.Description Unit Guaranteed Parameters
9 Number of contacts
a) Normally Open (Nos.)
b) Normally Closed (Nos.)
10 Contacts - (self reset / hand reset)
11 Burden (VA)
12 Operating indicator provided? (Yes/No)13 Contact ratings and configuration
i) Make and carry continuously (Amp)
ii) Make and carry for 0.5 sec. (Amp)
iii) Break
Resistive load (Amp)
Inductive load (with L/R = 40 ms) (Amp)
14 Suitable for single and three phase (single phase/
three phase)
15 Single phase dead time setting range (Sec)
16 Three phase dead time setting range (Sec)
17 Reclaim time setting range (Sec)
18 Whether check synchronizing and dead linecharging relays included as a part of the auto
(Yes/No)
19 Whether four position selector switch is included (Yes/No)
20 Whether single shot or multi shot.
21 Whether pole discrepancy relay included (Yes/No)
22 Descriptive literature/ leaflet enclosed (Yes/No)
23 Whether lock out facility provided (Yes/No)
24 Any other relevant information
Q. DIFFERENTIAL RELAYS
1 Makers name
2 Type
3 Current coil rating (Amp)
4 Maximum VA burdeni) Operating coil (VA)
ii) Restraining coil (VA)
5 Power consumption of
i) Operating coil (Watts)
ii) Restraining coil (Watts)
6 Is the slope setting variable (Yes/No)
7 Harmonic restraint provided or not with details. (Yes/No)
8 Is 5th harmonic by pass provided? (Yes/No)
9 Range of HT/LT ratios over which the relay can
be used
10 Details of auxiliary CTs.
11 Operating timea) At 2 x In (ms)
b) At 10 x In (ms)
c) At 5 x In (ms)
12 Descriptive literature/ leaflet enclosed (Yes/No)
13 Contact rating
a) Make and carry continuously (Amp)
b) Make and carry for 0.5 sec. (Amp)
Section - IX : Guaranteed & other Technical Particulars
-64-
8/12/2019 GTP.xls
40/152
Sl.
No.Description Unit Guaranteed Parameters
c) Break Resistive load and inductive load (with
L/R = 40 milli sec.)
(Amp)
14 Type of mounting
15 No. of pair of make and break contacts (Nos.)
16 Pick up/drop off ratio
17 Resetting time (ms)18 Normal voltage (Volts)
19 Permissible variation in voltage (%)
20 Nominal current (in case of current operated (Amp)
21 Permissible variation in current (%)
22 Type of casing and available number of terminal (Nos.)
23 Standards to which the relays conform.
24 Whether Disturbance Recorder provided (Yes/No)
25 No. of instantaneous high set over current units (Nos.)
R.TRANSFORMER OVER FLUXING RELAY
1 Make2 Type
3 Reference standards
4 Rated current & or voltage (A, V)
5 Rated DC voltage (Volts)
6 Operating principle
7 Solid state or electro mechanical or Numerical
8 Thermal rating (Amp)
9 Number of contacts
i) Normally open (Nos.)
ii) Normally closed (Nos.)
10 Contacts self reset / hand reset
11 Burden(VA)
12 Operation indicator provided (Yes/No)
13 Contact rating
i) Make and carry continuously (Amp)
ii) Make and carry for 0.5 sec (Amp)
iii) Break
a) Resistive load (Amp)
b) Inductive load (with L/R = 40 ms) (Amp)
14 Setting ranges
a) V/f (%)
b) Time for alarm (Sec)
c) Time for tripping (ms)
15 Detailed literature enclosed (Yes/No)
16 Resetting Ratio (%)
17 Whether provided on both HV and IV sides of the
transformers
(Yes/No)
S. OVER CURRENT AND EARTH FAULT
RELAY
I. NON - DIRECTIONAL
1 Makers name
2 Type & reference standard
Section - IX : Guaranteed & other Technical Particulars
-65-
8/12/2019 GTP.xls
41/152
Sl.
No.Description Unit Guaranteed Parameters
3 Current coil rating (Amp)
4 VA burden
i) Highest tap (VA)
ii) Lowest tap (VA)
5 Rated DC voltage (Volts)
6 Operating principle7 Thermal rating (Amp)
8 Rated current & or voltage (A, V)
9 Power consumption
i) Highest tap (Watts)
ii) Lowest tap (Watts)
10 Time of operation at
i) 5 times tap setting current (ms)
ii) 10 times tap setting current (ms)
11 Type of characteristics (ms)
12 Descriptive literature/leaflets enclosed (Yes/No)
13 Contact ratings
i) Make and carry continuously (Amp)ii) Make and carry for 0.5 sec (Amp)
iii) Break resistive load and inductive load with 40
milli sec. time constants
(Amp)
14 No. of pair of make and break contacts (Nos.)
15 Directional sensitivity (%)
16 Over current unit setting range
i) Inverse time (ms)
ii) High set instantaneous unit
17 Maximum torque angle (Degrees)
II. DIRECTIONAL
1 Makers name
2 Type
3 Polarization
i) Current
ii) Potential
4 Current coil rating (Amp)
5 Potential coil rating (Volts)
6 VA burden
i) Current coil (VA)
ii) Highest tap (VA)
iii) Lowest tap (VA)
iv) Potential coil (VA)
7 Time of operation at
i) 5 times tap setting (ms)
ii) 10 times tap setting sec8 Type of characteristic
9 Descriptive literature / leaflet enclosed (Yes/No)
10 Applicable standards
11 Dimensions / weights (mm, Kg)
T.RESTRICTED EARTH FAULT RELAY
1 Make
2 Type
Section - IX : Guaranteed & other Technical Particulars
-66-
8/12/2019 GTP.xls
42/152
Sl.
No.Description Unit Guaranteed Parameters
3 Reference standards
4 Rated current & or voltage (A, V)
5 Rated DC voltage (Volts)
6 Operating principle
7 Solid state or electro mechanical or Numerical
8 Thermal rating (Amp)9 Number of contacts
i) Normally Open (Nos.)
ii) Normally Closed (Nos.)
10 Case dimensions (Overall ) (mm x mmx mm)
11 Cut out dimensions (height x width) (mm x mm)
12 Weight (Kg)
13 Contacts self reset/ hand reset
14 Burden (VA)
15 Operation indicator provided (Yes/No)
16 Contacts ratings
i) Make and carry continuously (Amp)
ii) Make and carry for 0.5 secs (Amp)
iii) Break
a) Resistive load (Amp)
b) Inductive load (with L/R = 40 ms) (Amp)
17 Operating time at 2 x setting current (ms)
18 Tuned to system frequency? (Yes/No)
19 Setting range (%)
20 Is it with high impedance with stabilizing resistor
or not? If so, value / range of stabilizing resistor
(Ohms)
21 Detailed literature / leaflet enclosed (Yes/No)
22 Current setting range (%)
23 Operating time (ms)
24 Voltage setting range (%)
25 No. of alarm and trip output contacts (Nos.)
U. BUS BAR PROTECTION RELAY
1 Make and type designation
2 General design (Static modular / EM /
3 Impedance type (Low / High/ moderately high)
4 Principle of operation
5 Time of operation
i) At 5 times the setting (ms)
ii) At 10 times the setting if applicable (ms)
6 Current rating and burden (Amp, VA)
7 DC supply (Volts)
8 Whether relay is suitable for all types of faults (Yes/No)
9 Whether separate CT core required? (Yes/No)
10 Whether aux. CTs required and if yes state
whether these are built in or to be provided
separately?
(Yes/No)
11 Whether relays can perform correctly even under
CT saturation condition?
(Yes/No)
Section - IX : Guaranteed & other Technical Particulars
-67-
8/12/2019 GTP.xls
43/152
Sl.
No.Description Unit Guaranteed Parameters
12 Whether relay remains stable for severe through
faults?
(Yes/No)
13 Whether check feature available built in (Yes/No)
14 Type of indicators provided? (Yes/No)
15 Output contact ratings and configuration? (Amp)
16 Maximum number of feeders/circuits that can beconnected to the relay
(Nos.)
17 Whether CT secondary open circuit supervision
facility available
(Yes/No)
18 Whether isolator auxiliary contact monitoring
provided
(Yes/No)
19 Non linear voltage limiting resistors included
for each zone?
(Yes/No)
20 Does the scheme give 100 % security and
reliability during all system operating conditions?
(Yes/No)
21 Any other relevant information
22 Applicable standards
23 Whether high speed hand reset tripping relayprovided
(Yes/No)
24 Whether protection in/out switch provided (Yes/No)
25 Whether DC supply supervision / DC fail alarm
included
(Yes/No)
26 Whether lockout trip relay provided (Yes/No)
27 Is the relay self-monitoring (Yes/No)
28 Whether on line testing facility provided (Yes/No)
29 Descriptive literature / leaflets enclosed (Yes/No)
30 Dimensions / weights of the relay (mm, Kg)
V.CIRCUIT BREAKER FAILURE RELAY
1 Make
2 Type
3 Reference standards
4 Rated current & or voltage (A, V)
5 Rated DC voltage (Volts)
6 Operating principle
7 Thermal rating (Amp)
8 Number of contacts
i) Normally Open (Nos.)
ii) Normally Closed (Nos.)
9 VA Burden
a) At lowest tap (VA)
b) At highest tap (VA)
10 Operation indicator provided? (Yes/No)11 Contact ratings
i) Make and carry continuously (Amp)
ii) Make and carry for 0.5 secs (Amp)
12 Solid state or electro mechanical or numerical
13 Operating time
a) At 5 times tap setting (ms)
b) At 10 times tap setting (ms)
Section - IX : Guaranteed & other Technical Particulars
-68-
8/12/2019 GTP.xls
44/152
8/12/2019 GTP.xls
45/152
Sl.
No.Description Unit Guaranteed Parameters
b) 50 percent KPV (mA)
9 Internal impedance of
a) Primary (Ohms)
b) Secondary (Ohms)
10 Temperature rise (Deg. C)
11 Mounting details12 Overall dimensions (mm)
13 Any other details
14 One minute power frequency withstand voltage (kV rms)
15 Weight (Kg)
16 Location where these are to be used / mounted.
17 Descriptive literature / leaflets enclosed (Yes/No)
Y. PANEL WIRING
1 Insulation of wiring
2 Size of wiring conductor for the following
i) PT circuits (sq. mm)
ii) CT circuits (sq. mm)
iii) DC supply circuits (sq. mm)
iv) Other circuits (sq. mm)
3 Size of earthing bar for safety earthing ( sq. mm)
4 Type of terminal provided on wiring
5 Wiring conductor (aluminum/copper)
6 Whether ferrules and insulated sleeves provided? (Yes/No)
7 Type and size of lugs provided (sq. mm)
8 Applicable standards
9 Descriptive literature / leaflets / circuit diagrams
enclosed?
(Yes/No)
Z TRANSDUCER
1 Make
2 Type
3 Applicable standards4 Rated input (A, V,
AC/DC)
5 Rated output (A, V,AC/DC)
6 Terminal connectors
a) No. of input terminal connectors (Nos.)
b) No. of output terminal connectors (Nos.)
7 Response time (Sec)
8 Accuracy class
9 AC ripple content (%)
10 Suitable for load resistance (Ohms)
11 Temperature range (Deg. C)
12 Dimensions/weight (mm, Kg)13 Descriptive literature / leaflets enclosed? (Yes/No)
AA. RELAY TESTING SET
1 Makers name
2 Type
3 Capacity of loading transformer (kVA)
4 Primary voltage (Volts)
5 Secondary current and voltage (A, V)
6 Electric / electronic timing meters
Section - IX : Guaranteed & other Technical Particulars
-70-
8/12/2019 GTP.xls
46/152
Sl.
No.Description Unit Guaranteed Parameters
a) Operating voltage (Volts)
b) Accuracy
7 Instruments
a) Make
b) Current range (Amp)
c) Voltage range (Volts)d) Accuracy class
e) Standards to which applicable
8 Descriptive literature enclosed (Yes/No)
9 Relay test kit supplied (Yes/No)
10 Distance Relay test kits supplied (Yes/No)
AB. BUS BAR TRIP RELAY
1 Make & type designation
2 General design
3 Operating Time (ms)
4 Number & rating of trip contacts (A, V, AC /DC)
5 Burden (VA)
6 Any other feature7 Applicable standards
8 Descriptive literature / leaflet enclosed? (Yes/No)
AC. TRIP CIRCUIT SUPERVISION RELAY
1 Make & type designation
2 General design
3 DC rating (A, V)
4 Burden (VA)
5 Type of indication
6 Any other relevant details
AD. DC SUPPLY SUPERVISION RELAY
1 Manufacturers Name & Country
2 Type of Relay3 DC rating (A, V)
4 VA Burden (VA)
5 No. of potential free output contacts (Nos.)
6 Any other data
7 Time delay on drop off (ms)
8 Operation indication / flag provided? (Yes/No)
9 Applicable standards
AE. MASTER TRIP RELAY FOR
TRANSFORMERS (for HV & LV intertrip)
1 Manufacturers Name & Country
2 Type of Relay
3 DC rating (A, V)
4 VA Burden (VA)
5 Operating time (ms)
6 Number of output contacts and contact rating (A, V,AC/DC)
7 Any other details
8 Applicable standards
9 Descriptive literature / leaflets enclosed? (Yes/No)
AF . ENERGY METER
1 Make & type designation
Section - IX : Guaranteed & other Technical Particulars
-71-
8/12/2019 GTP.xls
47/152
Sl.
No.Description Unit Guaranteed Parameters
2 Type
3 Accuracy
4 Whether suitable for 3 phase balanced and
unbalanced loads
(Yes/No)
5 Any other relevant data
AG. SELECTOR SWITCHES1 Make & type designation
2 Current rating of contacts (Amp)
3 Number of contacts in each position
a) Open (Nos.)
b) Closed (Nos.)
4 Number of ways (Nos.)
5 Number of positions (Nos.)
6 Type of handle
7 Whether stay put type (Yes/No)
8 Whether locking facility provided. (Yes/No)
9 Applicable standards
10 Descriptive literature / leaflets enclosed?(Yes/No)
AH. BREAKER / ISOLATOR AUXILIARY
CONTACT MULTIPLICATION RELAY
1 Make & type designation
2 Rating & burden (A, V, VA)
3 No. of NO/NC contacts (Nos.)
4 Rating of contacts (A, V)
5 Applicable standards
6 Descriptive literature / leaflets enclosed? (Yes/No)
AI. EARTHING
1 Material of conductor
2 Size (sq. mm)
3 Type of end connection
4 Whether sufficient number of terminal connectors
and clamps are supplied?
(Yes/No)
5 Size of copper wires for earthing (sq. mm)
6 Detailed earthing scheme enclosed? (Yes/No)
AJ. CIRCUIT LABELS
1 Material, size, colour (mm x mm)
2 Size and colour of lettering (mm)
AK. MISCELLANEOUS
1 Tools
Whether following tools included in the scope
i) Special erection tools (Yes/No)
ii) Maintenance tools (Yes/No)
2 SparesWhether list of recommended spares for normal
maintenance for a period of 5 years furnished
(Yes/No)
3 Drawings
Whether following items submitted.
i) General arrangement drawings (Yes/No)
ii) Schematic drawings (Yes/No)
iii) Technical & descriptive literatures of all the
components supplied
(Yes/No)
Section - IX : Guaranteed & other Technical Particulars
-72-
8/12/2019 GTP.xls
48/152
8/12/2019 GTP.xls
49/152
Section - IX : Guaranteed & other Technical Particulars
-74-
8/12/2019 GTP.xls
50/152
Section - IX : Guaranteed & other Technical Particulars
-75-
8/12/2019 GTP.xls
51/152
8/12/2019 GTP.xls
52/152
Section - IX : Guaranteed & other Technical Particulars
-77-
8/12/2019 GTP.xls
53/152
Section - IX : Guaranteed & other Technical Particulars
-78-
8/12/2019 GTP.xls
54/152
Section - IX : Guaranteed & other Technical Particulars
-79-
8/12/2019 GTP.xls
55/152
Section - IX : Guaranteed & other Technical Particulars
-80-
8/12/2019 GTP.xls
56/152
Section - IX : Guaranteed & other Technical Particulars
-81-
8/12/2019 GTP.xls
57/152
Section - IX : Guaranteed & other Technical Particulars
-82-
8/12/2019 GTP.xls
58/152
Section - IX : Guaranteed & other Technical Particulars
-83-
8/12/2019 GTP.xls
59/152
8/12/2019 GTP.xls
60/152
Section - IX : Guaranteed & other Technical Particulars
-85-
8/12/2019 GTP.xls
61/152
8/12/2019 GTP.xls
62/152
Section - IX : Guaranteed & other Technical Particulars
-87-
8/12/2019 GTP.xls
63/152
Section - IX : Guaranteed & other Technical Particulars
-88-
8/12/2019 GTP.xls
64/152
Section - IX : Guaranteed & other Technical Particulars
-89-
8/12/2019 GTP.xls
65/152
Section - IX : Guaranteed & other Technical Particulars
-90-
8/12/2019 GTP.xls
66/152
Section - IX : Guaranteed & other Technical Particulars
-91-
8/12/2019 GTP.xls
67/152
8/12/2019 GTP.xls
68/152
Section - IX : Guaranteed & other Technical Particulars
-93-
8/12/2019 GTP.xls
69/152
8/12/2019 GTP.xls
70/152
C.
ACDB DCDB
I. GENERAL
1 Rated Voltage (Volts)
2 Symmetrical short circuit withstand current ofswitchgear cubicle
(kA)
3 Degree of protection as per IS: 13947
a) Breaker / AC & DC distribution cubicles.
b) Bus bar chamber.
4 Cubicle sheet metal thickness for front, rear, sides
and top.
(mm)
5 Painting shade as per IS:5
a) External surface
b) Internal surface
6 Standard height, width & depth of typical panel.
a) Air circuit breaker panel (mm)
b) Switch fuse cubicle. (mm)c) AC/DC Distribution Board. (mm)
7 Width of cable alley (mm)
8 Earth bus bar size and material. (mm x mm)
9 Recommended dynamic loading for foundation (N)
10 Approximate weight of AC/DC Distribution (Kg)
11 Is extension possible in future. (Yes/No)
12 Clearance in air
a) Between phases (mm)
b) Between phase and earth (mm)
II. CURRENT TRANSFORMERS
1 Manufacturer's Name
2 Applicable standard
3 Ratio
4 Rated output
5 Accuracy class
6 Instrument Security Factor (ISF).
7 Insulation level (kV rms)
8 Nominal rated voltage (kV)
9 Short time thermal rating for 1 sec. (kA rms )
10 Class of insulation.
III. POTENTIAL TRANSFORMERS
1 Manufacturer's Name
2 Applicable standard
3 Rated primary voltage (Volts)4 Rated Secondary voltage (Volts)
5 Accuracy class
6 Insulation level (kV rms)
7 Rated Burden (VA)
8 Over voltage factor
9 Class of insulation
IV. AIR CIRCUIT BREAKER
Guaranteed ParticularsSl.
No.Description Unit
AC/DC DISTRIBUTION BOARD.
Section - IX : Guaranteed & other Technical Particulars
-98-
8/12/2019 GTP.xls
71/152
ACDB DCDB
Guaranteed ParticularsSl.
No.Description Unit
1 Name of manufacturer and country
2 Manufacturer's type designation
3 Applicable standard
4 Rated voltage (kV)
5 Rated current at design ambient temperature (Amps)6 Continuous current at site ambient temperature. (Amps)
7 Rated symmetrical breaking current (kA)
8 Rated making current (kA)
9 Short time current rating (kA, sec)
10 Short circuit performance category
11 Temperature rise of main contacts when carrying
continuous current
(Deg. C)
12 Thickness of silver coating for main contacts (microns)
13 Number of operations circuit breaker can make
without inspection replacement of contacts or
other parts at 100% rated breaking current.
14 a) Number of auxiliary contacts provided and theirrating.
(Amps)
b) Total operating time (ms)
c) Whether trip free or fixed trip type
15 Operating mechanism (for ACB only.)
a) Motor rating (V, A, Watts)
b) Time for fully charging the closing spring (Sec)
c) Emergency manual charging facility provided (Yes/No)
d) Limits of voltage for satisfactory operation of
following devices, as percentage of normal
i) Motor (%)
ii) Closing Coil (%)
iii) Tripping Coil (%)
16 Air break switches
a) Type, make
b) Rated voltage (Volts)
c) Rated current (Amps)
d) Type and material of contacts
e) Applicable standard
f) Maximum through fault current withstand (kA)
g) Door inter locks provided (Yes/No)
h) Rated making and breaking capacity (kA)
17 Fuses
a) Make
b) Typec) Rupturing capacity (kA)
d) Peak cut-off current (kA)
e) Whether mounted on insulated carrier (Yes/ No)
18 Rated operating Duty
V. BUS BARS AND INSULATORS
1 Material and applicable standard
Section - IX : Guaranteed & other Technical Particulars
-99-
8/12/2019 GTP.xls
72/152
ACDB DCDB
Guaranteed ParticularsSl.
No.Description Unit
2 Bare/Painted/Epoxy insulated/Sleeved
3 Minimum clearance
a) Phase to phase (mm)
b) Phase to earth (mm)
4 Continuous current rating at ambient temperature (Deg. C)5 Minimum Cross section provided for
a) Horizontal bus bar (sq. mm)
b) Vertical bus bar (sq. mm)
6 Short time current rating for 1 sec. (kArms)
7 Material of the support insulators.
8 Temperature rise over ambient temperature for
continuous current rating
(Deg. C)
9 Whether bus joints are silver faced (Yes / No)
10 Dynamic current withstand rating (kApeak)
VI. CONTACTORS
1 Make
2 Type and applicable standard3 No. of poles (Nos.)
4 Rated voltage of main and auxiliary contacts. (Volts)
5 Limits of operation
a) Supply voltage variation (+/-%)
b) Supply frequency variation for closing. (+/-%)
c) Drop out voltage (Volts)
6 Rated breaking capacity (kA)
7 Rated making capacity (kA)
8 Rated thermal current (kA)
9 Maximum recommended back up HRC fuse size. (Amp)
10 Rated operating duty
11 Rated voltage of coils (Volts)
VII. AUXILIARY CONTACTOR
1 Make
2 Type
3 Coil voltage (Volts)
4 Coil burden (VA)
5 No. of contacts and their rating (V, A,AC/DC)
VIII. CONTROL / SELECTOR SWITCH
1 Make
2 Type
3 Type of handle
4 Number of contacts (Nos.)
5 Rating of contacts (V, A,AC/DC)
6 No. of positions (Nos.)
7 Contact material and plating
IX. PUSH BUTTONS
1 Make
2 Contact type
3 Number of contacts ( NO+ NC) (Nos.)
Section - IX : Guaranteed & other Technical Particulars
-100-
8/12/2019 GTP.xls
73/152
ACDB DCDB
Guaranteed ParticularsSl.
No.Description Unit
4 Contact rating (V, A,AC/DC)
X. SPACE HEATERS
1 Make
2 Type3 Rated Voltage (Volts)
4 Thermostat setting range (Deg. C)
5 Heater output (Watts)
XI. WIRING AND TERMINAL BLOCKS
1 Voltage grade of wires (Volts)
2 Minimum size of conductor for
a) Power wiring (sq. mm)
b) Control wiring (sq. mm)
3 Type of control terminal block on:-
a) Fixed portion and draw out portion
b) Switchgear and breaker
4 Make and type of terminal blocks
5 Current rating of terminal blocks (Amp)
6 Insulation of wires
7 Conductor material
XII. RELAYS
1 Make
2 Type
3 Application
4 Operating principle
5 Coil burden (VA)
6 Setting range (%)
7 Number of contacts (Nos.)
8 Contact rating (V, A,
AC/DC)9 Contacts - (self reset or hand reset)
10 Operation indicator provided (Yes/No)
11 Time of operation (ms)
XIII. INDICATING LAMPS
1 Make
2 Type
3 Voltage (Volts)
4 Series resistor value and rating (Ohms,Am )
XIV. INDICATING INSTRUMENTS
1 Voltmeter
a) Make
b) Typec) Accuracy class
d) Voltage coil rating (Volts)
e) Voltage coil burden (VA)
f) Case size (mm x mm)
g) Angle of defelection (Degrees)
h) Scale length
2 Ammeter
Section - IX : Guaranteed & other Technical Particulars
-101-
8/12/2019 GTP.xls
74/152
ACDB DCDB
Guaranteed ParticularsSl.
No.Description Unit
a) Make
b) Type
c) Accuracy class
d) Current coil rating (Amp)
e) Current coil burden (VA)f) Case size (mm x mm)
g) Angle of defelection (Degrees)
h) Scale length
XV. ENCLOSURES
1 Whether all the drawings as indicated in the
specification enclosed.
(Yes/No)
2 Whether all type test reports enclosed (Yes/No)
3 Whether characteristics of various types of relays
for MCCB enclosed.
(Yes/No)
4 Whether calculations furnished in support of
adequacy of bus bar size (AC bus/DC bus) for
specified current rating.
(Yes/No)
Section - IX : Guaranteed & other Technical Particulars
-102-
8/12/2019 GTP.xls
75/152
D.
Sl. No. Description Unit 3Cx300 3.5Cx240
1 Name & Address of the manufacturer
2 Applicable standard
3 Cable type designation
4 Voltage rating (Volts)
5 Conductor a) Material of conductor and flexibility class as per IS:8130
b) Size of conductor (sq. mm)
c) Is conductor stranded (Yes/No)
d) Stranded conductor
i) Number of strands in each core
ii) Size of strand (sq. mm)
iii) Shape of the stranded conductor
iv) Maximum DC resistance at 20 deg C (Ohms)/
Km)
6 Number of cores
7 Insulation
a) Insulation material and type designation
b) Minimum thickness of insulation (mm)
c) Tolerance on the measured value of thickness (%)
d) Minimum volume resistivity at 27 deg. C, 70 deg. C and
90 deg. C
(Ohm-cm)
8 Sheath
a) Material for inner sheath, type of sheathing (extruded or
wrapped) and type designation as per IS:5831.
b) Material for outer sheath, type of sheathing (extruded or
wrapped) and type designation as per IS:5831.
c) Thickness of inner sheath and tolerance on measured
value.
(mm, %)
d) Thickness of outer sheath and tolerance on measured
values.
(mm, %)
9 Armour a) Material
b) Shape
c) Dimension (mm)
10 a) Overall diameter of cable (mm)
b) Tolerance on diameter (%)
11 a) Minimum tensile strength of insulation (kg/sq. cm)
b) Minimum elongation at break. (%)
12 a) Minimum tensile strength of sheath. (kg/sq. cm)
b) Minimum elongation at break (%)
13 a) Tensile strength of the armour (kg/sq. cm)b) Elongation after break (%)
14 High voltage test and duration (PVC cables)
a) At room temperature (kV, mins.)b) Under water (kV, mins.)
15 XLPE cable
a) High voltage test (kV, mins.)
b) Short circuit current rating for 1 sec. (kA)
c) Short circuit current rating for armour (kA, Secs)
16 a) Current carrying capacity in air and corresponding
assum tions/conditions of installation
(Amp)
POWER AND CONTROL CABLE - XLPE CABLE
Section - IX : Guaranteed & other Technical Particulars
-103-
8/12/2019 GTP.xls
76/152
D.
Sl. No. Description Unit 3Cx300 3.5Cx240
POWER AND CONTROL CABLE - XLPE CABLE
b) Current carrying capacity under following conditions:
i) Ambient temperature of 38 Deg. C (Amp)
ii) Cable laid in covered cable trenches (Amp)
iii) 3 to 4 cable trays / racks in trench . (Amp)iv) 5 to 6 cables per tray and touching each other. (Amp)
17 Insulation resistance at 27 De . C Ohm/km18 Capacitive reactance per Km. (Ohm/km)
19 Inductive reactance per Km. (Ohm/km)
20 Minimum bending radius. (mm)
21 Short circuit current rating for 1 sec. (kA)
22 Conductor temperature rise during
a) Normal operation (Deg. C)
b) Short circuit (Deg. C)
23 Weight of cable per Km (Kg/km)\
24 a) Standard length of cable per drum (m)
b) Tolerance on length of cable per drum (%)
25 Net weight of drum length of cable (Kg)
26 Method of core identification fora) Cable upto five cores
b) Cable with more than five cores
27 Please indicate writing YES or NO whether the
following tests have been carried out.
i) Ageing test (Yes/No)
ii) Loss of mass test (Yes/No)
iii) Cold bend test (Yes/No)
iv) Cold impact test (Yes/No)
v) Heat shock test (Yes/No)
vi) Thermal stability as per IEC-540 (Yes/No)
vii) Oxygen index test and temperature index test as per
ASTM D-2863.
(Yes/No)
viii) Rodent and termite proof test (Yes/No)ix) Fire retardant test (Yes/No)
28 Enclosures
a) Whether all type test reports enclosed (Yes/No)
b) Whether technical literature enclosed (Yes/No)
c) Whether tables giving rating factors for variation in
standard conditions of installation enclosed
(Yes/No)
d) Whether relevant drawings enclosed (Yes/No)
Section - IX : Guaranteed & other Technical Particulars
-104-
8/12/2019 GTP.xls
77/152
D.
Sl. No. Description Unit 3.5Cx70 3.5Cx35 4Cx16 4Cx6 2Cx6
1 Name of the manufacturer and
country.
2 Applicable standard
3 Cable type designation
4 Voltage rating (Volts)5 Conductor
a) Material of conductor and
flexibility class as per IS:8130
b) Size of conductor (sq. mm)
c) Is conductor stranded (Yes/No)
d) Stranded conductor
i) Number of strands in each
core
ii) Size of strand (sq. mm)
iii) Shape of the stranded
conductor
iv) Maximum DC resistance at
20 deg C
(Ohms) /
Km
6 Number of cores7 Insulation
a) Insulation material and type
designation
b) Minimum thickness of (mm)
c) Tolerance on th