Presented at the 2003 IEEE IAS Pulp and Paper Industry Conference in Charleston, SC: © IEEE 2003 - Personal use of this material is permitted. GROUNDING AND GROUND FAULT PROTECTION OF MULTIPLE GENERATOR INSTALLATIONS ON MEDIUM-VOLTAGE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS PART 3: PROTECTION METHODS An IEEE/IAS Working Group Report [Working Group Members] - Prafulla Pillai (Chair), Alan Pierce, Bruce Bailey, Bruce Douglas, Charles Mozina, Clifford Normand, Daniel Love, David Shipp, Gerald Dalke, James R. Jones, Jay Fischer, Jim Bowen, Lorraine Padden, Louie Powell, Neil Nichols, Ralph Young, Norman T. Stringer Working Group Chair: Prafulla Pillai Kellogg Brown & Root, Inc. Houston, Texas 77002 Abstract - The paper discusses typical grounding practices and ground fault protection methods for medium voltage generator stators, highlighting their merits and drawbacks. Particular attention is given to applications of multiple generators connected to a single bus. The paper also provides an overview of the generator damage mechanism during stator ground faults. Problem areas associated with each type of grounding are identified and solutions are discussed. The paper also provides a list of references on the topic. The paper is intended as a guide to aid engineers in selecting adequate grounding and ground fault protection schemes for medium voltage industrial and commercial generators for new installations, for evaluating existing systems, and for future expansion of facilities, to minimize generator damage from stator ground faults. These topics are presented in four separate parts, Part 1 through Part 4. Part 1 covers scope, introduction, user examples of stator ground failure, and theoretical basis for the problem. Part 2 discusses various grounding methods used in industrial applications. Part 3 describes protection methods for the various types of grounding and Part 4 provides a conclusion and bibliography of additional resource material. I. GENERAL For internal generator ground faults, the generator should be shut down as quickly as possible. However, for an external ground fault such as a feeder fault, a time-delayed shut down is usually employed to permit selective isolation of the faulty circuit. Along with the time-delayed tripping, an instantaneous alarm will provide early warning for the operator to take necessary action to minimize generator damage from prolonged fault current flow. IEEE Guide C37.101 [1] for Generator Ground Protection provides a wide range of generator ground protection schemes for different generator grounding and system grounding configurations. A summary of the recommended protective schemes and grounding arrangements to which they may be applied is given in Table 1 of this IEEE guide. Typical generator ground fault protection methods include: Percentage phase differential protection (device 87) Ground differential protection (device 87GN) Ground time-overcurrent protection (device 51G) Instantaneous ground overcurrent protection (device 50G) Wye-broken-delta vt ground overvoltage protection (device 59G) Stator winding zero-sequence neutral overvoltage protection (device 59GN) Application of these protective functions requires subjective judgment. Larger generators will commonly be equipped with all of these functions, while some functions might be omitted from smaller generators on the basis that the incremental value in limiting damage does not justify the increase in cost. Refer to IEEE guide C37.101 [1] for a detailed discussion regarding settings, sensitivities, advantages and disadvantages of these protection schemes and available variations. All of the above protective functions should initiate a complete shut down of the generator, including tripping of the generator main and field circuit breakers and closing of the prime mover throttle valve.

GroundingandGroundFaultProtectionofMultipleGeneratorsPart3

Embed Size (px)

Citation preview

Page 1: GroundingandGroundFaultProtectionofMultipleGeneratorsPart3

Presented at the 2003 IEEE IAS Pulp and Paper Industry Conference in Charleston, SC: © IEEE 2003 - Personal use of this material is permitted.

GROUNDING AND GROUND FAULT PROTECTION OF MULTIPLEGENERATOR INSTALLATIONS ON MEDIUM-VOLTAGE

INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

PART 3: PROTECTION METHODS

An IEEE/IAS Working Group Report

[Working Group Members] - Prafulla Pillai (Chair), Alan Pierce, Bruce Bailey, Bruce Douglas,Charles Mozina, Clifford Normand, Daniel Love, David Shipp, Gerald Dalke, James R. Jones, JayFischer, Jim Bowen, Lorraine Padden, Louie Powell, Neil Nichols, Ralph Young, Norman T.Stringer

Working Group Chair:Prafulla Pillai

Kellogg Brown & Root, Inc.Houston, Texas 77002

Abstract - The paper discusses typical groundingpractices and ground fault protection methods formedium voltage generator stators, highlighting theirmerits and drawbacks. Particular attention is given toapplications of multiple generators connected to a singlebus. The paper also provides an overview of thegenerator damage mechanism during stator groundfaults. Problem areas associated with each type ofgrounding are identified and solutions are discussed. Thepaper also provides a list of references on the topic. Thepaper is intended as a guide to aid engineers in selectingadequate grounding and ground fault protection schemesfor medium voltage industrial and commercialgenerators for new installations, for evaluating existingsystems, and for future expansion of facilities, tominimize generator damage from stator ground faults.These topics are presented in four separate parts, Part 1through Part 4. Part 1 covers scope, introduction, userexamples of stator ground failure, and theoretical basisfor the problem. Part 2 discusses various groundingmethods used in industrial applications. Part 3 describesprotection methods for the various types of groundingand Part 4 provides a conclusion and bibliography ofadditional resource material.

I. GENERAL

For internal generator ground faults, the generator shouldbe shut down as quickly as possible. However, for an externalground fault such as a feeder fault, a time-delayed shut downis usually employed to permit selective isolation of the faultycircuit. Along with the time-delayed tripping, aninstantaneous alarm will provide early warning for theoperator to take necessary action to minimize generator

damage from prolonged fault current flow. IEEE GuideC37.101 [1] for Generator Ground Protection provides a widerange of generator ground protection schemes for differentgenerator grounding and system grounding configurations. Asummary of the recommended protective schemes andgrounding arrangements to which they may be applied isgiven in Table 1 of this IEEE guide. Typical generator groundfault protection methods include:

� Percentage phase differential protection (device 87)� Ground differential protection (device 87GN)� Ground time-overcurrent protection (device 51G)� Instantaneous ground overcurrent protection

(device 50G)� Wye-broken-delta vt ground overvoltage protection

(device 59G)� Stator winding zero-sequence neutral overvoltage

protection (device 59GN)

Application of these protective functions requiressubjective judgment. Larger generators will commonly beequipped with all of these functions, while some functionsmight be omitted from smaller generators on the basis thatthe incremental value in limiting damage does not justify theincrease in cost. Refer to IEEE guide C37.101 [1] for adetailed discussion regarding settings, sensitivities,advantages and disadvantages of these protection schemesand available variations.

All of the above protective functions should initiate acomplete shut down of the generator, including tripping ofthe generator main and field circuit breakers and closing ofthe prime mover throttle valve.

Page 2: GroundingandGroundFaultProtectionofMultipleGeneratorsPart3

II. PERCENTAGE PHASE DIFFERENTIALPROTECTION (DEVICE 87)

Conventional percentage differential protection for phase-to-phase winding faults (Fig. 19) will provide the ability todetect most internal ground faults, depending on theavailable ground fault current. If the maximum ground faultcurrent is below the phase percentage differential pick-up,the phase differential relays will not provide any ground faultprotection. In such cases a ground differential scheme asdiscussed below may be needed to provide adequateprotection of the generator.

Fig. 19. Generator Percentage Phase Differential Protection

III. GROUND DIFFERENTIAL PROTECTION(DEVICE 87GN)

Due to the high fault currents associated with low-resistancegrounded systems, it is important to provide sensitive, high-speed ground differential protection for generators. Asdiscussed above, with low-resistance grounding, the phasedifferential relays may not be sensitive enough to detectground faults internal to the generator, especially, since themaximum ground fault current may be limited to valuesbelow the phase differential pick-up. In such cases, a grounddifferential protection scheme as shown in Fig. 20 would bedesirable. When properly applied a ground differentialscheme may be able to detect ground faults to within 10% ofthe generator’s neutral without the risk of false tripping onexternal faults. A ground directional overcurrent relay isgenerally used in this application with differential current asthe operating quantity and neutral current as the polarizingquantity. The differential comparison is biased such that apositive restraint exists for an external fault. Depending uponthe rating of, and the burden presented to the phasetransformers, this scheme provides excellent security againstmisoperation for external faults while providing sensitivedetection of internal ground faults.

Fig. 20. Generator Ground Differential Protection

IV. GROUND TIME-OVERCURRENTPROTECTION (DEVICE 51G)

As previously mentioned, one of the most importantadvantages of low-resistance grounding is the ability toselectively coordinate ground overcurrent protection fordownstream faults; thereby tripping only the faulted part ofthe system. For example, consider a ground fault occurringon a load feeder supplied from a generator bus, as shown inFig. 21. The load feeders will be protected using sensitiveinstantaneous ground overcurrent relays (device 50G) oneach feeder , permitting high speed clearing of the fault. Inthe event of an uncleared feeder fault, an inverse time-overcurrent relay (device 51G) on the bus tie breaker willprovide back-up protection, isolating the faulted bus section.Further back-up protection will be provided by the inversetime-overcurrent relays (device 51G) on the groundedneutrals of the sources. Although, time-overcurrent groundrelays provide sensitive, high-speed protection for groundfaults, coordination can be difficult with multiple sourcessince the ground current magnitude will vary with addition orremoval of sources.

Fig. 21. Generator Ground Time OvercurrentProtection

However, there is a possibility of serious generatordamage from the prolonged high fault currents, especiallywhen a ground fault occurs near the terminals of thegenerator. This damage may be reduced by using aninstantaneous ground-overcurrent relay (device 50G) inconjunction with the time overcurrent relay. Theinstantaneous relay will detect faults near the generatorneutrals. It may also provide back up protection for feederfaults.

V. INSTANTANEOUS GROUND OVER-CURRENT PROTECTION (DEVICE 50G)

This is also called a generator self-balancing differentialground relay scheme and is shown in Fig. 22. A window(toroidal) type (also called core-balance or zero-sequence)current transformer that surrounds the generator phase andneutral leads measures the ground current coming from thegenerator and the system for a ground fault in the generator.The current transformer output operates an instantaneous

Page 3: GroundingandGroundFaultProtectionofMultipleGeneratorsPart3

overcurrent relay to trip the generator. For a ground fault inthe system external to the generator, the current transformeroutput will be zero. Therefore, the relay can be safely set to alow value for optimum protection of the generator. The limitof sensitivity can be affected by having to energize a largeblock of transformer load and by the physical position ofleads in the window of the toroid.

Fig. 22. Instantaneous Ground Overcurrent (Self-BalancingDifferential Ground Current) Protection

VI. WYE-BROKEN-DELTA VT, GROUNDOVERVOLTAGE PROTECTION

(DEVICE 59G)

This protection system is generally used for the high-resistance grounded generators. This protection scheme is avariation of the stator winding zero-sequence neutralovervoltage protection scheme that is described below. Inthis scheme as shown in Fig. 23, an overvoltage device(device 59G) is connected to a separate set of broken-deltasecondary windings of the voltage transformer (vt), whoseprimaries are connected to the generator terminals ingrounded wye configuration. A ground fault in the generatorstator winding is detected by measuring the voltage acrossthe broken delta secondary windings of the voltagetransformer. For example, during a single-phase-to-groundfault in the generator, the vectorial sum of the phase-to-ground voltages applied to the primary windings of the threevoltage transformers will be equal to three times the phase-to-neutral voltage of the generator. The voltage appearingacross the terminals of the 59G device operating circuit willbe the vectorial sum voltage divided by the voltagetransformer ratio. It should be noted that full line-to-linevoltage appears across each voltage transformer during aground fault; therefore, they should be rated accordingly. Aloading resistor may be placed across the broken delta tocontrol possible ferroresonance.

Fig. 23. Wye-Broken-Delta Vt, Ground OvercurrentProtection

VII. STATOR WINDING ZERO-SEQUENCENEUTRAL OVERVOLTAGE PROTECTION

(DEVICE 59GN)

The most conventional and widely used protectionscheme for high-resistance grounded systems is a time-delayed overvoltage relay (device 59GN) connected acrossthe grounding resistor, as shown in Fig. 24. The relay usedfor this application should be tuned to fundamental frequencyvoltage and be insensitive to third-harmonic voltages that arepresent at the generator neutral under normal operatingconditions.

51GN Neutral Overvoltage Relay59GN Neutral Overvoltage Relay Tuned to the

Fundamental (60Hz) Frequency

Fig. 24. High-Resistance Grounded, Unit-connectedGenerator, Zero-Sequence Voltage Protection

Since the grounding resistance is large compared to thegenerator impedance and other impedance in the circuit, thefull phase-to-neutral voltage will be impressed across thegrounding device for a phase-to-ground fault at the generatorterminals. The voltage at the relay is a function of thedistribution transformer ratio and the location of the fault.The voltage will be a maximum for a terminal fault and willdecrease in magnitude as the fault location moves towardsthe generator neutral. Typically, the overvoltage relay has aminimum pickup setting of approximately 5 V. With this

Page 4: GroundingandGroundFaultProtectionofMultipleGeneratorsPart3

setting and with typical distribution transformer ratios, thisscheme is capable of detecting faults to within about 2-5% ofthe stator neutral. The time setting for the overvoltage relayis selected to provide coordination with other systemprotective devices. Specific areas of concern are:

1) When grounded wye-grounded wye voltagetransformers (vt) are connected at the generator terminals, theneutral ground overvoltage relay should be coordinated withthe vt fuses to prevent tripping the generator for vt secondaryground faults. This would require very careful selection of vtfuses.

2) The ground voltage relay (device 59GN) may have tobe coordinated with system relaying for system groundfaults. System phase-to-ground faults will induce zero-sequence voltages at the generator neutral due to capacitivecoupling between the windings of the unit transformer. Thisinduced voltage will appear on the secondary of thegrounding distribution transformer and can cause operationof the 59GN voltage relay.

A time overcurrent ground relay (device 51GN) can beused as backup protection when the generator is groundedthrough a distribution transformer with a secondary resistoras shown in Fig. 24. The current transformer supplying theovercurrent relay may be located either in the primary neutralcircuit or in the secondary circuit of the distributiontransformer.

VIII. ADDITIONAL PROTECTION METHODS

Additional protection methods are used to provide moresensitive protection against ground faults in generators thatare high-resistance grounded. These include 100% statorwinding ground fault protection and the use of a generatorneutral breaker.

a) 100% Stator Winding Ground Fault Protection

Conventional protection for stator ground fault detectionon high-resistance grounded systems has been discussed inthe previous section. These protective schemes are straight-forward and dependable. However, these relays wouldtypically provide sensitive protection for only about 95% ofthe stator winding. This is because the fault in the remaining5% of the winding, near the neutral, does not cause sufficient60 Hz residual voltage and residual current to operate theserelays. Even if fault current magnitudes for ground faultsclose to the neutral point are negligible in causing anyimmediate damage, potential severe damage can be causedfrom a second fault, especially when the first fault is near theneutral. Furthermore, if the second fault occurs in the samewinding, the generator differential relay may not operate at

all since this condition can be regarded as an internal turn-to-turn fault. Therefore, complete winding protection should beconsidered for large generators.

Special protection schemes based on detection or absenceof third-harmonic voltages or neutral/residual voltageinjection techniques are available to detect ground faults inthe generator stator close to the neutral points that mayotherwise go undetected using the typical protection schemesmentioned above. However, these are only applicable onhigh-resistance grounded, unit-connected generators. Third-harmonic voltage based techniques are widely used toprovide such protection. They are applicable where there issufficient third-harmonic neutral voltage to apply suchschemes.

The techniques based on the use of third-harmonicvoltage can be divided as follows:

i) Third-harmonic neutral undervoltage technique

ii) Third-harmonic residual terminal overvoltagetechnique

iii) Third-harmonic comparator technique

i) Third-harmonic neutral undervoltage technique

This technique uses the fact that for a fault near theneutral, the level of third-harmonic voltage at the neutraldecreases. Therefore, an undervoltage relay (device 27)operating from third-harmonic voltage measured at thegenerator neutral can be used to detect ground faults near theneutral. The ground faults in the remaining portion of thewindings can be detected by conventional ground faultprotection such as an overvoltage relay (device 59GN) whichoperates on the 60 Hz neutral voltage. The combination ofboth relays can provide 100% stator winding protection. Aprotection scheme using this technique is shown in Fig. 25.See IEEE Guide for Generator Ground Protection [1] fordetails.

ii) Third-harmonic residual terminal overvoltage technique

This technique is based on the fact that for a fault near theneutral, the level of third-harmonic voltage at the generatorterminals increases. Therefore, an overvoltage relay usingthird-harmonic voltage at the terminals of a generator can beused for detecting faults near the neutral. As before, theground faults in the remaining portion of the windings can bedetected by the conventional 95% protection, e.g., anovervoltage relay which operates on 60 Hz neutral voltage.Both of these relays can provide 100% protection of statorwindings by covering different portions of the windings. Aprotection scheme using this technique is shown in Fig. 26.

Page 5: GroundingandGroundFaultProtectionofMultipleGeneratorsPart3

Fig. 25. High-Resistance Grounded Generator, Third-Harmonic Undervoltage Ground Fault Protection Scheme

Fig. 26. High-Resistance Grounded Generator, Third-Harmonic Residual Terminal Voltage BasedGround Fault Protection Scheme

Page 6: GroundingandGroundFaultProtectionofMultipleGeneratorsPart3

59GN Overvoltage Relay Tuned to the Fundamental (60 Hz) Frequency59D Overvoltage Differential Relay Tuned to the Third Harmonic (180 Hz) Frequency

Fig. 27. High-Resistance Grounded Generator, Third-Harmonic Comparator Based Ground Fault Protection Scheme

iii) Third-harmonic comparator technique

This scheme compares the magnitude of the third-harmonic voltage at the generator neutral to that at thegenerator terminals. The scheme is based on the premisethat the ratio of the third-harmonic voltage at the generatorterminals to that at the generator neutral is almost constantduring the normal operation of a generator. This ratio isupset for a ground fault near the neutral or near theterminals of a generator, and this fact is used to detect thesefaults. The ground faults in the remaining portion of thewindings are detected by the conventional 95% ground faultprotection such as 60 Hz overvoltage or overcurrent relayoperating from the neutral voltage or current respectively.Fig. 27 shows a diagram of the comparator scheme.

b) Generator Neutral Breaker

While this is a possible aid in minimizing stator groundfault damage, the cost and potential risks of using a neutralbreaker result in few application of these devices. Asexplained in Part 1 of the paper under damage mechanismfor a stator ground fault, tripping the generator main breakeralone does not interrupt the current from the faultedgenerator. Providing a generator neutral breaker willminimize stator damage (iron burning) from internal faults.If a neutral breaker cannot be justified, stator damage can besignificantly reduced by accelerating decay of field flux byfield forcing to zero using de-excitation circuits.

IX. SUMMARY

This paper presented Part 3 of a four-part WorkingGroup Report on generator grounding and ground faultprotection. Part 3 discussed the various protection methodsapplied to the various grounding systems described in Part 2of this report. A review of their advantages and limitationswere given along with alternative solutions.

Part 1 of this Working Group Report provided anintroduction and discussion of the generator damagemechanism during stator ground faults. Part 2 described thevarious grounding methods used in industrial applications,highlighting their advantages and limitations. Part 4provides a conclusion and bibliography of additionalreference material on the subject of generator groundingand ground fault protection.

X. REFERENCES

[1] IEEE Guide for Generator Ground Protection, IEEEStandard C37.101, 1993.

[2] IEEE Guide for AC Generator Protection, IEEEStandard C37.102, 1995.

[3] “IEEE Tutorial on the Protection of SynchronousGenerators”, IEEE Document 95TP102, 1995.