Data sheet
Grid feeding monitoring relay acc. VDE AR-N 4105CM-UFD.M21
The CM-UFD.M21 is a multifunctional grid feeding
monitoring relay for three-phase mains. It provides
different monitoring functions in accordance with
VDE AR-N 4105 to detect over- and undervoltage
(10 minutes average value, voltage increase and
decrease protection) as well as any changes in
grid frequency (frequency increase and decrease
protection). Additionally, vector shift detection is
configurable.
Characteristics – Monitoring of three-phase mains for grid feeding – Type-tested in accordance with VDE AR-N 4105 – Two-channel measuring circuit and two processors to
ensure single-fault tolerance – Over- and undervoltage, 10 minutes average value as well
as over- and underfrequency monitoring – Two-tier threshold settings for over-/ undervoltage/
-frequency configurable according to ‘BDEW guideline for generating plants connected to the medium voltage grid’
– Vector shift detection configurable – Measured values, thresholds and settings shown on the
display – All threshold values adjustable as absolute values – Default setting according to VDE AR-N 4105 – True RMS measuring principle – 2 input contacts for feedback signal of subsequent
section switch – Monitoring of subsequent section switch configurable – Tripping delay for each threshold adjustable – Alarm memory for up to 99 entries (incl. cause of alarm,
measured value, relative timestamp) – Test function – Simulation mode – Code lock and mechanical sealing possible – 5 digital outputs (transistor outputs) for signalling the
cause of alarm to a superior control system – 2 c/o (SPDT) contacts – 105 mm (4.13 in) width – LEDs for the indication of operational states
Marks
a CE
2CD
C 2
51 0
03 S
0012
Order data
Grid feeding monitoring relay
Type Rated control supply voltage Measuring range Order code
CM-UFD.M21 24-240 V AC/DC 3 x 15-520 V AC 1SVR 510 730 R0300
2 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet
Functions
Operating controls
1 Button Test
2 Indication of operational states
Q1: red LED - overvoltage
Q2: red LED - undervoltage
Q3: red LED - overfrequency
Q4: red LED - underfrequency
Q5: red LED - error, if PR1 or PR2 activated 1)
3 Dj: red LED - vector shift
4 11: yellow LED - 1st c/o (SPDT) contact energized
21: yellow LED - 2nd c/o (SPDT) contact energized
5 Display (4-digits)
Voltage, 10 minutes average value, frequency or vector shift value,
alarm and error messages
6 Indication of time
Time: yellow LED - a time delay is displayed
7 Indication of device mode
8 Button Set / Reset ►
9 Button Up / Down ▲▼
10 Indication of operational states
L1: yellow LED - kind of measured value
L2: yellow LED - kind of measured value
L3: yellow LED - kind of measured value
N: yellow LED - kind of measured value
11 Status indication of device locking and sealable lock button
Red LED - device is locked
1) if PR3 or PR4 activated, 2nd threshold referring to LED Q1-Q4
More details see ‚LEDs, status information and fault messages‘ on page 9.
1 2 4
5
6
7
8
9
11 10
3
Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 3
Application
The CM-UFD.M21 is a monitoring relay for feeding in three-phase mains. The device is connected between the decentral electrical energy source such as photovoltaic systems, wind turbines, block-type thermal power stations and the public grid. In case the public grid is disconnected due to any reason, for instance during maintenance work, the CM-UFD.M21 recognizes this powerless situation. Then, in conjunction with a section switch, the CM-UFD.M21 disconnects the decentral electrical energy source from the public grid, shows the corresponding alarm on the display and signals the cause of alarm to a superior control system. The grid feeding monitoring relay detects over- and undervoltage (10 minutes average value, voltage increase and decrease protection) as well as any changes in grid frequency (frequency increase and decrease protection). Additionally, vector shift detection is configurable.
Operation
The CM-UFD.M21 can be used to monitor 3-wire as well as 4-wire AC systems. It provides 2 c/o (SPDT) contacts for disconnection of the decentral electrical energy source from the public grid and two separate input contacts for the feedback signal of the section switch in order to enable monitoring of the disconnection. Five transistor outputs allow the signalling of the cause of alarm to a superior control system. The unit is adjusted by front-face setting buttons and a display, which allows the visualization of measured values and alarms. Furthermore, the display enables the selection of presettings as well as the precise adjustment of threshold values and delay times. To disable vector shift detection, jumper terminals Dj1 and Dj2.
All operational states are shown on the display and signalled by the front-face LEDs. See table ‚Indication of operational states‘ on page 9.
Button Test
Pressing the front-face button Test de-energizes the output relays immediately in order to disconnect the decentral electrical energy source from the public grid. If the input contacts Y0, Y1, Y2 for the feedback loop of the section switch are connected and monitoring of the feedback signal is activated, the CM-UFD.M21 will display the disconnection time of the system (reaction time of CM-UFD.M21 + tripping time of the section switch) until further pressing of any button.
Vector shift detection
To disable vector shift detection, jumper terminals Dj1 and Dj2.
∆ϕ1 ∆ϕ2
2CD
C 2
52 0
16 F
0012
To set-up vector shift detection vSr, go to menu mode and see ‚Control charts‘ on page 7 for more details. The detection can be configured to single-phase1PH, to trip in case of a vector shift in one of the three phase, or three-phase 3PH, to trip only in case of a simultaneous vector shift in all three phases. After applying control supply voltage or opening contacts Dj1 and Dj2, the vector shift detection is suppressed for the duration of the adjusted suppression time dEon.
Display mode (backmost decimal point 6 OFF)
The CM-UFD.M21 always starts-up in display mode and shows the values (voltage, frequency, etc.) as well as alarm messages and error codes.
Set / Reset ►
Press shortly to display the next measured value / alarm counter.
Press for > 2 s to reset, quit error message.
Press for > 4 s to display the selected program (e.g. PR1).
Press for > 10 s to display the firmware version (e.g. 0-02).
Up / Down ▲▼
Press shortly to change to menu mode, display of alarm memory (button Down) or cumulative time of alarms (button Up). Additional pressing of button Set for > 2 s makes a reset of the stored values. Press button Up / Down for > 2 s to display the maximum / minimum measured values (device needs to be unlocked). Additional pressing of button Set for > 2 s deletes the stored values.
4 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet
Menu mode (backmost decimal point 7 ON)
Set / Reset ►
Press shortly to change to configuration mode.
Press for > 2 s to confirm last entry and return to display mode.
Up / Down ▲▼
Press shortly to select menu item; return to display mode.
If more than 30 seconds pass before a key is pressed, the CM-UFD.M21 automatically returns to display mode.
Configuration mode (backmost decimal point 7 flashing)
The display alternates between parameter name and currently set parameter value until either button Up or button Down is pressed to change the parameter value.
If more than 2 seconds pass before a key is pressed, the display starts to alternate again.
Set / Reset ►
Press shortly to confirm and go to next parameter.
Press for > 2 s to confirm last entry and return to display mode.
Up / Down ▲▼
Press shortly / for a long time to modify the value slowly / rapidly.
Press buttons Up and Down simultaneously to set the adjusted value to zero.
If more than 30 seconds (in simulation mode 15 minutes) pass before a key is pressed, the CM-UFD.M21 automatically applies the last entry and returns to display mode.
Simulation mode
The simulation mode allows the simulation of measured voltage and frequency values in order to check the settings and the correct tripping of the CM-UFD.M21. During the simulation, alarm and error messages will only be displayed via LEDs. If the device is sealed or locked, simulation is not possible. If the input contacts Y0, Y1, Y2 for the feedback loop of the section switch are connected and monitoring of the feedback signal is activated, the CM-UFD.M21 will display the disconnection time of the system (reaction time of CM-UFD.M21 + tripping time of section switch) until further pressing of any button.
To start simulation:1. Change to menu mode and select Si (button Up / Down) and press button Set.2. The display alternates between Si and the measurement parameter.3. Select the measurement parameter to be simulated (button Up / Down) and press button Set.4. The value of the simulated measurement parameter can be altered by pressing button Up / Down. Once the simulated
measurement value and the adjusted threshold value coincide, the output relays de-energize.
Note: The simulation of voltage values always takes into account the last set frequency value of simulation and vice versa.
To stop simulation:
Press button Set to return to menu mode. The CM-UFD.M21 continues to monitor the adjusted threshold values.
If more than 15 minutes pass before a key is pressed, the CM-UFD.M21 automatically returns to display mode.
Hint: If a threshold higher than the adjusted 10 minutes average value needs to be simulated, monitoring of UM has to be temporarily deactivated. The same applies to U,, when simulating U,, , and to U_ when simulating U__ in PR3…PR6.
Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 5
Alarm counter
The alarm counter Ac will be incremented at every alarm and logs up to 99 alarms, which allows the documentation of the number of alarms since last resetting.
To view the alarm counter, change to display mode and see ‚Control charts‘ on page 7 for more details.
Cumulative time of alarms
The cumulative time of alarms tAL displays the duration of all cumulated disconnections of the decentral electrical energy source from the public grid.
Recording only with applied control supply voltage.
To view the cumulative time of alarms, change to display mode and see ‚Control charts‘ on page 7 for more details.
Press button Set / Reset for > 2 s to reset cumulative time of alarms and alarm counter.
Alarm memory
The non-volatile alarm memory contains the last 99 alarms including simulated alarms. The LEDs indicate the cause of alarm and the display alternates between tripping value and relative timestamp [hours].
To view the alarm memory, change to display mode and see ‚Control charts‘ on page 7 for more details.
The alarm memory will only be reset when changing program.
Scan mode
The scan mode Scn allows the cyclic display of all measured values. The corresponding display duration dit for each measured value is adjustable. To start scan mode, change to display mode and see ‚Control charts‘ on page 7 for more details. To change the display duration dit, go to menu mode and see ‚Control charts‘ on page 7 for more details.
Display refresh rate
To change the display refresh rate ddi, go to menu mode and see ‚Control charts‘ on page 7 for more details.
Code lock
The code lock can be activated to protect the adjusted parameters.
To set Pin and lock the device:1. Change to menu mode and select CodE (button Up / Down) and press button Set2. Enter Pin - default setting 504 (button Up / Down) and press button Set
An incorrect Pin will be notified by Err flashing three times3. Set code lock to oFF or on (button Up / Down) and press button Set4. Enter new Pin (button Up / Down) or go to 5.) to keep Pin unchanged5. Press button Set to confirm
– on flashing three times, code lock activated – oFF flashing three times, code lock deactivated
Lock button (sealable)
Slightly lift the button cover and turn 180°. Actuate the Lock button by strong pressing on the button cover > 2 s (LED
starts flashing) until the CM-UFD.M21 is locked or unlocked .
In case of setting attempts Loc is displayed for 3 seconds if device has been locked.
Sealing
The Lock button can be sealed to protected against unauthorized changes.
6 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet
Electrical connection
A1
A1 A2
U <, U>, U>>, f<, f>, �ϕ
A2
Y0 Y1 Y2 L1 L2 L3 N
A2 Q1 Q2 Q3 Q4 Q5 12 11 14 22 21 24VQ
L3 N
11
12 14 22 24
21
L2L1
�ϕ1 �ϕ2
2CD
C 2
52 0
02 F
0012
A1-A2
L1, L2, L3, N
11-12/14
21-22/24
Y0-Y1
Y0-Y2
Dj1-Dj2
VQ
Q1
Q2
Q3
Q4
Q5
Control supply voltage
Measuring input
1st c/o (SPDT) contact
2nd c/o (SPDT) contact
1st input contact for feedback signal
2nd input contact for feedback signal
Vector shift detection
Jumper = vector shift detection disabled
Supply voltage of digital outputs
Digital output for overvoltage
Digital output for undervoltage
Digital output for overfrequency
Digital output for underfrequency
Digital output for:
error, if PR1 or PR2 activated
if PR3 or PR4 activated, 2nd threshold
referring to LED Q1-Q4
Connection diagram
Configuration and settings
Program setup
The suitable program must be set on the CM-UFD.M21 in accordance with the application. If the CM-UFD.M21 is sealed / locked (red LED on), sealing has to be deactivated first.
PR Connection Threshold values Voltage
1* 3 AC with N Low voltage
1 x overvoltage, 1 x undervoltage
1 x overfrequency, 1 x underfrequency
10 min average value, 1 x vector shift
230 V
2 3 AC w/o N 400 V
3 3 AC with N Medium voltage
2 x overvoltage, 2 x undervoltage
2 x overfrequency, 2 x underfrequency
10 min average value, 1 x vector shift
57.7 V
4 3 AC w/o N 100 V
5 3 AC with N 230 V
6 3 AC w/o N 400 V
* Default setting
Adjustment process:
If present, remove the seal (only authorized person)1. Apply control supply voltage at A1-A22. Slightly lift the button cover and turn 180°3. Actuate the small blue button by strong pressing on the button cover (LED starts flashing) until the flashing green LED
turns steady.4. Press button Up 1x -> Display InFo5. Press button Set / Reset 5x -> Display PR16. Set the program with the button Up / Down7. Press button Set / Reset 1x -> Display no8. Press button Down 1x -> Display yes9. Press button Set / Reset
Device resets and starts with the newly selected program
Hint: When changing programs, all parameters of the selected program are reset to "default settings" (see ‘Default settings and firmware version’ on page 11). Only change the parameters after having selected the correct program.
Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 7
Control charts
PR1 3 AC with N, PR2 3 AC w/o N, acc. to VDE-AR-N 4105
Display modeM
enu
mod
e
Configuration mode
1) 3AC+N = 300 V
[ ] = Unit
Pressing buttons Up and Down simultaneously, sets the values to the smallest one.
Code-Reset = Press button Set 2 s while applying control supply voltage (Pin = 504)
8 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet
PR3, PR5 3 AC with N, PR4, PR6 3 AC w/o N acc. to BDEW - Technical Guideline ‘Generating Plants Connected to the Medium-Voltage Network, Guideline for generating plants’ connection to and parallel operation with the medium-voltage network’, June 2008 issue.
Display mode
Men
u m
od
e
Configuration mode
1) 3AC+N = 300 V
[ ] = Unit
Pressing buttons Up and Down simultaneously, sets the values to the smallest one.
Code-Reset = Press button Set 2 s while applying control supply voltage (Pin = 504)
Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 9
Indication of operational states
LEDs, status information and fault messages
Function Q1:
re
d L
ED
>U
Q2:
re
d L
ED
<U
Q3:
re
d L
ED
>F
Q4:
re
d L
ED
<F
Q5:
re
d L
ED
Dj
: re
d L
ED
11-1
2/14
, 21
-22/
24:
yello
w L
ED
Tim
e:
yello
w L
ED
L1:
ye
llow
LE
D
L2:
ye
llow
LE
D
L3:
ye
llow
LE
D
N:
yello
w L
ED
re
d/g
ree
n L
ED
Dis
pla
y
Ba
ck
mo
st d
ec
ima
l p
oin
t
Output relay energized V
Indication of time V
Indication of device locking
V
red: lockedgreen:
unlocked
Display mode OFF
Menu mode V
Configuration mode X
Scan mode Measured values 1)
Error or 2nd threshold value in Pr3…6 V
10 minutes average value (UN) V OFF OFF OFF OFF OFF OFF OFF AL N + Measured value 2)
10 minutes average value (UN),
ON-delay activeOFF OFF OFF OFF OFF OFF V OFF Measured value 2)
10 minutes average value (UN),
OFF-delay activeW OFF OFF OFF OFF OFF OFF V Time
Overvoltage (U>) V OFF OFF OFF OFF OFF OFF OFF AL + Measured value 2)
Overvoltage (U>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overvoltage (U>), OFF-delay active W OFF OFF OFF OFF OFF OFF V Time
Overvoltage (U>>) V OFF OFF OFF V OFF OFF OFF AL + Measured value 2)
Overvoltage (U>>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overvoltage (U>>), OFF-delay active W OFF OFF OFF W OFF OFF V Time
Undervoltage (U<) OFF V OFF OFF OFF OFF OFF OFF AL + Measured value 2)
Undervoltage (U<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Undervoltage (U<), OFF-delay active OFF W OFF OFF OFF OFF OFF V Time
Undervoltage (U<<) OFF V OFF OFF V OFF OFF OFF AL + Measured value 2)
Undervoltage (U<<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Undervoltage (U<<), OFF-delay active OFF W OFF OFF W OFF OFF V Time
Overfrequency (f>) OFF OFF V OFF OFF OFF OFF OFF AL + Measured value 2)
Overfrequency (f>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overfrequency (f>), OFF-delay active OFF OFF W OFF OFF OFF OFF V Time
Overfrequency (f>>) OFF OFF V OFF V OFF OFF OFF AL + Measured value 2)
Overfrequency (f>>), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Overfrequency (f>>), OFF-delay active OFF OFF W OFF W OFF OFF V Time
Underfrequency (f<) OFF OFF OFF V OFF OFF OFF OFF AL + Measured value 2)
Underfrequency (f<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Underfrequency (f<), OFF-delay active OFF OFF OFF W OFF OFF OFF V Time
Underfrequency (f<<) OFF OFF OFF V V OFF OFF OFF AL + Measured value 2)
Underfrequency (f<<), ON-delay active OFF OFF OFF OFF OFF OFF V OFF Measured value 2)
Underfrequency (f<<), OFF-delay active OFF OFF OFF W W OFF OFF V Time
Vector shift detection OFF OFF OFF OFF V OFF OFF AL + Measured value 2)
Vector shift detection, OFF-delay active OFF OFF OFF OFF W OFF V Time
Measured value (Voltage L1 against N) V OFF OFF V
Measured value (Voltage L2 against N) OFF V OFF V
Measured value (Voltage L3 against N) OFF OFF V V
Measured value (Voltage L1 against L2) V V OFF OFF
Measured value (Voltage L2 against L3) OFF V V OFF
Measured value (Voltage L1 against L3) V OFF V OFF
Vector shift (L1, L2, L3) X X X
1) In scan mode, all measured values are displayed cyclicIy. The display duration dit is adjustable.
2) The adjusted measured value is displayed.
10 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet
Example of application
L1L2L3N
K1
*)
K2
A1
m6 A
A2 11
14 22 24
21
12 Y2 Y1 Y0
L2L1 L3 N
A
B
K1
K2
A
B
Low voltage grid
Inverter(s)Generator(s)Power plant
Optional use of n/o contacts, automatic recognition
For example, remote disconnection via ripple control receiver
in series with
Expansion of existing installation:
in series with
where applicable, a transformer
*)
A B
2CD
C 2
52 0
13 F
0212
Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 11
Default settings and firmware version
When changing program, all parameters are reset to the default settings.
Default settings
Low voltage Medium voltage
3 AC + N L-L: 400 V L-N: 230 V
3 AC L-L: 400 V
3 AC + N L-L: 100 V L-N: 57.7 V
3 AC L-L: 100 V
3 AC + N L-L: 400 V L-N: 230 V
3 AC L-L: 400V
Menu point Parameter Unit Pr1 1) Pr2 Pr3 Pr4 Pr5 Pr6
U,,
Ove
rvol
tage
2
U,,: Alarm on/off - - on on on on
U,,: Threshold value V - - 66.4 115 264 458
H,,: Hysteresis V - - 1.0 1.0 3.0 3.0
dAL: ON-delay s - - 0.10 0.10 0.10 0.10
doF: OFF-delay s - - 60 60 60 60
U,
Ove
rvol
tage
1
U,: Alarm on/off on on on on on on
U,: Threshold value V 264 458 62.3 108 249 430
H,: Hysteresis V 5.0 5.0 1.0 1.0 3.0 3.0
dAL: ON-delay s 0.10 0.10 60.00 60.00 60.00 60.00
doF: OFF-delay s 60 60 60 60 60 60
UM
10 m
in.
aver
age
UM: Alarm on/off on on off off off off
UM: Threshold value V 253 438 253 438 253 438
HM: Hysteresis V 3.0 3.0 3.0 3.0 3.0 3.0
dAL: ON-delay s 0.10 0.10 0.10 0.10 0.10 0.10
doF: OFF-delay s 60 60 60 60 60 60
U_
Und
ervo
ltage
1
U_: Alarm on/off on on On On on on
U_: Threshold value V 184 318 46.2 80.0 184 318
H_: Hysteresis V 5.0 5.0 1.0 1.0 3.0 3.0
dAL: ON-delay s 0.10 0.10 2.70 2.70 2.70 2.70
doF: OFF-delay s 60 60 60 60 60 60
U__
Und
ervo
ltage
2
U__: Alarm on/off - - off off off off
U__: Threshold value V - - 26.0 45.0 104 180
H__: Hysteresis V - - 1.0 1.0 2.0 2.0
dAL: ON-delay s - - 0.30 0.30 0.30 0.30
doF: OFF-delay s - - 60 60 60 60
F,,
Ove
rfre
que
ncy
2
F,,: Alarm on/off - - off off off off
F,,: Threshold value Hz - - 51.50 51.50 51.50 51.50
H,,: Hysteresis Hz - - 1.45 1.45 1.45 1.45
dAL: ON-delay s - - 0.10 0.10 0.10 0.10
doF: OFF-delay s - - 60 60 60 60
F,
Ove
rfre
que
ncy
1
F,: Alarm on/off on on on on on on
F,: Threshold value Hz 51.50 51.50 51.50 51.50 51.50 51.50
H,: Hysteresis Hz 1.45 1.45 1.45 1.45 1.45 1.45
dAL: ON-delay s 0.10 0.10 0.10 0.10 0.10 0.10
doF: OFF-delay s 60 60 60 60 60 60
12 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet
Default settings
Low voltage Medium voltage
3 AC + N L-L: 400 V L-N: 230 V
3 AC L-L: 400 V
3 AC + N L-L: 100 V L-N: 57.7 V
3 AC L-L: 100 V
3 AC + N L-L: 400 V L-N: 230 V
3 AC L-L: 400V
Menu point Parameter Unit Pr1 1) Pr2 Pr3 Pr4 Pr5 Pr6
F_
Und
erfr
eque
ncy
1 F_: Alarm on/off on on on on on on
F_: Threshold value Hz 47.50 47.50 47.50 47.50 47.50 47.50
H_: Hysteresis Hz 1.00 1.00 1.00 1.00 1.00 1.00
dAL: ON-delay s 0.10 0.10 0.10 0.10 0.10 0.10
doF: OFF-delay s 60 60 60 60 60 60
F__
Und
erfr
eque
ncy
2 F__: Alarm on/off - - off off off off
F__: Threshold value Hz - - 47.50 47.50 47.50 47.50
H__: Hysteresis Hz - - 1.00 1.00 1.00 1.00
dAL: ON-delay s - - 0.10 0.10 0.10 0.10
doF: OFF-delay s - - 60 60 60 60
v5r
Vect
or s
hift
v5r: Alarm on/off off off off off off off
vsr: Threshold value ° 10.0 10.0 10.0 10.0 10.0 10.0
doF: OFF-delay s 3 3 3 3 3 3
dEon: Suppression time s 2 2 3 3 3 3
v5r: Number of phases 3ph 3ph 3ph 3ph 3ph 3ph
rEL
Sec
tion
switc
h
trEL: Switching time Y1,Y2 s 5.0 5.0 off off off off
ddi
Dis
pla
y ddi: Display refresh rate s 0.5 0.5 0.5 0.5 0.5 0.5
dit: Display duration SCn
s 3.5 3.5 3.5 3.5 3.5 3.5
Si
Sim
ulat
ion U: Voltage V 230 400 57.7 100 230 400
F: Frequency Hz 50.00 50.00 50.00 50.00 50.00 50.00
v5r: Vector shift ° 0.0 0.0 0.0 0.0 0.0 0.0
CodE Pin pin: Pin code 504 504 504 504 504 504
Info Info
fnr: Firmware version 0-02 0-02 0-02 0-02 0-02 0-02
snr: Serial number xxxxx xxxxx xxxxx xxxxx xxxxx xxxxx
h: Operating hours h xxxxx xxxxx xxxxx xxxxx xxxxx xxxxx
err: Error counter xxx xxx xxx xxx xxx xxx
Pr: Program 1 2 3 4 5 6
1) factory preset
2) A mains power failure, caused by external switching, normally generates a vector shift. Experience shows that these vector shifts during switching
operations in the grid are up to 5 °. In case of disturbances in the grid, the vector shifts are higher and may damage the generator, e.g. at the
power unit or coupling.
Protective functions, default settings according to VDE-AR-N 4105 section 6.5.2:
Terms according to VDE-AR-N 4105
Overvoltage monitoring U, Voltage increase protection U>> 1,15 Un 100 ms
10 minutes average value UM Voltage increase protection U> 1,1 Un 100 ms
Undervoltage monitoring U_ Voltage decrease protection U< 0,8 Un 100 ms
Overfrequency monitoring F, Frequency increase protection f> 51,5 Hz 100 ms
Underfrequency monitoring F_ Frequency decrease protection f< 47,5 Hz 100 ms
Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 13
Troubleshooting
Error Cause Remedy
EEEE or -EEE
appears in the display
Measured voltage, frequency or the vector
shift is too large or too small
Consider the measuring range
Err4 appears in the display Too high internal measurement deviation of the
two measuring channels
Perform a reset:
Interrupt the conrol supply voltage for >5 s
Err5 appears in the display Error internal regulation
Err6 appears in the display Communication error internal interface
Err7 appears in the display + LED of the
faulty output circuit is on
Error feedback contacts Feedback contacts not connected
- set trEl -> off
Feedback contacts connected
- check the correct connection
- adjust the turn-on time of the section switch
under trEL.
- perform a reset:
Interrupt the conrol supply voltage for >5 s
Err8 appears in the display Hysteresis error: overlapping of the release
points
Upper threshold value must be higher than
the lower threshold value, check the threshold
values
Err9 appears in the display Configuration error Reset to factory settings, see ‚Program setup‘
on page 6
A time expires in the display If an OFF-delay dof is active, the time runs
down in the display (the shortest one first)
Wait until the time is complete (depending on
the setting, several times may elapse one after
the other)
Device cannot be configured / only the
threshold values can be configured
Code lock / Sealing activated When having problems with the code lock (Pin
forgotten), the lock can be deactivated and the
Pin can be reset to 504, by pressing the button
► until Code / off is shown in the display,
while switching on the control supply voltage.
Implausible voltage values Pr selected with N, but N not connected Select Pr without N or connect N
Loc appears in the display Sealing is active See ‚Program setup‘ on page 6
Code appears in the display Code lock is active See ‚Code lock‘ on page 5
14 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet
Technical data
Data at Ta = 25 °C and rated values, unless otherwise indicated
Input circuits
Type CM-UFD.M21
Supply circuit A1-A2
Rated control supply voltage Us 24-240 V AC/DC
Rated control supply voltage Us tolerance -15...+20 %
Rated frequency DC and 50/60 Hz respectively
Frequency range AC 40-70 Hz
Typical current / power consumption 24 V DC 92 mA / 2.2 W
230 V AC 25 mA / 5.7 VA
Power failure buffering time 5 ms
Measuring circuit L1, L2, L3 (N)
Monitoring functions over-/undervoltage U,,, U, / U_, U__ yes, can be switched off
over-/underfrequency F,,, F, / F_, F__ yes, can be switched off
10 minutes average value per phase UM yes, can be switched off
vector shift v5r yes, can be switched off
Measuring ranges over-/undervoltage U,,, U, / U_, U__ 10-310 V AC (L1, L2, L3, N)
15-530 V AC (L1, L2, L3)
over-/underfrequency F,,, F, / F_, F__ 40-70 Hz
vector shift v5r 0…+45°
Threshold values over-/undervoltage, 10 minutes average value
U,,, U, / U_, U__, UM
15-300 V AC, adjustable in 0.1 V steps (< 100 V)
/ in 1 V steps (> 100 V) (L1, L2, L3, N)
15-520 V AC, adjustable in 0.1 V steps (< 100 V)
/ in 1 V steps (> 100 V) (L1, L2, L3)
over-/underfrequency F,,, F, / F_, F__ 45-65 Hz, adjustable in 0.01 Hz steps
vector shift v5r 2-20 °, adjustable in 0.1° steps
Hysteresis related to
the threshold value
over-/undervoltage,
10 minutes average value H,,, H, / H_, H__, HM1.0-99.9 V, adjustable in 0.1 V steps
over-/underfrequency H,,, H, / H_, H__ 0.05-10.00 Hz, adjustable in
0.05 Hz steps
Accuracy of
measurements
voltage measurement L1,L2,L3,N ± 0.6 % of measured value
voltage measurement L1,L2,L3 ± 0.8 % of measured value
frequency measurement ± 0.04 Hz ± 1 digit
Display accuracy > 100 V: ± 1 digit (1 V)
< 100 V: ± 1 digit (0.1 V)
Rated frequency of measuring signal 50/60 Hz
Frequency range of the measuring signal 40-70 Hz
Measuring principle True RMS
Max. reaction time (Measuring cycle CM-UFD.M21 +
switching time of the relays)
overvoltage U,,, U, < 65 ms
undervoltage U_, U__ < 65 ms
overfrequency F,,, F, < 65 ms
underfrequency F_, F__ < 65 ms
10 minutes average value per
phase UMdepending on the voltage jump
vector shift v5r < 50 ms
Accuracy within the rated control supply voltage tolerance DU ≤ 0.1 %
Accuracy within the temperature range DU ≤ 0.15 % / °C
Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 15
Feedback contacts Y0, Y1, Y2
Number 2
Kind of inputs signal source (Y0)
feedback loop section switch 1 (Y1)
feedback loop section switch 2 (Y2)
Electrical isolation from the supply voltage yes
from the measuring circuit no
from the relay outputs yes
from the transistor outputs yes
Type of triggering volt-free triggering
Max. switching current in the control circuit 4 mA
Max. cable length at the control input 5 m
No-load voltage at the control inputs < 35 V DC
Feedback time section switch trEL 0.5-99.0 s, adjustable in 0.1 s steps
Control circuit vector shift detection Dj1-Dj2
Type of triggering volt-free triggering
Electrical isolation from the supply voltage yes
from the measuring circuit no
from the relay outputs yes
from the transistor outputs yes
Control input, control function jumpered = vector shift detection de-activated
open = vector shift detection activated (additional
configuration in the software is necessary)
Max. switching current in the control circuit 4 mA
Max. cable length at the control input 5 m
No-load voltage at the control inputs < 35 V DC
Timing circuits
Start-up delay (prior to first grid connection) see 'adjustable OFF-delay' dof
Restart delay (after a short-term interruption <3 s) 5 s (fixed)
Tripping delay ON-and/or OFF-delay configurable
Adjustment range of the ON-delay over-/undervoltage, over-/
underfrequency dAL0.05-60.00 s, adjustable in 0.01 s steps
Tolerance of the ON-delay 0.1 % ± 5 ms
Adjustment range of the OFF-delay over-/undervoltage, over-/
underfrequency doF0 (>200 ms)-999 s, adjustable in 1 s steps
vector shift doF 3-240 s, adjustable in 1 s steps
Tolerance of the OFF-delay 0.1 % ± 105 ms
Delayed activation of the vector shift detection dEon
2-20 s, adjustable in 1 s steps
(Delay is effective just once after switching on or
restart)
Accuracy within the rated control supply voltage tolerance Dt ≤ 0.01 %
Accuracy within the temperature range Dt ≤ 0.0001 % / °C
User interface
Indication of operational states
See ‚Indication of operational states‘ on page 9
16 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet
Output circuits
Relay outputs
Kind of outputs 11-12/14 Relay, 1st c/o (SPDT) contact
21-22/24 Relay, 2nd c/o (SPDT) contact
2 x 1 c/o (SPDT) contact
Operating principle closed-circuit principle
Contact material AgNi
Rated operational voltage Ue (IEC/EN 60947-1) 250 V AC
Minimum switching voltage / minimum switching current 12 V / 10 mA
Maximum switching voltage / maximum switching current 400 V AC / 6A
Rated operational current Ie(IEC/EN 60947-5-1) AC12 (resistive) 230 V 6 A
AC15 (inductive) 230 V 1.5 A
DC12 (resistive) 24 V 6 A
DC13 (inductive) 24 V 2 A
Mechanical lifetime 30 x 106 switching cycles
Electrical lifetime at AC12, 230 V AC, 6 A 1 x 106 switching cycles
Maximum fuse rating to achieve short-circuit protection n/c contact 6 A, operating class gG/gL
n/o contact 6 A, operating class gG/gL
Conventional thermal current Ith (IEC/EN 60947-1) 6 A
Transistor outputs
Number 5
Rated operational voltage Ue 24 V DC
Operational voltage range 4.5-27 V DC
Residual ripple 5 %
Current state "0" max. 0.1 mA / output
state "1" max. 20 mA / output
Electrical isolation from the supply voltage yes
from the measuring circuit yes
from the relay outputs yes
from the inputs of the
feedback contactsyes
Maximum fuse rating to achieve short-circuit protection 100 mA fast-acting
General data
MTBF on request
Duty time 100%
Dimensions (W x H x D) product dimensions 105 x 90 x 69 mm (4.13 x 3.54 x 2.72 in)
packaging dimensions 175 x 107 x 130 mm (6.89 x 4.21 x 5.12 in)
Weight net weight 0.225 kg (0.496 lb)
gross weight 0.343 kg (0.756 lb)
Mounting DIN rail (IEC/EN 60715) TH 35-7.5 and
TH 35-15, snap-on mounting without any tool
Mounting position any
Minimum distance to other units vertical not necessary
horizontal not necessary
Degree of protection housing / terminals IP30 / IP20
Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 17
Electrical connection
Wire size fine-strand with(out) wire end ferrule 1 x 0.5 - 2.5 mm² (1 x 20 - 14 AWG)
rigid 1 x 0.5 - 4 mm² (1 x 20 - 12 AWG)
Stripping length 7 mm (0.28 in)
Tightening torque 0.5 Nm (4.42 lb.in)
Environmental data
Ambient temperature ranges operation -20...+55 °C
storage -20…+70 °C
transport -20…+70 °C
Damp heat, cyclic (IEC 60068-2-30) 55 °C, 6 cycles
Climatic category (EN 50178) 3K3
Vibration, sinusoidal (IEC/EN 60255-21-1) Class 1
Shock (IEC/EN 60255-21-2) Class 1
Isolation data
Rated insulation voltage Ui
(IEC/EN 60947-1, IEC/EN 60664-1)
supply/measuring/output circuits300 V
output circuit 1/output circuit 2
Rated impulse withstand voltage Uimp
(IEC/EN 60947-1, IEC/EN 60664-1)
supply/measuring/output circuits4 kV
output circuit 1/output circuit 2
Basic insulation (IEC/EN 60664-1) supply/measuring/output circuits300 V
output circuit 1/output circuit 2
Test voltage, routine test
(IEC/EN 60255-27, IEC/EN 61010-1)
supply/measuring/output circuits3820 V DC
output circuit 1/output circuit 2
Test voltage, type test
(IEC/EN 60255-27)
supply/measuring/output circuits4600 V DC
output circuit 1/output circuit 2
Protective separation
(IEC/EN 61140, EN 50178)
supply/measuring/output circuits300 V
output circuit 1/output circuit 2
Pollution degree (IEC/EN 60664-1) 2
Overvoltage category (IEC/EN 60664-1) III
Standards / Directives
Product standard IEC/EN 60255
Application standards VDE-AR-N 4105, BDEW
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
RoHS Directive 2002/95/EC
Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-1, IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kV / 8 kV
radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3, 10 V/m (80-1000 MHz)
Level 2, 3 V/m (1400-2000 MHz)
Level 1, 1 V/m (2000-2700 MHz)
electrical fast transient / burst IEC/EN 61000-4-4 Level 4, 4 kV / 5 kHz
surge IEC/EN 61000-4-5 Level 3, 1 kV L-L, 2kV L-earth
conducted disturbances, induced by
radio-frequency fields
IEC/EN 61000-4-6 Level 3, 10 V
Interference emission IEC/EN 61000-6-3, IEC/EN 61000-6-4
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B
18 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet
Technical diagrams
Load limit curves
300
200
100 80 60 50 40 30
20
10 1 2 4 6 10
I A
V
U
0.1 0.2 0.5
resistive load
2CD
C 2
52 0
10 F
0212
AC load (resistive)
300
200
100 80 60 50 40 30
20
10 1 2 5 10
I A
V
U
0.1 0.2 0.5
resistive load
2CD
C 2
52 0
11 F
0212
DC load (resistive)
104
2 4 6 8 10 12 14 16
105
106
107
Switching current [A]
250 V ACresistive load
Sw
itchi
ng c
ycle
s
2CD
C 2
52 0
12 F
0212
Contact lifetime
Data sheet | CM-UFD.M21 - Grid feeding monitoring relay - 19
Dimensions
in mm and inches
48 1.89”
45 1.77
”
90 3.54
”
3 0
.12”
61.8
2.43
”
16.5 0.65”
105 4.13”
58 2.28”
2CD
C 2
52 0
08 F
0012
Further documentation
Document title Document type Document number
Electronic products and relays Technical catalogue 2CDC 110 004 C020x
CM-UFD.M21 Grid feeding monitoring relay Instruction sheet 1SVC 510 810 M0000
You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products -> Electronic Relays and Controls -> Three Phase Monitors.
20 - CM-UFD.M21 - Grid feeding monitoring relay | Data sheet
Note:We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB AG.
Copyright© 2012 ABB All rights reserved
Contact us
Do
cum
ent
num
ber
2C
DC
112
193
D02
01 (0
9.20
12)ABB STOTZ-KONTAKT GmbH
P. O. Box 10 16 8069006 Heidelberg, GermanyPhone: +49 (0) 6221 7 01-0Fax: +49 (0) 6221 7 01-13 25E-mail: [email protected]
You can find the address of your local sales organisation on the ABB home pagehttp://www.abb.com/contacts -> Low Voltage Products and Systems