FUME HOODS HIGH PERFORMANCE WINDOWS FREE COOLING Energy recovery coils in air handlers pre-heat outside air while generating “free” chilled water when outside temperature is below 50°F “Free” chilled water can be used at G.G. Brown or be delivered to the North Campus chiller plant Chilled water is used at G.G. Brown for air handlers, fan coils and chilled beams CHILLED WATER Because of heat gain from lab equipment lab spaces require cooling year round. At the G.G. Brown Addition the heat from lab equipment is used to preheat ventilation air in the winter using the chilled water system. After the chilled water is cooled again from the cold ventilation air it is sent back to cool the lab spaces. This cycle continues, creating a perpetual “Free Cooling” process. The labs at G.G. Brown implement a variety of innovative fume hood technologies to save energy while maintaining a safe environment. Among these technologies are variable volume fume hoods with sash position sensors and reduced face velocity fume hoods. Glass was selected that reduces the amount of solar energy transmission into the building while still providing a large amount of natural light The Transparent design along with a giant LED wall showing abstract samples of active lab work creates a distinct presence on campus for the College of Engineering. PHOTO-VOLTAIC SOLAR PANELS Photo-Voltaic solar panels on the roof of the G.G. Brown Addition generate enough electricity to support 1% of the total building energy use. This ultimately reduces the environmental and economic impacts associated with the use of fossil fuels. Solar collectors on the roof use energy from the sun to heat domestic water for use in lavatories and sinks. This helps to reduce the consumption of steam. SOLAR WATER HEATING “FINDING SOLUTIONS AT THE FRONTIERS OF MECHANICAL ENGINEERING” LEED GOLD CERTIFIED DEVELOPING SUSTAINABLE SITES The site for the G.G. Brown Addition was previously a parking lot, selected to limit the disturbance of previously undeveloped land. The project restored more than 50% of the total site to native vegetation. The conversion of the existing parking lot to vegetation also reduced the volume of storm runoff by 25%. The use of high efficiency plumbing fixtures provides a 36% water use reduction when compared to fixture performance requirements of the Energy Policy Act of 1992. WATER USE REDUCTION 50% OF THE TOTAL SITE RESTORED TO NATIVE VEGETATION 25% REDUCTION OF STORMWATER RUNOFF 40% G.G. Brown Addition avoids excessive energy use by implementing a superior building envelope to minimize heat loss and by executing modern heating, ventilation and air conditioning strategies. G.G. Brown Addition exceeds the performance of a code minimum building by 40%. OPTIMIZE ENERGY PERFORMANCE THE G.G. BROWN ADDITION University of Michigan’s next-generation nano-mechanical engineering lab complex enables researchers to study the forces at work at the smallest scales and to advance nano-technologies in energy, manufacturing, healthcare and biotechnology. It houses The Center of Excellence in Nano Mechanical Science and Engineering and includes a state-of-the-art Ultra-Low Vibration Facility. Core laboratory and collaborative spaces are extremely flexible and shared by the occupants, as well as other researchers in the building to promote synergy and interdisciplinary engineering research. SUPPORTS 1% OF TOTAL BUILDING ENERGY USE 36% WATER USE REDUCTION THE G.G. BROWN ADDITION Building Use Location Size Number of Occupants LEED version LEED certification level ASHRAE 90.1 version Energy cost savings compared to ASHRAE baseline Total energy savings Total electrical savings Total gas savings CO2 emissions avoided Water fixture baseline Total water savings On-site renewable energy generation Construction/Demolition waste diverted from landfill Insulation (R-Value)* Wall assembly - above grade Wall assembly - below grade Roof assembly Glazing - Curtain wall system U-value** Solar Heat Gain Coefficient (SHGC)** Glazing - Fixed assembly U-value** Solar Heat Gain Coefficient (SHGC)** Glazing - Visible Light Transmittance (VT)*** Project Team Owner Architect Engineer Contractor Commissioning Authority Project Management v2009 Gold 2007 40.7% $125,168/ year 727,252 KWh / year 77,655 Therms / year 986 tons Energy Policy Act of 1992 36% 1% 82% Project 46.9 23.3 58.8 0.339 0.37 0.42 0.35 0.68 Code 15.6 8.4 20.8 0.45 0.40 0.55 0.40 University of Michigan - Michigan Engineering Integrated Design Solutions with Perkins & Will Integrated Design Solutions DeMaria Building Company U-M AEC U-M AEC Design Period: 10/2009 - 02/2012 Construction Period: 04/2012 - 08/2014 * The higher the R-value the better the insulating quality ** The lower the U-value and SHGC the more energy efficient the window *** The higher the VT value the more daylight in the space. VT is measured between 0 and 1 Engineering Lab Building Ann Arbor, Michigan 62,500 Square Feet 98 Sustainability Facts GG Brown Engineering Building / Addition r r recovery coils in air handlers pre-he ea at t outside e g ge e en n ne e er r ra a at t ti i in n ng g g f f f fr re e e ee e ec c ch h hi i il l ll l le e ed d d w w wa a at t te e er when outside ature is below 50°F chilled d w water can be used at ro ow wn n o or r be delivered to th h Campus chiller pla an nt water is used at rown for air handlers, s and chilled beams LLED WATER CHILLED WATER TO GG BROWN OUTSIDE AIR PUMP “FREE” CHILLED WATER NORTH CAMPUS CHILLER PLANT ENERGY RECOVERY COILS LAB SUPPLY AIR HAZARDOUS FUME HOOD EXHAUST AIR GENERAL LAB EXHAUST AIR SENSIBLE HEAT WHEEL TOTAL ENTHALPY WHEEL OUTSIDE AIR INTAKE ENERGY RECOVERY COIL VARIABLE VOLUME LAB EXHAUST FANS Solar collec the roof use from the sun domestic wat in lavatories a This helps t the consum S OLA R WATE R HE ATI N SOLAR THERMAL COLLECTOR COLD WATER PUMP PUMP DOMESTIC HOT WATER SYSTEM STORAGE TANK HEAT EXCHANGER GG Brown Engineering Building Addition U-M Project Number P00002049 U-M Building Number 1000407 INTEGRATED DESIGN SOLUTIONS ARCHITECTS & ENGINEERS IN ASSOCIATION WITH PERKINS + WILL NATIONAL DESIGN PARTNER

GG Brown Engineering Building / Addition “FINDING

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

FUME HOODS

HIGH PERFORMANCE

WINDOWS

FREE COOLING

Energy recovery coils in air handlers pre-heat outside air while generating “free” chilled water when outside temperature is below 50°F

“Free” chilled water can be used at G.G. Brown or be delivered to the North Campus chiller plant

Chilled water is used at G.G. Brown for air handlers, fan coils and chilled beams

CHILLED WATER

Because of heat gain from lab equipment lab spaces require cooling year round. At the G.G. Brown Addition the heat from lab equipment is used to preheat ventilation air in the winter using the chilled water system. After the chilled water is cooled again from the cold ventilation air it is sent back to cool the lab spaces. This cycle continues, creating a perpetual “Free Cooling” process.

The labs at G.G. Brown implement a variety of innovative fume hood technologies to save energy while maintaining a safe environment. Among these technologies are variable volume fume hoods with sash position sensors and reduced face velocity fume hoods.

Glass was selected that reduces the amount of solar energy transmission into the building while still providing a large amount of natural light

The Transparent design along with a giant LED wall showing abstract samples of active lab work creates a distinct presence on campus for the College of Engineering.

PHOTO-VOLTAIC SOLAR PANELSPhoto-Voltaic solar panels on the roof of the G.G. Brown Addition generate enough electricity to support 1% of the total building energy use. This ultimately reduces the environmental and economic impacts associated with the use of fossil fuels.

Solar collectors on the roof use energy from the sun to heat domestic water for use in lavatories and sinks. This helps to reduce the consumption of steam.

SOLAR WATER HEATING

“FINDING SOLUTIONS AT THE FRONTIERS

OF MECHANICAL ENGINEERING”

LEEDGOLD

CERTIFIED

DEVELOPING SUSTAINABLE SITES The site for the G.G. Brown Addition was previously a parking lot, selected to limit the disturbance

of previously undeveloped land. The project restored more than 50% of the total site to native vegetation. The conversion of the existing parking lot to vegetation also reduced the volume of storm

runoff by 25%.

The use of high effi ciency plumbing fi xtures provides a 36% water use

reduction when compared to fi xture performance requirements of the

Energy Policy Act of 1992.

WATER USE REDUCTION

50% OF THE TOTAL SITE RESTORED TO NATIVE VEGETATION

25% REDUCTION OF STORMWATER RUNOFF

40%

G.G. Brown Addition avoids excessive energy use by implementing a superior building envelope

to minimize heat loss and by executing modern heating, ventilation and air conditioning strategies.

G.G. Brown Addition exceeds the performance of a code minimum

building by 40%.

OPTIMIZE ENERGY PERFORMANCE

THE G.G. BROWN ADDITION

University of Michigan’s next-generation nano-mechanical engineering lab complex enables researchers to study the forces at work at the smallest scales and to advance nano-technologies in energy, manufacturing, healthcare and biotechnology. It houses The Center of Excellence in Nano Mechanical Science and Engineering and includes a state-of-the-art Ultra-Low Vibration Facility. Core laboratory and collaborative spaces are extremely fl exible and shared by the occupants, as well as other researchers in the building to promote synergy and interdisciplinary engineering research.

SUPPORTS 1% OF TOTAL BUILDING ENERGY USE

36% WATER USEREDUCTION

THE G.G. BROWN ADDITION

Building UseLocationSizeNumber of Occupants

LEED version LEED certification levelASHRAE 90.1 version Energy cost savings compared to ASHRAE baselineTotal energy savings Total electrical savings Total gas savings CO2 emissions avoidedWater fixture baseline Total water savingsOn-site renewable energy generation Construction/Demolition waste diverted from landfill

Insulation (R-Value)* Wall assembly - above grade Wall assembly - below grade Roof assemblyGlazing - Curtain wall system U-value** Solar Heat Gain Coefficient (SHGC)**Glazing - Fixed assembly U-value** Solar Heat Gain Coefficient (SHGC)**Glazing - Visible Light Transmittance (VT)***

Project Team Owner Architect Engineer Contractor Commissioning Authority Project Management

v2009Gold2007

40.7%$125,168/ year

727,252 KWh / year77,655 Therms / year

986 tonsEnergy Policy Act of 1992

36%1%

82%

Project46.923.358.8

0.3390.37

0.420.350.68

Code15.6

8.420.8

0.450.40

0.550.40

University of Michigan - Michigan EngineeringIntegrated Design Solutions with Perkins & Will

Integrated Design SolutionsDeMaria Building Company

U-M AECU-M AEC

Design Period: 10/2009 - 02/2012

Construction Period: 04/2012 - 08/2014

* The higher the R-value the better the insulating quality

** The lower the U-value and SHGC the more energy efficient the window

*** The higher the VT value the more daylight in the space. VT is measured between 0 and 1

Engineering Lab BuildingAnn Arbor, Michigan

62,500 Square Feet98

Sustainability FactsGG Brown Engineering Building / Addition

rrrecovery coils in air handlers pre-heeaatt outside e ggeeennneeerrraaatttiiinnnggg “““ffffrreeeeeee” ccchhhiiilllllleeeddd wwwaaattteeer when outside ature is below 50°F

chilledd wwater can be used at roowwnn oorr be delivered to thh Campus chiller plaannt

water is used at rown for air handlers, s and chilled beams

LLED WATER

CHILLED WATERTO GG BROWN

OUTSIDE AIR

PUMP

“FREE” CHILLED WATER

NORTH CAMPUS CHILLER

PLANT

ENERGY RECOVERY

COILS

LAB SUPPLY

AIR

HAZARDOUS FUME HOOD EXHAUST AIR

GENERAL LAB EXHAUST AIR

SENSIBLE HEAT WHEEL

TOTAL ENTHALPY WHEEL

OUTSIDE AIR INTAKE

ENERGY RECOVERY COIL

VARIABLE VOLUME LAB EXHAUST FANS

Solar collecthe roof usefrom the sundomestic watin lavatories aThis helps tthe consum

SOLARWATERHEATIN

SOLAR THERMAL

COLLECTOR

COLD WATER

PUMP

PUMP

DOMESTIC HOT WATER

SYSTEM

STORAGE TANK

HEATEXCHANGER

GG Brown Engineering Building Addition

U-M Project Number

P00002049

U-M Building Number

1000407