Page 1: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

Geotextile Sand Filter

CORPORATIONInnovative Environmental Products & Solutions Since 1970

Tech1
Typewritten Text
Tech1
Typewritten Text
Massachusetts Design & Installation Manual
Tech1
Typewritten Text
Tech1
Typewritten Text
Tech1
Typewritten Text
June 2013 www.eljen.com
Page 2: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 2 www.eljen.com

Table of Contents

SUBJECT: PAGE

GLOSSARY OF TERMS ................................................................................................................................................................ 3 INTRODUCTION ........................................................................................................................................................................... 5 GSF SYSTEM DESCRIPTION ...................................................................................................................................................... 6 TESTING AND PERFORMANCE .................................................................................................................................................. 7 1.0 GENERAL DESIGN AND INSTALLATION .............................................................................................................................. 8 2.0 TRENCH SIZING AND INSTALLATION GUIDELINES ......................................................................................................... 11 3.0 BED SIZING AND INSTALLATION GUIDELINES ................................................................................................................. 21 4.0 MOUND INSTALLATION GUIDELINES ................................................................................................................................ 30 5.0 PUMP DOSING DISTRIBUTION GUIDANCE ....................................................................................................................... 33 6.0 PRESSURE DISTRIBUTION GUIDANCE ............................................................................................................................. 33 7.0 PUMP CONTROLS ................................................................................................................................................................ 34 8.0 SYSTEM VENTILATION ........................................................................................................................................................ 35 9.0 INSPECTION/MONITORING PORT ...................................................................................................................................... 38

GSF DRAWINGS AND TABLES:

DRAWINGS: FIGURE 1: GSF SYSTEM OPERATION ............................................................................................................................. 6 FIGURE 2: TYPICAL B43 GSF CROSS SECTION ............................................................................................................. 8 FIGURE 3: TYPICAL A42 GSF CROSS SECTION ............................................................................................................. 8 FIGURE 4: PLAN VIEW – SINGLE ROW B43 TRENCH SYSTEM – LEVEL SITE ........................................................... 13 FIGURE 5: CROSS SECTION – SINGLE ROW B43 TRENCH SYSTEM – LEVEL SITE ................................................. 13 FIGURE 6: PLAN VIEW – MULTIPLE ROW B43 TRENCH SYSTEM – LEVEL SITE ...................................................... 14 FIGURE 7: CROSS SECTION – MULTIPLE ROW B43 TRENCH SYSTEM – LEVEL SITE ............................................ 14 FIGURE 8: CROSS SECTION – MULTIPLE ROW B43 TRENCH SYSTEM – SLOPING SITE ........................................ 15 FIGURE 9: PLAN VIEW – SINGLE ROW A42 TRENCH SYSTEM – LEVEL SITE ........................................................... 18 FIGURE 10: CROSS SECTION – SINGLE ROW A42 TRENCH SYSTEM – LEVEL SITE ................................................. 18 FIGURE 11: PLAN VIEW – MULTIPLE ROW A42 TRENCH SYSTEM – LEVEL SITE ...................................................... 19 FIGURE 12: CROSS SECTION – MULTIPLE ROW A42 TRENCH SYSTEM – LEVEL SITE ............................................ 19 FIGURE 13: CROSS SECTION – MULTIPLE ROW A42 TRENCH SYSTEM – SLOPED SITE ......................................... 20 FIGURE 14: PLAN VIEW – B43 BED SYSTEM – LEVEL SITE .......................................................................................... 24 FIGURE 15: CROSS SECTION – B43 BED SYSTEM – LEVEL SITE ................................................................................ 24 FIGURE 16: CROSS SECTION – B43 BED SYSTEM – SLOPING SITE ........................................................................... 25 FIGURE 17: PLAN VIEW – A42 BED SYSTEM – LEVEL SITE .......................................................................................... 28 FIGURE 18: CROSS SECTION – A42 BED SYSTEM – LEVEL SITE ................................................................................ 28 FIGURE 19: CROSS SECTION – A42 BED SYSTEM – SLOPING SITE ........................................................................... 29 FIGURE 20: CROSS SECTION – MOUND SYSTEM ......................................................................................................... 30 FIGURE 21: CROSS SECTION – SLOPED MOUND SYSTEM .......................................................................................... 30 FIGURE 22: PLAN VIEW – DISTRIBUTION CELL – PRESSURE MOUND SYSTEM ........................................................ 31 FIGURE 23: PRESSURE PIPE PLACEMENT .................................................................................................................... 33 FIGURE 24: PRESSURE PIPE PLACEMENT FOLLOWING CONTOURS IN TRENCH .................................................... 34 FIGURE 25: VENT FOR GRAVITY AND PRESSURE DOSED BED SYSTEMS ................................................................ 35 FIGURE 26: AIR BY-PASS LINE PLAN VIEW FOR VENTING OF PUMPED SYSTEMS .................................................. 36 FIGURE 27: AIR BY-PASS LINE CROSS SECTION FOR VENTING OF PUMPED SYSTEM ........................................... 36 FIGURE 28: PRESSURE CLEAN OUT PRESSURE DOSED SYSTEMS........................................................................... 37 FIGURE 29: GSF WITH 4” VENT EXTENDED TO CONVENIENT LOCATION .................................................................. 37 FIGURE 30: MONITORING WELL FOR SAND-SOIL INTERFACE .................................................................................... 38

TABLES:

TABLE 1: SPECIFIED SAND SIEVE REQUIREMENTS…………………………………………………………………………….4 TABLE 2: TESTING RESULTS……………………………………………………………………..................................................7 TABLE 3: TRENCH - B43 MODULES………………………………………………………………………………………………..11 TABLE 4: TRENCH - A42 MODULES………………………………………………………………………………………………..16 TABLE 5: BED - B43 MODULES……………………………………………………………………………………………………...22 TABLE 6: BED - A42 MODULES……………………………………………………………………………………………………...26

Page 3: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 3 www.eljen.com

Glossary of Terms

A42 Module 48” x 24” x 7” (L x W x H)

A22 Module 24” x 24” x 7” (L x W x H) Note: A22 Half Modules are half the length of the standard A42 Module and are utilized to round up trench rows to equal length.

B43 Module 48” x 36” x 7” (L x W x H)

B23 Module 24” x 36” x 7” (L x W x H) Note: B23 Half Modules are half the length of the standard B43 Module and are utilized to round up trench rows to equal length.

Bio-Matt™ fabric Proprietary filter fabric within the Geotextile Sand Filter Modules upon which the primary biomat layer forms.

Cover Fabric The geotextile cover fabric (provided by manufacturer) that is placed over the GSF modules.

Cuspated Core The rigid plastic core of the GSF module. It separates the geotextile fabric and creates downward infiltration channels and upward aeration channels to provide primary filtration and biological treatment of the septic effluent. The curvilinear shape of the cuspations offers increased treatment surface area and greater effluent storage.

Design Flow The estimated peak flow that is used to size a GSF system is 110 gallons per day per Bedroom for residential systems or as specified in 310 CMR 15.203. Non-residential systems shall meet effluent quality standards for residential septic effluent or include additional pretreatment to meet these water quality requirements.

Distribution Box A plastic or concrete box that receives effluent from a septic tank and splits the flow to pipes placed above the GSF modules. For equal distribution, the outlet pipe orifices are typically set at the same elevation to equalize the flow to each line.

Flow Dial/Equalizer Special insert placed in the end of distribution pipes within the distribution box to compensate for possible uneven installations and promote favorable flow to the distribution pipes.

GSF The Eljen Geotextile Sand Filter Modules and the 12-inch sand layer at the base and 6 inches along the sides of the modules.

GSF Module The individual module of a GSF system. The module is comprised of a cuspated plastic core and corrugated geotextile fabric.

Page 4: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 4 www.eljen.com

Glossary of Terms

Serial or Sequential Distribution:

Designs common to sloping sites where GSF lines, laid on contour, receive effluent from a series of drop boxes at different elevations. Effluent floods upslope lines and then spills excess effluent to down slope drop boxes. Each drop box allows inspection and control of effluent into each line of modules and can be used to rest upslope lines if the GSF system is managed. This method is not limited to sloping sites.

Specified Sand To ensure proper system operation, the system MUST be installed using ASTM C33 Sand.

ASTM C33 sand will have less than 10% passing the #100 Sieve and less than 5% passing the # 200 sieve. Ask your material supplier for a sieve analysis to verify that your material meets the required specifications.

TABLE 1: SPECIFIED SAND SIEVE REQUIREMENTS

ASTM C33 SAND SPECIFICATION

Sieve Size Sieve Square Opening Size

Specification Percent Passing

(Wet Sieve)

3/8 inch 9.52 mm 100 No. 4 4.76 mm 95 - 100 No. 8 2.38 mm 80 - 100

No. 16 1.19 mm 50 - 85 No. 30 590 µm 25 - 60 No. 50 297 µm 10 - 30 No. 100 149 µm 0 - 10 No. 200 75 µm 0 - 5

STE: Septic Tank Effluent that is discharged to the Geotextile Sand Filter. Wire Clamps: Clamps used to secure perforated pipe above the geotextile filter modules.

Page 5: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 5 www.eljen.com

Introduction

This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system using the B43 and A42 GSF modules. Design layouts and installation instructions for sequential, equal or dosed distribution systems are included. Details on unique design and construction procedures for Massachusetts are also provided. For design standards for specially engineered dosing systems, contact Eljen’s technical support at 1-800-444-1359. GSF systems must be designed and constructed according to the Massachusetts Department of Environmental Protection Title 5 regulations. The Eljen GSF system technology is based on research conducted by nationally recognized engineering scientists from the University of Connecticut. Eljen Corporation has over 30 years of success in the onsite wastewater industry, with tens of thousands of systems currently in use. The GSF is recognized by regulatory officials and experts in the industry as one of the most reliable pretreatment technologies in the marketplace today. The system specifications in this manual are founded on this research and history of installations of the GSF worldwide. The GSF technology is based on scientific principles which state that improved effluent quality provides increased soil absorption rates. GSF’s proprietary two-stage Bio-Matt™ pre-filtration process improves effluent quality while increasing reliability and ease of operation. Third-party independent testing data based on NSF/ANSI Standard 40 Protocol has shown that the Eljen GSF provides advanced treatment of septic tank effluent to better than secondary levels.

Page 6: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 6 www.eljen.com

GSF System Description

Primary Treatment Zone

• Perforated pipe is centered above the GSF module to distribute septic effluent over and into corrugations created by the cuspated core of the geotextile module.

• Septic effluent is filtered through the Bio-Matt fabric. The module’s unique design provides increased surface area for biological treatment that greatly exceeds the module’s footprint.

• Open air channels within the module support aerobic bacterial growth on the modules geotextile fabric interface, surpassing the surface area required for traditional absorption systems.

• An anti-siltation geotextile fabric covers the top and sides of the GSF module and protects the Specified Sand and soil from clogging, while maintaining effluent storage within the module.

Secondary Treatment Zone

▪ Effluent drips into the Specified Sand layer and supports unsaturated flow into the native soil. This Specified Sand/soil interface maintains soil structure, thereby maximizing the available absorption interface in the native soil. The Specified Sand supports nitrification of the effluent, which reduces oxygen demand in the soil, thus minimizing soil clogging from anaerobic bacteria.

• The Specified Sand layer also protects the soil from compaction and helps maintain cracks and crevices in the soil. This preserves the soil’s natural infiltration capacity, which is especially important in finer textured soils, where these large channels are critical for long-term performance.

• Native soil provides final filtration and allows for groundwater recharge.

FIGURE 1: GSF SYSTEM OPERATION

Page 7: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 7 www.eljen.com

Testing and Performance

GSF Modules were subjected to independent third-party testing in accordance with NSF/ANSI Standard 40 Protocol. Three different methods of distribution were tested:

• Pressure Distribution • Lift Pump/Gravity Demand Dosed Distribution • Gravity Distribution

The data and detailed reports for each system tested were reviewed by NSF in accordance with NSF/ANSI Standard 40 Protocol and the Pennsylvania Department of Environmental Protection Technical Verification Program. This independent review validates the performance data listed below for Demand Dosed, Pressure Dosed, and Gravity systems.

TABLE 2: TESTING RESULTS

Testing Arrangement & Common Factors: Common Factors for all tested systems listed in Table 2:

• A42 modules: (L x W x H) 48” x 24” x 7” plus Specified Sand. • Six modules per bedroom at 150 gal/day, 18 modules total for

three bedrooms per house equals 450 gal/day. • Standard distribution pipe with orifices at the 5 & 7 o’clock

position, • 12 inches of Specified Sand base extending 6 inches at either

edge of the modules. Lift Pump/Gravity Demand Dosed System:

• 1000 gal septic tank – 500 gallon pump chamber to distribution box.

• Dial-a-flow fittings set level to deliver effluent into each of the three rows of laterals via a 4-inch perforated distribution pipe with orifices at the 5 & 7 o’clock position.

• A non-perforated pipe connects the distal end to the end of other rows.

Time Pressure Dosed System:

• 1000 gal septic tank – 500 gal pump chamber – 1.25” low-pressure pipe (LPP) or other diameter as required.

• LPP placed inside a 4-inch perforated distribution pipe with orifices at 12 o’ clock, at least one drain hole per line at 6 o’clock.

• The 4-inch perforated pipe orifices are placed at the 5 & 7 o’clock positions with the end of pipe capped

Gravity System Trench Design:

• 1000 gal septic tank–gravity to distribution box. • Dial-a-flow fittings set level to deliver influent into three individual

trenches. • Perforated distribution pipe with orifices at the 5 & 7 o’clock

positions with the end of pipe capped.

GSF Modules Treatment Performance

NSF Standard 40 Protocol Wastewater Influent Median Characteristics:

CBOD 180 mg/L & TSS 180 mg/L

Demand Dosed CBOD (mg/L) TSS (mg/L)

Mean 2.0 2.7 Median 1.0 2.5 Min Value 1.0 2.5 Max Value 7.2 7.0

GSF Modules Treatment Performance

NSF Standard 40 Protocol Wastewater Influent Median Characteristics:

CBOD 180 mg/L & TSS 190 mg/L

Timed Pressure Dosed CBOD (mg/L) TSS (mg/L) Mean 2.6 2.7 Median 2.2 2.5 Min Value 1.0 2.5 Max Value 14.0 9.0

GSF Modules Treatment Performance

NSF Standard 40 Protocol Wastewater Influent Median Characteristics:

CBOD 180 mg/L & TSS 180 mg/L

Gravity CBOD (mg/L) TSS (mg/L) Mean 8.0 7.4 Median 7.6 5.0 Min Value 1.0 2.5 Max Value 18 55 TSS 2.5mg/L = sample was below detection limits CBOD 1.0mg/L = sample was below detection limits

Page 8: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 8 www.eljen.com

1.0 General Design and Installation

FIGURE 2: TYPICAL B43 GSF CROSS SECTION

48"

36"6" 6"

SPECIFIED SAND

GEOTEXTILE FABRIC12 - 18" OF

CLEAN FILL

7"

12"19"

SEED AND LOAM TO PROTECT FROM EROSION

B43 MODULE – (L x W x H) 48” x 36” x 7”

FIGURE 3: TYPICAL A42 GSF CROSS SECTION

36"

6" 6"

SPECIFIED SAND

GEOTEXTILE FABRIC12 - 18" OFCLEAN FILL

7"

12"19"

24"

SEED AND LOAM TO PROTECT FROM EROSION

A42 MODULE – (L x W x H) 48” x 24” x 7”

All systems are required to have a minimum of:

• 6 inches of Specified Sand is at the edges of the GSF module. • 6 inches of Specified Sand is at the beginning and end of each GSF Trench. • 12 inches of Specified Sand is directly below the GSF module. • Minimum 12 inches of native soil fill above the module.

Page 9: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 9 www.eljen.com

1.0 General Design and Installation

1.1 REQUIREMENTS: GSF systems must meet the local rules and regulations except as outlined in this manual. The Massachusetts Title 5 regulations and the local regulations will be referred to as the guidelines in this manual. The sizing charts apply to residential systems only. Please contact Eljen’s Technical Resource Department at 1-800-444-1359 for design information on commercial systems.

1.2 SPECIFIED SAND SPECIFICATION FOR TRENCH SYSTEMS: The first 12 inches of sand immediately under, and between rows of the GSF system must be ASTM C33 SAND, WITH LESS THAN 10% PASSING A #100 SIEVE AND LESS THAN 5% PASSING A #200 SIEVE. At the perimeter of the bed or trench a minimum of 6” of sand is required. Please place a prominent note to this effect on each design drawing. See Table 1 for more information on the sand and sieve specifications.

1.3 CONNECTIONS AND FITTINGS: Connections of lines to tanks and distribution boxes must be made using watertight mechanical seals. Use of any grouting material is not permitted.

1.4 PLACING GSF MODULES: The “White Stripe” on the GSF modules indicates the top of the module and is not intended to indicate the location of the distribution pipe. With the white stripe facing up, all rows of GSF modules are set level, end to end on the Specified Sand layer. No mechanical connection is required between modules.

1.5 DISTRIBUTION PIPE: SDR-35 or equivalent is required. Place perforated pipe on top of GSF modules with holes at 5 and 7 o’clock. Secure pipe to GSF modules with provided wire clamps, one clamp per Eljen module. Furthermore, all piping must meet state and local regulations. Connect mid points on level bed systems on rows over 40’ long.

1.6 DISTRIBUTION BOX: Provide D-Box(s) installed in accordance with 310 CMR 15.232. Velocity reduction tees or baffle may be installed if needed on sloping sites.

1.7 COVER FABRIC: Geotextile cover fabric is provided by Eljen Corporation for all GSF systems. It is placed over the top and sides of the module rows to prevent long term siltation and failure. Cover fabric substitution is not allowed. Fabric should drape vertically over the pipe and must not block holes in the distribution pipe or be stretched from the top of the pipe to the outside edge of the modules. “Tenting” will cause undue stress on fabric and pipe.

1.8 BACKFILL & FINISH GRADING: Complete backfill with a minimum of 12 inches of clean porous fill measured from the top of modules. Fill should conform to title 5 requirements. Title 5 requirements for Backfill are in 310 CMR 15.240 (9). Where natural backfill cannot be used, Title 5 fill is required. Backfill exceeding 18 inches requires venting at the far end of the trench or bed. Use well graded native soil fill that is clean, porous and devoid of large rocks. Do not use wheeled equipment over the system. A light track machine may be used with caution, avoiding crushing or shifting of pipe assembly. Divert surface runoff from the Effluent Disposal Area, (EDA). Finish grade to prevent surface ponding. Place topsoil and seed system area to protect from erosion.

1.9 ADDITIONAL FACTORS AFFECTING RESIDENTIAL SYSTEM SIZE: Homes with expected higher than normal water usage may consider increasing the septic tank volume as well as incorporating a multiple compartment septic tank. Consideration for disposal area may be up-sized for expected higher than normal water use.

For example:

• Luxury homes, homes with a Jacuzzi style tubs, and other high use fixtures. • Homes with known higher than normal occupancy. • Homes on high-pressure city water: recommend that the homeowner install a water pressure regulator to

reduce pressure.

Page 10: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 10 www.eljen.com

1.0 General Design and Installation

1.10 GARBAGE DISPOSALS: Eljen discourages the use of garbage disposals with septic systems. If a GSF system is to be designed and installed with garbage disposals the following measures must be taken to prevent solids from leaving the tank and entering the GSF system:

• Increase the septic tank capacity by a minimum of 50% or

• Installation of a second septic tank installed in series or

• Installation of an appropriate sized septic tank outlet effluent filter

Eljen requires the use of septic tank outlet effluent filters on all systems especially on those systems that have single compartment tanks, even if up-sized, and when the dwelling has a garbage disposal installed.

1.11 WATER SOFTENER BACKWASH: At no time should water softener backwash be disposed of in the septic system. Water softener backwash should be discharged to a separate soil absorption field.

1.12 SEPTIC TANKS: Many designers are now specifying dual compartment tanks for all their systems. Eljen supports this practice as it helps to promote long system life by reducing TSS and BOD to the effluent disposal area. Gas baffles and/or effluent filters are also recommended.

1.13 EFFLUENT FILTERS: Effluent filters are required as a means of preventing solids from leaving the tank and entering your system. Filter manufactures require that filters be cleaned from time to time. Ask your installer or designer for specific cleaning requirements based on the type or make of the filter installed. Eljen requires the septic tank to be pumped every three years or as needed which would be a good time to check and conduct filter maintenance.

1.14 SYSTEM VENTING: It is required to vent all systems that are over 18” below finished grade and systems beneath any surface condition that would not allow for surface air exchange with the system such as patios. Where trenches, fields or beds are used, the end of each distribution lateral shall be connected to one or more vents. See Section 8.0 for a more detailed explanation of venting GSF products.

1.15 NUMBER OF GSF MODULES REQUIRED: Residential systems use a minimum of six (6) A42 modules per bedroom or five (5) B43 modules per bedroom. In bed systems, we recommend not exceeding 11 B43 or 13 A42 modules per bedroom. See sizing tables for more information.

1.16 SIZING GSF SYSTEM FOR TRENCHES, BEDS & SAND MOUNDS: Eljen GSF products receive a 40% reduction to standard system sizing.

Eljen GSF modules can be used in conjunction with an ATU at a 50% sizing reduction. Eljen’s 40% reduction and an ATU’s 50% reduction cannot be combined. Individual counties may have different sizing based on local regulations.

Eljen GSF modules can also be used following nitrogen reduction systems.

Page 11: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 11 www.eljen.com

2.0 Trench Sizing and Installation Guidelines

1. The calculation of trench area is based on a 40% reduction from the Title 5 requirements in 310 CMR 15.242. 2. Wastewater flow based on 110 gallons per bedroom in accordance with 310 CMR 15.203. 3. Minimum number of B43 modules per bedroom is five (5). 4. Minimum square feet required for new construction is 400 sf. 5. When recorded percolation rates are between those listed in 310 CMR 15.242, the next slower rate shall be used for design

purposes. Trench Effective Area is determined by adding:

(Bottom Area) + (Two Sidewalls) (Divided by 12”) then multiplied by module length of 4 feet.

(48” + 38” = 86) (86 ÷ 12 = 7.16) (7.16 x 4’) = 28.6 sf of effective area per module.

Class I 1 - 5 0.74 400 400 446 15 20 25Class II 1 - 5 0.60 400 400 550 15 20 25Class I 6 0.70 400 400 471 15 20 25Class II 6 0.60 400 400 550 15 20 25Class I 7 0.68 400 400 485 15 20 25Class II 7 0.60 400 400 550 15 20 25Class I 8 0.66 400 400 500 15 20 25Class II 8 0.60 400 440 550 15 20 25Class II 10 0.60 400 440 550 15 20 25Class II 15 0.56 400 471 589 15 20 25Class III 15 0.37 535 714 892 19 25 32Class II 20 0.53 400 498 623 15 20 25Class III 20 0.34 582 776 971 21 28 34Class II 25 0.40 495 660 825 18 24 29Class III 25 0.33 600 800 1000 21 28 35Class II 30 0.33 600 800 1000 21 28 35Class III 30 0.29 683 910 1138 24 32 40Class III 40 0.25 792 1056 1320 28 37 47

Class III + IV 50 0.20 990 1320 1650 35 47 58Class III + IV 60 0.15 1320 1760 2200 47 62 77

Class III 40 0.15 1320 1760 2200 47 62 77

Class III 40 0.29 683 910 1138 24 32 40Class III + IV 50 0.25 792 1056 1320 28 37 47Class III + IV 60 0.2 990 1320 1650 35 47 58

4 5

Remedial Use 60-90 MPI Systems

Pressure Dosed Systems

MINIMUM AREA OF TRENCH REQUIRED (SF)

Table 3:Trench B43 Module

Soil Type 3 4 5 3Percolation

Rate (MPI)

Application Rate (GPD/SF)

TRENCH INSTALLATIONS EFFECTIVE AREA: 28.6 SQFT PER MODULE

MINIMUM NUMBER OF MODULES REQUIRED

Bedrooms per House Bedrooms per House

Page 12: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 12 www.eljen.com

2.0 Trench Sizing and Installation Guidelines

Trench Example: House size: 4 Bedrooms Soil Permeability min/in: 20 min/in Class III Soil Design Flow: 110 gpd x 4 bedrooms = 440 gpd Trench area in square feet (Table 3) = 776 ft² Total Number of B43 Modules Required (Table 3): 28 B43 Modules Calculate Minimum Trench Length

Multiply numbers of modules required by 4 feet per module and add an additional 1 foot of length for 6 inches of Specified Sand at the end of each row:

(28 modules x 4 ft/module) + 1 Specified Sand = 113 feet.

Minimum Trench Width

Module Width + Specified Sand: 3 feet module width + 6 inches of Specified Sand on each side = 4 foot trench width.

Final Dimension Layout

Trench is 113 feet in length by 4 feet in width with 452 square feet of system area provided. (Note: System layout will vary based on site constraints)

• Minimum Trench Length = 113 ft • Minimum Trench Width = 4 ft • Minimum Number of Rows = System layout will vary based on site constraints. See Drawings 4 – 8 • Minimum Number of Modules = 28 B43 • Minimum Total Area Required = 452 ft2

Note: If designing with multiple rows or split rows, number of modules may increase in order to even up number of modules per row.

Page 13: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 13 www.eljen.com

2.0 Trench Sizing and Installation Guidelines

FIGURE 4: PLAN VIEW – SINGLE ROW B43 TRENCH SYSTEM – LEVEL SITE

SPECIFIED SAND (TYP.)

PER DESIGN

PER DESIGN

6"4.0'

FIGURE 5: CROSS SECTION – SINGLE ROW B43 TRENCH SYSTEM – LEVEL SITE

48"

36"6" 6"

SPECIFIED SAND

GEOTEXTILE FABRIC12 - 18" OF

CLEAN FILL

7"

12"19"

SEED AND LOAM TO PROTECT FROM EROSION

Page 14: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 14 www.eljen.com

2.0 Trench Sizing and Installation Guidelines

FIGURE 6: PLAN VIEW – MULTIPLE ROW B43 TRENCH SYSTEM – LEVEL SITE

SPECIFIED SAND (TYP.)

6"

4.0'

8' MIN. PER DESIGN

PER DESIGN

FIGURE 7: CROSS SECTION – MULTIPLE ROW B43 TRENCH SYSTEM – LEVEL SITE

6"

SPECIFIED SAND

6"

MIN 12" OFCLEAN FILL

12"

NATIVE SOIL

36"

19"

8' MIN48"

Page 15: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 15 www.eljen.com

2.0 Trench Sizing and Installation Guidelines

FIGURE 8: CROSS SECTION – MULTIPLE ROW B43 TRENCH SYSTEM – SLOPING SITE

6"SPECIFIED SAND

6"

MIN 12" OFCLEAN FILL

12"

NATIVE SOIL

36"

19"

8' MIN

48"

Page 16: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 16 www.eljen.com

2.0 Trench Sizing and Installation Guidelines

1. The calculation of trench area is based on a 40% reduction from the Title 5 requirements in 310 CMR 15.242. 2. Wastewater flow based on 110 gallons per bedroom in accordance with 310 CMR 15.203. 3. Minimum number of A42 modules per bedroom is six (6). 4. Minimum square feet required for new construction is 400 sf. 5. When recorded percolation rates are between those listed in 310 CMR 15.242, the next slower rate shall be used for design

purposes.

Trench Effective Area is determined by adding:

(Bottom Area) + (Two Sidewalls) (Divided by 12”) then multiplied by module length of 4 feet.

(36” + 38” = 74) (74 ÷ 12 = 6.2) (6.2 x 4’) = 25 sf of effective area per module.

Class I 1 - 5 0.74 400 400 446 18 24 30Class II 1 - 5 0.60 400 400 550 18 24 30Class I 6 0.70 400 400 471 18 24 30Class II 6 0.60 400 400 550 18 24 30Class I 7 0.68 400 400 485 18 24 30Class II 7 0.60 400 400 550 18 24 30Class I 8 0.66 400 400 500 18 24 30Class II 8 0.60 400 440 550 18 24 30Class II 10 0.60 400 440 550 18 24 30Class II 15 0.56 400 471 589 18 24 30Class III 15 0.37 535 714 892 22 29 36Class II 20 0.53 400 498 623 18 24 30Class III 20 0.34 582 776 971 24 32 39Class II 25 0.40 495 660 825 20 27 33Class III 25 0.33 600 800 1000 24 32 40Class II 30 0.33 600 800 1000 24 32 40Class III 30 0.29 683 910 1138 28 37 46Class III 40 0.25 792 1056 1320 32 43 53

Class III + IV 50 0.20 990 1320 1650 40 53 66Class III + IV 60 0.15 1320 1760 2200 53 71 88

Class III 40 0.15 1320 1760 2200 53 62 77

Class III 40 0.29 683 910 1138 28 37 46Class III + IV 50 0.25 792 1056 1320 32 43 53Class III + IV 60 0.2 990 1320 1650 40 53 66

TRENCH INSTALLATIONS EFFECTIVE AREA: 25 SQFT PER MODULE

Table 4:Trench A42 Module

MINIMUM AREA OF TRENCH REQUIRED (SF)

MINIMUM NUMBER OF MODULES REQUIRED

Bedrooms per House Bedrooms per House

4 5

Remedial Use 60-90 MPI Systems

Pressure Dosed Systems

Soil Type 3 4 5 3Percolation

Rate (MPI)

Application Rate (GPD/SF)

Page 17: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 17 www.eljen.com

2.0 Trench Sizing and Installation Guidelines

Trench Example: House size: 4 Bedrooms Soil Permeability min/in: 30 min/in Class III Soil Design Flow – 110 gpd x 4 bedrooms = 440 gpd Trench area in square feet (Table 4) = 910 ft² Total Number of A42 Modules Required (Table 4): 37 A42 Modules Calculate Minimum Trench Length

Multiply numbers of modules required by 4 feet per module and add an additional 1 foot of length for 6 inches of Specified Sand at the end of each row:

(37 modules x 4 ft/module) + 1 ft Specified Sand = 149 ft

Minimum Trench Width

Module Width + Specified Sand: 2 feet module width + 6 inches of Specified Sand on each side = 3 ft

Final Dimension Layout

Trench is 149 feet in length by 3 feet in width with 447 square feet of system area provided. (Note: System layout will vary based on site constraints)

• Minimum Trench Length = 149 ft • Minimum Trench Width = 3 ft • Minimum Number of Rows = System layout will vary based on site constraints. See Drawings 9 – 13 • Minimum Number of Modules = 37 A42 or 38 A42 for even number of modules per row • Minimum Total Area Required = 447 ft2

Note: If designing with multiple rows or split rows, number of modules may increase in order to make the modules in each row even.

Page 18: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 18 www.eljen.com

2.0 Trench Sizing and Installation Guidelines

FIGURE 9: PLAN VIEW – SINGLE ROW A42 TRENCH SYSTEM – LEVEL SITE

SPECIFIED SAND (TYP.)

PER DESIGN

PER DESIGN

6"3.0'

FIGURE 10: CROSS SECTION – SINGLE ROW A42 TRENCH SYSTEM – LEVEL SITE

36"

6" 6"

SPECIFIED SAND

GEOTEXTILE FABRIC12 - 18" OFCLEAN FILL

7"

12"19"

24"

SEED AND LOAM TO PROTECT FROM EROSION

Page 19: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 19 www.eljen.com

2.0 Trench Sizing and Installation Guidelines

FIGURE 11: PLAN VIEW – MULTIPLE ROW A42 TRENCH SYSTEM – LEVEL SITE

SPECIFIED SAND (TYP.)

6"

PER DESIGN

3.0'

6' MIN.

PER DESIGN

FIGURE 12: CROSS SECTION – MULTIPLE ROW A42 TRENCH SYSTEM – LEVEL SITE

36"6"

SPECIFIED SAND

MIN 12" OFCLEAN FILL

7"

12"

NATIVE SOIL

36"6"

SPECIFIED SAND19"

24"

6' MIN

Page 20: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 20 www.eljen.com

2.0 Trench Sizing and Installation Guidelines

FIGURE 13: CROSS SECTION – MULTIPLE ROW A42 TRENCH SYSTEM – SLOPED SITE

36"6"

SPECIFIED SAND

MIN 12" OFCLEAN FILL

7"

12"

36"6"

SPECIFIED SAND19"

24"

NATIVE SOIL

6' MIN

Page 21: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 21 www.eljen.com

2.0 Trench Sizing and Installation Guidelines

Trench Installation Guidelines Additional guidance in State and Local regulations

Determine the Number Modules Determine the number of GSF Modules required using the trench sizing example.

Plan all Drainage Requirements Plan all drainage requirements above (up-slope) of the system. Set soil grades to ensure that storm water drainage and ground water is diverted away from the absorption area once the system is complete.

Excavating the Trench Area Scarify the receiving layer to maximize interface between the native soil and Specified Sand. Minimize walking in the trench prior to placement of the Specified Sand to avoid soil compaction.

Placing Specified Sand Base Place Specified Sand in two 6 inch lifts, compact each lift at a time. The compacted height below the GSF module must be level at 12 inches. A hand tamping tool or vibrating compactor is both acceptable.

Place GSF Modules Place the GSF Modules, PAINTED STRIPE FACING UP, end to end on top of the Specified Sand along their 4-foot length. Separation distance between excavated trenches is 2 x the trench width. Systems utilizing B43 modules will have 8’ native soil separating trenches, and systems utilizing A42 modules will have 6’ of native soil separating trenches. Separation distances are measured from trench edge to trench edge.

Distribution Pipes: Gravity & Lift Pump/Gravity Systems

A standard 4-inch perforated pipe, SDR 35 or equivalent, is centered along the modules 4-foot length. Orifices are set at the 5 & 7 o’clock position. All 4-inch pipes are secured with manufacturers supplied wire clamps, one per module. Connect mid points on level bed systems on rows over 40’ long.

Distribution Pipes: Pressure Systems

A standard 4-inch perforated pipe, SDR 35 or equivalent, is centered along the modules 4-foot length. Orifices are set at the 5 & 7 o’clock position. Insert a pressure pipe (size per design and code) into the standard 4-inch perforated pipe. The pressure pipe orifices are set at the 12 o’clock position as shown in Figure 23. Each pressure lateral will have a drain hole at the 6 o’clock position. All 4-inch pipes are secured with manufacturers supplied wire clamps, one per module.

Place Geotextile Cover Fabric Cover fabric substitution is not allowed. The installer should lay the Eljen provided geotextile cover fabric lengthwise down the trench, with the fabric fitted to the perforated pipe on top of the GSF modules. Fabric should be neither too loose, nor too tight. The correct tension of the cover fabric is set by:

• Spreading the cover fabric over the top of the module and down both sides of the module with the cover fabric tented over the top of the perforated distribution pipe.

• Place small amounts of Specified Sand directly over the pipe area allowing the cover fabric to form a mostly vertical orientation along the sides of the pipe. Repeat this step moving down the pipe.

Placing Specified Sand after Cover Fabric is in place

Place 6 inches of Specified Sand along both sides of the modules edge. A minimum of 6 inches of Specified Sand is placed at the beginning and end of each trench.

Backfilling the System Complete backfill with a minimum of 12 inches of soil in accordance with Title 5 requirements over the GSF modules. Backfill exceeding 18 inches requires venting at the distal end of the trench. Fill must be clean, porous and devoid of rocks. Do not use wheeled equipment over the system during backfill operation. A light track machine may be used with extreme caution, avoiding crushing or shifting of pipe assembly. Divert surface runoff. Finish grade to prevent surface ponding. Topsoil and seed to protect from erosion. Title 5 requirements for Backfill are in 310 CMR 15.240 (9). Where natural backfill cannot be used, Title 5 fill is required.

Page 22: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 22 www.eljen.com

3.0 Bed Sizing and Installation Guidelines

1. The calculation for bed area is based on a 40% reduction from the Title 5 requirements in 310 CMR 15.242. 2. Wastewater flow based on 110 gallons per bedroom in accordance with 310 CMR 15.203. 3. Minimum number of B43 modules per bedroom is five (5). 4. Minimum square feet required for new construction is 400 sf. 5. When recorded percolation rates are between those listed in 310 CMR 15.242, the next slower rate shall be used for design

purposes.

Class I 1 – 5 0.74 400 400 446 89 15 20 25 5Class II 1 – 5 0.6 400 440 550 110 15 20 25 5Class I 6 0.7 400 400 471 94 15 20 25 5Class II 6 0.6 400 440 550 110 15 20 25 5Class I 7 0.68 400 400 485 97 15 20 25 5Class II 7 0.6 400 440 550 110 15 20 25 5Class I 8 0.66 400 400 500 100 15 20 25 5Class II 8 0.6 400 440 550 110 15 20 25 5Class II 10 0.6 400 440 550 110 18 24 30 6Class II 15 0.56 400 471 589 118 18 24 30 6Class III 15 0.37 535 714 892 178 21 28 35 7Class II 20 0.53 400 498 623 125 21 28 35 7Class III 20 0.34 582 776 971 194 21 28 35 7Class II 25 0.4 495 660 825 165 24 32 40 8Class III 25 0.33 600 800 1000 200 24 32 40 8Class II 30 0.33 600 800 1000 200 24 32 40 8Class III 30 0.29 683 910 1138 228 27 36 45 9Class III 40 0.25 792 1056 1320 264 27 36 45 9

Class III & IV 50 0.2 990 1320 1650 330 30 40 50 10

Class III & IV 60 0.15 1320 1760 2200 440 33 44 55 11

Class III & IV 60 - 90 0.15 1320 1760 2200 440 33 44 55 11

Class III 40 0.29 683 910 1138 228 27 36 45 9

Class III & IV 50 0.25 792 1056 1320 264 30 40 50 10

Class III & IV 60 0.2 990 1320 1650 330 33 44 55 11

Remedial Use 60 – 90 MPI Systems

Pressure Dosed Systems

MINIMUM AREA OF BED REQUIRED (SF)

MINIMUM NUMBER OF MODULES REQUIRED

Bedrooms per House

Percolation Rate (MPI)

Application Rate

(GPD/SF)

Square Feet Per

Each Additional Bedroom

Modules Per Each

Additional Bedroom

Bedrooms per House

Soil Type 3 4 5 3 4 5

Table 5: Bed B43 Module

Page 23: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 23 www.eljen.com

3.0 Bed Sizing and Installation Guidelines

Bed Example: House size: 4 Bedrooms Soil Permeability min/in: 30 min/in Class III Soil Design Flow: 110 gpd x 4 bedrooms = 440 gpd Trench area in square feet (Table 5) = 910 ft² Total Number of B43 Modules Required (Table 5): 36 B43 Modules Calculate Bed Length:

Note: For this example, assume 3 rows of modules using 12 modules per row.

Multiply numbers of modules per row by 4 feet per module and add an additional 1 foot of length for 6 inches of Specified Sand at the end of each row:

(12 modules x 4 ft/module) + 1 Specified Sand = 49 feet.

Calculate Bed Width:

Divide the bed area in square feet by bed length calculated above:

910 ft² ÷ 49 lf = 18.6 ft Calculate the Center to Center Spacing for Module Rows:

Center to Center Module Spacing = Bed Width ÷ Number of Rows:

Bed width = 18.6 lf 18.6 lf ÷ 3 rows = 6.2 lf center to center module spacing.

Calculate Center to Edge of Bed Module Spacing:

Center to edge of bed module spacing = ½ center to center spacing:

6.2 lf x 0.5 = 3.1 lf center to edge of bed module spacing. Final Layout Dimensions:

Bed is 49 feet in length by 18.6 feet in width with 3 rows of modules containing 12 modules per row. • Minimum Bed Length = 49 ft • Minimum Bed Width = 18.6 • Number of Rows = 3 • Minimum Number of Modules per Row = 12 • Minimum Number of B43 Modules = 36 B43 • Total Area Provided = 911.4 ft2

Page 24: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 24 www.eljen.com

3.0 Bed Sizing and Installation Guidelines

FIGURE 14: PLAN VIEW – B43 BED SYSTEM – LEVEL SITE

PER DESIGN 12" MIN

PER DESIGN 6" MIN

PER

DESI

GN

PER DESIGN6" MIN

FIGURE 15: CROSS SECTION – B43 BED SYSTEM – LEVEL SITE

6"MIN

SPECIFIED SAND

6"

MIN 12" OFCLEAN FILL

12"

36"PER DESIGN

19"

12" MIN

PER DESIGN

Page 25: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 25 www.eljen.com

3.0 Bed Sizing and Installation Guidelines

FIGURE 16: CROSS SECTION – B43 BED SYSTEM – SLOPING SITE

6"MIN

SPECIFIED SAND

MIN 12" OFCLEAN FILL

12"

36"PER

DESIGN

19"

PER CODE12" MIN

PER DESIGN

Page 26: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 26 www.eljen.com

3.0 Bed Sizing and Installation Guidelines

1. The calculation for bed area is based on a 40% reduction from the Title 5 requirements in 310 CMR 15.242. 2. Wastewater flow based on 110 gallons per bedroom in accordance with 310 CMR 15.203. 3. Minimum number of A42 modules per bedroom is six (6). 4. Minimum square feet required for new construction is 400 sf. 5. When recorded percolation rates are between those listed in 310 CMR 15.242, the next slower rate shall be used for design

purposes.

Class I 1 – 5 0.74 400 400 446 89 18 24 30 6Class II 1 – 5 0.6 400 440 550 110 18 24 30 6Class I 6 0.7 400 400 471 94 18 24 30 6Class II 6 0.6 400 440 550 110 18 24 30 6Class I 7 0.68 400 400 485 97 18 24 30 6Class II 7 0.6 400 440 550 110 18 24 30 6Class I 8 0.66 400 400 500 100 18 24 30 6Class II 8 0.6 400 440 550 110 18 24 30 6Class II 10 0.6 400 440 550 110 21 28 35 7Class II 15 0.56 400 471 589 118 21 28 35 7Class III 15 0.37 535 714 892 178 24 32 40 8Class II 20 0.53 400 498 623 125 24 32 40 8Class III 20 0.34 582 776 971 194 24 32 40 8Class II 25 0.4 495 660 825 165 27 36 45 9Class III 25 0.33 600 800 1000 200 27 36 45 9Class II 30 0.33 600 800 1000 200 27 36 45 9Class III 30 0.29 683 910 1138 228 30 40 50 10Class III 40 0.25 792 1056 1320 264 33 44 55 11

Class III & IV 50 0.2 990 1320 1650 330 39 52 65 13Class III & IV 60 0.15 1320 1760 2200 440 39 52 65 13

Class III & IV 60 - 90 0.15 1320 1760 2200 440 39 52 65 13

Class III 40 0.29 683 910 1138 228 30 40 50 10Class III & IV 50 0.25 792 1056 1320 264 39 52 65 13Class III & IV 60 0.2 990 1320 1650 330 39 52 65 13

Remedial Use 60 – 90 MPI Systems

Pressure Dosed Systems

Square Feet Per

Each Additional Bedroom

3 4 5

Modules Per Each

Additional Bedroom

Soil TypePercolation

Rate (MPI)

Application Rate

(GPD/SF)3 4 5

Table 6: Bed A42 Module

MINIMUM AREA OF BED REQUIRED (SF)

MINIMUM NUMBER OF MODULES REQUIRED

Bedrooms per House Bedrooms per House

Page 27: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 27 www.eljen.com

3.0 Bed Sizing and Installation Guidelines

Bed Example: House size: 4 Bedrooms Soil Permeability min/in: 20 min/in Class II Soil Design Flow: 110 gpd x 4 bedrooms = 440 gpd Trench area in square feet (Table 6) = 498 ft² Total Number of A42 Modules Required (Table 6): 32 A42 Modules Calculate Bed Length:

Note: For this example, assume 2 rows of modules using 16 modules per row.

Multiply numbers of modules per row by 4 feet per module and add an additional 1 foot of length for 6 inches of Specified Sand at the end of each row:

(16 modules x 4 ft/module) + 1 Specified Sand = 65 feet.

Calculate Bed Width:

Divide the bed area in square feet by bed length calculated above:

498 ft² ÷ 65 lf = 7.7 ft – Round up to 8.0 Calculate the Center to Center Spacing for Module Rows:

Center to Center Module Spacing = Bed Width ÷ Number of Rows:

Bed width = 8.0 lf 8.0 lf ÷ 2 rows = 4.0 lf center to center module spacing.

Calculate Center to Edge of Bed Module Spacing:

Center to edge of bed module spacing = ½ center to center spacing:

4.0 lf x 0.5 = 2.0 lf center to edge of bed module spacing. Final Layout Dimensions:

Bed is 65 feet in length by 8.0 feet in width with 2 rows of modules containing 16 modules per row. • Minimum Bed Length = 65 ft • Minimum Bed Width = 8.0 • Number of Rows = 2 • Minimum Number of Modules per Row = 16 • Minimum Number of B43 Modules = 32 A42 • Total Area Provided = 520 ft2

Page 28: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 28 www.eljen.com

3.0 Bed Sizing and Installation Guidelines

FIGURE 17: PLAN VIEW – A42 BED SYSTEM – LEVEL SITE

PER

DESI

GN

PER DESIGN 12" MIN

6" MIN

PER DESIGN 6" MIN

PER DESIGN

FIGURE 18: CROSS SECTION – A42 BED SYSTEM – LEVEL SITE

MIN 12" OFCLEAN FILL

SPECIFIED SAND

PER DESIGN12" MIN

24"PER DESIGN

6" MIN

12"19"

Page 29: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 29 www.eljen.com

3.0 Bed Sizing and Installation Guidelines

FIGURE 19: CROSS SECTION – A42 BED SYSTEM – SLOPING SITE

SPECIFIED SAND

PER DESIGN12" MIN

MIN 12" OFCLEAN FILL

19"12"

6" MIN24"

PER CODE

Page 30: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 30 www.eljen.com

4.0 Mound Installation Guidelines

4.1 MOUND REFERENCE: The following guidelines provide an overview for mound design and construction. Mound distribution can either be pump to gravity or pressurized. Systems with 2000 GPD or greater shall require pressure distribution in accordance with 310 CMR 15.231.

FIGURE 20: CROSS SECTION – MOUND SYSTEM

*Note: Design Can Utilize Either B43 or A42 Modules

SPECIFIED SAND

12" MINPER DESIGN

ORIGINAL GRADE

TITLE 5 FILL

REMOVE TOP SOIL & SET SYSTEM BASE BELOW ORIGINAL GRADE

12" MIN

12" MIN

15' MINTOP SOIL & SEED TO PROTECT FROM EROSION

PERCODE

FIGURE 21: CROSS SECTION – SLOPED MOUND SYSTEM *Note: Design Can Utilize Either B43 or A42 Modules

SPECIFIED SANDORIGINAL GRADE

REMOVE TOP SOIL & SET SYSTEM BASE BELOW ORIGINAL GRADE

12" MIN

12" MIN TITLE 5 FILL

TOP SOIL & SEED TO PROTECT FROM EROSION

12" MINPER DESIGN

15' MIN

PERCODE

Page 31: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 31 www.eljen.com

4.0 Mound Installation Guidelines

FIGURE 22: PLAN VIEW – DISTRIBUTION CELL – PRESSURE MOUND SYSTEM *Note: Design Can Utilize Either B43 or A42 Modules

PRESSURE ORRIFICE (SIZE PER DESIGN) AT 12 O'CLOCKLPP

4" DISTRIBUTION PIPE

SPECIFIED SAND

PERDESIGN

6"

PER DESIGNPER DESIGN

VENT PORT

Page 32: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 32 www.eljen.com

4.0 Mound Installation Guidelines

Mound Installation Guidelines Additional guidance in State and Local regulations

Determine the Number Modules

Determine the number of GSF Modules required using the mound sizing example.

Excavating the Bed Area Scarify the receiving layer to maximize the interface between the native soil and Specified Sand. Minimize walking in the absorption area prior to placement of the Specified Sand to avoid soil compaction.

Placing Specified Sand Base Place Specified Sand in two 6 inch lifts. Compact each lift at a time. The compacted height below the GSF module must be level at 12 inches. A hand tamping tool or vibrating compactor is both acceptable.

Place GSF Modules Place the GSF Modules, PAINTED STRIPE FACING UP, end to end on top of the Specified Sand along their 4-foot length.

Distribution Options: • Pump Dosed • Siphons • Pressure

All methods use a standard 4-inch perforated pipe, SDR 35 or equivalent, centered along the modules 4-foot length. Orifices are set at the 5 & 7 o’clock position. For pressure systems, insert a pressure pipe (size per design and code) into the standard 4-inch perforated pipe. The pressure pipe orifices (size per design) are set at the 12 o’clock position. Each pressure lateral will have a drain hole at the 6 o’clock position. All 4-inch pipes are secured with manufacturers supplied wire clamps, one per module.

Pump Chamber to the GSF System

Refer to local regulations for guidance

· Pump Dosed Guidance

· Pressure Distribution Guidance

· Pump Controls

Place Geotextile Cover Fabric Cover fabric substitution is not allowed. The installer should lay the Eljen provided geotextile cover fabric lengthwise down the trench, with the fabric fitted to the perforated pipe on top of the GSF modules. Fabric should be neither too loose, nor too tight. The correct tension of the cover fabric is set by:

• Spreading the cover fabric over the top of the module and down both sides of the module with the cover fabric tented over the top of the perforated distribution pipe.

• Place shovel full’s of Specified Sand directly over the pipe area allowing the cover fabric to form a mostly vertical orientation along the sides of the pipe. Repeat this step moving down the pipe.

Backfilling the System Complete backfill with a minimum of 12 inches of soil in accordance with Title 5 requirements over the GSF modules. Backfill exceeding 18 inches requires venting at the distal end of the trench. Fill must be clean, porous and devoid of rocks. Do not use wheeled equipment over the system during backfill operation. A light track machine may be used with extreme caution, avoiding crushing or shifting of pipe assembly. Divert surface runoff. Finish grade to prevent surface ponding. Topsoil and seed to protect from erosion. Title 5 requirements for Backfill are in 310 CMR 15.240 (9). Where natural backfill cannot be used, Title 5 fill is required.

Page 33: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 33 www.eljen.com

5.0 Pump Dosing Distribution Guidance

5.1 PUMP DOSING DISTRIBUTION BOX: Specify an oversized distribution box for pumped dosed systems. Provide velocity reduction in the d-box with a tee or baffle. Set d-box outlets at the same elevation to equalize flow to each line or use drop boxes at the head of each line for serial distribution. If the absorption area is installed deeper than 18 inches, the system must be vented. See section 8.0 of this manual for detailed information on venting of systems.

5.2 PUMP DOSING DESIGN CRITERIA: Dosing volume must be set to deliver a maximum of 4 gallons per B43 Module and 3 gallons per A42 Module per dosing cycle. Higher flow rates and short dose cycle push the effluent down the line and thus disperse the effluent over a larger area. A valve on the force main is recommended to set the flow rate so that the outlet pipes are submerged but prevents the d-box from over flowing.

6.0 Pressure Distribution Guidance

The lateral pipe network (size per design and code) is placed within a 4-inch perforated distribution pipe (SDR 35 or equivalent). The perforations in the 4-inch distribution pipe are set at the 5 and 7 o’clock position. The drilled orifices for the pressure pipe are set to spray at the 12 o’clock position within the 4-inch perforated pipe as shown below. Orifices shall be spaced, at a minimum, so they fall in the center of each module. A minimum orifice size of 1/8 inch shall be maintained. A 1/4 inch diameter drain hole is required at the 6 o’clock position of each pressure lateral for drainage purposes. The maximum dose per module should be designed at 4 gallons for each B43 module and 3 gallons for each A42 module per dosing cycle. Systems with 2000 GPD or greater shall require pressure distribution in accordance with 310 CMR 15.231.

FIGURE 23: PRESSURE PIPE PLACEMENT

FROMPUMP CHAMBER

LOW PRESSURE PIPE (LPP)

CAP END OF 4" PIPE4" DIAMETERPERFORATED PIPE

4" DIAMETER PERFORATED PIPELOW PRESSURE PIPE (SIZE PER DESIGN)

PRESSURE PIPE CROSS SECTION FOR ALL APPLICATIONS

Page 34: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 34 www.eljen.com

6.0 Pressure Distribution Guidance

FIGURE 24: PRESSURE PIPE PLACEMENT FOLLOWING CONTOURS IN TRENCH

PRIOR TO PLACING FABRIC COVER, HANDSHOVEL SPECIFIED SAND IN THESE AREAS

STANDARD FITTING(S)

4" PERFORATED PIPE

PRESSURE PIPE(SIZE PER DESIGN/CODE)

PRESSURE PIPE EXTENDS THRU ENDCAP, AND IS EXTENDED FOR CLEAN OUT

DRAIN OPENING AT 6 O'CLOCK

CAP ENDOF 4" PIPE

GSF Pressure Distribution trench placed on a contour or winding trenches to maintain horizontal separation distances may also be used in Dosed or Gravity system by removing the pressure pipe and using the 4-inch diameter perforated distribution pipe.

7.0 Pump Controls

Pump and Pressure Dosed controlled systems will include an electrical control system that has the alarm circuit independent of the pump circuit, controls and components that are listed by UL or equivalent, is located outside, within line of sight of the pump chamber and is secure from tampering and resistant to weather (minimum of NEMA 4). The control panel shall be equipped with cycle counters and elapsed time meters. Where a water supply water meter is available it may be possible to eliminate the counters or timers.

The control panel shall be equipped with both audible and visual high liquid level alarms installed in a conspicuous location. Float switches shall be mounted independent of the pump and force main so that they can be easily replaced and/or adjusted without removing the pump.

Page 35: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 35 www.eljen.com

8.0 System Ventilation

8.1 SYSTEM VENTILATION: Air vents are required on all absorption systems located under impervious surfaces or systems with more than 18 inches of cover material as measured from the top of the GSF module to finished grade. This will ensure proper aeration of the modules and sand filter. Where trenches, fields or beds are used, the end of each distribution lateral shall be connected to one or more vents. The GSF PAD has aeration channels between the rows of GSF modules connecting to cuspations within the GSF modules. Under normal operating conditions, only a fraction of the filter is in use. The unused channels remain open for intermittent peak flows and the transfer of air. The extension of the distribution pipe to the vent provides adequate delivery of air into the GSF system. Home plumbing operates under negative pressure due to hot water heating the pipes and reducing the density of air in the house vent. As hot air rises and exits the home, it must be replaced by air from the GSF. To maintain this airflow and fully aerate the GSF system, it is important that air vents are located only on the distal end of the GSF pipe network.

System Ventilation Example Drawings

FIGURE 25: VENT FOR GRAVITY AND PRESSURE DOSED BED SYSTEMS

SPECIFIEDSAND

EDGE OF LAST MODULE

VENTED CAP

NON-PERFORATED 4"DIAMETER PIPE

8.2 VENTILATION FOR PRESSURE AND PUMP DOSED SYSTEMS: If a pressure or pump dosed system is specified with greater than 18 inches of cover, an additional 2-inch minimum airline must be extended from the GSF D-box back to a knockout or riser on the septic tank or pump chamber. This maintains the continuity of airflow from the field into the house plumbing.

Page 36: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 36 www.eljen.com

System Ventilation Example Drawings

FIGURE 26: AIR BY-PASS LINE PLAN VIEW FOR VENTING OF PUMPED SYSTEMS

SEPTIC TANK

PUMPCHAMBER DISTRIBUTION

BOX

GSF MODULES

VENT

BY-PASS LINE

FIGURE 27: AIR BY-PASS LINE CROSS SECTION FOR VENTING OF PUMPED SYSTEM

PUMP TANK RISER

INLET PIPEFROM SEPTICTANK

LPP PUMP LINEDISTRIBUTIONBOX

OUTLET PIPE TO GSFMODULE ROW

MINIMUM 2"DIAMETERBY-PASS AIRLINE

8.3 VENT PIPE FOR LOW PRESSURE DISTRIBUTION SYSTEMS: If the system is a low pressure distribution system with greater than 18 inches of cover, ensure that the LPP clean outs are located in the vent for easy access.

Page 37: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 37 www.eljen.com

System Ventilation Example Drawings

FIGURE 28: PRESSURE CLEAN OUT PRESSURE DOSED SYSTEMS

EDGE OF LAST MODULE

LOW PRESSURE PIPE

SPECIFIED SAND

THREADED CAP

4" DIAMETER PIPE

8.4 VENTILATION PLACEMENT: In a GSF system, the vent is usually a 4-inch diameter pipe extended to a convenient location behind shrubs, as shown below. Corrugated pipe may be used. If using corrugated pipe, ensure that the pipe does not have any bends that will allow condensation to pond in the pipe. This may close off the vent line. The pipe must have an invert higher than the system so that it does not drain effluent.

FIGURE 29: GSF WITH 4” VENT EXTENDED TO CONVENIENT LOCATION

GSF MODULES

MOUNDED BACKFILL OVER MODULES

COVER FABRIC NOT SHOWN OVER DISTRIBUTION PIPE AND MODULES

CLEAN BACKFILL FINISHED GRADE

SHRUB

Page 38: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

2013 Massachusetts Design & Installation Manual 38 www.eljen.com

9.0 Inspection/Monitoring Port

The system shall include an Inspection/Monitoring Port designed and installed with access from the ground surface. It shall be open and slotted at the bottom, and be void of sand or gravel to the infiltrative surface to allow visual monitoring of standing liquid in the trench. The figures below depict construction and placement of the Inspection/Monitoring Port. Positioning of the port in reference to the length of the trench is in accordance to your local regulations and specifications.

FIGURE 30: MONITORING WELL FOR SAND-SOIL INTERFACE

TYPAR SOCK

TAPE OR TIE TO PIPE

PIPE COVERNON-PERFORATED

4" PIPE COUPLING

PERFORATED4" PIPE

OPEN BOTTOM

SPECIFIED SANDSURRONDING PIPE

48"

36"6" 6"

SPECIFIED SAND

GEOTEXTILE FABRICMINIMUM 12"

OF CLEAN FILL

7"

12"19"

PIPE FLUSH WITH SAND-SOIL INTERFACEON TRENCH BOTTOM

Page 39: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system
Page 40: Geotextile Sand Filter Massachusetts Design & Installation Manual 5 Introduction This manual provides design and installation information for the Eljen GSF Geotextile Sand Filter system

125 McKee Street, East Hartford, CT 06108 • Tel: 800-444-1359 • Fax: 860-610-0427

www.eljen.com

COMPANY HISTORYEstablished in 1970, Eljen Corporation created the world’s first

prefabricated drainage system for foundation drainage and erosion control applications. In the mid-1980s, we introduced our Geotextile Sand Filter products for the passive advanced

treatment of onsite wastewater in both residential and commercial applications. Today, Eljen is a global leader in providing innovative

products and solutions for protecting our environment and public health.

COMPANY PHILOSOPHYEljen Corporation is committed to advancing the onsite industry through continuous development of innovative new products, delivering high quality products and services to our customers

at the best price, and building lasting partnerships with our employees, suppliers, and customers.