Genesis FSfloor standing condensing boiler
MODELS
OUTPUT(kW)
124 - 250
120
160
200
250
13:1Modulation
Turndown
10yrHeat Exchanger
Warranty6
NOx Class
Genesis FSThe Genesis floor standing boiler is available in a range of 4 models from 124 - 250kW, with a highly durable stainless steel heat exchanger offering thermal efficiency up to 108% net. The Genesis FS boiler has a modulation range up to 13:1, with a small footprint which makes it suitable for installation in areas with space constraints. The boiler has an intelligent control system which can cascade up to 16 boilers in a modular configuration.
I N T R O D U C T I O N
key featuresStainless steel heat exchanger
Cascade installations up to 16 boilers
Class 6 NOx emissions
High modulation ratio up to 13:1
0-10V control
Compact dimensions
Stainless steel internal pipework
Efficiency of up to 108% net
10 year warranty* on heat exchanger2 year warranty* on parts
warranty
BIMDrawings
*subject to Terms & Conditions
MODELS
120
160
200
250
Stainless Steel
Nat Gas & LPG
S I N G L E B O I L E R D I M E N S I O N S
HeightWidthDepthAir inletChimney connectionHeating return connectionHeating flow connectionGas connectionCondensate drain
120 160
1524
648
787
125
130
2
2
¾
25
1524
648
787
125
130
2
2
¾
25
mm
mm
mm
mm
mm
inches
inches
inches
mm
200 250
1524
648
860
125
180
2½
2½
1
25
1524
648
860
125
180
2½
2½
1
25
Width Depth
Hei
ght
Gas mixing system with constant air/gas modulation
Stainless steel heat exchanger
Condensate drain dish
Condensate trap
internal structure
FRONT VIEW SIDE VIEW REAR VIEW
Gas Return Flow
T E C H N I C A L D ATA
pow
er
Maximum boiler output (80-60°C) - NG (G20)Maximum boiler output (50-30°C) - NG (G20)Maximum boiler output (80-60°C) - LPG (G31)Maximum boiler output (50-30°C) - LPG (G31)Minimum boiler output (80-60°C) - NG (G20) Minimum boiler output (50-30°C) - NG (G20)Minimum boiler output (80-60°C) - LPG (G31)Minimum boiler output (50-30°C) - LPG (G31)Maximum boiler inputHeat efficiency (50-30°C) - maximum outputStandby losses ModulationBuilding regulations Part L seasonal efficiency (Non Domestic Building) - NG
Building regulations Part L seasonal efficiency (Non Domestic Building) - LPG
120 160 200 250MODEL
226.7249.7226.7244.524.627.456.261.4
232.0107.70.26013.6:195.597.7
112.8124.0112.8122.010.812.027.930.5115.5107.50.21510.3:196.198.2
148.0162.7148.0159.918.320.436.640.0151.4107.50.2257.9:195.897.9
185.6204.2185.6204.224.226.846.050.0190.0107.50.2487.6:195.597.7
kW
kW
kW
kW
kW
kW
kW
kW
kW
%
kW
ratio
% gross
% gross
Dry weight 185 199 224 236Kg
gas
Gas flow rate, NG (G20) - maximum Gas flow rate, LPG (G31-37 mbar) - maximum*Maximum gas inlet pressure - NG (G20)Maximum gas inlet pressure - LPG (G31-37 mbar) Nominal gas inlet pressure - NG (G20)Nominal gas inlet pressure - LPG (G31-37 mbar)Minimum gas inlet pressure - NG (G20)Minimum gas inlet pressure - LPG (G31-37 mbar)
21.99.0254520371725
10.74.5254520371725
14.35.9254520371725
18.27.4254520371725
m�/hr
m�/hr
mbar
mbar
mbar
mbar
mbar
mbar
Electrical supply Power consumption - maximumPower consumption - minimum Run current - maximum
elec
tric
230/1/500.2750.030
1.4
230/1/500.1780.022
0.9
230/1/500.1970.030
1.0
230/1/500.2080.028
1.1
(Fused supply requirement of 3 Amps)
kW
kW
A
669.010.10.86.090
477.28.80.86.090
Water content System design flow rate (20°C ΔT rise) single boiler Water side pressure loss (20°C ΔT rise) single boiler Minimum water pressure Maximum water pressure Maximum flow temperature setting
hydr
aulic
515.58.00.86.090
6211.110.90.86.090
litres
l/s
kPa
bar
bar
°C
Flue gas temperature at 80/60°CFlue gas temperature at 50/30°CMax. flue gas pressureMass flow rate of flue gassesMax. condensate volumeDry NOx emission (0% excess O�)
flue
6135
20010130.036.0
6034
20047
14.436.6
6134
20064
18.639.4
6234
20080
24.038.7
°C
°C
Pa
g/s
kg/h
mg/kWh
*Calculated based on GCV for commercial propane - 93.1m3/h
S Y S T E M S C H E M AT I C S
5
5
5
5
23B
23B
GENESIS
GENESIS
GENESIS
GENESIS
22
22
22
22
sealed system with plate heat exchanger
sealed system with low loss header
3
3
H.C. Heating circuitD.H.W. Domestic hot waterA Primary return/drainB DHW cold water supply1. Primary flow2. Primary return3. Outside temperature sensor4. Boiler pump5. Expansion vessel6. Safety group (safety valve, air vent - air purge, manometer)7. Plate heat exchanger/low loss header8. Air vent 9. DHW primary pump10. DHW storage tank
11. DHW storage tank temperature sensor12. Check valve13. Water pressure sensor14. Room unit/room thermostat15. Mixing valve16. Consumers17. Cascade return sensor18. DHW circulation pump (with timer)19. HC pump20. System flow temperature sensor21. HC1, HC2, HC3 temperature sensor22. Strainer23. System pressure manager
Modutherm Limited Unit 4 GenesisEndeavour Drive Basildon, SS14 3WF
modutherm.co.ukTel: 0345 521 [email protected] member of the Modular Heating Group. CB/0420