Instruction Book M-3425A Generator Protection

Generator Relay Protection

Embed Size (px)

DESCRIPTION

Beckwith 3425A

Citation preview

Page 1: Generator Relay Protection

Instruction Book

M-3425AGenerator Protection

Page 2: Generator Relay Protection

Generator ProtectionM-3425AIntegrated Protection System® for Generators of All Sizes

PROTECTION

Unit shown with optional M-3925A Target Module and M-3931 HMI (Human-Machine Interface) Module

• Exceeds IEEE C37.102 and Standard 242 requirements for generatorprotection

• Protects generators of any prime mover, grounding and connection type• Provides all major protective functions for generator protection

including Out-of-Step (78), Split-Phase Differential (50DT),Under Frequency Time Accumulation (81A), InadvertentEnergizing (50/27) and Turn-to-Turn Fault (59X)

• Expanded IPScom® Communications Software provides simple andlogical setting and programming, including logic schemes

• Simple application with Base and Comprehensive protection packages

• Load encroachment blinders and power swing blocking forsystem backup protection (21) to enhance security duringsystem abnormal conditions

• Options: Ethernet Connection, Field Ground/Brush Lift-OffProtection (64F/B), Sync Check (25), 100% Stator GroundFault Protection by low frequency injection (64S) andExpanded I/O (15 additional Output Contacts and8 additional Control/Status Inputs)

Page 3: Generator Relay Protection

–2–

M-3425A Generator Protection Relay

Optional Protective Functions• Sync Check with Phase Angle, ΔV and ΔF

with dead line/dead bus options (25)• Field Ground (64F) and Brush Lift Off (64B)

(Includes M-3921 Field Ground Coupler)• 100% Stator Ground protection by low

frequency injection (64S). The followingequipment is required with the 64S option:– 20 Hz signal generator (430-00426)– Band-pass Filter (430-00427)

– 400/5 A 20 Hz CT (430-00428)

Standard Features• Eight programmable outputs and six

programmable inputs• Oscillographic recording with COMTRADE

or BECO format• Time-stamped target storage for 32 events• Metering of all measured parameters and

calculated values• Three communications ports (two RS-232

and one RS-485)• M-3820D IPScom® Communications Software• Includes MODBUS and BECO 2200

protocols• Standard 19" rack-mount design (vertical

mounting available)• Removable printed circuit board and power supply• 50 and 60 Hz models available• Both 1A and 5 A rated CT inputs available• Additional trip inputs for externally connected

devices• IRIG-B time synchronization• Operating Temperature: –20° C to +70° C• Sequence of Events Log• Trip Circuit Monitoring• Breaker Monitoring• Four Setpoint Groups

Optional Features• Redundant power supply• M-3925A Target Module• M-3931 Human-Machine Interface (HMI)

Module• RJ45 Ethernet port utilizing MODBUS over

TCP/IP and BECO2200 over TCP/IP protocols• RJ45 Ethernet port utilizing IEC 61850 Protocol• M-3801D IPSplot® PLUS Oscillograph

Analysis Software• Expanded I/O (15 additional outputs and

8 additional inputs)• Standard and Expanded I/O Models

available in vertical panel mount.

Protective FunctionsBase Package

• Overexcitation (V/Hz) (24)• Phase Undervoltage (27)• Directional power sensitive triple-setpoint

Reverse Power, Low Forward Power orOverpower detection, one of which can beused for sequential tripping (32)

• Dual-zone, offset-mho Loss of Field (40), whichmay be applied with undervoltage controlledaccelerated tripping

• Sensitive Negative Sequence Overcurrentprotection and alarm (46)

• Instantaneous Phase Overcurrent (50)• Inadvertent Energizing (50/27)• Generator Breaker Failure (50BF)• Instantaneous Neutral Overcurrent (50N)• Inverse Time Neutral Overcurrent (51N)• Three-phase Inverse Time Overcurrent

(51V) with voltage control and voltage restraint.• Phase Overvoltage (59)• Neutral Overvoltage (59N)• Multi-purpose Overvoltage (59X)• VT Fuse-Loss Detection and blocking

(60FL)• Residual Directional Overcurrent (67N)• Four-step Over/Underfrequency (81)• Phase Differential Current (87)• Ground (zero sequence) Differential

Current (87GD)• IPSlogic takes the contact input status and

function status and generates outputs byemploying (OR, AND, and NOT) booleanlogic and a timer.

Protective FunctionsComprehensive PackageThe Comprehensive Package includes all BasePackage functions, as well as the following:

• Three-zone Phase Distance protection forphase fault backup protection (21). Zone threecan be used for Out-of-Step Blocking. Loadencroachment blinders can be applied.

• 100% Stator Ground Fault protection using ThirdHarmonic Neutral Undervoltage (27TN) or (59D)Third Harmonic Voltage Differential (ratio)

• Stator Overload (49) (Positive SequenceOvercurrent)

• Definite Time Overcurrent (50DT) can be usedfor split phase differential

• Out-of-Step (78)• UnderFrequency Accumulation (81A)• Rate of Change of Frequency (81R)

Page 4: Generator Relay Protection

–3–

M-3425A Generator Protection Relay

PROTECTIVE FUNCTIONSDevice SetpointNumber Function Ranges Increment Accuracy†

Phase Distance (three-zone mho characteristic)

Circle Diameter #1,#2,#3 0.1 to 100.0 Ω 0.1 Ω 0.1 Ω or 5%(0.5 to 500.0 Ω) ( 0.5 Ω or 5%)

Offset #1,#2,#3 –100.0 to 100.0 Ω 0.1 Ω 0.1 Ω or 5%(–500.0 to 500.0 Ω) ( 0.5 Ω or 5%)

Impedance Angle #1,#2,#3 0° to 90° 1° 1°

Load Encroachment Blinder #1,#2,#3Angle 1° to 90° 1° 1°R Reach 0.1 to 100 Ω

Time Delay #1,#2,#3 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Out-of-Step Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Overcurrent Supervision 0.1 to 20 A 0.1 A 0.1 A or 2%(0.02 to 4 A) 0.01 A 0.02 A or 2%

When out-of-step blocking on Zone 1 or Zone 2 is enabled, Zone 3 will not trip and it will be used to detect theout-of-step condition for blocking Function 21 #1 and/or 21 #2.

Volts / Hz

Definite TimePickup #1, #2 100 to 200% 1% 1%

Time Delay #1, #2 30 to 8160 Cycles 1 Cycle 25 Cycles

Inverse Time

Pickup 100 to 200% 1% 1%Characteristic Curves Inverse Time #1–#4 — —

Time Dial: Curve #1 1 to 100 1 1%Time Dial: Curves #2–#4 0.0 to 9.0 0.1 1%

Reset Rate 1 to 999 Sec. 1 Sec. 1 Second or 1%(from threshold of trip)

The percent pickup is based on nominal VT secondary voltage and nominal system frequency settings. Thepickup accuracy stated is only applicable from 10 to 80 Hz, 0 to 180 V, 100 to 150% V/Hz and a nominal voltagesetting of 120 V.

Phase Undervoltage

Pickup #1, #2, #3 5 to 180 V 1 V 0.5 V or 0.5%0.8 V or 0.75%*

Time Delay #1, #2, #3 1 to 8160 Cycles 1 Cycle 1 Cycle or 0.5%**

* When both RMS and Line-Ground to Line-Line VT connection is selected.

**When RMS (total waveform) is selected, timing accuracy is O20 cycles or 1%.

†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.

21

24

27

Page 5: Generator Relay Protection

–4–

M-3425A Generator Protection Relay

PROTECTIVE FUNCTIONS (cont.)Device SetpointNumber Function Ranges Increment Accuracy†

Third-Harmonic Undervoltage, Neutral

Pickup #1, #2 0.10 to 14.00 V 0.01 V 0.1 V or 1%

Positive SequenceVoltage Block 5 to 180 V 1 V 0.5 V or 0.5%

Forward Under Power Block 0.01 to 1.00 PU 0.01 PU 0.01 PU or 2%

Reverse Under Power Block –1.00 to –0.01 PU 0.01 PU 0.01 PU or 2%

Lead Under VAr Block –1.00 to –0.01 PU 0.01 PU 0.01 PU or 2%

Lag Under VAr Block 0.01 to 1.00 PU 0.01 PU 0.01 PU or 2%

Lead Power Factor Block 0.01 to 1.00 0.01 0.03 PU or 3%

Lag Power Factor Block 0.01 to 1.00 0.01 0.03 PU or 3%

High Band ForwardPower Block 0.01 to 1.00 PU 0.01 PU 0.01 PU or 2%

Low Band ForwardPower Block 0.01 to 1.00 PU 0.01 PU 0.01 PU or 2%

Time Delay #1, #2 1 to 8160 Cycles 1 Cycle –1 to +5 Cycles or 1%

Directional Power

Pickup #1, #2, #3 –3.000 to +3.000 PU 0.001 PU 0.002 PU or 2%

Time Delay #1, #2, #3 1 to 8160 Cycles 1 Cycle +16 Cycles or 1%

The minimum Pickup limits are –.002 and +.002 respectively.

The per-unit pickup is based on nominal VT secondary voltage and nominal CT secondary current settings. Thisfunction can be selected as either overpower or underpower in the forward direction (positive setting) or reversedirection (negative setting). Element #3 can be set as real power or reactive power. This function includes aprogrammable target LED that may be disabled.

Loss of Field (dual-zone offset-mho characteristic)

Circle Diameter #1, #2 0.1 to 100.0 Ω 0.1 Ω 0.1 Ω or 5%(0.5 to 500.0 Ω) ( 0.5 Ω or 5%)

Offset #1, #2 –50.0 to 50.0 Ω 0.1 Ω 0.1 Ω or 5%(–250.0 to 250.0 Ω) ( 0.5 Ω or 5%)

Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Time Delay withVoltage Control #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Voltage Control 5 to 180 V 1 V 0.5 V or 0.5%(positive sequence)

Directional Element 0° to 20° 1° —

Time delay with voltage control for each zone can be individually enabled.

†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.

40

32

27TN

Page 6: Generator Relay Protection

–5–

M-3425A Generator Protection Relay

PROTECTIVE FUNCTIONS (cont.)Device SetpointNumber Function Ranges Increment Accuracy†

Negative Sequence Overcurrent

Definite TimePickup 3 to 100% 1% 0.5% of 5 A

( 0.5% of 1 A)

Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Inverse TimePickup 3 to 100% 1% 0.5 % of 5 A

( 0.5% of 1 A)

Time Dial Setting 1 to 95 1 3 Cycles or 3%(K= IIIII2

2t)

Definite MaximumTime to Trip 600 to 65,500 Cycles 1 Cycle 1 Cycle or 1%

Definite Minimum Time 12 Cycles — fixed

Reset Time (Linear) 1 to 600 Seconds 1 Second 1 Second or 1%(from threshold of trip)

Pickup is based on the generator nominal current setting.

Stator Overload Protection

Time Constant #1, #2 1.0 to 999.9 minutes 0.1 minutes

Maximum Overload Current 1.00 to 10.00 A 0.01 A 0.1 A or 2%(0.20 to 2.00 A)

Instantaneous Phase Overcurrent

Pickup #1, #2 0.1 to 240.0 A 0.1 A 0.1 A or 3%(0.1 to 48.0 A) ( 0.02 A or 3%)

Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

When frequency f is < (fnom –5 ) Hz add an additional time of (1.5/f + 0.033) sec to the time delay accuracy.

Breaker Failure

PickupPhase Current 0.10 to 10.00 A 0.01 A 0.1 A or 2%

(0.02 to 2.00 A) ( 0.02 A or 2%)

Neutral Current 0.10 to 10.00 A 0.01 A 0.1 A or 2%(0.02 to 2.00 A) ( 0.02 A or 2%)

Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

50BF can be initiated from designated M-3425A output contacts or programmable control/status inputs.

Definite Time Overcurrent

Pickup Phase A #1, #2 0.20 A to 240.00 A 0.01 A 0.1 A or 3%(0.04 A to 48.00 A) ( 0.02 A or 3%)

Pickup Phase B #1, #2 (same as above)

Pickup Phase C #1, #2 (same as above)

Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

This function uses generator line-side currents.

When 50DT function is used for split-phase differential protection, 50BF, 87, and 87GD functions should not beused, and the IIIIIA, IIIIIB and IIIIIC inputs must be connected to the split phase differential currents.†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.

50DT

50

50BF

50BF-Ph

50BF-N

46

49

Page 7: Generator Relay Protection

–6–

M-3425A Generator Protection Relay

PROTECTIVE FUNCTIONS (cont.)Device SetpointNumber Function Ranges Increment Accuracy†

Instantaneous Neutral Overcurrent

Pickup 0.1 to 240.0 A 0.1 A 0.1 A or 3%(0.1 to 48.0 A) ( 0.02 A or 3%)

Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

When the frequency f is < (fnom –5) Hz add an additional time of (1.5/f + 0.033) sec to the time delay accuracy.

Inadvertent Energizing

OvercurrentPickup 0.5 to 15.00 A 0.01 A 0.1 A or 2%

(0.1 to 3.00 A) ( 0.02 A or 2%)

UndervoltagePickup 5 to 130 V 1 V 0.5 V

Pick-up Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Drop-out Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

When RMS (total Waveform) is selected, timing accuracy is O20 cycles or 1%.

Inverse Time Neutral Overcurrent

Pickup 0.25 to 12.00 A 0.01 A 0.1 A or 1%(0.05 to 2.40 A) ( 0.02 A or 1%)

Characteristic Curve Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC CurvesModerately Inverse/Very Inverse/Extremely Inverse/IEEE Curves

Time Dial 0.5 to 11.0 0.1 3 Cycles or 3%*0.05 to 1.10 (IEC curves) 0.010.5 to 15.0 (IEEE curves) 0.01

* For IEC Curves the timing accuracy is 5%.

When the frequency f is < (fnom –5 )Hz add an additional time of (1.5/f + 0.033) sec to the time delay accuracy.

Inverse Time Phase Overcurrent, with Voltage Control or Voltage Restraint

Pickup 0.50 to 12.00 A 0.01 A 0.1 A or 1%(0.10 to 2.40 A) ( 0.02 A or 1%)

Characteristic Curve Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC CurvesModerately Inverse/Very Inverse/Extremely Inverse/IEEE Curves

Time Dial 0.5 to 11.0 0.1 3 Cycles or 3%*0.05 to 1.10 (IEC curves) 0.010.5 to 15.0 (IEEE curves) 0.01

Voltage Control (VC) 5 to 180 V 1 V 0.5 V or 0.5% or

Voltage Restraint (VR) Linear Restraint — —

* For IEC Curves the timing accuracy is 5%.

51V

51N

50N

50/27

50

27

†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.

Page 8: Generator Relay Protection

–7–

M-3425A Generator Protection Relay

PROTECTIVE FUNCTIONS (cont.)Device SetpointNumber Function Ranges Increment Accuracy†

Phase Overvoltage

Pickup #1, #2, #3 5 to 180 V 1 V 0.5 V or 0.5%0.8 V or 0.75%*

Time Delay #1, #2, #3 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%**

Input Voltage Select Phase, Positive or Negative Sequence***

* When both RMS and Line-Ground to Line-Line is selected.

** When RMS (total waveform) is selected, timing accuracy is O20 cycles or 1%.

*** When positive or negative sequence voltage is selected, the 59 Function uses the discrete Fourier transform(DFT) for magnitude calculation, irrespective of the RMS/DFT selection, and timing accuracy is 1 Cycle or 1%.Positive and negative sequence voltages are calculated in terms of line-to-line voltage when Line to Line isselected for V.T. Configuration.

Third-Harmonic Voltage Differential Ratio

Ratio (Vx/VN) 0.1 to 5.0 0.1

Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Positive Seq Voltage Block 5 to 180 V 1 V 0.5 V or 0.5%

Line Side Voltage VX or 3V0 (calculated)

The 59D function with VX cannot be enabled if the 25 function is enabled. The line side voltage can be selectedas the third harmonic of 3V0 (equivalent to VA + VB + VC) or VX.

3V0 selection for line side voltage can only be used with line-ground VT configuration.

Neutral Overvoltage

Pickup #1, #2, #3 5.0 to 180.0 V 0.1 V 0.5 V or 0.5%

Time Delay #1, #2, #3 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

When 64S is purchased, the 59N Time Delay Accuracy is –1 to +5 cycles.

Multi-purpose Overvoltage

Pickup #1, #2 5.0 to 180.0 V 0.1 V 0.5 V or 0.5%

Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Multi-purpose input that may be used for turn-to-turn stator ground protection, bus ground protection, or as anextra Phase-Phase, or Phase-Ground voltage input.

When 64S is purchased, the 59N Time Delay accuracy is –1 to +5 cycles.

VT Fuse-Loss Detection

A VT fuse-loss condition is detected by using the positive and negative sequence componentsof the voltages and currents. VT fuse-loss output can be initiated from internally generatedlogic, and/or from input contacts.

Alarm Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Three Phase VTFuse Loss Detection Enable/Disable

59

59N

60FL

59X

59D

†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.

Page 9: Generator Relay Protection

–8–

M-3425A Generator Protection Relay

PROTECTIVE FUNCTIONS (cont.)Device SetpointNumber Function Ranges Increment Accuracy†

Residual Directional Overcurrent

Definite Time*Pickup 0.5 to 240.0 A 0.1 A 0.1 A or 3%

(0.1 to 48.0 A) ( 0.02 A or 3%)

Time Delay 1 to 8160 Cycles 1 Cycle –1 to +3 Cycles or 1%

Inverse Time*Pickup 0.25 to 12.00 A 0.01 A 0.1 A or 3%

(0.05 to 2.40 A) ( 0.02 A or 3%)

Characteristic Curve Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC CurvesModerately Inverse/Very Inverse/Extremely Inverse/IEEE Curves

Time Dial 0.5 to 11.0 0.1 3 Cycles or 5%0.05 to 1.10 (IEC Curves) 0.010.5 to 15.0 (IEEE curves) 0.01

Directional ElementMax Sensitivity Angle (MSA) 0 to 359° 1°

Polarizing Quantity 3Vo (calculated), VN or VX

*Directional control for 67NDT or 67NIT may be disabled.VX polarization cannot be used if 25 function is enabled.3Vo polarization can only be used with line-ground VT configuration.Operating current for 67N can be selected as 3IIIIIo (calculated) or IIIIIN (Residual CT).

If 87GD is enabled, 67N with IIIIIN (Residual CT) operating current will not be available.

Out of Step (mho characteristic)

Circle Diameter 0.1 to 100.0 Ω 0.1 Ω 0.1 Ω or 5%(0.5 to 500.0 Ω) ( 0.5 Ω or 5%)

Offset –100.0 to 100.0 Ω 0.1 Ω 0.1 Ω or 5%(–500.0 to 500.0 Ω) ( 0.5 Ω or 5%)

Impedance Angle 0° to 90° 1° 1°

Blinder 0.1 to 50.0 Ω 0.1 Ω 0.1 Ω or 5%(0.5 to 250.0 Ω) ( 0.5 Ω or 5%)

Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Trip on mho Exit Enable/Disable

Pole Slip Counter 1 to 20 1

Pole Slip Reset 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Frequency

Pickup #1,#2,#3,#4 50.00 to 67.00 Hz 0.01 Hz 0.02 Hz40.00 to 57.00 Hz*

Time Delay #1–#4 3 to 65,500 Cycles 1 Cycle 2 Cycles or 1%

The pickup accuracy applies to 60 Hz models at a range of 57 to 63 Hz, and to 50 Hz models at a range of 47 to53 Hz. Beyond these ranges, the accuracy is 0.1 Hz.

* This range applies to 50 Hz nominal frequency models.

†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.

81

78

67N

Page 10: Generator Relay Protection

–9–

M-3425A Generator Protection Relay

PROTECTIVE FUNCTIONS (cont.)Device SetpointNumber Function Ranges Increment Accuracy†

Frequency Accumulation

Bands #1, #2, #3, #4, #5, #6High Band #1 50.00 to 67.00 Hz 0.01 Hz 0.02 Hz

40.00 to 57.00 Hz*

Low Band #1–#6 50.00 to 67.00 Hz 0.01 Hz 0.02 Hz40.00 to 57.00 Hz*

Delay #1–#6 3 to 360,000 Cycles 1 Cycle 2 Cycles or 1%

When using multiple frequency bands, the lower limit of the previous band becomes the upper limit for the next band,i.e., Low Band #2 is the upper limit for Band #3, and so forth. Frequency bands must be used in sequential order, 1 to6. Band #1 must be enabled to use Bands #2–#6. If any band is disabled, all following bands are disabled.

When frequency is within an enabled band limit, accumulation time starts (there is an internal ten cycle delay prior toaccumulation) and allows the underfrequency blade resonance to be established to avoid unnecessary accumulationof time. When duration is greater than set delay, the alarm asserts and a target log entry is made.

The pickup accuracy applies to 60 Hz models at a range of 57 to 63 Hz, and 50 Hz models at a range of 47 to 53 Hz.Beyond these ranges, the accuracy is 0.1 Hz.

* This range applies to 50 Hz nominal frequency models.

Rate of Change of Frequency

Pickup #1, #2 0.10 to 20.00 Hz/Sec. 0.01 Hz/Sec. 0.05 Hz/Sec. or 5%

Time Delay #1, #2 3 to 8160 Cycles 1 Cycle + 20 Cycles

Negative SequenceVoltage Inhibit 0 to 99% 1% 0.5%

Phase Differential Current

Pickup #1, #2 0.20 A to 3.00 A 0.01 A 0.1 A or 5%(0.04 to 0.60 A) ( 0.02 A or 5%)

Percent Slope #1, #2 1 to 100% 1% 2%

Time Delay* #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

CT Correction** 0.50 to 2.00 0.01

*When a time delay of 1 cycle is selected, the response time is less than 1–1/2 cycles.

**The CT Correction factor is multiplied by IIIIIA,IIIIIB,IIIIIC.

Ground (zero sequence) Differential Current

Pickup 0.20 to 10.00 A 0.01 A 0.1 A or 5%(0.04 to 2.00 A) ( 0.02 A or 5%)

Time Delay 1 to 8160 Cycles* 1 Cycle +1 to -2 Cycles or 1%

CT Ratio Correction (RC) 0.10 to 7.99 0.01

*The Time Delay Setting should not be less than 2 Cycles.

The 87GD function is provided primarily for low-impedance grounded generator applications. This functionoperates as a directional differential. If 3IIIII0 or IIIIIn is extremely small (less than 0.2 secondary Amps), the elementbecomes non-directional.

If 67N function with IIIIIN (Residual) operating current is enabled, 87GD will not be available. Also, if 50DT is usedfor split-phase differential, 87GD function will not be available.

†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.

87

87GD

81R

81A

Page 11: Generator Relay Protection

–10–

M-3425A Generator Protection Relay

PROTECTIVE FUNCTIONS (cont.)Device SetpointNumber Function Ranges Increment Accuracy†

IPSlogicTM

IPSlogic uses element pickups, element trip commands, control/status input state changes,output contact close signals to develop 6 programmable logic schemes.

Time Delay #1–#6 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

Breaker Monitoring

Pickup 0 to 50,000 kA Cycles 1 kA Cycles 1 kACyclesor kA2 Cycles or kA2 Cycles or kA2 Cycles

Time Delay 0.1 to 4095.9 Cycles 0.1 Cycles 1 Cycle or 1%

Timing Method IIIIIT or IIIII2T

Preset Accumulators 0 to 50,000 kA Cycles 1 kA CyclePhase A, B, C

The Breaker Monitor feature calculates an estimate of the per-phase wear on the breaker contacts by measuring andintegrating the current (or current squared) through the breaker contacts as an arc.

The per-phase values are added to an accumulated total for each phase, and then compared to a user-programmedthreshold value. When the threshold is exceeded in any phase, the relay can set a programmable output contact.

The accumulated value for each phase can be displayed.

The Breaker Monitoring feature requires an initiating contact to begin accumulation, and the accumulation beginsafter the set time delay.

Trip Circuit Monitoring

Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%

The AUX input is provided for monitoring the integrity of the trip circuit. This input can be used for nominal tripcoil voltages of 24 V dc, 48 V dc, 125 V dc and 250 V dc.

Nominal Settings

Nominal Voltage 50.0 to 140.0 V 0.1 V —

Nominal Current 0.50 to 6.00 A 0.01 A —

VT Configuration Line-Line/Line-Ground/Line-Ground to Line-Line*

Delta/Wye UnitTransformer Disable/Delta AB/Delta AC

Seal-In Delay 2 to 8160 Cycles 1 Cycle 1 Cycle or 1%

*When Line-Ground to Line-Line is selected, the relay internally calculates the line-line voltages from the line-groundvoltages for all voltage-sensitive functions. This Line-Ground to Line-Line selection should only be used for a VTconnected Line-Ground with a secondary voltage of 69 V (not 120 V).

†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.

IPS

BM

TC

Page 12: Generator Relay Protection

–11–

M-3425A Generator Protection Relay

64F

64B

25

25S

25D

64S

OPTIONAL PROTECTIVE FUNCTIONSDevice SetpointNumber Function Ranges Increment Accuracy†

Sync Check

Dead CheckDead Voltage Limit 0 to 60 V 1 V 0.5 V or ±0.5%

Dead Time Delay 1 to 8160 Cycles 1 Cycle –1 to +3 Cycles or 1%

Sync CheckPhase Angle Limit 0° to 90° 1° 1°

Upper Voltage Limit 60 to 140 V 1 V 0.5 V or ±0.5%

Lower Voltage Limit 40 to 120 V 1 V 0.5 V or ±0.5%

Delta Voltage Limit 1.0 to 50.0 V 0.1 V 0.5 V or ±0.5%

Delta Frequency Limit 0.001 to 0.500 Hz 0.001 Hz 0.0007 Hz or ±5%

Sync Check Time Delay 1 to 8160 Cycles 1 Cycle –1 to +3 Cycles or ±1%

Various combinations of input supervised hot/dead closing schemes may be selected. The 25 function cannot beenabled if the 59D function with VX or 67N function with VX is enabled.

Field Ground Protection

Pickup #1, #2 5 to 100 KΩ 1 KΩ 10% or ±1KΩTime Delay #1, #2 1 to 8160 Cycles 1 Cycle ( 2

IF +1) Sec.

Injection Frequency (IF) 0.10 to 1.00 Hz 0.01 Hz

Brush Lift-Off Detection (measuring control circuit)Pickup 0 to 5000 mV 1 mV

Time Delay 1 to 8160 Cycles 1 Cycle ( 2IF +1) Sec.

When 64F is purchased, an external Coupler Module (M-3921) is provided for isolation from dc field voltages.

Figure 10, Field Ground Protection Block Diagram, illustrates a typical connection utilizing the M-3921 FieldGround Coupler. Hardware dimensional and mounting information is shown in Figure 11, M-3921 Field GroundCoupler Mounting Dimensions.

100% Stator Ground Protection by low frequency injection

Total Current Pickup 2 to 75 mA 0.1 mA 2 mA or 10%Real Component ofTotal Current Pickup 2 to 75 mA 0.1 mA 2 mA or 10%Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle* or 1%

An external Low Frequency Generator, Band Pass Filter and Current Transformer are required for this function.Figure 12, 64S Function Component Connection Diagram, illustrates a typical 100% Stator Ground Protection byLow Frequency Injection application. Hardware dimensional and mounting information is illustrated in Figures13, 14 and 15.

59D and 27TN function should be disabled when the 64S function is enabled. 59N may be applied when thisfunction is enabled.

* Time Delay accuracy in cycles is based on 20 Hz frequency.

†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.

Page 13: Generator Relay Protection

–12–

M-3425A Generator Protection Relay

DescriptionThe M-3425A Generator Protection Relay is suitable for all generator ratings and prime movers. Typicalconnection diagrams are illustrated in Figure 4, M-3425A One-Line Functional Diagram (configured for phasedifferential), and Figure 5, One-Line Functional Diagram (configured for split-phase differential).

Configuration OptionsThe M-3425A Generator Protection Relay is available in either a Base or Comprehensive package ofprotective functions. This provides the user with flexibility in selecting a protective system to best suit theapplication. Additional Optional Protective Functions may be added at the time of purchase at per-functionpricing.

The Human-Machine Interface (HMI) Module, Target Module, or redundant power supply can be selected attime of purchase.

When the Field Ground (64F) Premium Protective Function is purchased, an external coupler module(M-3921) is provided for isolation from the dc field voltages.

When 100% Stator Ground (64S) protection using low-frequency injection is purchased, an external bandpass filter and frequency generator is provided.

Multiple Setpoint Profiles (Groups)The relay supports four setpoint profiles. This feature allows multiple setpoint profiles to be defined for differentpower system configurations or generator operating modes. Profiles can be switched either manually usingthe Human-Machine Interface (HMI), by communications, programmable logic or by control/status inputs.

NOTE: During profile switching, relay operation is disabled for approximately 1 second.

MeteringThe relay provides metering of voltages (phase, neutral and sequence quantities), currents (phase, neutraland sequence quantities), real power, reactive power, power factor and impedance measurements.

Metering accuracies are:

Voltage: 0.5 V or 0.5%, whichever is greater0.8 V or 0.75%, whichever is greater (when both RMS and Line-Ground to Line-Line are

selected)

Current: 5 A rating, 0.1 A or 3%, whichever is greater1 A rating, 0.02 A or 3%, whichever is greater

Power: 0.01 PU or 2% of VA applied, whichever is greater

Frequency: 0.02 Hz (from 57 to 63 Hz for 60 Hz models; from 47 to 53 Hz for 50 Hz models)0.1 Hz beyond 63 Hz for 60 Hz models, and beyond 53 Hz for 50 Hz models

Volts/Hz: 1%

Oscillographic RecorderThe oscillographic recorder provides comprehensive data recording of all monitored waveforms, storing up to416 cycles of data. The total record length is user-configurable from 1 to 16 partitions. The sampling rate is 16times the power system nominal frequency (50 or 60 Hz). The recorder may be triggered using either thedesignated control/status inputs, trip outputs, or using serial communications. When untriggered, the recordercontinuously stores waveform data, thereby keeping the most recent data in memory. When triggered, therecorder stores pre-trigger data, then continues to store data in memory for a user-defined, post-trigger delayperiod. The data records can be stored in either Beckwith Electric format or COMTRADE format.

Target StorageInformation associated with the last 32 trips is stored. The information includes the function(s) operated, thefunctions picked up, input/output status, time stamp, and phase and neutral currents at the time of trip.

Page 14: Generator Relay Protection

–13–

M-3425A Generator Protection Relay

Sequence of Events LogThe Sequence of Events Log records relay element status, I/O status, measured values and calculated valuestime stamped with 1 ms resolution at user-defined events. The Sequence of Events Log includes 512 of themost recently recorded relay events. The events and the associated data is available for viewing utilizing theM-3820D IPScom Communications Software.

CalculationsCurrent and Voltage RMS Values: Uses Discrete Fourier Transform algorithm on sampled voltage and currentsignals to extract fundamental frequency phasors for relay calculations. RMS calculation for the 50, 51N, 59and 27 functions, and the 24 function are obtained using the time domain approach to obtain accuracy over awide frequency band. When the RMS option is selected, the magnitude calculation for 59 and 27 functions isaccurate over a wide frequency range (10 to 80 Hz). When the DFT option is selected, the magnitudecalculation is accurate near nominal frequency (50 Hz/60 Hz) but will degrade outside the nominal frequency.For 50 and 51N functions the DFT is used when the frequency is 55 Hz to 65 Hz for 60 Hz (nominal) and 45 Hzto 55Hz for 50 Hz (nominal), outside of this range RMS calculation is used.

Power Input OptionsNominal 110/120/230/240 V ac, 50/60 Hz, or nominal 110/125/220/250 V dc. Operates properly from 85 V acto 265 V ac and from 80 V dc to 312.5 V dc. Withstands 300 V ac or 315 V dc for 1 second. Nominal burden 40VA at 120 V ac/125 V dc.

Nominal 24/48 V dc, operates properly from 18 V dc to 56 V dc, withstands 65 V dc for 1 second. Burden 25 VAat 24 V dc and 30 VA at 48 V dc.

An optional redundant power supply is available for units that are purchased without the expanded I/O.

For those units purchased with the expanded I/O, the unit includes two power supplies which are required topower the relay. Burden (nominal) 46 VA @120 V ac.

Sensing InputsFive Voltage Inputs: Rated for a nominal voltage of 50 V ac to 140 V ac at 60 Hz or 50 Hz. Will withstand 240 Vcontinuous voltage and 360 V for 10 seconds. Source voltages may be line-to-ground or line-to-line connected.Phase sequence ABC or ACB is software selectable. Voltage transformer burden less than 0.2 VA at 120 V ac.

Seven Current Inputs: Rated nominal current (IIIIIR) of 5.0 A or 1.0 A at 60 Hz or 50 Hz. Will withstand 3IIIIIR

continuous current and 100IIIIIR for 1 second. Current transformer burden is less than 0.5 VA at 5 A, or 0.3 VA

at 1 A.

Control/Status InputsThe control/status inputs, INPUT1 through INPUT6, can be programmed to block any relay protective function,to trigger the oscillograph recorder, to operate one or more outputs or can be an input into IPSlogic. To providebreaker status LED indication on the front panel, the INPUT1 control/status input contact must be connected tothe 52b breaker status contact.

The optional expanded I/O includes an additional 8 programmable control/status inputs (INPUT7 throughINPUT14).

CAUTION: The control/status inputs should be connected to dry contacts only, and are internally connected(wetted) with a 24 V dc power supply.

Output ContactsAny of the functions can be individually programmed to activate any one or more of the eight programmableoutput contacts OUTPUT1 through OUTPUT8. Any output contact can also be selected as pulsed or latched.IPSlogic can also be used to activate an output contact.

The optional expanded I/O includes an additional 15 programmable output contacts (OUTPUT9 throughOUTPUT23). These contacts are configurable only using IPScom software.

The eight output contacts (six form ‘a’ and two form ‘c’), the power supply alarm output contact (form ‘b’), theself-test alarm output contact (form ‘c’) and the optional 15 expanded I/O output contacts (form 'a') are all ratedper ANSI/IEEE C37.90-1989 for tripping. Make 30 A for 0.2 seconds, carry 8 A, break 6 A at 120 V ac, break0.5 A at 48 V dc; 0.3 A, 125 V dc; 0.2 A, 250 V dc with L/R=40 mSec.

Page 15: Generator Relay Protection

–14–

M-3425A Generator Protection Relay

IPSlogicThis feature can be programmed utilizing the IPScom® Communications Software. IPSlogic takes the contactinput status and function status, and by employing (OR, AND, and NOT) boolean logic and a timer, canactivate an output or change setting profiles.

Target/Status Indicators and ControlsThe RELAY OK LED reveals proper cycling of the microcomputer. The BRKR CLOSED LED will illuminatewhen the breaker is closed (when the 52b contact input is open). The OSC TRIG LED indicates thatoscillographic data has been recorded in the unit's memory. The TARGET LED will illuminate when any of therelay functions operate. Pressing and releasing the TARGET RESET button resets the target LED if theconditions causing the operation have been removed. Holding the TARGET RESET push button displays thepresent pickup status of the relay functions. The PS1 and PS2 LEDs will remain illuminated as long as poweris applied to the unit and the power supply is operating properly. TIME SYNC LED illuminates when validIRIG-B signal is applied and time synchronization has been established.

CommunicationCommunications ports include rear panel RS-232 and RS-485 ports, a front panel RS-232 port, a rear-panelIRIG-B port and an Ethernet port (optional). The communications protocol implements serial, byte-oriented,asynchronous communication, providing the following functions when used with the Windows™-compatibleM-3820D IPScom® Communications Software. MODBUS and BECO 2200 protocols are supported providing:

• Interrogation and modification of setpoints

• Time-stamped information for the 32 most recent trips

• Real-time metering of all quantities measured

• Downloading of recorded oscillographic data and Sequence of Events Recorder data.

The optional Ethernet port can be purchased with MODBUS over TCP/IP and BECO2200 over TCP/IPprotocols or with the IEC 61850 protocol.

IRIG-BThe M-3425A Generator Protection Relay can accept either modulated or demodulated IRIG-B time clocksynchronization signal. The IRIG-B time synchronization information is used to correct the hour, minutes,seconds, and milliseconds information.

HMI Module (optional)Local access to the relay is provided through an optional M-3931 HMI (Human-Machine Interface) Module,allowing for easy-to-use, menu-driven access to all functions utilizing six pushbuttons and a 2-line by24 character alphanumeric vacuum florescent display. Features of the HMI Module include :

• User-definable access codes that allow three levels of security

• Interrogation and modification of setpoints

• Time-stamped information for the 32 most recent trips

• Real-time metering of all quantities measured

Target Module (optional)An optional M-3925A Target Module provides 24 target and 8 output LEDs. Appropriate target LEDs willilluminate when the corresponding function operates. The targets can be reset with the TARGET RESETpushbutton. The OUTPUT LEDs indicate the status of the programmable output relays.

Page 16: Generator Relay Protection

–15–

M-3425A Generator Protection Relay

Temperature Controller MonitoringAny Temperature Controller equipped with a contact output may be connected to the M-3425A and controlledby the relay's programmable IPSlogic function. Figure 1 is an example of a typical Temperature ControllerMonitoring application. The Omron E5C2 Temperature Controller is a DIN rail mounted RTD interface to theM-3425A Generator Protection relay. The E5C2 accepts type J or K thermocouples, platinum RTDs orthermistors as its input. Supply voltage for the E5C2 accepts 110/120 V ac, 50/60 Hz, or 220/240 V ac50/60 Hz or 24 V dc.

TemperatureController

Omron E5C2P.D. 750

or equivalent

IN X

IN RTN

M-3425A

IPSlogic

Alarm/TripR1C

R2

Figure 1 Typical Temperature Controller Monitoring Application

I/O Expansion (optional)Optional I/O Expansion provides an additional 15 form 'a' output contacts and an additional 8 control/statusinputs. Output LEDs indicate the status of the output relays.

Tests and StandardsThe relay complies with the following type tests and standards:

Voltage Withstand

Dielectric WithstandIEC 60255-5 3,500 V dc for 1 minute applied to each independent circuit to earth

3,500 V dc for 1 minute applied between each independent circuit1,500 V dc for 1 minute applied to IRIG-B circuit to earth1,500 V dc for 1 minute applied between IRIG-B to each independent circuit1,500 V dc for 1 minute applied between RS-485 to each independent circuit

Impulse VoltageIEC 60255-5 5,000 V pk, +/- polarity applied to each independent circuit to earth

5,000 V pk, +/- polarity applied between each independent circuit1.2 by 50 μs, 500 ohms impedance, three surges at 1 every 5 seconds

Insulation ResistanceIEC 60255-5 > 100 Megaohms

Page 17: Generator Relay Protection

–16–

M-3425A Generator Protection Relay

Electrical Environment

Electrostatic Discharge TestEN 60255-22-2 Class 4 (8 kV)—point contact discharge

EN 60255-22-2 Class 4 (15kV)–air discharge

Fast Transient Disturbance TestEN 60255-22-4 Class A (4 kV, 2.5 kHz)

Surge Withstand CapabilityANSI/IEEE 2,500 V pk-pk oscillatory applied to each independent circuit to earthC37.90.1- 2,500 V pk-pk oscillatory applied between each independent circuit1989 5,000 V pk Fast Transient applied to each independent circuit to earth

5,000 V pk Fast Transient applied between each independent circuit

ANSI/IEEE 2,500 V pk-pk oscillatory applied to each independent circuit to earthC37.90.1- 2,500 V pk-pk oscillatory applied between each independent circuit 2002 4,000 V pk Fast Transient burst applied to each independent circuit to earth

4,000 V pk Fast Transient burst applied between each independent circuit

NOTE: The signal is applied to the digital data circuits (RS-232, RS-485, IRIG-B, Ethernet communicationport and field ground coupling port) through capacitive coupling clamp.

Radiated SusceptibilityANSI/IEEE 25-1000 Mhz @ 35 V/mC37.90.2

Output ContactsANSI/IEEE Make 30 A for 0.2 seconds, off for 15 seconds for 2,000 operations, per Section 6.7.1, TrippingC37.90.0 Output Performance Requirements

Atmospheric Environment

TemperatureIEC 60068-2-1 Cold, –20° CIEC 60068-2-2 Dry Heat, +70° CIEC 60068-2-3 Damp Heat, +40° C @ 93% RH

Mechanical Environment

VibrationIEC 60255-21-1 Vibration response Class 1, 0.5 g

Vibration endurance Class 1, 1.0 g

IEC 60255-21-2 Shock Response Class 1, 5.0 gShock Withstand Class 1, 15.0 gBump Endurance Class 1, 10.0 g

Page 18: Generator Relay Protection

–17–

M-3425A Generator Protection Relay

ComplianceUL-Listed per 508 – Industrial Control Equipment

UL-Listed Component per 508A Table SA1.1 Industrial Control Panels

CSA-Certified per C22.2 No. 14-95 – Industrial Control Equipment

CE Safety Directive – EN61010-1:2001, CAT II, Pollution Degree 2

PhysicalWithout Optional Expanded I/O

Size: 19.00" wide x 5.21" high x 10.20" deep (48.3 cm x 13.2 cm x 25.9 cm)

Mounting: The unit is a standard 19", semiflush, three-unit high, rack-mount panel design, conforming toANSI/EIA RS-310C and DIN 41494 Part 5 specifications. Vertical or horizontal panel-mount options areavailable.

Approximate Weight: 17 lbs (7.7 kg)

Approximate Shipping Weight: 25 lbs (11.3 kg)

With Optional Expanded I/O

Size: 19.00" wide x 6.96" high x 10.2" deep (48.3 cm x 17.7 cm x 25.9 cm)

Mounting: The unit is a standard 19", semiflush, four-unit high, rack-mount panel design, conforming to ANSI/EIA RS-310C and DIN 41494 Part 5 specifications. Vertical or horizontal panel-mount options are available.

Approximate Weight: 19 lbs (8.6 kg)

Approximate Shipping Weight: 26 lbs (11.8 kg)

Recommended Storage Parameters

Temperature: 5° C to 40° C

Humidity: Maximum relative humidity 80% for temperatures up to 31° C, decreasing to 31° Clinearly to 50% relative humidity at 40° C.

Environment: Storage area to be free of dust, corrosive gases, flammable materials, dew,percolating water, rain and solar radiation.

See M-3425A Instruction Book, Appendix E, Layup and Storage for additional information.

Patent & WarrantyThe M-3425A Generator Protection Relay is covered by U.S. Patents 5,592,393 and 5,224,011.

The M-3425A Generator Protection Relay is covered by a five year warranty from date of shipment.

Specification subject to change without notice.

External ConnectionsM-3425A external connection points are illustrated in Figures 2 and 3.

Page 19: Generator Relay Protection

–18–

M-3425A Generator Protection Relay

Figu

re 2

Exte

rnal

Con

nect

ions

(With

out O

ptio

nal E

xpan

ded

I/O)

NO

TE

S:

1.S

ee M

-342

5A In

stru

ctio

n B

ook

Sec

tion

2.3,

Set

poin

ts a

nd T

ime

Set

tings

, sub

sect

ion

for

64B

/F F

ield

Gro

und

Pro

tect

ion.

2.B

efor

e m

akin

g co

nnec

tions

to

the

Trip

Circ

uit

Mon

itorin

g in

put,

see

M-3

425A

Ins

truc

tion

Boo

k S

ectio

n 5.

5, C

ircui

t B

oard

Sw

itche

s an

dJu

mpe

rs, f

or th

e in

form

atio

n re

gard

ing

setti

ng T

rip C

ircui

t Mon

itorin

g in

put v

olta

ge. C

onne

ctin

g a

volta

ge o

ther

than

the

volta

ge th

at th

e un

it is

conf

igur

ed to

may

res

ult i

n m

is-o

pera

tion

or p

erm

anen

t dam

age

to th

e un

it.

3.8888 8

WA

RN

ING

: ON

LY

DR

Y C

ON

TA

CT

S m

ust

be

con

nec

ted

to in

pu

ts (t

erm

inal

s 5

thro

ug

h 1

0 w

ith

11

com

mo

n) b

ecau

se th

ese

con

tact

inp

uts

are

inte

rnal

ly w

ette

d. A

pp

licat

ion

of

exte

rnal

vo

ltag

e o

n t

hes

e in

pu

ts m

ay r

esu

lt in

dam

age

to t

he

un

its.

4.8888 8

WA

RN

ING

: Th

e p

rote

ctiv

e g

rou

nd

ing

term

inal

mu

st b

e co

nn

ecte

d to

an

ear

thed

gro

un

d a

ny

tim

e ex

tern

al c

on

nec

tio

ns

hav

e b

een

mad

e to

th

e u

nit

.

!!

"#$

%&'

!!((

')

')

(

& *&'+

'%

,

-

'

....""..

(

(/

/

!"

""""!!!!

!

"

!

"

0

,!

1

!"

!

"

(

*

*

*

2.(............................................&2.(

(/

/(

(

(

(-')

3

"

-

Page 20: Generator Relay Protection

–19–

M-3425A Generator Protection Relay

!

"

'

!!((

"#$

!!

%&'

& *&'+

'%

!!

!!

!"

!"

""

""

""

""!

"""

3

....""..

-

!!!!

""""

!

"

(

/(

(

/

,

!

"

"

!

"

(

0 ,

!

!

!

"

1

!

"

"

!"

!!

!!

!!

*

*

*

(

(

//

((

(-')

2.(.......................&2.(

')

')

Figu

re 3

Exte

rnal

Con

nect

ions

(With

Opt

iona

l Exp

ande

d I/O

)

NO

TE

S:

1.S

ee M

-342

5A In

stru

ctio

n B

ook

Sec

tion

2.3,

Set

poin

ts a

nd T

ime

Set

tings

, sub

sect

ion

for

64B

/F F

ield

Gro

und

Pro

tect

ion.

2.B

efor

e m

akin

g co

nnec

tions

to

the

Trip

Circ

uit

Mon

itorin

g in

put,

see

M-3

425A

Ins

truc

tion

Boo

k S

ectio

n 5.

5, C

ircui

t B

oard

Sw

itche

s an

dJu

mpe

rs, f

or th

e in

form

atio

n re

gard

ing

setti

ng T

rip C

ircui

t Mon

itorin

g in

put v

olta

ge. C

onne

ctin

g a

volta

ge o

ther

than

the

volta

ge th

at th

e un

it is

conf

igur

ed to

may

res

ult i

n m

is-o

pera

tion

or p

erm

anen

t dam

age

to th

e un

it.

3.8888 8

WA

RN

ING

: O

NL

Y D

RY

CO

NT

AC

TS

mu

st b

e co

nn

ecte

d t

o i

np

uts

(te

rmin

als

5 th

rou

gh

10

wit

h 1

1 co

mm

on

an

d t

erm

inal

s 68

thro

ug

h 7

5 w

ith

66

and

67

com

mo

n)

bec

ause

th

ese

con

tact

in

pu

ts a

re i

nte

rnal

ly w

ette

d.

Ap

plic

atio

n o

f ex

tern

al v

olt

age

on

th

ese

inp

uts

may

res

ult

in d

amag

e to

th

e u

nit

s.

4.8888 8

WA

RN

ING

: Th

e p

rote

ctiv

e g

rou

nd

ing

term

inal

mu

st b

e co

nn

ecte

d to

an

ear

thed

gro

un

d a

ny

tim

e ex

tern

al c

on

nec

tio

ns

hav

e b

een

mad

e to

th

e u

nit

.

Page 21: Generator Relay Protection

–20–

M-3425A Generator Protection Relay

50DT

Utility System

52Unit

52Gen

50BFPh

87

492132 504078 60FL 51V 50/27

27

81R 81 27 59 24

64F 64B

M-3921+

-

CT

VT

M-3425A

87GD 50N50

BFN 51N

R

64S27TN

27

32R

High-impedance Grounding with ThirdHarmonic 100% Ground Fault Protection

Low-impedance Grounding with Ground Differentialand Overcurrent Stator Ground Fault Protection

These functions are available inthe Comprehensive Package. Asubset of these functions are alsoavailable in a Base Package.

This function is available as aoptional protective function.

This function provides control forthe function to which it points.

M-3425A TypicalConnection Diagram

25

59D

VT (Note 1)

Targets(Optional)

Integral HMI(Optional)

Metering

Waveform Capture

IRIG-B

Front RS232Communication

Multiple SettingGroups

Programmable I/O

Self Diagnostics

Dual Power Supply(Optional)

Rear Ethernet Port (Optional)

Rear RS-485Communication

BreakerMonitoring

Trip CircuitMonitoring

67N67N Polarization(Software Select)

81A

50N50BFN 51N

46

59X

59N

3VO (Calculated)VX

VN

3IO

IN

67N Operating Current(Software Select)

VT (Note 1)

(Note 3)

(Note 5)

CT (Residual)(Note 4)

59D Line SideVoltage

(Software Select)

VX3VO (Calculated)

CT (Neutral)(Notes 2 & 5)

CTM

(Metering)

M

(Metering)

Rear RS232Communication

Event Log

NOTES:1. When 25 function is enabled, 59X, 59D with V

X and 67N with V

X are not available, and vice versa.

2. When 67N function with IN (Residual) operating current is enabled, 87GD is not available, and vice

versa.3. When VT source is used as a turn-to-turn fault protection device (See M-3425A Instruction Book,

Chapter 2, Application, for additional 59X applications.)4. The current input I

N can be connected either from neutral current or residual current.

5. The 50BFN, 50N, 51N, 59D, 67N (with IN or V

N) and 87GD functions are unavailable when the 64S

function has been purchased. See the M-3425A Instruction Book for connection details.

Figure 4 One-Line Functional Diagram (Configured with Phase Differential)

Page 22: Generator Relay Protection

–21–

M-3425A Generator Protection Relay

Utility System

52Unit

52Gen

81R 81 59 27 24

M-3921+

-

VT

CT

M-3425A

50N 51N

R

CT

27

32R

High-impedance Grounding with ThirdHarmonic 100% Ground Fault Protection

Low-impedance Grounding withOvercurrent Stator Ground Fault Protection

These functions are available inthe Comprehensive Package. Asubset of these functions are alsoavailable in a Base Package.

This function is available as aoptional protective function.

This function provides control forthe function to which it points.

M-3425A TypicalConnection Diagram(Configured for Split-Phase Differential)

25

59D

50DT

67N

Targets(Optional)

Integral HMI(Optional)

Metering

Waveform Capture

IRIG-B

Front RS232Communication

Multiple SettingGroups

Programmable I/O

Self Diagnostics

Dual Power Supply(Optional)

Rear EthernetPort (Optional)

Rear RS-485Communication

BreakerMonitoring

Trip CircuitMonitoring

27TN

81A

46492132 504078 60FL 51V 50/27

2764F 64B

59X

64S 59N

CT (Residual)(Note 5)

VT (Note 1)

VT (Note 1)

67N Polarization(Software Select)

3VO (Calculated)

VX

VN

(Note 2)

CT (Note 3)

(Note 4)

59D Line SideVoltage

(Software Select)

VX 3VO (Calculated)

CT (Neutral)(Note 5)

M

(Metering)

M

(Metering)

Rear RS232Communication

Event Log

NOTES:

1. When 25 function is enabled, 59X, 59D with VX and 67N with V

X are not available, and vice versa.

2. When used as a turn-turn fault protection device.

3. CTs are connected for split-phase differential current.

4. 67N operating current can only be selected to IN

(Residual) for this configuration.

5. The current input (IN) can be connected either from neutral current or residual current.

6. The 50BFN, 50N, 51N, 59D, 67N (with IN or V

N) and 87GD functions are unavailable when the 64S

function has been purchased. See the M-3425A Instruction Book for connection details.

Figure 5 One-Line Functional Diagram (configured for split-phase differential)

Page 23: Generator Relay Protection

–22–

M-3425A Generator Protection Relay

Standard 19" Horizontal Mount Chassis

19.00[48.26]

17.50[44.5]

17.50[44.5]

ACTUAL

5.21[13.23]

ACTUAL

0.40 [1.02] X 0.27[0.68] Slot (4X)

10.20[25.91]

19.00[48.26]

18.34[46.58]

0.33[0.84]

1.48[3.8]

2.25[5.72]

NOTES: 1. Dimensions in brackets are in centimeters.

2. See Instruction Book Chapter 5 for Mounting and Cutout information.

Figure 6 Horizontal Unit Dimensions Without Expanded I/O (H1)

Page 24: Generator Relay Protection

–23–

M-3425A Generator Protection Relay

Optional Vertical Mount Chassis

1.67[4.24]

19.00[48.26]

18.34[46.58]

2.25[5.72]

0.28 [0.71]Dia. (4X)

17.50[44.5]

5.59[14.20]

1.67[4.24]

2.25[5.72]

10.20[25.91]

COM 1

M-3425AGENERATORPROTECTION

TARGETS

OUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

OUTPUTSOUT 7

OUT 8

EXIT ENTER

TARGET DIAG

TIME

OSC.TRIG

SYNC

BRKRCLOSED

OKRELAY

TARGETRESET

PS 2 PS 1

19.00[48.26]

17.50[44.5]

NOTES: 1. Dimensions in brackets are in centimeters.

2. See Instruction Book Chapter 5 for Mounting and Cutout information.

Figure 7 Vertical Unit Dimensions Without Expanded I/O (H2)

Page 25: Generator Relay Protection

–24–

M-3425A Generator Protection Relay

Figure 8 M-3425A Vertical Unit Layout

50

Hz

60

Hz

SE

RIA

LN

O.

MO

DEL: M

-3425A FIRM

WAR

E: D

-0150

659

IRIG- B

35

36

6 4 F

RA

TE

DV

OL

TA

GE

60

-140

VA

C,5

0/6

0H

z

39

40

37

38

44

42

43

41

64

COUPLER

ET HERNETCO M 2

FIELD GROUND

!

COM 3RS 4 8 5

B CV

V A B

VVA

BV

V C

VA

C

!

4824

125

A UX250 -

++

IN6

IN5

-

RA

TE

DC

UR

RE

NT

1A,N

OM

5A

,NO

M

45

46

V

65

X

50

47

49

48

55

53

54

51

520.0

1AN

OM

64

S

58

56

57

ALARMS

INPUTS

A

VN

I

BI

IC

!

IN2

IN1

(52b)

IN3

IN4

RT NIN

P/S

OUTPUTS

IN

aI

I b

I c

SELF-TEST

8

7

COM 2

BE

CK

WIT

HE

LEC

TR

ICC

O.

INC

.6

190

118th

AV

EN

O.

LA

RG

O,

FL

33

77

3

RS 2 3 2

1

3

5

4

2

6

72

7-5

44

-23

26

14

WA

RN

ING

!C

ON

TA

CT

WIT

HT

ER

MIN

AL

SM

AY

CA

US

EE

LE

CT

RIC

SH

OC

KF

OR

CO

NT

AC

TR

AT

ING

SS

EE

INS

TR

UC

TIO

NM

AN

UA

L

10

8

9

7

13

12

11

16

18

17

15

22

20

19

21

23

63

60

62

61

55

26

86

5-

18-

-6

58

52

1-

85

6

F3

F43 A MP,

(3A B) 1

+

-

-

+

PS 2

PS 1

PS2

F1

F2

5

4

3

2

PS1

25

24

27

26

28

31

29

30

33

32

34

U.S. PATEN

T 5,592,393, 5,224,011

NRTL /CLR 89464

R

COM 1

TARGETS

OUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

OUTPUTS

OUT 7

OUT 8

EXIT ENTER

TARGET

BRKRCLOSED

TARGETRESET

PS 2

DIAG

PS 1

OSC.TRIG

TIMESYNCOK

RELAY

R

M-3425AGENERATORPROTECTION

250V,

Page 26: Generator Relay Protection

–25–

M-3425A Generator Protection Relay

NOTES: 1. Dimensions in brackets are in centimeters.

2. See Instruction Book Chapter 5 for Mounting and Cutout information.

Figure 9 Horizontal and Vertical Unit Dimensions With Expanded I/O (H5 and H6)

045 67

+

%+

%

!89

""!89

( .

....8..9.

"89

"8!9

89

!

89

89

"

! "

'

% &

.

.

.

.

.

.

.!

.

Page 27: Generator Relay Protection

–26–

M-3425A Generator Protection Relay

FOR

CO

NTAC

T RATIN

GS SEE IN

STRU

CTIO

NAL M

ANU

ALW

ARN

ING

! CO

NTAC

T WITH

TERM

INALS M

AY CAU

SE ELECTR

IC SH

OC

K50H

z60H

zSER

IAL NO

.FIR

MW

ARE

: D-0150

MO

DE

L: M-3425A

COUPLER

FIELD

GND

IND. CONT. EQ.LISTED

RC US

83F4

RTNIN

COM 2

COM 2

IRIG-B

105

104

102

101

100

99

96

97

95

94

98

9392

90

91

103

89

88

86

85

84

83

87

80

81

79

78

77

76

74

73

75

82

72

71

69

68

70

67

66

RS232

ETHERNET

64F

IN 10

IN 9

IN 8

IN 7

IN 14

IN 13

IN 12

IN 11

INPUTS

OUTPUTS

15

16

17

18

19

20

21

22

23

9

10

11

12

13

14

F4 F2

F3 F1

6381

5-8 6

625

62

55 265-6

6181

59

58

608

5

1

PS 2 2

34

33

32

-

330

31

29

+PS1 4

-PS2 5

27

26

6I c

24

22

23

25+ O

UTPUTS 28

250V

PS1

57

55

56

54

6 4 S

530.01A NOM

51

50

48

47

49

52

bI7 21

19

20

8

17

18

16

I

P/SALARMS

C

15

14

13

BI

A !

RT N 11IN

12

SELF

46

65

45

XV

64

44

43

41

42

40

39

I

(52b)10

9

NV7

5

6

IN 6

8INPUTS

VCV AC

C

-COM 3RS485

4

3

2+

+

VV B

-AUX

V

BAVA

!48

250125

1

24

B

37

36

35

!

38

-

-

IN 5

IN 4

IN 3

IN 2

IN 1

TEST

3AMP

(3AB)

VOLTAGERATED

60-140VAC50/60Hz

5 A, NO M

1A ,N O M

RATEDCURRENT

I

I

a

N

LAR

GO

,FL

33

7736

190118

thAV

EN

O.

BE

CK

WIT

HE

LE

CT

RIC

CO

.IN

C.

727-54

4-23

26

OUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

OUTPUTSOUT 7

OUT 8

TARGETS

EXIT ENTER

COM 19

10

TARGET DIAG

TIME

OSC.TRIG

SYNC

BRKRCLOSED

OKRELAY

TARGETRESET

11

12

14

15

16

OUTPUTS

17

18

19

22

20

21

23

13

PS 2 PS 1

.

R

CHIWK T

IC RTEEBLEC CNI.CO

Made in U.S.A.

M-3425AGENERATORPROTECTION

NOTES:

1. The M-3425A Expanded I/O vertical panel is the same physical size as the M-3425A Expanded I/O horizontal panel. See Figure 7 for dimennsions.

2. See Instruction Book Section 5 for Mounting and Cutout information.

U.S. PATENT5,592,3935,224,011

Figure 10 M-3425A Expanded I/O Vertical Unit Layout

Page 28: Generator Relay Protection

–27–

M-3425A Generator Protection Relay

M-3921 Field Ground Coupler

!

"#$#%#

&##'(

#!''&

)*+,-./

0#!1#(

1#2 3'1

4! # 5' (

6

3'1'

Figure 11 Field Ground Protection Block Diagram

NOTES:1. The above circuit measures insulation resistance (R

f) between rotor field winding and ground (64F).

2. Relay injects 15 V squarewave (Vout

) and measures return signal (Vf) to calculate R

f.

3. The injection frequency can be set (0.1 to 1.0 Hz) based on the rotor capacitance, in order toimprove accuracy.

4. The signal rise time is analyzed to determine if shaft brushes are lifting or open (64B).

5. May also be applied on generators with brushless excitation with a grounding brush and pilotground fault detection brush.

Function SpecificationField/Exciter Supply Voltage Rating (Terminal (3) to (2)):

• 60 to 1200 V dc, continuous

• 1500 V dc, 1 minute

Operating Temperature: –20° to +70°, Centigrade

Patent & WarrantyThe M-3921 Field Ground Coupler is covered by a five-year warranty from date of shipment.

Tests and StandardsM-3921 Field Ground Coupler complies with the following tests and standards:

Page 29: Generator Relay Protection

–28–

M-3425A Generator Protection Relay

Voltage Withstand

Isolation5 kV ac for 1 minute, all terminals to case

Impulse VoltageIEC 60255–5, 5,000 V pk, 1.2 by 50 μs, 0.5 J, 3 positive and 3 negative impulses at 5 second

intervals per minute

Electrical InterferenceElectrostatic Discharge TestEN 60255-22-2 Class 4 (8 kV) — point contact discharge

Class 4 (15 kV) — air discharge

Fast Transient Disturbance TestsIEC 61000-4-4 Class 4 (4 kV, 2.5 kHz)

Surge Withstand CapabilityANSI/IEEE 2,500 V pk-pk oscillatory applied to each independent circuit to earthC37.90.1- 2,500 V pk-pk applied between each independent circuit1989 5,000 V pk Fast Transient applied to each independent circuit to earth

5,000 V pk Fast Transient applied between each independent circuit

ANSI/IEEE 2,500 V pk-pk oscillatory applied to each independent circuit to earthC37.90.1- 2,500 V pk-pk applied between each independent circuit2002 4,000 V pk Fast Transient applied to each independent circuit to earth

4,000 V pk Fast Transient applied between each independent circuit

NOTE: The signal is applied to the digital data circuits (RS-232, RS-485, IRIG-B, Ethernet communicationport and field ground coupling port) through capacitive coupling clamp.

Radiated SusceptibilityANSI/IEEE 25-1000 Mhz @ 35 V/mC37.90.2

Atmospheric EnvironmentIEC 60068–2–1 Cold, –20° CIEC 60068–2–2 Dry Heat, +70° CIEC 60068–2–3 Damp Heat, +40° C @ 93% RH

Enclosure ProtectionNEMA 1, IEC IPC-65

Page 30: Generator Relay Protection

–29–

M-3425A Generator Protection Relay

.18 DIA [0.46] 4 HOLES

MOUNTING PATTERNWITHOUT TABS

Field GroundCoupler4.72 [11.99]

7.87 [19.99] 2.96 REF [7.52]

3.54 [9.0]

NOTE: Dimensions in brackets are in centimeters.

7.40[18.79]

9.06 [23.01]

3.54 [9.0]

.18 DIA [0.46] 4 X

%&'

045.67.

M-3921

Figure 12 M-3921 Field Ground Coupler Mounting Dimensions

Page 31: Generator Relay Protection

–30–

M-3425A Generator Protection Relay

64S 100% Stator Ground Protection by Low Frequency Signal InjectionNOTE: The Stator Ground Protection function (64S) must be selected when the M-3425A is initially

ordered.

The 100% stator ground fault protection is provided by injecting an external 20 Hz signal into the neutral of thegenerator. The protection is provided when the machine is on-line as well as off-line (provided that the 20 Hzgenerator and relay are powered on.) This scheme requires the following external components in addition toM-3425A protection system:

• 20 Hz Signal-generator (BECO Surface/Flush Mount Part No. 430-00426) (Siemens 7XT33). For220 V ac supply applications an M-0331 2:1 150 VA Control Transformer is available (BECO Part No.410-00318).

• Band-pass filter (BECO Surface/Flush Mount Part No. 430-00427) (Siemens 7XT34)• 20 Hz Measuring Current Transformer, 400/5 A CT (BECO Part No. 430-00428)

(ITI-CTW3-60-T50-401)The voltage signal generated by the 20 Hz signal-generator is injected into the secondary of the generatorneutral grounding transformer through a band-pass filter. The band-pass filter passes the 20 Hz signal andrejects out-of-band signals. The output of the 20 Hz band-pass filter is connected to the V

N input of the

M-3425A relay through a suitable voltage divider, that limits the M-3425A to OOOOO 200 V ac (the voltage generatormay be bypassed if the expected 50/60 Hz voltage during a phase-to-ground fault of the generator is OOOOO 200 V.)The 20Hz current is also connected to the I

N input of the M-3425A, through the 20Hz current transformer.

When the generator is operating normally (no ground fault) only a small amount of 20 Hz current will flow as aresult of the stator capacitance to ground. When a ground fault occurs anywhere on the generator statorwindings the 20 Hz current will increase. The 64S function will issue a trip signal after a set time delay when themeasured 20 Hz current exceeds the pickup current.

For cases where the Load Resistor (RN) is small, the Undervoltage Inhibit should not be enabled, as thevoltage will be small.

The 59N function (90 to 95%) should also be used in conjunction with 64S protection to provide backup.

RN

1B1

1A1

1B4

1A3 1A4

20 HzBand Pass

Filter

20 HzGenerator

4A1[11]

Bl

Supply VoltageDC 120 V ac

UH+ L1

UH- L2

L3

ExternalBlock

DeviceOperative

44 45

M-3425A

52 53

400A5A

L Kl k

Max. 200 V

V N

I N

NeutralGrounding

Transformer

WiringShielded

20 Hz CT400/5 A

59N

High *Voltage

LowVoltage

* For applications with a transformer secondary rating that will result in 50/60 Hz phaseground fault voltages >200 V ac, use the "High Voltage" connection for the 59N Function.

Connection terminals forModel A00/CC shown.Connection terminals forModel A00/DE shown inbrackets [ ].

4A3[12]

1A1[1]

1A2[2]

1A3[3]

2A1[6]

2A3[8]

3A2[7]

3A3[9]

3A1[5]

M-03312:1 Control

Transformer

H2

H5

220 V ac

L2

L5

Figure 13 64S Function Component Connection Diagram

Page 32: Generator Relay Protection

–31–

M-3425A Generator Protection Relay

20 Hz Signal Generator Function Specifications

Auxiliary VoltageRated auxiliary voltage U

H ac 3x (100/120 V ac), 50/60 Hz 1x (100 to 120 V ac), 50/60 Hz

Permissible variations ac 88 to 130 V ac

OR

Rated auxiliary voltage UH dc 110 to 220 V dc

Permissible Variations dc 88 to 250 V dc

Permissible consumption at 8 Ohm impendance OOOOO100 VA

NOTE: 230 VAC is permissible for commissioning only, which is limited in time.

20 Hz Output VoltageConnections (11 and 12)

Output Voltage approx. 26 V ±10 %, rectangular; 20 Hz 0.1 Hz

Power Output, permanently 100 VA over all ranges

NOTE: Output is not resistant to short-circuits.

Binary Input for BlockingConnections (6 and 8)

Switching Threshold Adjustable voltage range with jumper

– For control voltages 24 V

48 V

60 V DC 19 V: Uhigh P P P P P DC 19 V, Ulow O O O O O DC 10 V

– For control voltages 110 V

125 V

220 V

250 V DC 88 V: Uhigh

P P P P P DC 88 V, Ulow

O O O O O DC 44 V

Permissible voltage, continuous 300 V dc

Life ContactConnections (5, 7 and 9)

Switching capacity MAKE 30W/VA BREAK 20 VA

30 W resistance load25 W @ L/R OOOOO 50 ms

Switching voltage DC 24 V to DC 250 VAC 24 to AC 230 V

Permissible current 1 A permanent

Permissible Ambient TemperaturesRL describes the load resistance at the Band Pass output.

with RL <<<<<5 Ohm OOOOO550 C or OOOOO1310 F

with RL >>>>>5 Ohm OOOOO700 C or OOOOO1580 F

NOTE: The device may produce up to 20 W power losses during service. In order to prevent heat pockets,the dissipation of the losses must not be restricted. The minimum clearance above and below thedevice to other units or walls is 100 mm or 4 inches. In cubicles, the device shall be installed in thebottom area.

Page 33: Generator Relay Protection

–32–

M-3425A Generator Protection Relay

NOTE: Detailed Mounting information is contained in the M-3425A Instruction Book Chapter 5, InstallationSection 5.6.

Figure 14 20Hz Signal Generator Dimensions

Dimensions in mm

JUMPERS BETWEEN(4,5) AND (2,3)

JUMPERS BETWEEN(2,3) AND (4,5)

1 2 3 4 5 6

123456

4.94[12.55]

2.75[6.99]

Four Slots0.22 X 0.75[0.56 X 1.91]

3.38[8.6]

4.0[10.16]

3.81[9.68]

Figure 15 M-0331 2:1 Control Transformer

Page 34: Generator Relay Protection

–33–

M-3425A Generator Protection Relay

Band-pass Filter Specifications

Load Capacity of the 20 Hz Band-pass FilterConnections (1B1-1B4)

Permissible voltage, continuous 55 V ac

Permissible voltage for OOOOO30 s 550 V ac

Frequency of superimposed ac voltage PPPPP 45 Hz

Overload capability, continuous 3.25 A ac

Test Voltage 2.8 kV dc

Load Capability of the Voltage Divider CircuitConnections (1A1-1A4):

Permissible voltage, continuous 55 V ac

Permissible voltage for OOOOO30 s 50 V ac

Test Voltage 2.8 kV dc

Permissible Ambient Temperatureswith R

L <<<<<5 Ω burden OOOOO400 C or OOOOO 1040 F

with RL >>>>>5 Ω burden OOOOO550 C or OOOOO 1310 F

NOTE: The device may produce up to 75 W power losses during service. In order to prevent heat pockets,the dissipation of the losses must not be restricted. The minimum clearance above and below thedevice to other units or walls is 100 mm or 4 inches. In cubicles, the device shall be installed in thebottom area.

Page 35: Generator Relay Protection

–34–

M-3425A Generator Protection Relay

NOTE: Detailed Mounting information is contained in the M-3425A Instruction Book Chapter 5, InstallationSection 5.

Figure 16 Band-pass Filter Dimensions

Page 36: Generator Relay Protection

–35–

M-3425A Generator Protection Relay

Figure 17 20 Hz Measuring Current Transformer 400-5 A CT

Page 37: Generator Relay Protection

800-3425A-SP-09MC2 02/10© 2001 Beckwith Electric Co.Printed in U.S.A. (#01-67) (04.25.03)

Page 38: Generator Relay Protection

!!"!#!! $!!% &'%($!%)#!) '!" &%(*)+! !++!!! + $!'!%(

DANGER! HIGH VOLTAGE

– This sign warns that the area is connected to a dangerous high voltage, and youmust never touch it.

PERSONNEL SAFETY PRECAUTIONSThe following general rules and other specific warnings throughout the manual must be followed during application,test or repair of this equipment. Failure to do so will violate standards for safety in the design, manufacture, and intendeduse of the product. Qualified personnel should be the only ones who operate and maintain this equipment. BeckwithElectric Co., Inc. assumes no liability for the customer’s failure to comply with these requirements.

– This sign means that you should refer to the corresponding section of the operation

manual for important information before proceeding.

Always Ground the Equipment

To avoid possible shock hazard, the chassis must be connected to an electrical ground. When servicingequipment in a test area, the Protective Earth Terminal must be attached to a separate ground securelyby use of a tool, since it is not grounded by external connectors.

Do NOT operate in an explosive environmentDo not operate this equipment in the presence of flammable or explosive gases or fumes. To do so wouldrisk a possible fire or explosion.

Keep away from live circuitsOperating personnel must not remove the cover or expose the printed circuit board while power is ap-plied. In no case may components be replaced with power applied. In some instances, dangerous volt-ages may exist even when power is disconnected. To avoid electrical shock, always disconnect power anddischarge circuits before working on the unit.

Exercise care during installation, operation, & maintenance proceduresThe equipment described in this manual contains voltages high enough to cause serious injury or death.Only qualified personnel should install, operate, test, and maintain this equipment. Be sure that all per-sonnel safety procedures are carefully followed. Exercise due care when operating or servicing alone.

Do not modify equipmentDo not perform any unauthorized modifications on this instrument. Return of the unit to a BeckwithElectric repair facility is preferred. If authorized modifications are to be attempted, be sure to followreplacement procedures carefully to assure that safety features are maintained.

Page 39: Generator Relay Protection

PRODUCT CAUTIONSBefore attempting any test, calibration, or maintenance procedure, personnel must be completely familiarwith the particular circuitry of this unit, and have an adequate understanding of field effect devices. If acomponent is found to be defective, always follow replacement procedures carefully to that assure safetyfeatures are maintained. Always replace components with those of equal or better quality as shown in theParts List of the Instruction Book.

Avoid static chargeThis unit contains MOS circuitry, which can be damaged by improper test or rework procedures. Careshould be taken to avoid static charge on work surfaces and service personnel.

Use caution when measuring resistancesAny attempt to measure resistances between points on the printed circuit board, unless otherwise notedin the Instruction Book, is likely to cause damage to the unit.

Page 40: Generator Relay Protection

NOTE

The following features, described in this Instruction Book, are only available for firmware versionD-0150-V01.00.34 and later:

59N 20 Hz Injection Mode (Page 2-58)

IEEE curves for 51N, 51V, and 67N functions (Appendix D)

Sequence of Events Recorder (Page 4-18)

Dropout/Reset Time Delay added to IPSlogic (Page 2-91)

Response Time Delay for Communications (Page 4-3)

25 Function (does not produce a target) (Page 2-21)

Page 41: Generator Relay Protection

This Page Left Intentionally Blank

Page 42: Generator Relay Protection

i

Table of Contents

Chapter 1 Introduction

1.1 Instruction Book Contents ...............................................................................1–1

1.2 M-3425A Generator Protection Relay .............................................................1–2

1.3 Accessories .....................................................................................................1–4

Chapter 2 Application

2.1 Configuration ..................................................................................................... 2–2Profiles .............................................................................................................. 2–3Functions .......................................................................................................... 2–3Special Considerations ...................................................................................... 2–3Relay System Setup ......................................................................................... 2–3

2.2 System Diagrams.............................................................................................. 2–8

2.3 Setpoints and Time Settings ........................................................................... 2–1421 Phase Distance .......................................................................................... 2–1424 Overexcitation Volts/Hz .............................................................................. 2–18M-3425A Firmware Versions D-0114VXX.XX.XX and Earlier ........................... 2–19M-3425A Firmware Version D-0150V 01.00.34 ................................................. 2–19M-3425A Firmware Version D-0150V 01.04.00 ................................................. 2–1925 Sync Check ................................................................................................ 2–21Phase Angle Check ......................................................................................... 2–21Delta Voltage and Delta Frequency Check ....................................................... 2–2127 Phase Undervoltage ................................................................................... 2–2527TN #2 Screens are identical to 27TN #1. ..................................................... 2–2832 Directional Power ........................................................................................ 2–29Protection from Generator Motoring ................................................................. 2–29Protection from Generator Overload ................................................................ 2–29Protection from Excessive Reactive Power ..................................................... 2–2940 Loss of Field............................................................................................... 2–3346 Negative Sequence Overcurrent ................................................................. 2–3749 Stator Overload Protection ......................................................................... 2–3950/50N Instantaneous Overcurrent, Phase and Neutral Circuits ...................... 2–4250BF Generator Breaker Failure/HV Breaker Flashover ................................... 2–4450DT Definite Time Overcurrent (for split-phase differential) ............................ 2–4650/27 Inadvertent Energizing ........................................................................... 2–4751N Inverse Time Neutral Overcurrent ............................................................. 2–4951V Inverse Time Phase Overcurrent with Voltage Control/Restraint ............... 2–5059 Phase Overvoltage ..................................................................................... 2–5259D Third Harmonic Voltage Differential (Ratio) ................................................ 2–5359N Overvoltage, Neutral Circuit or Zero Sequence ......................................... 2–5559X Multipurpose Overvoltage (Turn-to-Turn Stator Fault Protectionor Bus Ground Protection) ............................................................................... 2–5660FL VT Fuse Loss ......................................................................................... 2–58

TABLE OF CONTENTSM-3425A Generator Protection

Instruction Book

Page 43: Generator Relay Protection

ii

M-3425A Instruction Book

Chapter 2 Application (Cont.'d)

Internal Fuse Loss Detection Logic ................................................................. 2–58External Fuse-Loss Function ........................................................................... 2–5860FL VT Fuse Loss Alarm Function ................................................................ 2–5864B/F Field Ground Protection ........................................................................ 2–6164F Field Ground Detection ............................................................................. 2–61Factors Affecting 64F Performance ................................................................. 2–6164B Brush Lift-Off Detection ........................................................................... 2–6364S 100% Stator Ground Protection by low frequency injection ...................... 2–6567N Residual Directional Overcurrent .............................................................. 2–6878 Out-of-Step ................................................................................................. 2–7181 Frequency................................................................................................... 2–7481A Frequency Accumulator ........................................................................... 2–7681R Rate of Change of Frequency ................................................................... 2–7887 Phase Differential ....................................................................................... 2–7987GD Ground (Zero Sequence) Differential ...................................................... 2–81Breaker Monitoring .......................................................................................... 2–82Trip Circuit Monitoring ...................................................................................... 2–83IPSlogic™ ....................................................................................................... 2–84Settings and Logic Applicable when IPSlogic™ Function(s)programmed using IPScom® .......................................................................... 2–86DO/RST (Dropout/Reset) Timer Feature .......................................................... 2–88Reset Delay Timer ........................................................................................... 2–88Dropout Delay Timer ........................................................................................ 2–88

Chapter 3 Operation

3.1 Front Panel Controls ......................................................................................... 3–1Alphanumeric Display ....................................................................................... 3–1Screen Blanking ................................................................................................ 3–1Arrow Pushbuttons ............................................................................................ 3–1Exit Pushbutton ................................................................................................ 3–1Enter Pushbutton .............................................................................................. 3–1Target & Status Indicators and Controls ........................................................... 3–1Power Supply #1 (#2) LED ................................................................................ 3–2Relay OK LED .................................................................................................. 3–2Oscillograph Recorded LED .............................................................................. 3–2Breaker Closed LED.......................................................................................... 3–2Target Indicators and Target Reset ................................................................... 3–2Time Sync LED................................................................................................. 3–2Diagnostic LED ................................................................................................. 3–2Accessing Screens ........................................................................................... 3–2Default Message Screens ...............................................................................3–2

3.2 Initial Setup Procedure/Settings .....................................................................3–5

3.3 Setup Unit Data................................................................................................. 3–5Setup Unit Data Entry ....................................................................................... 3–5Setup Unit Features That Do Not Require Data Entry ....................................... 3–6

3.4 Setup System Data ........................................................................................... 3–6Configure Relay Data ........................................................................................ 3–7Setpoints and Time Settings ............................................................................. 3–7Oscillograph Recorder Data .............................................................................. 3–8Communications Settings ................................................................................. 3–8

Page 44: Generator Relay Protection

iii

Table of Contents

Chapter 3 Operation (Cont.'d)

3.5 Status/Metering................................................................................................. 3–9

3.6 Target History ................................................................................................. 3–10

Chapter 4 Remote Operation

4.1 Remote Operation ............................................................................................4–1Serial Ports (RS-232) .......................................................................................4–1Serial Port (RS-485) .......................................................................................... 4–1Optional Ethernet Port ....................................................................................... 4–1Direct Connection .............................................................................................. 4–2Setting up the M-3425A Generator ProtectionRelay for Communication .................................................................................. 4–3Serial Communication Settings ......................................................................... 4–3Ethernet Communication Settings ..................................................................... 4–3DHCP Protocol .................................................................................................. 4–3Ethernet Protocols ............................................................................................ 4–3Ethernet Port Setup .......................................................................................... 4–4HMI Ethernet Port Setup ................................................................................... 4–4Manual Configuration of Ethernet Board ............................................................ 4–5IPSutil™ Ethernet Port Setup with DHCP ......................................................... 4–7IPSutil Ethernet Port Setup without DHCP........................................................ 4–7Installing the Modems .....................................................................................4–7

4.2 Installation and Setup (IPScom®) ...................................................................... 4–8

4.3 Operation ..........................................................................................................4–9Activating Communications .............................................................................4–9Overview ..........................................................................................................4–9File Menu .........................................................................................................4–9Comm Menu ................................................................................................... 4–10Relay Menu .................................................................................................... 4–11Sequence of Events ...................................................................................... 4–21Oscillograph ................................................................................................... 4–23Profile ............................................................................................................. 4–25Window Menu/Help Menu .............................................................................. 4–26

4.4 Checkout Status/Metering ............................................................................. 4–27

4.5 Cautions ......................................................................................................... 4–35

4.6 Keyboard Shortcuts ....................................................................................... 4–36

4.7 IPSutil Communications Software ................................................................... 4–37M-3890 IPSutil ............................................................................................... 4–37Installation and Setup ..................................................................................... 4–37Installation ...................................................................................................... 4–37System Setup ................................................................................................. 4–37Overview ......................................................................................................... 4–37Comm Menu ................................................................................................... 4–38Relay Comm Command .................................................................................. 4–38Ethernet Command ......................................................................................... 4–38Clock Command ............................................................................................. 4–38Security Menu ................................................................................................. 4–38Miscellaneous Menu ....................................................................................... 4–39Help Menu....................................................................................................... 4–39

Page 45: Generator Relay Protection

iv

M-3425A Instruction Book

Chapter 5 Installation

5.1 General Information .........................................................................................5–1

5.2 Mechanical/Physical Dimensions ....................................................................5–2

5.3 External Connections .......................................................................................5–8

5.4 Commissioning Checkout .............................................................................. 5–14

5.5 Circuit Board Switches and Jumpers ........................................................... 5–19

5.6 Low Frequency Signal Injection Equipment .................................................. 5–23

Chapter 6 Testing

6 Testing .............................................................................................................. 6–1

6.1 Equipment/Test Setup ....................................................................................... 6–2Equipment Required .......................................................................................... 6–2Setup ................................................................................................................ 6–2

6.2 Functional Test Procedures ............................................................................... 6–6Power On Self Tests .......................................................................................... 6–721 Phase Distance (#1, #2 or #3) ...................................................................... 6–824 Volts/Hz Definite Time (#1 or #2) ................................................................... 6–924 Volts/Hz Inverse Time ................................................................................. 6–1025D Dead Check ............................................................................................. 6–1225S Sync Check ............................................................................................. 6–1427 Phase Undervoltage, 3 Phase (#1, #2, #3) .................................................. 6–1627TN Third-Harmonic Undervoltage, Neutral (#1 or #2) .................................... 6–1732 Directional Power, 3 Phase (#1, #2, #3) ...................................................... 6–2140 Loss of Field (#1 or #2, VC #1 or #2) .......................................................... 6–2446 Negative Sequence Overcurrent Definite Time ............................................ 6–2646 Negative Sequence Overcurrent Inverse Time ............................................ 6–2749 Stator Overload Protection (#1, #2) ............................................................ 6–2850 Instantaneous Phase Overcurrent (#1, #2) .................................................. 6–3050BF/50BF-N Breaker Failure .......................................................................... 6–3150/27 Inadvertent Energizing ........................................................................... 6–3350DT Definite Time Overcurrent (for split-phase differential), #1 or #2 ............. 6–3450N Instantaneous Neutral Overcurrent ........................................................... 6–3551N Inverse Time Neutral Overcurrent ............................................................. 6–3651V Inverse Time Phase Overcurrent with Voltage Control/Restraint ............... 6–3759 Phase Overvoltage, 3-Phase (#1, #2, #3) ................................................... 6–3959D Third-Harmonic Voltage Differential ........................................................... 6–4059N Overvoltage, Neutral Circuit or Zero Sequence (#1, #2, #3) ...................... 6–4159X Multi-purpose Overvoltage (#1 or #2) ........................................................ 6–4260FL VT Fuse Loss Detection ......................................................................... 6–4364F Field Ground Protection (#1 or #2) ............................................................ 6–4464B Brush Lift-Off Detection ........................................................................... 6–4664S 100% Stator Ground Protection by low frequency injection ...................... 6–4767N Residual Directional Overcurrent, Definite Time........................................ 6–5067N Residual Directional Overcurrent, Inverse Time ........................................ 6–5278 Out of Step ................................................................................................. 6–5481 Frequency (#1, #2, #3, #4) .......................................................................... 6–5681A Frequency Accumulator (Band #1, #2, #3, #4, #5, #6) .............................. 6–57

Page 46: Generator Relay Protection

v

Table of Contents

Chapter 6 Testing (Cont.'d)

81R Rate of Change of Frequency (#1, #2) ...................................................... 6–5887 Phase Differential (#1 or #2) ....................................................................... 6–6087GD Ground Differential ................................................................................. 6–62BM Breaker Monitoring .................................................................................... 6–64Trip Circuit Monitoring ...................................................................................... 6–66IPSlogicTM (#1, #2, #3, #4, #5, #6) ................................................................. 6–67

6.3 Diagnostic Test Procedures ............................................................................. 6–68Overview ......................................................................................................... 6–68Entering Relay Diagnostic Mode ...................................................................... 6–68Output Relay Test (Output Relays 1–23 and 25) .............................................. 6–69Output Relay Test (Power Supply Relay 24) ..................................................... 6–70Input Test (Control/Status) ............................................................................... 6–70Status LED Test .............................................................................................. 6–71Target LED Test ............................................................................................... 6–72Button Test ...................................................................................................... 6–72Display Test ..................................................................................................... 6–73COM1/COM2 Loopback Test ........................................................................... 6–73COM3 Test (2-Wire) ......................................................................................... 6–74Clock ON/OFF ................................................................................................ 6–75Relay OK LED Flash/Illuminated ..................................................................... 6–76Auto Calibration ............................................................................................... 6–76Factory Use Only ............................................................................................ 6–76

6.4 Auto Calibration ............................................................................................... 6–77Phase and Neutral Fundamental Calibration .................................................... 6–77Third Harmonic Calibration .............................................................................. 6–78

64S 100% Stator Ground by Low Frequency Injection Calibration .................... 6–78Field Ground Calibration .................................................................................. 6–79

Appendices

Appendix A: Configuration Record Forms ..................................................... A–1

Appendix B: Communications ........................................................................ B–1

Appendix C: Self-Test Error Codes ............................................................... C–1

Appendix D: Inverse Time Curves ................................................................. D–1

Appendix E: Declaration of Conformity ......................................................... E–1

Page 47: Generator Relay Protection

vi

M-3425A Instruction Book

Figures Page

Chapter 11-1 M-3925A Target Module ..........................................................................1–41-2 M-3931 Human-Machine Interface (HMI) Module ................................ 1–4

Chapter 22-1 Setup System Dialog Box ......................................................................... 2–62-2 Selection Screen for Expanded Input ........................................................ 2–72-3 Pulse Relay Expanded Output Screen ...................................................... 2–72-4 Latch Relay Expanded Output Screen ...................................................... 2–72-5 One-Line Functional Diagram .................................................................... 2–82-6 Alternative One-Line Functional Diagram

(configured for split-phase differential) ....................................................... 2–92-7 Three-Line Connection Diagram .............................................................. 2–102-8 Function 25 Sync Check Three-Line Connection Diagram ....................... 2–112-9 Function 59X Turn to Turn Fault Protection Three-Line Connection Diagram .. 2–122-10 Function 67N, 59D, 59X (Bus Ground) Three-Line Connection Diagram...... 2–132-11 Selection Screen for Expanded I/O Initiate ............................................ 2–142-12 Phase Distance (21) Coverage .............................................................. 2–162-13 Phase Distance (21) Function Applied for System Backup.................... 2–162-14 Phase Distance (21) Setpoint Ranges ................................................... 2–172-15 Example of Capability and Protection Curves (24) ................................. 2–192-16 Volts-Per-Hertz (24) Setpoint Ranges .................................................... 2–202-17 Sync Check Logic Diagrams ................................................................. 2–232-18 Sync Check (25) Setpoint Ranges ........................................................ 2–242-19 Phase Undervoltage (27) Setpoint Ranges ............................................ 2–252-20 Third Harmonic Undervoltage (27TN) Protection Characteristics ........... 2–262-21 27TN Blocking Regions ......................................................................... 2–272-22 Third Harmonic Undervoltage, Neutral Circuit (27TN) Setpoint Ranges .. 2–272-23 Tripping on Reverse Power Flow (Over Power with Negative Pickup) ..... 2–292-24 Tripping on Low Forward Power (Under Power with Positive Pickup) ...... 2–312-25 Tripping on Overpower (Over Power with Positive Pickup) ..................... 2–312-26 Tripping on Over Reactive Power with Element #3 (Over Power,

Positive Pickup and Directional Power Sensing Set to Reactive) .......... 2–322-27 Directional Power, 3-Phase (32) Setpoint Ranges .................................. 2–322-28 Loss of Field (40)—Protective Approach 1 ............................................ 2–352-29 Loss of Field (40)—Protective Approach 2 ............................................ 2–352-30 Loss-of-Field (40) Setpoint Ranges ....................................................... 2–362-31 Negative Sequence Overcurrent Inverse Time Curves .......................... 2–382-32 Negative Sequence Overcurrent (46) Setpoint Ranges .......................... 2–382-33 Time Constant, Function 49 .................................................................. 2–392-34 49 Function Overload Curves ................................................................ 2–402-35 Stator Thermal Protection (49) Setpoint Ranges .................................... 2–412-36 Instantaneous Overcurrent (50) Setpoint Ranges .................................. 2–432-37 Instantaneous Neutral Overcurrent (50N) Setpoint Ranges .................... 2–432-38 Breaker Failure Logic Diagram ............................................................... 2–442-39 Breaker Failure (50BF) Setpoint Ranges ................................................ 2–452-40 Definite Time Overcurrent (50DT) Setpoint Ranges ............................... 2–462-41 Inadvertent Energizing Function Logic Diagram .................................... 2–48

Page 48: Generator Relay Protection

vii

Table of Contents

Figures (Cont.'d) Page

Chapter 2 (Cont.'d)

2-42 Inadvertent Energizing (50/27) Setpoint Ranges .................................... 2–482-43 Inverse Time Neutral Overcurrent (51N) Setpoint Ranges ...................... 2–492-44 Voltage Restraint (51VR) Characteristic ................................................ 2–512-45 Inverse Time Overcurrent with Voltage .................................................. 2–512-46 Phase Overvoltage (59) Setpoint Ranges .............................................. 2–522-47 Third Harmonic Voltage Differential (Ratio) Scheme .............................. 2–542-48 Third Harmonic Voltage Differential (59D) Setpoint Ranges.................... 2–542-49 Overvoltage, Neutral Circuit or Zero Sequence (59N) Setpoint Ranges.. 2–552-50 Turn-to-Turn Stator Winding Fault Protection .......................................... 2–572-51 (59X) Multi-purpose Overvoltage Setpoint Ranges ................................ 2–572-52 Fuse Loss (60FL) Function Logic .......................................................... 2–592-53 Fuse Loss (60FL) Setpoint Ranges ....................................................... 2–602-54 M-3921 Field Ground Coupler ................................................................ 2–622-55 Field Ground Protection (64B/F) Setpoint Ranges ................................. 2–632-56 Figure 2-56 64S Function Component Connection Diagram ................... 2–662-57 Figure 2-57 64S Function Time Delay Pickup Current Correlation .......... 2–672-58 Figure 2-58 100% Stator Ground Protection (64S) Setpoint Ranges ...... 2–672-59 Residual Directional Overcurrent (67N) Trip Characteristics ................... 2–682-60 Residual Directional Overcurrent (67N) Setpoint Ranges ....................... 2–702-61 Out-of-Step Relay Characteristics ......................................................... 2–722-62 Out-of-Step Protection Settings ............................................................ 2–722-63 Out-of-Step (78) Setpoint Ranges.......................................................... 2–732-64 Example of Frequency (81) Trip Characteristics ..................................... 2–752-65 Frequency (81) Setpoint Ranges ........................................................... 2–752-66 Frequency Accumulator (81A) Example Bands ..................................... 2–772-67 Frequency Accumulator (81A) Setpoint Ranges .................................... 2–772-68 Rate of Change of Frequency (81R) Setpoint Ranges ............................ 2–782-69 Differential Relay (87) Operating Characteristics ................................... 2–802-70 Phase Differential (87) Setpoint Ranges ................................................ 2–802-71 Ground Differential (87GD) Setpoint Ranges ......................................... 2–812-72 Breaker Monitor (BM) Setpoint Ranges ................................................. 2–822-73 Trip Circuit Monitoring Input ................................................................... 2–832-74 Trip Circuit Monitor (TC) Setpoint Ranges .............................................. 2–832-75 IPSlogic™ Function Setup .................................................................... 2–852-76 IPSlogic Function Programing ............................................................... 2–862-77 Selection Screen for Initiating Function Timeout .................................... 2–872-78 Selection Screen for Initiating Function Pickup ..................................... 2–872-79 Dropout Delay Timer Logic Diagram....................................................... 2–882-80 Reset Delay Timer Logic Diagram.......................................................... 2–88

Chapter 33-1 M-3425A Front Panel ..............................................................................3–33-2 Screen Message Menu Flow ..................................................................3–33-3 Main Menu Flow ......................................................................................3–4

Page 49: Generator Relay Protection

viii

M-3425A Instruction Book

Figures (Cont.'d) Page

Chapter 44-1 Multiple System Addressing Using

Communications Line Splitter .................................................................4–24-2 IPScom® Menu Selections .....................................................................4–64-3 IPScom Program Icon ............................................................................4–84-4 System Type Dialog Box ...................................................................... 4–104-5 Communication Dialog Box ................................................................... 4–104-6 Setup System Dialog Box .................................................................... 4–124-7 Expanded Input Active State ............................................................... 4–134-8 Pulse Relay Expanded Output Screen ................................................ 4–134-9 Latch Relay Expanded Output Screen ................................................. 4–134-10 Relay Setpoints Dialog Box ................................................................ 4–144-11 Typical Setpoint Dialog Box ............................................................... 4–154-12 Expanded I/O Initiate .......................................................................... 4–154-13 All Setpoints Table Dialog Box (Partial) ............................................ 4–164-14 Configure Dialog Box (Partial) ............................................................ 4–174-15 Configure Dialog Box Partial

(shown with Expanded Input/Outputs) ............................................... 4–184-16 Unit Date/Time Dialog Box ................................................................. 4–194-17 Target Dialog Box................................................................................ 4–204-18 Trigger Events Screen with Expanded I/O ........................................ 4–224-19 Event Log Viewer ................................................................................ 4–224-20 Event Download Screen ...................................................................... 4–234-21 Setup Oscillograph Recorder .............................................................. 4–244-22 Retrieve Oscillograph Record Dialog .................................................. 4–244-23 Profile Switching Method Dialog ......................................................... 4–254-24 Select Active Profile ........................................................................... 4–254-25 Copy Active Profile ............................................................................. 4–254-26 About IPScom® Dialog Box ................................................................ 4–264-27 Primary Status Dialog Box ................................................................. 4–274-28 Secondary Status Dialog Box ............................................................ 4–284-29 Accumulator Status Screen ................................................................ 4–284-30 Phase Distance Dialog Box ................................................................ 4–294-31 Loss of Field Dialog Box .................................................................... 4–304-32 Out of Step Dialog Box ...................................................................... 4–314-33 Phasor Dialog Box .............................................................................. 4–324-34 Sync Scope Screen ............................................................................ 4–334-35 Function Status Screen ...................................................................... 4–344-36 IPSutil™ Main Menu Flow .................................................................. 4–374-37 Warning Message ................................................................................ 4–374-38 IPSutility Reset Relay Message ........................................................ 4–384-39 Monitor Status Screen ........................................................................ 4–394-40 Calibration Dialog Box ......................................................................... 4–394-41 Communication Dialog Box ................................................................. 4–394-42 Relay Comm Port Settings ................................................................. 4–404-43 Ethernet Settings ................................................................................. 4–404-44 Set Unit Date/Time Dialog Box .......................................................... 4–404-45 Change Communication Access Code Dialog Box ............................ 4–404-46 Change User Access Code Dialog Box ............................................. 4–414-47 Setup Dialog Box .................................................................................. 4–41

Page 50: Generator Relay Protection

ix

Table of Contents

Figures (Cont.'d) Page

Chapter 55-1 M-3425A Horizontal Chassis Mounting Dimensions Without Expanded I/O (H1) .... 5–25-2 M-3425A Vertical Chassis Mounting Dimensions Without Expanded I/O (H2) ..... 5–35-3 M-3425A Mounting Dimensions Horizontal and Vertical Chassis With Expanded I/O ..... 5–45-4 M-3425A Panel Mount Cutout Dimensions ................................................ 5–55-5 Mounting Dimensions for GE L-2 Cabinet (H3 and H4) .............................. 5–65-6 (H5) Mounting Dimensions ........................................................................ 5–75-7 Optional Dual Power Supply ...................................................................... 5–85-8 Expanded I/O Power Supply ..................................................................... 5–85-9 External Connections ................................................................................ 5–95-10 Three-Line Connection Diagram ............................................................ 5–105-11 Function 25 Sync Check Three-Line Connection Diagram ..................... 5–115-12 Function 59X Turn to Turn Fault Protection Three-Line Connection Diagram ... 5–125-13 Function 67N, 59D, 59X (Bus Ground) Three-Line Connection Diagram ... 5–135-14 M-3425A Circuit Board .......................................................................... 5–215-15 M-3425A Circuit Board (Expanded I/O).................................................. 5–225-16 Low Frequency Signal Injection Equipment Typical Connections ........... 5–235-17 20 Hz Frequency Generator Housing Panel Surface Mount .................... 5–245-18 20 Hz Frequency Generator Housing Panel Flush Mount ....................... 5–255-19 20 Hz Band Pass Filter Housing Panel Surface Mount .......................... 5–265-20 20 Hz Band Pass Filter Housing Panel Flush Mount .............................. 5–275-21 20 Hz Measuring Current Transformer 400-5 A CT ................................. 5–285-22 M-0331 2:1 Control Transformer ........................................................... 5–28

Chapter 66-1 Voltage Inputs: Configuration V1................................................................ 6–36-2 Voltage Inputs: Configuration V2................................................................ 6–36-3 Current Inputs: Configuration C1 .............................................................. 6–46-4 Current Inputs: Configuration C2................................................................ 6–46-5 Current Configuration C3 ........................................................................... 6–56-6 64S Test Configuration .............................................................................. 6–56-7 Field Ground Coupler .............................................................................. 6–456-8 Status LED Panel .................................................................................... 6–716-9 M-3925A Target Module Panel ................................................................. 6–726-10 M-3931 Human-Machine Interface Module ............................................ 6–726-11 COM1/COM2 Loopback Plug ................................................................ 6–736-12 RS-485 2-Wire Testing ........................................................................... 6–756-13 Current Input Configuration .................................................................... 6–806-14 Voltage Input Configuration ................................................................... 6–806-15 Voltage Input Configuration ................................................................... 6–806-16 Voltage Input Configuration ................................................................... 6–81

Appendix AA-1 Human-Machine Interface (HMI) Module .............................................. A–6A-2 Communication Data & Unit Setup Record Form ................................ A–7A-3 Functional Configuration Record Form ............................................... A–10A-4 Setpoint & Timing Record Form ......................................................... A–28

Page 51: Generator Relay Protection

x

M-3425A Instruction Book

Figures (Cont.'d) Page

Appendix BB-1 Null Modem Cable: M-0423 ................................................................... B–2B-2 RS-232 Fiber Optic Network ................................................................. B–3B-3 RS-485 Network ...................................................................................... B–4B-4 COM2 Pinout for Demodulated TTL Level Signal ................................ B–4

Appendix DD-1 Volts/Hz (24) Inverse Time Curve Family #1 (Inverse Square) .......... D–2D-2 Volts/Hz (24) Inverse Time Family Curve #2 ...................................... D–3D-3 Volts/Hz (24IT) Inverse Time Curve Family #3 ................................... D–4D-4 Volts/Hz (24IT) Inverse Time Curve Family #4 ................................... D–5D-5 BECO Definite Time Overcurrent Curve ............................................... D–8D-6 BECO Inverse Time Overcurrent Curve ............................................... D–9D-7 BECO Very Inverse Time Overcurrent Curve .................................... D–10D-8 BECO Extremely Inverse Time Overcurrent Curve ........................... D–11D-9 IEC Curve #1 – Inverse ..................................................................... D–12D-10 IEC Curve #2 – Very Inverse .......................................................... D–13D-11 IEC Curve #3 – Extremely Inverse .................................................. D–14D-12 IEC Curve #4 – Long Time Inverse .................................................... D–15D-13 IEEE Inverse Time Overcurrent Curves .............................................. D–16D-14 IEEE Very Inverse Time Overcurrent Curves ...................................... D–17D-15 IEEE Extremely Inverse Time Overcurrent Curves ............................. D–18

Tables Page

Chapter 11-1 M-3425A Device Functions .....................................................................1–3

Chapter 22-1 Input Activated Profile ............................................................................... 2–32-2 Impedance Calculation ............................................................................ 2–172-3 Voltage Control Time Settings ................................................................. 2–342-4 Delta/Wye Transformer Voltage-Current Pairs ........................................... 2–512-5 Typical Frequency Settings ..................................................................... 2–632-6 Typical Brush Lift-Off Pickup Setting ....................................................... 2–642-7 Low Frequency Signal Injection Equipment Part Number Cross Reference..... 2–66

Chapter 33-1 Recorder Partitions ................................................................................... 3–8

Page 52: Generator Relay Protection

xi

Table of Contents

Tables (Cont.'d) Page

Chapter 44-1 Dead-Sync Time ....................................................................................... 4–34-2 Protective System Firmware Association ............................................... 4–104-3 Microsoft Windows Keyboard Shortcuts ................................................. 4–36

Chapter 55-1 Jumpers .................................................................................................. 5–195-2 Dip Switch SW-1 ..................................................................................... 5–205-3 Trip Circuit Monitor Input Voltage Select Jumper Configuration ................ 5–20

Chapter 66-1 Output Contacts ..................................................................................... 6–696-2 Input Contacts ........................................................................................ 6–70

Appendix AA-1 Relay Configuration Table ....................................................................... A–2

Appendix BB-1 Communication Port Signals ................................................................... B–2

Appendix CC-1 Self-Test Error Codes.............................................................................. C–1C-2 IPScom® Error Messages ....................................................................... C–2

Appendix D

D-1A M-3425A Inverse Time Overcurrent Relay Characteristic Curves ......... D–6

Appendix E

E-1 Declaration of Conformity ........................................................................ E–2

Page 53: Generator Relay Protection

xii

M-3425A Instruction Book

800-3425A-IB-07MC2 02/10©1998 Beckwith Electric Co.Printed in U.S.A. (9.21.01)

Page 54: Generator Relay Protection

Introduction – 1

1–1

1 Introduction

1.1 Instruction Book Contents ......................................................... 1–1

1.2 M-3425A Generator Protection Relay ........................................ 1–2

1.3 Accessories ................................................................................ 1–4

1.1 Instruction Book Contents

This instruction book includes six chapters and fiveAppendices.

Chapter 1: IntroductionChapter One summarizes relay capabilities,introduces the instruction book contents, anddescribes accessories.

Chapter 2: ApplicationChapter Two is designed for the person or groupresponsible for the application of the M-3425AGenerator Protection Relay. It includes functionaland connection diagrams for a typical application ofthe relay; and describes the configuration processfor the unit (choosing active functions), output contactassignment and input blocking designation. It alsoillustrates the definition of system quantities andequipment characteristics required by the protectiverelay, and describes the individual function settings.

Chapter 3: OperationChapter Three is designed for the person(s)responsible for the operation, direct setting, andconfiguration of the relay. Chapter Three providesinformation regarding the operation and interpretationof the unit's front panel controls and indicators,including operation of the optional M-3931, HumanMachine Interface (HMI) and M-3925A TargetModules. It further describes the procedures forentering all required data to the relay. Included in thischapter is a description of the process necessary forreview of setpoints and timing, monitoring functionstatus and metering quantities, viewing the targethistory, and setup of the oscillograph recorder.

Chapter 4: Remote OperationChapter 4 is designed for the person or groupresponsible for the remote operation and setting ofthe relay using the M-3820D IPScom®

Communications Software or other means.

Chapter 5: InstallationThe person or group responsible for the installationof the relay will find herein all mechanical informationrequired for physical installation, equipment ratings,and all external connections in this chapter. Forreference, the Three-Line Connection Diagrams arerepeated from Chapter 2, Application. Further, acommissioning checkout procedure is outlined usingthe HMI option to check the external CT and VTconnections. Additional tests which may be desirableat the time of installation are described in Chapter6, Testing.

Chapter 6: TestingThis chapter provides step-by-step test proceduresfor each function, as well as diagnostic mode andautocalibration procedures for HMI-equipped units.

Appendix A: Configuration Record FormsThis Appendix supplies a set of forms to record anddocument the settings required for the properoperation of the relay.

Appendix B: CommunicationsThis Appendix describes port signals, protocols,and various topologies, and equipment required forremote communication.

Page 55: Generator Relay Protection

M-3425A Instruction Book

1–2

Appendix C: Self-Test Error CodesThis Appendix lists all the error codes and theirdefinitions.

Appendix D: Inverse Time CurvesThis Appendix contains a graph of the four familiesof Inverse Time Curves for V/Hz applications, theInverse Time Overcurrent Curves, and the IECcurves.

Appendix E: Layup and StorageThis Appendix includes the recommended storageparameters, periodic surveillance activities andlayup configuration for the M-3425A GeneratorProtection Relay.

Appendix F: IndexThis Appendix includes the index for the M-3425AInstruction Book.

Appendix G: Declaration of ConformityThis Appendix contains the Beckwith Electric Co.’sDeclaration of Conformity required by ISO/IEC17050–1:2004.

1.2 M-3425A GeneratorProtection Relay

The M-3425A Generator Protection Relay is amicroprocessor-based unit that uses digital signalprocessing technology to provide up to thirty-fourprotective relaying functions for generator protection.The relay can protect a generator from internal windingfaults, system faults, and other abnormal conditions.

The available internal functions of the relay arelisted in Table 1-1. The nomenclature follows thestandards of ANSI/IEEE Std. C37.2, StandardElectric Power Systems Device Function Numbers.

The control/status inputs can be programmed toblock any relay function and/or to trigger theoscillograph recorder. Any of the functions or thecontrol/status inputs can be individually programmedto activate any one or more of the programmableoutputs, each with a contact.

With the optional M-3931 HMI Module, all functionscan be set or examined using a local, menu-driven,2 line by 24 character alphanumeric display. OUT9–23 and IN 7–14 for units purchased with expandedI/O can only be set utilizing M-3820D IPScom®

Communications Software. The module allows localmetering of various quantities, including phase,neutral, and sequence voltages and currents, realand reactive power, power factor, and positivesequence impedance measurements.

The relay stores time-tagged target information forthe thirty-two most recent trips. For units equippedwith the optional M-3925A Target Module, LEDs areused to provide a detailed visual indication offunction operation for the most recent event.

The unit retains up to 472 cycles of oscillographwaveform data. This data can be downloaded andanalyzed using the M-3801D IPSplot® PLUSOscillograph Analysis Software.

The unit is powered from a wide input range switchmode power supply. An optional redundant powersupply is available for units without the ExpandedI/O. When expanded I/O option is selected, the unitincludes the second power supply.

The relay includes self-test, auto calibration, anddiagnostic capabilities, in addition to IRIG-B time-sync capability for accurate time-tagging of events.

Page 56: Generator Relay Protection

Introduction – 1

1–3

NOITCNUF NOITPIRCSED

snoitcnuFevitcetorP

12 ohmenoz-eerht(ecnatsiDesahP)citsiretcarahc

42 )emiTetinifeD&esrevnI(zH/stloV

72 egatlovrednUesahP

NT72 lartueN,egatlovrednUcinomraHdrihT

23 rewoPlanoitceriD

04 ohm-tesffoenoz-laud(dleiFfossoL)citsiretcarahc

64 tnerrucrevOecneuqeSevitageN

94 evitisoP(noitcetorPdaolrevOrotatS)tnerrucrevOecneuqeS

05 tnerrucrevOesahPsuoenatnatsnI

FB05 eruliaFrekaerB

TD05 tnerrucrevOemiTetinifeD

N05 tnerrucrevOlartueNsuoenatnatsnI

72/05 gnizigrenEtnatrevdanI

N15 tnerrucrevOlartueNemiTesrevnI

V15 egatloVhtiw,tnerrucrevOemiTesrevnItniartseRrolortnoC

95 egatlovrevOesahP

D95 laitnereffiDegatloVcinomraH-drihT

N95 egatlovrevOlartueN

X95 egatlovrevOesoprup-itluM

LF06 noitceteDssoL-esuFTV

N76 tnerrucrevOlanoitceriDlaudiseR

87 )citsiretcarahcohm(petSfotuO

18 ycneuqerF

A18 noitalumuccAycneuqerF

R18 ycneuqerFfoegnahCfoetaR

78 tnerruClaitnereffiDesahP

DG78 laitnereffiD)ecneuqesorez(dnuorG

SPI cigolSPI

MB rotinoMrekaerB

CT gnirotinoMtiucriCpirT

snoitcnuFevitcetorPlanoitpO

52 kcehCcnyS

B46/F46 /noitcetorPdnuorGdleiFnoitceteDffO-tfiLhsurB

S46 ybnoitcetorPdnuorGrotatS%001noitcejnI

Table 1-1 M-3425A Device Functions

Communication PortsThere are three physical communication portsprovided on the M-3425A. If the optional RJ45Ethernet port is purchased, then the relay includesfour physical communication ports:

• COM1, located on the relay front panel, isa standard 9-pin RS-232 DTE-configuredport. COM1 is used to locally set andinterrogate the relay using a portablecomputer.

• COM2, located on the rear of the relay, isa standard 9-pin RS-232 DTE-configuredport. When the optional RJ45 EthernetPort is enabled, COM2 port is disabled forcommunications. The demodulatedIRIG-B may still be used via the COM2Port when ethernet is enabled.

The RJ45 Ethernet port uses a 10Base-Ttype connection that accepts an RJ45connector using CAT5 twisted pair cable.The Ethernet port can support MODBUSover TCP/IP and BECO2200 over TCP/IPor IEC 61850. The IP address can beobtained automatically when using theDHCP protocol if enabled, or a static IPaddress can be manually entered, usingthe HMI.

• COM3, located on the rear terminal blockof the relay, is an RS-485 communicationsport.

The relay may be remotely set and interrogatedutilizing either a hard-wired RS-232 serial connectionor modem (COM2 when activated as RS-232, orCOM3), or when purchased, the ethernet connection(RJ45 activated).

M-3820D IPScom® Communications SoftwareIPScom is shipped standard with every relay. Thissoftware runs on a PC-compatible computer operatingunder Microsoft Windows® 98 or later. When properlyconnected using either a direct serial connection,modem or ethernet network connection. IPScomcan provide the following functions:

• Setpoint interrogation and modification

• Line status real-time monitoring

• Recorded oscillograph data downloading

Page 57: Generator Relay Protection

M-3425A Instruction Book

1–4

1.3 Accessories

M-3925A Target ModuleThe optional target module, shown below, includes 24individually labelled TARGET LEDs to indicateoperation of the functions on the front panel. Eightindividually labelled OUTPUT LEDs will be lit as longas the corresponding output contact is picked up.

!!

!

"! "#!

! $$!

!!

%

!"!!"

!%&

!!

!!

'

Figure 1-1 M-3925A Target Module

M-3933/M-0423 Serial Communication CablesThe M-3933 cable is a 10-foot RS-232 cable for usebetween the relay’s rear panel (COM2) port and amodem. This cable has a DB25 (25-pin) connector(modem) and a DB9 (9-pin) at the relay end.

The M-0423 cable is a 10-foot null-modem RS-232cable for direct connection between a PC and therelay’s front panel COM1 port, or the rear COM2port. This cable has a DB9 (9-pin) connector ateach end.

M-3931 HMI (Human-Machine Interface) ModuleThe optional HMI module provides the means tointerrogate the relay and to input settings, accessdata, etc. directly from the front of the relay. Itsoperation is described in detail in Section 3.1, FrontPanel Controls.

Figure 1-2 M-3931 Human-MachineInterface (HMI) Module

M-3801D IPSplot® PLUS Oscillograph AnalysisSoftware PackageThe IPSplot PLUS Oscillograph Analysis Softwareruns in conjunction with the IPScom®

Communications Software on any IBMPC-compatible computer, enabling the plotting,printing, and analysis of waveform data downloadedfrom the M-3425A Generator Protection Relay.

Page 58: Generator Relay Protection

Application – 2

2–1

2 Application

2.1 Configuration ............................................................................... 2–2

2.2 System Diagrams ....................................................................... 2–8

2.3 Setpoints and Time Settings ................................................... 2–14

Menu screens in the following examples are as theywould appear on units equipped with the M-3931Human Machine Interface (HMI) Module. The samesetting may be entered remotely usingM-3820D IPScom® Communications Software(see Chapter 4, Remote Operation).

Chapter Two is designed for the person or groupresponsible for the application of the M-3425AGenerator Protection Relay. It includes functionaland connection diagrams for a typical application ofthe relay; and describes the configuration processfor the unit (enabling functions), output contactassignment and input blocking designation. It alsoillustrates the definition of system quantities andequipment characteristics required by the protectiverelay, and describes the individual function settings.

Page 59: Generator Relay Protection

M-3425A Instruction Book

2–2

2.1 Configuration

Configuration of the relay consists of enabling thefunctions for use in a particular application,designating the output contacts each function willoperate, and which control/status inputs will blockthe function. The choices include eight programmableoutput contacts (OUT1–OUT8) and six control/statusinputs (IN1–IN6), or OUT9–23 and IN7–14 for unitspurchased with expanded I/O, plus a block choicefor fuse loss logic operation (see Section 2.3,Setpoint and Time Settings, 60FL Fuse Losssubsection for details).

The blocking control/status inputs and output contactassignments must be chosen before entering thesettings for the individual functions. Both may berecorded on the Relay Configuration Table inAppendix A, Configuration Record Forms.

Control/status input IN1 is preassigned to be the52b breaker status contact. If a multiple breakerscheme is used, the control/status input IN1 mustbe the series combination of the “52b” breakercontacts. Additional user-chosen control/statusinputs may initiate actions such as breaker failure,initiate external fuse loss detection, or trigger theoscillograph recorder.

The relay allows the user to designate up to sixlogic functions which perform similarly to internalrelay functions, using IPSlogicTM. These externalfunctions may be enabled or disabled, and outputcontacts and blocking control/status inputs arechosen the same as for the internal functions. Theexternal functions are described in further detail inSection 2.3, Setpoint and Time Settings, IPSlogicsubsection.

27#1 PHASE UNDERVOLTAGEdisable ENABLE

27#1 BLOCK INPUTfl i6 i5 i4 i3 i2 I1

27#1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 O1

NOTE: Uppercase text indicates selection.

This menu designation is required for each relay function. Afterenabling the function, the user is presented with the two followingscreens:

This submenu item assigns the blocking designations (up to six, plusfuse-loss logic) for the enabled function. “OR” logic is used if more thanone input is selected.

This submenu item assigns the output contacts (up to eight) for theparticular relay function. If no output contacts are assigned, the functionwill not generate any output or targets even though the function is enabled.

NOTE: Units with expanded I/O can only set OUT9–OUT23 and IN7–IN14 using IPScom®.

Page 60: Generator Relay Protection

Application – 2

2–3

ProfilesUp to four setpoint profiles may be used. Eachprofile contains a complete set of functionconfiguration and settings. One of the four profilesmay be designated as the Active Profile, which willcontain the settings that the relay will actively use.

The Active Profile may be chosen manually or bycontact input. When the profile Switching Method isset to Manual, the HMI, remote communications orone of the IPSlogic elements will select the ActiveProfile. When the Switching Method is set to InputContact, the profile is selected by the input contacts.When Input Contact is selected, only the inputcontacts can switch the relay’s profile, and none ofthe Manual methods will switch the profile.

A Copy Profile feature is available. This featurecopies an image of the Active Profile to any one ofthe other three profiles. This feature can speed upthe configuration process. Consider, for example, asituation where a breaker will be removed fromservice. Two profiles will be used: an “In Service”profile (Profile 1), and an “Out of Service” profile(Profile 2).

Profile 2 will be identical to the “In Service” profile,with the exception of the overcurrent settings.

Profile 1 is set to be the Active Profile, and allsetpoints entered. An image of Profile 1 will then becopied to Profile 2 with the Copy Active Profilecommand. Profile 2 is then selected as the ActiveProfile, and the overcurrent setpoints modified.

CAUTION: During profile switching, relay operationis disabled for approximately 1 second.

FunctionsConfiguration of the relay consists of enabling thefunctions for use in a particular application,designating the output contacts each function willoperate, and which control/status inputs will blockthe function. The choices include eight programmableoutput contacts (OUT1–OUT8) and six control/statusinputs (IN1–IN6)/(OUT1–OUT23 and IN1–IN14 forexpanded I/O units) plus a block choice for fuseloss logic operation (see Section 2.3, Setpoint andTime Settings, 60FL Fuse Loss subsection fordetails.)

Control/status inputs may also initiate actions, suchas Breaker Failure Initiate, Trigger OscillographRecorder, Switch Setpoint Profile, or initiate anIPSlogic function. The control/status inputs andoutput contacts need to be chosen before configuringthe individual functions. Both can be recorded onthe Relay Configuration Table in Appendix A, Forms.

Special ConsiderationsControl/status input IN1 is preassigned to be the52b breaker contact. IN5 and IN6 may be used toselect setpoint profiles.

Outputs 1–6 and 9–23 are form “a” contacts (normallyopen), and outputs 7 and 8 are form “c” contacts(center tapped “a” and “b” normally closed) contacts.Output contacts 1–4 contain special circuitry forhigh-speed operation and pick up 4 ms faster thanoutputs 5–8. Function 87 outputs are recommendedto be directed to OUT1 through OUT4 contacts.

Relay System SetupThe system setup consists of defining all pertinentinformation regarding the system quantities. Setupscreens shown here may be accessed through theSYSTEM SETUP menu. Regardless of the functionsthat are enabled or disabled, all System Setupvalues are required to be input. Several functionsrequire proper setting of these values for correctoperation. The Nominal Voltage and Nominal Currentsettings are needed for proper normalization of perunit quantities. CT and VT ratios are used only inmonitoring and displaying system primary quantities.

Input 5 Input 6 Selection

Open Open Profile 1

Closed Open Profile 2

Open Closed Profile 3

Closed Closed Profile 4

Table 2-1 Input Activated Profile

Page 61: Generator Relay Protection

M-3425A Instruction Book

2–4

INPUT ACTIVATED PROFILESdisable enable

ACTIVE SETPOINT PROFILE________________

COPY ACTIVE PROFILETO_PROFILE_1

NOMINAL VOLTAGE_____________ Volts

NOMINAL CURRENT______________ Amps

VT CONFIGURATIONline-line line-ground

line-gnd_to_line-line

DELTA-Y TRANSFORMdis delta_ab delta_ac

PHASE ROTATIONa-c-b a-b-c

When Input Activated Profiles is disabled, the Active Profile can beselected using HMI or remote communication. When enabled, theActive Profile is selected by the state of Input 5 and 6 (see Table 2-1).

This screen sets the active setpoint profile.

This screen initiates a copy of the Active Profile to any one of theother profiles.

The secondary VT voltage when primary voltage is equal to therated generator voltage. Vnominal=( V gen rated I VT ratio) for L-LVT connections. Vnominal=(Vgen rated I (S3 VT ratio)) for L-G VTconnections.

The secondary CT current of the phase CT’s with rated generatorcurrent. I nom = (VA I (Vgen rated(S3) )(CT ratio) )

Indicates VT connection. (See Figure 2-7, Three-Line ConnectionDiagram.) When line-ground voltages are used, functions 24, 27, and59 may operate for line-ground faults. If this is not desired, the line-gnd-to-line-line selection should be used to prevent operation of thesefunctions for line-ground faults.When line-gnd-to-line-line is selected,the relay internally calculates line-line voltages from line-ground voltagesfor all voltage-sensitive functions. This line-gnd-to-line-line selectionshould be used only for a VT line-to-ground nominal secondary voltageof 69V (not for 120 V). For this selection, the nominal voltage settingentered should be line-line nominal voltage, which is S3 times line-groundnominal voltage, and voltage function pickup setpoints calculationshould be made using line-to-line voltage.

When the generator is connected through a Delta-Y (delta ab or deltaac) unit transformer, the relay will internally consider the 30° phaseshift for 51V and 21 functions.It defines the connection of the Deltawindings of the Delta /Y transformer. If the polarity of the A windingis connected to the non-polarity of the C winding, it is defined asDelta-AC and if the polarity of the A winding is connected to the non-polarity of the B winding, then it is defined as Delta-AB. In the ABCphase rotation, delta lags Y by 30 degrees in Delta-AC and deltaleads Y by 30 degrees in Delta-AB.

This screen allows the user to select the phase rotation of theM-3425A to match the generator.

Page 62: Generator Relay Protection

Application – 2

2–5

This screen allows the selection of RMS or DFT for the 59 and 27 functions.The magnitude can be selected as the RMS of the total waveform (includingharmonics) or the RMS of the 60/50 Hz fundamental component of thewaveform using the Discrete Fourier Transform (DFT). When the RMSoption is selected, the magnitude calculation is accurate over a wide frequencyrange (10 to 80 Hz) and the accuracy of the time delay is +20 cycles.When the DFT option is selected, the magnitude calculation is accuratenear 50 or 60 Hz and the timer accuracy is K1 cycle. When a wider frequencyresponse is needed, select RMS. For generator protection applications, itis recommended to use the RMS selection. RMS is the default whenshipped from the factory. For 59 function when positive sequence voltageis selected, the calculation uses DFT irrespective of DFT/RMS selection.

NOTE: If neither pulsed or latched output is enabled, then the outputcontact will default to the Normal Mode. Normal Mode maintains theoutput contact energized as long as the condition that caused it tooperate exists. After the actuating condition is cleared, the contactwill reset after the programmed seal-in time has elapsed.

If the 50DT function is to be used for split-phase differential protection,this selection should be enabled. If the 50DT function is to be usedas a definite time overcurrent function, or if 50DT is not enabled, thisselection should be disabled.

If pulse relay operation is selected, output will dropout after the seal-in delay expires, even if the condition which caused the relay to pickup is still out of band. When selected, latching outputs are notavailable.*

If any of the outputs are selected as latched, then after tripping, thisoutput will stay activated, even when the tripping condition is removed.The Latched Output can be reset using the TARGET RESETpushbutton. When selected, Pulse Relay is not available. *

Minimum time the output contact will remain picked up to ensureproper seal-in, regardless of the subsequent state of the initiatingfunction. Individual Seal-In settings are available for all outputs.*

This designates the “active” state for the individual status input.Programming uppercase (see I6) causes the “active” or “operated”condition to be initiated by the external contact opening. Otherwise,external contact closure will activate the input.*

* NOTE: Settings for expanded I/O must be made through IPScom®.

Ratio of the phase VTs. Example: 13,800 V : 120 V =13,800/120=115:1

Ratio of the neutral VT. Example: 13,800 V : 120 V =13,800/120=115:1

Ratio of auxiliary VT. Example: 13,800 V : 120 V =13,800/120=115:1

Ratio of phase CTs. Example: 3,000:5 = 3000/5=600:1

Ratio of neutral CT. Example: 3,000:5 = 3000/5=600:1

59/27 MAGNITUDE SELECTrms dft

50DT SPLIT-PHASE DIFFdisable enable

PULSE RELAYo8 o7 o6 o5 o4 o3 o2 o1

LATCHED OUTPUTSo8 o7 o6 o5 o4 o3 o2 o1

RELAY SEAL-IN TIME OUT1_____________ Cycles

ACTIVE INPUT OPEN/closeI6 i5 i4 i3 i2 i1

V.T. PHASE RATIO______________ : 1

V.T. NEUTRAL RATIO_______________ :1

V.T. VX RATIO_______________ :1

C.T. PHASE RATIO______________ : 1

C.T. NEUTRAL RATIO______________ : 1

Page 63: Generator Relay Protection

M-3425A Instruction Book

2–6

Figure 2-1 Setup System Dialog Box

Path: Relay menu / Setup submenu / Setup System command

COMMAND BUTTONS

Input Active When the unit is equipped with expanded I/O, this command opens the Expanded Input ActiveState State screen (Figure 2-2), to allow the selection of Expanded Inputs 7 through 14.Expanded

Pulse/Latch When the unit is equipped with expanded I/O, this command opens the Pulse/LatchRelay screen (Figures 2-3 and 2-4) to allow the selection of expanded outputs 9 through 23.ExpandedOutputs

Save When connected to a protection system, sends the currently displayed information to the unit.Otherwise, saves the currently displayed information.

Cancel Returns you to the IPScom® main window; any changes to the displayed information are lost.

NOTE: Checking the inputs for the Active Input Open parameter designates the “operated” state established byan opening rather than a closing external contact.

Page 64: Generator Relay Protection

Application – 2

2–7

Figure 2-2 Selection Screen for Expanded Input

NOTE: If neither pulsed or latched output is enabled, then the output contact will default to the Normal Mode.Normal Mode maintains the output contact energized as long as the condition that caused it to operate exists.After the actuating condition is cleared, the contact will reset after the programmed seal-in time has elapsed.

Figure 2-3 Pulse Relay Expanded Output Screen

Figure 2-4 Latch Relay Expanded Output Screen

Page 65: Generator Relay Protection

M-3425A Instruction Book

2–8

2.2 System Diagrams

50DT

Utility System

52Unit

52Gen

50BFPh

87

492132 504078 60FL 51V 50/27

27

81R 81 27 59 24

64F 64B

M-3921+

-

CT

VT

M-3425A

87GD 50N50

BFN 51N

R

64S27TN

27

32R

High-impedance Grounding with ThirdHarmonic 100% Ground Fault Protection

Low-impedance Grounding with Ground Differentialand Overcurrent Stator Ground Fault Protection

These functions are available inthe Comprehensive Package. Asubset of these functions are alsoavailable in a Base Package.

This function is available as aoptional protective function.

This function provides control forthe function to which it points.

M-3425A TypicalConnection Diagram

25

59D

VT (Note 1)

Targets(Optional)

Integral HMI(Optional)

Metering

Waveform Capture

IRIG-B

Front RS232Communication

Multiple SettingGroups

Programmable I/O

Self Diagnostics

Dual Power Supply(Optional)

Rear Ethernet Port (Optional)

Rear RS-485Communication

BreakerMonitoring

Trip CircuitMonitoring

67N67N Polarization(Software Select)

81A

50N50BFN 51N

46

59X

59N

3VO (Calculated)VX

VN

3IO

IN

67N Operating Current(Software Select)

VT (Note 1)

(Note 3)

(Note 5)

CT (Residual)(Note 4)

59D Line SideVoltage

(Software Select)

VX3VO (Calculated)

CT (Neutral)(Notes 2 & 5)

CTM

(Metering)

M

(Metering)

Rear RS232Communication

Event Log

NOTES:1. When 25 function is enabled, 59X, 59D with V

X and 67N with V

X are not available, and vice versa.

2. When 67N function with IN (Residual) operating current is enabled, 87GD is not available, and vice

versa.

3. The 50BFN, 50N, and 51N may utilize either the neutral current or the residual current.

4. When used as a turn-to-turn fault protection device.

5. The current input IN can be either from neutral current or residual current.

6. The 50BFN, 50N, 51N, 59D, 67N (with IN or V

N) and 87GD functions are unavailable when the 64S

function has been purchased. See the M-3425A Instruction Book for connection details.

Figure 2-5 One-Line Functional Diagram

Page 66: Generator Relay Protection

Application – 2

2–9

Utility System

52Unit

52Gen

81R 81 59 27 24

M-3921+

-

VT

CT

M-3425A

50N 51N

R

CT

27

32R

High-impedance Grounding with ThirdHarmonic 100% Ground Fault Protection

Low-impedance Grounding with OvercurrentStator Ground Fault Protection

These functions are available inthe Comprehensive Package. Asubset of these functions are alsoavailable in a Base Package.

This function is available as aoptional protective function.

This function provides control forthe function to which it points.

M-3425A TypicalConnection Diagram(Configured for Split-PhaseDifferential)

25

59D

50DT

67N

Targets(Optional)

Integral HMI(Optional)

Metering

Waveform Capture

IRIG-B

Front RS232Communication

Multiple SettingGroups

Programmable I/O

Self Diagnostics

Dual Power Supply(Optional)

Rear EthernetPort (Optional)

Rear RS-485Communication

BreakerMonitoring

Trip CircuitMonitoring

27TN

81A

46492132 504078 60FL 51V 50/27

2764F 64B

59X

64S 59N

CT (Residual)(Note 5)

VT (Note 1)

VT (Note 1)

67N Polarization(Software Select)

3VO (Calculated)

VX

VN

(Note 2)

CT (Note 3)

(Note 4)

59D Line SideVoltage

(Software Select)

VX 3VO (Calculated)

CT (Neutral)(Note 5)

M

(Metering)

M

(Metering)

Rear RS232Communication

Event Log

NOTES:

1. When 25 function is enabled, 59, 59X, 59D with VX and 67N with V

X are not available, and vice

versa.

2. When used as a turn-to-turn fault protection device.

3. CTs are connected as split-phase differential current.

4. 67N operating current can only be selected to IN (Residual) for this configuration.

5. The current input (IN) can be either from neutral current or residual current.

6. The 50BFN, 50N, 51N, 59D, 67N (with IN or V

N) and 87GD functions are unavailable when the 64S

function has been purchased. See the M-3425A Instruction Book for connection details.

Figure 2-6 Alternative One-Line Functional Diagram (configured for split-phase differential)

Page 67: Generator Relay Protection

M-3425A Instruction Book

2–10

52Gen

A B C

Generator

58 59

56 57

54 55

OtherRelays

R45 44

M-3425A

M-3425A

WARNING: ONLY dry contact inputs mustbe connected because these contact inputsare internally wetted. Application of externalvoltage on these inputs may result indamage to the units.NOTE : M-3425A current terminal polarity marks( . ) indicate "entering" current direction whenprimary current is "from" the generator to thesystem. If CT connections differ from thoseshown, adjust input terminals.

M-3921Field Ground

Coupler Module

10

1152b

M-3425A

43 41 3942 40 38

M-3425A

Two Vt Open-DeltaConnection

43 41 3942 40 38

M-3425A

Three VT Wye-WyeConnection

434139 424038

M-3425A

Three VT Wye-WyeAlternate Connection

A

B

C

A

B

C

55 54

57 56

59 58

M-3425A

55 54

57 56

59 58

M-3425AOtherRelays

OtherRelays

a b c

a b c a b c

OR OR

High Impedance Grounding

52 53

M-3425A

R Low Impedance Grounding

OR

50 51

48 49

46 47

M-3425AOtherRelays

1

1

1

A B C

Example of Control/Output Connections

M-3425A

PowerSupply

52G

+

-

TRIPALARM

SELF-TEST

FAILUREALARM

POWEROK

STATUSALARM

VTFUSELOSS

EXTERNALINPUTS

ALARMOUTPUTS

CONTROLOUTPUTS

TRIPOUTPUT

BREAKERFAILUREINITIATE

52Ga

5

3 336

OSCILLOGRAPHRECORDER

INITIATE

60FL52b

2

60 6261 63 11 10

4

+

-

DC: 24V 48V

ORDC: 110V 125V 220V 250VAC: 110V 120V 230V 240V

16

15

12

13

4

5

6

Alarm output can be grouped to a singlealarm at the discretion of user.Available control output to service other relaysfor VT Fuse Loss can be designated.Input contact number is designated by user.

2

3

1 Wire to split phase differential CTs foruse with 50DT split phase function.Required generator breaker status input(52b). Contact is closed when generatorbreaker is open. Use unit breakercontact if no generator breaker present.Output contact pairs designated byuser.

Figure 2-7 Three-Line Connection Diagram

Page 68: Generator Relay Protection

Application – 2

2–11

52Gen

A B C

Generator

10

1152b

M-3425A

VX

43

41

39

42

40

38

M-3425A

Three VT Wye-WyeConnection

A B C

OR

VX

64

65

M-3425A

64

65

M-3425A

VX

Two VT Open-DeltaConnection

43

41

39

42

40

38

M-3425A

OR

A B C

Used when GeneratorSide VTs are connected

Line-Ground.

Used when Generator Side VTsare connected Line-Line

Used for Sync Check (25)

NOTE: When VX is connected for Sync Check function (25), turn-to-turn fault protection (59X) is not

available.

Figure 2-8 Function 25 Sync Check Three-Line Connection Diagram

Page 69: Generator Relay Protection

M-3425A Instruction Book

2–12

52Gen

A B C

Generator

10

1152b

M-3425A

a b c

52 53

M-3425A

R Low Impedance Grounding

65

64

M-3425A

A B C

Line to NeutralVoltage Rated

Cable

R

R45 44

M-3425A

High Impedance Grounding

OR

VX used for turn-to-turnfault protection (59X)

VX

NOTE: When VX is connected for turn-to-turn fault protection, 59X and 25 functions are not available.

Figure 2-9 Function 59X Turn to Turn Fault Protection Three-Line Connection Diagram

Page 70: Generator Relay Protection

Application – 2

2–13

52Gen

A B C

Generator

10

1152b

M-3425A

a b c

52 53

M-3425A

R Low Impedance Grounding

A

B

C

I N input can be connectedeither at Neutral or as Residual.

I N input can be connectedeither at Neutral or as Residual.

OR

R45 44

M-3425A

High Impedance Grounding

65 64

M-3425A

R

59XBus Ground

65

64

M-3425A

A B C

R

67N, 59DConnection

53

52

M-3425A

67NConnection

Residual CT

Bus Section

VX

VX can be used for both 67N and59D if connected in this manner.

NOTE: When VX is connected for bus ground protection (59X, 67N, or 59D) , 25 function is not available.

Figure 2-10 Function 67N, 59D, 59X (Bus Ground) Three-Line Connection Diagram

Page 71: Generator Relay Protection

M-3425A Instruction Book

2–14

If Zone 1 is not set to see the transmission system,out-of-step blocking is not recommended.

When Zone 3 is used for Out-of-step blocking, theout of step delay is used for the detection of thetransit time of the swing between Zone 3 and Zone2 impedances.

The load encroachment blinder function can be setwith a reach and an angle as shown in Figure 2-13.When enabled, this feature will block the 21 Functionfrom misoperating during high load conditions.

When the generator is connected to the system througha delta/wye transformer, proper voltages and currents(equivalent to the high side of the transformer) must beused in order for the relay to see correct impedancesfor system faults. By enabling the Delta-Y Transformfeature (see Section 2.1, Configuration, Relay SystemSetup), the relay can internally consider the 30° phaseshift (30° lead delta-ab or 30° lag delta-ac) through thedelta/wye transformer, saving auxiliary VTs. Impedancecalculations for various VT connections are shown inTable 2-2. All impedance settings are secondary relayquantities and can be derived from the following formula:

Z SEC

= ZPRI

x (RC ÷ R

V)

where ZSEC = secondary reflected impedance, ZPRI =primary impedance, R

C = current transformer ratio,

and RV = voltage transformer ratio.

The minimum current sensitivity depends on theprogrammed reach (diameter and offset). If thecurrent is below the minimum sensitivity current,the impedance calculated will saturate, and not beaccurate. This will not cause any relay misoperation.

An overcurrent supervision feature can be enabled,which will block the 21 function when all threephase currents are below the pickup value.

2.3 Setpoints and Time Settings

The individual protective functions, along with theirmagnitude and timing settings are described in thefollowing pages. Settings for disabled functions donot apply. Some menu and setting screens do notappear for functions that are disabled or notpurchased. Menu screens are as they would appearon units equipped with the M-3931 HMI Module.The same setting may be entered using M-3820DIPScom Communications Software.

For those units equipped with Expanded I/O, settingof Expanded Inputs and Outputs is accomplishedby selecting “Expanded I/O” from the individualfunction screen. IPScom® will display the ExpandedI/O Initiate dialog screen (Figure 2-11).

21 Phase DistanceThe Phase Distance function (21) is designed forsystem phase fault backup protection and isimplemented as a three-zone mho characteristic.

Three separate distance elements are used to detectAB, BC, and CA fault types. The ranges andincrements are shown in Figure 2-14. The diameter,offset, system impedance angle (relay characteristicangle), and definite time delay need to be selectedfor each zone for coordination with the systemrelaying in the specific application.

Zone 1, Zone 2 and Zone 3 may be used for backupprotection for unit transformer and transmissionfaults. Zone 3 in conjunction with Zone 2 can beused to detect an Out of Step condition and it canbe programmed to block Function 21 #1 and/or 21#2. If Zone 3 is being used for out-of-step blocking,it does not trip.

Figure 2-11 Selection Screen for Expanded I/O Initiate

Page 72: Generator Relay Protection

Application – 2

2–15

21 #1 DIAMETER______________ Ohms

21 #1 OFFSET______________ Ohms

21 #1 IMPEDANCE ANGLE____________ Degrees

21#1 LOAD ENCROACHMENTdisable ENABLE

21 #1 LOAD ENCR ANGLE____________ Degrees

21 #1 LOAD ENCR R REACH______________ Ohms

21 #1 OC SUPERVISIONdisable enable

21 #1 OC SUPERVISION______________ Amps

21 #1 OUT OF STEP BLOCKdisable enable

21 #1 DELAY_____________ Cycles

21 #3 OUT OF STEP DELAY_____________ Cycles

Typically the first zone of protection is set to an impedance valueenough in excess of the first external protective section (typicallythe unit transformer) to assure operation for faults within thatprotective zone. See Figure 2-12, Phase Distance (21) Coverage.

A negative or positive offset can be specified to offset the mhocircle from the origin. This offset is usually set at zero. See Figure2-13, Phase Distance (21) Function Applied For System Backup.

The impedance angle should be set as closely as possible to theactual impedance angle of the zone being protected.

When enabled the 21 Function is blocked when the impedancefalls within the zone but above the R Reach and below the LoadEncroachment angle.

NOTE: The 21 #2 and #3 zone settings can be set for an additionalexternal section of protection on the system (typically transmissionZone 1 distance relays) plus adequate overreach. #2 and #3 screensare identical to those in #1. Element #3 also includes out-of-steptime delay when out-of-step blocking is enabled for Zone #1 and/orZone #2.

When enabled, the overcurrent supervision blocks the 21 Func-tion when all three phase currents are below the pickup.

When enabled the 21 Function is blocked on the detection of anout-of-step condition.

The time delays are set to coordinate with the primary protectionof those overreached zones and, when applicable, with the breakerfailure schemes associated with those protective zones.

In Zone #3 when out-of-step blocking is enabled for Zone #1 or #2.

Page 73: Generator Relay Protection

M-3425A Instruction Book

2–16

3

21

52

Protected Range Zone 1

+X

+R

–X

–R

M-3425A

Protected Range Zone 2

Protected Range Zone 3

52

Bus

52

Figure 2-12 Phase Distance (21) Coverage

NOTE: The reach settings of the distance elements (21) should not include generator impedance sincethe distance measurement starts at the VT location. However, since the neutral side CTs areused for this function, backup protection for generator Phase-to-Phase faults is also provided

R1 Zone 1 Load Encroachment Blinder R Reach

R2 Zone 2 Load Encroachment Blinder R Reach

δ1 Zone 1 Load Encroachment Blinder Angle

δ2 Zone 2 Load Encroachment Blinder Angle

Θ Impedance Angle Setting

NOTE: Zone #3 is used for power swing detection in this example.

Figure 2-13 Phase Distance (21) Function Applied for System Backup

Page 74: Generator Relay Protection

Application – 2

2–17

Table 2-2 Impedance Calculation

Figure 2-14 Phase Distance (21) Setpoint Ranges

Page 75: Generator Relay Protection

M-3425A Instruction Book

2–18

24 Overexcitation Volts/HzThe Volts-Per-Hertz function (24) providesoverexcitation protection for the generator and unit-connected transformers. This function incorporatestwo definite time elements which can be used torealize traditional two-step overexcitation protection.In addition, the relay includes an inverse timeelement that provides superior protection by closelyapproximating the combined generator/unittransformer overexcitation curve. Industry standardinverse time curves may be selected along with alinear reset rate which may be programmed tomatch specific machine cooling characteristics. Thepercent pickup is based on the Nominal Voltagesetting and the nominal frequency. The V/Hz functionprovides reliable measurements of V/Hz up to 200%for a frequency range of 2–80 Hz. The ranges andincrements are presented in Figure 2-16.

Setting this relay function involves determining thedesired protection levels and operating times. Thefirst step is to plot the combined generator andassociated unit transformer overexcitation capabilitylimits. This data is typically available from themanufacturer and should be plotted on the samevoltage base. Depending on the resultingcharacteristic, one of the four families of inversetime curves (as shown in Appendix D, InverseTime Curves) can be matched to provide theprotection. The two definite time elements can beused to further shape the protection curve or providean alarm.

Figure 2-15 illustrates a composite graph of generatorand transformer limits, a chosen inverse time curveand pickup, and a definite time pickup and delay.

24DT #1 PICKUP_______________ %

24DT #1 DELAY_____________ Cycles

24DT #2 PICKUP_______________ %

24DT #2 DELAY_____________ Cycles

24IT PICKUP_______________ %

24IT CURVEcrv#1 crv#2 crv#3 crv#4

24IT TIME DIAL________________

24IT RESET RATE____________ Seconds

Definite time setpoint #1 establishes the V/Hz level above which theprotection operating time will be fixed at the definite time delay #1.

Delay time #1 establishes the operation time of the protection forall V/Hz values above the level set by definite time setpoint #1.

Definite time setpoint #2 could be programmed to alarm, alerting theoperator to take proper control action to possibly avoid tripping.

Time to operation at any V/Hz value exceeding Definite time setting#2.

The pickup value is the V/Hz value at which the chosen inversecurve begins protective operation. Typical value is 105%.

Allows the user to designate the appropriate curve family for thisprotection application. These curves are shown in Appendix D,Inverse Time Curves.

The appropriate curve in the family is designated by the associated“K” value of the curve.

The value entered here should be the time needed for the unit tocool to normal operating temperature if the V/Hz excursion timewas just under the trip time.

Page 76: Generator Relay Protection

Application – 2

2–19

M-3425A Firmware Versions D-0114VXX.XX.XXand Earlier

NOTE: When the inverse time element isenabled, the definite time element #1must be enabled which will providedefinite minimum time setting for theinverse time curve.

The following steps must be followed when settingthe inverse time element and definite time element#1:

1. The pickup of the inverse time elementmust be less than the pickup of thedefinite time element #1

2. The operating time of the inverse timeelement at the definite time element #1pickup should be greater than the definitetime element #1 time delay setting(A2>A1 in Figure 2-15).

3. When the inverse time element isenabled, definite time element #1 shouldnot be used for alarm. Only definite timeelement #2 can be used for alarm.

After any V/Hz excursion, cooling time must alsobe taken into account. If the unit should again besubjected to high V/Hz before it has cooled tonormal operating levels, damage could be causedbefore the V/Hz trip point is reached. For thisreason, a linear reset characteristic, adjustable totake into account the cooling rate of the unit, isprovided. If a subsequent V/Hz excursion occursbefore the reset characteristic has timed out, thetime delay will pick up from the equivalent point (asa %) on the curve. The Reset Rate setting enteredshould be time needed for the unit to cool to normaloperating temperature if the V/Hz excursion timewas just under the trip point.

M-3425A Firmware Version D-0150V 01.00.34The inverse time element has a definite minimumtime of 30 cycles. Definite Time Element #1 isindependent, and has no effect on inverse timeelements.

M-3425A Firmware Version D-0150V 01.04.00The inverse time element has a definite minimumtime of 60 cycles. Definite Time Element #1 isindependent, and has no effect on inverse timeelements.

!"

## #$ # $ # $ # $ %# %$ $#

#&#

#&

#

##

###

'

(

)*(+

,(*

(*,

)*-.((*/0$

12(*

(+

3456

)*3(+7456

Figure 2-15 Example of Capability and Protection Curves (24)

Page 77: Generator Relay Protection

M-3425A Instruction Book

2–20

Figure 2-16 Volts-Per-Hertz (24) Setpoint Ranges

Page 78: Generator Relay Protection

Application – 2

2–21

25 Sync CheckNOTE: The 25 function cannot be enabled under

any one of the following conditions:• 67N (Residual Directional Overcurrent)

is enabled and the polarizing quantityhas been set to V

X.

• 59D is enabled and the line side voltageis set to V

X.

• 59X is connected for turn-to-turn faultprotection or bus ground protection.

The Synchronism (Sync) Check function (25) isused to ensure that the voltage magnitude, phaseangle and frequency of the generator (V1) and theutility system (V

X) are within acceptable limits before

the generator is synchronized with the system.Generator voltage (V1) can be selected as A, B, orC (line-to-ground and line-ground to line-line) or AB,BC, or CA (line-to-line).

The sync check function includes phase angle,delta frequency, and delta voltage checks.

Phase Angle CheckThe phase angle is considered acceptable when theselected sync phase voltage (V1) and systemvoltage (V

X) are within the Upper Volt Limit and

Lower Volt Limit window and the measured phaseangle is within the phase angle window.

Phase Angle Limit is defined as twice the PhaseAngle Limit setting. For example, if the PhaseAngle Limit is set at 10 degrees, a phase anglewindow of 20 degrees exists between –10 degreesand +10 degrees. The logic diagram of the phaseangle check is shown in Figure 2-17.

Delta Voltage and Delta Frequency CheckDelta Voltage and Delta Frequency elements maybe individually enabled or disabled, as desired. TheDelta Voltage check will compare the absolutedifference between the selected sync phase voltage(V1) and the measured system voltage (VX) with theDelta Voltage Limit setting. Likewise, the DeltaFrequency measures the frequency differencebetween V1 and V

X voltage signals. The Phase

Angle Check, Delta Voltage and Delta FrequencyCheck all combine through an appropriate timer withthe output directed to the programmed 25S outputcontact. A logic diagram representing this logic ispresented in Figure 2-17.

Dead Line/Dead Bus CheckThe Dead Volt Limit defines the Hot/Dead voltagelevel used in Deadline/Dead Bus closing schemes.When the measured V

X voltage is equal to or below

the Dead Volt Limit, VX is considered dead. When

the measured VX is above the Dead Volt Limit, V

X is

considered hot. The opposite side of the breakeruses the positive sequence voltage measurement(V1) for 3-phase consideration in determining hot/dead detection. Different combinations of hot line/dead bus closings may be selected, depending onhow the buses are referenced. A logic diagram ofthe Deadline/Dead Bus scheme is presented inFigure 2-17.

The Dead V1, Dead VX, and Dead V1 & V

X enable

are software switches used to enable the dead line/dead bus logic. Further conditioning can be performedon the dead detection logic by selecting one ormore input contacts (Dead Input Enable) to controlthe enabled dead detection element. For example,if INPUT2 (I2) is selected under the Dead InputEnable screen, and both the Dead V1 and Dead V

Xelements are enabled, the dead check timer willstart when INPUT2 is activated, and either V1dead/V

X hot or V1 hot/V

X dead. This allows for

external control of the desired dead closing scheme.Dead Input Enable selections are common to alldead detection elements. If no inputs are selectedunder the Dead Input Enable screen, and any deadelement is enabled, the dead check timer will startimmediately when the dead condition exists.

The 25S and 25D can be programmed to be sent totwo different contacts, if desired.

NOTE: The 25 function does not produce a targetor LED and is accompanied by the HMImessage “F25 Function Operated”.

Page 79: Generator Relay Protection

M-3425A Instruction Book

2–22

If this function is enabled, the following settings are applicable:

25S PHASE LIMITDegrees

25S UPPER VOLT LIMITVolts

25S LOWER VOLT LIMITVolts

25S SYNC CHECK DELAYCycles

25S DELTA VOLTdisable ENABLE

25S DELTA VOLT LIMITVolts

25S DELTA FREQUENCYdisable ENABLE

25S DELTA FREQ LIMITHz

25S SYNC-CHECK PHASEa b c

25D DEAD VOLT LIMITVolts

25D DEAD V1 HOT VXdisable ENABLE

25D DEAD VX HOT V1disable ENABLE

25D DEAD V1 & VXDISABLE enable

25D DEAD INPUT ENABLEi6 i5 i4 I3 i2 i1

25D DEAD DELAYCycles

Phase angle setting.

Upper voltage limit for voltage acceptance.

Lower voltage limit for voltage acceptance.

Sync check time delay.

Delta voltage element.

Delta voltage setting.

Delta frequency element.

Delta frequency setting.

Selects the phase voltage on the generator side for Sync Check func-tions (A, B, or C for line-to-ground and line-ground to line-line, and AB,BC, CA for line-to-line)

Voltage less than this setting is defined as “DEAD”; above this set-ting as “HOT”.

Enables Dead V1/Hot VX setting.

Enables Hot V1/Dead VX setting.

Enables Dead V1/Dead VX closing.

Externally controlled dead closing. Inputs IN7–IN14 must be set us-ing IPScom.

Dead delay timer setting.

Page 80: Generator Relay Protection

Application – 2

2–23

Phase Angle Check Logic

Dead Line/ Dead Bus Check Logic

Dead Line/ Dead Bus Check Input Initiate Logic

Dead Input Enable

AND

OR AND

ANDAND

AND

AND

AND

AND

OR

OR

AND

AND AND

AND

AND

|V1 - V X| < Delta V Limit

Delta V Is Enabled

Delta F Is Enabled

V1 Lower Voltage Limit>

V1 Upper Voltage Limit<

VX Lower Voltage Limit>

VX Upper Voltage Limit<

Phase Angle Phase Limit<

|F1 - F X | < Delta F Limit

Phase Angle OK

AND

AND

|V1- VX| < Delta V Limit

Delta V Is Enabled

Delta F Is Enabled

|F 1 - FX | < Delta F Limit

With Delta V OR Delta F Enabled

With Delta V AND Delta F Enabled

V1pos Dead Limit<

Dead V1 Hot V X Enabled

VX > Dead Limit

Dead V X Hot V1 Enabled

V1pos Dead Limit<

VX < Dead Limit

VX < Dead Limit

Dead V1 V X Enabled

V1pos Dead Limit<

VX > Dead LimitDead V1 Hot V X Enabled

V1pos Dead Limit>

V1pos Dead Limit>

VX < Dead Limit AND

Dead V X Hot V1 Enabled

Selected INPUT Is Activated

AND

User Software Setting

Measured Variable

Delta V and Delta F Check Logic

Delta V and Delta F Check Logic

Only one Delta V and Delta F Check Scheme may be active at a time.

Only one Delta V and Delta F Check Scheme may be active at a time.

Sync Check TimerOutput Seal-in Timer

25SOutputContact

OR

Dead Check TimerOutput Seal-in Timer

25DOutputContact

Figure 2-17 Sync Check Logic Diagrams

Page 81: Generator Relay Protection

M-3425A Instruction Book

2–24

Figure 2-18 Sync Check (25) Setpoint Ranges

Page 82: Generator Relay Protection

Application – 2

2–25

27 Phase UndervoltageThe Phase Undervoltage function (27) may be usedto detect any condition causing long- or short-termundervoltage. This is a true three-phase function inthat each phase has an independent timing element.The ranges and increments are presented in Figure2-19.

Magnitude measurement depends on the 59/27Magnitude Select setting. (See Section 2.1,Configuration, Relay System Setup.) When the RMScalculation is selected, the magnitude calculation isaccurate over a wide frequency range (10 to 80 Hz)and the accuracy of the time delay is +20 cycles. IfDFT calculation is selected, the magnitudecalculation is accurate near 50 or 60 Hz, and thetimer accuracy is K1 cycle.

Figure 2-19 Phase Undervoltage (27) Setpoint Ranges

27 #2 and 27 #3 Screens are identical to 27 #1.27 #1 PICKUP_____________ Volts

27 #1 DELAY_____________ Cycles

Page 83: Generator Relay Protection

M-3425A Instruction Book

2–26

27TN Third Harmonic Undervoltage, NeutralFor ground faults near the stator neutral, the ThirdHarmonic (180/150 Hz) Neutral undervoltagefunction (27TN) provides stator ground-faultprotection for high-impedance-grounded generatorapplications (See Figure 2-20). When used inconjunction with the fundamental neutralovervoltage (60/50Hz) function (59N), 100% statorground-fault protection can be provided. This isillustrated in Figure 2-20.

The 27TN function can be supervised by thepositive-sequence undervoltage element.Undervoltage supervision can prevent tripping whenthe generator field is not energized or the unit isnot yet synchronized.

In some generators, the third harmonic voltagecan be very low, especially during light loadconditions. It is also observed in some generatorinstallations that the third harmonic voltage isconsiderably reduced for a specific range of poweroutput (band). To prevent mis-operation duringthese conditions, the 27TN function can beprogrammed to be supervised (blocked) by lowforward power, low reverse power, low Vars (leadand lag), low power factor (lead/lag), and whenthe forward power is inside a band.

To properly handle pump storage operations, theM-3425A forward power blocking algorithm is enablefrom “zero per unit” to the forward power setpoint.During plant startup, after the field is flashed and

before the unit synchronized, small currentmeasurement errors cause the measured powerto fluctuate (typically <0.2%.) This may result ina measured power value that is negative (i.e.,–0.001 pu.) If the reverse power blocking is notenabled, the 27TN may be momentarily unblocked,resulting in a relay operation and nuisance generatortrip. It is highly recommended that if the ForwardPower Blocking is used, both the Forward PowerBlocking and Reverse Power Blocking be enabledand set.

In the majority of the cases, these blockingfunctions will be disabled, except for those operatingcases where the third harmonic neutral voltagemagnitude is less than 0.5 V. The settings forthe blocking functions should be set based onfield measurements. Blocking regions are illustratedin Figure 2-21.

The 27TN setting depends on the actual third-harmonic neutral voltage level seen during normaloperation of the generator. The setting should beabout 50% of the minimum third-harmonic voltageobserved during various loading conditions. Thiscan be most conveniently measured duringcommissioning of the relay. Since the relaymeasures the third harmonic voltage levels andwill display those values directly, no additionalequipment is required. The undervoltage inhibitsetting should be about 80% to 90% of the nominalvoltage. The ranges and increments are presentedin Figure 2-22.

#8 #9

+*2213:

(2,

(

#9 $#9;(

49<2(2(26

##9

2,

;(24=# $#!"6(*2((2(

>2!4?# $#!"6(*2((2(

8(>2>**

$98#9

@-+8((2(**

$A-+43+3$6

Figure 2-20 Third Harmonic Undervoltage (27TN) Protection Characteristics

Page 84: Generator Relay Protection

Application – 2

2–27

-P +P

Lag VAr Block

Lead VAr Block

ReversePowerBlock

ForwardPowerBlock

Low Band ForwardPower Block

High BandForward

Power Bloc

Block Block

+Q

-QFigure 2-21 27TN Blocking Regions

Figure 2-22 Third Harmonic Undervoltage, Neutral Circuit (27TN) Setpoint Ranges

Page 85: Generator Relay Protection

M-3425A Instruction Book

2–28

27TN #2 Screens are identical to 27TN #1.Relay volts are equal to the primary neutral volt-age divided by the grounding transformer ratio. Gen-erally set for approximately 50% of the minimumthird harmonic voltage observed during various load-ing conditions.

27TN #1 PICKUP_____________ Volts

27TN #1 POS SEQ VOLT BLKdisable ENABLE

27TN #1 POS SEQ VOLT BLKVolts

27TN #1 FWD POWER BLKdisable ENABLE

27TN #1 FWD POWER BLKPU

27TH #1 REV POWER BLKdisable ENABLE

27TN #1 REV POWER BLKPU

27TN #1 LEAD VAR BLKdisable ENABLE

27TN #1 LEAD VAR BLKPU

27TN #1 LAG VAR BLKdisable ENABLE

27TN #1 LAG VAR BLKPU

27TN #1 LEAD PF BLKdisable enable

27TN #1 LEAD PF BLKLEAD

27TN #1 LAG PF BLKdisable enable

27TN #1 LAG PF BLKLAG

27TN #1 BAND FWD PWR BLKdisable enable

27TN#1 LO B FWD PWR BLKPU

27TN#1 HI B FWD PWR BLKPU

27TN #1 DELAYCycles

Page 86: Generator Relay Protection

Application – 2

2–29

32 Directional PowerThe Directional Power function (32) can provideprotection against both generator motoring andoverload. It provides three power setpoints, eachwith a magnitude setting and a time delay. TheForward Power direction (power flow to system) isautomatically chosen when the pickup setting ispositive and the Reverse Power direction (powerflow to generator) is automatically chosen when thepickup setting is negative. The range, as shown isfrom –3.000 PU to 3.000 PU where 1.0 PU is equalto the generator MVA rating. Normalized PU powerflow measurements are based on Nominal Voltageand Nominal Current setting, as shown in Section2.1, Configuration, Relay System Setup.

Protection from Generator MotoringProtection against motoring is provided by selectinga negative pickup with Over/Under power set toOver. The relay will operate when the measured realpower is greater (more negative) than the pickupsetting in the reverse direction.

In some steam generator applications it is desirableto trip the generator when the forward power is lessthan a small value. This is due to the fact that thetrapped steam will cause the generator to supply asmall amount of power even though the steam

valves are closed. In this case the Over/Underpower setting is set to Under and a positive pickupsetting is chosen. The relay will trip when themeasured forward power is less than the pickupvalue. The function should be blocked when thegenerator breaker is open (using contact inputblocking) otherwise the function will trip and preventthe generator from being brought online.

Protection from Generator OverloadProtection from generator overload is provided byselecting a positive pickup setting with Over/UnderPower setting set to Over. The relay will operatewhen the measured real power is greater than thepickup setting.

Protection from Excessive Reactive PowerThe directional power element #3 can be set tooperate on either real power or reactive power.When protection from excessive reactive power isrequired the element #3 can be set to operate onreactive power. The relay will operate when themeasured reactive power exceeds the pickup setting.

Figures 2-23 through 2-26 show reverse power, lowforward power, over power, and over reactive powerapplications.

B)

B*<;<

(+

&#8&#

;<2<;<

Figure 2-23 Tripping on Reverse Power Flow (Over Power with Negative Pickup)

Page 87: Generator Relay Protection

M-3425A Instruction Book

2–30

32 #1 PICKUP_______________ PU

32 #1 DELAY_____________ Cycles

32 #1 TARGET LEDdisable enable

32#1 UNDER/OVER POWERover under

32 #2 PICKUP_______________ PU

32 #2 DELAY_____________ Cycles

32 #2 TARGET LEDdisable enable

32#2 UNDER/OVER POWERover under

32 #3 PICKUP_______________ PU

32 #3 DELAY_____________ Cycles

32 #3 TARGET LEDdisable enable

32#3 UNDER/OVER POWERover under

32 #3 DIR POWER SENSINGreal reactive

The reverse power pickup setting should be based on the type ofprime mover and the losses when the generator is motoring.

Reverse power relays should always be applied with a time delayin order to prevent mis-operation during power swing conditions.Typical time delay settings are 20 to 30 seconds.

Target LED for the 32 Function elements can be individually enabledor disabled.

When Low Forward Power protection is desired, set this to Underwith a positive pickup setting. The relay will trip when the realpower measurement is less than or equal to the pickup setpoint.

If used, positive direction power settings can be used for overloadprotection, providing either alarm or tripping or both, when powerequals or exceeds the setting. The pickup and time delay settingsshould be based on the capability limit of the generator.

A second reverse power setting can be used for sequential trip-ping of the generator in which case the associated time delay willbe in the range of 2 to 3 seconds.

Directional Power Sensing for Element #3 can be selected as Realor Reactive.

Page 88: Generator Relay Protection

Application – 2

2–31

B)

B*<;<

(+

&#8&#

;<2<;<

Figure 2-24 Tripping on Low Forward Power (Under Power with Positive Pickup)

B)

B*<;<

(+

&#8&#

;<2<;<

Figure 2-25 Tripping on Overpower (Over Power with Positive Pickup)

Page 89: Generator Relay Protection

M-3425A Instruction Book

2–32

B)

B*<;<

(+

&#8&#

;<2<;<

B*<)-3

B*<),

Figure 2-26 Tripping on Over Reactive Power with Element #3 (Over Power, Positive Pickup andDirectional Power Sensing Set to Reactive)

Figure 2-27 Directional Power, 3-Phase (32) Setpoint Ranges

Page 90: Generator Relay Protection

Application – 2

2–33

40 Loss of FieldThe Loss-of-Field function (40) provides protectionfor a partial or complete loss of field. A variety ofpossible settings make the M-3425A GeneratorProtection Relay very flexible when applied to loss-of-field protection. Ranges and increments arepresented in Figure 2-30.

The loss-of-field function is implemented with twooffset mho elements, an undervoltage element, anda directional element. The setting for each mhoelement, diameter, offset, and time delay, areadjusted individually. Each element has two timedelay settings. The second time delay (delay withVC) is applicable with voltage control, and the timeronly starts if the positive sequence voltage is belowthe voltage control setting. The function with voltagecontrol and without voltage control can beprogrammed to send to two different output contacts,if desired. The delay with voltage control may beenabled on each element but the voltage levelsetting is common. The voltage control allows forfaster tripping when low voltage may be caused bythe VAr intake by the machine with loss of excitation.A common directional unit is provided to block therelay operation during slightly underexcitedconditions (since approach #1 with negative offsetis inherently directional, the directional element isnot required). The directional unit’s angle setting(QD) can be set from 0° to 20°.

The settings of the offset mho elements should besuch that the relay detects the loss-of-field conditionfor any loading while not mis-operating during powerswings and fault conditions. Two approaches arewidely used in the industry, both of which aresupported by the M-3425A relay. Both approachesrequire knowledge of the reactances and otherparameters of the generator. They are described inFigure 2-28, Loss of Field (40) — ProtectiveApproach I and Figure 2-29, Loss of Field (40) —Protective Approach II.

Positive sequence impedance measurements areused for the loss of field functions. All impedancesettings are secondary relay quantities and can bederived from the following formula:

Z SEC

= ZPRI

x (RC ÷ R

V)

where ZSEC

= secondary reflected impedance,Z

PRI = primary impedance, R

C = current transformer

ratio, and RV = voltage transformer ratio.

The first approach is shown in Figure 2-28, Loss ofField (40) — Protective Approach I. Here, both ofthe offset mho elements (#1 and #2) are set with anoffset of –Xl

d÷2, where Xl

d is the (saturated) direct

axis transient reactance of the generator. Thediameter of the smaller circle (#1) is set at 1.0 puimpedance on the machine base. This mho elementdetects loss-of-field from full load to about 30%load. A small time delay provides fast protection.

The diameter of the larger circle (#2) is set equal toX

d, where X

d is the (unsaturated) direct axis

synchronous reactance of the machine. This mhoelement can detect a loss-of-field condition fromalmost no load to full load. A time delay of 30 to 60cycles (#2) should be used in order to preventpossible incorrect operation on stable swings.

The time delay with voltage control is typically setshorter than the other time delay.

The second approach is shown in Figure 2-29,Loss of Field (40) – Protective Approach II. In thisapproach, one of the mho elements is set with anoffset of –Xl

d ÷ 2, a diameter of 1.1 X

d-(Xl

d ÷ 2), and

a time delay of 10 to 30 cycles. The second elementis set to coordinate with the generator minimumexcitation limit and steady-state stability limit.

In order to obtain proper coordination, the offset ofthis element must be adjusted to be positive.Typically, the offset is set equal to the unittransformer reactance (X

T). The diameter is

approximately equal to (1.1 Xd + XT). A time delayof 30 to 60 cycles would prevent mis-operation onstable swings.

The following table provides suggested time settingswhen time delay with VC is used in addition tostandard time delay.

Typical setting is 13° (0.974 power factor). Thissetting is common to both element #1 and #2.

Approach #1 can also be used for Zone #1, andapproach #2 for Zone #2, where better coordinationwith AVR limiters, machine capability limits, andsteady state stability limits can be obtained.

Page 91: Generator Relay Protection

M-3425A Instruction Book

2–34

40 #1 DIAMETEROhms

40 #1 OFFSETOhms

40 #1 DELAYCycles

40VC #1 DELAY WITH VCCycles

40 #2 DIAMETEROhms

40 #2 OFFSETOhms

40 #2 DELAYCycles

40VC #2 DELAY WITH VCCycles

40 VOLTAGE CONTROLVolts

40 DIRECTIONAL ELEMENTDegrees

Zone 1Voltage Control

SettingDelay

Delay with VC

N/A

15 Cycles

Disable

Zone 280 to 90% of

Nominal Voltage

3,600 Cycles

60 Cycles

Table 2-3 Voltage Control Time Settings

Page 92: Generator Relay Protection

Application – 2

2–35

C

DCE

C

F

!

"!#"" !

F$%

Figure 2-29 Loss of Field (40)—Protective Approach 2

C

&

DCE

F

!

"!#"" !

F$%

Figure 2-28 Loss of Field (40)—Protective Approach 1

Page 93: Generator Relay Protection

M-3425A Instruction Book

2–36

Figure 2-30 Loss-of-Field (40) Setpoint Ranges

NOTE: Out of Step Block Enable is not available for this release, and will appear greyed-out in display.

Page 94: Generator Relay Protection

Application – 2

2–37

46 Negative Sequence OvercurrentThe Negative Sequence Overcurrent function (46)provides protection against possible rotoroverheating and damage due to unbalanced faultsor other system conditions which can causeunbalanced three phase currents in the generator.Ranges and increments are presented in Figure2-32.

This function has a definite time element and aninverse time element. The definite time pickup valueand definite operating time are normally associatedwith an alarm function. The inverse time element isusually associated with a trip function and has apickup and an operating time defined by an (I

2)2 t =

K, where K is the Time Dial Setting and I2 is the per

unit negative sequence current.

The minimum delay for the inverse time function isfactory set at 12 cycles to avoid nuisance tripping.A maximum time to trip can be set to reduce theoperating times for modest imbalances. An importantfeature that helps protect the generator from damagedue to recurring imbalances is a linear resetcharacteristic. When I

2 decreases below the pickup

value, the trip timer takes the reset time settingfrom its 100% trip level. Figure 2-31, Negative

Sequence Overcurrent Inverse Time Curves,illustrates the inverse time characteristic of thenegative sequence overcurrent function.

Operating times are lower than shown in Figure 2-31when measured current values are greater than 15A (3 A for 1 A rated circuit).

The first task of setting this function is to determinethe capabilities of the associated machine. Asestablished by ANSI standards, the machine limitsare expressed as (I

2)2t = K. The value of K is

established by the machine design and is generallyprovided on test sheets of the machine. The relaycan accommodate any generator size because ofthe wide range of K settings from 1 to 95. Typicalvalues can be found in ANSI C50.13-1977.

The negative sequence pickup range is from 3% to100% of the Nominal Current value input duringsystem setup (see Section 2.1, Configuration).

This protection must not operate for system faultsthat will be cleared by system relaying. This requiresconsideration of line protection, bus differential andbreaker failure backup protections.

The pickup setting is usually quite low (3–5%) and the output ofthis function is usually connected to alarm only.

Time delay should be set high enough to avoid alarms on tran-sients.

The 46 Inverse Time pickup setting should coincide with thecontinuous negative sequence current capability of the generatoroperating at full output.

The maximum trip time is used to reduce the longer trip timesassociated with low to moderate imbalances to a preset time.

Emulates generator cool down time.

The time dial setting corresponds to the K provided by the generatormanufacturer for the specific unit being protected. See Figure 2-31for the negative sequence overcurrent inverse time curves.

46DT PICKUP_______________ %

46DT DELAY_____________ Cycles

46IT PICKUP_______________ %

46IT MAX DELAY_____________ Cycles

46IT RESET TIME____________ Seconds

46IT TIME DIAL________________

Page 95: Generator Relay Protection

M-3425A Instruction Book

2–38

!!!"!!

#!!

$!!

%!!

!!

"!

#!

$!

%!

!"

#

$

%

!&#

!&$

!&%

!& $ ' # " ! %! $! #! "! !! '! %!! (!! $!! '!! #!! "!! !!! !!! %!!! (!!! $!!!

)*'

#'+'!!,

'!%'

!'

%

- ./

0%%1)

- .

NOTE: When the phase current exceeds 3X I nominal, the operating times will be greater than thoseshown.

* 0.24 seconds for 50 Hz units.

Figure 2-31 Negative Sequence Overcurrent Inverse Time Curves

Figure 2-32 Negative Sequence Overcurrent (46) Setpoint Ranges

Page 96: Generator Relay Protection

Application – 2

2–39

49 Stator Overload ProtectionThe Stator Thermal Overload function (49) providesprotection against possible damage during overloadconditions. The characteristic curves are based onIEC-255-8 standard, and represent both cold andhot curves. The function uses the thermal timeconstant of the generator and stator maximumallowable continuous overload current (I

max) in

implementing the inverse time characteristic.

'F%

(

Where: t = time to tripτ = thermal time constantIL = load current

IPL

= pre-load currentImax

= maximum allowed continuous overload current

Selects the time constant, ‘τ’

Selects the maximum allowed continuous overload current.

49#2 Screens are identical to those for 49#1.

Example: If we consider that the generator wasloaded with 80% of its rating power prior to overload,then the current goes up to 2.0 times the maximumcurrent ((I

L/I

max)=2.0). Selecting the curve P=0.8

(see Figure 2-34), we have t/τ=0.1133. If τ=30minutes, then the time delay for this conditionwould be: t = 0.1133 x 30 = 3.3999 minutes.

The 49 function has two elements, one of which canbe used for trip and the other for alarm.

t

Current-Square

tTripped Not Tripped

Imax2

IL2

IL2

IL2

I2PL

I2PL

Figure 2-33 Time Constant, Function 49

49 #1 TIME CONSTANTMin

49#1 MAX OVERLOAD CURRAmps

Page 97: Generator Relay Protection

M-3425A Instruction Book

2–40

$*23

4

('&&('&)('&*('&+

('&,

('&-

Figure 2-34 49 Function Overload Curves

Page 98: Generator Relay Protection

Application – 2

2–41

Figure 2-35 Stator Thermal Protection (49) Setpoint Ranges

Page 99: Generator Relay Protection

M-3425A Instruction Book

2–42

50/50N Instantaneous Overcurrent, Phase andNeutral CircuitsThe Instantaneous Phase (50) and InstantaneousNeutral (50N) overcurrent functions provide fasttripping for high fault currents. The settings of bothfunctions must be set such that they will not pickupfor fault or conditions outside the immediateprotective zone. If the neutral current input isconnected to a step-up transformer’s neutral CT,the 50N function can be used as a breaker flashoverprotection when used in conjunction with externalbreaker failure protection. Ranges and Incrementsare presented in Figures 2-36 and 2-37. The functionautomatically selects fundamental RMS or totalRMS calculation based on the input frequency.When the generator frequency is within 5 Hz fromthe nominal frequency, it uses fundamental RMScalculation. Outside of this range, it uses total RMScalculation, which will provide protection duringoffline down to a frequency of 8 Hz.

For providing off-line protection, one of the elementscan be supervised by a breaker ‘b’ contact, and theelement blocked when the breaker is closed. Thisallows the function to be set sensitively (below fullload current).

The relay current (IR) is equal to the primary current (Ip) dividedby the appropriate CT ratio. These screens are repeated for 50#2element.

50#1 PICKUPAmps

50#1 DELAYCycles

50N PICKUPAmps

50N DELAYCycles

Page 100: Generator Relay Protection

Application – 2

2–43

Figure 2-36 Instantaneous Overcurrent (50) Setpoint Ranges

Figure 2-37 Instantaneous Neutral Overcurrent (50N) Setpoint Ranges

Page 101: Generator Relay Protection

M-3425A Instruction Book

2–44

Implementation of the generator breaker failurefunction is illustrated in Figure 2-38. The breakerfailure timer will be started whenever any one of thedesignated output contacts or the externalprogrammed breaker failure initiate status input areoperated. The timer continues to time if any one ofthe phase currents are above the 50BF-Ph pickupsetting or if the 52b contact indicates the breaker isstill closed; otherwise, the timer is reset.

Since current in the generator high side CT whichenergizes the 50BF protection (I

A, I

B, I

C) might not

extinguish concurrently with the breaker opening forfaults between the CT location and the generatorbreaker, a possible area of mis-operation exists.Usually the risk of faults in this limited area is smallenough to be ignored but should be considered.

50BF-Neutral Element: This instantaneousovercurrent relay is energized from the generatorneutral CT (See Figure 2-5, One-Line FunctionalDiagram). This function is internally in series with abreaker “b” contact (IN1) to provide logic for thebreaker flashover protection (see Figure 2-38).

HV Breaker Failure (limited) The breaker failurefunction may be used for a unit breaker rather thana generator breaker. It is limited in that it has nofault detector associated with the unit breaker. Outputcontact operation would occur if any of the initiatecontacts close and the 52b contact indicated aclosed breaker after the set time delay.

This operation is chosen by disabling the neutralelement, disabling the phase element, anddesignating initiating inputs and outputs and a timedelay setting.

50BF Generator Breaker Failure/HV BreakerFlashoverThe Generator Breaker Failure/HV Breaker Flashoverfunction (50BF) is applicable when a generatorbreaker is present and line side generator CTs arebeing used. The 50BF-Ph phase detector element(if enabled) is used for breaker failure and the50BF-N (if enabled) provides breaker flashoverprotection by providing an additional breaker failureinitiate which is only active when the breaker isopen. For high impedance grounded applications,the 50BF-N function is inapplicable and must bedisabled. Ranges and increments are presented inFigure 2-39.

50BF-Ph Generator Breaker Failure: When theM-3425A Generator Protection Relay detects aninternal fault or an abnormal operating condition, itcloses an output contact to trip the generator breakeror the unit HV breaker. When a generator breaker isused, protection is available for the instance whereit fails to clear the fault or abnormal condition. Suchgenerator breaker failure protection output contactsmust be connected to trip the additional necessarybreakers to isolate the generator from the system.

The breaker-failure condition is usually detected bythe continued presence of current in any one ormore of the phases after a trip has been sent to thebreaker. However, the current detector (50BF-Ph)may not always give the correct status of thebreaker, especially for generator breakers. This isbecause faults and abnormal operating conditionssuch as ground faults, overexcitation, over/underfrequency, and reverse power may not produceenough current to operate the current detectors. Forthis reason, the breaker status input 52b contactmust be used, in addition to the 50BF-Ph, to provideadequate breaker status indication.

>)1

)4$16

>><>12

!"#$%&

.(+()

)+()

!"#

$%&

()1

'()$*'

+,-../!#0!#1+"#- #2

>><>1+

Figure 2-38 Breaker Failure Logic Diagram

Page 102: Generator Relay Protection

Application – 2

2–45

50BF PHASE ELEMENTdisable enable

50BF PICKUP PHASEAmps

50BF NEUTRAL ELEMENTdisable enable

50BF PICKUP NEUTRALAmps

50BF INPUT INITIATE i6 i5 i4 i3 i2 i1

50BF OUTPUT INITIATEo8 o7 o6 o5 o4 o3 o2 o1

50BF DELAYCycles

If generator breaker failure function is used in this application,ENABLE here.

Set phase pickup amps.

If the breaker flashover protection is to be used with the generatorbreaker failure function of the relay, set ENABLE (enable phaseelement also for this application.)

Set the neutral pickup amps.

Designate the status inputs which will initiate the breaker failuretimer. Inputs IN7–IN14 must be set using IPScom®.

Designate the outputs that will initiate the breaker failure timer.Outputs OUT9–OUT23 must be set using IPScom.

For generator breaker failure protection, the time delay should beset to allow for breaker operating time plus margin.

Figure 2-39 Breaker Failure (50BF) Setpoint Ranges

Page 103: Generator Relay Protection

M-3425A Instruction Book

2–46

NOTE: When 50DT function is used for split-phase differential, 50BF, 87 and 87GDfunctions must be disabled.

Refer to Section 2.1, Configuration, Relay SystemSetup for a description of the 50DT Split-PhaseOperate setting, and Section 2.2, System Diagrams.

In some cases, the generators may be run with afaulted turn shorted until the generator winding isrepaired. To prevent mis-operation under theseconditions, the pickup setting of the faulted phaseshould be set higher than the other phases. Toaccommodate this function, individual pickupsettings are available for each phase. Ranges andincrements are presented in Figure 2-40

50DT Definite Time Overcurrent (for split-phasedifferential)The Definite Time Overcurrent (50DT) function canbe applied in two different configurations based onthe CT connections. When CT configuration shownin Figure 2-5, One Line Functional Diagram is used,the 50DT function is used as a definite time phaseovercurrent function to provide protection for externaland internal faults in the generator. When the CTsare connected to measure the split phase differentialcurrent (shown in Figure 2-6, Alternative One LineFunctional Diagram), the 50DT function can beused as a split-phase differential relay.

Figure 2-40 Definite Time Overcurrent (50DT) Setpoint Ranges

50DT #1 PICKUP PHASE A______________ Amps

50DT #1 PICKUP PHASE B______________ Amps

50DT #1 PICKUP PHASE C______________ Amps

50DT #1 DELAY_____________ Cycles

50DT #2 screens are identical to 50DT #1.

Page 104: Generator Relay Protection

Application – 2

2–47

50/27 Inadvertent EnergizingThe Inadvertent Energizing function (50/27) of therelay is an overcurrent function supervised bygenerator terminal bus voltage. Inadvertent oraccidental energizing of off-line generators hasoccurred frequently enough to warrant the use ofdedicated protection logic to detect this condition.Operating errors, breaker flashovers, control circuitmalfunctions or a combination of these causeshave resulted in generators being accidentallyenergized while off-line. The problem is particularlyprevalent on large generators connected through ahigh voltage disconnect switch to either a ring busor breaker-and-a-half bus configuration. When agenerator is accidentally energized from the powersystem, it will accelerate like an induction motor.

Typical pickup setting is 0.5 amps. No coordination is required withother protection since this function is only operational when thegenerator is off-line.

The purpose of the undervoltage detector is to determine whetherthe unit is connected to the system. The voltage level during thisaccidental energization depends on the system strength. Typicalsetting is 50%–70% of rated voltage (in some cases, it may be setas low as 20%.)

The pickup time delay is the time for the undervoltage unit tooperate to arm the protection. It must coordinate with other protectionfor conditions which cause low voltages (typically longer than 21and 51V time delay settings.)

The dropout time delay is the time for the unit to operate to disarmthe protection when the voltage is increased above the pickupvalue or the generator is brought on-line.

50/27 PICKUP______________ Amps

50/27 VOLTAGE CONTROL_____________ Volts

50/27 PICKUP DELAY_____________ Cycles

50/27 DROPOUT DELAY_____________ Cycles

While the machine is accelerating, high currentsinduced into the rotor can cause significant damagein a matter of seconds. Voltage supervisedovercurrent logic is designed to provide thisprotection. (See Figure 2-41, Inadvertent EnergizingFunction Logic Diagram)

An undervoltage element (all three phase voltagesmust be below pickup) with adjustable pickup anddropout time delay supervises instantaneousovercurrent tripping. The undervoltage detectorsautomatically arm the overcurrent tripping when thegenerator is taken off-line. This undervoltage detectorwill disable or disarm the overcurrent operationwhen the machine is put back in service. Rangesand increments are presented in Figure 2-42.

Page 105: Generator Relay Protection

M-3425A Instruction Book

2–48

!

"#

$%!&'

Figure 2-41 Inadvertent Energizing Function Logic Diagram

Figure 2-42 Inadvertent Energizing (50/27) Setpoint Ranges

Page 106: Generator Relay Protection

Application – 2

2–49

51N Inverse Time Neutral OvercurrentThe Inverse Time Neutral Overcurrent function (51N)provides protection against ground faults. Since nozero sequence or ground current is usually presentduring normal operation, this function can be set forgreater sensitivity than the phase overcurrentprotection. If the 51N and 50N functions are notused at the generator neutral, they can be used todetect system ground faults by being energized bythe step-up transformer neutral CTs. Ranges andincrements are presented in Figure 2-43.

The curves available for use are shown in AppendixD, Inverse Time Curves. They cover a range from1.5 to 20 times the pickup setting. An additional one

Figure 2-43 Inverse Time Neutral Overcurrent (51N) Setpoint Ranges

The relay current (IR) is equal to the primary current (I

P) divided by

the appropriate CT ratio. IR = IP ÷ CT ratio

Select one of the time curves shown in Appendix D, Inverse TimeCurves. The appropriate curve in the selected family is designatedhere.

Appropriate Time Dial for coordination with “downstream” relayprotection chosen from the time curve above.

51N PICKUP______________ Amps

51N CURVEbedef beinv bevinv

51N TIME DIAL________________

cycle time delay should be added to these curves inorder to obtain the relay operating time. Inversetime curves saturate beyond 20 times pickup. Forcurrents in excess of 20 times pickup, operatingtimes are fixed at the 20 times pickup level.

The function automatically selects fundamental RMSor total RMS calculation based on the inputfrequency. When the generator frequency is within

5 Hz from the nominal frequency, it usesfundamental RMS calculation. Outside of this range,it uses total RMS calculation, which will provideprotection during offline down to a frequency of 8Hz.

Page 107: Generator Relay Protection

M-3425A Instruction Book

2–50

The inverse time overcurrent function can be voltagecontrolled (VC), voltage restrained (VR), or neither.For voltage-controlled operation, the function is notactive unless the voltage is below the voltage controlsetpoint. This philosophy is used to confirm that theovercurrent is due to system fault. When applied,most users will set voltage control limits in therange of 0.7 to 0.9 per unit RMS voltage. Whenvoltage restraint is selected (See Figure 2-44,Voltage Restraint (51VR) Characteristic), the pickupsetting is continuously modified in proportion to thecollapsing terminal voltage. The voltage restraintfunction is well-suited to small generators withrelatively short time constants.

NOTE: The 51V function should be blocked byfuse loss if in the voltage control modeonly. Fuse loss blocking is not desirablefor voltage restraint mode because thepickup is automatically held at 100%pickup during fuse loss conditions, andoperation will continue as normal.

The internally derived voltage used to realize thevoltage control or restraint feature depends on theconfigured VT configuration and the Delta-YTransform setting (see Section 2.1, Configuration,Relay System Setup). Table 2-4, Delta/WyeTransformer Voltage-Current Pairs describes thecalculation for the various system VT configurations.

51V Inverse Time Phase Overcurrent withVoltage Control/RestraintTime-overcurrent relays, one per phase, are used totrip circuits selectively and to time-coordinate withother up- or downstream relays. For this function,eight complete series of inverse time trippingcharacteristics are included. The same descriptionsand nomenclature which are traditionally used withelectromechanical relays are used in the relay. Thus,user may choose from four BECO curves (BEDEF,BEINV, BEVINV, and BEEINV), four IEC curves(IECI, IECVI, IECEI, and IECLT), and three IEEEcurves (MINV, VINV, EINV.) Within each family, theoperator selects time dial setting and pickup (tap)setting, just as with electromechanical relays. Rangesand increments are presented in Figure 2-45.

The curves available for use are shown in AppendixD, Inverse Time Curves. They cover a range from1.5 to 20 times the pickup setting. An additional onecycle time delay should be added to these curves inorder to obtain the relay operating time. Inversetime curves saturate beyond 20 times pickup. Forcurrents in excess of 20 times pickup, operatingtimes are fixed at the 20 time pickup level. Theparticular settings will be made by information fromshort-circuit fault studies and knowledge of thecoordination requirements with other devices in thesystem that respond to time overcurrent.

51V is a true three-phase function, in that the relayincorporates separate integrating timers on eachphase.

The pickup of the 51V is set in relay amps.(Relay amps = primary amps ÷ CT ratio)

Selects one of the time curves as shown in Appendix D, InverseTime Curves. The appropriate curve in the selected family ofcurves is designated here.

Disable if neither voltage control nor voltage restraint is desired. Ifvoltage restraint is designated, the tap setting is modified asshown in Figure 2-43. If voltage control is designated, the 51V willonly operate when the voltage is less than the 51V voltage controlsetting specified below. When applied, the voltage control is usuallyset in the range of 70% to 90% of the nominal voltage.

51V PICKUPAmps

51V CURVEbedef beinv bevinv

51V TIME DIAL________________

51V VOLTAGE CONTROLdisable V_CNTL v_rstrnt

51V VOLTAGE CONTROLVolts

Page 108: Generator Relay Protection

Application – 2

2–51

50

25 50 75 100

75

25

Input Voltage (% of rated voltage)0

100

Tap Setting as %of Tap Setting atRated Voltage

Figure 2-44 Voltage Restraint (51VR) Characteristic

Generator Directly Connected Generator Connected ThroughDelta AB/Wye or Delta AC/Wye Transformer

CurrentVoltage Control or Restraint

CurrentVoltage Control or Restraint

L-G L-L or L-G to L-L L-G L-L or L-G to L-L

Ia (VA VC)/S3 VAB Ia VA (VAB VCA)/S3

Ib (VB VA)/S3 VBC Ib VB (VBC VAB)/S3

Ic (VC VB)/S3 VCA Ic VC (VCA VBC)/S3

Table 2-4 Delta/Wye Transformer Voltage-Current Pairs

Figure 2-45 Inverse Time Overcurrent with VoltageControl/Voltage Restraint (51VC/VR) Setpoint Ranges

Page 109: Generator Relay Protection

M-3425A Instruction Book

2–52

59 Phase OvervoltageThe Phase Overvoltage function (59) may be usedto provide overvoltage protection for the generator.The relay provides overvoltage protection functionswith three voltage levels and three definite-timesetpoints, any one or more of which can beprogrammed to trip the unit or send an alarm. Thisis a true 3-phase function in that each phase has anindependent timing element.

The 59 function can be programmed to use phasevoltage (any one of the three phases) or positivesequence voltage as input.

Positive and negative sequence voltages arecalculated in terms of line-to-line voltage when Lineto Line is selected for V.T. Configuration.

V1 = 1/3 (V

ab +aV

bc + a2V

ca)

V2 = 1/3 (V

ab +a2V

bc + aV

ca)

Magnitude measurement depends on the 59/27Magnitude Select setting (See Section 2.1,Configuration, Relay System Setup). When the RMSoption is selected, the magnitude calculation isaccurate over a wide frequency range (10 to 80 Hz)and the accuracy of the time delay is +20 cycles. IfDFT option is selected, the magnitude calculationis accurate near 50 or 60 Hz, and the timer accuracyis K1 cycle. When the input voltage select is set topositive sequence voltage, the 59 functions usesDFT to measure the positive sequence voltage,irrespective of DFT/RMS selection. Ranges andincrements are presented in Figure 2-46.

Figure 2-46 Phase Overvoltage (59) Setpoint Ranges

Generator capability is generally 105% of rated voltage.59 #2 and 59 #3 screens are identical to 59 #1.

59 #1 INPUT VOLTAGE SEL.phase_volt pos_seq_volt

59 #1 PICKUP_____________ Volts

59 #1 DELAY_____________ Cycles

Page 110: Generator Relay Protection

Application – 2

2–53

59D Third Harmonic Voltage Differential (Ratio)This scheme, when used in conjunction with 59Nfunction may provide 100% Stator Ground faultprotection.

Figure 2-47 illustrates a third harmonic voltagedifferential scheme. This scheme compares thethird harmonic voltage appearing at the neutral tothat which appears at the generator terminals. Theratio of these third harmonic voltages is relativelyconstant for all load conditions. A stator phase-to-ground fault will disrupt this balance, causingoperation of the differential relay (see Figure 2-20).The generator terminal voltage (Line Side Voltage)can be selected as 3V

0 (Calculated by the relay

from VA, V

B and V

C) or V

X (broken delta VT input

connected at the VX input.) Positive sequence

undervoltage blocking will prevent the function frommisoperating when the generator is offline (theterminal voltage is below the set value).

59D RATIO________________

The ratio (or third harmonic) voltage measured at the generatorterminals to the third harmonic voltage measured at neutral.

The 59D Ratio Pickup Setting can be calculated using fieldmeasurement of Third Harmonic Voltages as follows:

This setting is typically enabled.

Where:

is the maximum measured Ratio of the Third Harmonic Voltages atvarious loading conditions of the generator.

Selection of VX will give better accuracy and sensitivity than 3V

0. If

3V0 is selected, VT configuration must be set to Line-Ground. If thenominal third harmonic voltage is <1 V, 3V0 line side voltageselection is not recommended, because noise in the 3V

0 and V

Ncan cause 59D misoperation.

59D POS SEQ VOLT BLKdisable ENABLE

59D POS SEQ VOLT BLK_____________ Volts

59D DELAY_____________ Cycles

59D Ratio PickupV

3XM

V3NM

3VOM

V3NM

OR( () )= 1.5 x

59D LINE SIDE VOLTAGE3v0 VX

V3XM

V3NM

3VOM

V3NM

OR( ( ))

Page 111: Generator Relay Protection

M-3425A Instruction Book

2–54

V3N V3X

M-3425A

Figure 2-48 Third Harmonic Voltage Differential (59D) Setpoint Ranges

The ratioV

3X

V3N

3Vo

V3N

PickupOR >( () )Where: V

3x is the Third Harmonic Triple Zero Sequence voltage measured at the generator

terminals.

V3N is the Third Harmonic voltage measure at the neutral.

Figure 2-47 Third Harmonic Voltage Differential (Ratio) Schemefor Generator Ground Fault Protection

Page 112: Generator Relay Protection

Application – 2

2–55

59N Overvoltage, Neutral Circuit or ZeroSequenceThe Neutral Overvoltage function (59N) providesstator ground fault protection for high impedancegrounded generators. The 59N function can provideground fault protection for 90–95% of the statorwinding (measured from the terminal end).

Figure 2-49 Overvoltage, Neutral Circuit or Zero Sequence (59N) Setpoint Ranges

59N #1 PICKUPVolts

59N #1 DELAYCycles

59N 20HZ INJECTION MODEdisable ENABLE

59N #2 and 59N #3 screensare identical to 59N #1.

With typical grounding transformer ratios and a typical minimum setting of5 volts, this protection is capable of detecting ground faults in about 95% ofthe generator stator winding from the terminal end.

If grounded-wye/grounded-wye VTs are connected at the machine terminals,the voltage relay must be time coordinated with VT fuses for faults on thetransformer secondary winding. If relay time delay for coordination is notacceptable, the coordination problem can be alleviated by grounding one of thesecondary phase conductors instead of the secondary neutral. When thistechnique is used, the coordination problem still exists for ground faults on thesecondary neutral conductor. Thus, its usefulness is limited to those applicationswhere the exposure to ground faults on the secondary neutral is small.

Since system ground faults can induce zero sequence voltages at thegenerator due to transformer capacitance coupling, this relay mustcoordinate with the system ground fault relaying. It is possible to set59N#1, 59N#2, and 59N#3 to coordinate with the PT secondary fuses, andalso coordinate with worst case capacitive coupling interference voltagefrom system ground faults (high side of the GSU).

For applications where the M-3425A relay (where the 64S function ispurchased or not) is used with 100% Stator Ground protection with 20 Hzinjection schemes, the 59N 20 Hz injection mode must be enabled in orderto calculate the voltage magnitude accurately for the 59N function, due tothe 20 Hz injection voltage. The time delay accuracy of the function is –1 to+5 cycles when the 20 Hz injection mode is enabled.

The 59N function provides three setpoints, andresponds only to the fundamental frequencycomponent, rejecting all other harmonic components.Ranges and increments are presented in Figure 2-50.

Page 113: Generator Relay Protection

M-3425A Instruction Book

2–56

59X Multipurpose Overvoltage (Turn-to-TurnStator Fault Protection or Bus GroundProtection)For generators where the stator-winding configurationdoes not allow the application of split-phasedifferential, a neutral voltage method can be used todetect turn-to-turn stator winding faults. Figure 2-50illustrates this method. Three VTs are connected inwye and the primary ground lead is tied to thegenerator neutral. The secondary is connected in a“broken delta” with an overvoltage relay connectedacross its open delta to measure 3V

0 voltage. In

High Impedance grounded generators, connectingthe primary ground lead to the generator neutral,makes this element insensitive to stator groundfaults. The relay will, however, operate for turn-to-turn faults, which increase the 3V

0 voltage above

low normal levels. Installation requires the cablefrom the neutral of the VT to generator neutral beinsulated for the system line-to-ground voltage andthe relay to be tuned to fundamental (60/50 Hz)frequency components of the voltage since somethird-harmonic frequency component of the voltagewill be present across the broken delta VT input.

Alternatively, this function can be used to detectbus ground faults, when connected as shown inFigure 2-10.

When used for Turn-to-Turn fault protection the pickup should beset above the normal zero sequence voltage level. Typically thepickup is set to 5 V.

When used for Bus Ground protection it is again set above thenormal zero sequence voltage seen at the bus. Typical setting isbetween 10 and 20 Volts to provide sensitive protection.

The Time Delay for Turn-to-Turn faults should be set to approximately5 cycles. For bus ground fault protection application the time delayshould coordinate with other ground fault relaying and VT fuses.

59X #2 screens are identical to 59X #1.

59X #1 PICKUP_____________ Volts

59X #1 DELAY_____________ Cycles

Page 114: Generator Relay Protection

Application – 2

2–57

59X

R

3V0

VT

R

GENERATOR

See Note Below

NOTE: Installation requires the cable from the neutral of the VT to generator neutral be insulated for thesystem line-to-ground voltage.

Figure 2-50 Turn-to-Turn Stator Winding Fault Protection

Figure 2-51 (59X) Multi-purpose Overvoltage Setpoint Ranges

Page 115: Generator Relay Protection

M-3425A Instruction Book

2–58

A frequency check element is included in the fuseloss detection logic to avoid erroneous alarms whenthe generator is in a start up condition. For a 50Hzsystem, the 60FL alarm will be inhibited if themeasured frequency is greater than 55.12 Hz F

U or

less than 44.88 Hz FL. For a 60 Hz system, the 60FL

alarm will be inhibited if the measured frequency isgreater than 65.12 Hz F

U or less than 54.88 Hz F

L.

The Frequency Band Detector does not inhibit the60FL three-phase loss of potential logic.

External Fuse-Loss FunctionFor the specific application where the precedinglogic cannot be considered reliable (such as whencurrent inputs to the relay are not connected, orsustained positive sequence current during faultconditions is minimal), an external fuse failurefunction can be used as an input to the relay. Theexternal 60 FL Function contact is connected acrossany control/status input. The relay protectionfunctions are then blocked by an assertion of thecontrol/status input (INx), as a blocking function ineach function’s respective setting screen.

60FL VT Fuse Loss Alarm FunctionThe 60FL alarm function is enabled by the internallogic by selecting the “FL” option in the 60 FLfunction setup screen. It is enable by the externallogic by selecting the appropriate control/statusinput (INx) in the 60FL function setup screen.

A timer associated with the fuse loss alarm logic isavailable. This timer is to assure proper coordinationfor conditions that may appear as a fuse loss, suchas secondary VT circuit faults that will be clearedby local low voltage circuit action (fuses or circuitbreakers). Ranges and increments are presented inFigure 2-53.

60FL VT Fuse LossSome functions may operate inadvertently when aVT fuse is blown or an event causes a loss of one,two, or all three potentials to the relay. Provisionsare incorporated for both internal and externalpotential loss detection and blocking of user definedfunctions. The logic scheme and options areillustrated in Figure 2-52.

Internal Fuse Loss Detection LogicThe internal logic scheme available will detect aloss of one, two, and all three potentials.

For the loss of one or two potentials, positive andnegative sequence quantities are compared. Thepresence of negative sequence voltage in the absenceof negative sequence current is considered to be afuse loss condition. An additional supervising conditionincludes a minimum positive sequence voltage toassure voltage is being applied to the relay.

For the loss of all three phase potentials, acomparison of the three phase voltages is made tothe three phase currents. If all three potentials areunder 0.05 V

nom, and all three currents are below

1.25 Inom

combined with I1 > 0.33A, a three phase

potential loss is declared. A seal in circuit is providedto ensure a three phase fuse loss condition is notdeclared during a three phase fault if the faultcurrent decays below the 1.25 Inom pickup setting.

Protection functions in the relay may be blocked byan assertion of the fuse failure logic (FL), in eachfunction’s respective setting screen. Typicalfunctions to block on a loss of potential event are21, 27, 32, 40, 51V (for Voltage Control only), 67,67N, 78 and 81.

The 60FL function does not have to be enabled inorder to use the FL as a blocking input in the relayconfiguration menu.

The initiating control/status inputs are user-designated. The closingof any of the externally connected contacts (across these in-puts) will start the associated time delay to the 60FL functionoperation. In order to use internal fuse loss logic for 60FL func-tion, “FL” must be checked. Externally initiated fuse loss detec-tion may be input to other status inputs. Inputs IN7–IN14 mustbe set using IPScom®.

The time delay is set to coordinate for conditions which mayappear as a fuse loss but will be corrected by other protection(such as a secondary VT circuit fault which will be cleared bylocal low voltage circuit action). This delay does not affect inter-nal FL blocking option.

60FL INPUT INITIATEFL i6 i5 i4 i3 i2 i1

60FL 3 PHASE DETECTdisable enable

60FL DELAYCycles

Page 116: Generator Relay Protection

Application – 2

2–59

V1 >

12.8

V

V2 >

0.33

V1

I 2 >

0.16

7 I 1

I 1 >

0.33

A

I A >

1.2

5 I N

I B >

1.2

5 I N

I C >

1.2

5 I N

VA

< 0

.05

VN

VB

< 0

.05

VN

VC

< 0

.05

VN

Softw

are

Sele

ctEn

able

/Dis

able

3 Ph

ase

Fuse

Loss

Det

ectio

n

Ena

ble

Dis

able

OR

OR

AN

D

AN

D

AN

D

OR

AN

D

AN

D

F <

F U

F >

F L

AN

D

AN

D

Inte

rnal

60F

L Lo

gic:

3 P

hase

Los

s of

Pot

entia

l

Inte

rnal

60F

L Lo

gic:

1 &

2 P

hase

Los

s of

Pot

entia

l

Freq

uenc

y C

heck

ing

I 1Ve

rifie

s O

n-Li

ne c

ondi

tion

V A,B

,CIn

dica

tion

of 3

-pha

se lo

ss o

f pot

entia

lI A

,B,C

Prev

ents

ope

ratio

n du

ring

faul

ts

Seal

-in c

ircui

t ens

ures

logi

c do

esn'

t pro

duce

an o

utpu

t dur

ing

3-ph

ase

faul

t whe

n cu

rren

tde

cays

bel

ow 1

.25

I N

(.067

A)*

* Val

ues

in p

aren

thes

es a

pply

to a

1 A

CT

seco

ndar

y ra

ting.

Ext

erna

l "FL

"Fu

nctio

nIN

xEx

tern

al F

use

Loss

Fun

ctio

n

T Del

ay

60FL

Ala

rm F

unct

ion

initi

ate

by in

tern

al "

FL"

orSt

atus

Inpu

t Con

tact

INx

Prot

ectio

n Fu

nctio

n B

lock

Sign

al b

y IN

x fr

om E

xter

nal F

L

60FL

Ala

rm S

igna

l

Prot

ectio

n Fu

nctio

n B

lock

Sign

al b

y In

tern

al F

L Lo

gic

FL

V 1Ve

rifie

s VT

vol

tage

is a

pplie

d.V 2

Prov

ides

indi

catio

n of

blo

wn

fuse

.I 2

Prev

ents

ope

ratio

n du

ring

phas

e-ph

ase

faul

ts.

I 1Pr

even

ts o

utpu

t con

tact

s fr

om c

hatte

ring

whe

re

a fu

se b

low

s du

ring

no lo

ad o

pera

tion.

OR

Figure 2-52 Fuse Loss (60FL) Function Logic

Page 117: Generator Relay Protection

M-3425A Instruction Book

2–60

Figure 2-53 Fuse Loss (60FL) Setpoint Ranges

Page 118: Generator Relay Protection

Application – 2

2–61

64B/F Field Ground Protection64F Field Ground DetectionTypical connections for Field Ground Protectionapplications (including hydro turbine-generator andbrushless generators) is given in Figure 2-54. Thisfunction requires the connection of an externalcoupler (M-3921). To improve accuracy andminimize the effects of stray capacitance, theM-3921 Field Ground Coupler should be mountedclose to the exciter. Connections from the couplerto the relay should use low capacitance shieldedcable, and be as short as possible. Cable shieldshould be terminated at the relay end to the RelayGround Stud (See Figure 5-9, External Connections).If cabling between the coupler and relay exceeds100 feet, provisions should be made for in circuitcalibration to nullify the effects of cablingcapacitance. See Section 6.4, Auto Calibration, forcalibration procedure.

The Field Ground function provides detection ofinsulation breakdown between the excitation fieldwinding and the ground. There are two pickup andtime delay settings, and one adjustable injectionfrequency setting for the 64F function. The adjustablefrequency is provided to compensate for the amountof capacitance across the field winding and theground so that the function accuracy is improved.The minimum time delay should be set greater than(2/IF + 1) seconds. Where IF = Injection frequency.Ranges and increments are presented in Figure 2-55.

64F #1 PICKUPkOhm

64F #1 DELAYCycles

64F #2 PICKUPkOhm

64F #2 DELAYCycles

Table 2-5 gives typical frequency settings based onthe rotor capacitance. The rotor capacitance can bemeasured with a capacitance meter by connectingthe meter across the field winding to ground.

Factors Affecting 64F PerformanceSome excitation systems include shaft voltagesuppressors which include capacitors that areinstalled between the +/- field and ground. The effectof these capacitors is given by the following equation:

R JJJJJ___1___ (2π IF C)

where:R = Parallel winding-ground resitance

IF = Injection frequency setting

C = Capacitance value

To minimize this effect the following my beimplemented:

• The injection frequency setting can bereduced, however accuracy decreasesas a result.

• With the concurrence of the excitermanufacturer, surge capacitors rated ata lower value may be installed.

This setting should not exceed 80% of the ungrounded resitance valueto prevent nuisance tripping. Typical setting for the 64F #1 pickupelement for alarming is 20 Kohms.

Typical delay setting for tripping is 800 cycles.

Typical setting for 64F #2 pickup element for tripping is 5 Kohms.

Typical delay setting for alarming is 180 cycles.

Page 119: Generator Relay Protection

M-3425A Instruction Book

2–62

PROCESSOR

PROTECTION RELAYM-3425A

SquarewaveGenerator

SignalMeasurement and

Processing

Field GroundDetection

37

35

36

Relay Ground Stud

CouplingNetworkM-3921

TB5

TB4

TB1

Vf

Shield

TB3

TB2

TB1

Vout

Rear TerminalBlock Pin No.

Gen.Rotor

ExcitationSystem

Rf.CfShaft

GroundBrush

Brushes

Ground/Generator Frame

Typical Field Ground Protection

TB3

TB2

TB1

Gen.Rotor

Rf.CfShaft

GroundBrush

MeasurementBrush

Ground/Generator Frame

Jumper TB2 to TB3 ifonly one brush is used

Brushless Generator Application64F Application for Brushless Generators

The 64F Function can be implemented on brushlessgenerators that employ a "measurement" brush (seeFigure 2-54 Detail C) to verify the integrity of field. In thisconfiguration generally only one field polarity is available.Therefore, a suitably sized jumper must be installed fromTB2 to TB3 (Coupling Network box M-2931) and then tothe positive or negative field lead.

In some configurations the measurement brush iscontinuously applied. In others the measurement brush isapplied periodically. In configurations that automatically liftthe measurement brush, the 64B Function must beblocked by an input to the relay to prevent an alarm whenthe measurement brush is lifted. If the 64B Function is notdesired, then the 64B Function should be disabled.

The 64F Function can not be used on brushlessgenerators utilizing LED coupling.

Detail A

TB3

TB2

TB1

Gen.Rotor

ExcitationSystem

Rf.Cf

Water providesalternate

ground path.

Brushes

Ground/Generator Frame

Francis or Kaplan Turbine-GeneratorApplication

64F Application for Hydro Turbine-Generators

The application of the 64F Function requires a groundreturn path, either through a shaft ground brush (Figure2-54 Detail A) or though an alternate ground path (i.e.water for some hydro machines.)

Hydro Turbine-Generator unit shafts that extend into thewater with no electrical isolation between the turbine shaftand the generator shaft can use the water as the alternateground path (see Figure 2-54 Detail B). In this application,the water provides the alternate ground path and a shaftgrounding brush is not required. Francis and KaplanTurbine Generators usually meet this applicationrequirement. If the unit can experience a low watercondition, the low water may not provide a reliable groundreturn. For this condition, a shaft ground brush may berequired.

A shaft ground brush must be utilized for the 64F Functionon Pelton Hydro Turbine-Generator applications.

Detail B

Detail C

Figure 2-54 M-3921 Field Ground Coupler

Page 120: Generator Relay Protection

Application – 2

2–63

64B Brush Lift-Off DetectionBrush Lift-Off Detection (64B) provides detection ofopen brushes of the rotor shaft. This function worksin conjunction with the 64F Field Ground Detectionfunction, and requires the M-3921 Field GroundCoupler.

88888 WARNING: Machine should be off-line andfield excitation should be off during thecapacitance measurement.

NOTE: Field breaker should be closed for thecapacitance measurements.

otgnidniWdleiFecnaticapaCdnuorG gnitteSycneuqerFlacipyT

1 2ot μF zH25.0

3ot2 μF zH94.0

4ot3 μF zH64.0

5ot4 μF zH34.0

5 6ot μF zH93.0

7ot6 μF zH53.0

8ot7 μF zH23.0

9ot8 μF zH03.0

01ot9 μF zH82.0

01> μF zH62.0

Table 2-5 Typical Frequency Settings

Figure 2-55 Field Ground Protection (64B/F) Setpoint Ranges

Page 121: Generator Relay Protection

M-3425A Instruction Book

2–64

When 64B operates, indicating open brushconditions, the 64F Function cannot detect a fieldground. For most generators, when the brushes ofthe rotor shaft are lifted, the capacitance across thefield winding and the ground significantly reduces toless than 0.15 μF. The 64B Function analyzes thiscapacitance-related signal, and initiates an outputcontact when it detects an open brush condition.Typically, this output is used to alert operatingpersonnel of an open brush condition. Ranges andincrements are presented in Figure 2-58. The typicalpickup setting is listed in Table 2-6, Typical BrushLift-Off Pickup Settings.

In order to assure correct setting, it is recommendedthat the actual operating value be predeterminedduring the final stage of the relay installation. Byintroducing a brush-open condition, the actual valuecan be easily obtained from the relay. The followingprocedure can be used to obtain the actual operatingvalue of the 64B during an open brush condition:

88888 WARNING: Machine should be off-line andfield excitation should be off during thecapacitance measurement.

NOTE: Field breaker should be closed for thecapacitance measurements.

64B PICKUP_______________ mV

64B DELAY_____________ cycles

64B/F FREQUENCY_______________ Hz

1. After installation has been completed,determine the rotor capacitance, asoutlined for the 64F function.

2. With the machine still off-line, applypower to the relay and set the 64B/Foperating frequency in accordance withthe value listed in Table 2-5, TypicalFrequency Settings.

3. Introduce a brush-open condition bydisconnecting the rotor brushes or liftingthe brushes from their ground. Observethe 64B voltage value displayed byIPScom or the relay. The displayed valueis the actual measured operating valueof the 64B function.

4. To ensure correct operation and preventerroneous trips, the Pickup Setting forthe 64B Lift-off condition should be setat 80–90% of the actual operating value.

The 64B/F Frequency is a shared setting common to both the 64Band 64F Functions. If either function is enabled, this setpoint isavailable, and should be set to compensate for the amount ofcapacitance across the field winding and ground, so that themeasurement accuracy is improved.

To minimize measurement errors, the 64B/F frequency shouldbe set according to the amount of capacitance across the fieldwinding and the ground. Table 2-5 includes typical settings of thefrequency for capacitance, ranging from 1 μF to 10 μF.

ecnaticapaCffO-tfiLhsurBtnelaviuqE ffO-tfiLhsurBlacipyTgnitteSpukciP

52.0~50.0 μF Vm0052

Table 2-6 Typical Brush Lift-Off Pickup Setting

Page 122: Generator Relay Protection

Application – 2

2–65

The expected 20 Hz current during no fault conditionis given by:

V20

• N2

INF

=X

CS

Where V20 is the 20 Hz voltage measured acrossthe load resistor RL and X

CS is the capacitive

reactance of the generator stator winding and unittransformer referred to the grounding transformersecondary. N is the turn ratio of the groundedtransformer. The pickup setting should be based onthe required insulation resistance setting. In orderto detect a fault of 5,000 Ohms on the generatorstator, the pickup current should be set at:

)/0#

$###G/-

#!"B

When the generator is operating normally (no groundfault) only a small amount of 20 Hz current will flowas a result of the stator capacitance to ground.When a ground fault occurs anywhere on thegenerator stator windings the 20 Hz current willincrease. The 64S function will issue a trip signalafter a set time delay when the measured 20 Hzcurrent exceeds the pickup current as illustrated inFigure 2-57.

The 64S protection can be blocked by UndervoltageInhibit. If the 20 Hz voltage (nominal 25 V) is lessthan the Undervoltage Inhibit setting (andUndervoltage Inhibit is enabled), the 64S functionwill be blocked. For cases where the Load Resistor(RL) is small, the Undervoltage Inhibit should not beenabled, as the voltage will be small.

The 59N function (90 to 95%) should also be usedin conjunction with 64S protection to provide backup.

CAUTION: Dangerous high voltages may bepresent at the generator terminals if the 20 Hzinjection voltage is not removed when the generatoris taken out of service.

If the 20 Hz injection voltage generator receivespower from the generator terminal voltage, then the20 Hz injection voltage generator will be automaticallyswitched off whenever the generator terminal voltageis not present.

64S 100% Stator Ground Protection by LowFrequency Signal Injection

NOTE: The Stator Ground Protection function(64S) must be selected when theM-3425A is initially ordered.

The 100% stator ground fault protection is providedby injecting an external 20 Hz signal into the neutralof the generator. The protection is provided whenthe machine is on-line as well as off-line (providedthat the 20 Hz generator and relay are powered on.)This scheme requires the following externalcomponents in addition to M-3425A protectionsystem (See Table 2-7 for details):

• 20 Hz Signal-generator• Band-pass filter• 20 Hz Measuring Current Transformer,

400/5 A CT

NOTE: Chapter 5, Installation contains lowfrequency signal injection equipmentinstallation information.

The voltage signal generated by the 20 Hz signal-generator is injected into the secondary of thegenerator neutral grounding transformer through aband-pass filter. The band-pass filter passes the 20Hz signal and rejects out-of-band signals. The outputof the 20 Hz band-pass filter is connected to the V

Ninput of the M-3425A relay through a suitable voltagedivider, that limits the M-3425A to OOOOO 200 V ac (thevoltage generator may be bypassed if the expected50/60 Hz voltage during a phase-to-ground fault ofthe generator is OOOOO 200 V.) The 20Hz current is alsoconnected to the IIIIIN

input of the M-3425A, throughthe 20Hz current transformer.

64S PICKUPmAmps

64S VOLT INHIBITdisable ENABLE

64S VOLT INHIBITVolts

64S DELAYCycles

Page 123: Generator Relay Protection

M-3425A Instruction Book

2–66

RN

1B1

1A1

1B4

1A3 1A4

20 HzBand Pass

Filter

20 HzGenerator

4A1[11]

Bl

Supply VoltageDC AC+VAux VA(L1)

-VAux VB(L2)

VC(L3)

ExternalBlock

DeviceOperative

44 45

M-3425A

52 53

400A5A

L Kl k

Max. 200 V

V N

I N

NeutralGrounding

Transformer

WiringShielded

20 Hz CT400/5 A

59N

High *Voltage

LowVoltage

* For applications with a transformer secondary rating that will result in 50/60 Hz phaseground fault voltages >200 V ac, use the "High Voltage" connection for the 59N Function.

Connection terminals forModel A00/CC shown.Connection terminals forModel A00/DD shown inbrackets [ ].

4A3[12]

1A1[1]

1A2[2]

1A3[3]

2A1[6]

2A3[8]

3A2[7]

3A3[9]

3A1[5]

Figure 2-56 64S Function Component Connection Diagram

20 Hz Signal-Generator

20 Hz Band-pass Filter

20 Hz Measuring Current Transformer400-5 A CT

Siemens7XT33

Siemens7XT34

ITICTWS-60-T50-401

M-0331 2:1 Control Transformer PH150MQMJ

Equipment Description OEM Part No.

430-00426

430-00427

430-00428

430-00318

Surface/Flush MountBECO

Part No.

Table 2-7 Low Frequency Signal Injection Equipment Part Number Cross Reference

Page 124: Generator Relay Protection

Application – 2

2–67

20 Hz Injection Voltage

I20

5 V 10 V 15 V 20 V 25 V 30 V 35 V 40 V

140 %

60 %

TRIP

45 V0 V

64SPickupCurrent

Figure 2-57 64S Function Time Delay Pickup Current Correlation

Figure 2-58 100% Stator Ground Protection (64S) Setpoint Ranges

Page 125: Generator Relay Protection

M-3425A Instruction Book

2–68

calculated using VA, V

B and V

C inputs. The function

provides both definite time and inverse timeelements. The inverse time element provides severalcurves. The curves available for use are shown inAppendix D, Inverse Time Curves. They cover arange from 1.5 to 20 times the pickup setting. Anadditional one cycle time delay should be added tothese curves in order to obtain the relay operatingtime. Inverse time curves saturate beyond 20 timespickup. For currents in excess of 20 times pickup,operating times are fixed at the 20 time pickuplevel.

To obtain maximum sensitivity for fault currents,the directional element is provided with a maximumsensitivity angle adjustment (MSA). This setting iscommon to both the 67NDT and 67NIT elements.The pickup sensitivity of the relay remains constantfor 90° either side of the so-called MaximumSensitivity Angle (MSA). At angles over 90° fromMSA, the relay operation is blocked. Typical MSAsetting for a generator internal ground fault protectoris approximately 150°.

67N Residual Directional OvercurrentThe Residual Directional Overcurrent function (67N)provides protection from ground faults. The 67Nfunction can provide generator ground faultprotection. It can also provide directionaldiscrimination when multiple generators are busedtogether. The 67N Function is subject to the followingconfiguration limitations:

• VX polarization cannot be selected if 25

(Sync) function is enabled.

• 3V0 polarization can only be used with

Line-Ground VT configuration.

• 67N Function is not available if 87GD isenabled.

The 67N Function operates on the residual currenteither from internal calculation (3I

0) using I

A, I

B and

IC or using a residual current input from I

N input of

the relay (this is preferred compared to 3I0). The

relay can be polarized with the neutral voltage (VN),

broken delta voltage connected at VX

input or 3V0

Figure 2-59 Residual Directional Overcurrent (67N) Trip Characteristics

Page 126: Generator Relay Protection

Application – 2

2–69

Pickup value for the 67N element.

Directional discrimination enable. When disabled, this functionwill work like a 50N.

Time Delay setting.

Inverse Time Pickup

Directional discrimination enabled. When disabled, this functionwill operate like 51N.

Select the inverse time curve.

Time dial setting

See Figure 2-60 for Max Sensitivity Angle (MSA) settings.

Select the operating current.

Select the polarization voltage. If 3V0 is selected, VT configu-ration must be set to Line-Ground.

67NDT PICKUP______________ Amps

67NDT DIR ELEMENTdisable ENABLE

67NDT DELAY_____________ Cycles

67NIT PICKUP______________ Amps

67NIT DIR ELEMENTdisable ENABLE

67NIT CURVEbdef binv bvinv beinv

67NIT TIME DIAL________________

67N MAX SENSITIVITY ANGLE____________ Degrees

67N OPERATING CURRENT3I0 in

67N POLARIZING QUANTITY3V0 vn vx

Page 127: Generator Relay Protection

M-3425A Instruction Book

2–70

Figure 2-60 Residual Directional Overcurrent (67N) Setpoint Ranges

Page 128: Generator Relay Protection

Application – 2

2–71

78 Out-of-StepThe Out-of-Step function (78) is used to protect thegenerator from out-of-step or pole slip conditions.This function uses one set of blinders, along with asupervisory MHO element. Ranges and incrementsare presented in Figure 2-63.

The pickup area is restricted to the shaded area inFigure 2-58, Out-of-Step Relay Characteristics, definedby the inner region of the MHO circle, the region to theright of the blinder A and the region to the left of blinderB. For operation of the blinder scheme, the operatingpoint (positive sequence impedance) must originateoutside either blinder A or B, and swing through thepickup area for a time greater than or equal to the timedelay setting and progress to the opposite blinder fromwhere the swing had originated. When this scenariohappens, the tripping logic is complete. The contactwill remain closed for the amount of time set by theseal-in timer delay.

XT

= Transformer Reactance

XS

= System Reactance

Xd’= Transient Reactance of the Generator

Consider, for example, Figure 2-59. If the Out-of-step swing progresses to impedance Z

0(t

0), the

MHO element and the blinder A element will bothpick up. As the swing proceeds and crosses blinderB at Z

1(t

1), blinder B will pick up. When the swing

reaches Z2(t

2), blinder A will drop out. If TRIP ON

MHO EXIT option is disabled and the timer hasexpired (t

2–t

1>time delay), then the trip circuit is

complete. If the TRIP ON MHO EXIT option isenabled and the timer has expired, then for the tripto occur the swing must progress and cross theMHO circle at Z

3(t

3) where the MHO element drops

out. Note the timer is active only in the pickupregion (shaded area). If the TRIP ON MHO EXIToption is enabled, a more favorable tripping angle isachieved, which reduces the breaker tripping duty.The relay can also be set with a Pole Slip Counter.The relay will operate when the number of pole slipsare equal to the setting, provided the Pole SlipReset Time was not expired. Typically, the PoleSlip Counter is set to 1, in which case the Pole SlipReset Time is not applicable.

Typical setting is (1.5XT+2Xd’)

Typical setting is –2Xd’.

Typical setting is (1/2) (Xd’+ XT + XS) tan(Θ–(δ/2)). Typicalvalue for δ is 120°.

Typical setting for Θ is 90°.

The time delay should be set based on the stability study. Inthe absence of such a study, it can be set between 3 and 6cycles.

This setting is typically enabled.

Typical setting is 1 pole slip.

Typical setting is 120 cycles.

78 DIAMETER______________ Ohms

78 OFFSET______________ Ohms

78 BLINDER IMPEDANCE______________ Ohms

78 IMPEDANCE ANGLE____________ Degrees

78 DELAY_____________ Cycles

78 TRIP ON MHO EXITdisable enable

78 POLE SLIP COUNT_____________ slips

78 POLE SLIP RESET TIME_____________ Cycles

Page 129: Generator Relay Protection

M-3425A Instruction Book

2–72

SYSTEM

A B

R

P GN F

HM

MHOELEMENT

ELEMENTS

GEN(X'

d)

TRANS

O

X

BLINDER

C

XT

XS

D

d

'

SWINGLOCUS

1.5 X T

2Xd

Figure 2-62 Out-of-Step Protection Settings

A B

Z3(t3)

Z2(t2)Z1(t1)

Z0(t0)

Figure 2-61 Out-of-Step Relay Characteristics

Page 130: Generator Relay Protection

Application – 2

2–73

Figure 2-63 Out-of-Step (78) Setpoint Ranges

Page 131: Generator Relay Protection

M-3425A Instruction Book

2–74

81 FrequencyThe Frequency function (81) provides eitheroverfrequency or underfrequency protection of thegenerator. It has four independent pickup and timedelay settings. The overfrequency mode isautomatically selected when the frequency setpointis programmed higher than the base frequency (50or 60 Hz), and the underfrequency mode selectedwhen the setpoint is programmed below the basefrequency. Ranges and increments are presented inFigure 2-65.

The steam turbine is usually considered to be morerestrictive than the generator at reduced frequenciesbecause of possible natural mechanical resonancein the many stages of the turbine blades. If thegenerator speed is close to the natural frequency ofany of the blades, there will be an increase invibration. Cumulative damage due to this vibrationcan lead to cracking of the blade structure.

Sample settings of the 81 function are shown inFigure 2-64. The frequency functions are

81 #1 PICKUP_______________ Hz

81 #1 DELAY_____________ Cycles

81 #2 PICKUP_______________ Hz

81 #2 DELAY_____________ Cycles

81 #3 PICKUP_______________ Hz

81 #3 DELAY_____________ Cycles

81 #4 PICKUP_______________ Hz

81 #4 DELAY_____________ Cycles

automatically disabled when the input voltage(positive sequence) is very low (typically between2.5 V and 15 V, based on the frequency.)

The 81 function should be disabled using breakercontact when the unit is offline.

These magnitude and time settings describe a curve(as shown in Figure 2-64, Example of Frequency(81) Trip Characteristics) which is to be coordinatedwith the capability curves of the turbine and generatoras well as the system underfrequency load-sheddingprogram. These capabilities are given by adescription of areas of prohibited operation, restrictedtime operation, and continuous allowable operation.

The underfrequency function is usually connectedto trip the machine whereas the overfrequencyfunction is generally connected to an alarm.

In order to prevent mis–operation during switchingtransients, the time delay should be set to greaterthan five (5) cycles.

Page 132: Generator Relay Protection

Application – 2

2–75

Figure 2-65 Frequency (81) Setpoint Ranges

61.0

60.8

60.6

60.4

60.2

60.0

59.8

59.6

59.4

59.2

59.0

Time (cycles)

81O

ver

Fre

qu

ency

(H

z)81

Un

der

Fre

qu

ency

(H

z)

Trip

Trip

Over FrequencyTime Delay #2

Over FrequencyTime Delay #1

Under FrequencyTime Delay #4

Under FrequencyTime Delay #3

Over FrequencyMagnitude #1

Under FrequencyMagnitude #4

Over FrequencyMagnitude #2

Under FrequencyMagnitude #3

Figure 2-64 Example of Frequency (81) Trip Characteristics

Page 133: Generator Relay Protection

M-3425A Instruction Book

2–76

81A Frequency AccumulatorFrequency Accumulation feature (81A) provides anindication of the amount of off frequency operationaccumulated.

Turbine blades are designed and tuned to operate atrated frequencies, operating at frequencies differentthan rated can result in blade resonance and fatiguedamage. In 60 Hz machines, the typical operatingfrequency range for 18 to 25 inch blades is 58.5 to61.5 Hz and for 25 to 44 inch blades is between59.5 and 60.5 Hz. Accumulated operation, for thelife of the machine, of not more than 10 minutes forfrequencies between 56 and 58.5 Hz and not morethan 60 minutes for frequencies between 58.5 and59.5 Hz is acceptable on typical machines.

The 81A function can be configured to track offnominal frequency operation by either set point orwhen the frequency is within a frequency band.

When using multiple frequency bands, the lowerlimit of the previous band becomes the upper limit

81A #1 HIGH BAND PICKUP_______________ Hz

81A #1 LOW BAND PICKUP_______________ Hz

81A #1 DELAY_____________ Cycles

81A #2 LOW BAND PICKUP_______________ Hz

81A #2 DELAY_____________ Cycles

81A #3 LOW BAND PICKUP_______________ Hz

81A #3 DELAY_____________ Cycles

81A #4 LOW BAND PICKUP_______________ Hz

81A #4 DELAY_____________ Cycles

81A #5 LOW BAND PICKUP_______________ Hz

81A #5 DELAY_____________ Cycles

81A #6 LOW BAND PICKUP_______________ Hz

81A #6 DELAY_____________ Cycles

for the next band, i.e., Low Band #2 is the upperlimit for Band #3, and so forth. Frequency bandsmust be used in sequential order, 1 to 6. Band #1must be enabled to use Bands #2–#6. If any band isdisabled, all following bands are disabled.

When frequency is within an enabled band limit,accumulation time starts (there is an internal tencycle delay prior to accumulation), this allows theunderfrequency blade resonance to be establishedto avoid unnecessary accumulation of time. Whenaccumulated duration is greater than set delay,then the 81A function operated the programmedoutput contact. The contact can be used to alert theoperator or trip the machine.

The accumulator status can be set to preserve theaccumulated information from previous devices.This allows the relay to begin accumulatinginformation at a pre-defined value. This setpoint isonly available through IPScom® CommunicationsSoftware.

Page 134: Generator Relay Protection

Application – 2

2–77

0 5 10 15Time (mins)

81-4 LB

81-3 LB

81-2 LB

81-1 LB

81-1 HB

Fn

Example- Band

#1 Band

#2 Band

#3 Band

#4 Band

#5 Band

Figure 2-66 Frequency Accumulator (81A) Example Bands

Figure 2-67 Frequency Accumulator (81A) Setpoint Ranges

Page 135: Generator Relay Protection

M-3425A Instruction Book

2–78

81R Rate of Change of FrequencyThe Rate of Change of Frequency function (81R) canbe used for load shedding or tripping applications.

The function also has an automatic disable featurewhich disables 81R function during unbalanced faultsand other system disturbances. This feature usesnegative sequence voltage to block the 81R function.When the measured negative sequence voltageexceeds the inhibit setting, the function 81R andmetering are blocked. The time delay and magnitudesettings of 81R should be based on simulation studies.The ranges and increments are shown in Figure 2-68.

Figure 2-68 Rate of Change of Frequency (81R) Setpoint Ranges

81R #1 PICKUP______________ Hz/s

81R #1 DELAY_____________ Cycles

81R #2 PICKUP______________ Hz/s

81R #2 DELAY_____________ Cycles

81R NEG SEQ VOLT INHIBIT_______________ %

Page 136: Generator Relay Protection

Application – 2

2–79

87 Phase DifferentialThe Phase Differential function (87) is a percentagedifferential with an adjustable slope of 1–100%.Although this protection is used to protect themachine from all internal winding faults, single-phase to ground faults in machines with highimpedance grounding may have currents less thanthe sensitivity of the differential relay (typicallybetween 3 and 30 primary amps). Ranges andincrements are presented in Figure 2-70.

Turn-to-turn faults are not detected by differentialrelays because the current into the generator equalsthe current out (see functions 50DT and 59X forturn-to-turn fault protection.) Even though thepercentage differential relay is more tolerant of CTerrors, all CTs should have the same characteristicsand accuracies.

A typical setting is 0.3 amps.

A typical setting is 10%.

A typical setting is one cycle. Typical settings given above assumematched current transformer performance, and that transformer in-rush of the unit transformer does not cause dc saturation of thegenerator CTs. If there is a significant difference in current trans-former ratings (C800 vs C200, for example), or if saturation of thegenerator CTs is expected during energizing of the step up trans-former, more appropriate settings might be 0.5 A pick up, 20% slope,and a delay of 5 to 8 cycles.

If line side and neutral side CTs do not have the same ratio, the ratioerror can be corrected (the line side measured current is multipliedby the phase CT correction settings.)

Line Side CTRPhase CT Correction =

Neutral Side CTR

To provide restraint for CT saturation at high offsetcurrents, the slope is automatically adjusted (at arestraining current equal to two times nominal current)to four times the slope setting, see Figure 2-69.

For very high currents in large generators, theproximity of CTs and leads in different phases cancause unbalanced currents to flow in the secondaries.These currents must be less than the minimumsensitivity of the relay.

There are two elements in this function. Element #2is intended to provide phase differential protectionfor SFC (Static Frequency Converter) starting gasturbine generator applications. Element #1 shouldbe disabled with a contact blocking input during aconverter start operation (generator off-line), sincethe current is carried by only neutral side CTs andthe resulting differential current may mis-operate87#1 function. The 87#2 element, which is set witha higher current pickup, will still provide protectionfor this condition.

87 #1 PICKUP______________ Amps

87 #1 SLOPE_______________ %

87 #1 DELAY_____________ Cycles

87 #2 PICKUP______________ Amps

87 #2 SLOPE_______________ %

87 #2 DELAY_____________ Cycles

87 PHASE CT CORRECTION________________

Page 137: Generator Relay Protection

M-3425A Instruction Book

2–80

3$'45$*

!

!

!

"#$

%&'

%&'(

(16

Where IA and Ia are generator high side and neutral side currents respectively, and CTC is theCT Phase correction.

Figure 2-69 Differential Relay (87) Operating Characteristics

Figure 2-70 Phase Differential (87) Setpoint Ranges

Page 138: Generator Relay Protection

Application – 2

2–81

87GD Ground (Zero Sequence) DifferentialThe Zero Sequence Differential function (87GD)provides ground fault protection for low impedancegrounded generator applications. High sensitivityand fast operation can be obtained using thisfunction. Ranges and increments are presented inFigure 2-71.

The relay provides a CT Ratio Correction Factor(R

C) which removes the need for auxiliary CTs when

the phase and neutral CT ratios are different.

When the system can supply zero sequence currentto the ground fault (such as when several generatorsare bussed together), the 87GD function operatesdirectionally. The directional element calculates theproduct (–3I

0INCosØ) for directional indication. The

relay will operate only if I0 (Zero sequence current

derived from phase CTs) and IN (Neutral current

from Neutral CT) have the opposite polarity, whichis the case for internal generator faults.

87GD PICKUP______________ Amps

87GD DELAY_____________ Cycles

87GD C.T. RATIO CORRECT________

A typical setting is 0.2 amps. (Relay amps = primary amps ÷ CTratio.) For higher values of R

C, noise may create substantial

differential current making higher pickup settings desirable.

CAUTION: Do NOT set the Delay to less than 2 Cycles.

In order to prevent mis-operation during external faults with CTsaturation conditions, a time delay of 6 cycles or higher isrecommended.

CT Ratio Correction Factor = (Phase CT Ratio)/(Neutral CT Ratio)

The advantage of directional supervision is thesecurity against ratio errors and CT saturation duringfaults external to the protected generator.

The directional element is inoperative if the residualcurrent (3I

0) is approximately less than 0.2 A, in

which case the algorithm automatically disables thedirectional element and the 87GD function becomesnon-directional differential. The pickup quantity isthen calculated as the difference between thecorrected triple zero-sequence current (R

C3I

0) and

the neutral current (IN). The magnitude of the

difference (RC3I

0–I

N) is compared to the relay pickup.

For security purposes during external high phase-fault currents causing CT saturation, this function isdisabled any time the value of I

N is less than

approximately 0.20 amps.

NOTE: When 87GD is enabled, 67N function isnot available.

Figure 2-71 Ground Differential (87GD) Setpoint Ranges

Page 139: Generator Relay Protection

M-3425A Instruction Book

2–82

Breaker MonitoringThe Breaker Monitoring feature calculates an estimateof the per-phase wear on the breaker contacts bymeasuring and integrating the current (IT) or currentsquared (I2T) passing through the breaker contactsduring the interruption period. The per-phase valuesare added to an accumulated total for each phase,and then compared to a user-programmed thresholdvalue. When the threshold is exceeded in any phase,the relay can operate a programmable output contact.The accumulated value for each phase can be displayed

Expanded Inputs IN7–IN14 (if equipped) must be set usingIPScom.

Expanded Outputs OUT9–OUT23 (if equipped) must be set usingIPScom.

Figure 2-72 Breaker Monitor (BM) Setpoint Ranges

BM PICKUP______ kA-cycles

BM INPUT INITIATEi6 i5 i4 i3 i2 i1

BM OUTPUT INITIATE08 07 06 05 04 03 02 01

BM DELAY____________ Cycles

BM TIMING METHODit i2t

as an actual value. The accumulation starts after aset time delay from the trip initiate command toaccount for the time it takes for the breaker to startopening its contacts. The accumulation continuesuntil the current drops below 10% of the nominalcurrent setting or 10 cycles, whichever occurs first.

NOTE: Preset Accumulator Setpoints are onlyavailable through IPScom®.

Page 140: Generator Relay Protection

Application – 2

2–83

Trip Circuit MonitoringExternal connections for the Trip Circuit Monitoringfunction are shown in Figure 2-73. The default TripCircuit Monitor input voltage is 250 V dc. See Section5.5, Circuit Board Switches and Jumpers, Table 5-3for other available trip circuit input voltage selections.

This function should be programmed to block whenthe breaker is open, as indicated by 52b contactinput (IN1). If the TCM is monitoring a lockout relay,a 86 contact input (INx) should be used to blockwhen the lockout relay is tripped.

When the Output Contact is open, and continuityexists in the Trip Circuit, a small current flows thatactivates the Trip Circuit Monitoring Input. If the TripCircuit is open, and the output contact is open, nocurrent flows and the Trip Circuit Monitoring Input is

52b

M-3425A

Trip CircuitMonitoring Input

2

1 Aux Input

OutputContact

StationBattery

+

-

OtherContacts

52a

52 or 86Trip Coil

86or

Figure 2-73 Trip Circuit Monitoring Input

deactivated. An Output Contact that is welded closedwould also cause the Trip Circuit Monitoring Input todeactivate, indicating failure of the Output Contact.

When the Output Contact is closed, no current flowsin the Trip Circuit Monitoring Input. If the M-3425Ahas issued a trip command to close the OutputContact and Trip Circuit Monitoring Input remainsactivated, this is an indication that the Output Contactfailed to close.

The output of the Trip Circuit Monitoring function canbe programmed as an alarm to alert maintenancepersonnel.

Figure 2-74 Trip Circuit Monitor (TC) Setpoint Ranges

TCM DELAY_____________ Cycles

Page 141: Generator Relay Protection

M-3425A Instruction Book

2–84

IPSlogic™The relay provides six logic functions and associatedIPSlogic. The logic functions can be used to allowexternal devices to trip through the relay, providingadditional target information for the external device.More importantly, these functions can be used inconjunction with IPSlogic to expand the capabilityof the relay by allowing the user to define customizedoperating logic.

Programming the IPSlogic can only be implementedthrough IPScom® Communications Software.The IPSlogic cannot be programmed using theHuman-Machine Interface (HMI).

IPS LOGICUSE IPSCOM TO CONFIGURE

Page 142: Generator Relay Protection

Application – 2

2–85

Bloc

king

Intp

uts

Sel

ecta

ble

And/

Or

Initi

atin

g In

tput

s

Sel

ecta

ble

And/

Or

Prog

ram

mab

leIn

puts

1-6

*Inp

uts

7-14

Initi

atin

g Fu

nctio

n Tr

ip(in

clud

es e

xter

nal e

lem

ents

)

Sel

ecta

ble

And/

Or/N

or/N

and

Prog

ram

mab

leFu

nctio

n(s)

Tim

ed O

ut

Pic

ked

Up

Initi

atin

g O

utpu

ts

Sel

ecta

ble

And/

Or

Prog

ram

mab

leO

utpu

ts 1

-8*O

utpu

ts 9

-23

Initi

ate

Via

Com

mun

icat

ion

Poi

nt

Sele

ctab

le A

nd/O

r

Sel

ecta

ble

And/

Or

Initi

ate

Via

Com

mun

icat

ion

Poi

nt

Prog

ram

mab

leIn

puts

1-6

*Inp

uts

7-14

Pro

gram

med

Tim

e D

elay

1- 6

5,50

0 C

ycle

s(1

091

sec)

Pro

gram

med

Pro

file

Set

ting

Gro

up 1

-4

Pro

gram

med

Out

puts

1-8

*Out

puts

1-2

3

Log

Targ

et

IPSl

ogic

Act

ivat

ed

Log

Pick

up

This

sec

tion

of th

e IP

Slo

gic

initi

ates

the

Func

tion

Out

put

This

sec

tion

of th

e IP

Slog

ic is

used

to B

lock

the

Func

tion

Out

put

* For

uni

ts w

ith E

xpan

ded

I/O

This

sec

tion

of th

e IP

Slog

ic is

use

dto

act

ivat

e th

e de

sire

d O

utpu

t

Figure 2-75 IPSlogic™ Function Setup

Page 143: Generator Relay Protection

M-3425A Instruction Book

2–86

Settings and Logic Applicable whenIPSlogic™ Function(s) programmed usingIPScom®

There are four initiating input sources: InitiatingOutputs, Initiating Function Trips, Function Pickup(including the IPSlogic Functions themselves),Initiating Inputs, and initiation using theCommunication Port. The only limitation is that anIPSlogic Function may not be used to initiate itself.There are two blocking input sources: BlockingInputs and blocking using the Communication Port.

The activation state of the input function selected inthe Initiating Function can be either timeout (Trip) orpickup. The desired time delay for securityconsiderations can be obtained in the IPSlogicFunction time delay setting.

Notes:

1. This logic gate may be selected as either AND or OR.

2. This logic gate may be selected as AND, OR, NOR, or NAND.

Figure 2-76 IPSlogic Function Programing

The IPSlogic Function can be programmed toperform any or all of the following tasks:

• Change the Active Setting Profile

• Close an Output Contact

• Be activated for use as an input to anotherExternal Function

Since there are six IPSlogic Functions per settingprofile, depending on the number of different relaysettings defined, the scheme may provide up to 24different logic schemes. The IPScom IPSlogicFunction programming screen is shown inFigure 2-76.

Page 144: Generator Relay Protection

Application – 2

2–87

Figure 2-77 Selection Screen for Initiating Function Timeout

Figure 2-78 Selection Screen for Initiating Function Pickup

Page 145: Generator Relay Protection

M-3425A Instruction Book

2–88

DO/RST (Dropout/Reset) Timer FeatureThe DO/RST timer can be set as either Dropout orReset mode. The operation of the Dropout DelayTimer and the Reset Delay Timer are describedbelow.

Reset Delay TimerThe Reset Delay Timer logic is presented inFigure 2-80. The Reset Delay Timer feature allowsthe user to delay the reset of the PU Time DelayTimer and hold the accumulated timer value (A) forthe duration of the Reset Time Delay time period (B).The Reset Delay Timer starts when the IPSlogic PUStatus drops out (C).

PU Status

PU Time DelaySetting (30)

Output

25 35

Dropout Delay Timer

Seal in Delay

Seal in Delay

Dropout Delay

Cycles

PU Time Delay Timing

IPSlogic Functions (1 - 6)

A

B

C D

E

Figure 2-79 Dropout Delay Timer Logic Diagram

Dropout Delay TimerThe Dropout Delay Timer logic is presented inFigure 2-79. The Dropout Delay Timer feature allowsthe user to affect an output time delay that startswhen the IPSlogic PU Status drops out (A) and canhold the Output (D) status true beyound the OutputSeal In Delay value (C).

However, the Seal In Delay (E) may hold the Output(B) true if the time after IPSlogic PU Status dropout(A) and Dropout Delay Timer value (D) are less thanthe Seal In Delay time (E).

Reset Delay Timer

PU Status

Output

25 25

Reset Delay10 Cycles

12 8Cycles

ResetDelay

5

Seal InTimer

ResetDelay

10

PU Time Delay Timing

IPSlogic Functions (1 - 6)

A

DC

B

E

F

G

PU Time DelaySetting (30)

Figure 2-80 Reset Delay Timer Logic Diagram

If the IPSlogic PU Status remains dropped out (D)after the reset delay has timed out, then the IPSlogicPU timer value will be reset to zero (E).

If the IPSlogic PU Status reasserts (F) while theReset Delay Timer is still timing, then the PU TimerDelay begins timing from the accumulated value (G).

Page 146: Generator Relay Protection

Operation – 3

3–1

3Operation

3.1 Front Panel Controls .................................................................. 3–1

3.2 Initial Setup Procedure/Settings ................................................ 3–5

3.3 Setup Unit Data .......................................................................... 3–5

3.4 Setup System Data .................................................................... 3–6

3.5 Status/Metering .......................................................................... 3–9

3.6 Target History ........................................................................... 3–10

Arrow PushbuttonsThe left and right arrow pushbuttons are used tochoose among the displayed menu selections. Whenentering values, the left and right arrow pushbuttonsare used to select the digit (by moving the cursor) ofthe displayed setpoint that will be increased ordecreased by the use of the up and down pushbuttons.

The up and down arrow pushbuttons increase ordecrease input values or change between upperand lower case inputs. If the up or down pushbuttonis pressed when adjusting numerical values, thespeed of increment or decrement is increased.

EXIT PushbuttonThe EXIT pushbutton is used to exit from a displayedscreen and move up the menu tree. Any changedsetpoint in the displayed screen will not be saved ifthe selection is aborted using the EXIT pushbutton.

ENTER PushbuttonThe ENTER pushbutton is used to choose ahighlighted menu selection, to replace a setpoint orother programmable value with the currently displayedvalue, or to move down within the menu tree.

Target & Status Indicators and ControlsThe target/status indicators and controls consist ofthe POWER SUPPLY (2) LEDs, RELAY OK LED,the OSCILLOGRAPH TRIG LED, BREAKERCLOSED LED, TARGET LED, DIAGNOSTIC LEDand TIME SYNC LED.

This chapter contains information that describes theoperation of the M-3931 Human Machine InterfaceModule (HMI) and the M-3925A Target module. Itfurther describes the direct setting and configurationprocedures for entering all required data to the relay.Included in this chapter is a description of the processnecessary for review of setpoints and timing, monitoringfunction status and metering quantities, viewing thetarget history, and setup of the oscillograph recorder.

3.1 Front Panel Controls

The relay has been designed to be set andinterrogated locally with the optional HMI panel. Anintegral part of this design is the layout and functionof the front panel indicators and controls, illustratedin Figure 3-1.

Alphanumeric DisplayTo assist the operator in setting and interrogatingthe relay locally, the HMI displays menus whichguide the operator to the desired function or setpointvalue. These menus consist of two lines. The bottomline lists lower case abbreviations of each menuselection with the chosen menu selection shown inuppercase. The top menu line provides a descriptionof the chosen menu selection.

Screen BlankingThe display will automatically blank after exiting fromthe Main Menu, or from any screen after five (5)minutes of unattended operation. To wake up thedisplay, the user must press any key except EXIT.

Page 147: Generator Relay Protection

M-3425A Instruction Book

3–2

Power Supply #1 (#2) LEDThe green PS LED indicator will remain illuminatedfor the appropriate power supply whenever power isapplied to the unit and the power supply is operatingcorrectly. A second power supply is available as anoption, for units without expanded I/O.

Relay OK LEDThe green RELAY OK LED is controlled by therelay's microprocessor. A flashing RELAY OK LEDindicates proper program cycling. The LED can alsobe programmed to be continuously illuminated.

Oscillograph Triggered LEDThe red OSC TRIG LED will illuminate to indicatethat oscillographic data has been recorded in theunit’s memory and is available for download.

Breaker Closed LEDThe red BRKR CLOSED LED will illuminate to indicatewhen the breaker status input IN1 (52b) is open.

Target Indicators and Target ResetWhen a condition exists that causes the operationof outputs 1 through 8 (1 through 23 for units withexpanded I/O), the TARGET LED will illuminate,indicating a relay operation. The TARGET LED willremain illuminated until the condition causing thetrip is cleared, and the operator presses the TARGETRESET pushbutton. For units equipped with theoptional M-3925A Target Module, additional targetinginformation is available. The Target module includesan additional 24 target LEDs, and 8 output statusLEDs. LEDs corresponding to the particular operatedfunction as well as the present state of the outputsare available. Pressing and holding the TARGETRESET pushbutton will display the present pickupstatus of all functions available on the target module.This is a valuable diagnostic tool which may beused during commissioning and testing.

Time Sync LEDThe green TIME SYNC LED will illuminate to indicatethat the IRIG-B time signal is received and theinternal clock is synchronized with the IRIG-B timesignal. IRIG-B time information is used to accuratelytag target and oscillograph events.

Diagnostic LEDThe diagnostic DIAG LED will flash when a self-testerror is detected. The LED will flash the Error Codenumber; for example, for Error Code 32, the LED

will flash 3 times, followed by a short pause, andthen flash 2 times, followed by a long pause, thenrepeat LED flash sequence. For units equipped withthe HMI, the Error Code number is also displayedon the screen.

Accessing ScreensTo prevent unauthorized access to relay functions,the unit includes a provision for assigning accesscodes. If access codes have been assigned, theaccess code entry screen will be displayed afterENTER is pressed from the default message screen.

Default Message ScreensWhen power is applied to the unit, the relay performsa number of self-tests to ensure that it is operatingcorrectly. During the self-tests, the screen displaysan “X” for each test successfully executed.

If all self-tests are executed successfully, the relaywill briefly display the word PASS and then a seriesof status screens that include:

• Model Number

• Software Version Number

• Serial Number

• Date and time as set in the system clock

• User Logo Screen

If a test fails, an error code will be displayed and therelay will not allow operation to proceed. In such acase, the error code should be noted and the factorycontacted. A list of error codes and their descriptionsare provided in Appendix C, Error Codes.

When the relay has power applied and is unattended,the user logo lines are blanked.

If a function has operated and the targets have notbeen reset, the screen will display the time and dateof the operation and automatically cycle throughscreens for each applicable target (see Figure 3-2).Pressing the ENTER pushbutton will enter localmode operation, displaying the access code entryscreen or, if access codes have been disabled, thefirst level menu.

Figure 3-3 presents the software menu flow mapfor HMI-equipped units. This map can be used asa quick reference guide to aid in navigating therelay's menus.

Page 148: Generator Relay Protection

Operation – 3

3–3

!"#$

!%"#$

&'()*"'+,

#))!!)$

'))!!#$-

))!!$#($-

./0!, !1,2,345)*6( )())

/ '

'78247/'9.9

4,%402%

&'2"40,2:

;;;;;;;;6#!<!!

!!6#!<!!

!(#"=5'/

'78247/'.9>9/

./0!, !1,2,345?3,,3)

5?3,,3)

5?3,,3)

5?3,,3)

=7/>.5?3,,3)

Figure 3-2 Screen Message Menu Flow

Figure 3-1 M-3425A Front Panel

Page 149: Generator Relay Protection

M-3425A Instruction Book

3–4

VOLTAGE RELAYVOLT curr freq v/hz

• 27 Phase Undervoltage• 59 Phase Overvoltage• 27TN Neutrl Undervolt• 59X Overvoltage• 59N Neutral Overvoltage• 59D Volt. Diff. 3rd Har.

CURRENT RELAYvolt CURR freq v/Hz

• 46 Neg Seq Overcurrent• 50 Inst Overcurrent• 50/27 Inadvertent Energing• 50BF Breaker Failure• 50DT Def. Time Overcurr• 50N Inst Overcurrent• 51N Inv Time Overcurrent• 49 Stator Overload• 51V Inv Time Overcurrent• 87 Differential Overcurr• 87GD Gnd Diff Overcurr• 67N Res Dir Overcurr

FREQUENCY RELAYvolt curr FREQ v/hz

• 81 Frequency• 81R Rate of Change Freq• 81A Frequency Accum.

VOLTS PER HERTZ RELAYvolt curr freq V/HZ

• 24 Def Time Volts/Hertz• 24 Inv Time Volts/Hertz

POWER RELAY PWR lof fuse dist

• 32 Directional Power

LOSS OF FIELD RELAY pwr LOF fuse dist

• 40 Loss of Field

V. T. FUSE LOSS RELAY pwr los FUSE dist

• 60FL V. T. Fuse Loss

PHASE DISTANCE RELAY pwr lof fuse DIST

• 21 Phase Distance• 78 Out of Step

FIELD GROUND RELAYFIELD stator sync

• 64B/F Field Ground

STATOR GROUND RELAY field STATOR sync

• 64S Stator Ground

SYNC CHECK RELAY field stator SYNC

• 25S Sync Check• 25D Dead Volt

BREAKER MONITORBRKR trpckt ipslog

• Set Breaker Monitoring• Preset Accumulators• Clear Accumulators

TRIP CIRCUIT MONITORbrkr TRPCKT ipslog

• Trip Circuit Monitor

IPS LOGICbrkr trpckt IPSLOG

• IPS Logic

CONFIGURE RELAYCONFIG sys stat

• Voltage Relay• Current Relay• Frequency Relay• Volts per Hertz Relay• Power Relay• Loss of Field Relay• V.T. Fuse Loss Relay• Phase Distance Relay• Field Gnd Relay• Stator Gnd Relay• Sync Check Relay• Breaker Mon Relay• Trip Ckt Mon Relay• IPSLogic Relay

SETUP SYSTEMconfig SYS stat

• Input Activated Profiles• Active Setpoint Profile• Copy Active Profile• Nominal Voltage• Nominal Current• V. T. Configuration• Delta-Y Transform• Phase Rotation • 59/27 Magnitude Select• 50DT Split-phase Diff.• Pulse Relay• Latched Outputs• Relay Seal-in Time• Active Input State• V.T. Phase Ratio• V.T. Neutral Ratio• V.T. VX Ratio• C.T. Phase Ratio• C.T. Neutral Ratio

STATUSconfig sys STAT

• Voltage Status• Current Status• Frequency Status• V/Hz Status• Power Status• Impedance Status• Sync Check Status• Breaker Mon Acc Status• 81A Accumulators Status• In/Out Status• Timer Status• Relay Temperature• Counters• Time of Last Power Up• Error Codes• Checksums

VIEW TARGET HISTORYTARGETS osc_rec comm

• View Target History• Clear Target History

OSCILLOGRAPH RECORDERtargets OSC_REC comm

• View Record Status• Clear Records• Recorder Setup

COMMUNICATIONtargets osc_rec COMM

• COM1 Setup• COM2 Setup• COM3 Setup• Communication Address• Response Time Delay• Comm Access Code• Ethernet Setup• Ethernet IP Address

SETUP UNIT SETUP exit

• Software Version• Serial Number• Alter Access Codes• User Control Number• User Logo Line 1• User Logo Line 2• Clear Output Counters• Clear Alarm Counter• Date & Time• Clear Error Codes• Ethernet Firmware Ver.• Diagnostic Mode

EXIT LOCAL MODE setup EXIT

NOTE: Depending on which functions are purchased, somemenus may not appear.

Figure 3-3 Main Menu Flow

Page 150: Generator Relay Protection

Operation – 3

3–5

3.2 Initial Setup Procedure/Settings

The M-3425A Generator Protection Relay is shippedfrom the factory with all functions disabled (user willonly be able to enable purchased functions).

The Setup Procedure provided below is a suggestedsetup procedure for initially entering settings intothe relay. While it is written for HMI-equipped units,the same procedure is applicable when setting therelay through remote communication utilizingM-3820D IPScom® Communications Software.

Following the Setup Procedure are several sectionswhich provide additional detail concerning thesettings required for proper commissioning.

Setup Procedure NOTE: Configuration Record forms are available

in Appendix A, Configuration RecordForms, to record settings for futurereference.

1. Enter the Setup Unit data. This is generalinformation required including alteringaccess codes, setting date and time,defining user logos, and otheradjustments. See Section 3.3, SetupUnit Data.

2. Configure the Setup System data. Thisis the general system and equipmentinformation required for operation,including such items as CT and VT ratios,VT configuration, and Nominal values.See Section 3.4, Setup System Datasubsection.

3. Enable the desired functions andelements. See Section 3.4, ConfigureRelay Data subsection.

4. Enter the desired setpoints for theenabled functions. See Section 3.4,Setpoints and Time Settings subsection.

5. Enter configuration information for theoscillograph recorder. See Section 3.4,Oscillograph Recorder Data subsection.

6. If remote communication is used, setthe parameters as needed. See Section3.4, Communications Settingssubsection, or in Chapter 4, RemoteOperation.

3.3 Setup Unit Data

NOTE: Please see Figure 3-3, Main Menu Flow,for a list of submenus associated withthe SETUP UNIT menu.

To access the SETUP UNIT menu proceed asfollows:

1. Press the ENTER pushbutton to displaythe main menu.

2. Press the right arrow pushbutton untilSETUP UNIT is displayed on the topline of the screen.

3. Press the ENTER pushbutton to accessthe SETUP UNIT menu.

SETUP UNIT SETUP exit

4. Press the ENTER pushbutton to movedown within the SETUP UNIT menu tothe desired category. To exit a specificcategory and continue to the next menucategory, press the EXIT pushbutton.

Setup Unit Data EntryThe general information required to complete theentry of Setup Unit Data includes:

Access Codes: The relay includes three levels ofaccess codes. Depending on their assigned code,users have varying levels of access to the installedfunctions.

1. Level 1 Access = Read setpoints,monitor status, view target history.

2. Level 2 Access = All of level 1 privileges,plus read & change setpoints, targethistory, set time clock.

3. Level 3 Access = All of level 2 privileges,plus access to all configuration functionsand settings.

Each access code is a user-defined one- to four-digit number. Access codes can only be altered bya level 3 user.

If the level 3 access code is set to 9999, theaccess code feature is disabled. When accesscodes are disabled, the access screens arebypassed, and all users have full access to all therelay menus. The relay is shipped from the factorywith the access code feature disabled.

Page 151: Generator Relay Protection

M-3425A Instruction Book

3–6

User Control Number: This is a user-defined valuewhich can be used for inventory or identification.The relay does not use this value, but it can beaccessed through the HMI or the communicationsinterface, and can be read remotely.

User Logo: The user logo is a programmable, two-line by 24-character string, which can be used toidentify the relay, and which is displayed locallywhen the relay is idle. This information is alsoavailable remotely.

Date and Time: This screen is used to view and setthe relay's internal clock. The clock is used to timestamp system events such as trip and oscillographoperations.

The clock is disabled when shipped from the factory(indicated by “80” seconds appearing on the clock)to preserve battery life. If the relay is to beunpowered for an extended length of time, the clockshould be stopped (see Diagnostic Mode). If theIRIG-B interface is used, the hours, minutes, andseconds information in the clock will besynchronized with IRIG-B time information everyhour.

The relay can accept a modulated IRIG-B signalusing the rear panel BNC connector, or ademodulated TTL level signal using extra pins onthe rear panel COM2 RS-232 interface connector(see Figure B-4 for COM2 pinout.) If the TTL signalis to be used, then Jumper 5 will be required to bepositioned (see Section 5.5, Circuit Board Switchesand Jumpers).

Setup Unit Features That Do Not Require DataEntryThe Setup Unit menu categories that provide theuser with read only information are SoftwareVersion, Serial Number and Ethernet FirmwareVer..

The Setup Unit menu also contains features thatprovide the user with the ability to Clear OutputCounters, Clear Alarm Counter, Clear ErrorCodes and access the Diagnostic Mode. The errorcodes are described in Appendix C, Self Test ErrorCodes. Note that while the relay is in DiagnosticMode, all protective functions are inoperative.

3.4 Setup System Data

NOTE: Please see Figure 3-3, Main Menu Flow,for a list of submenus associated withthe SETUP SYSTEM menu.

To access the SETUP SYSTEM menu proceed asfollows:

1. Press the ENTER pushbutton to displaythe main menu.

2. Press the right arrow pushbutton untilSETUP SYSTEM is displayed on thetop line of the screen.

3. Press the ENTER pushbutton to accessthe SETUP SYSTEM menu.

SETUP SYSTEMconfig SYS stat

To input the data, access the menu as follows:

1. Press the ENTER pushbutton to displaythe main menu.

2. Press the right arrow pushbutton untilSETUP SYSTEM is displayed on thetop line of the screen.

3. Press the ENTER pushbutton to accessthe SETUP SYSTEM menu and beginthe data input.

System setup data is required for proper operationof the relay. Information needed to complete thissection includes: Nominal Voltage, Nominal Current,VT Configuration, and other system-relatedinformation. See Section 2.1, Configuration, RelaySystem Setup subsection for a more detaileddescription of the settings required.

Page 152: Generator Relay Protection

Operation – 3

3–7

Configure Relay Data NOTE: Please see Figure 3-3, Main Menu Flow,

for a list of submenus associated withthe CONFIGURE RELAY menu.

To input the data, access the CONFIGURE RELAYmenu as follows:

1. Press the ENTER pushbutton to displaythe main menu.

2. Press the right arrow pushbutton untilCONFIGURE RELAY is displayed onthe top line of the screen.

3. Press ENTER to access theCONFIGURE RELAY menu and beginthe data input.

CONFIGURE RELAYCONFIG sys stat

The general information required to complete theinput data in this section includes:

• enable/disable

• output choices (OUT1–OUT8; for unitswith expanded I/O, OUT9–OUT23 mayonly be set through IPScom®)

• input blocking choices (IN1–IN6; for unitswith expanded I/O, IN7–IN14 may only beset through IPScom), plus fuse lossblocking

Each of the purchased functions within the relaymay be individually enabled or disabled. In addition,many functions have more than one element whichmay also be enabled or disabled. Unused functionsand elements should be disabled to avoid nuisancetripping and speed up HMI response time.

After enabling a function/element, the user ispresented with two additional screens for selectionof input blocking and output contact designations.Any combination of the control/status inputs or theinternally generated VT fuse loss logic can beselected to dynamically block the enabled function.“OR” logic is used if more than one input is selected.

Outputs 1–6 (OUT9–OUT23 for units with expandedI/O, set through IPScom only) are form “a” contacts(normally open) and outputs 7 and 8 are form “c”contacts (center tapped “a” and “b” contacts). Outputcontacts 1–4 contain special circuitry for high-speedoperation and pick up approximately 4 ms fasterthan other contacts.

See Section 2.1, Configuration, for more information.

Setpoints and Time Settings NOTE: Please see Figure 3-3, Main Menu Flow,

for a list of submenus and specificelements associated with the Setpointsand Time Setting menus.

To input the data, access these menus as follows:

1. Press the ENTER pushbutton to displaythe main menu.

2. Press the right arrow pushbutton untilVOLTAGE RELAY, the first of thesetpoint and time setting menus, isdisplayed on the top line of the screen.

NOTE: Some menus are dynamic, and do notappear if the function is not purchasedor is unavailable.

3. Press ENTER to begin the data input forthis menu, or continue pressing the rightarrow pushbutton until the desiredsetpoint and time setting menu isdisplayed, then press ENTER to beginthe data input.

The general information required to complete theinput data in this section includes individual relayfunction:

• pickup settings (converted to relayquantities)

• time delay settings

• frequency settings

• time dials

• power level settings (in percent rated)

• impedance diameter in relay ohms fordistance and offset settings

Settings should be programmed based on systemanalysis as described in Chapter 2, Application. Acomplete description of the individual function aswell as guidelines for settings are explained therein.

Page 153: Generator Relay Protection

M-3425A Instruction Book

3–8

Oscillograph Recorder Data NOTE: Please see Figure 3-3, Main Menu Flow,

for a list of submenus associated withthe OSCILLOGRAPH RECORDERmenu.

To input the data, access the OSCILLOGRAPHRECORDER menu as follows:

1. Press the ENTER pushbutton to displaythe main menu.

2. Press the right arrow pushbutton untilOSCILLOGRAPH RECORDER isdisplayed on the top line of the screen.

3. Press the ENTER pushbutton to accessthe OSCILLOGRAPH RECORDER menuand begin the data input.

OSCILLOGRAPH RECORDERtargets OSC_REC comm

The Oscillograph Recorder provides comprehensivedata recording (voltage, current, and status input/output signals) for all monitored waveforms (at 16samples per cycle). Oscillograph data can bedownloaded using the communications ports to anyIBM compatible personal computer running theM-3820D IPScom® Communications Software. Oncedownloaded, the waveform data can be examinedand printed using the optional M-3801D IPSplot®

PLUS Oscillograph Data Analysis Software.

CAUTION: Oscillograph records are not retainedif power to the relay is interrupted.

The general information required to complete theinput data of this section includes:

• Recorder Partitions: When untriggered,the recorder continuously recordswaveform data, keeping the data in abuffer memory. The recorder's memorymay be partitioned into 1 to 16 partitions.

When triggered, the time stamp is recorded,and the recorder continues recording for auser-defined period. The snapshot of thewaveform is stored in memory for laterretrieval using IPScom CommunicationsSoftware. The OSC TRIG LED on the frontpanel will indicate a recorder operation (datais available for downloading).

• Trigger Inputs and Outputs: The recordercan be triggered remotely through serialcommunications using IPScom, orautomatically using programmed statusinputs or outputs.

• Post-Trigger Delay: A post-trigger delayof 5% to 95% must be specified. Aftertriggering, the recorder will continue tostore data for the programmed portion ofthe total record before re-arming for thenext record. For example, a setting of80% will result in a record with 20%pretrigger data, and 80% post-trigger data.

forebmuNsnoititraP

selcyCforebmuNnoititraPhcaErep

1 selcyC614

2 selcyC082

3 selcyC802

4 selcyC861

5 selcyC631

6 selcyC021

7 selcyC401

8 selcyC88

9 selcyC08

01 selcyC27

11 selcyC46

21 selcyC46

31 selcyC65

41 selcyC65

51 selcyC84

61 selcyC84

Table 3-1 Recorder Partitions

Communications SettingsTo enter the communications settings, access theCOMMUNICATION menu as follows:

1. Press the ENTER pushbutton to accessthe main menu.

2. Press the right arrow pushbutton untilCOMMUNICATION is displayed on thetop line of the screen.

Page 154: Generator Relay Protection

Operation – 3

3–9

3. Press the ENTER pushbutton to accessthe COMMUNICATION menu and beginthe data entry.

COMMUNICATIONtargets osc_rec COMM

The general information required to complete thecommunications settings entry of this sectioninclude:

• Baud rate for COM1 and COM2communication ports. The COM3 port doesnot have a separate baud rate setting butuses the setting of COM2 (or COM1: seeSection 5.5 Circuit Board Switches andJumpers).

• Communications address is used toaccess multiple relays using a multidropor network communication line.

• Communications access code is used forcommunication system security (enteringan access code of 9999 disables thecommunication security).

• Communication protocol and dead synctime for COM2 and COM3.

• Parity for COM2 or COM3 if MODBUS orMODBUS over TCP/IP protocol is used.

• Response Time Delay

• IP Address, Net Mask and GatewayAddress are required if the ethernet port isutilized and the network does not supportthe DHCP protocol.

Detailed information concerning setup and operationof the communication ports is described in Chapter4, Remote Operation.

3.5 Status/Metering

Monitor Status/Metering NOTE: Please see Figure 3-3, Main Menu Flow,

for a list of submenus associated withthe STATUS menu.

To access the STATUS menu and begin monitoring,proceed as follows:

1. Press the ENTER pushbutton to displaythe main menu.

2. Press the right arrow pushbutton untilSTATUS is displayed on the top line ofthe screen.

3. Press the ENTER pushbutton to accessthe STATUS menu.

STATUSconfig sys STAT

NOTE: Some menus are dynamic, and do notappear if the function is not purchasedor is unavailable.

4. Press the ENTER pushbutton to movedown within the STATUS menu to thedesired category. To exit a specificcategory and continue to the next menucategory, press the EXIT pushbutton.

The menu categories for monitored values are:

• Voltage Status: phase voltages, neutralvoltage, positive sequence voltage,negative sequence voltage, zero sequencevoltage, third harmonic neutral voltage,field ground measurement circuit, statorlow frequency injection voltage

• Current Status: phase currents (A–B–C/a-b-c), differential current, neutral current,ground differential current, positivesequence current, negative sequencecurrent, zero sequence current, stator lowfrequency injection current

• Frequency Status: frequency, rate ofchange of frequency

• Volts/Hz Status: volts per hertz

• Power Status: real power, reactive power,apparent power, power factor

• Impedance Status: impedance (Zab, Zbc,Zca), positive sequence impedance, fieldground resistance

• Sync Check Status: 25S Sync Checkand 25D Dead Volt

• BRKR Monitor

• 81A Accum. Status

• IN/OUT Status: Status of input and outputcontacts

• Timer: 51V Delay Timer, 51N Delay Timer,46IT Delay Timer, 24IT Delay Timer

• Relay Temperature

• Counters: output, alarm counter

• Time of Last Power up

• Error Codes

• Checksums: setpoints, calibration, ROM

Page 155: Generator Relay Protection

M-3425A Instruction Book

3–10

3.6 Target History

The M-3425A Generator Protection Relay includesthe ability to store the last 32 target conditions in anonvolatile memory. A target is triggered wheneveran output is operated. A second function attemptingto operate an output (which is already operated) willnot trigger a new target, since no new output hasbeen operated or closed. If the second functionoperation closes a different, unoperated output, anew target will be triggered. A target includes:

• An indication of which function(s) haveoperated, and timers expired (operated)

• Status information which indentifies anyfunction that is timing (picked up)

• Individual phase element information atthe time of the trigger, if the operatingfunction was a three phase function

• Phase currents at the time of operation

• Neutral current at the time of operation

• Input and output status, and a date/timetag

When a target is triggered, the front panel TARGETLED will light, indicating a recent event. If theoptional M-3925A Target Module is present, thecorresponding function LED will be lit. If the optionalM-3931 HMI module is available, a series of screenswill be presented, describing the most recentoperation. This information is also available remotelyby using the IPScom® Communication Software.

To access the TARGET HISTORY menu performthe following:

1. Press the ENTER pushbutton to accessthe main menu.

2. Press the right arrow pushbutton untilTARGET HISTORY is displayed on thetop line of the screen.

To view Target History records proceed as follows:

1. Ensure that the View Target HistoryMenu is selected to TRGT (upper case).

VIEW TARGET HISTORYTRGT clear

If TRGT is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select TRGT.

2. Press ENTER, the following will bedisplayed:

VIEW TARGET HISTORY1 Target number

Detailed descriptions for each View TargetHistory screen are presented on thefollowing page.

Page 156: Generator Relay Protection

Operation – 3

3–11

TARGET 1PHASE A=X B=X C=X

TARGET 1-CURRENT STATUS-

TARGET 1a=0.02 b=0.03 c=0.04

TARGET 1N=0.50 AMPS

This display gives the phase pickup information for the specificfunction.

This screen displays the phase current at the time the targetoperated.

This screen displays the neutral current at the time the targetoperated.

VIEW TARGET HISTORYTRGT clear

VIEW TARGET HISTORY 1 Target number

TARGET 101-JAN-2001 12:27:35.125

TARGET 108 05 01

TARGET 1I3 I1

TARGET 1-OPERATE TARGETS-

TARGET 127#1 PHASE UNDERVOLTAGE

TARGET 1PHASE A=X B= C=

TARGET 1-PICKUP TARGETS-

TARGET 127#1 PHASE UNDERVOLTAGE

This screen gives access to the target history, and also allowsthe user to clear the target history record from memory.

Using up and down buttons, user may select which particulartarget to view from the last 24 recorded triggers.

This screen gives the date and time tag of the selected target.

This screen displays operated outputs.

This screen displays operated inputs at time of trip.

The following screens display the timed out or “operate” func-tions.

This screen displays the specific function which timed out andtriggered the target.

This screen displays the phase information for the displayedfunction at time out.

The following screens display the timing on “picked up” func-tions when the target was recorded.

Page 157: Generator Relay Protection

M-3425A Instruction Book

3–12

This Page Left Intentionally Blank

Page 158: Generator Relay Protection

1

3

A

B

C

4–1

Remote Operation – 4

4Remote Operation

4.1 Remote Operation ...................................................................... 4–1

4.2 Installation and Setup (IPScom®) ............................................. 4–8

4.3 Operation .................................................................................... 4–8

4.4 Checkout Status/Metering (Windows) ..................................... 4–22

4.5 Cautions .................................................................................... 4–27

4.6 Keyboard Shortcuts ................................................................. 4–28

4.7 IPSutil™ Communications Software ........................................ 4–29

This chapter is designed for the person or groupresponsible for the remote operation and setting ofthe relay using the M-3820D IPScomCommunications Software or other means.

4.1 Remote Operation

The M-3425A Generator Protection Relay providesthree serial communication ports and one ethernetport.

Serial Ports (RS-232)Two serial interface ports, COM1 and COM2, arestandard 9-pin, RS-232, DTE-configured ports. Thefront-panel port, COM1, can be used to locally setand interrogate the relay using a temporaryconnection to a PC or laptop computer. The secondRS-232 port, COM2, is provided at the rear of theunit. COM2 is unavailable for communications whenthe optional ethernet port is enabled. Thedemodulated IRIG-B may still be used via the COM2Port when ethernet is enabled.

The individual addressing capability of IPScom andthe relay allows multiple systems to share a director modem connection when connected throughCOM2 using a communications-line splitter (seeFigure 4-1). One such device enables 2 to 6 units toshare one communications line. Appendix B, FigureB-2 illustrates a setup of RS-232 Fiber Optic network.

Serial Port (RS-485)COM3 located on the rear terminal block of theM-3425A is an RS-485, 2-wire connection. AppendixB, Figure B-3 illustrates a 2-wire RS-485 network.

Individual remote addressing also allows forcommunications through a serial multidrop network.Up to 32 relays can be connected using the same2-wire RS-485 communications line.

Optional Ethernet PortThe M-3425A when equipped with the optionalEthernet Port can be accessed from a local network.When the ethernet port is enabled the COM2 serialport (RS-232) is unavailable for communications.Although the ethernet connection speed is fasterthan the RS-232 port (can be up to 10 Mbps), theethernet module connects internally through theCOM2 serial connection and is therefore limited toconnection speeds up to 9600 bps.

Either COM2, COM3 or Ethernet port may be used toremotely set and interrogate the relay using a localarea network, modem or other direct serial connection.Equipment such as RTU’s, data concentrators,modems, or computers can be interfaced for direct,on-line, real time data acquisition and control.Generally, all data available to the operator throughthe front panel of the relay with the optional M-3931HMI module is accessible remotely through the BECO2200, MODBUS, BECO 2200 over TCP/IP orMODBUS over TCP/IP data exchange protocols.

Page 159: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–2

The communication protocols are used to fulfill thefollowing communications functions:

• Real-time monitoring of line status

• Interrogation and modification of setpoints

• Downloading of recorded oscillograph data

• Reconfiguration of all relay functions

Protocol documents are available directly fromBeckwith Electric or from our websitewww.beckwithelectric.com.

Direct ConnectionIn order for IPScom to communicate with the relayusing direct serial connection, a serial “null modem”cable is required, with a 9-pin connector (DB9P) forthe system, and an applicable connector for thecomputer (usually DB9S or DB25S). Pin-outs for anull modem adapter are provided in Appendix B,Communications.

An optional 10 foot null modem cable (M-0423) isavailable from the factory, for direct connectionbetween a PC and the relay’s front panel COM port,or the rear COM2 port.

When fabricating communication cables, every effortshould be made to keep cabling as short as possible.Low capacitance cable is recommended. The RS-232standard specifies a maximum cable length of 50feet for RS-232 connections. If over 50 feet of cablelength is required, other technologies should beinvestigated.

Other communication topologies are possible usingthe M-3425A Generator Protection Relay. AnApplication Note, “Serial Communication withBeckwith Electric’s Integrated Protection SystemRelays” is available from the factory or from ourwebsite at www.beckwithelectric.com.

Communications-Line Splitter

Up to six controlscan be used with a

communications-line splitter.Address 2

Address 4

Address 5

Address 6

Address 3Address 1

IBM-Compatible PC

Integrated ProtectionSystem

Null Modem Cable forDirect RS-232 Connection

Master Port

Figure 4-1 Multiple Systems Addressing Using Communications-Line Splitter

Page 160: Generator Relay Protection

1

3

A

B

C

4–3

Remote Operation – 4

Communication Access Code: If additional linksecurity is desired, a communication access codecan be programmed. Like the user access codes, ifthe communication access code is set to 9999(default), communication security is disabled.

Individual relay communication addresses shouldbe between 1 and 200. The dead sync time, whilenot critical for most communication networks, shouldbe programmed to match the communicationschannels baud rate (see Table 4-1, below).

etaRduaB emiTcnyS-daeD

0069 sm4

0084 sm8

0042 sm61

0021 sm23

Table 4-1 Dead-Sync Time

Ethernet Communication SettingsThe RJ45 ethernet port can be enabled utilizingeither IPSutil™ from the Ethernet Settings menu orfrom the HMI Communication menu. When theethernet port is enabled the COM2 Serial Port is notavailable for communications. The demodulatedIRIG-B may still be used via the COM2 Port whenethernet is enabled.

The following parameters must be set for properethernet communication:

DHCP Protocol

ENABLE: If the network server supports the DHCPprotocol the network server will assign the IPAddress, Net Mask and Gateway Address.

DISABLE: If the network server does not supportthe DHCP protocol or the user chooses to manuallyinput ethernet settings, then obtain the IP Address,Net Mask and Gateway address from the NetworkAdministrator and enter the settings.

ETHERNET ProtocolsSERCONV:To utilize the BECO2200 protocol overa TCP/IP connection select the SERCONV(BECO2200 TCP/IP) protocol. The IP Address ofthe relay must be entered in the IPScomCommunication screen. Also, ensure that the COM2protocol is selected to BECO2200 and the baudrate is set to 9600 bps.

Setting Up the M-3425A Generator ProtectionRelay for CommunicationThe initial setup of the relay for communicationmust be completed by utilizing the optional M-3931HMI Module or using direct serial connection.

For units shipped without the optional HMI Module,the communication parameters may be altered byfirst establishing communication using the defaultparameters and the IPSutil™ program.

IPSutil is an auxiliary program shipped on the samedisk with the IPScom® program. It is used exclusivelyfor altering communication and setup parameters onunits shipped without the M-3931 HMI Module.

Serial Communication SettingsThe following parameters must be set for properserial communication:

COM1 Baud Rate: Standard baud rates from 300 to9600 are available.

COM2 Baud Rate: Standard baud rates from 300 to9600 are available. COM2 and COM3 share thesame baud rate (see Section 5.5, Circuit BoardSwitches and Jumpers).

COM2 Dead Sync Time: This delay establishesthe line idle time to re-sync packet communication.Dead sync time should be programmed based onthe channel’s baud rate.

COM2 Protocol: BECO 2200 or MODBUS protocolis supported on COM2.

COM2 Parity: None, odd or even parity is availableif MODBUS protocol is selected.

COM2 Stop Bits: One or two stop bits available ifMODBUS protocol is selected.

COM3 Dead Sync Time: This delay establishesthe line idle time to re-sync packet communication.Dead sync time should be programmed based onthe channel’s baud rate.

COM3 Protocol: BECO 2200 or MODBUS protocolis supported on COM3.

COM3 Parity: None, odd or even parity is availableif MODBUS protocol is selected.

COM3 Stop Bits: One or two stop bits available ifMODBUS protocol is selected.

Communications Address: For multidrop networks,each device must have a unique address.

Response Time Delay: The extra time delay maybe added while the relay is sending the response. Ifset to 0, the response of the relay will be equal tothe time required to process the incoming packet(usually 20–80 ms.)

Page 161: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–4

6. Ensure that TCP is selected (Upper Case).

If TCP is not selected (Upper Case), thenuse the Right/Left arrow pushbuttons toselect TCP.

7. Press ENTER, the following will bedisplayed:

DHCP PROTOCOLDISABLE enable

8. If the network does not support the DHCPprotocol, then go to Manual Configurationof Ethernet Board (following page) tomanually configure the ethernet board.

9. If the DHCP Protocol is to be enabled, thenuse the Right/Left arrow pushbutton to selectENABLE (Upper Case), then press ENTER,the following will be displayed:

TCP/IP SETTINGSTCP prot

10. Ensure that PROT is selected (Upper Case).

If PROT is not selected (Upper Case), thenuse the Right arrow pushbutton to selectPROT.

11. Press ENTER, depending on the Ethernetboard that is installed one of the followingscreens will be displayed:

SELECT PROTOCOLmodbus serconv

SELECT PROTOCOLIEC 61850

12. Use the Right/Left arrow pushbuttons toselect the desired protocol (Upper Case),then press ENTER, the following will bedisplayed:

TCP/IP SETTINGStcp PROT

13. Press EXIT, the ethernet board willreconfigure and the following will bedisplayed:

CONFIGURING ETH...

If the ethernet board successfully obtainsan IP Address the following will be displayedfor approximately 2 seconds:

ETHERNET IP ADDRESSXX.XX.XX.XX

The ethernet board is now configured foruse and may be accessed through anetwork.

The Standard Port Number for the BECO2200 overTCP/IP protocol is 8800. The master device mayrequire the entry of the Standard Port Number.

MODBUS: To utilize the MODBUS protocol over aTCP/IP connection select the MODBUS (MODBUSover TCP/IP) protocol. The IP Address of the relaymust be entered in the IPScom® Communicationscreen. Also, ensure that the COM2 protocol isselected to MODBUS, baud rate is set to 9600 bps,1 stop bit and no parity selected.

The Standard Port Number for the MODBUS overTCP/IP protocol is 502. The master device mayrequire the entry of the Standard Port Number.

IEC61850: When the Ethernet option is purchasedwith the IEC61850 protocol, no other protocol maybe selected.

Ethernet Port SetupEnabling the ethernet port and selecting the requiredsupport settings can be accomplished using eitherthe HMI or IPSutil™. Both methods are presentedbelow.

HMI Ethernet Port Setup1. Ensure that the Communication Menu is

selected to COMM (upper case).

COMMUNICATION targets osc_rec COMM

If COMM is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select COMM.

2. Press ENTER, the following will bedisplayed:

COM1 SETUPCOM1 com2 com3 com_adr

3. Use the Right arrow pushbutton to selectETH (Upper Case).

ETHERNET SETUP access ETH eth_ip

4. Press ENTER, the following will bedisplayed:

ETHERNETDISABLE enable

5. Use the Right arrow pushbutton to selectENABLE (Upper Case), then press ENTER,the following will be displayed:

TCP/IP SETTINGSTCP prot

Page 162: Generator Relay Protection

1

3

A

B

C

4–5

Remote Operation – 4

8. Use the Right/Left arrow pushbuttons toselect the desired protocol (Upper Case),then press ENTER, the following will bedisplayed:

TCP/IP SETTINGStcp PROT

9. Press EXIT, the ethernet board willreconfigure and the following will bedisplayed:

CONFIGURING ETH...

If the ethernet board is successfullyconfigured, then the entered IP Addresswill be displayed for approximately 2seconds:

ETHERNET IP ADDRESSXX.XX.XX.XX

The ethernet board is now configured foruse and may be accessed through anetwork.

IPSutilTM Ethernet Port Setup with DHCP1. Connect the appropriate RS232 cable from

the PC hosting IPSutil to the target relay.

2. Launch IPSutil, then select Ethernet fromthe menu bar. IPSutil will display the EthernetSettings screen Figure 4-43.

3. From the Ethernet Settings screen selectEthernet Enable.

4. Select DHCP Protocol Enable.

5. Select the desired protocol.

6. Select Save, IPSutil will respond with theAdvance Setup dialog box stating “It willtake about 15 seconds to reset Ethernetboard to allow the menu of the unit toreflect the change.”

7. Select OK, IPSutil will configure the ethernetboard, then close the Ethernet Settingsscreen. The ethernet board is nowconfigured for use and may be accessedthrough a network.

IPSutilTM Ethernet Port Setup without DHCP1. Connect the appropriate RS232 cable from

the PC hosting IPSutil to the target relay.

2. Launch IPSutil, then select Ethernet fromthe menu bar. IPSutil will display the EthernetSettings screen Figure 4-43.

Then the display will return to the following:

ETHERNET SETUP

access ETH eth_ip

If the ethernet board fails to obtain an IPAddress within 15 seconds the followingwill be displayed (for approximately 2seconds):

CONFIGURING ETH...

ETH BOARD ERROR

Contact the Network Administrator todetermine the cause of the configurationfailure.

Manual Configuration of Ethernet Board1. Ensure that DISABLE is selected (Upper

Case) for DHCP Protocol.

If DISABLE is not selected (Upper Case),then use the Left arrow pushbutton to selectDISABLE.

2. Press ENTER, the following will bedisplayed:

IP ADDRESSXX.XX.XX.XX

3. Enter the desired IP Address, then pressENTER, the following will be displayed:

NET MASKXX.XX.XX.XX

4. Enter the desired Net Mask, then pressENTER, the following will be displayed:

GATEWAYXX.XX.XX.XX

5. Enter the desired Gateway, then pressENTER, the following will be displayed:

TCP/IP SETTINGStcp prot

6. Ensure that PROT is selected (Upper Case).

If PROT is not selected (Upper Case), thenuse the Right arrow pushbutton to selectPROT.

7. Press ENTER, depending on the Ethernetboard that is installed one of the followingscreens will be displayed:

SELECT PROTOCOLmodbus serconv

SELECT PROTOCOLIEC 61850

Page 163: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–6

User Logo LinesUnit Identifier

Relay TypeUnit Address

Figure 4-2 IPScom® Menu Selections

NOTE: Greyed-out menu items are for future release, and are not currently available.

Page 164: Generator Relay Protection

1

3

A

B

C

4–7

Remote Operation – 4

3. From the Ethernet Settings screen selectEthernet Enable.

4. Select DHCP Protocol Disable.

5. Enter values for IP Address, Net Mask andGateway.

6. Select the desired protocol.

7. Select Save, IPSutil will respond with theAdvance Setup dialog box stating “It willtake about 15 seconds to reset Ethernetboard to allow the menu of the unit toreflect the change.”

8. Select OK, IPSutil will configure the ethernetboard, then close the Ethernet Settingsscreen. The ethernet board is nowconfigured for use and may be accessedthrough a network.

Installing the ModemsUsing IPScom to interrogate, set or monitor therelay using a modem requires both a remote modemconnected at the relay location and a local modemconnected to the computer with IPScom installed.

In order to use IPScom to communicate with therelay using a modem, the following must be providedwith the unit:

• An external modem (1200 baud or higher),capable of understanding standard ATcommands.

• Serial modem cable with 9-pin connectorfor the unit and the applicable connectorfor the modem.

NOTE: Any compatible modem may be used;however, the unit only communicates at1200 to 9600 baud.

Similarly, the computer running IPScom must alsohave access to an internal or external compatiblemodem.

The local modem can be initialized, using IPScom,by connecting the modem to the computer, andselecting the COMM menu in IPScom. SelectMODEM, enter the required information, and finallyselect INITIALIZE from the expandedCommunications dialog box. The following stepsoutline the initialized modem setup procedure.

1. Connecting the modem to the computer:a. If the computer has an external modem,

use a standard straight-through RS-232modem cable to connect the computerand modem (M-3933). If the computerhas an internal modem, refer to themodem’s instruction book to determinewhich communications port should beselected.

b. The modem must be attached to (ifexternal) or assigned to (if internal) thesame serial port as assigned in IPScom.While IPScom can use any of the fourserial ports (COM1 through COM4),most computers support only COM1and COM2.

c. Connect the modem to the telephoneline and power up.

2. Connecting the Modem to the Relay:Setup of the modem attached to the relaymay be slightly complicated. It involvesprogramming the parameters (using the ATcommand set), and storing this profile inthe modem’s nonvolatile memory.

After programming, the modem will powerup in the proper state for communicatingwith the relay. Programming may beaccomplished by using “Hyperterminal” orother terminal software. Refer to your modemmanual for further information.

NOTE: The relay does not issue or understandany modem commands. It will not adjustthe baud rate and should be considereda “dumb” peripheral. It communicateswith 1 start, 8 data, and 1 stop bit.

a. Connect the unit to an external modemby attaching a standard RS-232 modemcable to the appropriate serialcommunications port on both the unitand the modem.

b. Connect the modem to the telephoneline and power up.

The modem attached to the unit must have thefollowing AT command configuration:

E0 No EchoQ1 Don’t return result code&D3 On to OFF DTR, hang-up and reset&S0 DSR always on&C1 DCD ON when detectedS0=2 Answer on second ring

The following commands may also be required atthe modem:

&Q6 Constant DTE to DCEN0 Answer only at specified speedW Disable serial data rate adjust\Q3 Bi-directional RTS/CTS relay&B1 Fixed serial port rateS37 Desired line connection speed

There are some variations in the AT commandssupported by modem manufacturers. Refer to thehardware user documentation for a list of supportedAT commands and direction on issuing thesecommands.

Page 165: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–8

4.2 Installation and Setup (IPScom)

IPScom runs with the Microsoft Windows® 95operating system or later. IPScom® only supportscommunication using the BECO 2200 protocol.

IPScom is available on CD-ROM, or it my bedownloaded from our website atwww.beckwithelectric.com

The M-3820D IPScom Communications Softwarepackage is not copy-protected and can be copied toa hard disk. For more information on your specificrights and responsibilities, see the licensingagreement enclosed with your software or contactBeckwith Electric.

Hardware RequirementsIPScom will run on any IBM PC-compatible computerthat provides at least the following:

• 8 MB of RAM

• Microsoft Windows 95 or later

• CD-ROM drive

• one serial (RS-232) communication port

• pointing device (mouse)

Installing IPScom1. Insert software CD-ROM into your drive.

An Auto-Install program will establish aprogram folder (Becoware) and subdirectory(IPScom). After installation, the IPScomprogram item icon (see Figure 4-3) islocated in Becoware. The default locationfor the application files is on drive C:, in thenew subdirectory “IPScom”(C:\Becoware\Ipscom).

2. If the Auto-Install program does not launchwhen the CD-ROM is inserted into the drivethen proceed as follows:

a. Select Run from the Start Menu.b. In the Run dialog box, locate the

installation file contained on theinstallation disk(sfi_m3425Acom_V______.exe).

c. Select Run to start the installationprocess.

Figure 4-3 IPScom Program Icon

Installing IPSutil™IPSutil is utility software used to program system-level parameters for units shipped without the M-3931HMI Module. The IPSutil.exe file is automaticallyinstalled in the Becoware folder, along with theIPScom files, and does not require separateinstallation.

4.3 Operation

Activating CommunicationsAfter the relay has been set up, the modemsinitialized, and IPScom installed, communication isactivated as follows:

1. Choose the IPScom icon from theBecoware folder.

2. The IPScom splash screen is displayedbriefly, providing the software versionnumber and copyright information. Thisinformation is also available by choosingthe About... command from the Help menu.

3. Choose the COMM menu selection.Complete the appropriate information onthe window for the relay to be addressed.a. If communication is through a modem,

choose the Modem command buttonto expand the communications dialogbox. Choose the desired relay locationand choose Dial button. This actionestablishes contact and automaticallyopens communication to the relay.

b. If computer is connected through thefront port, choose the Open COMbutton. This action establishescommunications.

4. Enter any valid IPScom command(s) asdesired.

5. To end communication whencommunicating by modem, choose the HangUp command button from the expandedCommunication dialog box. To close thecommunication channel when connectedlocally, choose the Close COM commandbutton.

OverviewWhen IPScom® is run, a menu and status bar isdisplayed, as shown in Figure 4-2. This sectiondescribes each IPScom menu selection and explainseach IPScom command in the same order as theyare displayed in the software program. For detailedinformation regarding each dialog box field (function),refer to Chapter 2, Application.

Page 166: Generator Relay Protection

1

3

A

B

C

4–9

Remote Operation – 4

When starting IPScom, the initial menu choices arethe File menu or the Comm menu. The choicespecifies whether the operator desires to write to adata file or to communicate directly with the relay.

File Menu

The File menu enables the user to create a newdata file, open a previously created data file, close,print, and save the file. The IPScom program canalso be exited through the File menu.

Since IPScom can be used with several Beckwithprotection systems in addition to the M-3425AGenerator Protection Relay, the format and contentsof a file must be established depending on whichprotective system is being addressed. When notconnected to one of the protection systems, usingthe New command, a new file is established withthe System Type dialog box (see Figure 4-4). Choicesfor Unit Type in the System Type Screen includeM-3425, M-3425A, M-3425A(SOE) and M-3425AExpanded I/O. The selected Unit Type ensures thatthe “New” file is consistant with the protective systemfirmware version (Table 4-2). Choosing the OKcommand button allows the new data file to beopened. Selecting Save or Save As commandsallows the file to be named and saved.

NOTE: By choosing the NEW command, unitand setpoint configuration values arebased on factory settings specified forthe profiled protection system.

Figure 4-4 System Type Dialog BoxPath: File menu / New command

COMMAND BUTTONS

OK Allows the selected Unit Type File to beopened.

Cancel Returns you to the IPScom main screen;any changes to the displayed informationis lost.

The Save and Save As... commands allow re-saving a file or renaming a file, respectively. TheOpen command allows opening a previously createddata file. With an opened data file, use the Relay...Setup... menu items to access the setpointwindows.

If communication can be established with a relay, itis always safer to use the Read Data From Relaycommand to update the PC’s data file with therelay data. This file now contains the proper systemtype information, eliminating the need to set theinformation manually.

The Print and Printer Setup commands allow userto select printer options and print out all setpointdata from the data file or directly from the relay, if arelay is communicating with the PC.

The Exit command quits the IPScom program.

Comm Menu

HelpWindowFile RelayComm

The Communication dialog box (see Figure 4-5)allows setup of the IPScom communication data tocoordinate with the relay and by choosing theModem button, to establish contact for remotelocations. When communicating by way of a fiberoptic loop network, echo cancelling is available bychecking the Echo Cancel box. This commandmasks the sender’s returned echo.

If the modem was not used to establishcommunication (direct connection), press the OpenCOM button to start. If the relay has a defaultcommunication access code of 9999, a messagewindow will be displayed showing Access Level #3was granted. Otherwise, another dialog box willappear to prompt the user to enter the access codein order to establish the communication. CloseCOM discontinues communication.

Protective System Unit Type Firmware Version

M-3425 D-0070XXX.XX.XX

M-3425A D-0114XXX.XX.XX

M-3425A (SOE) D-0150XXX.XX.XX

M-3425A Expanded I/O D-0150XXX.XX.XX

Table 4-2 Protective System FirmwareAssociation

Page 167: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–10

Figure 4-5 Communication Dialog BoxPath: Comm menu

COMMAND BUTTONS

Open COM Initiates contact withthe protectivesystem, either by direct serial or modemcommunication.

Close COM Breaks communication with theprotective system, for both direct serialor modem communication.

TCP_IP Opens the ethernet applicablecommunication screen selections toallow user to enter a TCP_IP address (ifnecessary), and opening and closingcommunication with the target relay.

Modem Displays the expanded Communicationdialog box.

Cancel Returns you to the IPScom main window;any changes to the displayedinformation are lost.

Open TCP_IP Initiates contact with the protectivesystem by ethernet connection.

Close TCP_IP Closes Ethernet connection.

Bring Up When selected, following connection toTerminal the target modem, allows the user toWindow send commands to the modem.AfterDialing

Add Displays the Add/Edit dialog box,allowing you to type a protectivesystem’s unit identifier, phone number,and communication address.

Edit Displays the Add/Edit dialog box,allowing you to review and change theuser lines (unit identifier), phonenumber, and communication address ofa selected entry.

Delete Deletes a selected entry.

Save Saves any changes to the displayedinformation

Initialize Allows the user to send special setup orother AT commands directly to themodem.

Dial Dials the entry selected from thedirectory.

Hang Up Ends modem communication, allowingthe user to dial again.

Relay Menu

The Relay menu provides access to the windowsused to set, monitor, or interrogate the relay. Sixsubmenus are provided: Setup, Monitor, Target ,Sequence of Events, Oscillograph

and Profile

as well as two commands, Write File to Relay, andRead Data From Relay.

The Setup submenu provides three commands:Setup System, Setpoints, and Set Date/Time.The Setup System command displays the SetupSystem dialog box (Figure 4-6) allowing the input ofthe pertinent information regarding the system onwhich the protective relay is applied (see Section2.1, Configuration, Relay System Setup).

Page 168: Generator Relay Protection

1

3

A

B

C

4–11

Remote Operation – 4

NOTE: Pulse/Latched Relay Outputs should be selected in 2 steps.

1. Deselect Latched/Pulsed Relay Outputs and Save.

2. Select Pulse/Latched Outputs and Save

Figure 4-6 Setup System Dialog Box

Path: Relay menu / Setup submenu / Setup System command

COMMAND BUTTONS

Input Active When the unit is equipped with expanded I/O, this command opens the Expanded Input ActiveState State screen (Figure 4-7), to allow the selection of Expanded Inputs 7 through 14.Expanded

Pulse/Latch When the unit is equipped with expanded I/O, this command opens the Pulse/LatchRelay screen (Figures 4-8 and 4-9) to allow the selection of expanded outputs 9 through 23.ExpandedOutputs

Save When connected to a protection system, sends the currently displayed information to the unit.Otherwise, saves the currently displayed information.

Cancel Returns you to the IPScom® main window; any changes to the displayed information are lost.

NOTE: Checking the inputs for the Active Input Open parameter designates the “operated” state established byan opening rather than a closing external contact.

Page 169: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–12

Figure 4-7 Expanded Input Active State

Figure 4-8 Pulse Relay Expanded Output Screen

Figure 4-9 Latch Relay Expanded Output Screen

Page 170: Generator Relay Protection

1

3

A

B

C

4–13

Remote Operation – 4

The Setpoints command displays the RelaySetpoints dialog box (see Figure 4-10) from whichthe individual relay function dialog boxes can beaccessed. Choosing a Relay function button willdisplay the corresponding function dialog box (seeFigure 4-11 for example).

Figure 4-10 Relay Setpoints Dialog BoxPath: Relay menu / Setup submenu / Setpoints window

COMMAND BUTTONS

Functions Opens the All Setpoints Table dialog boxfor the specified range of functions.

Configure Opens the Configure dialog box.

Exit Saves the currently displayedinformation and returns you to theIPScom® main window.

The Relay Setpoints dialog box gives access to twoadditional dialog boxes: All Setpoints Table andConfigure.

Choosing either of the Functions command buttons(either 21–51V or 59–TC) displays an All SetpointsTable dialog box for the specified range of setpoints(see Fig. 4-13). This dialog box contains a list ofsettings for each relay within a single window toallow scrolling through all relay setpoint configurationvalues. Choosing the Configure command buttondisplays the Configure dialog box (see Fig. 4-14),which contains a chart of programmed input andoutput contacts, in order to allow scrolling throughall relay output and blocking input configurations.Both dialog boxes (All Setpoint Table and Configure),feature hotspots which allows the user to jump from

a scrolling dialog box to an individual relay functiondialog box and return to the scrolling dialog boxagain. All available parameters can be reviewed orchanged when jumping to a relay configuration dialogbox from either scrolling dialog box.

Figure 4-11 Typical Setpoint Dialog BoxPath: Relay menu / Setup submenu / Setpoints window/ 46command button OR 46 jump hotspot within All SetpointsTable or Configure dialog box

COMMAND BUTTONS

Save When connected to a protection system,sends the currently displayedinformation to the unit. Otherwise, savesthe currently displayed information andreturns you to the Relay Setpoints, AllSetpoints Table, or Configure dialogbox.

Cancel Returns the user to the Relay Setpoints,All Setpoints Table, or Configure dialogbox; any changes to the displayedinformation are lost.

Expanded When the unit is equipped with expandedI/O’s I/O, this selection allows the user to select

expanded outputs 9–23 and expandedinputs 7–14.

Figure 4-12 Expanded I/O Dialog Box

Page 171: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–14

Figure 4-13 All Setpoints Table Dialog Box (partial)Path: Relay menu / Setup submenu / Setpoints window/ Display All command button

JUMP HOTSPOTS

This window provides you with jump hotspots, identified by the hand icon, that take you to each relay dialog box andthe Setup Relay dialog box. Exiting any of these dialog boxes will return you to the All Setpoints Table dialog box.

CONTROL MENU

Close Returns you to the Relay Setpoints dialog box.

Move Allows you to reposition the dialog box.

Page 172: Generator Relay Protection

1

3

A

B

C

4–15

Remote Operation – 4

Figure 4-14 Configure Dialog Box (partial)

Path: Relay menu / Setup submenu / Setpoints window/ Configure command button

JUMP HOTSPOTS

This window provides you with jump hotspots, identified by the hand icon, that take you to each relay dialog box.Exiting any of these dialog boxes will return you to the Configure dialog box.

CONTROL MENU

Close Returns you to the Relay Setpoints dialog box.

Move Allows you to reposition the dialog box.

Page 173: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–16

Figure 4-15 Configure Dialog Partial (Shown with Expanded Input/Outputs)

Path: Relay menu / Setup submenu / Setpoints window/ Configure command button

JUMP HOTSPOTS

This window provides you with jump hotspots, identified by the hand icon, that take you to each relay dialog box.Exiting any of these dialog boxes will return you to the Configure dialog box.

CONTROL MENU

Close Returns you to the Relay Setpoints dialog box.

Move Allows you to reposition the dialog box.

Page 174: Generator Relay Protection

1

3

A

B

C

4–17

Remote Operation – 4

The Set Date/Time command (see Figure 4-16)allows the system date and time to be set, orsystem clock to be stopped. This dialog box alsodisplays an LED mimic to identify when the TimeSync is in use (preventing date/time from beingchanged by user).

Figure 4-16 Unit Date/Time Dialog Box

Path: Relay menu/ Setup submenu/ Set Date/TimeCommand

There is a blue Time Sync LED mimic in this dialogbox (the LED is displayed as different shading on amonochrome monitor). When this LED is blue, therelay is synchronized with the IRIG-B signal and theTime field is grayed out, indicating that this fieldcan’t be changed. But the Date field can be changed(by editing and pressing Save).

When the LED is not blue, the relay is not time-synchronized and therefore, both the Date and Timefields can be changed.

The time field in the dialog box is not updatedcontinuously. The time at which the dialog box wasopened is the time that is displayed and remains assuch. This is true whether the relay is synchronizedwith the IRIG-B signal or not.

COMMAND BUTTONS

Stop Clock This toggles between start/stop, the relayclock. ‘Stop’ pauses, ‘Start’ resumes.

Save Saves Time and Date settings to therelay when applicable.

Cancel Returns you to the IPScom® mainwindow. Any changes to the displayedinformation is lost.

The Monitor submenu provides access for reviewingthe present status of the relay's measured andcalculated values, other real-time parameters andconditions as well as examining real-time andhistorical demand metering information (see Section4.4, Checkout Status/Metering). A cascading menuappears, providing several command options asshown below.

NOTE: Displayed parameters in status screenswill vary depending on unit configuration.

The Targets submenu provides three commandoptions: Display, Reset LED, and Clear History.The Display command displays the Target Dialog.This dialog box (see Figure 4-17) provides detaileddata on target events, including time, date, functionstatus, phase current values, and IN/OUT contactstatus at the time of trip. Individually recordedevents may be selected within the dialog box andsaved into a text file, or be printed out with optionaladded comments. The Reset LED is similar topushing the Target Reset button on the relay’s frontpanel, resetting current target(s) displayed on therelay. This command does not reset any targethistory.

The Clear History command clears all stored targetdata.

Page 175: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–18

Figure 4-17 Target Dialog BoxPath: Relay menu / Targets submenu / Display window

Time is displayed in milliseconds.

COMMAND BUTTONS

Comment Opens comment dialog box for annotation.

Print Prints out selected target information, with comment.

Save Saves selected target information, with comment, as a text file.

Close Exits the currently displayed dialog box.

Sequence of EventsThe Sequence of Events function provides a timestamped history of the Pickup (PU), Trip (TR) orDropout (DR) for each element, input or outputselected in the Event Trigger Setup screen.

During each event the voltage, current, impedance,frequency, input and output status and Volts/Hz arerecorded. Up to 512 events are logged before thebuffer begins to write over the oldest event. If multipleevents occur, then the log entries are recorded withone millisecond resolution within each event.

The Sequence of Events submenu allows the userto Setup the events that trigger the Sequence ofEvents recorder, Retrieve events from the relay,

View the pararmeters captured at the time of theevent and Clear the event recorder.

The Setup menu item displays the Event TriggerSetup screen Figure 4-18. Protective function Pickup,Trip, Dropout and/or Output/Input Pickup or Dropoutare selected to trigger the Sequence of EventsRecorder.

The Retrieve command downloads the events fromthe currently connected relay (events must beretrieved from the relay and stored in a file in order toview them.)

View permits the user to see a detailed list of pastevents and their corresponding captured parameters(real power, reactive power, differential current, deltavoltage, delta frequency, phase angle, 59D ratio, Vbrush (64B), field insulation resistance (64F), Vstator(20 Hz), and Istator (20 Hz) which are displayed inthe Event Log Viewer screen Figure 4-19.

The event log viewer screen includes the commandsOpen, Close, Print Summary, and Print Detail.Open opens a saved sequence of events file. Closecloses the print file. Print Summary prints an eventsummary, and Print Detail prints the detailed eventreport. Clear deletes event history from the control.

Page 176: Generator Relay Protection

1

3

A

B

C

4–19

Remote Operation – 4

NOTE: When in “File Mode,” selecting “Send” will result in a warning message stating, “To send settings,IPScom needs to be connected to relay.”

Elements trigger on Trip,Drop Out and Pickup

I/O triggers on Pickup, Dropout

Figure 4-18 Trigger Events Screen with Expanded I/O

Pickup, Dropout, Trip Event #, Date, Time

Voltages, Currents and I/O Status

Impendance, Sync Information

Figure 4-19 Event Log Viewer

Page 177: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–20

Figure 4-20 Event Download Screen

The Oscillograph submenu allows storing data onselected parameters for review and plotting at alater time. The Setup command allows the user toset the number of partitions and triggeringdesignations to be made (see Table 3-1, RecorderParticitions). The Retrieve command downloadsand stores collected data to a file; Trigger allowsthe manual triggering of the recorder; Clear erasesthe existing records. Run the optional M-3801DIPSplot® PLUS Oscillograph Analysis Softwareprogram to view the downloaded oscillograph files.

CAUTION: Oscillograph records are not retainedif power to the relay is interrupted.

NOTE: Oscillograph Post Trigger Delay is setto 5% in “File Mode”.

NOTE: When in “File Mode,” selecting “Send”will result in a warning message stating,“To send settings, IPScom needs to beconnected to relay.”

Figure 4-21 Setup Oscillograph Recorder

Figure 4-22 Retrieve Oscillograph RecordDialog

The Profile submenu provides three commandoptions: Switching Method, Active Profile, andCopy Profile.

Switching Method command allows selection ofeither Manual or Input contact. Active Profile allowsuser to designate active profile. Copy Profile copiesactive profile to one of four profiles (user shouldallow approximately 2 minutes for copying.)

CAUTION: Switching the active profile when therelay is on-line may cause unexpected operation ifthe wrong profile is selected.

NOTE: When in “File Mode” selecting OK tochange Profile Switching Method willresult in a warning message, “To changeProfile Switching Method, IPScom needsto be connected to relay”.

Figure 4-23 Profile Switching Method Dialog

NOTE: During Profile Switching, relay operationis disabled for approximately 1 second.

Page 178: Generator Relay Protection

1

3

A

B

C

4–21

Remote Operation – 4

NOTE: When in “File Mode” selecting OK to selectthe Active Profile will result in a warningmessage, “To select the Active Profile,IPScom needs to be connected to Relay”.

Figure 4-24 Select Active Profile

NOTE: When in “File Mode” selecting OK tocopy the Active Profile will result in awarning message, “To copy the ActiveProfile, IPScom needs to be connectedto Relay”.

Figure 4-25 Copy Active Profile

The Write File To Relay command is used to writethe data to the relay. The Read Data From Relaycommand is used to retrieve the data from the relayto the computer for display.

Window Menu/Help Menu

The Window menu enables the positioning andarrangement of all IPScom® windows so that there isbetter access to available functions. This featureallows the display of several windows at the sametime. Clicking on an inactive window activates thatwindow.

Currently in revision, the Help menu will enable theuser to look up information about any IPScom menusor commands. Though displaying (greyed-out) Helpcommands, this menu item is currently unavailable.

The Help menu provides three commands. TheContents command initiates a link to a PDF (PortableDocument File) version of this instruction book foreasy reference. An Adobe Acrobat® reader isrequired to view this document.

The M-3425A Instruction Book has been indexed toits table of contents. By selecting the “Navigatorpane’ in Adobe Acrobat Reader, the user can directlyaccess selected topics. The About commanddisplays IPScom version and developmentinformation. Profile Info displays user infromationfor input and editing.

Figure 4-26 About IPScom Dialog Box

Page 179: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–22

4.4 Checkout Status/Metering

Figure 4-27 Primary Status Dialog Box

Path: Relay menu/ Monitor submenu/ Primary Status window

These are calculated values based on the VT and CT inputs.

Figure 4-28 Secondary Status Dialog Box

Path: Relay menu/ Monitor submenu/ Secondary Status window

Page 180: Generator Relay Protection

1

3

A

B

C

4–23

Remote Operation – 4

Figure 4-29 Accumulator Status Screen

Figure 4-30 Phase Distance Dialog Box

Path: Relay menu / Monitor submenu / Phase Distance window

Phase Distance window shows a graphic representation of phase distance settings.

Move the scope window to the right

Zoom In

Zoom Out

Refresh Scope

CONTROL BUTTONS

Move up the scope window

Move down the scope window

Move the scope window to the left

Page 181: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–24

Figure 4-31 Loss of Field Dialog Box

Path: Relay menu / Monitor submenu / Loss of Field window

Loss-of-Field window shows a graphic representation of loss-of-field settings, and also displays the positive sequenceimpedance.

CONTROL BUTTONS

Move up the scope window

Move down the scope window

Move the scope window to the left

Move the scope window to the right

Zoom In

Zoom Out

Refresh Scope

Figure 4-32 Out-of-Step Dialog

Path: Relay menu / Monitor submenu / Out-of-Step window

Move the scope window to the right

Zoom In

Zoom Out

Refresh Scope

CONTROL BUTTONS

Move up the scope window

Move down the scope window

Move the scope window to the left

Page 182: Generator Relay Protection

1

3

A

B

C

4–25

Remote Operation – 4

Figure 4-33 Phasor Dialog Box

Path: Relay menu / Monitor submenu / Phasor Diagram window

CONTROL BUTTONS

p Voltage Toggle & display voltage channel information

p Currents (A) Toggle & display current channel information.

p Freeze Toggle & update information

Figure 4-34 Sync Scope Screen

Page 183: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–26

Figure 4-35 Function Status Screen

Path: Relay menu / Monitor submenu / Function Status window

Function Status window shows the status of various functions, with “T” representing the function which has tripped, and “P”representing the function which has picked up and is timing.

Page 184: Generator Relay Protection

1

3

A

B

C

4–27

Remote Operation – 4

4.5 Cautions

System and IPScom® CompatibilityEvery attempt has been made to maintaincompatibility with previous software versions. Insome cases (most notably with older protectionsystems), compatibility cannot be maintained. Ifthere is any question about compatibility, contactthe factory.

System PrioritySystem conflicts will not occur, as local commandsinitiated from the front panel receive priorityrecognition. When the unit is in local mode,communication using the serial ports is suspended.IPScom displays an error message to indicate thisfact.

Time and Date StampingTime and date stamping of events is only as usefulas the validity of the unit’s internal clock. Under theRelay menu, the Set Date/TIme command allowsyou to manually set the unit’s clock.

Echo CancelThe Echo Cancel check box, under the Commmenu, should only be used when several relays areconnected using a fiber optic loop network.Otherwise, echo cancel must not be selected orcommunication will be prevented.

Serial Port ConnectionsIf the serial port is connected to something otherthan a modem, and an IPScom modem commandis executed, the results are unpredictable. In somecases, the computer may have to be reset.

CAUTION: Oscillograph records are not retainedif power to the relay is interrupted.

Page 185: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–28

4.6 Keyboard Shortcuts

Keyboard ShortcutsSYSTEM KEYS

These keys can be used within Microsoft Windows® and IPScom®.

Alt-Tab To switch between applications.

Ctrl-Esc To open Task List dialog box. Opens Start Menu (Win 95/98).

Ctrl-Tab To switch between windows within an application.

Arrow Keys To select an application or group icon.

First Character of Name To select application or group icon.

Enter To open selected group or run selected application.

MENU KEYS

These keys enable you to select menus and choose commands.

Alt or F10 To select or cancel selection of the Setup menu on the menu bar.

Left Arrow, Right Arrow To move between menus.

Up Arrow, Down Arrow To move between commands.

A character key To choose the menu or command. The underlined character matchesthe one you type.

Enter To choose the selected menu name or command.

Esc To cancel the selected menu name, or to close the open menu.

DIALOG BOX KEYS

These keys are useful when working in a dialog box.

Alt-a character key To move to the option or group whose underlined letter or numbermatches the one you type.

Arrow Keys To move highlighted selections within list boxes.

Alt-Down Arrow To open a list.

Spacebar To select an item or cancel a selection in a list. Also to select orclear a check box.

Enter To carry out a command.

Esc or Alt-F4 To close a dialog box without completing the command.

Table 4-3 Microsoft Windows Keyboard Shortcuts

Page 186: Generator Relay Protection

1

3

A

B

C

4–29

Remote Operation – 4

4.7 IPSutil™ Communications Software

Figure 4-36 IPSutil Main Menu Flow

M-3890 IPSutilThe M-3890 IPSutil Communication software packageprovides communication with the Beckwith IntegratedProtection System® (IPS) for setting up the relays.Its main purpose is to aid in setting up IPS relaysthat are ordered without the optional front panel HMIinterface.

Installation and SetupIPSutil runs with the Microsoft® Windows 95 operatingsystem or above. Hardware requirements are thesame as those stated for IPScom®.

Page 187: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–30

InstallationAn installation utility has been provided as a part ofIPScom® and IPSutil™ programs. After installation,IPSutil can be run from the hard drive by choosingIPSUTIL.EXE.

System SetupConnect a null modem cable from COM1 of therelay to the PC serial port. IPSutil supports COM1port direct connection only. Modem connection isnot supported. IPSutil is not supported throughCOM2 or COM3 ports of the relay.

OverviewIPSutil helps in setting up IPS relays which wereordered without the optional front panel HMI interface.Units delivered without HMI’s are shipped with a setof factory default settings for various parametersthat the end user may wish to change. While theutility program is directed to users that do not haveHMI, users of HMI-provided relays can also useIPSutil to set various parameters. When IPSutil isstarted, a warning window appears:

Figure 4-37 Warning Message

After the user accepts the warning, the user canaccess the IPSutil main menu. The following sectionsdescribe each IPSutil menu items.

Comm Menu

The Comm menu allows the user to makeconnections to the relay. This is the first commandthe user must use to access the unit. After the userselects the Connect submenu item, theCommunications dialog box appears (See Figure4-41).

• Select the correct PC communication portwhere the null modem cable is connectedfor the relay.

• Select the baud rate of the relay. Factorydefault is 9600 baud.

• Select the access code resident in therelay. Factory default is 9999.

• Select “Open com”.

The following message window will be displayedshowing COM opened. Now, the title bar will displaythe relay model and the software version.

The Exit submenu allows you to quit IPSutil. If therelay was connected, this submenu disconnectsthe relay. When the relay was connected, if youhave made any changes for some parameters (forexample, baud rate, phase rotation) the followingmessage window appears.

Figure 4-38 IPSutility Reset Relay Message

Relay Comm CommandWhen Relay Comm command is selected, theRelay Comm Port Settings dialog box appears (SeeFigure 4-42). It allows you to set the relaycommunication ports COM1 or COM2/COM3 baudrate. For COM2/COM3, it allows you to set theprotocol and dead synch time. Additionally, forCOM2 and COM3, if you select MODBUS protocol,the dialog box allows you to enable the parityoption.

NOTE: If COM1 baud rate is changed and therelay is reset, the new baud rate must beused to communicate with COM1

Ethernet CommandWhen the Ethernet command is selected, theEthernet Settings dialog box appears (see Figure4-43.) This command allows the user to enable ordisable the ethernet connection and enable/setprotocols.

Clock CommandWhen the Clock command is selected, the “SetUnit Date/Time” dialog box appears (See Figure4-44). Date and Time can be changed and sent tothe relay. This dialog box allows you to start or stopthe clock in the relay.

Page 188: Generator Relay Protection

1

3

A

B

C

4–31

Remote Operation – 4

Security Menu

The Security Menu allows you to set thecommunication access code and the level accesscodes for the relay.

The Change Comm Access Code allows you toassign new communication access code to therelay. The range of the access code is 1 to 9999.Note that the access code 9999 is a factory default(See Figure 4-45).

NOTE: Setting the access code to 9999 disablessecurity.

The Change User Access Code allows you toassign three different levels of access code for therelay functions accessibility. The range of the levelaccess code is 1 to 9999 (See Figure 4-46).

CAUTION: This submenu allows you to changethe relay level access codes.

Miscellaneous Menu

The Miscellaneous menu allows you to set andmonitor some of the relay parameters.

The Setup command allows you to change theusers Logo information, test outputs, assigncommunication address and user control number,phase rotation, OK LED flash mode in the relay.Note that the highest number used for thecommunication address is 255 and the highestcontrol number allowed is 9999 (See Figure 4-47).

The Monitor Status command allows you to monitorand clear the error code counters, monitor the checksums, and to view inputs test status. Note thatpowerloss counter cannot be cleared.

Figure 4-39 Monitor Status Screen

The Calibration command provides the user withinstructions to recalibrate Nominal Frequency, ThirdHarmonic, (64F) Field Ground, and (64S) StatorProtection.

Figure 4-40 Calibration Dialog

COMMAND BUTTONS

Calibrate Sends the currently displayedinformation to the relay.

Cancel Returns you to the IPSutil main window.

Page 189: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–32

Figure 4-43 Ethernet Settings

COMMAND BUTTONS

Ethernet Enable/Disable: Allows user to enableand disable the Ehternet Port.

DHCP Protocol Enable/Disable: Allows the userto enable or disable the DHCP protocol. WhenDHCP protocol is enabled the the IP Address portionof the screen is grayed out. When DHCP protocol isdisabled the IP Address can be manually entered.

EGD Protocol Enable/Disable: Not available.

Protocol Selection MODBUS/Serconv: Providesthe user with the ability to select either MODBUSover TCP/IP or Serconv (BECO2200 over TCP\IP)protocol.

Save Saves values to the relay.

Cancel Returns you to the IPSutil main window.Any changes to the displayedinformation are lost.

Figure 4-44 Set Unit Date/Time Dialog Box

Help Menu

Under Help, the About... submenu provides youthe information on the IPSUtil™ version numbers.

Figure 4-41 Communication Dialog

COMMAND BUTTONS

Open COM Initiates communication with theprotective system by direct serialcommunication.

Close COM Discontinues communication with theprotective system.

Cancel Returns you to the IPSutil main window.Any changes to the displayedinformation are lost.

Figure 4-42 Relay Comm Port Settings

COMMAND BUTTONS

OK Sends the currently displayedinformation to the relay.

Cancel Returns you to the IPSutil main window.Any changes to the displayedinformation are lost.

Page 190: Generator Relay Protection

1

3

A

B

C

4–33

Remote Operation – 4

COMMAND BUTTONS

Stop Clock This toggles between start/stop the clockof the relay. The ‘Stop’ stops the clock inthe relay. The ‘Start’ resumes the clockin the relay.

Save When connected to the protectionsystem, the date and time informationon the display is sent to the relay.

Cancel Returns you to the IPSutil™ mainwindow. Any changes to the displayedinformation are lost.

There is a blue Time Sync LED mimic on the Set Date/Time dialog box (the LED is displayed as differentshading on a monochrome monitor). When this LED isblue, the relay is synchronized with the IRIG-B signaland the Time field is grayed out, indicating that this fieldcan’t be changed. But the Date field can be changed(by editing and pressing Save). When the LED is notblue, the relay is not time-synchronized and therefore,both the Date and Time fields can be changed. Thetime field in the dialog box is not updated continuously.The time at which the dialog box was opened is thetime that is displayed and remains as such. This is truewhether the relay is synchronized with the IRIG-B signalor not.

Figure 4-45 Change Communication AccessCode Dialog Box

COMMAND BUTTONS

OK Sends the currently displayedinformation to the relay.

Cancel Returns you to the IPSutil™ mainwindow. Any changes to the displayedinformation are lost.

Figure 4-46 Change User Access CodeDialog Box

COMMAND BUTTONS

OK Sends the currently displayedinformation to the relay.

Cancel Returns you to the IPSutil main window.Any changes to the displayedinformation are lost.

Figure 4-47 Setup Dialog Box

COMMAND BUTTONS

OK Sends the currently displayedinformation to the relay.

Cancel Returns you to the IPSutil main window.Any changes to the displayedinformation are lost.

NOTE: Output Test is not available on someversions of the M-3425A Relay.

Page 191: Generator Relay Protection

1

3

A

B

C

M-3425A Instruction Book

4–34

This Page Left Intentionally Blank

Page 192: Generator Relay Protection

Installation – 5

5–1

5 Installation

5.1 General Information .................................................................... 5–1

5.2 Mechanical/Physical Dimensions .............................................. 5–2

5.3 External Connections ................................................................. 5–8

5.4 Commissioning Checkout ........................................................ 5–14

5.5 Circuit Board Switches and Jumpers ...................................... 5–19

5.6 Low Frequency Signal Injection Equipment ............................ 5–23

5.1 General Information

NOTE: Prior to installation of the equipment, it isessential to review the contents of thismanual to locate data which may be ofimportance during installation procedures.The following is a quick review of thecontents in the chapters of this manual.

The person or group responsible for the installationof the relay will find herein all mechanical informationrequired for physical installation, equipment ratings,and all external connections in this chapter. Forreference, the Three-Line Connection Diagrams arerepeated from Chapter 2, Application. Further, acommissioning checkout procedure is outlined usingthe HMI option to check the external CT and VTconnections. Additional tests which may be desirableat the time of installation are described in Chapter6, Testing.

Service Conditions and Conformity to CEStandardStating conformance to CE Standard EN 61010-12001, operation of this equipment within the followingservice conditions does not present any knownpersonnel hazards outside of those stated herein:

• 5° to 40° Centigrade

• Maximum relative humidity 80% fortemperatures up to 31° C, decreasing ina linear manner to 50% relative humidityat 40° C.

This equipment will function properly, and at statedaccuracies beyond the limits of this CE Standard, asper the equipment's specifications, stated in thisInstruction Book.

It is suggested the terminal connections illustratedhere be transferred to station one-line wiring andthree-line connection diagrams, station panel drawingsand station DC wiring schematics.

If during the commissioning of the M-3425A GeneratorProtection Relay, additional tests are desired, Chapter6, Testing, may be consulted.

The operation of the relay, including the initial setupprocedure, is described in Chapter 3, Operation,for HMI front panel users and in Chapter 4, RemoteOperation, when using a personal computer. Section3.1, Front Panel Controls, details the front panelcontrols.

Section 3.2, Initial Setup Procedure/Settings, detailsthe HMI setup procedure. This includes detailsnecessary for input of the communications data, unitsetup data, configure relays data, the individualsetpoints and time settings for each function, andoscillograph recorder setup information. Section 3.5,Status/Metering, guides the operator through thestatus and metering screens, including monitoringthe status. Section 3.6 includes information on viewingthe target history.

Page 193: Generator Relay Protection

M-3425A Instruction Book

5–2

NOTE: Dimensions in brackets are in centimeters.

Figure 5-1 M-3425A Horizontal Chassis Mounting Dimensions Without Expanded I/O (H1)

5.2 Mechanical/PhysicalDimensions

Figures 5-1 through 5-6 contain physical dimensionsof the relay that may be required for mounting theunit on a rack.

Standard 19" Horizontal Mount Chassis

19.00[48.26]

17.50[44.5]

17.50[44.5]

ACTUAL

5.21[13.23]

ACTUAL

0.40 [1.02] X 0.27[0.68] Slot (4X)

10.20[25.91]

19.00[48.26]

18.34[46.58]

0.33[0.84]

1.48[3.8]

2.25[5.72]

Page 194: Generator Relay Protection

Installation – 5

5–3

Optional Vertical Mount Chassis

1.67[4.24]

19.00[48.26]

18.34[46.58]

2.25[5.72]

0.28 [0.71]Dia. (4X)

17.68[44.91]

5.59[14.20]Actual

1.70[4.32]

2.25[5.72]

10.20[25.91]

COM 1

M-3425AGENERATORPROTECTION

TARGETS

OUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

OUTPUTSOUT 7

OUT 8

EXIT ENTER

TARGET DIAG

TIME

OSC.TRIG

SYNC

BRKRCLOSED

OKRELAY

TARGETRESET

PS 2 PS 1

17.5[44.45]

ACTUAL

5.65[14.40]

Recommended cutout when relay is not used asstandard rack mount and is panel cut out mounted.

19.00[48.26]

17.50[44.5]

NOTE: Dimensions in brackets are in centimeters.

Figure 5-2 M-3425A Vertical Chassis Mounting Dimensions Without Expanded I/O (H2)

Page 195: Generator Relay Protection

M-3425A Instruction Book

5–4

Figure 5-3 M-3425A Mounting DimensionsHorizontal and Vertical Chassis With Expanded I/O

!

""#!

$# %

%&% %%' %&% ! %

" ('!

'"''(!

'!

(#'

##( !

(# '(!

" # '

"( #

)

*

%

%

%#

%

%

%'

%

%(

Page 196: Generator Relay Protection

Installation – 5

5–5

!" #!

!" $#!%!

!&'

Figure 5-4 M-3425A Panel Mount Cutout Dimensions

Page 197: Generator Relay Protection

M-3425A Instruction Book

5–6

()*+,+-./+0

+1.**+23+3 )2+/4,.4,(*+20(.20

&(*+20(.20(25-)16+,0)-+(21+2,(*+,+-0

Figure 5-5 Mounting Dimensions for GE L-2 Cabinet (H3 and H4)

Page 198: Generator Relay Protection

Installation – 5

5–7

Figure 5-6 (H5) Mounting Dimensions

FRONT VIEW (H5)

20.78[52.78]

19.89[50.52]

17.72[45.00]

9.94[25.24]

2.15[5.47]

.45[1.13] .41

[1.04]1.13[2.87]

6.69[16.99]

7.81[19.84]

8.63[21.92]

9.70[24.64]

9.70[24.64]

3.53[8.97]

3.53[8.97]

∅ .28[∅ 0.71]

10 HOLES

Page 199: Generator Relay Protection

M-3425A Instruction Book

5–8

5.3 External Connections

88888WARNING: The protective grounding terminalmust be connected to an earthed ground anytimeexternal connections have been made to theunit.

88888 WARNING: ONLY DRY CONTACTS must beconnected to inputs (terminals 5 through 10with 11 common and terminals 68 through 75with 66 and 67 common) because these contactinputs are internally wetted. Application ofexternal voltage on these inputs may result indamage to the units.

88888 WARNING: Do not open live CT circuits. LiveCT circuits should be shorted prior todisconnecting CT wiring to the M-3425A. Deathor severe electrical shock may result.

CAUTION: Mis-operation or permanent damagemay result to the unit if a voltage is applied toTerminals 1 and 2 (aux) that does not match theconfigured Trip Circuit Monitoring input voltage.

To fulfill requirements for UL and CSA listings,terminal block connections must be made with No.12 AWG solid or stranded copper wire inserted inan AMP #324915 (or equivalent) connector, andwire insulation used must be rated at 60° C minimum.

Power SupplyWhen the M-3425A without expanded I/O is equippedwith the optional second power supply (Figure 5-7) ,the power source may be the same or two differentsources.

3 AMP,2 5 0 V ( 3 AB)3 AMP,2 5 0 V ( 3 AB)

F4

PS2

F2

PS1I c

58 59

+ -+ -

2P S SP 1

60 61 62 63

F1

F3

-+ + -

55 2 6865-18 6

68 5 21 -8 5

5

Figure 5-7 Optional Dual Power Supply

When the M-3425A with expanded I/O is equippedwith two (not redundant) power supplies, the powersupplies must be powered from the same source.

3 AMP,2 5 0 V ( 3 AB)3 AMP,2 5 0 V ( 3 AB)

F4

PS2

F2

PS1I c

58 59

+ -

2P S SP 1

60 61 62 63

F1

F3

-+ + -

55 2 6865-18 6

68 5 21 -8 5

5

Figure 5-8 Expanded I/O Power Supply

Grounding RequirementsThe M-3425A is designed to be mounted in anadequately grounded metal panel, using groundingtechniques (metal-to-metal mounting) and hardwarethat assures a low impedance ground.

Unit IsolationSensing inputs should be equipped with test switchesand shorting devices where necessary to isolatethe unit from external potential or current sources.

A switch or circuit breaker for the M-3425A's powershall be included in the building installation, and shallbe in close proximity to the relay and within easyreach of the operator, and shall be plainly marked asbeing the power disconnect device for the relay.

Insulation CoordinationSensing Inputs: 60 V to 140 V, Installation CategoryIV, Transient Voltages not to exceed 5,000 V.

Torque Requirements• Terminals 1–34 & 66–105: 7.5 in-lbs,

minimum, and 8.0 in-lbs, maximum

• Terminals 35–65: 8.5 in-lbs, minimum,and 9.0 in-lbs, maximum

Relay OutputsAll outputs are shown in the de-energized state forstandard reference. Relay standard reference is definedas protective elements in the non-trip, reconnectionand sync logic in the non-asserted state, or power tothe relay is removed. Output contacts #1 through #4are high speed operation contacts. The power supplyrelay (P/S) is energized when the power supply is OK.The self-test relay is energized when the relay hasperformed all self-tests successfully.

Replacement FusesF1–F4 replacement fuses must be fast-acting3 Amp, 250 V (3AB) Beckwith Electric Part Number420-00885.

Page 200: Generator Relay Protection

Installation – 5

5–9

Figu

re 5

-9Ex

tern

al C

onne

ctio

ns

NO

TE

S:

1.S

ee S

ectio

n 2.

3, S

etpo

ints

and

Tim

e S

ettin

gs, s

ubse

ctio

n fo

r 64

B/F

Fie

ld G

roun

d P

rote

ctio

n.

2.B

efor

e m

akin

g co

nnec

tions

to th

e T

rip C

ircui

t Mon

itorin

g in

put,

see

Sec

tion

5.5,

Circ

uit B

oard

Sw

itche

s an

d Ju

mpe

rs, f

or th

e in

form

atio

nre

gard

ing

setti

ng T

rip C

ircui

t Mon

itorin

g in

put v

olta

ge. C

onne

ctin

g a

volta

ge o

ther

than

the

volta

ge th

at th

e un

it is

con

figur

ed to

may

resu

ltin

mis

-ope

ratio

n or

per

man

ent d

amag

e to

the

unit.

3.8888 8

WA

RN

ING

: ON

LY

DR

Y C

ON

TA

CT

S m

ust

be

con

nec

ted

to

inp

uts

(te

rmin

als

5 th

rou

gh

10

wit

h 1

1 co

mm

on

an

d t

erm

inal

s 68

thro

ug

h 7

5 w

ith

66

and

67

com

mo

n) b

ecau

se th

ese

con

tact

inp

uts

are

inte

rnal

ly w

ette

d. A

pp

licat

ion

of e

xter

nal

vo

ltag

e o

n th

ese

inp

uts

may

res

ult

in d

amag

e to

the

un

its.

4.8888 8

WA

RN

ING

: Th

e p

rote

ctiv

e g

rou

nd

ing

term

inal

mu

st b

e co

nn

ecte

d to

an

ear

thed

gro

un

d a

ny

tim

e ex

tern

al c

on

nec

tio

ns

hav

eb

een

mad

e to

the

un

it.

!

(

"

#

#

)

$ $#'

'"

(+,

-

./

###

*)

* 0

*)

)

/

'(

(

"(

(#(

( ((

('(

(("

""

""

"#"'

""

"""(

#

1

(#/

%% %%.".#"#.%%. .

2

#'#'#'#'####

#(#(#(#(####

#"#"#"#"

# # # #

' -&

'

'

(

"

/

$

#

&

- -

- -

-

-

(

#

3$

$'

3

#

456

-

#

(

'

"

"

#.-4#

6

#.-4#

6

(

#

'

'

'"

''#

/#

/

#

/$

5

(

#

'

(

"

(

'

7

'

/

#

#

'

#

"(

##

/

# ##

"

'(''

''"

#

#

0

(0

0

'

((

'$

('

(

'

$ '

33

$$

-

'$

-.2'

)8

9%

$#

%%%%%%%%%%%%%%%%%%%%%%%/*9%$

)8

')8

.

.

' /

Page 201: Generator Relay Protection

M-3425A Instruction Book

5–10

52Gen

A B C

Generator

58 59

56 57

54 55

OtherRelays

R45 44

M-3425A

M-3425A

WARNING: ONLY dry contact inputs must beconnected because these contact inputs areinternally wetted. Application of externalvoltage on these inputs may result indamage to the units.NOTE : M-3425A current terminal polarity marks( . ) indicate "entering" current direction whenprimary current is "from" the generator to thesystem. If CT connections differ from thoseshown, adjust input terminals.

M-3921Field Ground

Coupler Module

10

1152b

M-3425A

43 41 3942 40 38

M-3425A

Two Vt Open-DeltaConnection

43 41 3942 40 38

M-3425A

Three VT Wye-WyeConnection

434139 424038

M-3425A

Three VT Wye-WyeAlternate Connection

A

B

C

A

B

C

55 54

57 56

59 58

M-3425A

55 54

57 56

59 58

M-3425AOther

RelaysOther

Relays

a b c

a b c a b c

OR OR

High Impedance Grounding

52 53

M-3425A

R Low Impedance Grounding

OR

50 51

48 49

46 47

M-3425AOtherRelays

1

1

1

A B C

Example of Control/Output Connections

M-3425A

PowerSupply

52G

+

-

TRIPALARM

SELF-TEST

FAILUREALARM

POWEROK

STATUSALARM

VTFUSELOSS

EXTERNALINPUTS

ALARMOUTPUTS

CONTROLOUTPUTS

TRIPOUTPUT

BREAKERFAILUREINITIATE

52Ga

5

3 336

OSCILLOGRAPHRECORDER

INITIATE

60FL52b

2

60 6261 63 11 10

4

+

-

DC: 24V 48V

ORDC: 110V 125V 220V 250VAC: 110V 120V 230V 240V

16

15

12

13

4

5

6

Alarm output can be grouped to a single alarmat the discretion of user.Available control output to service other relaysfor VT Fuse Loss can be designated.Input contact number is designated by user.

2

3

1 Wire to split phase differential CTs foruse with 50DT split phase function.Required generator breaker status input(52b). Contact is closed when generatorbreaker is open. Use unit breakercontact if no generator breaker present.Output contact pairs designated byuser.

Figure 5-10 Three-Line Connection Diagram

Page 202: Generator Relay Protection

Installation – 5

5–11

52Gen

A B C

Generator

10

1152b

M-3425A

VX

43

41

39

42

40

38

M-3425A

Three VT Wye-WyeConnection

A B C

OR

VX

64

65

M-3425A

64

65

M-3425A

VX

Two VT Open-DeltaConnection

43

41

39

42

40

38

M-3425A

OR

A B C

Used when GeneratorSide VTs are connected

Line-Ground.

Used when Generator Side VTsare connected Line-Line

Used for Sync Check (25)

Figure 5-11 Function 25 Sync Check Three-Line Connection Diagram

Page 203: Generator Relay Protection

M-3425A Instruction Book

5–12

52Gen

A B C

Generator

10

1152b

M-3425A

a b c

52 53

M-3425A

R Low Impedance Grounding

65

64

M-3425A

A B C

Line to NeutralVoltage Rated

Cable

R

R45 44

M-3425A

High Impedance Grounding

OR

VX used for turn-to-turnfault protection (59X)

VX

Figure 5-12 Function 59X Turn to Turn Fault Protection Three-Line Connection Diagram

Page 204: Generator Relay Protection

Installation – 5

5–13

52Gen

A B C

Generator

10

1152b

M-3425A

a b c

52 53

M-3425A

R Low Impedance Grounding

A

B

C

I N input can be connectedeither at Neutral or as Residual.

I N input can be connectedeither at Neutral or as Residual.

OR

R45 44

M-3425A

High Impedance Grounding

65 64

M-3425A

R

59XBus Ground

65

64

M-3425A

A B C

R

67N, 59DConnection

53

52

M-3425A

67NConnection

Residual CT

Bus Section

VX

VX can be used for both 67N and59D if connected in this manner.

Figure 5-13 Function 67N, 59D, 59X (Bus Ground) Three-Line Connection Diagram

Page 205: Generator Relay Protection

M-3425A Instruction Book

5–14

7. Press ENTER to display Third HarmonicDifferential Ratio:

3RD HARMONIC DIFF RATIO__________

Press ENTER once more to display theline side Third Harmonic Voltage:

3RD HARMONIC 3V0 VOLT__________

8. Press ENTER to display Stator LowFrequency Injection (20 Hz) Voltage:

STATOR LOW FREQUENCY INJECT._____ Volts

9. Display positive, negative and zerosequence voltages. Press ENTER untilthe unit displays:

POS SEQUENCE VOLTAGE_____ Volts

The positive sequence voltage should beV

POSy V

A y V

B y V

C or V

AB y V

BC y V

CA.

10. Press ENTER until the unit displays:

NEG SEQUENCE VOLTAGE____ Volts

The negative sequence voltage shouldbe V

NEGy 0.

11. Press ENTER until the unit displays:

ZERO SEQUENCE VOLTAGE____ Volts

The zero sequence voltage should beV

ZEROy0.

If the negative sequence voltage showsa high value and the positive sequencevoltage is close to zero, the phasesequence is incorrect and proper phasesmust be reversed to obtain correct phasesequence. If the phase sequence isincorrect, frequency- and power-relatedfunctions will not operate properly andthe Frequency Status menu will readDISABLE.

If positive, negative and zero sequencevoltages are all present, check the polaritiesof the VT connections and changeconnections to obtain proper polarities.

5.4 Commissioning Checkout

During field commissioning, check the following toensure that the CT and VT connections are correct.

1. Press ENTER. After a short delay, theunit should display

VOLTAGE RELAYVOLT curr freq v/hz pwr

2. Press the right arrow button until the unitdisplays:

STATUS config sys STAT

3. Press ENTER. The unit should display:

VOLTAGE STATUSVOLT curr freq v/hz

4. Press ENTER. The unit should displayeither V

A, V

B, V

C (line-to-ground

connections) or VAB

, VBC

, VCA

(line-to-lineor line-ground to line-line connections).

PHASE VOLTAGEA= B= C=

Compare these voltages with actualmeasurements using a voltmeter. If thereis a discrepancy, check for looseconnections to the rear terminal block ofthe unit. If line-ground to line-line voltageselection is used, the voltages displayedare S3 times of the line-ground voltagesapplied.

5. Press ENTER to display the NeutralVoltage:

NEUTRAL VOLTAGE_____ Volts

The neutral voltage should be near zerovolts.

6. Press ENTER to display VX Voltage:

VX VOLTAGE_____ Volts

Page 206: Generator Relay Protection

Installation – 5

5–15

12. Press ENTER until the unit displays:

3RD HARMONIC NTRL VOLT_____ Volts

13. Press ENTER until the unit displays:

FIELD GND MEAS. CIRCUIT_______ mV

14. Press EXIT until the unit displays:

VOLTAGE STATUSVOLT curr freq v/hz

15. Press the right arrow to display:

CURRENT STATUSvolt CURR freq v/hz

16. Press ENTER to display line currents(I

A, I

B, I

C). The unit should display:

PHASE CURRENTA= B= C=

Compare these currents with themeasured values using a meter. If thereis a discrepancy, check the CTconnections to the rear terminal block ofthe unit.

17. Press ENTER for the unit to display:

PHASE CURRENTa= b= c=

Compare these currents with themeasured values using a meter. If thereis a discrepancy, check the CTconnections to the rear terminal block ofthe unit.

18. Press ENTER for the unit to display:

DIFFERENTIAL CURRENTA= B= C=

Differential current should be near zeroamps. If a significant amount ofdifferential current is present, check theCT polarities.

19. Press ENTER for the unit to display:

NEUTRAL CURRENT______ Amps

20. Press ENTER for the unit to display:

GND DIFFERENTIAL CURRENT______ Amps

21. Press ENTER for the unit to display:

STATOR LOW FREQ INJECT.I= ___ mAmps

22. Press ENTER to display:

POS SEQUENCE CURRENT______ Amps

The positive sequence current should beIPOS

y Iay I

b y I

c.

23. Press ENTER to display:

NEQ SEQUENCE CURRENT______ Amps

Negative sequence current should nearzero amperes.

24. Press ENTER to display:

ZERO SEQUENCE CURRENT______ Amps

The zero sequence current should beIZEROy0 A. If a significant amount ofnegative or zero sequence current(greater than 25% of I

A, I

B, I

C,) then

either the phase sequence or thepolarities are incorrect. Modifyconnections to obtain proper phasesequence and polarities.

25. Press ENTER to display:

F49 THERMAL CURRENT #1______ Amps

Press ENTER once more to display:

F49 THERMAL CURRENT #2______ Amps

Page 207: Generator Relay Protection

M-3425A Instruction Book

5–16

26. Press EXIT, then the Right arrow todisplay:

FREQUENCY STATUSvolt curr FREQ v/hz

27. Press ENTER to display:

FREQUENCY________ Hz

28. Press ENTER to display:

RATE OF CHANGE FREQUENCY___ Hz/Sec

29. Press EXIT, then right arrow to display:

V/HZ STATUSvolt curr freq V/HZ

30. Press ENTER to display:

VOLTS PER HERTZ_________ %

31. Press EXIT, then right arrow to display:

POWER STATUS POWR imped sync brkr

32. Press ENTER to display real power andcheck its sign. The unit should display:

REAL POWER________ PU _______ W

The sign should be positive for forwardpower and negative for reverse power. Ifthe sign does not agree with actualconditions, check the polarities of thethree neutral-end CTs and/or the PTs.

33. Press ENTER for the unit to display:

REACTIVE POWER________ PU _____ VAr

34. Press ENTER for the unit to display:

APPARENT POWER________ PU ______ VA

35. Press ENTER to display:

POWER FACTOR__ Lag/Lead

36. Press EXIT and then right arrow todisplay:

IMPEDANCE STATUS powr IMPED sync brkr

37. Press ENTER to display:

IMPEDANCE Zab (Ohms)R= X=

Press ENTER once more to display:

IMPEDANCE Zbc (Ohms)R= X=

Press ENTER once more to display:

IMPEDANCE Zca (Ohms)R= X=

38. Press ENTER to display:

IMPEDANCE POS SEQ (Ohms)R= X=

39. Press ENTER to display:

FIELD GND RESISTANCE______ Ohms

40. Press EXIT and then right arrow todisplay:

SYNC CHECK STATUS powr imped SYNC brkr

41. Press ENTER to display:

PHASE ANGLE___ DEGREES

42. Press ENTER to display:

DELTA VOLTAGE_____ Volts LO

Page 208: Generator Relay Protection

Installation – 5

5–17

43. Press ENTER to display:

DELTA FREQUENCY_____ Hz HI

44. Press EXIT, then right arrow until unitdisplays:

BREAKER MON ACC. STATUS power imped sync BRKR

45. Press ENTER to display:

BREAKER MON ACC. STATUSA= A-cycles

Press ENTER to cycle through Acc.Status screens for B and C.

46. Press EXIT, then right arrow until unitdisplays:

81A ACCUMULATORS STATUS FREQ_ACC i/o timer

47. Press ENTER to display:

81A #1 ACCUMULATORS STAT____ Cycles

Pressing ENTER will display a statusscreen for each of the six elements.

48. Press ENTER to display:

81A #1 ACC. STARTUP TIME00-20XX 00:00:00:000

Pressing ENTER will display a statusscreen for each of the six elements.

49. Press EXIT, then right arrow until unitdisplays:

IN/OUT STATUS freq_acc I/O timer

50. Press ENTER to display:

FL I6 I5 I4 I3 I2 I1

Press ENTER again to view outputs:

O8 O7 O6 O5 O4 O3 O2 O1

51. Press EXIT, then arrow button to display:

TIMER STATUS freq_acc i/o TIMER

52. Press ENTER to display:

51V DELAY TIMERA= B= C=

53. Press ENTER to display:

51N DELAY TIMER_________ %

54. Press ENTER to display:

46IT DELAY TIMER_________ %

55. Press ENTER to display:

24IT DELAY TIMER_________ %

56. Press EXIT, then right arrow until unitdisplays:

RELAY TEMPERATURE TEMP count powerup

57. Press ENTER to display:

RELAY TEMPERATURE________ C

Page 209: Generator Relay Protection

M-3425A Instruction Book

5–18

58. Press EXIT, then right arrow until unitdisplays:

COUNTERS temp COUNT powerup

59. Press ENTER to display:

OUTPUT COUNTER 1__________

Pressing ENTER will display a statusscreen for each of the 23 outputs.

60. Press ENTER to display:

ALARM COUNTER__________

61. Press EXIT, then right arrow until theunit displays:

TIME OF LAST POWER UP temp count POWERUP

62. Press ENTER to display:

TIME OF LAST POWER UP05-Jan-2003 20:39:29

NOTE: The CT and VT polarities can be easilyverified by looking at the oscillographicwaveforms, using M-3801D IPSplot®

PLUS analysis software.

63. Press EXIT, then right arrow until theunit displays:

ERROR CODES ERROR check

64. Press ENTER to display:

ERROR CODES (LAST)__________

Pressing ENTER will display a statusscreen for three previous error codes.

65. Press ENTER to display:

RST LOCATION0000 CBR=___ BBR=___

66. Press ENTER to display:

COMM ERROR CODE (LAST)__________

67. Press ENTER to display:

COMM PACKET COUNTER__________

68. Press ENTER to display:

COMM RX ERROR COUNTER__________

69. Press ENTER to display:

SELFTEST COUNTER__________

70. Press ENTER to display:

RESET COUNTER__________

71. Press ENTER to display:

POWERLOSS COUNTER__________

72. Press EXIT, then right arrow until theunit displays:

CHECKSUMS error CHECK

73. Press ENTER to display:

SETPOINTS CHECKSUMEECS= BBCS= CAL=

74. Press ENTER to display:

CALIBRATION CHECKSUMEECS= BBCS= CAL=

75. Press ENTER to display:

ROM CHECKSUM__________

Page 210: Generator Relay Protection

Installation – 5

5–19

5.5 Circuit Board Switches andJumpers

See Figure 5-14, M-3425A Circuit Board for Jumperand Switch locations.

Accessing Switches and Jumpers88888 WARNING: Operating personnel must notremove the cover or expose the printed circuitboard while power is applied. IN NO CASE maythe circuit-based jumpers or switches be movedwith power applied.

88888 WARNING: The protective grounding terminalmust be connected to an earthed ground anytime external connections have been made tothe unit. See Figure 5-9, Note #4.

CAUTION: This unit contains MOS circuitry,which can be damaged by static discharge. Careshould be taken to avoid static discharge on worksurfaces and service personnel.

1. De-energize the M-3425A.

2. Remove the screws that retain the frontcover.

3. Remove the "J" connectors from thecorresponding plugs, P4, 5, 6, 7, 9 and11.

4. Loosen the two circuit board retentionscrews (captured).

5. Remove the circuit board from thechassis.

6. Jumpers J5, J18, J20, J21, J22, J46,J60, and J61 are now accessible. SeeFigure 5-13, M-3425A Circuit Board forlocations.

7. Dipswitch SW1 is now accessible. SeeFigure 5-13 for location.

8. Insert circuit board into chassis guidesand seat firmly.

9. Tighten circuit board retention screws.

10. Reconnect "J" connectors tocorresponding plugs.

11. Reinstall cover plate.

REPMUJ NOITISOP NOITPIRCSED

5JBotA 2MOC6nipnolangisLTTB-GIRIdetaludomeD

CotB )tluafeD(CNBlangisB-GIRIdetaludoM

81JBotA detresnirotsisernoitanimretmho0023MOC

CotB )tluafeD(noitanimreton3MOC

64JBotA 1MOChtiwetarduaBserahs3MOC

CotB )tluafeD(2MOChtiwetarduaBserahs3MOC

06JBotA )tluafeD(2MOCfo1nipotlangisDCDstcennoC

CotA 2MOCfo1nipotV51+stcennoC

16JCotB 2MOCfo9nipotV51-stcennoC

BotA )tluafeD(taolf9nip2MOC

NOTE: Short circuit protection (100 ma limit) is incorporated on pins 1 and 9 when used for +/- 15V.

Table 5-1 Jumpers

Page 211: Generator Relay Protection

M-3425A Instruction Book

5–20

TCELESEGATLOVTUPNIROTINOMTIUCRICPIRT

EGATLOVTUPNI 02JREPMUJNOITISOP

12JREPMUJNOITISOP

22JREPMUJNOITISOP

cdV42 BotA BotA BotA

cdV84 CotB BotA BotA

cdV521 CotB CotB BotA

*cdV052 CotB CotB CotB

.yrotcafmorfdeppihssatluafeD*

Table 5-3 Trip Circuit Monitor Input Voltage Select Jumper Configuration

1WShctiwspiD

1 2 3 4

X X X )pu(nepO

X )nwod(desolC

pu3 pu4 edoMnuR

pu3 nwod4 woleBnoituaCeeS*tluafedotMORPEEezilaitinI

nwod3 pu4 *noitacinummoCdnasedoCsseccAezilaitinI

nwod3 nwod4 esUyrotcaF

pu2 )tluafeDyrotcaF(elbasiDetadpUhsalF

nwod2 elbanEetadpUhsalF

pu1 tinUylppuSrewoPlauD

nwod1 tinUylppuSrewoPelgniS

nehwthgillliwDELcitsongaiDehtdnaffosniamerthgilDELKOeht,purewopretfA*detelpmocylirotcafsitasneebsahnoitarepo ..

Switches should not be changedwhile unit is energized.

CAUTION: A loss of calibration, setpoints, and configuration will occur when the EEPROM is initialized todefault.

Table 5-2 Dip Switch SW-1

Page 212: Generator Relay Protection

Installation – 5

5–21

Figu

re 5

-14

M-3

425A

Cir

cuit

Boar

d

(

"

'

:"

'

"

'

(

(

:(

"

*)

"

; $'

$" %-

"

3

-

:"

'

'

(

(#

#

'(

(

'"

'

''

:

:

:

"'

"

(

#

"

##'

(

#

-"

#

'

#

(

'

(#

#(

"

-

'(

'"

-

-

'

-'

#

-

'

-(

''

(

'

#

'

'

' '

'

( (

"

'

(

'

"

#

#(

''

'#

#

(

("

((

#(

3(

3

'

3

#

##

#

'

#

#

"'

3"

'

:'

"

#

(

('

:

#

:'

"

"#

#

"

"

"

"

"

'

#

#

'( '"

#'

:

:

'

"

"

:(

(

(

"

3

3

3

##

# "

# 3

#"

:'

#

"#

(

'

'

'

#

'#

'

"

"

(

#

#

#

#'

'

:'"

3 #

:'(

#

3

#

##

#

(

"

3

#1

'

"

" #

'

(

"

(

'

''

'

'(

'

(

(

'

#

'

#

"# '

'

#

"

"

'

#

3

#

3

#

3

(

"

(

#

3

#

#

'

(

#

'

#

#

(#

:'#

:'

#

3

(

(

#'

'

3

#(

#

" "

(

:'

"

(

'

#

#

#

#

#

""

#

#'

(

"

#

#"

#

#

-

-

-

(

'

-"

-(

#

-'

#

-

#(

##

-

-

-#

-

-#

-

#

3

#

1

'#

'

"

"

:#

:

"(

'

'

:(

#

(

(

"

3

#

:

(

'

#

"

1(

:#

"

"

"

'

1

'

: '

(

#

"

'

#

#

#'

#

3

(

'

#

"

(

#

: "

: (

(

(

#

#

:

:

:#

'

'

'

"

#

'

(

#

(

'

'

(

#

:

"

'

#

(

#

:

:"'

:

''

#

#

#

'

#

'

#(

##

#

'

'

'

3

#

(

#(

:'

'

:

:

*

#

#

1#

'

#

3

'

3

:

(

3

"

..$

#

#

:#

3

'

3 ('

'

:"

3

( '

'#

#

(

3

#

:'

:

:

:

"

:

'

:'

(

1

1

:

3

'

"

##

(

(

(

1

##

(

3

"

"

:

3

""

:(

:

:

"

*

3

'

3

(

(

##

1

3

"

#

3

3

"(

(

'

3

3

"

:' :

:'

:

:

:

:(

: '

*

Page 213: Generator Relay Protection

M-3425A Instruction Book

5–22

;% $#

$"(%-%#

''

"

(

(

"#

-

'

-

-#

#(

/"

" (

-

#

#

#"

#

/'

-

#

#

"(

(#

#(

"

""

(

/

-#

/

-(

/(

-"

(

##'(

#

'"

#

(

"

'#

-(

/

-

/#

/

-

'

#(

"

'

"

"

#

#'

(

"

#

"'

#"

#

'

#

#

(

"

'

(

#

#

/

(

'

-

/

#

##

/

(

#

'#

'

(

'

'"

#'

"#

#

'

'(

(

'

''

#

'

"

'

'

'

'

(

(

#

(

'

"

#

'

(

"

"

(

"

'

#'

#

-

-

(

-

-

"

-

"

-

'

-'

-

-'

-"

"

-

#

-#

(

'

"

"

#

'

'

#

#

#

#

#

#

#"

#

##

'

#

#

#

'

#

'

"

(

#

3

3

3

3

3

3

3

3

3

%

*)

3

3

3

3

3

3

3

3

3

Figu

re 5

-15

M-3

425A

Cir

cuit

Boar

d (E

xpan

ded

I/O)

Page 214: Generator Relay Protection

Installation – 5

5–23

RN

1B1

1A1

1B4

1A3 1A4

20 HzBand Pass

Filter

20 HzGenerator

4A1[11]

Bl

Supply VoltageDC 120 V ac

UH+ L1

UH- L2

L3

ExternalBlock

DeviceOperative

44 45

M-3425A

52 53

400A5A

L Kl k

Max. 200 V

V N

I N

NeutralGrounding

Transformer

WiringShielded

20 Hz CT400/5 A

59N

High *Voltage

LowVoltage

* For applications with a transformer secondary rating that will result in 50/60 Hz phaseground fault voltages >200 V ac, use the "High Voltage" connection for the 59N Function.

Connection terminals forModel A00/CC shown.Connection terminals forModel A00/DE shown inbrackets [ ].

4A3[12]

1A1[1]

1A2[2]

1A3[3]

2A1[6]

2A3[8]

3A2[7]

3A3[9]

3A1[5]

M-03312:1 Control

Transformer

H2

H5

220 V ac

L2

L5

Figure 5-16 Low Frequency Signal Injection Equipment Typical Connections

5.6 Low Frequency SignalInjection Equipment

Figure 5-16 represents typical connections for theLow Frequency Signal Injection Equipment. Figures5-16 through 5-22 illustrate equipment mountingdimensions.

Page 215: Generator Relay Protection

M-3425A Instruction Book

5–24

Figure 5-17 20 Hz Frequency Generator Housing Panel Surface Mount

Page 216: Generator Relay Protection

Installation – 5

5–25

Figure 5-18 20 Hz Frequency Generator Housing Panel Flush Mount

Page 217: Generator Relay Protection

M-3425A Instruction Book

5–26

Figure 5-19 20 Hz Band Pass Filter Housing Panel Surface Mount

Page 218: Generator Relay Protection

Installation – 5

5–27

Figure 5-20 20 Hz Band Pass Filter Housing Panel Flush Mount

Page 219: Generator Relay Protection

M-3425A Instruction Book

5–28

Figure 5-21 20 Hz Measuring Current Transformer 400-5 A CT

Figure 5-22 M-0331 2:1 Control Transformer

JUMPERS BETWEEN(4,5) AND (2,3)

JUMPERS BETWEEN(2,3) AND (4,5)

1 2 3 4 5 6

123456

4.94[12.55]

2.75[6.99]

Four Slots0.22 X 0.75

[0.56 X 1.91]

3.38[8.6]

4.0[10.16]

3.81[9.68]

Page 220: Generator Relay Protection

6–1

Testing – 6

6 Testing

6.1 Equipment/Test Setup ............................................................... 6–2

6.2 Functional Test Procedures ....................................................... 6–6Power On Self Tests ................................................................. 6–721 Phase Distance ..................................................................... 6–824 Volts per Hertz ...................................................................... 6–925D/25S Sync Check .............................................................. 6–1227 Phase Undervoltage ............................................................ 6–1627TN Third-Harmonic Undervoltage, Neutral ........................... 6–1732 Directional Power, 3-Phase ................................................ 6–2140 Loss of Field ....................................................................... 6–2446 Negative Sequence Overcurrent Definite Time ................. 6–2646 Negative Sequence Overcurrent Inverse Time ................. 6–2749 Stator Overload ................................................................... 6–2850 Instantaneous Phase Overcurrent ...................................... 6–3050BF/50BF-N Breaker Failure .................................................. 6–3150/27 Inadvertent Energizing ................................................... 6–3350DT Definite Time Overcurrent for Split-Phase Differential ... 6–3450N Instantaneous Neutral Overcurrent .................................. 6–3551N Inverse Time Neutral Overcurrent ................................... 6–3651V Inverse Time Phase Overcurrent withVoltage Control/Restraint ......................................................... 6–3759 Phase Overvoltage ............................................................. 6–3959D Third Harmonic Voltage Differential ................................. 6–4059N Overvoltage, Neutral Circuit or Zero Sequence .............. 6–4159X Multipurpose Overvoltage................................................. 6–4260FL VT Fuse Loss Detection ................................................ 6–4364F Field Ground Protection.................................................... 6–4464B Brush Lift Off Detection ................................................... 6–4664S 100% Stator Ground Protection by Injection .................. 6–4767N Residual Directional Overcurrent ..................................... 6–5078 Out of Step ......................................................................... 6–5481 Frequency ............................................................................ 6–5681A Frequency Accumulator .................................................... 6–5781R Rate of Change of Frequency .......................................... 6–5887 Phase Differential ................................................................ 6–6087GD Ground Differential ......................................................... 6–62Breaker Monitoring ................................................................... 6–64Trip Circuit Monitoring .............................................................. 6–66IPSLogic ................................................................................... 6–67

6.3 Diagnostic Test Procedures .................................................... 6–68

6.4 Auto-Calibration ........................................................................ 6–77

Page 221: Generator Relay Protection

M-3425A Instruction Book

6–2

6.1 Equipment/Test Setup

No calibration is necessary, as the M-3425AGenerator Protection Relay is calibrated and fullytested at the factory. If calibration is necessarybecause of a component replacement, follow theauto calibration procedure detailed in Section 6.4,Auto Calibration (or see Section 4.7, Calibrationsubsection for units without an HMI). These testprocedures are based on the prerequisite that thefunctions are enabled and have settings as describedin Chapter 2, Application, and that the unit is fittedwith the optional HMI module.

Equipment RequiredThe following equipment is required to carry out thetest procedures:

1. Two Digital Multimeters (DMM) with 10A current range.

2. 120 V ac or 0 to 125 V dc variablesupply for system power.

3. Three-phase independent voltage sources(0 to 250 V) variable phase to simulateVT inputs.

4. Three-phase independent current sources(0 to 25 A) variable phase to simulateCT inputs.

5. Electronic timer accurate to at least 8ms.

6. For relays with the 64F/B option:

a. Resistor decade box capable of 500ohms to 150 kOhms, able to step in100 ohm increments.

b. Capacitors ranging from 0.15 mf to10 mf.

7. For relays with the 64S option:

a. 20 Hz Voltage Generator (variable) 0to 40 V.

b. 20 Hz Current Generator (variable) 0to 40 mA.

Setup1. Connect system power to the power input

terminals 62 (hot) and 63 (neutral). Therelay can be ordered with a nominal inputpower supply of 110/120/230/240 Vac,110/125/220/250 Vdc or 24/48 Vdc. Anoptional redundant power supply isavailable.

NOTE: The proper voltage for the relay is clearlymarked on the power supply label affixedto the rear panel.

2. For each test procedure, connect thevoltage and current sources accordingto the configuration listed in the testprocedure and follow the steps outlined.

Page 222: Generator Relay Protection

6–3

Testing – 6

NOTE: The phase angles shown here use leading angles as positive and lagging angles as nega-tive. Some manufacturers of test equipment have used lagging angles as positive, in which caseVB=120 V a120° and VC=120 V a240°. Similarly other voltages and currents phase angles shouldbe adjusted. These test configurations are for ABC phase rotation. They must be adjusted appropriate-ly for ACB phase rotation.

Figure 6-1 Voltage Inputs: Configuration V1

Figure 6-2 Voltage Inputs: Configuration V2

Page 223: Generator Relay Protection

M-3425A Instruction Book

6–4

Ia ∠0°

55

54

57

56

59

58

Current Input 1

Polarity

Current Input 2

Current Input 3

Ib ∠–120°

Ic ∠120°

Figure 6-3 Current Inputs: Configuration C1

IA ∠0°

47

46

49

48

51

50

53

52

Current Input 1

Polarity

Current Input 2

Current Input 3

IB ∠–120°

IC ∠120°

IN

Figure 6-4 Current Inputs: Configuration C2

Page 224: Generator Relay Protection

6–5

Testing – 6

Figure 6-5 Current Configuration C3

!"##

$#%

#&

'$ #( '

#

$#

%

)

*!'+

)

*!'+

Figure 6-6 64S Test Configuration

Current Input 2

Polarity 47

AØ 46 IA

49

BØ 48 IB

51

CØ 50 IC

120o

240o

Page 225: Generator Relay Protection

M-3425A Instruction Book

6–6

6.2 Functional Test Procedures

This section details test quantities, inputs andprocedures for testing each relay function. Thepurpose is to confirm the functions’ designatedoutput operation, the accuracy of the magnitudepickup settings, and the accuracy of time delaysettings. Whereas the first test described, “PowerOn Self Test”, does not require electrical quantityinputs, all other functional tests do require inputs,and the necessary connection configurations arenoted.

In all test descriptions, a process for calculatinginput quantities to test the actual settings of thefunction will be given if needed. Disable all otherfunctions not being tested at the time. This action isto prevent the operation of multiple functions withone set of input quantities, which could causeconfusion of operation of outputs or timers. Thecomplete description of the method to disable/enablefunctions may be found in detail in Section 3.2,Initial Setup Procedure/Settings, Configure RelayData subsection or Chapter 4, Remote Operation.The complete description of the method to installsetting quantities may be found in Section 3.4,System Data, Setpoints and Time Settingssubsection.

It is desirable to record and confirm the actualsettings of the individual functions before beginningtest procedures. Use Figure A-3, FunctionalConfiguration Record Form and Figure A-4, Setpoint& Timing Record Form, found in Appendix A,Configuration Record Forms, to record settings. Itis also possible to download the relay settings intoa file using IPScom®.

It may be desirable to program all test settings in analternate profile, or to save the relay settings inIPScom to preserve desired setup.

The tests are described in this section in ascendingfunction number order as used in Chapter 2,Application.

NOTE: User should disable all functions notcurrently being tested before beginningany function test.

During the lifetime of the relay, testing of individualfunctions due to changes in application settings willbe more likely than an overall testing routine. Anindex of the individual test procedures is illustratedat the beginning of this chapter.

NOTE: Care must be taken to reset or enableany functions that have been changedfrom their intended application settingswhen the test procedures are complete.

Many options for test sequences and methods arepossible. As an example, the operation of the outputcontacts can be tested along with the operation ofthe LEDs in the Diagnostic Test Procedures. Theoperation of the output contacts may also beconfirmed with the LED and function operation duringFunctional Test Procedures, if desired.

If timer quantities are to be checked, the timer mustbe activated by the appropriate output contacts.The contact pin numbers are enumerated in Table6-1, Output Contacts.

It is suggested that copies of the following be madefor easy referral during test procedures:

Input Configurations – pg 6–3 to 6-5Output Contact Numbers – pg 6–68Relay Configuration Table – pg A–2Setpoint & Timing Record Form – pg A–20

Page 226: Generator Relay Protection

6–7

Testing – 6

Power On Self Tests

VOLTAGE INPUTS: none

CURRENT INPUTS: none

1. Apply proper power to the power input terminals (60 HOT and 61 NEUTRAL).

2. The following sequence of actions will take place in the following order:

a. The unit will display the following:

POWER ON SELFTESTSXXXXXXxxxxxxxxxxx

b. All LEDs will illuminate for approximately 1 second.

c. The POWER and RELAY OK LEDs will remain illuminated, all other LEDs will extinguish.

d. The unit will display the following:

POWER ON SELFTESTSPASS

e. The unit will display the model number:

BECKWITH ELECTRIC CO.M-3425A Expanded

f. The unit will display the firmware version.

BECKWITH ELECTRICD-0150xx.xx.xx

g. The unit will display the serial number.

BECKWITH ELECTRIC CO.SERIAL NUMBER xxx

h. The POWER LED(s) will illuminate.

i. The RELAY OK LED will flash (or stay on as programmed in the diagnostic menu).

j. The BREAKER CLOSED LED will remain illuminated. If the relay breaker position contactIN1 is connected to a breaker position contact (52b) and the breaker is open the LED will beextinguished.

3. The power-on self-tests end with the unit displaying the system date, time and default logo.

4. If there are any recorded targets they are then displayed.

Page 227: Generator Relay Protection

M-3425A Instruction Book

6–8

21 Phase Distance (#1, #2 or #3)

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: Configuration C1

TEST SETTINGS: Diameter P Ohms (0.1 to 100)1 Amp CT Rating (0.5 to 500.0)

Offset O Ohms (–100 to 100)1 Amp CT Rating (–500.0 to 500.0)

Impedance Angle A Degrees (0 to 90)

Time Delay D Cycles (1 to 8160)

Programmed Outputs Z Output (1 to 8)Expanded I/O (9 to 23)

VT Configuration Line - Ground or Line-Line

NOTE: It would be efficient to disable the element with the higher “reach” (Diameter plus Offset)setting first (lower current), and test the lower reach setting operation, since the higherreach setting operation can be tested without disabling the lower setting.

Test Setup:

1. Determine the Function 21 Phase Distance settings to be tested.

2. Enter the Function 21 Phase Distance settings to be tested utilizing either the HMI or IPScom®

Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

5. Connect test current inputs as shown in Figure 6-3, Current Inputs: Configuration C1.

6. The level of current at which pickup operation is to be expected for an individual setting isdetermined as follows:a. Define “reach” as R ohms = (P ohms + O ohms) [O, usually set at zero ohms].b. For Line-Ground configuration, define “current” as I = ((Selected Voltage)I R ohms). The

voltage level may be selected based on the desired test current level. For Line-Lineconfiguration, define “current” as I = ((Selected Voltage/S3) I R ohms).

Pickup Test:

1. Set the three-phase voltages to the Selected Voltage value from Step 6b above.

2. Set the phase angle between the voltage and current inputs at (A) degrees from settings above(for Line-Line configuration, set the phase angle at (A–30°).

3. Press and hold the TARGET RESET pushbutton, then slowly increase the three-phase inputcurrents until the 21 PHASE DISTANCE LED illuminates, or the pickup indicator illuminates onthe IPScom Function Status screen.

The level at which the 21 PHASE DISTANCE actuates should be equal to I calculated in Step 6with the resulting impedance 0.1 ohms or 5%.

4. Release the TARGET RESET pushbutton, then decrease the three-phase input currents. Theassigned OUTPUT LEDs will extinguish.

5. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply approximately 110% of the current (I) found in Step 6, and start timing. The contacts willclose after D cycles within 1 cycle or 1%.

Page 228: Generator Relay Protection

6–9

Testing – 6

24 Volts/Hz Definite Time (#1 or #2)

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: None

TEST SETTINGS: Definite Time Pickup P % (100 to 200)

Time Delay D Cycles (30 to 8160)

Programmed Outputs Z Output (1 to 8)Expanded I/O (9 to 23)

NOTE: It would be efficient to disable the 24 Definite Time element with the lower pickup settingfirst and test the higher setting operation, since the lower setting operation can be tested withoutdisabling the higher setting.

Test Setup:

1. Determine the Function 24 Voltz/Hz Definite Time settings to be tested.

2. Enter the Function 24 Voltz/Hz Definite Time settings to be tested utilizing either the HMI orIPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

5. The Volts per Hertz pickup level at a percentage setting at Nominal Frequency (50 or 60 Hz) is:Pickup voltage = (P% ÷ 100) x (Nominal Voltage) where the Nominal Values have beenprogrammed in the system setup data described in Section 2.1, Configuration and are recorded onFigure A-3, Functional Configuration Record Form.

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly increase the voltage on Phase Auntil the 24 VOLTS/Hz LED illuminates, or the pickup indicator illuminates on the IPScomFunction Status screen. The voltage level of operation will equal to P volts ±1%.

2. Release the TARGET RESET pushbutton, then decrease the Phase A voltage. The assignedOUTPUT LED(s) will extinguish.

3. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply approximately (P + 10 volts) volts, and start timing. The contacts will close after D cycles± 25 cycles.

3. Repeat Pickup Test and Time Test for Phase B and C.

Page 229: Generator Relay Protection

M-3425A Instruction Book

6–10

24 Volts/Hz Inverse Time

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: None

TEST SETTINGS: Inverse Time Pickup P % (100 to 200)

Inverse Time Curve C (1 to 4)

Time Dial (Curve 1) K (1 to 100)

Time Dial (Curves 2-4) (0.0 to 9.0)

Reset Rate R Seconds (1 to 999)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine the Function 24 Voltz/Hz Inverse Time settings to be tested.

2. Enter the Function 24 Voltz/Hz Inverse Time settings to be tested utilizing either the HMI orIPScom® Communications Software.

3. Enter a Function 24 Voltz/Hz Definite Time Pickup #1 setting of 200%, with a Delay of 1200cycles.

4. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

5. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

6. The Volts/Hz pickup level of a percentage setting at nominal frequency (50 or 60 Hz) is: Pickupvoltage = (P% ÷ 100) x (Nominal Voltage) where the Nominal Values have been programmed inthe system setup data described in Section 2.1, Configuration and are recorded on Figure A-3,Functional Configuration Record Form.

7. Test levels may be chosen at any percentages of Nominal Voltage which are a minimum of 5%higher than the pickup percentage, P%. (Suggest 4 or 5 test levels chosen and calculated inStep 6.)

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly increase the voltage on Phase Auntil the 24 VOLTS/Hz LED light illuminates, or the pickup indicator illuminates on the IPScomFunction Status screen. The voltage level of operation will equal P volts ±1%.

2. Release the TARGET RESET pushbutton, then decrease the Phase A voltage. The assignedOUTPUT LED(s) will extinguish.

3. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply a voltage equal to the chosen test level calculated in Step 6 to Phase A and start timing.

The operating time will be as read from the appropriate Inverse Curve Family and K (Time Dial)setting (refer to Appendix D, Inverse Time Curves). The measured time should be within the timecorresponding to 1% of the pickup value.

Page 230: Generator Relay Protection

6–11

Testing – 6

3. Press and hold the TARGET RESET pushbutton.

4. Reduce the applied voltage and start timing when the voltage drops below the pickup value, stoptiming when the TARGET LED extinguishes. The time should be the reset time within ±1 secondor ±1%.

5. Repeat Pickup Test and Time Test for all chosen test levels. The curve portion extending to lowerthan P% V/Hz values are inactive and can be ignored. The tested points verify the operatingtimes of the function.

NOTE: If retesting is required, remove power from the unit or wait for the programmed reset timeperiod before the next test to assure resetting of the timer.

Page 231: Generator Relay Protection

M-3425A Instruction Book

6–12

25D Dead Check

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: None

TEST SETTINGS: Dead V1 See Below

Dead VX

See Below

Dead V1 & VX

See Below

Dead Input Enable DIN Input (1 to 6)Expanded I/O (7 to 14)

Dead Time Delay DD Cycles (1 to 8160)

Dead Voltage Limit DVL Volts (0 to 60)

Programmed Outputs Z Output (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine the Function 25D Dead Check settings to be tested.

2. Enter the Function 25D Dead Check settings to be tested utilizing either the HMI or IPScom®

Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. The 25D function requires positive sequence voltage and VX for testing. The following tests will

reference the positive sequence voltage as V1.

5. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

6. Set V1 and VX to the Nominal Voltage.

The Nominal Voltage value previously input to the relay is described in Section 2.1 and shouldbe recorded on Figure A-3, Functional Configuration Record Form.

Dead V1 Hot VX Test:

1. Enable Dead V1 Hot VX and disable Dead V

X Hot V1 (if enabled) utilizing either the HMI or IPScom

Communications Software..

2. Set V1 to DVL +5 V.

3. Press and hold the TARGET RESET pushbutton, then slowly decrease the voltage applied to V1until Output Z LED illuminates, or the pickup indicator illuminates on the IPScom Function Statusscreen. The voltage level should be equal to DVL 0.5 V or 0.5 %.

4. Release the TARGET RESET pushbutton, then increase the voltage applied to V1. The OUTPUTLED will extinguish.

5. Set V1 to the Nominal Voltage.

6. Decrease VX to less than DVL, verify that the function does not operate.

Page 232: Generator Relay Protection

6–13

Testing – 6

Dead VX Hot V1 Test:

1. Enable Dead VX Hot V1 and disable Dead V1 Hot V

X (if enabled) utilizing either the HMI or IPScom

Communications Software.

2. Set V1 to the Nominal Voltage.

The Nominal Voltage value previously input to the relay is described in Section 2.1 and shouldbe recorded on Figure A-3, Functional Configuration Record Form.

3. Set VX to DVL +5 V.

4. Press and hold the TARGET RESET pushbutton, then slowly decrease the voltage applied to VX

until Output Z LED illuminates, or the pickup indicator illuminates on the IPScom Function Statusscreen. The voltage level should be equal to DVL 0.5 V or 0.5 %.

5. Release the TARGET RESET pushbutton, then increase the voltage applied to VX. The OUTPUT

LED will extinguish.

6. Set VX to the Nominal Voltage.

7. Decrease V1 to less than DVL, verify that the function does not operate.

Dead V1 Dead VX Test:

1. Enable Dead V1 Dead VX utilizing either the HMI or IPScom Communications Software.

2. Disable Dead VX Hot V1 and Dead V1 Hot V

X (if enabled).

3. Set V1 and VX to DVL +5 V.

4. Press and hold the TARGET RESET pushbutton, then slowly decrease the voltage applied to V1and V

X until Output Z LED illuminates, or the pickup indicator illuminates on the IPScom Function

Status screen. The voltage level should be equal to DVL 0.5 V or 0.5 %.

5. Release the TARGET RESET pushbutton, then increase the voltage applied to V1 and VX. The

OUTPUT LED will extinguish.

6. Set V1 to Nominal Voltage.

7. Decrease VX to less than DVL, then verify that the function does not operate.

8. Set VX to Nominal Voltage.

9. Decrease V1 to less than DVL, then verify that the function does not operate.

Dead Input Enable Test:

1. Select one of the Dead Inputs (DIN) and activate it.

2. Repeat the Dead VX Hot V1 Test and Dead V1 Hot VX Test, verify that the function operates as inDead V

X Hot V1 Test and Dead V1 Hot V

X Testing.

3. Deactivate the DIN and repeat the Dead VX Hot V1 Test and Dead V1 Hot V

X Test once more.

Verify that the function does not operate.

4. Disable Dead Input feature.

Dead Timer Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Enable Dead V1 Dead VX , utilizing either the HMI or IPScom Communications Software.

3. Set V1 and VX to DVL +5 V.

4. Remove V1 and VX and start timing. The contacts will close within –1 to +3 cycles or 1%.

Page 233: Generator Relay Protection

M-3425A Instruction Book

6–14

25S Sync Check

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: None

TEST SETTINGS: Phase Angle Window PA Degrees (0 to 90)

Voltage LimitsUpper Limit UL Volts (60 to 140)Lower Limit LL Volts (40 to 120)

Sync Check Time Delay SD Cycles (1 to 8160)

Delta Voltage Limit DV Volts (1.0 to 50.0)

Delta Frequency Limit DF Hz (0.001 to 0.500)

Phase Select (AB, BC, CA)

Programmed Outputs Z Output (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine the Function 25S Sync Check settings to be tested.

2. Enter the Function 25S Sync Check settings to be tested utilizing either the HMI or IPScom®

Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. The 25 function requires only one phase voltage and VX for testing in the Line-to-Ground

configuration. The phase voltage used for reference may be selected through the System Setupmenu. The following tests will reference the phase voltage as V1, although any phase may beused for testing. Line-to-Line testing will follow the same procedures, with V1 representing theproper Line-to-Line phase input. Each test below can be performed using any of the three phasesas a reference.

5. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

6. Set V1 and VX to the Nominal Voltage.

The Nominal Voltage value previously input to the relay is described in Section 2.1 and shouldbe recorded on Figure A-3, Functional Configuration Record Form.

Phase Angle Limit Test:

1. Establish a phase angle difference of more than PA +5°.

2. Press and hold the TARGET RESET pushbutton, then slowly decrease the phase angledifference until Output Z LED illuminates, or the pickup indicator illuminates on the IPScom®

Function Status screen. The phase angle difference should be equal to PA ±1°.

3. Release the TARGET RESET pushbutton, then increase the phase angle difference. TheOUTPUT LED will extinguish.

Page 234: Generator Relay Protection

6–15

Testing – 6

Upper Voltage Limit Test:

1. Apply a voltage 5 V greater than UL to V1.

2. Ensure VX voltage is less than UL but greater than LL. Slowly decrease the voltage applied to V1

until Output Z LED illuminates, or the pickup indicator illuminates on the IPScom Function Statusscreen. The voltage should be equal to UL 0.5 V or ±0.5 %.

3. Increase the voltage applied to V1. The OUTPUT LED will extinguish. If desired, repeat this testusing V

X.

Lower Voltage Limit Test:

1. Apply a voltage 5 V less than LL to V1.

2. Ensure VX voltage is greater than LL but less than UL. Slowly increase the voltage applied to V1

until Output Z LED illuminates, or the pickup indicator illuminates on the IPScom Function Statusscreen. The voltage level should be equal to LL ±0.5 V or ±0.5 %.

3. Decrease the voltage applied to V1. The OUTPUT LED will extinguish. If desired, repeat this testusing V

X.

Sync Check Time Delay Test:

1. Set V1 and VX to the Nominal Voltage. The Nominal Voltage value previously input to the relay

is described in Section 2.1 and should be recorded on Figure A-3, Functional Configuration RecordForm.

2. Establish a phase angle difference of more than PA +5°.

3. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

4. Remove the phase angle difference and start timing. The contacts will close after SD cycleswithin –1 to +3 cycles or 1 %.

Delta Voltage Test:

1. Set the Upper and Lower Voltage limits to their maximum and minimum values, respectively.

2. Set VX to 140 V and V1 to 40 V.

3. Press and hold the TARGET RESET pushbutton, then slowly increase the voltage applied to V1until Output Z LED illuminates, or the pickup indicator illuminates on the IPScom Function Statusscreen. The voltage difference should be equal to DV 0.5 V.

4. Release the TARGET RESET pushbutton, then decrease the voltage applied to V1. The OUTPUTLED will extinguish. If desired, repeat the test using V

X with V1 at 140 volts.

Delta Frequency Test:

1. Set V1 and VX to the Nominal Voltage. The Nominal Voltage value previously input to the relayis described in Section 2.1 and should be recorded on Figure A-3, Functional Configuration RecordForm.

2. Set the frequency of V1 to 0.05 less than Nominal Frequency –DF.

3. Press and hold the TARGET RESET pushbutton, then slowly increase the frequency of V1 untilOutput Z LED illuminates, or the pickup indicator illuminates on the IPScom® Function Statusscreen. The frequency difference value should be equal to DF 0.0007 Hz or 5 %.

4. Release the TARGET RESET pushbutton, then decrease the frequency of V1. The OUTPUT LEDwill extinguish. If desired, repeat the test using V

X with V1 at Nominal Frequency.

Page 235: Generator Relay Protection

M-3425A Instruction Book

6–16

27 Phase Undervoltage, 3 Phase (#1, #2, #3)

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: None

TEST SETTINGS: Pickup P Volts (5 to 180)

Time Delay D Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)

Expanded I/O (9 to 23)

NOTE: If 27 #1 and 27 #2 have different pickup settings, it would be efficient to disable the one with thehigher setting first and test the lower setting operation. The higher setting operation could then betested without disabling the lower setting.

Test Setup:

1. Determine the Function 27 Phase Undervoltage settings to be tested.

2. Enter the Function 27 Phase Undervoltage settings to be tested utilizing either the HMI orIPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly decrease the Phase A input voltageuntil the 27 PHASE UNDERVOLTAGE LED illuminates, or the pickup indicator illuminates on theIPScom Function Status screen.

The voltage level should be equal to P volts ±0.5 V or ± 0.5%. When both RMS and Line-Groundto Line-Line is selected, the accuracy is 0.8V or 0.75%.

2. Release the TARGET RESET pushbutton, then increase the Phase A input voltage to the nominalvoltage, the OUTPUT LEDs will extinguish.

3. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply approximately (P – 1) volts and start timing.

The contacts will close after D cycles ± 20 cycles or 1%(RMS), or 1 cycle or 0.5% (DFT),whichever is greater.

3. Repeat Pickup Test and Time Test for Phase B and C.

Page 236: Generator Relay Protection

6–17

Testing – 6

27TN Third-Harmonic Undervoltage, Neutral (#1 or #2)

VOLTAGE INPUTS: Configuration V2

CURRENT INPUTS: See Below

TEST SETTINGS: Pickup P Volts (0.10 to 14.0)

Positive Sequence Volt Block PSV Volts (5 to 180)

Forward Power Block FP PU (0.01 to 1.00)

Reverse Power Block RP PU (–1.00 to –0.01)

Lead VAR Block –VAR PU (–1.00 to –0.01)

Lag VAR Block +VAR PU (0.01 to 1.00)

Lead Power Factor Block PFLead PU (0.01 to 1.00)

Lag Power Factor Block PFLag PU (0.01 to 1.00)

High Band Forward Power Block HFP PU (0.01 to 1.00)

Low Band Forward Power Block LFP PU (0.01 to 1.00)

Time Delay D Cycles (1 to 8160)

Programmed Outputs Z OUT ( 1 to 8)

Expanded I/O (9 to 23)

NOTE: If 27TN #1 and 27 #2 have different pickup settings, it would be efficient to disable the onewith the higher setting first and test the lower setting operation. The higher setting operation couldthen be tested without disabling the lower setting.

Test Setup:

1. Determine the Function 27TN Third-Harmonic Undervoltage, Neutral settings to be tested.

2. Enter the Function 27TN Third-Harmonic Undervoltage, Neutral settings to be tested utilizingeither the HMI or IPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-2, Voltage Inputs: Configuration V2.

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly decrease the neutral voltage inputuntil the 27TN/59D 100% STATOR GND LED illuminates, or the pickup indicator illuminates onthe IPScom Function Status screen. The voltage level should be equal to P volts ±0.1 V or ±1%.

2. Release the TARGET RESET pushbutton, then increase the neutral voltage to nominal voltage.The OUTPUT LED(s) will extinguish.

3. Press TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply approximately (P – 1) volts and start timing. The contacts will close after D cycles within1 cycle or 1%.

Page 237: Generator Relay Protection

M-3425A Instruction Book

6–18

Positive Sequence Voltage Block Test:

1. Decrease the neutral voltage input to less than P volts.

2. Apply a three phase voltage input greater than PSV volts.

The 27TN/59D 100% STATOR GND LED will illuminate, then the OUTPUT LED will illuminatewhen the delay setting has timed out.

3. Enable the Positive Sequence Voltage Block utilizing either the HMI or IPScom® CommunicationsSoftware.

4. Decrease the applied three phase voltage until the OUTPUT LED(s) extinguishes.

The voltage level should be equal to PSV volts ±0.5 V or ±0.5%.

5. Disable the Positive Sequence Voltage Block utilizing either the HMI or IPScom CommunicationsSoftware.

Forward/Reverse Power Block Test:

1. Apply a three phase nominal voltage input.

The Nominal Voltage value previously input to the relay is described in Section 2.1 and shouldbe recorded on Figure A-3, Functional Configuration Record Form.

2. Apply a nominal current input consistent with Figure 6-3, Current Inputs: Configuration C1.

The Nominal Current value is described in Section 2.1, Configuration and should be recorded onFigure A-3, Functional Configuration Record Form.

NOTE: The POWER Real p.u. value can be obtained utilizing either the HMI (Status/Power Status) or IPScom® Communications Software (Relay/Monitor/Secondary Status).

3. Adjust three phase voltage and current inputs to obtain a Power Real p.u. value greater than FP.

4. Enable the Forward Power Block utilizing either the HMI or IPScom Communications Software.

5. Decrease the applied three phase current until the OUTPUT LED(s) extinguishes.

The Power Real p.u. value should be equal to FP ±0.01 PU or ±2%.

6. Utilizing either the HMI or IPScom Communications Software disable the Forward Power Blockand then enable the Reverse Power Block.

7. Adjust three phase voltage and current inputs to obtain a Power Real p.u. value greater than RP.

8. Decrease the applied three phase current until the OUTPUT LED(s) extinguishes.

The Power Real p.u. value should be equal to RP ±0.01 PU or ±2%.

9. Enable the Reverse Power Block utilizing either the HMI or IPScom Communications Software.

Lead/Lag VAr Block Test:

1. Apply a three phase nominal voltage input.

The Nominal Voltage value previously input to the relay is described in Section 2.1 and shouldbe recorded on Figure A-3, Functional Configuration Record Form.

2. Apply a nominal current input consistent with Figure 6-3, Current Inputs: Configuration C1.

The Nominal Current value is described in Section 2.1, Configuration and should be recorded onFigure A-3, Functional Configuration Record Form.

Page 238: Generator Relay Protection

6–19

Testing – 6

NOTE: The POWER Reactive var value can be obtained utilizing either the HMI (Status/Power Status) or IPScom® Communications Software (Relay/Monitor/Secondary Status).

3. Adjust three phase voltage and current inputs to obtain a Power Reactive var value greater than–VAR.

The 27TN/59D 100% STATOR GND LED will illuminate, then the OUTPUT LED will illuminatewhen the delay setting has timed out.

4. Enable the Lead VAR Block utilizing either the HMI or IPScom® Communications Software.

5. Adjust the applied three phase current phase angles until the OUTPUT LED(s) extinguishes.

The Power Reactive var value should be equal to –VAR ±0.01 PU or ±2%.

6. Utilizing either the HMI or IPScom® Communications Software disable the Lead VAR Block andthen enable the Lag VAR Block.

7. Adjust three phase voltage and current inputs to obtain a Power Reactive var value greater than+VAR.

8. Adjust the applied three phase current phase angles until the OUTPUT LED(s) extinguishes.

The Power Reactive var value should be equal to +VAR ±0.01 PU or ±2%.

9. Disable the Lag VAR Block utilizing either the HMI or IPScom Communications Software.

Lead/Lag Power Factor Block Test:

1. Apply a three phase nominal voltage input.

The Nominal Voltage value previously input to the relay is described in Section 2.1 and shouldbe recorded on Figure A-3, Functional Configuration Record Form.

2. Apply a nominal current input consistent with Figure 6-3, Current Inputs: Configuration C1.

The Nominal Current value is described in Section 2.1, Configuration and should be recorded onFigure A-3, Functional Configuration Record Form.

3. Adjust three phase voltages and currents to obtain a Lead Power Factor Block value greater thanPFLead.

The 27TN/59D 100% STATOR GND LED will illuminate, then the OUTPUT LED will illuminatewhen the delay setting has timed out.

4. Enable the Power Factor Lead Block utilizing either the HMI or IPScom CommunicationsSoftware.

5. Adjust three phase voltage phase angles until the OUTPUT LED(s) extinguishes.

The Power Factor Lead Block value should be equal to PFLead ± 0.03 or ± 3%.

6. Disable the Power Factor Lead Block.

7. Enable the Power Factor Lag Block.

8. Adjust three phase voltages and currents to obtain a Lag Power Factor Block value greater thanPFLag.

The 27TN/59D 100% STATOR GND LED will illuminate, then the OUTPUT LED will illuminatewhen the delay setting has timed out.

9. Enable the Power Factor Lag Block utilizing either the HMI or IPScom Communications Software.

10. Adjust three phase voltage phase angles until the OUTPUT LED(s) extinguishes.

The Power Factor Lag Block value should be equal to PFLag ± 0.03 PU or ± 3%.

11. Disable the Power Factor Lag Block.

Page 239: Generator Relay Protection

M-3425A Instruction Book

6–20

Forward Power Block (Band) Test:

1. Apply a three phase nominal voltage input.

The Nominal Voltage value previously input to the relay is described in Section 2.1 and shouldbe recorded on Figure A-3, Functional Configuration Record Form.

2. Apply a nominal current input consistent with Figure 6-3, Current Inputs: Configuration C1.

The Nominal Current value is described in Section 2.1, Configuration and should be recorded onFigure A-3, Functional Configuration Record Form.

3. Enable the High/Low Band Forward Power Block utilizing either the HMI or IPScom CommunicationsSoftware.

4. Adjust three phase voltages and currents to obtain a High/Low Forward Power Block value eithergreater than the Low Band Forward Power Block LFP, or less than the High Band Forward PowerBlock HFPThe 27TN/59D 100% STATOR GND LED will illuminate, then the OUTPUT LED will illuminatewhen the delay setting has timed out.

5. Adjust the three phase current until the OUTPUT LED(s) extinguishes.

The Power Real p.u. value should be within the High Band and Low Band setpoint band ±0.1 PUor ±2%.

6. Disable the High/Low Band Forward Power Block.

Page 240: Generator Relay Protection

6–21

Testing – 6

32 Directional Power, 3 Phase (#1, #2, #3)

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: Configuration C1

TEST SETTINGS: Pickup P PU (–3.000 to +3.000)

Time Delay D Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

VT Configuration Line-Ground

Power Sensing (Over/Under)

#3 Directional Power Sensing (Real/Reactive)

NOTE: It would be efficient to disable the element with the lower pickup setting first and test thehigher setting operation, since the lower setting operation can be tested without disabling the highersetting.

Test Setup:

1. Determine the Function 32 Directional Power settings to be tested.

2. Enter the Function 32 Directional Power settings to be tested utilizing either the HMI or IPScom®

Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

5. Connect test current inputs as shown in Figure 6-3, Current Inputs: Configuration C1.

6. The level of current at which operation is to be expected for an individual power setting is given bymultiplying the PU pickup value (P above) by the Nominal Current value previously input to therelay. The Nominal Current value is described in Section 2.1, Configuration and should berecorded on Figure A-3, Functional Configuration Record Form.

7. Set the three phase voltages to the Nominal Voltage. The Nominal Voltage value previouslyinput to the relay is described in Section 2.1 and should be recorded on Figure A-3, FunctionalConfiguration Record Form.

Pickup Test, Positive/Forward Over Power Flow:

1. Press and hold the TARGET RESET pushbutton, then slowly increase the three phase currentsuntil the 32 DIRECTIONAL POWER LED illuminates, or the pickup indicator illuminates on theIPScom Function Status screen.

The level of operation will be equal to that calculated in Step 6, ±2% or ±0.002 PU, whichever isgreater.

2. Release the TARGET RESET pushbutton.

3. Decrease the currents. The OUTPUT LED(s) will extinguish.

4. Press TARGET RESET pushbutton to reset targets.

Page 241: Generator Relay Protection

M-3425A Instruction Book

6–22

Pickup Test, Negative/Reverse Over Power Flow:

1. Set the phase currents at 180 degrees from the respective phase voltages.

2. Press and hold the TARGET RESET pushbutton, then slowly increase the three phase currentsuntil the 32 DIRECTIONAL POWER LED illuminates, or the pickup indicator illuminates on theIPScom® Function Status screen. The level of operation will be equal to that calculated in Step 6,±2% or ±0.002 PU, whichever is greater.

3. Release the TARGET RESET pushbutton.

4. Decrease the three phase currents. The OUTPUT LED(s) will extinguish.

5. Press the TARGET RESET pushbutton to reset targets.

Pickup Test, Positive Forward Under Power Flow:

1. Set the phase currents in phase with the respective phase voltages.

2. Select Underpower sensing utilizing either the HMI or IPScom Communications Software.

3. Press and hold the TARGET RESET pushbutton, then slowly decrease the three phase currentsuntil the 32 DIRECTIONAL POWER LED illuminates, or the pickup indicator illuminates on theIPScom Function Status screen. The level of operation will be equal to that calculated in Step 6,±2% or ±0.002 PU, whichever is greater.

4. Release the TARGET RESET pushbutton.

4. Increase the three phase currents. The OUTPUT LED(s) will extinguish.

5. Press the TARGET RESET pushbutton to reset targets.

Pickup Test, Negative/Reverse Under Power Flow:

1. Set the phase currents at 180 degrees from the respective phase voltages.

2. Press and hold the TARGET RESET pushbutton, then slowly decrease the three phase currentsuntil the 32 DIRECTIONAL POWER LED illuminates, or the pickup indicator illuminates on theIPScom Function Status screen. The level of operation will be equal to that calculated in Step 6,±2% or ±0.002 PU, whichever is greater.

3. Release the TARGET RESET pushbutton.

4. Increase the three phase currents. The OUTPUT LED(s) will extinguish.

5. Press the TARGET RESET pushbutton to reset targets.

Pickup Test, Reactive Over Power (Element #3 Only):

1. Set the Three phase voltages, current magnitudes and phase angles to less than the Reactivep.u. pickup level.

2. Press and hold the TARGET RESET pushbutton, then slowly swing current angles until the 32DIRECTIONAL POWER LED illuminates, or the pickup indicator illuminates on the IPScomFunction Status screen. The level of operation will be equal to the Reactive Pickup ±2% or±0.002 PU, whichever is greater.

3. Release the TARGET RESET pushbutton.

4. Adjust phase angles until the OUTPUT LED(s) extinguish.

5. Press the TARGET RESET pushbutton to reset targets.

Page 242: Generator Relay Protection

6–23

Testing – 6

Pickup Test, Reactive Under Power (Element #3 Only):

1. Set the Three phase voltages, current magnitudes and phase angles to greater than the Reactivep.u. pickup level.

2. Press and hold the TARGET RESET pushbutton, then slowly swing current angles until the 32DIRECTIONAL POWER LED illuminates, or the pickup indicator illuminates on the IPScom®

Function Status screen. The level of operation will be equal to the Reactive Pickup ±2% or±0.002 PU, whichever is greater.

3. Release the TARGET RESET pushbutton.

4. Adjust phase angles until the OUTPUT LED(s) extinguish.

5. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply approximately 110% of the pickup current and start timing. The contacts will close after Dcycles within +16 cycles or ±1%.

Page 243: Generator Relay Protection

M-3425A Instruction Book

6–24

40 Loss of Field (#1 or #2, VC #1 or #2)

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: Configuration C1

TEST SETTINGS: Circle Diameter P Ohms (0.1 to 100)1 Amp CT Rating (0.5 to 500)

Offset O Ohms (–50 to 50)1 Amp CT Rating (–250 to 250)

Time Delay D Cycles (1 to 8160)

Voltage Control V Volts (5 to 180)

Delay with VC Cycles (1 to 8160)

Directional Element E Degrees (0 to 20)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

VT Configuration Line-Ground

NOTE: It would be efficient to disable the function with the higher “reach” (diameter minus offset)setting first (lower current) and test the lower “reach” setting operation. Since the higher settingoperation can be tested without disabling the lower setting, the 40 functions will be enabled whenthe tests are complete.

Test Setup:

1. Determine the Function 40 Loss of Field settings to be tested.

2. Enter the Function 40 Loss of Field settings to be tested utilizing either the HMI or IPScom®

Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

5. Connect test current inputs as shown in Figure 6-3, Current Inputs: Configuration C1.

NOTE: For proper testing, use I ≤ 3 x CT rating.

6. The level of current at which operation is to be expected for an individual setting is as follows:a. Define “reach” as R ohms = (P - O ohms) where O is usually negative.

b. Define “trip current” as I = (Selected Voltage ÷ R ohms). The voltage level may be selectedbased on the desired test current level.

c. Define “offset current” as IO = (Selected Voltage ÷ O ohms).

7. Set the three-phase voltages VA, V

B, and V

C to the Selected Voltage value from Step 6, and

set the phase angle between the voltage and current inputs to 90° (current leading voltage).

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly increase the three-phase currentsuntil the 40 LOSS OF FIELD LED illuminates, or the pickup indicator illuminates on the IPScomFunction Status screen. The level will be equal to “I” calculated in Step 6 with the resultingimpedance within 0.1 ohms or 5%.

Page 244: Generator Relay Protection

6–25

Testing – 6

2. If the offset setting is negative, continue to increase the three-phase currents until the 40 LOSSOF FIELD LED light extinguishes, or the pickup indicator extinguishes on the IPScom® FunctionStatus screen. The level will be equal to “IO” calculated in Step 6 with the resulting offsetimpedance within ±0.1 ohms or ±5%.

3. Release the TARGET RESET pushbutton.

4. Decrease the three-phase currents. The OUTPUT LED(s) will extinguish.

5. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Set the three-phase voltages VA, V

B, and V

C to the Selected Voltage value from Step 6, and set

the phase angle between the voltage and current inputs to 90° (current leading voltage).

3. Apply I + 10% Amps and start timing. Contacts will close after D cycles K1 cycle or K1%.

Time Test With Voltage Control:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Enable the Voltage Control setting utilizing either the HMI or IPScom Communications Software.

3. Set the three-phase voltages VA, V

B, and V

C to a voltage where the positive sequence voltage is

less than the Voltage Control setting.

4. Set phase currents and phase angles to establish the impedance value within the mho pickup andstart timing. Contacts will close after D cycles 1 cycle or 1%.

Page 245: Generator Relay Protection

M-3425A Instruction Book

6–26

46 Negative Sequence Overcurrent Definite Time

VOLTAGE INPUTS: None

CURRENT INPUTS: Configuration C1 (MODIFIED)

TEST SETTINGS: Pickup Def Time P % (3 to 100)

Time Delay D Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

NOTE: Although no voltage input is required for the testing of the 46 function, it is suggested thatNominal Voltage be applied to restrain the functions which use both voltage and current inputs foroperation.

Test Setup:

1. Determine the Function 46 Negative Sequence Overcurrent Definite Time settings to be tested.

2. Enter the Function 46 Negative Sequence Overcurrent Definite Time settings to be tested utilizingeither the HMI or IPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test current inputs as shown in Figure 6-3, Current Inputs: Configuration C1 (Modified).Modify Configuration C1 by exchanging Current Input 2 and 3 (Phase B current = Input 3 andPhase C current = Input 2).

NOTE: For proper testing, use I ≤ 3 x CT rating.

5. The level of current at which operation is to be expected for an individual setting is given by;Pickup current = (P% ÷ 100) x Nominal Current previously input to the relay. The NominalCurrent value is described in Section 2.1, Configuration and should be recorded on Figure A-3,Functional Configuration Record Form.

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly increase the three-phase currentsuntil the NEG SEQ OVERCURRENT 46 LED illuminates, or the pickup indicator illuminates on theIPScom Function Status screen. The level will be equal to pickup current calculated in Step 5±0.5% of 5 A.

2. Release the TARGET RESET pushbutton.

3. Decrease the three-phase currents. The OUTPUT LED(s) will extinguish.

4. Press TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply current of at least (1.1 x pickup) amps and start timing. The contacts will close after Dcycles within 1 cycle or 1%.

Page 246: Generator Relay Protection

6–27

Testing – 6

46 Negative Sequence Overcurrent Inverse Time

VOLTAGE INPUTS: None

CURRENT INPUTS: Configuration C1 (MODIFIED)

TEST SETTINGS: Pickup Inv Time P % (3 to 100)

Time Dial Setting K (1 to 95)

Maximum Trip Time D Cycles (600 to 65,500)

Reset Time R Seconds (1 to 600)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

NOTE: Although no voltage input is required for the testing of the 46 function, it is suggested thatNominal Volts be applied to restrain the functions which use both voltage and current inputs foroperation.

Test Setup:

1. Determine the Function 46 Negative Sequence Overcurrent Inverse Time settings to be tested.

2. Enter the Function 46 Negative Sequence Overcurrent Inverse Time settings to be tested utilizingeither the HMI or IPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test current inputs as shown in Figure 6-3, Current Inputs: Configuration C1 (Modified).Modify Configuration C1 by exchanging Current Input 2 and 3 (Phase B current = Input 3 andPhase C current = Input 2).

NOTE: For proper testing, use I ≤ 3 x CT rating.

5. The current pickup level at a percentage setting is: Pickup current = (P% ÷ 100) x NominalCurrent previously input to the relay.a. Test levels may be chosen at any percentages of Nominal Current which are a minimum of

5% higher than the pickup percentage, P%. (Suggest 4 or 5 test levels chosen and calculatedin amps.)

b. The Nominal Current value is described in Section 2.1, Configuration and should berecorded on Figure A-3, Functional Configuration Record Form.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply currents equal to the chosen test levels calculated in Step 5 and start timing. The operatingtime will be as read from Figure 2-31, Negative Sequence Inverse Time Curves, negativesequence current in % of Nominal Current and appropriate K (Time Dial) setting, or the maximumtrip time (whichever is faster).

NOTE: If retesting is required, power should be removed from the unit or wait R seconds before the nexttest to assure resetting of the timer.

3. Repeat Step 2 for all test levels chosen.

Reset Time Test:

1. Press and hold the TARGET RESET pushbutton.

2. Reduce the applied voltage and start timing when the voltage decreases to less than the pickupvalue, stop timing when the TARGET LED extinguishes, or the pickup indicator extinguishes onthe IPScom Function Status screen. The time should be approximately equal to the reset timesetting R.

NOTE: If retesting is required, power should be removed from the unit or wait for the reset time before thenext test to assure resetting of the timer.

Page 247: Generator Relay Protection

M-3425A Instruction Book

6–28

49 Stator Overload Protection (#1, #2)

VOLTAGE INPUTS: None

CURRENT INPUTS: Configuration C1

TEST SETTINGS: Time Constant τ Minutes (1.0 to 999.9)

Max Overload Current Imax

Amps (1 to 10)1 Amp CT Rating (.2 to 2)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine the Function 49 Stator Overload settings to be tested. This test requires that thevalues for the following elements (described in detail in Chapter 2, Application) be determined:

• τ = time constant

• I0 = pre-load current

• Imax = maximum allowed continuous overload current

2. Enter the Function 49 Stator Overload settings to be tested utilizing either the HMI or IPScom®

Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test current inputs as shown in Figure 6-3, Current Inputs: Configuration C1.

5. Calculate t (time to trip in minutes) for the desired test settings as follows:

Where:

Where: t = time to trip in minutesτ = time constantIIIIIL= relay current (applied)IIIIIPL = pre-load currentIIIIImax = maximum allowed continuous overload current

Pickup Test:1. Press and hold the TARGET RESET pushbutton, then slowly increase the current until the

STATOR OVERLOAD 49 LED illuminates or the pickup indicator illuminates on the IPScomFunction Status screen.

The current level of operation will be (Imax) Amps 0.1 A ( 0.02 Amp for 1 A CT) or 3%.

2. Release the TARGET RESET pushbutton, then decrease the current. The OUTPUT LED willextinguish.

3. Press TARGET RESET button to remove targets.

Page 248: Generator Relay Protection

6–29

Testing – 6

Time Test (Cold Start):1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

NOTE: The 49 Stator Overload 49 #1 and 49 #2 current values can be obtained utilizing either the HMI(Status/Current Status) or IPScom® Communications Software (Relay/Monitor/Secondary Status).

2. Determine the 49 Stator Overload 49 #1 and 49 #2 current values. If the either value is greaterthan 0.00 A, then remove power from the relay and then reapply power to reset the current values.

3. Apply a three phase current (I) to the relay greater than (Imax) Amps and start timing.

The time to trip should be t minutes 5 %.

Time Test (Preload):1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

NOTE: The 49 Stator Overload 49 #1 and 49 #2 current values can be obtained utilizing either the HMI(Status/Current Status) or IPScom Communications Software (Relay/Monitor/Secondary Status).

2. Determine the 49 Stator Overload 49 #1 and 49 #2 current values. If the either value is greaterthan 0.00 A, then remove power from the relay and then reapply power to reset the current values.

3. Apply a three phase preload current to the relay equal to (IO) Amps and allow current readings tostabilize.

4. Apply a three phase current (I) to the relay greater than (Imax) Amps and start timing.

The time to trip should be t minutes 5 %.

Page 249: Generator Relay Protection

M-3425A Instruction Book

6–30

50 Instantaneous Phase Overcurrent (#1, #2)

VOLTAGE INPUTS: None

CURRENT INPUTS: Configuration C1

TEST SETTINGS: Pickup P Amps (0.1 to 240.0)1 Amp CT Rating (0.1 to 48.0)

Delay Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)

Expanded I/O (9 to 23)

NOTE: Although no voltage input is required for the testing of the 50 function, it is suggested that NominalVolts be applied to restrain the functions which use both voltage and current inputs for operation.

Test Setup:

1. Determine the Function 50 Instantaneous Phase Overcurrent settings to be tested.

2. Enter the Function 50 Instantaneous Phase Overcurrent settings to be tested utilizing either theHMI or IPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test current inputs as shown in Figure 6-3, Current Inputs: Configuration C1.

Pickup Test:

1 Press and hold the TARGET RESET pushbutton, then slowly increase Current Input 3 (Phase C)until the PHASE OVERCURRENT 50 LED illuminates, or the pickup indicator illuminates on theIPScom Function Status screen.

The current level of operation will be (P) amps ±0.1 amps or ±3%.

2. Release the TARGET RESET pushbutton.

3. Decrease the current input. The OUTPUT LED(s) will extinguish.

4. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply approximately 110% of P amps and start timing. The operating time will be 1 cycle or 1%.

3. Reduce Current Input 3, to 0 amps.

4. Test may be repeated using Current Inputs 1 (Phase A) and 2 (Phase B) individually.

Page 250: Generator Relay Protection

6–31

Testing – 6

50BF/50BF-N Breaker Failure

VOLTAGE INPUTS: None

CURRENT INPUTS: Configuration C3

TEST SETTINGS: 50BF-Ph Pickup P Amps (0.10 to 10.00)1 Amp CT Rating (0.02 to 2.00)

50BF-N Pickup N Amps (0.10 to 10.00)1 Amp CT Rating (.02 to 2.00)

Time Delay D Cycles (1 to 8160)

Breaker Failure Initiate B OUT (1 to 8)Input Initiate I IN (1 to 6)

Expanded I/O (7 to 14)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

2. Connect test current inputs as shown in Figure 6-5, Current Inputs: Configuration C3. CurrentInput #2 only.

Test Setup for 50BF-Ph Generator Breaker Failure Operation:

1. Determine the Function 50BF-Ph Generator Breaker Failure settings to be tested.

2. Utilizing either the HMI or IPScom® Communications Software enter the following settings:a. Enable the 50BF-Phase Element and disable the 50BF-Neutral Elementb. 50BF-Ph Pickup Setting > P amps, Time delay setting = D cycles.

Testing 50BF-Ph Generator Breaker Failure Operation:

1. Externally short any ONE set of contacts (I) IN shown above.

2. Short IN1 (connect contacts 10 & 11) to simulate 52b contact closure (breaker open). Alternatively,the external contact may be operated if all connections are made.

3. Press and hold the TARGET RESET pushbutton, then slowly increase Current Input 3 until the50BF BREAKER FAILURE LED illuminates, or the pickup indicator illuminates on the IPScomFunction Status screen.

The current level of operation will be (P) amps ±0.1 amps or ±2%.

4. Release the TARGET RESET pushbutton.

5. Decrease the current input. The OUTPUT LED(s) extinguish.

6. Press the TARGET RESET pushbutton to reset targets.

Time Test 50BF-Ph Generator Breaker Failure Operation:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply approximately 110% of P amps and start timing. The operating time will be D cycles within1 cycle or 1%.

3. Reduce Current Input 3, to 0 amps.

Page 251: Generator Relay Protection

M-3425A Instruction Book

6–32

Test Setup for 50BF-N Generator Breaker Failure Operation:

1. Determine the Function 50BF-Ph Generator Breaker Failure settings to be tested.

2. Utilizing either the HMI or IPScom® Communications Software enter the following settings:a. Enable the 50BF-Neutral Element and the 50BF-Phase Elementb. 50BF-N Pickup Setting > N amps, 50BF-Ph Pickup Setting < P amps, Time delay setting =

D cycles.

Testing 50BF-N Generator Breaker Failure Operation:,

1. Short IN1 (connect contacts 10 & 11) to simulate 52b contact closure (breaker open).

3. Press and hold the TARGET RESET pushbutton, then slowly increase Current Input 3 until the50BF BREAKER FAILURE LED illuminates, or the pickup indicator illuminates on the IPScomFunction Status screen.

The current level of operation will be (N) amps ±0.1 amps or ±2%.

4. Release the TARGET RESET pushbutton.

5. Decrease the current input. The OUTPUT LED(s) extinguish.

6. Press the TARGET RESET pushbutton to reset targets.

Time Test 50BF-N Generator Breaker Failure Operation:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply approximately 110% of N amps and start timing. The operating time will be D cycles within1 cycle or 1%.

3. Reduce Current Input 3, to 0 amps.

Test Setup for HV Breaker Failure Operation:

1. Utilizing either the HMI or IPScom Communications Software enter the following settings:a. Disable the 50BF-Neutral Element and 50BF-Phase Element.b. Select 1 input initiate from #2 to #6, utilizing either the HMI or IPScom Communications

Software.c. Time delay setting = D cyclesd. Input 1 IN breaker closed state.

Testing HV Breaker Failure Operation:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Initiate operation by externally shorting any ONE set of contacts (I) IN except Input 1 above.Remove short from Input (1) IN. The operating time will be D cycles within 1 cycle or 1%.

Page 252: Generator Relay Protection

6–33

Testing – 6

50/27 Inadvertent Energizing

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: Configuration C1

TEST SETTINGS: 50 Pickup P Amps (0.50 to 15.00)1 Amp CT Rating (.01 to 3.00)

27 Pickup V Volts (5 to 130)

Pickup Delay D Cycles (1 to 8160)

Dropout Delay T Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine the Function 50/27 Inadvertent Energizing settings to be tested.

2. Enter the Function 50/27 Inadvertent Energizing settings to be tested utilizing either the HMI orIPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

5. Connect test current inputs as shown in Figure 6-3, Current Inputs: Configuration C1.

50 Overcurrent Test and 27 Undervoltage Test:

1. Set Voltage inputs to zero volts, then verify the Pickup Time Delay times out after a minimum ofD cycles.

2. Press and hold the TARGET RESET pushbutton, then slowly increase the Phase A current (Input1) until the 50/27 INADVERTENT ENRGNG LED illuminates, or the pickup indicator illuminateson the IPScom Function Status screen.

The level of operation will be (P) amps ±0.1 A or ±2%.

3. If desired, set the dropout time delay (T) to minimum setting.

4. Press and hold the TARGET RESET pushbutton, then slowly increase the voltage input in stages(waiting at least T cycles between each voltage change) until the 50/27 INADVERTENT ENRGNGLED extinguishes, or the pickup indicator extinguishes on the IPScom Function Status screen..

The level of operation will be V volts ±0.5 Volts.

27 Pickup Delay and Dropout Delay Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Reduce voltage to 0 volts and start timing. The operating time to close will be D cycles within 1cycle or 1%.

3. Increase current by one (1) amp.

4. Input approximately 110% of V volts (pickup setting) and start timing. The operating time to openwill be T cycles within 1 cycle or 1%.

Page 253: Generator Relay Protection

M-3425A Instruction Book

6–34

50DT Definite Time Overcurrent (for split-phase differential), #1 or #2

VOLTAGE INPUTS: None

CURRENT INPUTS: Configuration C2

TEST SETTINGS: Pickup A Phase A Amps (0.20 to 240.00)1 Amp CT Rating (0.04 to 48.00)

Pickup B Phase B Amps (0.20 to 240.00)1 Amp CT Rating (0.04 to 48.00)

Pickup C Phase C Amps (0.20 to 240.00)1 Amp CT Rating (0.04 to 48.00)

Delay Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

NOTE: Although no voltage input is required for the testing of the 50DT function, it is suggested thatNominal Volts be applied to restrain the functions which use both voltage and current inputs foroperation. If other functions operate during these tests they will need to also be disabled for thetest and enabled after the tests are complete.

Test Setup:

1. Determine the Function 50DT Definite Time Overcurrent settings to be tested.

2. Enter the Function 50DT Definite Time Overcurrent settings to be tested utilizing either the HMI orIPScom® Communications Software.

3. Disable the functions listed above. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test current inputs as shown in Figure 6-4, Current Inputs: Configuration C2.

5. Set the three-phase voltages VA, V

B, and V

C to the Nominal Voltage. The Nominal Voltage value

previously input to the relay is described in Section 2.1 and should be recorded on Figure A-3,Functional Configuration Record Form.

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly increase the Phase A Current Inputuntil the PHASE OVERCURRENT 50 LED illuminates, or the pickup indicator illuminates on theIPScom Function Status screen.

The current level of operation will be (A) amps ±0.1 amps or ±3%.

2. Release the TARGET RESET pushbutton.

3. Decrease the Phase A Current Input. The OUTPUT LED(s) will extinguish.

4. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply approximately 110% of A amps and start timing. The operating time will be 1 cycle or1%, whichever is greater.

3. Reduce Phase A Current Input to 0 amps.

4. Repeat Steps 2 and 3 for Phase B & C.

5. If testing is complete, enable any functions disabled for this test.

Page 254: Generator Relay Protection

6–35

Testing – 6

50N Instantaneous Neutral Overcurrent

VOLTAGE INPUTS: None

CURRENT INPUTS: As described

TEST SETTINGS: Pickup P Amps (0.1 to 240.0)1 Amp CT Rating (0.1 to 48.0)

Time Delay D Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

NOTE: Although no voltage input is required for the testing of the 50N function, it is suggested thatNominal Volts be applied to restrain the functions which use both voltage and current inputs foroperation.

Test Setup:

1. Determine the Function 50N Instantaneous Neutral Overcurrent settings to be tested.

2. Enter the Function 50N Instantaneous Neutral Overcurrent settings to be tested utilizing either theHMI or IPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly increase Current Input IN (terminals

53 and 52) until the NEUTRAL O/C 50N/51N LED illuminates, or the pickup indicator illuminateson the IPScom Function Status screen.

The current level of operation will be (P) amps ±0.1 amps or ±3%.

2. Release the TARGET RESET pushbutton.

3. Decrease Current Input IN. The OUTPUT LED(s) will extinguish.

4. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply approximately 110% of P amps to Current Input IN (terminals 53 and 52) and start timing.

The operating time will be D cycles ±1 Cycle or ±1%.

3. Reduce Current Input IN to 0 amps.

Page 255: Generator Relay Protection

M-3425A Instruction Book

6–36

51N Inverse Time Neutral Overcurrent

VOLTAGE INPUTS: None

CURRENT INPUTS: As described

TEST SETTINGS: Pickup P Amps (0.25 to 12.00)1 Amp CT Rating (0.05 to 2.40)

BECO Time Curves(definite time/inverse/very inverse/extremely inverse)

Time Dial Setting K (0.5 to 11.0)

IEC Inverse Time Curves:1

(inverse/very inverse/extremely inverse/long time inverse)

IEE Curves(moderately inverse/very inverse/extremely inverse)

Time Dial Setting K (0.5 to 15.0)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

1 Either a standard curve or an IEC curve must be selected.

NOTE: Although no voltage input is required for the testing of the 51N function, it is suggested thatNominal Volts be applied to restrain the functions which use both voltage and current inputs foroperation.

Test Setup:

1. Determine the Function 51N Inverse Time Neutral Overcurrent settings to be tested.

2. Enter the Function 51N Inverse Time Neutral Overcurrent settings to be tested utilizing either theHMI or IPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Refer to Appendix D, Figures D5–D12, or Tables D-1A and D-1B. Test levels may be chosen interms of multiples of pickup value and associated time in seconds. (Suggest 4 or 5 test levelschosen and calculated in amps.)

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply current equal to the chosen test level calculated in Step 6 to Current Input IN (Terminals 53and 52) and start timing.

Operating time will be within ±3 cycles or ±3% whichever is greater.

3. Repeat Steps 2 and 3 for all test levels chosen. The tested points verify the operating times of thefunction.

Page 256: Generator Relay Protection

6–37

Testing – 6

51V Inverse Time Phase Overcurrent with Voltage Control/Restraint

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: Configuration C1

TEST SETTINGS: Pickup P Amps (0.50 to 12.00)

1 Amp CT Rating (0.10 to 2.40)

BECO Time Curves(definite time/inverse/very inverse/extremely inverse)

Time Dial Setting K (0.5 to 11.0)

IEC Inverse Time Curves:1

(inverse/very inverse/extremely inverse/long time inverse)

IEE Curves(moderately inverse/very inverse/extremely inverse)

Time Dial Setting K (0.5 to 15.0)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

1 Either a standard curve or an IEC curve must be selected.

Test Setup:

1. Determine the Function 51V Inverse Time Phase Overcurrent settings to be tested.

2. Enter the Function 51V Inverse Time Phase Overcurrent settings to be tested utilizing either theHMI or IPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

5. Connect test current inputs as shown in Figure 6-3, Current Inputs: Configuration C1

6. Test levels may be chosen at any ampere values which are a minimum of 50% higher than thepickup amps, P Amps. It is suggested that the user select 4 or 5 test levels to verify curve.

Pickup Test:

1. If Voltage Control or Voltage Restraint is enabled, then disable 51V Voltage Control/Restraintutilizing either the HMI or IPScom Communications Software.

2. Press and hold the TARGET RESET pushbutton, then slowly increase the Phase A CurrentInput until the PHASE OVERCURRENT 51V LED illuminates, or the pickup indicator illuminateson the IPScom Function Status screen.

The current level of operation will equal P Amps ±0.1A or ±1%.

3. Release the TARGET RESET pushbutton.

4. Reduce the Phase A Current Input to 0 amps. The assigned OUTPUT LED(s) will extinguish.

5. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. If Voltage Control or Voltage Restraint is enabled, then disable 51V Voltage Control/Restraintutilizing either the HMI or IPScom Communications Software.

Page 257: Generator Relay Protection

M-3425A Instruction Book

6–38

3. Apply current equal to the chosen test level calculated in Step 6 to Phase A Current Input andstart timing. The operating time will be as read from the appropriate Inverse Curve Family and K(Time Dial) setting in Appendix D, Figures D-5 through D-8, or Tables D-1A through D-1B. Theaccuracy specified is valid for currents above 1.5 times the pickup current.

4. Reduce Phase A Current Input to 0 amps. The OUTPUT LED(s) will extinguish.

5. Press the TARGET RESET pushbutton to reset targets.

6. Repeat Steps 3, 4 and 5 for all test levels chosen.

Voltage Control Test:

1. If Voltage Control is disabled, then enable 51V Voltage Control utilizing either the HMI or IPScom®

Communications Software.

2. Press and hold the TARGET RESET pushbutton, then slowly increase the Phase A (B,C) CurrentInput until the PHASE OVERCURRENT 51V LED illuminates, or the pickup indicator illuminateson the IPScom Function Status screen.

3. Release the TARGET RESET pushbutton.

4. When the assigned OUTPUT LED(s) illuminates, then increase the Phase A(B,C) Input Voltageto at least 0.5 Volts greater than V Volts.

The assigned OUTPUT LED(s) will extinguish at V Volts ±0.5 V or ±0.5%.

5. Press the TARGET RESET pushbutton to reset targets.

6. Reduce Phase A (B,C) Current Input to 0 amps.

7. Decrease the Phase A (B,C) Input Voltage to Nominal Voltage.

The Nominal Voltage value previously input to the relay is described in Section 2.1 and shouldbe recorded on Figure A-3, Functional Configuration Record Form.

Voltage Restraint Test:

1. If Voltage Restraint is disabled, then enable 51V Voltage Restraint utilizing either the HMI orIPScom Communications Software.

2. Set P Amps equal to 2 Amps utilizing either the HMI or IPScom Communications Software.

3. Apply current equal to 1.5 Amps to the Phase Current Input.

4. Increase the Phase A (B,C) Input Voltage to 75% of Nominal Voltage. The Nominal Voltagevalue previously input to the relay is described in Section 2.1 and should be recorded on FigureA-3, Functional Configuration Record Form.

The PHASE OVERCURRENT 51V LED will illuminate, or the pickup indicator illuminates on theIPScom Function Status screen.

5. Repeat Steps 2, 3 and 4 with reduced input voltage values and current reduced by the samepercentage as value (see Figure 2-44).

Page 258: Generator Relay Protection

6–39

Testing – 6

59 Phase Overvoltage, 3-Phase (#1, #2, #3)

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: None

TEST SETTINGS: Pickup P Volts (5 to 180)

Time Delay D Cycles (1 to 8160)

Input Voltage Select (Phase, Positive or Negative Sequence)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

NOTE: If 59 #1 and 59 #2 have different pickup settings, it would be efficient to disable the one with thelower setting first and test the higher setting operation. The lower setting operation could then betested without disabling the higher setting.

Test Setup:

1. Determine the Function 59 RMS Overvoltage settings to be tested.

2. Enter the Function 59 RMS Overvoltage settings to be tested utilizing either the HMI or IPScom®

Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

5. Set the three-phase voltages VA, V

B, and V

C to the Nominal Voltage.

The Nominal Voltage value previously input to the relay is described in Section 2.1 and shouldbe recorded on Figure A-3, Functional Configuration Record Form.

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly increase the Phase A Voltage Inputuntil the 59 PHASE OVERVOLTAGE LED illuminates, or the pickup indicator illuminates on theIPScom Function Status screen.

The voltage level of operation should be equal to P Volts ±0.5 V or ±0.5%. When both RMS andLine-Ground to Line-Line is selected, the accuracy is 0.8V or 0.75%

2. Release the TARGET RESET pushbutton.

3. Decrease the Phase A Voltage Input to Nominal Voltage. The OUTPUT LED(s) will extinguish.

4. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply (P+1) Volts to the Phase A (B,C) Voltage Input and start timing. The contacts will closeafter D cycles 1 cycle or 1% (DFT) or within +20 cycles or 1% (RMS).

3. Reduce Phase A (B,C) Voltage Input to Nominal Voltage.

4. Repeat Steps 2 and 3 for Phase B & C.

Page 259: Generator Relay Protection

M-3425A Instruction Book

6–40

59D Third-Harmonic Voltage Differential

VOLTAGE INPUTS: As described

CURRENT INPUTS: None

TEST SETTINGS: Ratio (0.1 to 5.0)

Time Delay D Cycles (1 to 8160)

Line Side Voltage LSV (VX or 3V

O Calculated)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine the Function 59D Third-Harmonic Voltage Differential settings to be tested.

2. Enter the Function 59D Third-Harmonic Voltage Differential settings to be tested utilizing eitherthe HMI or IPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect a voltage input to VN

at 180 Hz (150 Hz for 50 Hz unit) terminal numbers 44 and 45.

Pickup Test:

NOTE: If 3VO is being used, then use anyone of the phase voltages or all three at zero sequence.

1. Apply a voltage greater than VN to the selected line side voltage (V

X or 3V

O ) at 180 Hz (150 Hz for

50 Hz unit).

2. Press and hold the TARGET RESET pushbutton, then slowly increase Voltage Input VN until the

59D THIRD HARM VOLT DIFF LED illuminates, or the pickup indicator illuminates on the IPScomFunction Status screen.

2. Release the TARGET RESET pushbutton.

3. Decrease the Voltage Input (VX or 3V

0) to less than the ratio pickup level. The OUTPUT LED(s) will

extinguish.

4. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply a voltage greater than the ratio pickup level and start timing. The contacts will close after Dcycles within 1 cycle or 1%.

Page 260: Generator Relay Protection

6–41

Testing – 6

59N Overvoltage, Neutral Circuit or Zero Sequence (#1, #2, #3)

VOLTAGE INPUTS: As described

CURRENT INPUTS: None

TEST SETTINGS: Pickup P Volts (5.0 to 180)

Time Delay D Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

NOTE: If 59N #1 and 59N #2 have different pickup settings, it would be efficient to disable the one withthe lower setting first and test the higher setting operation. The lower setting operation could thenbe tested without disabling the higher setting.

Test Setup:

1. Determine the Function 59N RMS Overvoltage settings to be tested.

2. Enter the Function 59N RMS Overvoltage settings to be tested utilizing either the HMI orIPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect a voltage input to VN terminal numbers 44 and 45.

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly increase Voltage Input VN until the

59N NEUT/GND OVERVOLT LED illuminates, or the pickup indicator illuminates on the IPScomFunction Status screen.

The voltage level of operation should be equal to P Volts ±0.5 V or ±0.5%.

2. Release the TARGET RESET pushbutton.

3. Decrease the Voltage Input VN

to 0 volts. The OUTPUT LED(s) will extinguish.

4. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply (P+1) Volts and start timing. The contacts will close after D cycles within 1 cycle or1%. When 64S is purchased, the time delay accuracy is –1 to +5 cycles.

Page 261: Generator Relay Protection

M-3425A Instruction Book

6–42

59X Multi-purpose Overvoltage (#1 or #2)

VOLTAGE INPUTS: As described

CURRENT INPUTS: None

TEST SETTINGS: Pickup P Volts (5.0 to 180.0)

Time Delay D Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

NOTE: If 59X #1 and 59X #2 have different pickup settings, it would be efficient to disable the one withthe lower setting first and test the higher setting operation. The lower setting operation could thenbe tested without disabling the higher setting.

Test Setup:

1. Determine the Function 59X Overvoltage settings to be tested.

2. Enter the Function 59X Overvoltage settings to be tested utilizing either the HMI or IPScom®

Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect a voltage input to VX terminal numbers 64 and 65.

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly increase Voltage Input VX until the

59N NEUT/GND OVERVOLT LED illuminates, or the pickup indicator illuminates on the IPScomFunction Status screen.

The voltage level of operation should be equal to P Volts ±0.5 V or ±0.5%.

2. Release the TARGET RESET pushbutton.

3. Decrease the Voltage Input VX to 0 volts. The OUTPUT LED(s) will extinguish.

4. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply (P+1) Volts and start timing. The contacts will close after D cycles within 1 cycle or1%.

Page 262: Generator Relay Protection

6–43

Testing – 6

60FL VT Fuse Loss Detection

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: Configuration C1

TEST SETTINGS: Time Delay D Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

NOTE: It is necessary for “FL” to be designated as an initiating input (see Section 2.3, Setpoints andTime Settings) before this function can be tested.

NOTE: Refer to Figure 2-52, Fuse Loss (60FL) Function Logic, for single phase and three phase fuseloss.

Test Setup:

1. Determine the Function 60FL VT Fuse Loss Detection settings to be tested.

2. Enter the Function 60FL VT Fuse Loss Detection settings to be tested utilizing either the HMI orIPScom® Communications Software. (FL initiate must be selected for this test.)

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

5. Connect test current inputs as shown in Figure 6-3, Current Inputs: Configuration C1.

6. Set the three-phase voltages VA, V

B, and V

C to the Nominal Voltage. The Nominal Voltage value

previously input to the relay is described in Section 2.1 and should be recorded on Figure A-3,Functional Configuration Record Form.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Disconnect the Phase A (B,C) Voltage Input and start timing. The 60FL V.T. FUSE LOSS LEDand Output Z LEDs will illuminate, or the pickup indicator illuminates on the IPScom FunctionStatus screen.

The operating time will be D cycles within 1 cycle or 1%.

3. Reconnect the Phase A (B,C) Voltage Input.

4. Press the TARGET RESET pushbutton to reset targets.

5. Repeat Steps 2, 3 and 4 for Phase B and C.

Time Test - Three Phase Fuse Loss:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Enable Three Phase Fuse Loss Detection utilizing either the HMI or IPScom CommunicationsSoftware.

3. Apply current to Phase A 1.25% greater than Nominal Current.

4. Disconnect Phase A, B and C Voltage Inputs and start timing. The 60FL V.T. FUSE LOSS LEDand Output Z LEDs will illuminate, or the pickup indicator illuminates on the IPScom FunctionStatus screen. The operating time will be D cycles within 1 cycle or 1%.

5. Reconnect the Phase A, B and C Voltage Inputs.

6. Press the TARGET RESET pushbutton to reset targets.

Page 263: Generator Relay Protection

M-3425A Instruction Book

6–44

64F Field Ground Protection (#1 or #2)

VOLTAGE INPUTS: None

CURRENT INPUTS: None

TEST SETTINGS: Pickup P kOhms (5 to 100)

Time Delay D Cycles (1 to 8160)

Injection Frequency IF Hz (0.10 to 1.00)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine the Function 64F Field Ground Protection settings to be tested.

2. Enter the Function 64F Field Ground Protection settings to be tested utilizing either the HMI orIPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect an M-3921 Field Ground Coupler and decade box as described in Figure 6-7, FieldGround Coupler.

5. Set decade box resistance to 10% greater than pickup P kOhms.

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly decrease the resistance on thedecade box until the FIELD GND/BRUSH LIFT 64F/B LED illuminates or the pickup indicator onthe IPScom Function Status screen illuminates.

The level of operation will be P kOhms ±1 kOhms or ±10%.

2. Release the TARGET RESET pushbutton.

3. Increase the resistance on the decade box. The OUTPUT LED(s) will extinguish.

4. Press the TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Set the resistance on the decade box to 90% of P and start timing. The operating time will beafter D cycles, within ±(2/IF + 1).

Page 264: Generator Relay Protection

6–45

Testing – 6

When the capacitance value and the operatingfrequency have been determined, the actualinsulation resistance can be verified by installing avariable resistor (5 to 100 KΩ) and a discretecapacitor to the coupler module (M-3921).

88888 WARNING: When auto-calibrating, the jumperused to short pins 2 & 3 must be removed whencalibration is complete. Placing the M-3921 inservice with this jumper installed will result inserious damage.

!"#

""!

$

$%

&#'()*

+!)(,-

++.

/

0

-

-

'1""""#""

"+"#2!+

%%

03-33$""#" 1++.$!

*The value of Cf should approximate the rotor capacitance.

Figure 6-7 Field Ground Coupler

*

Page 265: Generator Relay Protection

M-3425A Instruction Book

6–46

64B Brush Lift-Off Detection

VOLTAGE INPUTS: None

CURRENT INPUTS: None

TEST SETTINGS: Pickup P mV (0 to 5000)

Time Delay D Cycles (1 to 8160)

Injection Frequency IF Hz (0.10 to 1.00)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine the Function 64F Field Ground Protection settings to be tested.

2. Enter the Function 64F Field Ground Protection settings to be tested utilizing either the HMI orIPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect a M-3921 Field Ground Coupler and the test equipment described in Figure 6-7, FieldGround Coupler.

5. Set Rf to open (infinity) and Cf to 1 μF.

Pickup Test:

1. Access the FIELD GND MEAS. CIRCUIT display under the VOLTAGE menu in STATUS. Set thepickup (P) to 110% of the displayed value.

Refer to Section 3.3, Status/Metering, for details that describe how to access the STATUS MENUwhich contains the FIELD GND MEAS. CIRCUIT value in mV.

2. Press and hold the TARGET RESET pushbutton, then Open the Test Switch. The FIELD GND/BRUSH LIFT 64F/B LED will illuminate or the pickup indicator on the IPScom Function Statusscreen will illuminate.

3. Close the Test Switch. The FIELD GND/BRUSH LIFT 64F/B LED will extinguish or the pickupindicator on the IPScom Function Status screen will extinguish.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Remove the capacitance connected to the decade box and start timing. The operating time will beafter D cycles, within ±(2/IF + 1) sec.

Page 266: Generator Relay Protection

6–47

Testing – 6

64S 100% Stator Ground Protection by low frequency injection

VOLTAGE INPUTS: Adjustable 20 Hz Voltage Source (0 to 40 V)

CURRENT INPUTS: Adjustable 20 Hz Current Source (0 to 100 mA)

TEST SETTINGS: Total Current Pickup P mA (2 to 75)

Real Component Pickup P/2 mA (2 to 75)

Time Delay D Cycles (1 to 8160)

Voltage Restraint (Enabled/Disabled)

Under Frequency Inhibit (Enabled/Disabled)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine settings for F64S to be tested.

2. Enter the settings for F64S into the relay to be tested using either the HMI or IPScomCommunications software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

Pickup Test (Voltage Restraint Disabled and Under Frequency Inhibit Disabled):

1. Enable the Total Current Pickup.

2. Disable the Real Component of Current Pickup.

3. Adjust the 20 Hz voltage generator to apply 25 a0° volts across terminals 44 and 45.

4. Press and hold the TARGET RESET pushbutton in, then slowly increase the 20 Hz currentapplied to terminals 52 and 53 until the 27TN/59D/64S STATOR GND LED illuminates, or thefunction status indicator on the Monitor Function Status screen indicates that the function haspicked up.

The 20 Hz current level should be equal to P mA 2 mA or 10%.

5 Release the TARGET RESET pushbutton.

6. Disable the Total Current Pickup.

7. Enable the Real Component of Current Pickup.

8. Adjust the 20 Hz Voltage Generator to apply 25 a0° Volts across terminals 44 and 45.

9. Press and hold the TARGET RESET pushbutton in, then slowly increase the 20 Hz current at anangle of 60 degrees leading the the 20 Hz voltage applied to terminals 52 and 53 until the 27TN/59D/64S STATOR GND LED illuminates, or the function status indicator on the MonitorFunction Status screen indicates that the function has picked up.

The 20 Hz current level should be equal to P/2 mA 2 mA or 10%.

10. Release the TARGET RESET pushbutton.

11. Decrease the applied 20 Hz current to 0 mA and the applied 20 Hz voltage to 0 Volts.

Page 267: Generator Relay Protection

M-3425A Instruction Book

6–48

Pickup Test (Voltage Restraint Enabled and Under Frequency Inhibit Disabled):

1. Enable the Total Current Pickup.

2. Disable the Real Component of Current Pickup.

3. Adjust the 20 Hz voltage generator to apply 25 a0° volts across terminals 44 and 45.

4. Press and hold the TARGET RESET pushbutton in, then slowly increase the 20 Hz currentapplied to terminals 52 and 53 until the 27TN/59D/64S STATOR GND LED illuminates, or thefunction status indicator on the Monitor Function Status screen indicates that the function haspicked up.

The 20 Hz current level should be equal to P mA 2 mA or 10%.

5 Release the TARGET RESET pushbutton.

6. Adjust the 20 Hz Voltage Generator to apply 35 a0° Volts across terminals 44 and 45.

7. Press and hold the TARGET RESET pushbutton in, then slowly increase the 20 Hz current at anangle of 60 degrees leading the the 20 Hz voltage applied to terminals 52 and 53 until the 27TN/59D/64S STATOR GND LED illuminates, or the function status indicator on the MonitorFunction Status screen indicates that the function has picked up.

The 20 Hz current level should be equal to 1.4 P mA 2 mA or 10%.

8. Release the TARGET RESET pushbutton.

9. Disable the Total Current Pickup.

10. Enable the Real Component of Current Pickup.

11. Adjust the 20 Hz voltage generator to apply 25 a0° volts across terminals 44 and 45.

12. Press and hold the TARGET RESET pushbutton in, then slowly increase the 20 Hz currentapplied to terminals 52 and 53 until the 27TN/59D/64S STATOR GND LED illuminates, or thefunction status indicator on the Monitor Function Status screen indicates that the function haspicked up.

The 20 Hz current level should be equal to 2 P mA 2 mA or 10%.

13. Release the TARGET RESET pushbutton.

14. Adjust the 20 Hz Voltage Generator to apply 35 a0° Volts across terminals 44 and 45.

15. Press and hold the TARGET RESET pushbutton in, then slowly increase the 20 Hz current at anangle of 60 degrees leading the the 20 Hz voltage applied to terminals 52 and 53 until the 27TN/59D/64S STATOR GND LED illuminates, or the function status indicator on the MonitorFunction Status screen indicates that the function has picked up.

The 20 Hz current level should be equal to 1.4 P mA 2 mA or 10%.

16. Release the TARGET RESET pushbutton.

17. Decrease the applied 20 Hz test voltage and current to zero.

Page 268: Generator Relay Protection

6–49

Testing – 6

Pickup Test (Voltage Restraint Disabled and Under Frequency Inhibit Enabled):

1. Apply balanced nominal three-phase voltage to VA (V

AB), V

B (V

BC), and V

C (V

CA) at nominal

frequency (that is, 50 or 60 Hz).

2. Enable the Total Current Pickup.

3. Disable the Real Component of Current Pickup.

4. Adjust the 20 Hz voltage generator to apply 25 a0° volts across terminals 44 and 45.

5. Press and hold the TARGET RESET pushbutton in, then slowly increase the 20 Hz currentapplied to terminals 52 and 53 until the 27TN/59D/64S STATOR GND LED illuminates, or thefunction status indicator on the Monitor Function Status screen indicates that the function haspicked up.

The 20 Hz current level should be equal to P mA 2 mA or 10%. The functions should pickupand close the trip contact output.

6. Release the TARGET RESET pushbutton.

7. Decrease the applied 20 Hz test voltage and current to zero.

8. Decrease the frequency of the balanced nominal three-phase voltage to VA (V

AB), V

B (V

BC), and V

C(V

CA) to 30 Hz.

9. Adjust the 20 Hz Voltage Generator to apply 25 a0° Volts across terminals 44 and 45.

10. Press and hold the TARGET RESET pushbutton in, then slowly increase the 20 Hz currentapplied to terminals 52 and 53 until the the 20 Hz current level is equal to 1.2 P mA. This functionshould pick up but not close the trip contact output.

11. Release the TARGET RESET pushbutton.

12. Decrease the applied 20 Hz test voltage and current to zero.

Timer Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Enable the Total Current Pickup.

3. Disable the Real Component of Current Pickup.

4. Disable Voltage Restraint.

5. Disable Under Frequency Inhibit.

6. Adjust the 20 Hz Voltage Generator to apply 25 a0° Volts across terminals 44 and 45.

7. Step the 20 Hz current applied to terminals 52 and 53 to a value greater than P and start timing.The contacts will close after D cycles within 1 cycle or 1%. Time delay accuracy in cycles isbased on 20 Hz frequency.

Page 269: Generator Relay Protection

M-3425A Instruction Book

6–50

67N Residual Directional Overcurrent, Definite Time

VOLTAGE INPUTS: See Below

CURRENT INPUTS: See Below

TEST SETTINGS: Pickup P Amps (0.50 to 240.0)1 Amp (0.1 to 48.0)

Directional Element See Below

Time Delay D Cycles (1 to 8160)

Max Sensitivity Angle MSA Degrees (0 to 359)

Operating Current 3IO or I

N

Polarization Type* VN, V

X, 3V

O (Calculated)

Programmed Outputs Z Output (1 to 8)Expanded I/O (9 to 23)

* VX cannot be selected if Function 25 (Sync) is enabled. 3V

O can only be used with Line-Ground VT.

Test Setup:

1. Determine the Function 67NDT Residual Directional Overcurrent, Definite Time settings to betested.

2. Enter the Function 67N Residual Directional Overcurrent, Definite Time settings to be testedutilizing either the HMI or IPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Disable the Directional Element.

5. Connect inputs for the polarization type and operating current selected for testing.

Pickup Test (non-directional):

1. Apply current 10% less than pickup P to the operating current. If 3I0, use any one of I

A, I

B, or I

C, or

all three in zero sequence.

2. Press and hold the TARGET RESET pushbutton in, then slowly increase the current applied tothe selected operating current until the GND DIFF/DIR O/C 87GD/67N LED illuminates, or thefunction status indicator on the Monitor Function Status screen indicates that the function haspicked up.

The level should be equal to PI3 Amps 0.1A or 3%.

3 Release the TARGET RESET pushbutton.

4. Decrease the current applied to all phases of the selected operating current. The OUTPUT LEDwill extinguish.

Page 270: Generator Relay Protection

6–51

Testing – 6

Directional Test:

1. Enable the Directional Element utilizing either the HMI or IPScom Communications Software.

2. Press the TARGET RESET pushbutton to reset targets.

3. Set the voltage of the selected polarization type to the Nominal Voltage (If 3V0 is selected, use

any one of the phase voltages, or all three in zero sequence.) The Nominal Voltage valuepreviously input to the relay is described in Section 2.1 and should be recorded on Figure A-3,Functional Configuration Record Form.

4. Set the current angle to an angle greater than 100° from MSA.

5. Apply current 10% greater than P to the input of the selected operating current.

6. Press and hold the TARGET RESET pushbutton, then slowly swing the angle of the selectedoperating current applied towards the MSA until the GND DIFF/DIR O/C 87GD/67N LEDilluminates, or the function status indicator on the Monitor Function Status screen indicates thatthe function has picked up.

The angle should be equal to A –90° or +90°, depending to which side of MSA the current hasbeen set.

7. Release the TARGET RESET pushbutton.

8. Swing the current angle away from the MSA. The OUTPUT LED will extinguish.

Timer Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Disable the Directional Element utilizing either the HMI or IPScom Communications Software.

3. Apply P +10% Amps to the input of the selected operating current, and start timing. The contactswill close after D cycles within –1 to +3 cycles or 1%.

Page 271: Generator Relay Protection

M-3425A Instruction Book

6–52

67N Residual Directional Overcurrent, Inverse Time

VOLTAGE INPUTS: See Below

CURRENT INPUTS: See Below

TEST SETTINGS: Pickup P Amps (0.25 to 12.0)1 Amp CT Rating (0.05 to 2.40)

Directional See Below

BECO Inverse Time Curves

Definite Time\Inverse\Very Inverse\Extremely InverseTime Dial TD (0.5 to 11.0)

IEC Inverse Time Curves

IECI / IECVI / IECEI / IECLTITime Dial TD (0.05 to 1.10)

IEEE Inverse Time Curves IEEEI/IEEEVI/IEEEEI Time Dial TD (0.5 to 15)Operating Current 3I

O or I

N

Max Sensitivity Angle MSA Output (0 to 359)

Polarization Type VN, V

X, 3V

O (Calculated)

Programmed Outputs Z Output (1 to 8)Expanded I/O (9 to 23)

* VX cannot be selected if Function 25 (Sync) is enabled. 3V

O can only be used with Line-Ground VT.

Test Setup:

1. Determine the Function 67N Residual Directional Overcurrent, Inverse Time settings to be tested.

2. Enter the Function 67N Residual Directional Overcurrent, Inverse Time settings to be testedutilizing either the HMI or IPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Disable Directional Element.

5. Refer to Appendix D, Inverse Time Curves, and IEC equations below to calculate test times forlevels represented on the graphs. It is suggested that 4 or 5 test levels be chosen.

Curve 5

Curve 6

Curve 7

Curve 8

IEC Class AStandard Inverse

IEC Class BVery Inverse

IEC Class CExtremely Inverse

IEC Class DLong Time Inverse

t = time in seconds TD = Time Dial setting M = current in multiples of pickup

Time Delay Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply the input current used in the calculations from Step 5 to the input of the selected operatingcurrent, and start timing.

The operating time will be ±3 cycles or ±5% of the calculated time. Repeat this step for each testlevel chosen. The points tested verify the operation of this function.

Page 272: Generator Relay Protection

6–53

Testing – 6

Directional Test:

1. Enable Directional Element.

2. Press the TARGET RESET pushbutton to reset targets.

3. Apply Nominal Voltage to the input of the selected Polarization Type. If 3V0, use any one of the

phase voltages, or all three at zero sequence.

The Nominal Voltage value previously input to the relay is described in Section 2.1 and shouldbe recorded on Figure A-3, Functional Configuration Record Form.

4. Set the current angle to an angle greater than 100° from MSA.

5. Apply current 10% greater than PI3, (for type 3, use P) to all three phases.

6. Press and hold the Target Reset pushbutton, then slowly swing the angle of the selectedoperating current towards the MSA until the GND DIFF/DIR O/C 87GD/67N LED illuminates, orthe function status indicator on the Monitor Function Status screen indicates that the functionhas picked up.

The angle should be equal to A –90° or +90°, depending to which side of MSA the current hasbeen set.

7. Release the TARGET RESET pushbutton.

8. Swing the current angle away from the MSA. The OUTPUT LED will extinguish.

Page 273: Generator Relay Protection

M-3425A Instruction Book

6–54

78 Out of Step

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: Configuration C1

TEST SETTINGS: Circle Diameter P Ohms (0.1 to 100)1 Amp CT Rating (0.5 to 500)

Offset O Ohms (–100 to 100)1 Amp CT Rating (–500 to 500)

Impedance Angle A Degrees (0 to 90)

Time Delay D Cycles (1 to 8160)

Blinder Impedance B Ohms (0.1 to 50.0)1 Amp CT Rating (0.5 to 250.0)

Pole Slip Counter (1 to 20)

Pole Slip Reset Cycles (1 to 8160)

Trip on MHO Exit See Below

Programmed Output Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. An accurate stopwatch is required for this test.

2. Determine the Function 78 Out of Step settings to be tested.

3. Establish communications with the relay utilizing IPScom® Communications Software.

4. Enter the Function 78 Out of Step settings to be tested utilizing IPScom CommunicationsSoftware.

5. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

6. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

7. Connect test current inputs as shown in Figure 6-4, Current Inputs: Configuration C1.

8. Set the three-phase voltages VA, V

B, and V

C to the Nominal Voltage.

The Nominal Voltage value previously input to the relay is described in Section 2.1 and should berecorded on Figure A-3, Functional Configuration Record Form.

Pickup Test:

1. Disable the Function 78 Out of Step TRIP ON MHO EXIT setting, then set the delay, D, to aminimal setting (2–3 cycles).

2. Open the IPScom Out-of-Step Dialog Box, Figure 4-32 (Relay/Monitor/Out of Step Dialog Box).

3. While monitoring the Positive Sequence Impedance, set the magnitude and phase angle of theInput Currents to a point similar to point Z0 in Figure 2-61.

4. Press and hold the TARGET RESET pushbutton, then sweep the current angle towards point Z1.

When the impedance passes through point Z1, verify that the 78 OUT OF STEP LED illuminates,or the function status indicator on the Monitor Function Status screen indicates that the functionhas picked up.

Page 274: Generator Relay Protection

6–55

Testing – 6

5. Pause testing until the delay timer has time to expire, then continue to sweep the current angle topoint Z2, and verify output Z operates as point Z2 is crossed, and resets after the seal-in timedelay.

6. If testing is complete, then reduce voltages and currents to zero.

Blocking on Stable Swing Test:

1. While monitoring the Positive Sequence Impedance, set the magnitude and phase angle of theInput Currents to a point outside of the mho circle.

2. While monitoring the Positive Sequence Impedance, set the magnitude and phase angle of theInput Currents to point Z0 in Figure 2-61.

3. Press and hold the TARGET RESET pushbutton, then sweep past point Z1.

When the impedance passes through point Z1, verify that the 78 OUT OF STEP LED illuminates,or the function status indicator on the Monitor Function Status screen indicates that the functionhas picked up.

4. Pause testing until the delay timer has time to expire, then reverse the sweep direction and sweepthe current angle to point Z1.

As point Z1 is crossed, verify output Z does not operate and the 78 OUT OF STEP LEDextinguishes or the function status indicator on the Monitor Function Status screen indicatesthat the function has reset.

6. If testing is complete, then reduce voltages and currents to zero.

Pickup Test (Trip on mho Exit):

1. Enable the TRIP ON MHO EXIT setting.

2. While monitoring the Positive Sequence Impedance, set the magnitude and phase angle of theInput Currents to point Z0 in Figure 2-61.

3. Press and hold the TARGET RESET pushbutton, then sweep the current angle towards point Z1.

When the impedance passes through point Z1, verify that the 78 OUT OF STEP LED illuminatesor the function status indicator on the Monitor Function Status screen indicates that the functionhas picked up.

4. Pause testing until the delay timer has time to expire, then continue to sweep the current angle tobeyond point Z2. Verify that output Z does not operate as point Z2 is crossed.

5. Sweep the impedance further towards point Z3. Verify output Z operates as point Z3 is crossed,and resets after the seal-in time delay has timed out.

6. If testing is complete, then reduce voltages and currents to zero.

Page 275: Generator Relay Protection

M-3425A Instruction Book

6–56

81 Frequency (#1, #2, #3, #4)

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: None

TEST SETTINGS: Pickup P Hz (50.00 to 67.00)50 Hz Relay (40.00 to 57.00)

Time Delay D Cycles (3 to 65,500)50 Hz Relay

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

NOTE: It would be efficient to disable the elements with the settings nearest to nominal frequency first(testing over or underfrequency functions).

Test Setup:

1. Determine the Function 81 Frequency settings to be tested.

2. Enter the Function 81 Frequency settings to be tested utilizing either the HMI or IPScom®

Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

5. Set the three-phase voltages VA, V

B, and V

C to the Nominal Voltage (nominal frequency). The

Nominal Voltage value previously input to the relay is described in Section 2.1 and should berecorded on Figure A-3, Functional Configuration Record Form.

Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly increase/decrease the InputVoltage (V

A, V

B, and V

C ) Frequency until the FREQUENCY/ROCOF 81/81R LED illuminates or the

function status indicator on the Monitor Function Status screen indicates that the function haspicked up.

The frequency level will be equal to P Hz ±0.02 Hz only if P is within 3 Hz of Fnom,

otherwise,0.1 Hz.

2. Increase/decrease the Input Voltage (VA, V

B, and V

C ) Frequency to nominal input frequency. The

OUTPUT LED(s) will extinguish.

3. Press TARGET RESET pushbutton to reset targets.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply (P + or – 0.5) Hz and start timing. The contacts will close after D cycles within 2 cyclesor 1%, whichever is greater.

Page 276: Generator Relay Protection

6–57

Testing – 6

81A Frequency Accumulator (Band #1, #2, #3, #4, #5, #6)

VOLTAGE INPUTS: V1

CURRENT INPUTS: None

TEST SETTINGS: High Pickup (#1 only) P Hz (50.00 to 67.00)50 Hz Relay (40.00 to 57.00)

Low Pickup P Hz (50.00 to 67.00)50 Hz Relay (40.00 to 57.00)

Delay D Cycles (3 to 360,000)

Acc Status Cycles (0 to 360,000)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine the Function 81A Frequency Accumulator settings to be tested.

2. Enter the Function 81A Frequency Accumulator settings to be tested utilizing either the HMI orIPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

5. Set the three-phase voltages VA, V

B, and V

C to the Nominal Voltage (nominal frequency). The

Nominal Voltage value previously input to the relay is described in Section 2.1 and should berecorded on Figure A-3, Functional Configuration Record Form.

Output Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Set the frequency to a value between the upper and lower limits of the selected band under testand start timing.

3. Utilizing either the HMI (Status/81A Accumulator Status) or IPScom Communications Software(Relay/Monitor/Accumulator Status), verify that the Accumulator Status value for the band undertest is incrementing.

Output Contacts Z will close after D cycles within 2 cycles or 1%.

4. Repeat Steps 1 to 3 for the remaining bands if desired.

Page 277: Generator Relay Protection

M-3425A Instruction Book

6–58

81R Rate of Change of Frequency (#1, #2)

VOLTAGE INPUTS: Configuration V1

CURRENT INPUTS: None

TEST SETTINGS: Pickup P Hz/Sec (0.10 to 20.00)

Time Delay D Cycles (3 to 8160)

Negative SequenceVoltage Inhibit N % (0 to 99)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. It is recommended that the 81 Function be used to establish a window of operation for the 81RFunction which is smaller than the actual sweep range of the frequency applied. This isaccomplished as follows:

NOTE: The frequencies given are suggested for testing rates below 10 Hz/Sec. Higher rates will requireconsideration of the capabilities of the test equipment involved.

a. Enable the 81#1 with a unique Output assigned, a Pickup Setting of 1 Hz greater than theminimum frequency of the ramp and a time delay and seal-in time setting at minimum (Thiswill result in an operational window that is free of erroneous Hz/Sec measurements when thevoltage source begins or ends the sweep.).

b. Enable the 81#2 with a unique Output assigned, a Pickup Setting of 1 Hz less than themaximum frequency of the ramp and a time delay and seal-in time setting at minimum (Thiswill result in an operational window that is free of erroneous Hz/Sec measurements when thevoltage source begins or ends the sweep.).

NOTE: Using this setup, it is important to remember that the 81 elements being used will be operating inthe 81R blocking regions, and the 81R contact operation must be distinguished from the 81contacts.

F81#1 Block 81R Active Region F81#2 Block

56.5 Hz 57.5 Hz 60 Hz 62.5 Hz 63.5 Hz

c. Utilizing a jumper, connect the 81#1 and 81#2 assigned Outputs to a unique Input.d. Set the 81R Function to block on this input.

2. Determine the Function 81R Rate of Change of Frequency settings to be tested.

3. Enter the Function 81R Rate of Change of Frequency settings to be tested utilizing either the HMIor IPScom Communications Software.

4. Disable all other functions prior to testing with the exception of Function 81. Refer to Section 3.2,Initial Setup Procedure/Settings, Configure Relay Data subsection, for details that describedisabling/enabling functions.

NOTE: Testing of the 81R function requires a 3-phase voltage source capable of smoothly sweeping thefrequency of all voltages at a variable rate, continuously.

5. Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.

6. Set the three-phase voltages VA, V

B, and V

C to the Nominal Voltage (nominal frequency).

The Nominal Voltage value previously input to the relay is described in Section 2.1 and shouldbe recorded on Figure A-3, Functional Configuration Record Form.

Page 278: Generator Relay Protection

6–59

Testing – 6

Pickup Test:

1. Calculate the time for the pickup setting, then apply a sweep rate of 25% less than the Pickup (P)to all three phases.

2. Press and hold the TARGET RESET pushbutton, then slowly decrease the sweep time until theFREQUENCY/ROCOF 81/81R LED illuminates, or the function status indicator on the MonitorFunction Status screen indicates that the function has picked up.

The level should be equal to P 0.05 Hz/Sec. or 5 %.

3. Release the TARGET RESET pushbutton, then increase the sweep time. The OUTPUT LED willextinguish.

Negative Sequence Voltage Inhibit Test:

1. Press the TARGET RESET pushbutton to reset targets.

2. Apply Nominal Voltage to all three phases at a sweep rate 25% above P. The Nominal Voltagevalue previously input to the relay is described in Section 2.1 and should be recorded on FigureA-3, Functional Configuration Record Form.

Verify that the FREQUENCY/ROCOF 81/81R LED illuminates, or the function status indicator onthe Monitor Function Status screen indicates that the function has picked up.

3. Swing the phase angle of a Phase Voltage and monitor the Positive and Negative SequenceVoltage levels. The 81R OUTPUT should reset when the negative sequence voltage is N %,

0.5% of the positive sequence voltage.

Timer Test:

1. Press the TARGET RESET pushbutton to reset targets.

2. Apply Nominal Voltage to all three phases at a sweep rate 25% below P. The Nominal Voltagevalue previously input to the relay is described in Section 2.1 and should be recorded on FigureA-3, Functional Configuration Record Form.

3. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

4. Apply a sweep rate 25% above P and start timing. The contacts will close after D cycles within+20 cycles.

Page 279: Generator Relay Protection

M-3425A Instruction Book

6–60

87 Phase Differential (#1 or #2)

VOLTAGE INPUTS: None

CURRENT INPUTS: Configuration C3

TEST SETTINGS: Minimum Pickup P Amps (0.20 to 3.00)1 Amp CT Rating (0.04 to 0.60)

Percent Slope S % (1 to 100)

Time Delay D Cycles (1 to 8160)

CT Correction (0.5 to 2.0)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

NOTE: Although a voltage input is not required for the testing of the 87 function, it is suggested thatNominal Voltage be applied to restrain the functions which use both voltage and current inputs foroperation.

Test Setup:

1. Determine the Function 87 Phase Differential settings to be tested.

2. Enter the Function 87 Phase Differential settings to be tested utilizing either the HMI or IPScom®

Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect test current inputs as shown in Figure 6-5, Current Inputs: Configuration C3.

Minimum Pickup Test:

1. Set Current Input 1( Ia ) to 0 Amps.

2. Press and hold the TARGET RESET pushbutton, then slowly increase Current Input 2 (IA ) until

the PHASE DIFF CURRENT 87 LED illuminates, or the function status indicator on the MonitorFunction Status screen indicates that the function has picked up.

The current level of operation will be equal to P amps ±0.1 A or ±5%.

3. Release the TARGET RESET pushbutton, then decrease the Current Input 2 (IA ). The OUTPUT

LED(s) will extinguish.

4. Press TARGET RESET pushbutton to reset targets.

5. Repeat Steps 1,2,3 and 4 for each remaining phase exchanging IA(B,C)

and Ia(b,c)

as appropriate.

Timer Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply a current level to Current Input 2 (IA ) at least 10% greater than the minimum current pickup

level and start timing. The contacts will close after D cycles within 1 cycle or ±1%. When theTime Delay is set to 1 cycle, the relay operation is less than 1-1/2 cycles.

Page 280: Generator Relay Protection

6–61

Testing – 6

Slope Test:

1. Define a representative number of testing points to verify the trip curve.

2. For each Ia (Current Input 1) test point defined in Step 1, calculate the expected operating

current IA (Current Input 2) as follows:

(IA-Ia) > (IA+Ia) x Slope/100 ÷2Difference in currents is greater than sum of the currents times the per unit slope ÷2

or IA = [(1+K) ÷ (1-K)] x Ia where K = S/200 and where S is % slope input above.

NOTE: For tests above the restraint current (IA+I

a)/2 value of 2X Nominal Current; use a slope % value

equal to 4 times the input slope value (S) for these computations.

3. Set Current Input 1 (Ia ) and Current Input 2 (I

A ) to the values chosen in Step 1 and calculated in

Step 2 respectively.

4. Press and hold the TARGET RESET pushbutton, then slowly increase either Current Input 1 or 2until the PHASE DIFF CURRENT 87 LED illuminates, or the function status indicator on theMonitor Function Status screen indicates that the function has picked up.

The current level of operation will be equal to IA ±0.1 A or ±2% slope calculation. The difference in

current must be greater than minimum pickup current for proper operation.

5. Release the TARGET RESET pushbutton, then decrease the larger CURRENT. The OUTPUTLED(s) will extinguish.

6. Press TARGET RESET pushbutton to reset targets.

Page 281: Generator Relay Protection

M-3425A Instruction Book

6–62

87GD Ground Differential

VOLTAGE INPUTS: None

CURRENT INPUTS: As described

TEST SETTINGS: Pickup P Amps (0.20 to 10.00)1 Amp CT Rating (0.04 to 2.00)

CAUTION: Do NOT set the delay to less than 2 Cycles

Time Delay D Cycles (1 to 8160)

CT Ratio Correction (0.10 to 7.99)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine the Function 87GD Ground Differential settings to be tested.

2. Enter the Function 87GD Ground Differential settings to be tested utilizing either the HMI orIPScom® Communications Software.

3. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

4. Connect a current input to IN terminals 53 and 52.

5. Connect a current input to IA terminals 46 and 47, or I

B terminals 48 and 49.

Non–Directional Pickup Test:

1. Press and hold the TARGET RESET pushbutton, then slowly increase Current Input IN (terminals

53 and 52) until the GND DIFF/DIR O/C 87GD/67N LED illuminates, or the function statusindicator on the Monitor Function Status screen indicates that the function has picked up.

The current level of operation will be equal to P amps ±0.1 A or 5%.

2. Release the TARGET RESET pushbutton, then decrease the Current Input IN to 0 Amps. The

OUTPUT LED(s) will extinguish.

3. Press TARGET RESET pushbutton to reset targets.

Timer Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply a current level to Current Input IN at least 10% greater than the minimum current pickup

level and start timing. The contacts will close after D cycles within +1 to -2 cycles or ±1%.

3. Decrease the Current Input IN to 0 Amps.

Directional Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Apply a current of 1.0 Amp with a phase angle of 0 degrees to Current Input IN (terminals 53 and52).

3. Apply a current of P – 0.9 amps with a phase angle of 180 degrees to either Current Input IA or I

Band start timing.

The contacts will close after D cycles within 1 cycle or 1%.

4. Decrease the applied currents to 0 Amps.

Page 282: Generator Relay Protection

6–63

Testing – 6

5. Press the TARGET RESET pushbutton to reset targets.

6. Set the phase angle of the Current Input selected in Step 3, to 0 degrees, the Current Inputs arenow in phase.

7. Reapply a current of 1.0 Amp to Current Input IN (terminals 53 and 52).

8. Reapply a current of P – 0.9 Amps to the Current Input selected in Step 3, and start timing.

The relay will not operate. If the IA or I

B current input value is reduced to 140 ma or less and the

difference current exceeds the pickup value, the relay will operate regardless of polarities of thecurrents.

9. Decrease the applied currents to 0 amps.

Page 283: Generator Relay Protection

M-3425A Instruction Book

6–64

BM Breaker Monitoring

VOLTAGE INPUTS: None

CURRENT INPUTS: As Described

TEST SETTINGS: Pickup P kAmps (kA2)* (0 to 50,000)

Delay D Cycles (0.1 to 4095.9)

Timing Method ( IT or I2T)

Preset Accumulators

Phase A, B, or C kAmp (kA2) Cycles*(0 to 50,000)

Programmed Outputs Z OUT (1 to 8)

Blocking Inputs (1 to 6)Expanded I/O (7 to 14)

Output Initiate (1 to 8)Expanded I/O (9 to 23)

Input Initiate (1 to 6)Expanded I/O (7 to 14)

* kA/kA cycles or kA2/kA2 cycles is dependent on the Timing Method that is selected.

Test Setup:

1. Determine the Breaker Monitoring Function settings to be tested (Input Initiate or Output Initiate).

2. Enter the Breaker Monitoring Function settings to be tested utilizing either the HMI or IPScom®

Communications Software.

3. Connect a current input to IA terminals 46 and 47, I

B terminals 48 and 49, and I

C terminals 50 and

51.

4. Connect inputs for the polarization type selected for testing.

Accumulator Test:

1. Apply a current value that considers Timing Method and Pickup Setting to current input IA.

2. Place a jumper between the designated input and/or energize output contact selected as initiate.

3. Utilizing either the HMI (Status/Breaker Monitor Accumulator Status) or IPScom CommunicationsSoftware (Relay/Monitor/Accumulator Status), verify that the Accumulator Status value for PhaseA increments in D cycles 1 cycles or 1%.

4. De-energize the output and/or remove the jumper placed in Step 2.

5. Decrease applied IA current to 0 amps.

6. If desired, repeat test for IB and I

C.

Pickup Test:

1. Apply a current value that considers Timing Method and Pickup Setting to current input IA.

NOTE: If the target pickup setting is a large value (0 to 50,000) the Preset Accumulator Settings featurecan be used to pre-set the accumulator values to just below the target setting.

Page 284: Generator Relay Protection

6–65

Testing – 6

2. Utilizing either the HMI (Status/Breaker Monitor Accumulator Status) or IPScom CommunicationsSoftware (Relay/Monitor/Accumulator Status) to monitor the accumulator value, place a jumperbetween the designated input or energize the output contact selected as initiate and then removethe jumper and/or de-energize the output.

Following the time out of the Delay the accumulator will increment, repeat the placement andremoval of the jumper as necessary to increment the accumulator to a point where the pickupsetting is exceeded.

3. When the accumulator value exceeds the pickup value the OUTPUT LED(s) will illuminate, or thefunction status indicator on the Monitor Function Status screen indicates that the function haspicked up.

The output contacts Z will operate in D cycles 1 cycle or 1% from the last initiate.

4. If desired, repeat test for IB and I

C.

Page 285: Generator Relay Protection

M-3425A Instruction Book

6–66

Trip Circuit Monitoring

VOLTAGE INPUTS: As Described

CURRENT INPUTS: None

TEST SETTINGS: Delay D Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Test Setup:

1. Determine the Trip Circuit Monitoring function settings to be tested.

2. Disable all other functions prior to testing. Refer to Section 3.2, Initial Setup Procedure/Settings,Configure Relay Data subsection, for details that describe disabling/enabling functions.

3. Connect a DC voltage supply capable of supplying 24/48/125/250 V dc (marked on the rear of therelay) to terminals 1 (–) and 2 (+) on the relay.

4. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

Pickup Test:

1. Apply the applicable DC voltage (24/48/125/250 V dc marked on the rear of the relay) to terminals1 and 2.

2. Enable the Trip Circuit Monitoring function and then enter the settings to be tested utilizing eitherthe HMI or IPScom Communications Software.

3. Remove the DC voltage applied in Step 1. The OUTPUT LED will illuminate, or the function statusindicator on the Monitor Function Status screen will indicate that the Trip Circuit Monitoringfunction has actuated.

The contacts will close after D cycles within 1 cycle or 1%.

4. Simulate a 52b contact open by connecting a jumper between terminal 11 (INRTN) and terminal 10(IN1) which. The BRKR CLOSED and OUTPUT LEDs on the front of the relay should extinguish.

Also, the function status indicator on the Monitor Function Status screen will indicate that theTrip Circuit Monitoring function has cleared and the Secondary Status screen will indicate that thebreaker is closed.

5. Remove the jumper installed in Step 4.

The contacts will close after D cycles within 1 cycle or 1%.

Page 286: Generator Relay Protection

6–67

Testing – 6

IPSlogicTM (#1, #2, #3, #4, #5, #6)

VOLTAGE INPUTS: As Needed

CURRENT INPUTS: As Needed

TEST SETTINGS: Time Delay D Cycles (1 to 8160)

Programmed Outputs Z OUT (1 to 8)Expanded I/O (9 to 23)

Blocking Inputs (1 to 6)Expanded I/O (7 to 14)

Output Initiate (1 to 8)Expanded I/O (9 to 23)

Function Initiate Pickup (All Available Functions)

Function Initiate Time Out

Initiate by Communication

Input Initiate (1 to 6)Expanded I/O (7 to 14)

Block from Communication

Test Setup:

1. Refer to Figure 2-75, IPSlogic Function Setup, for logic gate configurations.

2. Select gate configuration (AND/OR/NAND/NOR) for Output Initiate, Function Initiate, BlockingInputs and Inputs Main.

3. Select Initiating Inputs for each gate (if AND gate is selected, ensure at least two outputs arechosen). It will be necessary to enable and operate other functions to provide inputs for theFunction Initiate and Output Initiate gates.

Time Test:

1. Connect a timer to output contacts (Z) so that the timer stops timing when the contacts (Z) close.

2. Connect a jumper from IN RTN (Terminal 11) to the designated Inputs (Terminals 1–6) for theIPSlogic gates and start timing. The IPS LOGIC LED and the OUTPUT LED will illuminate, or thefunction status indicator on the Monitor Function Status screen indicates that the function haspicked up.

The operating time will be D cycles ±1 cycle or 1%.

Blocking Input Test:

1. Press and hold the TARGET RESET pushbutton, then place a jumper from IN RTN (terminal 11)to the designated Blocking Inputs (terminals 1-6) to be tested. The EXTERNAL #1 EXT 1 LED willextinguish.

2. Repeat Step 1 for each designated external triggering contact.

Page 287: Generator Relay Protection

M-3425A Instruction Book

6–68

6.3 Diagnostic Test Procedures

OverviewThe diagnostic test procedures perform basicfunctional relay tests to verify the operation of thefront-panel controls, inputs, outputs, andcommunication ports.

88888 WARNING: Do not enter DIAGNOSTIC MODEwhen protected equipment is in service. EnteringDIAGNOSTIC MODE when protected equipmentis in service removes all protective functions ofthe relay.

The diagnostic menu includes the following tests:

• OUTPUT (Output Test Relay)

• INPUT (Input Test Status)

• LED (Status LED Test)

• TARGET (Target LED Test)

• EX_IO (Expanded I/O Test, Not Availableat this time)

• BUTTON (Button Test)

• DISP (Display Test)

• COM1 (COM1 Loopback Test)

• COM2 (COM2 Loopback Test)

• COM3 (COM3 Echo Test 2-Wire)

Each test is described individually in this section.

The diagnostic menu also provides access to thefollowing relay feature settings:

• CLOCK (Clock On/Off)

• LED (Relay OK LED Flash/Solid)

• CAL (Auto Calibration)

• FACTORY (Factory Use Only)

Auto Calibration is described in detail in Section6.4, Auto Calibration.

Entering Relay Diagnostic Mode88888 WARNING: Do not enter DIAGNOSTIC MODEwhen protected equipment is in service. EnteringDIAGNOSTIC MODE when protected equipmentis in service removes all protective functions ofthe relay.

1. Press ENTER to access the main menu.

2. Press the right arrow pushbutton untilthe following is displayed:

SETUP UNIT SETUP exit

3. Press ENTER, the following will bedisplayed:

SOFTWARE VERSIONVERS sn access number

4. Press the right arrow pushbutton untilthe following is displayed:

DIAGNOSTIC MODE time error DIAG

5. Press ENTER, the following warning willbe displayed:

PROCESSOR WILL RESET!ENTER KEY TO CONTINUE

88888 WARNING: Do not enter DIAGNOSTIC MODEwhen protected equipment is in service. EnteringDIAGNOSTIC MODE when protected equipmentis in service removes all protective functions ofthe relay.

6. Press ENTER, the relay will reset andDIAGNOSTIC MODE will be temporarilydisplayed followed by:

OUTPUT TEST (RELAY)OUTPUT input led target button disp com1 com2 com3 clock led cal factory

This marks the beginning of the diagnostic menu.The left arrow and right arrow pushbuttons are usedto navigate within the diagnostic menu. Exiting thediagnostic menu is accomplished by pressing EXIT,PRESS EXIT TO EXIT DIAGNOSTIC MODE isdisplayed, then pressing EXIT a second time.

Page 288: Generator Relay Protection

6–69

Testing – 6

Output Relay Test (Output Relays 1–23 and 25) NOTE: This test does not include testing of

Power Supply Relay (Output Relay 24).

1. Ensure the protected equipment is in aconfiguration/state that can support relayoutput testing.

2. Confirm the positions of the outputs inthe unoperated or OFF position. Thiscan be accomplished by connecting aDMM (Digital Multimeter) across theappropriate contacts and confirming openor closed. The de-energized or OFFposition for outputs 1 through 25 arelisted in Table 6-1.

TUPTUOYALERREBMUN

NEPOYLLAMRONTCATNOC

DESOLCYLLAMRON*TCATNOC

1 43-33 --

2 23-13 --

3 03-92 --

4 82-72 --

5 62-52 --

6 42-32 --

7 02-12 22-12

8 81-71 91-81

9 501-401 --

01 301-201 --

11 101-001 --

21 99-89 --

31 79-69 --

41 59-49 --

51 39-29 --

61 19-09 --

71 98-88 --

81 78-68 --

91 58-48 --

02 38-28 --

12 18-08 --

22 97-87 --

32 77-67 --

)42(ylppuSrewoP -- 31-21

)52(tseT-fleS 51-41 61-51

ehtfoetats)dezigrene-ed(FFOehtotsdnopserroctcatnocehtfonoitisop"lamroN"*.yaler

Table 6-1 Output Contacts

3. If the relay is already in the DiagnosticMode, then go to Step 4.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Diagnostic Modesection of this chapter, then go to Step 4.

4. Ensure that the Diagnostic Menu isselected to OUTPUT (Upper Case).

OUTPUT TEST (RELAY)OUTPUT input led target button disp com1 com2 com3 clock led cal factory

If OUTPUT is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select OUTPUT.

5. Press ENTER, the relay will display thefollowing:

RELAY NUMBER1

6. Select the Output Relay (from Table 6-1)to be tested, utilizing the Up/Down arrowpushbuttons.

7. Press ENTER. The following will bedisplayed for the selected relay:

RELAY NUMBER 1OFF on

8. Select ON (Upper Case) utilizing theRight arrow pushbutton. The relay willrespond as follows:a. Output relay energizes (On position)b. Appropriate red OUTPUT LED

illuminates, if equipped.If testing all output relays, then pressEXIT to return to the output relayselection menu, then repeat Steps 6, 7and 8 for each output relay.

9. The DMM can now be used to verify thatthe output relay contact is in the operatedor ON position. The readings should bethe opposite of the initial readingdetermined in Step 2.

10. When output relay testing is completethen restore all output relays to their de-energized or OFF positions listed in Table6-1 and press EXIT to return to theDiagnostic Menu.

Page 289: Generator Relay Protection

M-3425A Instruction Book

6–70

11. If all Diagnostic Testing is complete,then exit the diagnostic menu by pressingEXIT, PRESS EXIT TO EXITDIAGNOSTIC MODE is displayed, thenpress EXIT a second time.

Output Relay Test (Power Supply Relay 24)The power supply output relay can be tested byperforming the following:

NOTE: For this test the relay is not required tobe in the Diagnostic Mode.

1. Ensure the protected equipment is in aconfiguration/state that can support relayoutput testing.

2. Confirm the position of output relay 24 inthe unoperated or OFF position. Thiscan be accomplished by connecting aDMM (Digital Multimeter) across theappropriate contacts and confirming openor closed. The de-energized or OFFposition for Output 24 is listed in Table6-1.

3. Remove power from the relay. The DMMcan now be used to verify that outputrelay 24 contact is in the operated or ONposition. The reading should be theopposite of the initial reading determinedin Step 2.

4. Restore power to the relay.

Input Test (Control/Status)The INPUT TEST menu enables the user todetermine the status of the individual control/statusinputs. Individual inputs can be selected by numberusing the up and down arrow pushbuttons. Thestatus of the input will then be displayed.

TUPNIREBMUN

NOMMOCLANIMRET LANIMRET

)b25(1 11 01

2 11 9

3 11 8

4 11 7

5 11 6

6 11 5

stupnIO/IdednapxE

7 76ro66 57

8 76ro66 47

9 76ro66 37

01 76ro66 27

11 76ro66 17

21 76ro66 07

31 76ro66 96

41 76ro66 86

Table 6-2 Input Contacts

1. Ensure the protected equipment is in aconfiguration/state that can support relayinput testing.

2. If the relay is already in the DiagnosticMode, then go to Step 3.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Diagnostic Modesection of this chapter, then go to Step 3.

Page 290: Generator Relay Protection

6–71

Testing – 6

3. Ensure that the Diagnostic Menu isselected to INPUT (Upper Case).

INPUT TEST (RELAY)output INPUT led target button disp com1 com2 com3 clock led cal factory

If INPUT is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select INPUT.

4. Press ENTER. The following is displayed:

INPUT NUMBER1

5. Select the Input Relay (from Table 6-2)to be tested utilizing the Up/Down arrowpushbuttons.

6. Press ENTER. The following is displayedfor the selected relay:

INPUT NUMBER 1CIRCUIT OPEN

7. If no external control/status inputs areconnected to the relay, then place ajumper between the IN RTN terminal(terminal #11 for Inputs 1–6, and eitherterminal #66 or #67 for Inputs 7–14) andthe IN1 terminal (terminal #10). See Table6-2 for terminals for inputs 2 through 14.

Alternatively, if this specific input isbeing used in this application and theexternal wiring is complete, the actualexternal control/status input contact canbe manually closed. This will test theinput contact operation and the externalwiring to the input contacts.

The following is immediately displayed:

INPUT NUMBER 1CIRCUIT CLOSED

8. Remove the jumper between the IN RTNterminal (terminal #11 for Inputs 1–6,and either terminal #66 or #67 for Inputs7–14) and the IN1 terminal (terminal #10).

The following is immediately displayed:

INPUT NUMBER 1CIRCUIT OPEN

9. If testing all inputs, press EXIT to returnto the input selection menu, then repeatSteps 5, 6, 7 and 8 for each input.

10. When input testing is complete theninsure all jumpers have been removedand press EXIT to return to the DiagnosticMenu.

11. If all Diagnostic Testing is complete,then exit the diagnostic menu by pressingEXIT, PRESS EXIT TO EXITDIAGNOSTIC MODE is displayed, thenpress EXIT a second time.

Status LED TestThe STATUS LED TEST menu enables the user tocheck the front-panel LEDs individually.

!

"#

Figure 6-8 Status LED Panel

1. If the relay is already in the DiagnosticMode, then go to Step 2.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Diagnostic Modesection of this chapter, then go to Step 2.

2. Ensure that the Diagnostic Menu isselected to LED (Upper Case).

STATUS LED TESToutput input LED target button disp com1 com2 com3 clock led cal factory

If LED is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select LED.

3. Press ENTER. LED #1 (RELAY OK)illuminates and the following is displayed:

STATUS LED TESTLED NUMBER 1 = ON

Page 291: Generator Relay Protection

M-3425A Instruction Book

6–72

4. If testing all Status LEDs, press theright arrow pushbutton to toggle throughthe remaining LEDs illustrated in Figure6-8, with the exception of the PS1 &PS2 LEDs.

5. When Status LED testing is completepress EXIT to return to the DiagnosticMenu.

6. If all Diagnostic Testing is complete,then exit the diagnostic menu by pressingEXIT, PRESS EXIT TO EXITDIAGNOSTIC MODE is displayed, thenpress EXIT a second time.

Target LED TestThe TARGET LED TEST menu allows the user tocheck the M-3925A Target Module LEDs individually.

TARGETS

OUTPUTSOUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

OUT 7

OUT 8

24 VOLTS/Hz

27 PHASE UNDERVOLTAGE

59 PHASE OVERVOLTAGE

27TN/59D/64S STATOR GND

59N/59X NEUT/GND OVERVOLT

32 DIRECTIONAL POWER

21 PHASE DISTANCE

40 LOSS OF FIELD

78 OUT OF STEP

50BF BREAKER FAILURE

50/27INADVERTENT ENRGNG

60FL V.T. FUSE LOSS

PHASE OVERCURRENT 50

PHASE OVERCURRENT 51V

NEUTRAL O/C 50N/51N

SPLIT PHASE DIFF 50DT

STATOR OVERLOAD 49

NEG SEQ OVERCURRENT46

FIELD GND/BRUSH LIFT64F/B

FREQUENCY 81/81R/81A

PHASE DIFF CURRENT 87

GND DIFF/DIR O/C 87GD/67N

TRIP CIRCUIT MONITOR TC

IPS LOGIC LOGIC

Figure 6-9 M-3925A Target Module Panel

1. If the relay is already in the DiagnosticMode, then go to Step 2.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Diagnostic Modesection of this chapter, then go to Step 2.

2. Ensure that the Diagnostic Menu isselected to TARGET (Upper Case).

TARGET LED TESToutput input led TARGET button disp com1 com2 com3 clock led cal factory

If TARGET is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select TARGET.

3. Press ENTER. Target LED #1 lights andthe following is displayed:

TARGET LED TESTLED NUMBER 1 = ON

4. If testing all Target LEDs, press the rightarrow pushbutton to toggle through theremaining Target LEDs illustrated inFigure 6-9.

5. When Target LED testing is completepress EXIT to return to the DiagnosticMenu.

6. If all Diagnostic Testing is complete,then exit the diagnostic menu by pressingEXIT, PRESS EXIT TO EXITDIAGNOSTIC MODE is displayed, thenpress EXIT a second time.

Button TestThe BUTTON TEST menu selection allows the userto check the M-3931 HMI Module buttons. As eachpushbutton is pressed, its name is displayed.

45& )&

Figure 6-10 M-3931 Human-MachineInterface Module

1. If the relay is already in the DiagnosticMode, then go to Step 2.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Diagnostic Modesection of this chapter, then go to Step 2.

Page 292: Generator Relay Protection

6–73

Testing – 6

2. Ensure that the Diagnostic Menu isselected to BUTTON (Upper Case).

BUTTON TESToutput input led target BUTTON disp com1 com2 com3 clock led cal factory

If BUTTON is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select BUTTON.

3. Press ENTER. The following is displayed:

BUTTON TEST0

NOTE: Pressing the EXIT pushbutton will exitfrom this test, and therefore should belast pushbutton tested. If it is pushedbefore this test sequence is completed,the test may be restarted by pushingENTER. Notice that the word EXIT isdisplayed temporarily before the testsequence is exited.

4. Press each pushbutton for test. As eachbutton is pressed, the display will brieflyshow the name for each key (“RIGHTARROW”, “UP ARROW”, etc).

5. When pushbutton testing is completepress EXIT to return to the DiagnosticMenu.

6. If all Diagnostic Testing is complete,then exit the diagnostic menu by pressingEXIT, PRESS EXIT TO EXITDIAGNOSTIC MODE is displayed, thenpress EXIT a second time.

Display TestThe DISPLAY TEST menu selection enables theuser to check the display. This test cycles throughvarying test patterns until EXIT is pressed.

1. If the relay is already in the DiagnosticMode, then go to Step 2.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Diagnostic Modesection of this chapter, then go to Step 2.

2. Ensure that the Diagnostic Menu isselected to DISPLAY TEST (UpperCase).

DISPLAY TESToutput input led target button DISP com1 com2 com3 clock led cal factory

If DISP is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select DISP.

3. Press ENTER, the unit will display asequence of test characters until EXITis pushed.

4. After the test has cycled throughcompletely, press EXIT to return to theDiagnostic Menu.

5. If all Diagnostic Testing is complete,then exit the diagnostic menu by pressingEXIT, PRESS EXIT TO EXITDIAGNOSTIC MODE is displayed, thenpress EXIT a second time.

COM1/COM2 Loopback TestThe COM1 LOOPBACK TEST menu allows theuser to test the front-panel RS-232 port. COM2LOOPBACK TEST menu tests the rear panel RS-232port.

A loopback plug is required for this test. The requiredloopback plug consists of a DB9P connector (male)with pin 2 (RX) connected to pin 3 (TX) and pin 7(RTS) connected to pin 8 (CTS). No otherconnections are necessary.

,-%#.,/.,

0

1 2

%)30 #

(12) &2)

Figure 6-11 COM1/COM2 Loopback Plug

Page 293: Generator Relay Protection

M-3425A Instruction Book

6–74

1. If the relay is already in the DiagnosticMode, then go to Step 2.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Diagnostic Modesection of this chapter, then go to Step 2.

2. Ensure that the Diagnostic Menu isselected to COM1 LOOPBACK TEST(Upper Case).

COM1 LOOPBACK TESToutput input led target button disp COM1 com2 com3 clock led cal factory

If COM1 is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select COM1.

3. Press ENTER. The following is displayed:

COM1 LOOPBACK TESTCONNECT LOOPBACK PLUG

4. Connect the loop-back plug to COM1,the front-panel RS-232C connector.

5. Press ENTER, the relay will initiate theloopback test.

If the COM Port passes the loopbacktest the following will be displayed:

COM1 LOOPBACK TEST-DONE-

If the COM Port fails the loopback testthe following will be displayed:

COM1 LOOPBACK TESTRX–TX FAIL

6. Press EXIT to return to the DIAGNOSTICMenu.

7. If all Diagnostic Testing is complete,then exit the diagnostic menu by pressingEXIT, PRESS EXIT TO EXITDIAGNOSTIC MODE is displayed, thenpress EXIT a second time.

8. Ensure that the Diagnostic Menu isselected to COM2 LOOPBACK TEST(Upper Case).

COM2 LOOPBACK TESToutput input led target button disp com1 COM2 com3 clock led cal factory

If COM2 is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select COM2.

8. Press ENTER, then repeat Steps 3through 6 for COM2.

COM3 Test (2-Wire)The COM3 Echo Test 2-Wire allows the user to testthe RS-485 rear terminal connections for properoperation.

NOTE: This test requires a PC with an RS-485converter and terminal emulator softwareinstalled.

1. If the relay is already in the DiagnosticMode, then go to Step 2.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Diagnostic Modesection of this chapter, then go to Step2.

2. Ensure that the Diagnostic Menu isselected to COM3 ECHO TEST 2 WIRE(Upper Case).

COM3 ECHO TEST 2 WIREoutput input led target button disp com1 com2 COM3 clock led cal factory

If COM3 is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select COM3.

3. Press ENTER. The following is displayed:

COM3 ECHO TEST 2WIREIDLING...9600, N, 8, 1

Page 294: Generator Relay Protection

6–75

Testing – 6

4. From the rear of the unit, connect a PCto the relay at terminals 3(-) and 4(+)using an RS-485 converter set for 2-wireoperation. See Figure 6-12 for diagram.

4

!

" #$%

$

%

Figure 6-12 RS-485 2-Wire Testing

5. Set the following PC communicationsparameters:

Baud Rate 9600

Parity None

Data Bits 8

Stop Bits 1

Duplex Half

6. Open the terminal emulator program onthe PC, then open the COM port for theRS-485 converter.

7. Press a key on the PC keyboard, thenverify the following:

a. The character pressed is displayedtemporarily on the relay display.

b. The character pressed is displayedon the PC monitor.

8. When communication has been verified,press EXIT, the following is displayed:

COM3 ECHO TEST 2WIRE-DONE-

9. Press EXIT to return to the DIAGNOSTICMenu.

10. Close the COM port on the PC, and exitthe terminal program.

11. If all Diagnostic Testing is complete,then exit the diagnostic menu by pressingEXIT, PRESS EXIT TO EXITDIAGNOSTIC MODE is displayed, thenpress EXIT a second time.

Clock ON/OFFThis feature provides the user with the ability toeither start or stop the clock.

1. If the relay is already in the DiagnosticMode, then go to Step 2.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Diagnostic Modesection of this chapter, then go to Step 2.

2. Ensure that the Diagnostic Menu isselected to CLOCK ON/OFF (UpperCase).

CLOCK START/STOPoutput input led target button disp com1 com2 com3 CLOCK led cal factory

If CLOCK is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select CLOCK.

NOTE: ‘80’ will be displayed in the secondsplace when the clock is stopped.

3. Press ENTER, the following is displayed:

a. If the clock is already running thefollowing will be displayed and willcontinue to update.

CLOCK TEST01-Jan-2003 01:01:01

b. If the clock was NOT running thefollowing will be displayed:

CLOCK TEST01-Jan-2003 01:01:80

4. To start or stop the clock press ENTER,the following is displayed:

a. If the clock is already running thefollowing will be displayed:

CLOCK TESTCLOCK STOP

CLOCK TEST01-Jan-2003 01:01:80

Page 295: Generator Relay Protection

M-3425A Instruction Book

6–76

b. If the clock was NOT running thefollowing will be displayed:

CLOCK TESTCLOCK START

CLOCK TEST01-Jan-2003 01:01:01

NOTE: To preserve battery life the clock shouldbe OFF if the unit is to be left de-energized for a long period of time.

5. The clock can be toggled ON or OFF bypressing any arrow pushbutton or ENTER.

To exit the Clock ON/OFF mode pressEXIT, the following will be displayed:

CLOCK TEST-DONE-

6. To exit the CLOCK ON/OFF DiagnosticMenu press EXIT.

7. If all Diagnostic Testing is complete,then exit the diagnostic menu by pressingEXIT, PRESS EXIT TO EXITDIAGNOSTIC MODE is displayed, thenpress EXIT a second time.

Relay OK LED Flash/IlluminatedThis feature provides the user with the ability to setthe relay OK LED to either Flash or be Illuminatedwhen the relay is working properly.

1. If the relay is already in the DiagnosticMode, then go to Step 2.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Diagnostic Modesection of this chapter, then go to Step 2.

2. Ensure that the Diagnostic Menu isselected to FLASH RELAY OK LED(Upper Case).

FLASH RELAY OK LEDoutput input led target button disp com1 com2 com3 clock LED cal factory

If LED (to the left of cal) is not selected(Upper Case), then use the Right/Leftarrow pushbuttons to select LED.

3. Press ENTER, the following will bedisplayed:

FLASH RELAY OK LEDOFF on

4. Select (upper case) either ON (to flash)or OFF (to Illuminate) by pressing theright/left arrow pushbutton once.

5. Press ENTER, the following will bedisplayed:

FLASH RELAY OK LED-DONE-

6. To exit the FLASH RELAY OK LEDDiagnostic Menu press EXIT.

7. If all Diagnostic Testing is complete,then exit the diagnostic menu by pressingEXIT, PRESS EXIT TO EXITDIAGNOSTIC MODE is displayed, thenpress EXIT a second time.

Auto CalibrationRefer to the following Section 6.4, Auto Calibration,for more information on that function.

AUTO CALIBRATION clock led CAL factory

Factory Use OnlyThis function is provided to allow access by factorypersonnel.

FACTORY USE ONLY clock led cal FACTORY

Page 296: Generator Relay Protection

6–77

Testing – 6

6.4 Auto Calibration

NOTE: The M-3425A Generator Protection Relayhas been fully calibrated at the factory.There is no need to recalibrate the unitprior to initial installation. However, in-system calibration of the 64F functionmay be needed for units purchased withthe 64F Field Ground option. Calibrationcan be initiated using the HMI or IPSutil™program.

Phase and Neutral Fundamental Calibration1. If the relay is already in the Diagnostic

Mode, then go to Step 2.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Diagnostic Modesection of this chapter, then go to Step 2.

2. Ensure that the Diagnostic Menu isselected to CAL (upper case).

FLASH RELAY OK LEDoutput input led target button disp com1 com2 com3 clock led CAL factory

If CAL is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select CAL.

3. Press ENTER, the following will bedisplayed:

60 HZ CALIBRATION60_HZ field_gnd

4. Ensure that the 60 HZ Calibration Menuis selected to 60_HZ (Upper Case).

If 60_HZ is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select 60_HZ.

5. Press ENTER, the following will bedisplayed:

60 HZ CALIBRATIONNOM_F 3rdh_F 64s_f

6. Ensure that NOM_F is selected (UpperCase).

If NOM_F is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select NOM_F.

7. Press ENTER, the following will bedisplayed:

CONNECT REFERENCE INPUTSPRESS ENTER TO CALIBRATE

8. Connect VA

= VB

= VC

= VN

= VX

=120.0(±0.01) V at 0° phase. (See Figure 6-14.)

9. Connect Ia=I

b=I

c=I

A=I

B=I

C=I

N=5.00**

Amps at 0° (see Figure 6-13).

** For a 1 A CT rating, use 1 A.If 64S is purchased, do not put nominalcurrent in the IN channel. The IN input iscalibrated separately (see 64Sprocedure.)

The calibration can be verified by exiting from theDiagnostic menu and reading status:

VA=VB=VC=VN=VX=120V V1=V2=0 V0=120V

IA=IB=IC=5 A** I1=I2=0 I0=5 A**

Ia=Ib=Ic=5 A**

Real=1 pu Reactive=0.0 pu

Power Factor = 1.0

Idiffa = Idiffb = Idiffc = 0

Where subscript 0, 1, and 2 represent zero, positive,and negative sequence quantities, respectively.

** For a 1 A CT rating, use 1 A.

NOTE: The phase angle difference betweenvoltage and current input source shouldbe 0°, ±0.05°, and an accurate low-distortion source should be used. (THDless than 1%).

10. Press ENTER, the following will bedisplayed while the relay is beingcalibrated:

CALIBRATINGWAIT

When the calibration is complete, thefollowing will be displayed:

CALIBRATINGDONE

11. Remove the calibration source inputs.

Page 297: Generator Relay Protection

M-3425A Instruction Book

6–78

Third Harmonic Calibration1. If it is desired to calibrate the third

harmonic only and the relay is already inthe Diagnostic Mode, then go to Step 2.

If it is desired to calibrate the thirdharmonic only and the relay is NOT inthe Diagnostic Mode, then enter the relaydiagnostic mode by performing the stepsdescribed in the Entering RelayDaignostic Mode section of this chapter,then go to Step 2.

2. Ensure that the Diagnostic Menu isselected to CAL (upper case).

FLASH RELAY OK LEDoutput input led target button disp com1 com2 com3 clock led CAL factory

If CAL is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select CAL.

3. Press ENTER, the following will bedisplayed:

60 HZ CALIBRATION60_HZ field_gnd

4. Ensure that the 60 HZ Calibration Menuis selected to 60_HZ (Upper Case).

If 60_HZ is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select 60_HZ.

5. Press ENTER, the following will bedisplayed:

60 HZ CALIBRATIONnom_f 3RDH_F 64s_f

6. Ensure that 3RDH_F is selected (UpperCase).

If 3RDH_F is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select 3RDH_F.

7. Press ENTER, the following will bedisplayed:

INPUT 180 HZPRESS ENTER TO CALIBRATE

(150 Hz for 50 Hz units)

8. Connect Voltage Inputs as follows:a. Connect V

N= V

X =10.0 V, 180 Hz

(150 Hz for 50 Hz units). See Figure6-15.

b. Connect VA=V

B=V

C=120.0 V, 180 Hz

(150 Hz for 50 Hz units). See Figure6-16.

9. Press ENTER, the following will bedisplayed while the Third Harmonic iscalibrated:

CALIBRATINGWAIT

When the calibration is complete, thefollowing will be displayed:

AUTO CALIBRATIONDONE

10. Remove the voltage from VN and V

X.

11. Remove the calibration source inputs.

64S 100% Stator Ground by Low FrequencyInjection Calibration

1. If it is desired to calibrate the 64S 100%Stator Ground by Low FrequencyInjection only and the relay is already inthe Diagnostic Mode, then go to Step 2.

If it is desired to calibrate the 64S 100%Stator Ground by Low FrequencyInjection only and the relay is NOT in theDiagnostic Mode, then enter the relaydiagnostic mode by performing the stepsdescribed in the Entering RelayDaignostic Mode section of this chapter,then go to Step 2.

2. Ensure that the Diagnostic Menu isselected to CAL (upper case).

FLASH RELAY OK LEDoutput input led target button disp com1 com2 com3 clock led CAL factory

If CAL is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select CAL.

3. Press ENTER, the following will bedisplayed:

60 HZ CALIBRATION60_HZ field_gnd

4. Ensure that the 60 HZ Calibration Menuis selected to 60_HZ (Upper Case).

If 60_HZ is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select 60_HZ.

Page 298: Generator Relay Protection

6–79

Testing – 6

5. Press ENTER, the following will bedisplayed:

60 HZ CALIBRATIONnom_f 3rdh_f 64S_F

6. Ensure that 64S_F is selected (UpperCase).

If 64S_F is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select 64S_F.

7. Press ENTER, the following will bedisplayed:

INPUT 20 HZPRESS ENTER TO CALIBRATE

8. Connect VN=10.0 V ( 0.01 V) 20 Hz,

IN=10.0 mA ( 0.01 mA) 20 Hz. See

Figure 6-6.

9. Press ENTER, the following will bedisplayed while the 64S is calibrated:

CALIBRATINGWAIT

When the calibration is complete, thefollowing will be displayed:

CALIBRATINGDONE

10. Remove the voltage from VN and I

N.

11. Remove the calibration source inputs.

Field Ground CalibrationField Ground Calibration only applies to unitspurchased with the 64F Field Ground option.Calibration is necessary for long cable lengths(greater than 100 feet) to compensate for cablinglosses from the M-3425A and the M-3921 Couplermodule, and therefore should be accomplished insystem, after all wiring is complete.

1. Connect the M-3921 Field Ground Couplerbox as shown in Figure 6-7, Field GroundCoupler.

2. If the relay is already in the DiagnosticMode, then go to Step 3.

If the relay is NOT in the DiagnosticMode, then enter the relay diagnosticmode by performing the steps describedin the Entering Relay Daignostic Modesection of this chapter, then go to Step 3.

3. Ensure that the Diagnostic Menu isselected to CAL (upper case).

FLASH RELAY OK LEDoutput input led target button disp com1 com2 com3 clock led CAL factory

If CAL is not selected (Upper Case),then use the Right/Left arrow pushbuttonsto select CAL.

4. Press ENTER, the following will bedisplayed:

60 HZ CALIBRATION60_HZ field_gnd

5. Ensure that the 60 HZ Calibration Menuis selected to FIELD_GND (Upper Case).

If FIELD_GND is not selected (UpperCase), then use the Right arrowpushbutton to select FIELD_GND.

6. Press ENTER, the following will bedisplayed:

CONNECT 1 KOHM REF.PRESS ENTER TO CALIBRATE

7. Set the decade box for 1 kΩ resistance,then press ENTER, the following will bedisplayed:

CALIBRATINGWAIT

8. When the calibration is complete thefollowing will be displayed:

CALIBRATINGDONE

9. Press ENTER, the unit will display thenext resistance in the calibrationsequence to be tested.

10. Set the decade box to the resistancespecified by the HMI, then press ENTER.When the display shows DONE pressENTER.

11. Repeat Step 10 until the calibration iscomplete for 100 kΩ.

12. Press EXIT twice to exit the DiagnosticMode.

Page 299: Generator Relay Protection

M-3425A Instruction Book

6–80

IA

55

54

57

56

59

58

53

52

Current Input

Polarity

IB

IC

IN

Ia

Ib

Ic50

51

48

49

46

47

Figure 6-13 Current Input Configuration

Figure 6-14 Voltage Input Configuration

Figure 6-15 Voltage Input Configuration

Page 300: Generator Relay Protection

6–81

Testing – 6

Hot

Neutral

VoltageInput VA

39

38

41

40

43

42

VB

VC

Figure 6-16 Voltage Input Configuration

Page 301: Generator Relay Protection

M-3425A Instruction Book

6–82

This Page Left Intentionally Blank

Page 302: Generator Relay Protection

A–1

Appendix – A

AAppendix A – Configuration Record Forms

This Appendix contains photocopy–ready forms forrecording the configuration and setting of theM-3425A Generator Protection Relay. The formscan be supplied to field service personnel forconfiguring the relay, and kept on file for futurereference.

A copy of the Relay Configuration Table (TableA-1) is provided to define and record the blockinginputs and output configuration. For each function;check the D (disabled) column or check the outputcontacts to be operated by the function, and checkthe inputs designated to block the function operation.

Figure A-2, Communication Data & Unit SetupRecord Form reproduces the Communication andSetup unit menus. This form records definition ofthe parameters necessary for communication withthe relay, as well as access codes, user logo lines,date & time setting, and front panel display operation.

Figure A-3, Functional Configuration Record Formreproduces the Configure Relay menus. For eachfunction or setpoint, refer to the configuration youhave defined using the Relay Configuration Table,and circle whether it should be enabled or disabled,the output contacts it will activate, and the inputsthat will block its operation.

Figure A-4, Setpoint & Timing Record Form allowsrecording of the specific values entered for eachenabled setpoint or function. The form follows themain menu selections of the relay.

Unpurchased or unavailable functions will not bevisible within the menus. If a function is DISABLED,the input/output screens for that function will not bedisplayed.

Page 303: Generator Relay Protection

A–2

M-3425A Instruction Book

Check each box applicable : (See page A-1 for information on using this table.)D Column = Function Disabled.OUTPUTS Columns =Designated function output(s)fl Column = Function blocked by fuse loss.INPUTS Columns =Designated function blocking input(s)

NOITCNUFD O U T P U T S I N P U T S

8 7 6 5 4 3 2 1 LF 6 5 4 3 2 1

12

1

2

3

421

2

52

72

1

2

3

NT721

2

23

1

2

3

041

2

64FED

VNI

94

051

2

FB05

N05

TD051

2

72/05

N15

V15

95

1

2

3

D95

N95

1

2

3

Table A-1 Relay Configuration Table (page 1 of 4)

Page 304: Generator Relay Protection

A–3

Appendix – A

Table A-1 Relay Configuration Table (page 2 of 4)

FUNCTIOND O U T P U T S I N P U T S

8 7 6 5 4 3 2 1 FL 6 5 4 3 2 1

59X

60FL

64B

64F1

2

67NDEF

INV

64S

78

81

1

2

3

4

81A

1

2

3

4

5

6

81R1

2

871

2

87GD

BM

TCKT

IPS

1

2

3

4

5

6

Check each box applicable : (See page A-1 for information on using this table.)D Column = Function Disabled.OUTPUTS Columns =Designated function output(s)fl Column = Function blocked by fuse loss.INPUTS Columns =Designated function blocking input(s)

Page 305: Generator Relay Protection

A–4

M-3425A Instruction Book

Table A-1 Relay Configuration Table (page 3 of 4)

FUNCTIOND EXPANDED OUTPUTS EXPANDED INPUTS

23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 14 13 12 11 10 9 8 7

21

1

2

3

241

2

25

27

1

2

3

27TN1

2

32

1

2

3

401

2

46DEF

INV

49

501

2

50BF

50N

50DT1

2

50/27

51N

51V

59

1

2

3

59D

59N

1

2

3

Page 306: Generator Relay Protection

A–5

Appendix – A

NOITCNUFD STUPTUODEDNAPXE STUPNIDEDNAPXE

32 22 12 02 91 81 71 61 51 41 31 21 11 01 9 41 31 21 11 01 9 8 7

X95

LF06

B46

F461

2

N76FED

VNI

S46

87

18

1

2

3

4

A18

1

2

3

4

5

6

R181

2

781

2

DG78

MB

TKCT

SPI

1

2

3

4

5

6

Table A-1 Relay Configuration Table - Expanded I/O (page 4 of 4)

Page 307: Generator Relay Protection

A–6

M-3425A Instruction Book

KEY TO INPUT DATA RECORD FORMS

A. All heavily bordered screens are either MENU screens which have horizontal choices(made with right - left arrows) or screens displaying a result of a choice previously made.

B. Dashed boxes enclose screens which bound areas that pushbutton ENTER willmove in. In order to move out of one of the dotted boxes it is necessary to either push EXIT ormake a menu choice change using the Right - Left arrow.

C. The Up/Down arrows only adjust value or letter (lower/upper case) inputs; they do not move withinthe menus or between menu displays.

D. The Right/Left arrows are used only to make horizontally displayed choices. These can be eithermenu choices or input value digit choices. The previous choice or location in a menu is highlightedimmediately.

E. The ENTER pushbutton records the setting change (whatever is in that screen when ENTER ispressed will be installed in memory) and moves down within a menu. The operator will notice thatafter the last menu item, ENTER moves to the top of the same menu but does not change menupositions.

F. Pressing EXIT at any time will exit the display screen to the last screen containing a horizontalchoice. (Return to the preceding menu).

Figure A-1 Human-Machine Interface Module

G. The symbol or in a screen indicates additional horizontal menu choices are available in theindicated direction. As previously described, the Right and Left arrows will move the operator tothose additional choices.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 308: Generator Relay Protection

A–7

Appendix – A

COM3 SETUPcom1 com2 COM3 com_adr

COM3 DEAD SYNC TIME________ MS

COM3 PROTOCOLbeco2200 MODBUS

COM3 PARITYNONE odd even

COM3 STOP BITS________

COMMUNICATION ADDRESScom1 com2 com3 COM_ADR

COMMUNICATION ADDRESS________

RESPONSE TIME DELAY DLY accss eth eth_ip

COMM ACCESS CODE dly ACCSS eth eth_ip

COMM ACCESS CODE________

Figure A-2 Communication Data & Unit Setup Record Form (page 1 of 3)

COM1 SETUPCOM1 com2 com3 com-adr

COM1 BAUD RATEbaud_300 baud_600 baud_1200 baud_4800 BAUD_9600

COM2 SETUPcom1 COM2 com3 com_adr

COM2 BAUD RATEbaud_300 baud_600 baud_1200 baud_4800 BAUD_9600

COM2 DEAD SYNC TIME________ MS

COM2 PROTOCOLbeco2200 MODBUS

COM2 PARITYnone odd even

COM2 STOP BITS________

COMMUNICATIONtargets osc_rec COMM

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 309: Generator Relay Protection

A–8

M-3425A Instruction Book

ETHERNET dly accss ETH eth_ip

ETHERNETdisable ENABLE

TCP/IP SETTINGSTCP prot

DHCP PROTOCOLdisable ENABLE

DHCP PROTOCOLDISABLE enable

IP ADDRESS________

NET MASK________

GATEWAY________

COMMUNICATIONtargets osc_rec COMM

ETHERNET PROTOCOLtcp PROT

SELECT PROTOCOLmodbus serconv

ETHERNET ADDRESS accss eth ETH_IP

ETHERNET IP ADDRESSXX.XX.XX.XX

Figure A-2 Communication Data & Unit Setup Record Form (page 2 of 3)

After EXIT to Comm menu,the following will be dis-played (if any changes havebeen made in ETHERNET menu)

CONFIGURING ETH...

ETHERNET IP ADDRESSXX.XX.XX.XX

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 310: Generator Relay Protection

A–9

Appendix – ASETUP UNIT SETUP exit

SOFTWARE VERSIONVERS sn access number

SOFTWARE VERSIOND-XXXXV__.__.__

SERIAL NUMBERvers SN access number

SERIAL NUMBER________

ALTER ACCESS CODESvers sn ACCESS number

ENTER ACCESS CODELEVEL#1 level#2 level#3

LEVEL #1________

ENTER ACCESS CODElevel#1 LEVEL#2 level#3

LEVEL #2________

ENTER ACCESS CODElevel#1 level#2 LEVEL#3

LEVEL #3________

USER CONTROL NUMBERvers sn access NUMBER

USER CONTROL NUMBER________

USER LOGO LINE 1 LOGO1 logo2 out alrm

USER LOGO LINE 1

USER LOGO LINE 2 logo1 LOGO2 out alrm

USER LOGO LINE 2

CLEAR OUTPUT COUNTERS logo1 logo2 OUT alrm

CLEAR OUTPUT COUNTERSPRESS ENTER KEY TO CLEAR

CLEAR ALARM COUNTER logo1 logo2 out ALRM

CLEAR ALARM COUNTERPRESS ENTER KEY TO CLEAR

DATE & TIMETIME error eth_ver

DATE & TIME01-Jan-2001 12:00:00

DATE & TIME________ YEAR

DATE & TIMEJAN feb mar apr may jun jul aug sep oct nov dec

DATE & TIME________ DATE

DATE & TIMEsun mon tue wed thu fri sat

DATE & TIME________ HOUR

DATE & TIME________ MINUTES

DATE & TIME________ SECONDS

CLEAR ERROR CODES time ERROR eth_ver

CLEAR ERROR CODESPRESS ENTER KEY TO CLEAR

ETHERNET FIRMWARE VER time error ETH_VER

ETHERNET FIRMWARE VERD-____V__.__.__

DIAGNOSTIC MODE DIAG

PROCESSOR WILL RESET!ENTER KEY TO CONTINUE

Figure A-2 Communication Data & Unit Setup Record Form (page 3 of 3)

Page 311: Generator Relay Protection

A–10

M-3425A Instruction Book

CONFIGURE RELAYVOLTAGE_RELAY

27 #1 PHASE UNDERVOLTAGEdisable ENABLE

27 #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

27 #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

27 #2 PHASE UNDERVOLTAGEdisable ENABLE

27 #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

27 #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

27 #3 PHASE UNDERVOLTAGEdisable ENABLE

27 #3 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

27 #3 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

59 #1 PHASE OVERVOLTAGEdisable ENABLE

59 #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

59 #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

59 #2 PHASE OVERVOLTAGEdisable ENABLE

59 #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

59 #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

59 #3 PHASE OVERVOLTAGEdisable ENABLE

59 #3 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

59 #3 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Figure A-3 Functional Configuration Record Form (1 of 18)

CONFIGURE RELAY CONFIG sys stat

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

Page 312: Generator Relay Protection

A–11

Appendix – A

CONFIGURE RELAY CONFIG sys stat

27TN #1 NEUTRL UNDERVOLTdisable ENABLE

27TN #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

27TN #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

27TN #2 NEUTRL UNDERVOLTdisable ENABLE

27TN #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

27TN #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

59X #1 OVERVOLTAGEdisable ENABLE

59X #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

59X #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Figure A-3 Functional Configuration Record Form (2 of 18)

59X #2 OVERVOLTAGEdisable ENABLE

59X #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

59X #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

59N #1 NEUTRAL OVERVOLTdisable ENABLE

59N #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

59N #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAYVOLTAGE_RELAY

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

Page 313: Generator Relay Protection

A–12

M-3425A Instruction Book

59N #2 NEUTRAL OVERVOLTdisable ENABLE

59N #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

59N #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

59N #3 NEUTRAL OVERVOLTdisable ENABLE

59N #3 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

59N #3 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Figure A-3 Functional Configuration Record Form (3 of 18)

CONFIGURE RELAY CONFIG sys stat

CONFIGURE RELAYVOLTAGE_RELAY

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

59D VOLTAGE DIFF.disable ENABLE

59D BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

59D RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Page 314: Generator Relay Protection

A–13

Appendix – A

50 #2 INST OVERCURRENTdisable enable

50 #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

50 #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

50/27 INADVERTANT ENRGNGdisable ENABLE

50/27 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

50/27 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

50BF BREAKER FAILUREdisable ENABLE

50BF BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

50BF RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAY CURRENT_RELAY

46DT NEG SEQ CURRENT DEFdisable ENABLE

46DT BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

46DT RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

46IT NEG SEQ CURRENT INVdisable ENABLE

46IT BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

46IT RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

50 #1 INST OVERCURRENTdisable ENABLE

50 #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

50 #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Figure A-3 Functional Configuration Record Form (4 of 18)

CONFIGURE RELAY CONFIG sys stat

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Page 315: Generator Relay Protection

A–14

M-3425A Instruction Book

50DT#1 DEF TIME OVERCURRdisable ENABLE

50DT#1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

50DT#1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

50DT#2 DEF TIME OVERCURRdisable ENABLE

50DT#2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

50DT#2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

50N NTRL INST OVERCURRNTdisable ENABLE

50N BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

50N RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Figure A-3 Functional Configuration Record Form (5 of 18)

CONFIGURE RELAY CONFIG sys stat

51N NTRL OVERCURRNT INVdisable ENABLE

51N BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

51N RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

49#1 STATOR OVERLOADdisable ENABLE

49#1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

49#1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

49#2 STATOR OVERLOADdisable ENABLE

49#2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

49#2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAY CURRENT_RELAY

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Page 316: Generator Relay Protection

A–15

Appendix – A

51V OVERCURRENT INVdisable ENABLE

51V BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

51V RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

87 #1 DIFF CURRENTdisable ENABLE

87 #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

87 #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

87 #2 DIFF CURRENTdisable ENABLE

87 #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

87 #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAY CONFIG sys stat

Figure A-3 Functional Configuration Record Form (6 of 18)

87GD GND DIFFERENTIALdisable ENABLE

87GD BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

87GD RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

67NDT RES DIR OVERCURRdisable ENABLE

67NDT BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

67NDT RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

67NIT RES DIR OVERCURRdisable ENABLE

67NIT BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

67NIT RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAY CURRENT_RELAY

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Page 317: Generator Relay Protection

A–16

M-3425A Instruction Book

CONFIGURE RELAY FREQUENCY_RELAY

81 #1 FREQUENCYdisable ENABLE

81 #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81 #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

81 #2 FREQUENCYdisable ENABLE

81 #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81 #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

81 #3 FREQUENCYdisable ENABLE

81 #3 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81 #3 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Figure A-3 Functional Configuration Record Form (7 of 18)

81 #4 FREQUENCYdisable ENABLE

81 #4 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81 #4 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

81R #1 RATE OF CHNG FREQdisable ENABLE

81R #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81R #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

81R #2 RATE OF CHNG FREQdisable ENABLE

81R #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81R #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAY CONFIG sys stat

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Page 318: Generator Relay Protection

A–17

Appendix – A

81A #4 FREQ ACCUMULATORdisable ENABLE

81A #4 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81A #4 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

81A #5 FREQ ACCUMULATORdisable ENABLE

81A #5 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81A #5 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

81A #6 FREQ ACCUMULATORdisable ENABLE

81A #6 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81A #6 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAY FREQUENCY_RELAY

81A #1 FREQ ACCUMULATORdisable ENABLE

81A #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81A #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

81A #2 FREQ ACCUMULATORdisable ENABLE

81A #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81A #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

81A #3 FREQ ACCUMULATORdisable ENABLE

81A #3 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

81A #3 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Figure A-3 Functional Configuration Record Form (8 of 18)

CONFIGURE RELAY CONFIG sys stat

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Page 319: Generator Relay Protection

A–18

M-3425A Instruction Book

24IT VOLTS/HZ INVdisable ENABLE

24IT BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

24IT RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAYVOLTS_PER_HERTZ_RELAY

24DT #1 VOLTS/HZ DEFdisable ENABLE

24DT #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

24DT #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

24DT #2 VOLTS/HZ DEFdisable ENABLE

24DT #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

24DT #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Figure A-3 Functional Configuration Record Form (9 of 18)

CONFIGURE RELAY CONFIG sys stat

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 320: Generator Relay Protection

A–19

Appendix – A

CONFIGURE RELAYPOWER_RELAY

32 #1 DIRECTIONAL POWERdisable ENABLE

32 #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

32 #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

32 #2 DIRECTIONAL POWERdisable ENABLE

32 #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

32 #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

32 #3 DIRECTIONAL POWERdisable ENABLE

32 #3 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

32 #3 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Figure A-3 Functional Configuration Record Form (10 of 18)

CONFIGURE RELAY CONFIG sys stat

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 321: Generator Relay Protection

A–20

M-3425A Instruction Book

CONFIGURE RELAY CONFIG sys stat

CONFIGURE RELAYLOSS_OF_FIELD_RELAY

40 #1 LOSS OF FIELDdisable ENABLE

40 #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

40 #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

40VC #1 LOF WITH VCdisable ENABLE

40VC #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

40VC #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

40 #2 LOSS OF FIELDdisable ENABLE

40 #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

40 #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

40VC #2 LOF WITH VCdisable ENABLE

40VC #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

40VC #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAYV.T._FUSE_LOSS_RELAY

60FL V.T. FUSE LOSSdisable enable

60FL BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

60FL RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Figure A-3 Functional Configuration Record Form (11 of 18)

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Page 322: Generator Relay Protection

A–21

Appendix – A

CONFIGURE RELAY CONFIG sys stat

CONFIGURE RELAYPHASE DISTANCE_RELAY

21 #1 PHASE DISTANCEdisable ENABLE

21 #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

21 #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

21 #2 PHASE DISTANCEdisable ENABLE

21 #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

21 #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

21 #3 PHASE DISTANCEdisable ENABLE

21 #3 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

21 #3 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

78 OUT OF STEPdisable ENABLE

78 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

78 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

Figure A-3 Functional Configuration Record Form (12 of 18)

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 323: Generator Relay Protection

A–22

M-3425A Instruction Book

CONFIGURE RELAYFIELD_GND_RELAY

64F#1 FIELD GROUNDdisable ENABLE

64F #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

64F #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

64F #2 FIELD GROUNDdisable ENABLE

64F #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

64F #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

64B BRUSH LIFTOFFdisable ENABLE

64B BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

64B RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAYSTATOR_GND_RELAY

64S 100% STATOR GROUNDdisable ENABLE

64S BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

64S RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAYSYNC_CHECK_RELAY

25S SYNC CHECKdisable ENABLE

25S BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

25S RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

25D DEAD CHECKdisable ENABLE

25D BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

25D RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAY CONFIG sys stat

Figure A-3 Functional Configuration Record Form (13 of 18)

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Page 324: Generator Relay Protection

A–23

Appendix – A

CONFIGURE RELAYBREAKER_MON_RELAY

BM BREAKER MONITORdisable ENABLE

BM BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

BM RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAY CONFIG sys stat

CONFIGURE RELAYTRIP_CKT_MON_RELAY

TCM TRIP CIRCUIT MONdisable ENABLE

TCM BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

TCM RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

NOTE: Unpurchased or un-available functions will not bevisible within the menus.

Figure A-3 Functional Configuration Record Form (14 of 18)

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 325: Generator Relay Protection

A–24

M-3425A Instruction Book

CONFIGURE RELAYIPS_LOGIC_RELAY

IPSL #1 IPS LOGICdisable ENABLE

IPSL #1 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

IPSL #1 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

IPSL #2 IPS LOGICdisable ENABLE

IPSL #2 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

IPSL #2 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

IPSL #3 IPS LOGICdisable ENABLE

IPSL #3 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

IPSL #3 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

IPSL #4 IPS LOGICdisable ENABLE

IPSL #4 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

IPSL #4 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

IPSL #5 IPS LOGICdisable ENABLE

IPSL #5 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

IPSL #5 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

IPSL #6 IPS LOGICdisable ENABLE

IPSL #6 BLOCK INPUTfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

IPSL #6 RELAY OUTPUTo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

CONFIGURE RELAY CONFIG sys stat

Figure A-3 Functional Configuration Record Form (15 of 18)

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Page 326: Generator Relay Protection

A–25

Appendix – A

INPUT ACTIVATED PROFILESIN ap cpy volt curr vt

INPUT ACTIVATED PROFILESdisable ENABLE

ACTIVE SETPOINT PROFILEin AP cpy volt curr vt

ACTIVE SETPOINT PROFILE________

COPY ACTIVE PROFILEin ap CPY volt curr vt

COPY ACTIVE PROFILETO_PROFILE_1

NOMINAL VOLTAGEin ap cpy VOLT curr vt

NOMINAL VOLTAGE________ Volts

NOMINAL CURRENTin ap cpy volt CURR vt

NOMINAL CURRENT________ Amps

V.T. CONFIGURATIONin ap cpy volt curr VT

V.T. CONFIGURATIONline_line line_ground line_gnd_to_line_line

DELTA-Y TRANSFORM D_YTX rot mag splt

DELTA-Y TRANSFORMdis delta_ab delta_ac

PHASE ROTATION d_ytx ROT mag splt

PHASE ROTATIONa-c-b a-b-c

59/27 MAGNITUDE SELECT d_ytx rot MAG splt

59/27 MAGNITUDE SELECTrms dft

50DT SPLIT-PHASE DIFF d_ytx rot mag SPLT

50DT SPLIT-PHASE DIFFdisable enable

PULSE RELAYPLSE latch seal in

PULSE RELAYo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

LATCHED OUTPUTSplse LATCH seal in

LATCHED OUTPUTSo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

SETUP SYSTEMconfig SYS stat

Figure A-3 Functional Configuration Record Form (16 of 18)

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Page 327: Generator Relay Protection

A–26

M-3425A Instruction Book

RELAY SEAL-IN TIMEplse latch SEAL in

RELAY SEAL-IN TIME OUT1________ Cycles

RELAY SEAL-IN TIME OUT2________ Cycles

RELAY SEAL-IN TIME OUT3________ Cycles

RELAY SEAL-IN TIME OUT4________ Cycles

RELAY SEAL-IN TIME OUT5________ Cycles

RELAY SEAL-IN TIME OUT6________ Cycles

RELAY SEAL-IN TIME OUT7________ Cycles

RELAY SEAL-IN TIME OUT8________ Cycles

RELAY SEAL-IN TIME OUT9________ Cycles

RELAY SEAL-IN TIME OUT10________ Cycles

RELAY SEAL-IN TIME OUT11________ Cycles

Figure A-3 Functional Configuration Record Form (17 of 18)

SETUP SYSTEM config SYS stat

RELAY SEAL-IN TIME OUT12________ Cycles

RELAY SEAL-IN TIME OUT13________ Cycles

RELAY SEAL-IN TIME OUT14________ Cycles

RELAY SEAL-IN TIME OUT15________ Cycles

RELAY SEAL-IN TIME OUT16________ Cycles

RELAY SEAL-IN TIME OUT17________ Cycles

RELAY SEAL-IN TIME OUT18________ Cycles

RELAY SEAL-IN TIME OUT19________ Cycles

RELAY SEAL-IN TIME OUT20________ Cycles

RELAY SEAL-IN TIME OUT21________ Cycles

RELAY SEAL-IN TIME OUT22________ Cycles

RELAY SEAL-IN TIME OUT23________ Cycles

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 328: Generator Relay Protection

A–27

Appendix – A

ACTIVE INPUT STATEplse latch seal IN

ACTIVE INPUT OPEN/closefl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

V.T. PHASE RATIO VT vt_n vt_x ct ct_n

V.T. PHASE RATIO________ :1

V.T. NEUTRAL RATIO vt VT_N vt_x ct ct_n

V.T. NEUTRAL RATIO________ :1

V.T. VX RATIO vt vt_n VT_X ct ct_n

V.T. VX RATIO________ :1

C.T. PHASE RATIO vt vt_n vt_x CT ct_n

C.T. PHASE RATIO________ :1

C.T. NEUTRAL RATIO VT vt_n vt_x ct CT_N

C.T. NEUTRAL RATIO________ :1

SETUP SYSTEM config SYS stat

Figure A-3 Functional Configuration Record Form (18 of 18)

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 329: Generator Relay Protection

A–28

M-3425A Instruction Book

59 PHASE OVERVOLTAGE PHASE_OVER

59 #1 INPUT VOLTAGE SELphase_volt pos_seq_volt

59 #1 PICKUP________ Volts

59 #1 DELAY________ Cycles

59 #2 INPUT VOLTAGE SELphase_volt pos_seq_volt

59 #2 PICKUP________ Volts

59 #2 DELAY________ Cycles

59 #3 INPUT VOLTAGE SELphase_volt pos_seq_volt

59 #3 PICKUP________ Volts

59 #3 DELAY________ Cycles

27 PHASE UNDERVOLTAGEPHASE_UNDER

27 #1 PICKUP________ Volts

27 #1 DELAY________ Cycles

27 #2 PICKUP________ Volts

27 #2 DELAY________ Cycles

27 #3 PICKUP________ Volts

27 #3 DELAY________ Cycles

Figure A-4 Setpoint & Timing Record Form (1 of 15)

VOLTAGE RELAYVOLT curr freq v/hz

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 330: Generator Relay Protection

A–29

Appendix – A

27TN NEUTRL UNDERVOLT NUTRL_UNDER vx_over

27TN #1 PICKUP________ Volts

27TN #1 POS SEQ VOLT BLKdisable ENABLE

27TN #1 POS SEQ VOLT BLK________ Volts

27TN #1 FWD POWER BLKdisable ENABLE

27TN #1 FWD POWER BLK________ PU

27TN #1 REV POWER BLKdisable ENABLE

27TN #1 REV POWER BLK________ PU

27TN #1 LEAD VAR BLKdisable ENABLE

27TN #1 LEAD VAR BLK________ PU

27TN #1 LAG VAR BLKdisable ENABLE

27TN #1 LAG VAR BLK________ PU

27TN #1 LEAD PF BLKdisable ENABLE

27TN #1 LEAD PF BLK________ LEAD

27TN #1 LAG PF BLKdisable ENABLE

27TN #1 LAG PF BLK________ LAG

27TN #1 BAND FWD PWR BLKdisable ENABLE

27TN #1 LO B FWD PWR BLK________ PU

27TN #1 HI B FWD PWR BLK________ PU

27TN #1 DELAY________ CYCLES

VOLTAGE RELAYVOLT curr freq v/hz

27TN #2 PICKUP________ VOLTS

27TN #2 POS SEQ VOLT BLKdisable ENABLE

27TN #2 POS SEQ VOLT BLK________ Volts

27TN #2 FWD POWER BLKdisable ENABLE

27TN #2 FWD POWER BLK________ PU

27TN #2 REV POWER BLKdisable ENABLE

27TN #2 REV POWER BLK________ PU

27TN #2 LEAD VAR BLKdisable ENABLE

27TN #2 LEAD VAR BLK________ PU

27TN #2 LAG VAR BLKdisable ENABLE

27TN #2 LAG VAR BLK________ PU

27TN #2 LEAD PF BLKdisable ENABLE

27TN #2 LEAD PF BLK________ LEAD

27TN #2 LAG PF BLKdisable ENABLE

27TN #2 LAG PF BLK________ LAG

27TN #2 BAND FWD PWR BLKdisable ENABLE

27TN #2 LO B FWD PWR BLK________ PU

27TN #2 HI B FWD PWR BLK________ PU

27TN #2 DELAY________ CYCLES

Figure A-4 Setpoint & Timing Record Form (2 of 15)

Page 331: Generator Relay Protection

A–30

M-3425A Instruction Book

59X OVERVOLTAGE nutrl_under VX_OVER

59X #1 PICKUP________ Volts

59X #1 DELAY________ Cycles

59X #2 PICKUP________ Volts

59X #2 DELAY________ Cycles

59N NEUTRAL OVERVOLTAGE NUTRL_OVER vol_diff

59N #1 PICKUP________ Volts

59N #1 DELAY________ Cycles

59N #2 PICKUP________ Volts

59N #2 DELAY________ Cycles

59N #3 PICKUP________ Volts

59N #3 DELAY________ Cycles

59N 20HZ INJECTION MODEdisable ENABLE

59D VOLT DIFF 3RD HAR nutrl_over VOL_DIFF

59D RATIO________

59D LINE SIDE VOLTAGE3vo vx

59D POS SEQ VOLT BLKdisable ENABLE

59D POS SEQ VOLT BLK________ VOLTS

59D DELAY________ Cycles

Figure A-4 Setpoint & Timing Record Form (3 of 15)

VOLTAGE RELAYVOLT curr freq v/hz

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 332: Generator Relay Protection

A–31

Appendix – A

50/27 INADVERTANT ENRGNGINADVTNT_ENG brk_fail

50/27 PICKUP________ Amps

50/27 VOLTAGE CONTROL________ Volts

50/27 PICKUP DELAY________ Cycles

50/27 DROPOUT DELAY________ Cycles

50BF BREAKER FAILUREinadvtnt_eng BRK_FAIL

50BF PHASE ELEMENTdisable ENABLE

50BF PICKUP PHASE________ Amps

50BF NEUTRAL ELEMENTdisable ENABLE

50BF PICKUP NEUTRAL________ Amps

50BF INPUT INITIATEfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

50BF OUTPUT INITIATEo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

50BF DELAY________ Cycles

46 NEG SEQ OVERCURRENTNEG_SEQ inst

46DT PICKUP________ %

46DT DELAY________ Cycles

46IT PICKUP________ %

46IT MAX DELAY________ Cycles

46IT RESET TIME________ Seconds

46IT TIME DIAL________

50 INST OVERCURRENTneg_seq INST

50 #1 PICKUP________ Amps

50 #1 DELAY________ Cycles

50 #2 PICKUP________ Amps

50 #2 DELAY________ Cycles

Figure A-4 Setpoint & Timing Record Form (4 of 15)

CURRENT RELAYvolt CURR freq v/hz

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 333: Generator Relay Protection

A–32

M-3425A Instruction Book

50DT DEF TIME OVERCURR P_INST n_inst n_inv

50DT #1 PICKUP PHASE A________ Amps

50DT #1 PICKUP PHASE B________ Amps

50DT #1 PICKUP PHASE C________ Amps

50DT #1 DELAY________ Cycles

50DT #2 PICKUP PHASE A________ Amps

50DT #2 PICKUP PHASE B________ Amps

50DT #2 PICKUP PHASE C________ Amps

50DT #2 DELAY________ Cycles

50N INST OVERCURRENT p_inst N_INST n_inv

50N PICKUP________ Amps

50N DELAY________ Cycles

CURRENT RELAYvolt CURR freq v/hz

51N INV TIME OVERCURRENT p_inst n_inst N_INV

51N PICKUP________ Amps

51N CURVEbedef beinv bevinv beeinv ieci iecvi iecei ieclti

minv vinv einv

51N TIME DIAL________

49 STATOR OVERLOAD ST_OVL v_inv diff

49#1 TIME CONSTANT________ Min

49 #1 MAX OVERLOAD CURR________ Amps

49 #2 TIME CONSTANT________ Min

49 #2 MAX OVERLOAD CURR________ Amps

51V INV TIME OVERCURRENT st_ovl V_INV diff

51V PICKUP________ Amps

51V CURVEbedef beinv bevinv beeinv ieci iecvi iecei ieclti

minv vinv einv

51V TIME DIAL________

51V VOLTAGE CONTROLdisable V_CNTRL v_rstrnt

51V VOLTAGE CONTROL________ Volts

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Figure A-4 Setpoint & Timing Record Form (5 of 15)

Page 334: Generator Relay Protection

A–33

Appendix – A

67N RES DIR OVERCURR g_diff RES_DIR_OC

67NDT PICKUP________ Amps

67NDT DIR ELEMENTdisable ENABLE

67NDT DELAY________ Cycles

67NIT PICKUP________ Amps

67NIT DIR ELEMENTdisable ENABLE

67NIT CURVEbedef beinv bevinv beeinv ieci iecvi iecei ieclti

minv vinv einv

67NIT TIME DIAL________

67N MAX SENSITIVITY ANGL________ Degrees

67N OPERATING CURRENT3io in

67N POLARIZING QUANTITY3vo vn vx

87 DIFFERENTIAL OVERCURR st_ovl v_inv DIFF

87 #1 PICKUP________ Amps

87 #1 SLOPE________ %

87 #1 DELAY________ Cycles

87 #2 PICKUP________ Amps

87 #2 SLOPE________ %

87 #2 DELAY________ Cycles

87 PHASE CT CORRECTION________

87GD GND DIFF OVERCURR G_DIFF res_dir_oc

87GD PICKUP________ Amps

87GD DELAY________ Cycles

87GD C.T. RATIO CORRECT________

Figure A-4 Setpoint & Timing Record Form (6 of 15)

CURRENT RELAYvolt CURR freq v/hz

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 335: Generator Relay Protection

A–34

M-3425A Instruction Book

81A FREQUENCY ACCUM.freq rcfreq FREQ_ACC

81A SET FREQUENCY ACC.SET reset

81A #1 HIGH BAND PICKUP________ Hz

81A #1 LOW BAND PICKUP________ Hz

81 #1 DELAY________ Cycles

81A #2 LOW BAND PICKUP________ Hz

81 #2 DELAY________ Cycles

81A #3 LOW BAND PICKUP________ Hz

81 #3 DELAY________ Cycles

81A #4 LOW BAND PICKUP________ Hz

81 #4 DELAY________ Cycles

81A #5 LOW BAND PICKUP________ Hz

81 #5 DELAY________ Cycles

81A #6 LOW BAND PICKUP________ Hz

81 #6 DELAY________ Cycles

81 FREQUENCYFREQ rcfreq freq_acc

81 #1 PICKUP________ Hz

81 #1 DELAY________ Cycles

81 #2 PICKUP________ Hz

81 #2 DELAY________ Cycles

81 #3 PICKUP________ Hz

81 #3 DELAY________ Cycles

81 #4 PICKUP________ Hz

81 #4 DELAY________ Cycles

81R RATE OF CHANGE FREQfreq RCFREQ freq_acc

81R #1 PICKUP________ Hz/s

81R #1 DELAY________ Cycles

81R #2 PICKUP________ Hz/s

81R #2 DELAY________ Cycles

81R NEG SEG VOLT INHIBIT________ %

Figure A-4 Setpoint & Timing Record Form (7 of 15)

FREQUENCY RELAYvolt curr FREQ v/hz

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 336: Generator Relay Protection

A–35

Appendix – A

81A RESET ACCUMULATORSset RESET

81A #1 ACCUMULATOR RESETyes no

81A #2 ACCUMULATOR RESETyes no

81A #3 ACCUMULATOR RESETyes no

81A #4 ACCUMULATOR RESETyes no

81A #5 ACCUMULATOR RESETyes no

81A #6 ACCUMULATOR RESETyes no

FREQUENCY RELAYvolt curr FREQ v/hz

Figure A-4 Setpoint & Timing Record Form (8 of 15)

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 337: Generator Relay Protection

A–36

M-3425A Instruction Book

24 DEF TIME VOLTS/HERTZDEF_V/HZ inv_v/hz

24DT #1 PICKUP________ %

24DT #1 DELAY________ Cycles

24DT #2 PICKUP________ %

24DT #2 DELAY________ Cycles

Figure A-4 Setpoint & Timing Record Form (9 of 15)

VOLTS PER HERTZ RELAYvolt curr freq V/HZ

24 INV TIME VOLTS/HERTZdef_v/hz INV_V/HZ

24IT #1 PICKUP________ %

24IT CURVEcrv#1 crv#2 crv#3 crv#4

24IT TIME DIAL________

24IT RESET RATE________ Seconds

POWER RELAYPWR lof fuse dist

32 DIRECTIONAL POWERPWR

32 #1 PICKUP________ PU

32 #1 DELAY________ Cycles

32 # 1 TARGET LEDdisable enable

32 #1 UNDER/OVER POWERover under

32 #2 PICKUP________ PU

32 #2 DELAY________ Cycles

32 # 2 TARGET LEDdisable ENABLE

32 #2 UNDER/OVER POWERover under

32 #3 PICKUP________ PU

32 #3 DELAY________ Cycles

32 # 3 TARGET LEDdisable ENABLE

32 #3 UNDER/OVER POWERover under

32#3 DIR POWER SENSINGreal reactive

NOTE: Unpurchased or unavailable func-tions will not be visible within the menus.

Page 338: Generator Relay Protection

A–37

Appendix – A

40 #2 DELAY________ Cycles

40VC #2 DELAY WITH VC________ Cycles

40 VOLTAGE CONTROL________ Volts

40 DIRECTIONAL ELEMENT________ Degrees

Figure A-4 Setpoint & Timing Record Form (10 of 15)

LOSS OF FIELD RELAY pwr LOF fuse dist

40 LOSS OF FIELDLOF

40 #1 DIAMETER________ Ohms

40 #1 OFFSET________ Ohms

40 #1 DELAY________ Cycles

40VC #1 DELAY WITH VC________ Cycles

40 #2 DIAMETER________ Ohms

40 #2 OFFSET________ Ohms

V.T. FUSE LOSS RELAY pwr lof FUSE dist

60FL V.T. FUSE LOSSFUSE

60FL INPUT INITIATEfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

IPSCOM INPUT INIT

60FL 3 PHASE DETECTdisable enable

60FL DELAY________ Cycles

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 339: Generator Relay Protection

A–38

M-3425A Instruction Book

21#2 OC SUPERVISIONdisable ENABLE

21#2 OC SUPERVISION________ Amps

21#2 OUT OF STEP BLOCKdisable enable

21#2 DELAY________ Cycles

21#3 DIAMETER________ Ohms

21#3 OFFSET________ Ohms

21#3 IMPEDANCE ANGLE________ Degrees

21#3 LOAD ENCROACHMENTdisable ENABLE

21#3 LOAD ENCR ANGLE________ Degrees

21#3 LOAD ENCR R REACH________ Ohms

21#3 OC SUPERVISIONdisable ENABLE

21#3 OC SUPERVISION________ Amps

21#3 DELAY________ Cycles

21#3 OUT OF STEP DELAY________ Cycles

21 PHASE DISTANCEDIST ostp

21#1 DIAMETER________ Ohms

21#1 OFFSET________ Ohms

21#1 IMPEDANCE ANGLE________ Degrees

21#1 LOAD ENCROACHMENTdisable ENABLE

21#1 LOAD ENCR ANGLE________ Degrees

21#1 LOAD ENCR R REACH________ Ohms

21#1 OC SUPERVISIONdisable ENABLE

21#1 OC SUPERVISION________ Amps

21#1 OUT OF STEP BLOCKdisable enable

21#1 DELAY________ Cycles

21#2 DIAMETER________ Ohms

21#2 OFFSET________ Ohms

21#2 IMPEDANCE ANGLE________ Degrees

21#2 LOAD ENCROACHMENTdisable ENABLE

21#2 LOAD ENCR ANGLE________ Degrees

21#2 LOAD ENCR R REACH________ Ohms

Figure A-4 Setpoint & Timing Record Form (11 of 15)

PHASE DISTANCE RELAY pwr lof fuse DIST

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 340: Generator Relay Protection

A–39

Appendix – A

78 OUT OF STEPdist OSTP

78 DIAMETER________ Ohms

78 OFFSET________ Ohms

78 BLINDER IMPEDANCE________ Ohms

78 IMPEDANCE ANGLE________ Degrees

78 DELAY________ CYCLES

PHASE DISTANCE RELAY pwr lof fuse DIST

Figure A-4 Setpoint & Timing Record Form (12 of 15)

78 TRIP ON MHO EXITdisable ENABLE

78 POLE SLIP COUNT________ Slips

78 POLE SLIP RESET TIME________ Cycles

FIELD GROUND RELAY FIELD stator sync

64B/F FIELD GROUNDFIELD

64F #1 PICKUP________ kOhm

64F #1 DELAY________ Cycles

64F # 2 PICKUP________ kOhm

64F # 2 DELAY________ Cycles

64B PICKUP________ mV

64B DELAY________ Cycles

64B/F FREQUENCY________ Hz

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 341: Generator Relay Protection

A–40

M-3425A Instruction Book

Figure A-4 Setpoint & Timing Record Form (13 of 15)

NOTE: Unpurchased or un-available functions will not bevisible within the menus.

SYNC CHECK RELAY field stator SYNC

25S SYNC CHECKSYNC dead

25S PHASE LIMIT________ Degrees

25S UPPER VOLT LIMIT________ Volts

25S LOWER VOLT LIMIT________ Volts

25S SYNC CHECK DELAY________ Cycles

25S DELTA VOLTdisable ENABLE

25S DELTA VOLT LIMIT________ Volts

25S DELTA FREQUENCYdisable ENABLE

25S DELTA FREQ LIMIT________ Hz

25S SYNC-CHECK PHASEab bc ca

25D DEAD VOLTsync DEAD

25D DEAD VOLT LIMIT________ VOLTS

25D DEAD V1 HOT VXdisable ENABLE

25D DEAD VX HOT V1disable ENABLE

25D DEAD V1 & VXdisable ENABLE

25D DEAD INPUT ENABLEfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

25D DEAD DELAY________ Cycles

STATOR GROUND RELAY field STATOR sync

64S 100% STATOR GROUNDSTATOR

64S PICKUPmAmps

64S VOLT INHIBITdisable ENABLE

64S VOLT INHIBIT________ Volts

64S DELAY________ Cycles

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 342: Generator Relay Protection

A–41

Appendix – A

Figure A-4 Setpoint & Timing Record Form (14 of 15)

SET BREAKER MONITORINGBRKR prst clr

BM PICKUP________ kA-cycles

BM INPUT INITIATEfl i6 i5 i4 i3 i2 i1i11 i10 i9 i8 i7i14 i13 i12

BM OUTPUT INITIATEo8 o7 o6 o5 o4 o3 o2 o1o14 o13 o12 o11 o10 o9o19 o18 o17 o16 o15o23 o22 o21 o20

BM DELAY________ Cycles

BM TIMING METHODit i2t

BREAKER MONITOR BRKR trpckt ipslog

PRESET ACCUMULATORSbrkr PRST clr

ACC. PHASE A SETPH_A ph_b ph_c

BRKR. ACCUMULATOR________ kA-cycles

ACC. PHASE B SETph_A PH_B ph_c

BRKR. ACCUMULATOR________ kA-cycles

ACC. PHASE C SETph_A ph_b PH_C

BRKR. ACCUMULATOR________ kA-cycles

CLEAR ACCUMULATORSbrkr prst CLR

ACC. PHASE A CLEARPH_A ph_b ph_c

ACC. PHASE B CLEARph_a PH_B ph_c

ACC. PHASE C CLEARph_a ph_b PH_C

TRIP CIRCUIT MONITORTRIPCKT

TCM DELAY________ Cycles

TRIP CIRCUIT MONITOR brkr TRPCKT ipslog

Inputs 7 to 14 and Outputs9 to 23 must be set throughIPScom®.

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 343: Generator Relay Protection

A–42

M-3425A Instruction Book

Figure A-4 Setpoint & Timing Record Form (15 of 15)

IPS LOGIC brkr trpckt IPSLOG

IPS LOGICUSE IPSCOM TO CONFIGURE

NOTE: Unpurchased or unavailable functions will not be visible within the menus.

Page 344: Generator Relay Protection

Communications: Appendix – B

B–1

B Appendix B–Communications

The M-3425A Generator Protection Relayincorporates three serial ports and an optional RJ45Ethernet port for intelligent, digital communicationwith external devices. Equipment such as RTU's,data concentrators, modems, or computers can beinterfaced for direct, on-line, real time data acquisitionand control. Generally, all data available to theoperator through the front panel of the relay with theoptional M-3931 Human-Machine Interface moduleis accessible remotely through the BECO 2200 orMODBUS data exchange protocol. These protocoldocuments and the database-specific protocoldocument are available from the factory or from ourwebsite at www.beckwithelectric.com.

The M-3820D IPScom® Communication Softwarepackage has been supplied for communication toany IBM compatible computer running underMicrosoft® Windows 95 or higher.

The communication protocols implement serial, byteoriented, asynchronous communication and can beused to fulfill the following communications functions:

• Real time monitoring of line status.

• Interrogation and modification of setpoints.

• Downloading of recorded oscillograph data.

• Reconfiguration of relay functions.

NOTE: The following restrictions apply forMODBUS protocol use:

1. MODBUS protocol is not supported onCOM1.

2. Parity is supported on COM2 and COM3;valid selections are 8,N,2; 8,O,1; 8,E,1;8,N,1; 8,O,2 or 8,E,2.

3. ASCII mode is not supported (RTU only).

4. Standard baud rates from 300 to 9600are supported.

5. Only the following MODBUS commandsare supported:

a. read holding register (function 03)

b. read input register (function 04)

c. force single coil (function 05)

d. preset single register (function 06)

For detailed information on IPScom communications,refer to Chapter 4, Remote Operation.

Serial PortsThe relay has both front and rear panel RS-232 portsand a rear RS-485 port. The front and rear panelRS-232 ports are 9-pin (DB9S) connector configuredas DTE (Data Terminal Equipment) per the EIA-232D standard. Signals are defined in Table B-1,Communication Port Signals .

The 2-wire RS-485 port is assigned to the rear panelterminal block pins 3 (–) and 4 (+).

Each communication port may be configured tooperate at any of the standard baud rates (300,600, 1200, 2400, 4800, and 9600). The RS-485port shares the same baud rate with COM 2 (forCOM1 see Section 5.4, Circuit Board Switches andJumpers).

A null modem cable is also shown in Figure B-1, NullModem Cable: M-0423, if direct connection to a PC(personal computer) is desired.

Optional Ethernet PortThe M-3425A, when equipped with the optionalEthernet port can be accessed from a local network.When the ethernet port is enabled, the COM2 serialport (RS-232) is unavailable for communications.The demodulated IRIG-B may still be used via theCOM2 Port when ethernet is enabled. Although theethernet connection speed is faster than the RS-232port (can be up to 10 Mbps), the ethernet moduleconnects internally through the COM2 serialconnection and is therefore limited to connectionspeeds up to 9600 bps.

Either port COM2 (Ethernet) or COM3 may be usedto remotely set and interrogate the relay using alocal area network, modem or other direct serialconnection.

Page 345: Generator Relay Protection

B–2

M-3425A Instruction Book

Signal COM1 COM2

RX Receive Data Pin 2 Pin 2

TX Transmit Data Pin 3 Pin 3

RTS Request to Send Pin 7 Pin 7

CTS Clear to Send Pin 8

DTR Data Terminal Ready Pin 4 Pin 4

DCD Data Carrier Detect Pin 1*

GND Signal Ground Pin 5 Pin 5

+15 V Pin 1*

-15 V Pin 9*

TTL IRIG-B (+) Pin 6*

* Optional: See Section 5.5, Circuit Board Switches andJumpers, 15V ( 15%) @100 mA maximum.

Table B-1 Communication Port Signals

NOTE: Also see Tables 5-1, 5-2 and Figure 5-12.

Figure B-1 Null Modem Cable: M-0423

Page 346: Generator Relay Protection

Communications: Appendix – B

B–3

RS-232

TR

T R

TR TR

REPOFF

DCEDTE

DCEDTE

REPOFF

DCEDTE

REPOFF

DCEDTE

REPOFF

RS-232 RS-232

Echo Cancel On

25 pin or9-25 pin Straight-Through Cable

FOC

FOC

FOC

FOC

DYMEC Fiber OpticLink / Repeater

Slave #1Address 1

Slave #2Address 2

Slave #3Address 3

9-25 pin "Straight-Through" Cables

PC Master

Figure B-2 RS-232 Fiber Optic Network

Page 347: Generator Relay Protection

B–4

M-3425A Instruction Book

RS-232 to RS-485 2-wireconverter or RS-485 PC Card

PC Master - + - +

RS-485 2-Wire Network

B(-)

A(+)

Twisted

200 Ω*

Slave #1Address 6

Slave #2Address 8

Slave #3Address 1

CAUTION: Due to the possibility of ground potential difference between units, all units should be mountedin the same rack. If this is not possible, fiber optics with the appropriate converters should be used forisolation.

NOTE: Each address on the network must be unique. Only the last physical slave on the network shouldhave the termination resistor installed. This may be completed externally or using a jumper internalto the unit. See Section 5.5, Circuit Board Switches and Jumpers.

Figure B-3 RS-485 Network

Figure B-4 COM Pinout for Demodulated TTL Level Signal

Page 348: Generator Relay Protection

Self-Test Error Codes Appendix – C

C–1

CAppendix C–Self-test Error Codes

Table C-1 Self-Test Error Codes

1

2 Battery backed RAM test fail

3 EEPROM write power-up fail

4 EEPROM read back power-up fail

5 Dual port RAM test fail

6 EEPROM write calibration checksum fail

7 EEPROM write setpoint checksum failloss of power

8 EEPROM write setpoint checksum failloss of battery backed RAM

9 DMA checksum/physical block fail

10 Oscillograph Memory Test fail

11 DSP external program RAM fail

12 DSP A/D convert fail

13 DSP ground channel fail

14 DSP reference channel fail

15 DSP PGA gain fail

16 DSP DSP<-> HOST interrupt 1 fail

17 DSP DSP -> HOST interrupt 2 set fail

18 DSP DSP -> HOST interrupt 2 reset fail

19 DSP program load fail

20 DSP not running run mode code

21 DSP not running primary boot code

22 DSP DPRAM pattern test fail

23 EEPROM write verify error

26 WARNING calibration checksum mis-match warning

27 WARNING setpoint checksum mismatchwarning

28 WARNING low battery (BBRAM) warning

29 Supply/mux PGA running test fail

30 External DSP RAM test fail

31 Unrecognized INT1 code

32 Values update watchdog fail

33 Abort Error

34 Restart Error

35 Interrupt Error

36 Trap Error

37 Calibration running check fail

38 Ethernet Board not running (Warning)

39 Not used

40 Interrupt noise INT2

41 Interrupt noise INT1

42 Not used

43 Not used

44 Oscillograph buffer overflow

45 Oscillograph buffer underflow

46 Failure of DSP to calculate calibrationphasors

47 Unable to calibrate input (gain)

48 Unable to calibrate input (phase)

49 Not used

50 Stack Overflow

51 Setpoint Write Overflow

52 Field Ground Error

Page 349: Generator Relay Protection

M-3425A Instruction Book

C–2

Table C-2 IPScom® Error Messages

edoCrorrE noitpircseD

kcoLlennahCmmoC sihtnitluserlliwlortnocehtotdeilppusdrowssaptcerrocninA.egassem

edoMlacoLnilortnoC yllacoldetarepogniebsilortnocehttahtsetacidniegassemsihT.dednepsussinoitacinummoclairesdna

tuoemiTohcE noitacinummocehthtiwsmelborperaerehtfistluserrorresihT.yltcerrocnidesusinoitcnuflecnacohceehtfiroknil

ataDdilavnI .deretnesiatadegnar-fo-tuorotcerrocnifistluserrorresihT

DIdilavnI ahtiwetacinummocotgnitpmettanehwdeyalpsidsiegassemsihT.seires5243-Mehtnahtrehtoecived

forebmuNdilavnIstnioP

sierawtfosmocSPIfonoisrevelbitapmocninafistluserrorresihThtiwkceBatcatnoC.rorrelocotorpnoitacinummocasisihT.desu

.evitatneserperyrotcaf.oCcirtcelE

rebmuNtnioPdilavnIsierawtfosmocSPIfonoisrevelbitapmocninafistluserrorresihThtiwkceBatcatnoC.rorrelocotorpnoitacinummocasisihT.desu

.evitatneserperyrotcaf.oCcirtcelE

muskcehCdilavnIdaeR noitacinummocehthtiwsmelborperaerehtfistluserrorresihT.yltcerrocnidesusinoitcnuflecnacohceehtfiroknil

tuoemiTtekcaPdaeR tsolsilortnocehthtiwnoitacinummocnehwstluserrorresihT.lortnocehtotataddaerotgnitpmettaelihw

tuoemiTesnopseR tsolsilortnocehthtiwnoitacinummocnehwstluserrorresihT.lortnocehtmorfataddaerotgnitpmettaelihw

rorrEmetsySnwonknU .lortnocehtfonoitcnuflamaybdesuacebdluocrorresihT

lecnaCresU .desserpsiyek)CSE(epacseehtnehwsyalpsidegassemsihT

muskcehCdilavnIetirW noitacinummocehthtiwsmelborperaerehtfistluserrorresihT.yltcerrocnidesusinoitcnuflecnacohceehtfiroknil

tuoemiTtekcaPetirW tsolsilortnocehthtiwnoitacinummocnehwstluserrorresihT.lortnocehtotatadetirwotgnitpmettaelihw

Page 350: Generator Relay Protection

Inverse Time Curves: Appendix– D

D–1

D Appendix D – Inverse Time Curves

This Appendix contains two sets of Inverse Time Curve Families. The first set is used for Volts per Hertzfunctions (Figures D-1 through D-4), and the second set is for the M-3425A functions which utilize the InverseTime Overcurrent curves (Figures D-5 through D-12).

NOTE: Table D-1A and D-1B on pages D–6 and D–7 contains a list of the data that characterizes DefiniteTime, Inverse Time, Very Inverse Time, and Extremely Inverse Time Overcurrent Curves.

Expression for Time Delay SettingOperating time defined by IEC and ANSI/IEEE:

IEC Equation

t = TD AM - 1P

IEEE Equation(IEEE equation constants are

defined at TD of 5)

t = TD AM - 1P5 + B

where= Relay operating time in seconds= Time dial, or time multiplier setting= Fault current level in secondary amps= Tap or pickup current selected= Constant= Slope constant= Slope constant

tTDIIpBpA

M = IIp

Setting Time Delay on Overcurrent Relays ANSI/IEEE and IEC constants for overcurrent relays

IDMT Curve Description

Moderately Inverse

Very Inverse

Extremely Inverse

Standard Inverse

Very Inverse

Extremely Inverse

Standard

IEEE

IEEE

IEEE

IEC

IEC

IEC

p

0.02

2

2

0.02

1.0

2.0

19.61

A

0.0515

28.2

0.14

13.5

80.0

B

0.114

0.491

0.1217

-

-

-

Page 351: Generator Relay Protection

D–2

M-3425A Instruction Book

Figure D-1 Volts/Hz (24) Inverse Curve Family #1 (Inverse Square)

Page 352: Generator Relay Protection

Inverse Time Curves: Appendix– D

D–3

Figure D-2 Volts/Hz (24) Inverse Family Curve #2

Page 353: Generator Relay Protection

D–4

M-3425A Instruction Book

Figure D-3 Volts/Hz (24IT) Inverse Curve Family #3

Page 354: Generator Relay Protection

Inverse Time Curves: Appendix– D

D–5

Figure D-4 Volts/Hz (24IT) Inverse Curve Family #4

Page 355: Generator Relay Protection

D–6

M-3425A Instruction Book

NOTE: The abovetimes are in secondsand are given for atime dial of 1.0. Forother time dial values,multiply the above bythe time dial value.

gnitteSpaTfoelpitluM emiTetinifeD emiTesrevnI emiTesrevnIyreV emiTesrevnIylemertxE

05.1 99896.0 45935.4 87564.3 02538.4

55.1 26846.0 33551.4 30211.3 74782.4

06.1 93506.0 30918.3 82218.2 26538.3

56.1 30865.0 56225.3 45655.2 60754.3

07.1 85535.0 78952.3 70633.2 37531.3

57.1 52705.0 85520.3 13441.2 49958.2

08.1 54284.0 66518.2 02679.1 49026.2

58.1 86064.0 37626.2 97728.1 80214.2

09.1 65144.0 99554.2 79596.1 22822.2

59.1 77424.0 11103.2 32875.1 92560.2

00.2 60014.0 31061.2 45274.1 60029.1

50.2 12793.0 93130.2 32773.1 49987.1

01.2 60683.0 84319.1 39092.1 87276.1

51.2 84673.0 91508.1 94212.1 68665.1

02.2 45563.0 75227.1 21821.1 02874.1

03.2 39253.0 49045.1 62610.1 86223.1

04.2 51143.0 40193.1 70229.0 05291.1

05.2 81033.0 16562.1 09148.0 12280.1

06.2 99913.0 54951.1 10377.0 08789.0

07.2 75013.0 17860.1 43317.0 62609.0

08.2 98103.0 94099.0 72166.0 72538.0

09.2 29392.0 85229.0 45516.0 30377.0

00.3 66682.0 52368.0 51575.0 11817.0

01.3 70082.0 31118.0 03935.0 93966.0

02.3 51472.0 41567.0 33705.0 39526.0

03.3 98862.0 93427.0 07874.0 00785.0

04.3 72462.0 81886.0 79254.0 69155.0

05.3 03062.0 19556.0 77924.0 23025.0

06.3 79652.0 01726.0 97804.0 36194.0

07.3 92452.0 53106.0 77983.0 45564.0

08.3 92252.0 23875.0 84273.0 57144.0

00.4 57942.0 40935.0 20143.0 92104.0

02.4 27542.0 14605.0 82513.0 46563.0

04.4 79142.0 64774.0 23392.0 06433.0

06.4 25832.0 67154.0 35472.0 14703.0

08.4 14532.0 49824.0 14852.0 64382.0

Table D-1A M-3425A Inverse Time Overcurrent Relay Characteristic Curves (1 of 2)

Page 356: Generator Relay Protection

Inverse Time Curves: Appendix– D

D–7

gnitteSpaTfoelpitluM emiTetinifeD emiTesrevnI emiTesrevnIyreV emiTesrevnIylemertxE

00.5 66232.0 17804.0 65442.0 72262.0

02.5 92032.0 87093.0 96232.0 34342.0

04.5 43822.0 59473.0 45222.0 06622.0

06.5 48622.0 20163.0 49312.0 15112.0

08.5 38522.0 48843.0 37602.0 39791.0

00.6 43522.0 82833.0 18002.0 76581.0

02.6 62522.0 17723.0 11591.0 13571.0

04.6 29422.0 93913.0 44091.0 68561.0

06.6 06322.0 05113.0 20681.0 13751.0

08.6 03222.0 20403.0 78181.0 75941.0

00.7 20122.0 59692.0 79771.0 35241.0

02.7 77912.0 72092.0 13471.0 11631.0

04.7 55812.0 89382.0 09071.0 72031.0

06.7 63712.0 70872.0 37761.0 29421.0

08.7 12612.0 35272.0 97461.0 30021.0

00.8 01512.0 43762.0 90261.0 55511.0

02.8 30412.0 15262.0 16951.0 44111.0

04.8 00312.0 30852.0 63751.0 86701.0

06.8 30212.0 88352.0 43551.0 22401.0

08.8 11112.0 70052.0 45351.0 50101.0

00.9 52012.0 06642.0 79151.0 41890.0

05.9 31802.0 53932.0 07741.0 07090.0

00.01 04702.0 22432.0 37441.0 47480.0

05.01 76602.0 32922.0 08141.0 34970.0

00.11 49502.0 24422.0 49831.0 96470.0

05.11 12502.0 97912.0 51631.0 64070.0

00.21 94402.0 63512.0 54331.0 76660.0

05.21 87302.0 51112.0 48031.0 92360.0

00.31 01302.0 61702.0 33821.0 62060.0

05.31 34202.0 14302.0 39521.0 55750.0

00.41 97102.0 19991.0 46321.0 31550.0

05.41 91102.0 66691.0 64121.0 79250.0

00.51 26002.0 76391.0 14911.0 40150.0

05.51 90002.0 59091.0 74711.0 43940.0

00.61 16991.0 15881.0 66511.0 48740.0

05.61 81991.0 53681.0 89311.0 25640.0

00.71 18891.0 94481.0 34211.0 93540.0

05.71 15891.0 49281.0 20111.0 24440.0

00.81 72891.0 17181.0 47901.0 26340.0

05.81 11891.0 28081.0 16801.0 89240.0

00.91 30891.0 92081.0 26701.0 05240.0

05.91 30891.0 41081.0 97601.0 91240.0

00.02 30891.0 41081.0 11601.0 50240.0

Table D-1B M-3425A Inverse Time Overcurrent Relay Characteristic Curves (2 of 2)

NOTE: The abovetimes are in secondsand are given for atime dial of 1.0. Forother time dial values,multiply the above bythe time dial value.

Page 357: Generator Relay Protection

D–8

M-3425A Instruction Book

Figure D-5 BECO Definite Time Overcurrent Curve

Page 358: Generator Relay Protection

Inverse Time Curves: Appendix– D

D–9

Figure D-6 BECO Inverse Time Overcurrent Curve

Page 359: Generator Relay Protection

D–10

M-3425A Instruction Book

Figure D-7 BECO Very Inverse Time Overcurrent Curve

Page 360: Generator Relay Protection

Inverse Time Curves: Appendix– D

D–11

Figure D-8 BECO Extremely Inverse Time Overcurrent Curve

Page 361: Generator Relay Protection

D–12

M-3425A Instruction Book

Figure D-9 IEC Curve #1 Inverse

Page 362: Generator Relay Protection

Inverse Time Curves: Appendix– D

D–13

Figure D-10 IEC Curve #2 Very Inverse

Page 363: Generator Relay Protection

D–14

M-3425A Instruction Book

Figure D-11 IEC Curve #3 Extremely Inverse

Page 364: Generator Relay Protection

Inverse Time Curves: Appendix– D

D–15

Figure D-12 IEC Curve #4 Long-Time Inverse

Page 365: Generator Relay Protection

D–16

M-3425A Instruction Book

Figure D-13 IEEE (Moderately) Inverse Time Overcurrent Curves

Page 366: Generator Relay Protection

Inverse Time Curves: Appendix– D

D–17

Figure D-14 IEEE Very Inverse Time Overcurrent Curves

Page 367: Generator Relay Protection

D–18

M-3425A Instruction Book

Figure D-15 IEEE Extremely Inverse Time Overcurrent Curves

Page 368: Generator Relay Protection

Appendix E – Layup and Storage

E–1

Appendix E includes the recommended storageparameters, periodic surveillance activities and layupconfiguration for the M-3425A Generator ProtectionRelay.

Storage Requirements (Environment)The recommended storage environment parametersfor the M-3425A are:

• The ambient temperature where theM-3425A is stored is within a range of 5°C to 40° C

• The maximum relative humidity is lessthan or equal to 80% for temperatures upto 31° C, decreasing to 31° C linearly to50% for relative humidity at 40° C.

• The storage area environment is free ofdust, corrosive gases, flammablematerials, dew, percolating water, rain andsolar radiation.

Storage Requirements (Periodic SurveillanceDuring Storage)The M-3425A power supply contains electrolyticcapacitors. It is recommended that power be appliedto the relay (PS1 and optional PS2 redundant powersupply when installed and PS2 on extended outputunits) every three to five years for a period of notless than one hour to help prevent the electrolyticcapacitors from drying out.

Layup ConfigurationThe M-3425A includes a removable lithium batterybacked TIMEKEEPER® module (Beckwith Electriccomponent U25, Figure 5-17). The TIMEKEEPERmodule is the M-3425A real-time clock and alsoprovides power to the unit’s nonvolatile memorywhen power is not applied to the unit.

E Appendix – Layup and Storage

Layup of the M-3425A requires verifying that thesystem clock is stopped. The steps necessary toverify system clock status are as follows:

CAUTION: Do not use the diagnostic mode inrelays that are installed in an active protectionscheme.

For units with the optional HMI panel:

1. Verify that the Power Supply (PS) fusesare installed.

2. Determine the unit power supply ratingby observing the check box below thePS terminals on the rear of the unit.

3. Apply power to the unit consistant withthe rating determined in Step 2 (seeSection 5.3 , External Connections). Theunit will enter the selftest mode.

4. When the selftests are complete, thenpress ENTER to begin main menu.

5. Press the right arrow pushbutton untilSETUP UNIT is displayed.

6. Press ENTER to access the SETUPUNIT menu.

7. Press the right arrow pushbutton untilDIAGNOSTIC MODE is displayed.

8. Press ENTER. A reset warning will bedisplayed:

PROCESSOR WILL RESET!ENTER KEY TO CONTINUE

WARNING: All relay functions and protectionwill be inoperative while the relay is in diagnosticmode.

9. Press ENTER. Unit will now reset andDIAGNOSTIC MODE will be temporarilydisplayed, followed by OUTPUT TEST(RELAY). This is the beginning of thediagnostic menu.

Page 369: Generator Relay Protection

M-3425A Instruction Book

E–2

10. Press the right arrow pushbutton untilthe following is displayed:

CLOCK TEST com1 com2 com3 CLOCK

11. Press ENTER. The following isdisplayed:

CLOCK TEST03-JAN-1998 09:00:00.000

12. If the clock is running, press ENTER tostop the clock. The following isdisplayed:

CLOCK TEST-CLOCK STOP-

NOTE: When the relay clock is stopped, theseconds will be displayed as 80.

13. Press ENTER and verify the relay clockis stopped. A display similar to thefollowing is shown with the secondsstopped:

CLOCK TEST03-JAN-09:01:80.000

14. When the clock has been verified to bestopped, then press EXIT until thefollowing message appears:

PRESS EXIT TOEXIT DIAGNOSTIC MODE

15. Press EXIT again to exit DIAGNOSTICMODE. The relay will reset and normalrunning mode will resume.

NOTE: Pressing any button other than EXIT willreturn the user to DIAGNOSTIC MODE.

16. Remove power from the unit. The unitcan now be placed in storage.

For units without the optional HMI panel:

1. Verify that the Power Supply (PS) fusesare installed.

2. Determine the unit power supply ratingby observing the check box(s) below thePS terminals on the rear of the unit.

3. Apply power to the unit consistant withthe rating determined in Step 2 (seeSection 5.3 , External Connections). Theunit will enter the selftest mode.

4. Install IPScomTM CommunicationsSoftware (see Section 4.2, Installationand Setup) on a PC that includes thefollowing:

• Microsoft WindowsTM 95 OperatingSystem or above

• Equipped with a serial port

5. Connect a null modem cable from COM1of the relay to the PC serial port.

6. Open communications with the relay (seeSection 4.3 Operation, ActivatingConnections).

7. Select “Relay/Setup/Set Date/Time” fromthe menu bar. IPScom will display the “UnitDate/Time Dialog Screen” Figure 4-16.

8. Verify that “Start Clock” is displayed,then proceed as follows:

a. If “Start Clock” is displayed, thenselect “Save” and go to Step 9.

b. If “Stop Clock” is displayed, thenselect “Stop Clock” and then select“Save”.

9. Close communications with the unit byselecting “Comm” from the menu barand then select “Exit”.

10. Disconnect the null modem cable andthen remove power from the unit. Theunit can now be placed in storage.

Storage of the M-3425A greater than five yearsmay require replacement of the lithium battery priorto placing the unit in service. Contact BeckwithElectric Customer Service for replacementprocedure.

Page 370: Generator Relay Protection

Declaration of Conformity: Appendix – F

F–1

F Appendix F–Declaration of Conformity

Page 371: Generator Relay Protection

DECLARATION OF CONFORMITY ( in accordance to ISO/IEC 17050-1:2004 )

No. M-3425A Manufacturer’s Name: Beckwith Electric CO, INC.Manufacturer’s Address: 6190 118th Avenue North

Largo, FL 33773-3724

The manufacturer hereby declares under our sole responsibility that the M-3425A product conforms to the following product standardas of January 14th, 2004 in accordance to Directive 2004/108/EC for equipment incorporated into stationary installations:

BS EN 50263:2000 Electromagnetic compatibility ( EMC ) Product standard for measuring relays and protection equipment

Electromagnetic Emissions: EN 60255-25:2000

Conducted 150 kHz to 30MHzRadiated 30MHz to 1000MHzClass A Limits

Electromagnetic Immunity

1 MHz DisturbanceEN 60255-22-1:1988 ( ANSI C37.90.1:2002 )

Electrostatic Discharge 8kV Contact; 15kV Air EN 60255-22-2:1997

Radiated RF 80MHz to 1000MHz 10V/m, 80% AM ( 1kHz )EN 60255-22-3:2001

Fast Transients 5ns/50ns Bursts @ 5kHz for 15ms 300ms for 1 min.2kV power supply lines and earth 2kV signal data and control linesEN 60255-22-4:2002 Surge 1Kv Line to Line coupling, 2Kv Line to Earth coupling power supply lines 12Ω source impedance EN 61000-4-5:1995

Conducted RF 150KHz to 80MHz 10V emfEN 60255-22-6:2001

Power frequency magnetic field immunity test30 A/m continuousEN 61000-4-8:1994

Voltage dips, short interruptions and voltage variations immunity testsEN 61000-4-11:1994

EN 61010-1: 2001 Safety requirements for electrical equipment for measurement, control, andlaboratory use Part 1. General requirements European Safety Directive

Manufacturers Contact: Engineering Manager 6190 118th Ave North Largo, FL 33773-3724 Tel ( 727 ) 544-2326

Page 372: Generator Relay Protection

Legal Information

PatentThe units described in this manual are covered byU.S. Patents, with other patents pending.

Buyer shall hold harmless and indemnify the Seller,its directors, officers, agents, and employees fromany and all costs and expense, damage or loss,resulting from any alleged infringementof UnitedStates Letters Patent or rights accruing thereform ortrademarks, whether federal, state, or common law,arising from the Seller’s compliance with Buyer’sdesigns, specifications, or instructions.

WarrantySeller hereby warrants that the goods which are thesubject matter of this contract will be manufacturedin a good workmanlike manner and all materialsused herein will be new and reasonably suitable forthe equipment. Seller warrants that if, during aperiod of five years from date of shipment of theequipment, the equipment rendered shall be foundby the Buyer to be faulty or shall fail to peform inaccordance with Seller’s specifications of theproduct, Seller shall at his expense correct thesame, provided, however, that Buyers shall ship theequipment prepaid to Seller’s facility. The Seller’sresponsibility hereunder shall be limited to replace-ment value of the equipment furnished under thiscontract.

Seller makes no warranties expressed or impliedother than those set out above. Seller specificallyexcludes the implied warranties of merchantibilityand fitness for a particular purpose. There are nowarranties which extend beyond the descriptioncontained herein. In no event shall Seller be liable forconsequential, exemplary, or punitive damages ofwhatever nature.

Any equipment returned for repair must be sentwith transportation charges prepaid. The equipmentmust remain the property of the Buyer. The afore-mentioned warranties are void if the value of theunit is invoiced to the Seller at the time of return.

IndemnificationThe Seller shall not be liable for any propertydamages whatsoever or for any loss or damagearising out of, connected with, or resulting fromthis contract, or from the performance or breachthereof, or from all services covered by or furnishedunder this contract.

In no event shall the Seller be liable for special,incidental, exemplary, or consequential damages,including but not limited to, loss of profits orrevenue, loss of use of the equipment or anyassociated equipment, cost of capital, cost ofpurchased power, cost of substitute equipment,facilities or services, downtime costs, or claims ordamages of customers or employees of the Buyerfor such damages, regardless of whether said claimor damages is based on contract, warranty, tortincluding negligence, or otherwise.

Under no circumstances shall the Seller be liablefor any personal injury whatsoever.

It is agreed that when the equipment furnishedhereunder are to be used or performed in connec-tion with any nuclear installation, facility, oractivity, Seller shall have no liability for anynuclear damage, personal injury, property damage,or nuclear contamination to any property located ator near the site of the nuclear facility. Buyer agreesto indemnify and hold harmless the Seller againstany and all liability associated therewith whatso-ever whether based on contract, tort, or otherwise.Nuclear installation or facility means any nuclearreactor and includes the site on which any of theforegoing is located, all operations conducted onsuch site, and all premises used for such opera-tions.

Notice:Any illustrations and descriptions by BeckwithElectric Co., Inc. are for the sole purpose ofidentification.

The drawings and/or specifications enclosed hereinare the proprietary property of Beckwith ElectricCo., Inc., and are issued in strict confidence;therefore, shall not be used as a basis of reproduc-tion of the apparatus described therein withoutwritten permission of Beckwith Electric Co., Inc.

No illustration or description contained hereinshall be construed as an express warranty ofaffirmation, promise, description, or sample, andany and all such express warranties are specificallyexcluded nor shall such illustration or descriptionimply a warranty that the product is merchantableor fit for a particular purpose. There shall be nowarranties which extend beyond those contained inthe Beckwith Electric Co., Inc. terms of sale.

All rights reserved by Beckwith Electric Co., Inc. No reproduction may be made without prior written approvalof the Company.

Page 373: Generator Relay Protection

This Page Left Intentionally Blank

Page 374: Generator Relay Protection