    General Recommendations for Cable Installation

    a) Minimum Bending Radius for PVC Cables

    i) Multi core up to 1.1 KV : 12D

    ii) Multi core 3.3 KV & 6.6 KV : 15D

    iii) Single core : 15DD is the diameter of the cable

    b) Depth of laying

    i) Low voltage power and control cables : 75 cm

    ii) HV up to 11 KV : 90 cm

    iii) Cables at road crossing : 100 cmiv) Cables at railway level crossing : 100 cm (below rails)

    c) Minimum clearance between

    i) Power cable to control cables : 20 cm

    ii) Power cable to communication cable : 30 cmiii) Power cable to power cable : more the betteriv) Power cable to gas/water pipe line : 30 cm

    d) Test before laying

    Recommended voltage rating of meggar:-

    i) 1.1 KV : 500 V

    ii) 3.3 KV to 11 KV : 1000 V

    iii) Above 11 KV : 2500 V

    e) Tests after installation (High DC voltage test)

    Rated voltage (KV) Test voltage (KV) 15 min.i) 0.65/1.1 3

    ii) 1.9/3.3 6

    iii) 3.3/3.3 8iv) 3.3/6.6 10

    v) 6.6/6.6 & 6.6/11.3 15

    ---------------------------------------