General Recommendations for Cable Installation
a) Minimum Bending Radius for PVC Cables
i) Multi core up to 1.1 KV : 12D
ii) Multi core 3.3 KV & 6.6 KV : 15D
iii) Single core : 15DD is the diameter of the cable
b) Depth of laying
i) Low voltage power and control cables : 75 cm
ii) HV up to 11 KV : 90 cm
iii) Cables at road crossing : 100 cmiv) Cables at railway level crossing : 100 cm (below rails)
c) Minimum clearance between
i) Power cable to control cables : 20 cm
ii) Power cable to communication cable : 30 cmiii) Power cable to power cable : more the betteriv) Power cable to gas/water pipe line : 30 cm
d) Test before laying
Recommended voltage rating of meggar:-
i) 1.1 KV : 500 V
ii) 3.3 KV to 11 KV : 1000 V
iii) Above 11 KV : 2500 V
e) Tests after installation (High DC voltage test)
Rated voltage (KV) Test voltage (KV) 15 min.i) 0.65/1.1 3
ii) 1.9/3.3 6
iii) 3.3/3.3 8iv) 3.3/6.6 10
v) 6.6/6.6 & 6.6/11.3 15
---------------------------------------