General Specifications <<Contents>> <<Index>> GENERAL This document describes the general specifications of the FCN autonomous controller with NFCP100 CPU module. (FCN is an acronym for field control node.) Notation in this document: • The term “FCN” refers to the module consisting type autonomous controllers. • The term “FCN-100” refers to the autonomous controllers with NFCP100 CPU module. For Function, refer to FCN/FCJ Autonomous Controller Functions (FCN-100/FCJ), GS 34P02Q03-01E. FCN Autonomous Controller Hardware (FCN-100) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5616 URL: http://www.stardom.biz GS 34P02Q12-01E GS 34P02Q12-01E ©Copyright Nov. 2001(YK) 34th Edition Mar. 29, 2016(YK) FEATURES • High-performance, high-reliability modular controller • Memory with ECC • Low heat dissipation eliminates the need for a fan • A wealth of RAS features — CPU self-diagnostics, temperature monitoring, I/O diagnostics, and more • The CPU, power supply module, local bus (SB bus), and control network can all be duplexed, and all modules are hot-swappable. • Can function as link active schedulers (LASs) for low-speed voltage mode (H1) FOUNDATION Fieldbus segments, and link up FOUNDATION Fieldbus-enabled field devices. CONFIGURATION An FCN-100 consists of the following: • Base module • Power supply module • CPU module • SB bus repeat module (extending the SB bus, the local bus for FCNs, to connect an extension unit) • I/O modules There are two types of base module. - NFBU200 base module (long): Up to 2 extension units connectable for I/O expansion - NFBU050 base module (short): Compact and dedicated to one-unit-configuration Maximum I/O Module Configurations Base Module Unit Configuration Standard Duplexed (*1) NFBU200 base module (long) Control unit only Max. 8 modules Max. 6 modules With 1 extension unit Max. 16 modules Max. 12 modules With 2 extension unit Max. 25 modules Max. 20 modules NFBU050 base module (short) Control unit (*2) Max. 3 modules Not applicable (*3) *1: When CPU and SB bus repeat modules are duplexed *2: SB bus repeat modules cannot be mounted on NFBU050. *3: Neither power supply nor CPU modules can be duplexed on NFBU050.

Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

GeneralSpecifications

<<Contents>> <<Index>>

GENERALThis document describes the general specifications of the FCN autonomous controller with NFCP100 CPU module. (FCN is an acronym for field control node.)Notation in this document:•Theterm“FCN”referstothemoduleconsistingtypeautonomouscontrollers.

•Theterm“FCN-100”referstotheautonomouscontrollerswithNFCP100CPUmodule.

ForFunction,refertoFCN/FCJAutonomousControllerFunctions(FCN-100/FCJ),GS34P02Q03-01E.

FCNAutonomousControllerHardware(FCN-100)

YokogawaElectricCorporation2-9-32,Nakacho,Musashino-shi,Tokyo,180-8750JapanTel.:81-422-52-5616URL:http://www.stardom.biz

GS 34P02Q12-01E

GS34P02Q12-01E©CopyrightNov.2001(YK)

34thEditionMar.29,2016(YK)

FEATURES•High-performance,high-reliabilitymodularcontroller•MemorywithECC•Lowheatdissipationeliminatestheneedforafan•AwealthofRASfeatures—CPUself-diagnostics,temperaturemonitoring,I/Odiagnostics,andmore•TheCPU,powersupplymodule,localbus(SBbus),andcontrolnetworkcanallbeduplexed,andallmodulesarehot-swappable.

•Canfunctionaslinkactiveschedulers(LASs)forlow-speedvoltagemode(H1)FOUNDATIONFieldbussegments,andlinkupFOUNDATIONFieldbus-enabledfielddevices.

CONFIGURATIONAnFCN-100consistsofthefollowing:•Basemodule•Powersupplymodule•CPUmodule•SBbusrepeatmodule(extendingtheSBbus,thelocalbusforFCNs,toconnectanextensionunit)•I/Omodules

Therearetwotypesofbasemodule.-NFBU200basemodule(long):Upto2extensionunitsconnectableforI/Oexpansion-NFBU050basemodule(short):Compactanddedicatedtoone-unit-configuration

Maximum I/O Module Configurations

Base Module Unit Configuration Standard Duplexed (*1)

NFBU200basemodule(long)

Controlunitonly Max.8modules Max.6modules

With1extensionunit Max.16modules Max.12modules

With2extensionunit Max.25modules Max.20modules

NFBU050basemodule(short) Controlunit(*2) Max.3modules Notapplicable(*3)

*1: WhenCPUandSBbusrepeatmodulesareduplexed*2: SBbusrepeatmodulescannotbemountedonNFBU050.*3: NeitherpowersupplynorCPUmodulescanbeduplexedonNFBU050.

Page 2: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

2

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 34P02Q12-01E Jul.14,2009-00

l Examples of ConfigurationStandard control unit alone

F01E.ai

1SlotUnit:1 2 3 4 5 6 7 8 9 10

Ethernet

IOM

IOM

IOM

IOM

IOM

IOM

IOM

IOM

CP

U

PW

M

DM

Y

Control unit alone with duplexed CPU and power supply modules

F02E.ai

1SlotUnit:1 2 3 4 5 6 7 8 9 10

CP

U

CP

U

PW

M

PW

M

IOM

IOM

IOM

IOM

IOM

IOM

Ethernet

Abbreviation DescriptionPWM PowersupplymoduleCPU CPUmoduleIOM I/OmoduleNFSB SBbusrepeatmoduleDMY DummycoverforpowersupplyModuleSlot

Standard control unit + 2 extension units

F03E.ai

Ethernet

IOM

IOM

IOM

IOM

IOM

IOM

IOM

CP

U

PW

M

DM

Y

1SlotUnit:1 2 3 4 5 6 7 8 9 10

IOM

IOM

IOM

IOM

IOM

IOM

IOM

IOM

IOM

PW

M

DM

Y

1SlotUnit:2 2 3 4 5 6 7 8 9 10

IOM

IOM

IOM

IOM

IOM

IOM

IOM

IOM

IOM

PW

M

DM

Y

1SlotUnit:3 2 3 4 5 6 7 8 9 10

NFS

BN

FSB

NFS

B

Control unit with duplexed CPU modules, power supply modules, and SB bus + 2 extension units

Note:TheCPUmodule,powersupplymodule,andSBbuscanbemadeduplexindividually,whenrequired.

F04E.ai

IOM

IOM

IOM

IOM

IOM

IOM

IOM

IOM

PW

M

PW

M

NFS

B

NFS

B

NFS

B

NFS

B

1SlotUnit:2 2 3 4 5 6 7 8 9

IOM

IOM

IOM

IOM

IOM

IOM

IOM

IOM

PW

M

PW

M

1SlotUnit:3 2 3 4 5 6 7 8 9 10

1SlotUnit:1 2 3 4 5 6 7 8 9

CP

U

CP

U

PW

M

PW

M

IOM

IOM

IOM

IOM

10

10

Ethernet

NFS

B

NFS

B

Short control unit

F10E.ai

1SlotUnit:1 2 3 4 5

Ethernet

IOM

IOM

IOM

CP

U

PW

M

Page 3: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

3<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E

INSTALLATION REQUIREMENTSItem Specification

AmbienttemperatureOperation 0°to55°CTransportation/storage –40°to85°C(*1)

AmbienthumidityOperation 5to95%RH(nocondensation)Transportation/storage 5to95%RH(nocondensation)

Rateofchangeintemperature

Operation Within±10°C/hTransportation/storage Within±20°C/h

Dust 0.3mg/m3orlessProtectionclass IP20Resistancetocorrosivegases ANSI/ISAS71.04ClassG2(Standard)(ANSI/ISAS71.04ClassG3,option)Resistancetovibration 0.15mmP-P(5to58Hz),1G(58to150Hz)Resistancetoshock 15G,11ms(duringpower-off,forsinehalf-wavesinXYZ-directions)Altitude 2000morless

NoiseElectricfield 3V/morless(26MHzto1GHz)Magneticfield 30A/m(AC)orless,400A/m(DC)orlessElectrostaticdischarge 4kVorlesscontactdischarge,8kVorlessaerialdischarge

Grounding Applythegroundingsystemwhichisdefinedbytherulesandstandardsofthecountryortheregion.

Cooling Naturalaircooling

*1: Systemclockmayberesetifthetemperaturefallsbelow-10°C.

Aug.10,2015-00

Page 4: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

4

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 34P02Q12-01E

COMPLIANT STANDARDS Item Standards

Safetystandards(*1)(*8)(*15)

CSA CAN/CSA-C22.2No.61010-1

CEMarkingLowVoltageDirectiveEN61010-1(*12)EN61010-2-201(*12)EN61010-2-030

EACMarking CUTR004

EMCstandards

CEMarkingEMCDirective (*12)

EN55011ClassAGroup1(emission)(*13)EN61000-6-2(immunity)(*1)(*2)(*9)EN61000-3-2EN61000-3-3(*3)

RCM EN55011ClassAGroup1(*13)KCMarking KoreaElectromagneticConformityStandardEACMarking CUTR020

StandardsforHazardousLocationEquipment(*4)(*5)

FMNonincendive(*1)

ClassIDivision2,GroupsA,B,C,DT4Class3600:2011Class3611:2004Class3810:2005

ATEXType"n"(*6)(*7)(*12)

II3GExnAnCIICT4GcX(*10)(*14)II3GExnAIICT4GcX(*11)(*14)

EN60079-0:2009EN60079-0:2012EN60079-15:2010

CSANon-Incendive(*1)

ClassIDivision2,GroupsA,B,C,DT4CAN/CSA-C22.2No.0-M91CAN/CSA-C22.2No.0.4-04CAN/CSA-C22.2No.157-92C22.2No.213-M1987TN-078

*1: Fortherack-mountabledevices,DINrail-mountabledevices,andwall-mountabledevicestomeettheSafetyStandardsandEMCStandards,thedevicesmustbeinstalledinalockablemetalcabinet.ThecabinetmustconformtoIEC/EN/CSA61010-2-201orprovidedegreesofprotectionIP3XoraboveandIK09orabove.

*2: Forlightningsurgeimmunity,adevicesuchasalightningarresterneedstobeinstalledexternally.Somemodulecanselectapressureclampterminalblockwithsurgeabsorber.Fordetails,see“TerminalBlock”(GS34P02Q41-01E).

*3: Thespecifiedmagnitudeofthevoltagedropdeterminedbythecablewiringlengthneedsbemet.*4: RefertoTI34P02Q91-01EfortheproductsmeetingNI.*5: Formodulesconformingtoexplosion-proofstandards,refertothesection“I/OModule”andthetable“ListofFCN’s

ModulesandModulesConformingtoExplosionProtectionStandard”ofthisdocument.*6: WhenFCNisusedundertheATEXType“n”environment,theInstructionManual,IM34P02Q11-02E“ExplosionProtection

ofFCN/FCJProducts”isrequiredforsaferinstallationandwiring.*7: Tobecompliantwiththesestandards,theFCNhardwareneedstobeinstalledinalockablemetalcabinetofIP54orhigher

protectionrating.*8: ForensuringtheFCNhardwaretosatisfythesafetystandards,thededicatedbreakersinthepowersupplysidemustbe

installedandconformtothefollowingspecifications. •[CSA]CSAC22.2No.5orUL489 •[CEMarking]EN60947-1andEN60947-3*9: WhenusingtheNFLP121,mountone(A1193MN)ferritecoreontheNFLP121sideofthePROFIBUScabletomeetthe

EMCstandards.*10: AppliedforNFDR541andFCN. “Typeofprotection”ofFCNisincludingthewholemountedmodule.*11: AppliedforproductsexceptforNFDV541.*12: NFDR541iscompliantwiththestandardsonlywhenthevoltageof24VDCorlessisappliedtoitsoutputterminal.*13: AClassAhardwaredeviceisdesignedforuseintheindustrialenvironment.Pleaseusethisdeviceintheindustrial

environmentonly.*14: Symbol‘X’denotesthespecificconditionofuse.See“ExplosionProtectionofFCN/FCJProducts”(IM34P02Q11-02E)for

detail.*15: Tobecompliantwiththesestandards,theFCN’scablewhichisdrawnoutfromthemetal,needstobeusedtheVW-1class

ormoreofflame-retardantcable.

InrelationtotheCEMarking,themanufacturerandtheauthorisedrepresentativefortheProductintheEEAareindicatedbelow:•Manufacturer: YokogawaElectricCorporation(2-9-32Nakacho,Musashino-shi,Tokyo180-8750,Japan)•AuthorisedrepresentativeintheEEA: YokogawaEuropeB.V.(Euroweg2,3825HDAmersfoort,TheNetherlands)

Mar.29,2016-00

Page 5: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

5<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E

BASE MODULE AbasemoduleisachassisonwhichvariousfunctionmodulessuchasCPU,powersupply,SBbusrepeat,andI/Omodulesaremountedtoconfigureacontrolunitorextensionunit.

l Features

Model Usage “Number of Mountable I/O Modules”

“Number of Mountable Power Supply Modules” SB Bus

NFBU200ControlUnit 8(*1)

1or2(whenduplexed) DuplexExtensionUnit 9(*2)

NFBU050 ControlUnit 3(*3) 1 Single

*1: TwofromthetenslotsareexclusiveforatleastoneCPUmoduleinthecontrolunit.*2: OnefromthetenslotsisexclusiveforatleastoneSBbusrepeatmoduleintheextensionunit.*3: TwofromthefiveslotsareexclusiveforoneCPUmodule.NoSBbusrepeatmodulescanbemounted.

l Model and Suffix CodesBase Module (long)

Description Model NFBU200 Basemodule(long)

Suffix Codes

-S Standardtype 0 19-inchrack-mounted 1 DINrail-mounted 5 Basictypewithnoexplosionprotection 6 WithISAStandardG3optionandnoexplosionprotection E Basictypewithexplosionprotection F WithISAStandardG3optionandexplosionprotection

Base Module (short)

DescriptionModel NFBU050 Basemodule(short)

Suffix Codes

-S Standardtype 1 DINrail-mounted 5 Basictypewithnoexplosionprotection 6 WithISAStandardG3optionandnoexplosionprotection E Basictypewithexplosionprotection F WithISAStandardG3optionandexplosionprotection

Optional Accessories

Description

Model NFDCV01 DummycoverforI/OmoduleslotNFDCV02 Dummycoverforpowersupplymoduleslot

l Specifications

Item SpecificationModel NFBU200-S0 NFBU200-S1 NFBU050-S1Weight 1.9kg 1.0kg 0.58kgDimensions(WxHxD) 482.6132.540.5mm 44013142.3mm 28313124.2mmMounting 19-inchrack-mounted DINrail-mountedMaximumpowerconsumption

5V Self-consumption 0.4A(max) 0.025A24V Self-consumption 0

Mar.10,2015-00

Page 6: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

6

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 34P02Q12-01E

l Dimensions19-inch rack-mounted Model (NFBU200)

44021.3

8.45 465.7482.6

40.5

Unit: mm

17.6

132.

5

57.1

37.7

18.4

F05E.ai

DIN rail-mounted Model (NFBU200)401.5

444

35

Unit: mm

131

16

7

F06.ai

440.2

18181.25

1.9

DIN rail-mounted Model (NFBU050)

16.1273

243.6

24.220.6

283

110

10.5

131

66.5

F11E.ai

Unit: mm

Mar.10,2015-00

Page 7: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

7<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E

POWER SUPPLY MODULEMountedonabasemodule,apowersupplymodulesuppliessteadypowertoothermodules.Twopowersupplymodulescanbeinstalledonabasemoduleforredundancy.Thispowersupplymoduleisequippedwithinputterminalsfora24VDCpowersupplyinadditiontothemainpowerinput.The24VDCpowerinputfromtheseterminalsarereferredtoasanalogfieldpowersupplyandfedtoanalogI/Omodulestodrivetheirfieldinterfacecircuitsandsupplypowertotheconnectedfielddevicesthroughthebasemodule.However,whena24VDCpowersupplyisneededfordigitaloutputs,itmustbesuppliedtoindividualterminalsofthecorrespondingI/Omodules.(Fordetails,seetherespectivespecificationsforI/Omodules.)

l Model and Suffix Codes

Description

Model NFPW441 Powersupplymodule(100-120VACinput)

Suffix Codes

-5 Standardtypewithnoexplosionprotection

-E Standardtypewithexplosionprotection

0 Basictype 1 WithISAStandardG3option

Description

Model NFPW442 Powersupplymodule(220-240VACinput)

Suffix Codes

-5 Standardtypewithnoexplosionprotection

0 Basictype 1 WithISAStandardG3option

Description

Model NFPW444 Powersupplymodule(24VDCinput)

Suffix Codes

-5 Standardtypewithnoexplosionprotection

-E Standardtypewithexplosionprotection

0 Basictype 1 WithISAStandardG3option

l Pin AssignmentPower supply terminals (Models NFPW441 and 442)

Pin No. Name Signal

1 FLD24VDC+ 24Vanalogfieldpowersupply(+)(*1)

2 FLD24VDC– 24Vanalogfieldpowersupply(-)(*1)

3 G Groundoflinefilter4 L

Powerinput5 N

Power supply terminals (Model NFPW444)

Pin No. Name Signal

1 FLD24VDC+ 24Vanalogfieldpowersupply(+)(*1)

2 FLD24VDC– 24Vanalogfieldpowersupply(-)(*1)

3 G Groundoflinefilter4 +

Powerinput5 –

*1: WhenanalogI/OmodulessuchasNFAI141(with2-wiretransmitter),NFAI135,NFAI841,NFAB841,NFAI835,NFAF135,andNFAP135areinstalled,ananalogfieldpowersupplyisneeded.

Checking terminals

Pin No. Name Signal 1 +5V-CHK Checkingof5Vsystempower

2 +24V-CHK Checkingof24Vfieldpowersupply

3 GND Signalgrounding

l LEDs

LED Indicator Color Description

SYS-POWER Green Lightswhenthe5Vsystempoweroutputison.

FLD-POWER Green Lightswhenthe24Vfieldpowersupplyison.

Mar.10,2015-00

Page 8: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

8

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 34P02Q12-01E

l Dimensions

F07E.ai

49.7146.5133

130

13.5

Unit: mm

l Specifications

Item SpecificationModel NFPW441 NFPW442 NFPW444

Powersupplyinput

Ratedinputvoltage 100to120VAC 220to240VAC 24VDCInputvoltagerange 80to132VAC(rms) 170to264VAC(rms) 21.6to31.2VDCInputfrequency 47to66Hz(Rating:50/60Hz)Inputcurrent Max.1.4A Max.0.7A Max.3.3AFuserating 3.15A 3.15A 6.3ARushcurrent Max.80Afor5msorless Max.90Afor5msorless Max.20ALeakcurrent Max.1mA —Withstandingvoltage 3000VACfor1minute 500VACfor1minuteInsulationresistance 50MΩat500VDCInsensitivemomentarypower-failuretime 10ms(80%) 2ms(90%)

Output

Ratedoutputvoltage +5.1VDCRatedoutputcurrent 0to7.8APeakcurrent 11.8ATotaloutput 40W(60Wpeak)Startuptimeafterpower-on

Max.300msMax.100ms(afterapowerfailureof200mslongwiththeratedinput)

Overvoltageprotection Max.7VOvercurrentprotection Min.105%(shutdownafter4to14secondslongovercurrent)

Analogfieldpowersupply

InputRatedinputvoltage 24VDC±10%Inputcurrent Max.4AFuserating 6.3A

OutputRatedoutputvoltage Inputvoltageminusmatching-diodedropRatedoutputcurrent 4AOvervoltageprotection 35V

Duplexconfiguration Possible(wheninstalledonbasemoduleNFBU200)Weight 0.6kgDimensions(WxHxD) 49.7x130x146.5mm

Mar.10,2015-00

Page 9: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

9<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E

CPU MODULEOneCPUmoduleismountedineachcontrolunit,ortwoforaduplexedCPUconfiguration.TheCPUmodulerunsareal-timeoperatingsystem,supportsprogramminglanguagescompliantwiththeIEC61131-3internationalstandard,andservesasaJavavirtualmachine.

l Model and Suffix Codes

DescriptionModel NFCP100 CPUmoduleforFCN

Suffix Codes

-S Standardtype 0 Always0

5 Basictypewithnoexplosionprotection

6 WithISAStandardG3optionandnoexplosionprotection

E Basictypewithexplosionprotection

F WithISAStandardG3optionandexplosionprotection

l Specifications

Item SpecificationModel NFCP100-S0Processor MMX-Pentium166MHz

MemoryMain 128MBwithECCStaticRAM 1MBwithECC,backedupbybattery

Systemcard 1slot

SerialPort(*2) 1RS-232-Cport:D-sub9pins,male(*1)

Communicationmethod Fullduplex

Synchronisation Asynchronous

Baudrate 0.3,1.2,2.4,4.8,9.6,14.4,19.2,28.8,38.4,57.6,or115.2kbps

Networkinterface2Ethernetports:100/10Mbps,100BASE-TXor10BASE-T,RJ45modularjacks

I/Ointerface SBbus(duplex)

RASfeatures Watchdogtimer,temperaturemonitor,etc.

Battery 2700mAHlithiumbattery

Display 3LEDsforCPUstatusindication,2LEDsforLANstatusindication

Switches Reset,shutdown

Powersupply

Supplyvoltage 5VDC±5%

Currentconsumption Max.1800mA

Duplexconfiguration PossibleWeight 0.7kg

Size

Dimensions(WxHxD) 65.8x132x145.7mm

Occupyingslots 2

*1: Connectorsarefastenedusinginchscrewthreads(No.4-40UNC).

*2: AserialportcannotbeusedwhenCPUmodulesareconfiguredinredundancy.

l Pin Assignments of CPU Module’s Serial Port

Table Connector Pin Assignment (D-sub 9-pin, male)

Pin No Signal name Function

1 CD Datachannelreceivingcarrierdetection

2 RD Receivingdata

3 SD Transmissiondata

4 ER Dataterminalready

5 SG Signalground

6 DR Datasetready

7 RS Transmissionrequest

8 CS Transmissionenabled

9 — Not used

F12E.ai

12345

6789

Figure Pin Position (Front View)

l LEDs

Status Indicators

LED Indicator Color DescriptionHRDY Green Lightswhenthehardwareisnormal.RDY Green Lightswhenthesystemisnormal.

CTRL Green Lightswhenthecontrolactionsarecarriedoutnormally.

LAN status indicators (near RJ45 modular jacks)

LED Indicator Color Description

LINK Green Lightswhentheconnectiontoahubisnormal.

ACT Orange Lightswhenthetransmission/receptionison.

Mar.10,2015-00

Page 10: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

10

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 34P02Q12-01E

l Dimensions

NFCP100-S00

RESET SYSTEMMEDIA

SHUTDOWN

NETWORKSERIAL

S1

CPU MODULE

F08E.ai

MODELSUFFIXNO.

STYLE

145.7129 13.5(3.2)65.8

Unit: mm

132

130

(2)

N200

NFCP100–OO S1011E07002B

MAC ADDRESS:00006482C001 00006482C002

Made in Japan

SB BUS REPEAT MODULEUsedtoconnectacontrolunittoI/Oextensionunits.ToduplextheSBbus,installtwoSBbusrepeatmodulesineachunit.EachSBbusrepeatmoduleisconnectedtoanotherviaadedicatedT-jointandcable.

l Model and Suffix Codes

Description Model NFSB100 SBbusrepeatmoduleforFCN

Suffix Codes

-S Standardmodel 5 Withnoexplosionprotection E Withexplosionprotection 0 Basictype 1 WithISAStandardG3option

Option Codes

/SBT01 WithanSBbusT-joint

/SBT02 WithanSBbusT-jointwithbuilt-interminator

Note: Whenconnectingacontrolunitandextensionunits,installatbothendsaT-jointwithbuilt-interminatoroneachSBbusrepeatmodule.

Description Models NFSBT01 SBbusT-joint

NFSBT02 SBbusT-jointwithbuilt-interminator

Description Model NFCB301 SBbuscable

Suffix Codes

-C030 Cablelength30cm-C100 Cablelength1m-C200 Cablelength2m-C400 Cablelength4m-C800 Cablelength8m

Mar.10,2015-00

l Specifications

Item Specification Model NFSB100Transmissionmethod SerialcommunicationBaudrate 128MbpsTransmissiondistance Max.8mperline

Extensionunits Max.2units (3unitsincludingacontrolunit)

Duplexconfiguration Possible

Powersupply

Supplyvoltage 5VDC±5%

Currentdissipation Max.500mA

Weight 0.2kg

Size

Dimensions(WxHxD) 32.8x130x142.5mm

Occupyingslots 1

Slotstobeinstalledin SlotNo.10(forsingleSBbus)SlotNos.9and10(forduplexedSBbus)

l LEDs

LED Indicator Color Description STATUS Green Lightswhenthehardwareisnormal.SND Green Lightswhenthetransmissionison.RCV Green Lightswhenthereceptionison.

l Dimensions

F09E.ai

129112 (WITHOUT T-CONN.)

(13.5)142.5

32.8

130

Unit: mm

Page 11: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

11<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E

I/O MODULEAnautonomouscontrollerFCNsupportsversatileI/Omodules.Fordetails,refertothefollowinggeneralspecifications:•GS34P02Q31-01E AnalogI/OModules•GS34P02Q35-01E DigitalI/OModules•GS34P02Q36-01E SerialCommunicationModule•GS34P02Q55-01E FoundationFieldbusCommunicationModule•GS34P02Q57-01E PROFIBUS-DPCommunicationModule•GS34P02Q58-01E CANopenCommunicationModule

l List of FCN’s Modules and Modules Conforming to Explosion Protection Standards

Table List of FCN’s Modules and Modules Conforming to Explosion Protection Standards (1/2)

Type Model Function

Explosion protectionFM NI (Non-incen-dive)

ATEX Type “n”

CSA NI (Non-Incen-dive)

BasemoduleNFBU200 Basemodule(long) X X XNFBU050 Basemodule(short) X X X

Powersupplymodule

NFPW441 Powersupplymodule(100-120VACinput) X – XNFPW442 Powersupplymodule(220-240VACinput) – – –NFPW444 Powersupplymodule(24VDCinput) X X X

CPUmodule NFCP100 CPUmoduleforFCN X X XSBbusrepeatmodule NFSB100 SBbusrepeatmoduleforFCN X X X

AnalogI/OModules(*1)

NFAI141 AnalogInputModule(4to20mA,16-channel,Non-Isolated) XX(*2) X XX(*2)

NFAV141 AnalogInputModule(1to5V:differentialinput,16-channel,Non-Isolated) X X X

NFAV142 AnalogInputModule(-10to+10V,16-channel,Non-Isolated) X X X

NFAI841 AnalogI/OModule(4to20mAinput,4to20mAoutput,8-channelinput/8-channeloutput,Non-Isolated) XX(*2) X XX(*2)

NFAB841 AnalogI/OModule(1to5Vinput:differentialinput,4to20mAoutput,8-channelinput/8-channeloutput,Non-Isolated) X X X

NFAV542 AnalogOutputModule(-10to+10V,16-channel,Non-Isolated) X X XNFAI143 AnalogInputModule(4to20mA,16-channel,Isolated) X X XNFAI543 AnalogOutputModule(4to20mA,16-channel,Isolated) X X XNFAV144 AnalogInputModule(-10to+10V,16-channel,Isolated) X X XNFAV544 AnalogOutputModule(-10to+10V,16-channel,Isolated) X X XNFAT141 TC/mVInputModule(16-channel,Isolated) X X XNFAR181 RTDInputModule(12-channel,Isolated) X X XNFAI135 AnalogInputModule(4to20mA,8-channel,Isolatedchannels) X X X

NFAI835 AnalogI/OModule(4to20mA,4-channelinput/4-channeloutput,Isolatedchannels) X X X

NFAP135 PulseInputModule(8-channel,Pulsecount,0to10kHz,Isolatedchannels) X X X

NFAF135 FrequencyInputModule(8-channel,0.1Hzto10kHz,Isolatedchannels) X X X

DigitalI/OModules(*1)

NFDV151 DigitalInputModule(32-channel,24VDC,Isolated) X X X

NFDV157 DigitalInputModule(32-channel,24VDC,PressureClampTerminalsupportonly,Isolated) X X X

NFDV161 DigitalInputModule(64-channel,24VDC) – – –NFDV141 DigitalInputModule(16-channel,100V-120VAC,Isolated) X – XNFDV142 DigitalInputModule(16-channel,200-240VAC) – – –

X: ConformingXX: ConformingconditionallyN.A.: Notapplicable*1: Tousemodulesashazardouslocationequipment(non-incendive),usethespecifiedpressure-clampterminalblocksorMIL

connectorcables(KMS40,KMS50)/MILconnectorterminalblocks(TAS40andTAS50).*2: I/Omoduleswithsuffixcode“withHARTcommunication”donotconformtotheexplosion-proofstandards.

Mar.10,2015-00

Page 12: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

12

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 34P02Q12-01E

Table List of FCN’s Modules and Modules Conforming to Explosion Protection Standards (2/2)

Type Model Function

Explosion protectionFM NI (Non-incen-dive)

ATEX Type “n”

CSA NI (Non-Incen-dive)

DigitalI/OModules(*1)

NFDV532 PulseWidthOutputModule(4-channel:UpPulse/DownPulse,24VDC,Isolated) – – –

NFDV551 DigitalOutputModule(32-channel,24VDC,Isolated) X X X

NFDV557 DigitalOutputModule(32-channel,24VDC,PressureClampTerminalsupportonly,Isolated) X X X

NFDV561 DigitalOutputModule(64-channel,24VDC) – – –

NFDR541 RelayOutputModule (16-channel,24to110VDC/100to240VAC,Isolated) XX(*3) XX(*4) XX(*3)

TurbomachineryI/OModules(*5)

NFGS813 ServoModule – – –NFGP813 HighSpeedProtectionModule – – –

CommunicationModules

NFLC121 CANopenCommunicationModule(1-port,10kbpsto1Mbps) – – –NFLF111 Foundationfieldbuscommunicationmodule(4-port) X X X

NFLP121 PROFIBUS-DPCommunicationModule (1-port,9.6kbpsto12Mbps) – – –

NFLR111 RS-232-CCommunicationModule (2-port,300bpsto115.2kbps) X X X

NFLR121 RS-422/RS-485CommunicationModule (2-port,300bpsto115.2kbps) X X X

PressureClampTerminalBlock

NFTA4S PressureClampTerminalBlockforAnalog(16-channel) X X X

NFTT4S PressureClampTerminalBlockforThermocouple/mV (16-channel) X X X

NFTR8S PressureClampTerminalBlockforRTD(12-channel) X X XNFTB5S PressureClampTerminalBlockforDigitalInput(32-channel) X X XNFTD5S PressureClampTerminalBlockforDigitalOutput(32-channel) X X X

NFTI3SPressureClampTerminalBlockforIsolatedAnalogModuleandPulseModule(forNFAI135,NFAP135,NFAF135:8-channel,NFAI835:4-channelinput,4-channeloutput)

X X X

NFTC4S PressureClampTerminalBlockforDigital(16-channel,withdedicatedconnector,withoutsurgeabsorber) X X X

NFTC5S PressureClampTerminalBlockforDigital(32-channel,withdedicatedconnector) X X X

NFTF9S PressureClampTerminalBlockforFoundationFieldbus X X X

TerminalBlockTAS40 MILConnectorTerminalBlock(40PolePlugTypes,M3.5) X X XTAS50 MILConnectorTerminalBlock(50PolePlugTypes,M3.5) X X X

CableNFCB301 SBBusCable X X XKMS40 MILConnectorCable(40PolePlugTypes) X X XKMS50 MILConnectorCable(50PolePlugTypes) X X X

SBBusT-jointNFSBT01 SBBusT-joint X X XNFSBT02 SBBusT-jointwithBuilt-inTerminator X X X

DummyCoverNFDCV01 DummyCoverforI/OModuleSlot N.A. N.A. N.A.NFDCV02 DummyCoverforPowersupplyModuleSlot N.A. N.A. N.A.NFCCC01 MILCableConnectorCover N.A. N.A. N.A.

X: ConformingXX: ConformingconditionallyN.A.: Notapplicable*1: Tousemodulesashazardouslocationequipment(non-incendive),usethespecifiedpressure-clampterminalblocksorMIL

connectorcables(KMS40,KMS50)/MILconnectorterminalblocks(TAS40andTAS50).*2: I/Omoduleswithsuffixcode“withHARTcommunication”donotconformtotheexplosion-proofstandards.*3: Therelayoutputmodule(NFDR541)doesnotconformtotheexplosion-proofstandardswhenitisusedinbetween100to

240VAC..*4: Therelayoutputmodule(NFDR541)iscompliantwiththestandardsonlywhenthevoltageof24VDCorlessisappliedto

itsoutputterminal.*5: ForTurbomachineryI/OModules,refertoGS34P02Q04-01ETurbomachineryControllerOverview.

Aug.10,2015-00

Page 13: Geneal 6SHFL¿FDWLRQV FCN Autonomous Controller …*7: To be compliantwith these standards,the FCN hardware needs to be installedin a lockable metal cabinet of IP54 or higher protectionrating

13<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E

CABLE SPECIFICATIONSThefollowingdescribesthespecificationsrequiredforthepowerandgroundingcablesused.Forfieldsignalwiringcables,see“FieldConnections”(GS34P02Q30-01E).

l Applicable CablesInsulatedcablesforindustrialequipmentsuchas:•600Vpolyvinylchlorideinsulatedwires(IV);JISC3307

•Polyvinylchlorideinsulatedwiresforelectricalapparatus(KIV);JISC3316

•600Vgradeheat-resistantpolyvinylchlorideinsulatedwires(HIV);JISC3317

•HeatproofvinylinsulatedwiresVW-1(UL1015/UL1007)

•Controlcables(vinylinsulatedvinylsheathcable)(CVV);JISC3401

l Recommended SizesPowercable:AWG20to14(0.5to2mm2)withring

tongueterminalGroundingcable:AWG14to13(2to2.6mm2)with

ringtongueterminal

l Recommended Solderless TerminalsPowercable:InsulatedM4solderlessterminals,8.5

mmwideorlessGroundingcable:InsulatedM4solderlessterminal,

8.5mmwideorless

FollowthespecificationsrequiredbytheM4solderlessterminalsused.

RESTRICTIONS AND PRECAUTIONS ON INSTALLATION

SeeInstallationGuidefor“STARDOMFCN/FCJInstallationGuide”(TI34P02Q91-01E).

l Limitations of Installation for NFAT141 (the combination of Thermocouple input and Pressure clamp terminal)

Tokeepthereferencejunctioncompensationaccuracy(GS34P02Q31-01E),makesuretomeetthefollowingconditions.Thepressureclampterminalshouldnotbeaffectedbyradiatedheat.•Donotinstallaheat-radiatingunitbeneaththeNFAT141installedunit.

•DonotinstallNFAT141inaplacewhereairflowimpingesdirectly.

•DonotinstallNFAT141nexttotheCPUmodules(NFCP100),powersupplymodules(NFPW44x).

•TheinstallablemodulesnexttotheNFAT141areasfollows.WheninstallingotherthanfollowingI/Omodules,makeanemptyslot(oneormore)ineachside.Installablemodules:NFAT141,NFAR181,NFAV141,

NFAV142,NFAV144,NFAV542

Mar.29,2016-00Subjecttochangewithoutnotice.

l Limitations of Installation for Communication Modules

•AtotalofuptoeightNFLR111/NFLR121canbeinstalledforeachFCN-100.

•AtotalofuptoeightNFLF111/NFLC121/NFLP121canbeinstalledforeachFCN-100.

l Limitations of Installation for I/O Modules WhenyouinstallthefollowingI/Omodules,ensurethattherequiredpowervolumedoesnotexceedtheratedpoweroutputofthepowersupplymodule.FortheamountofpowersupplythateachI/Omodulerequires(5VDCand24VDC),refertotheapplicablegeneralspecifications.

l About Use of NFBU050•NFBU050isdedicatedtocontrolunit.Itcannotbeusedasextensionunit.

•SBbusrepeatmodulecannotbemountedonNFBU050.

l Precaution on NFPW426 (Power Supply Module for FCN-RTU)

NFPW426(PowersupplymoduleforFCN-RTU)cannotbeusedforFCN-100.OnlyNFPW441,NFPW442orNFPW444canbeusedforFCN-100.

For Type “n”WhenFCN-100isusedundertheType“n”environment,theInstructionManual,“ExplosionProtectionofFCN/FCJProducts”(IM34P02Q11-02E)belowisrequiredforsaferinstallationandwiring.

Document No. Name

IM34P02Q11-02E ExplosionProtectionofFCN/FCJProducts

ORDERING INFORMATIONSpecifythemodelandsuffixcodes.Forselectingtherightproductsforexplosionprotection,pleasereferto“STARDOMFCN/FCJInstallationGuide”(TI34P02Q91-01E)withoutfail.

TRADEMARKS•AllbrandorproductnamesofYokogawaElectricCorporationinthisbulletinaretrademarksorregisteredtrademarksofYokogawaElectricCorporation.

•EthernetisaregisteredtrademarkofXeroxCorporation,theUnitedStates.

•PentiumisaregisteredtrademarkofIntelCorporation.

•Othercompanyandproductnamesappearinginthisdocumentaretrademarksorregisteredtrademarksoftheirrespectiveholders.